123456789101112131415161718192021222324252627282930313233343536373839404142434445464748495051525354555657585960616263646566676869707172737475767778798081828384858687888990919293949596979899100101102103104105106107108109110111112113114115116117118119120121122123124125126127128129130131132133134135136137138139140141142143144145146147148149150151152153154155156157158159160161162163164165166167168169170171172173174175176177178179180181182183184185186187188189190191192193194195196197198199200201202203204205206207208209210211212213214215216217218219220221222223 |
- #Rs232协议命令
- [CMD]
- #;命令总数
- cmd-count=35
- cmd-1=制冷温度设定点
- cmd-2=加热温度设定点
- cmd-3=温度下限
- cmd-4=温度上限
- cmd-5=湿度设定值
- cmd-6=湿度下限
- cmd-7=湿度上限
- cmd-8=蜂鸣器状态
- cmd-9=EEPROM 状态
- cmd-10=压缩机1高压
- cmd-11=压缩机2高压
- cmd-12=压缩机1低压
- cmd-13=压缩机2低压
- cmd-14=气流故障
- cmd-15=滤网堵塞
- cmd-16=加热器故障
- cmd-17=风机过载
- cmd-18=压缩机过载
- cmd-19=加湿器故障
- cmd-20=总报警
- cmd-21=烟感报警
- cmd-22=水流故障报警
- cmd-23=压缩机1
- cmd-24=压缩机2
- cmd-25=加热1
- cmd-26=加热2
- cmd-27=风机
- cmd-28=去湿器
- cmd-29=空调状态
- cmd-30=温度
- cmd-31=湿度
- cmd-32=低环境温度报警
- cmd-33=高环境温度报警
- cmd-34=低环境湿度报警
- cmd-35=高环境湿度报警
- ;制冷温度设定点
- [cmd-1]
- type=A
- index=11
- ;加热温度设定点
- [cmd-2]
- type=A
- index=12
- ;温度下限
- [cmd-3]
- type=A
- index=13
- ;温度上限
- [cmd-4]
- type=A
- index=14
- ;湿度设定值
- [cmd-5]
- type=A
- index=18
- ;湿度下限
- [cmd-6]
- type=A
- index=19
- ;湿度上限
- [cmd-7]
- type=A
- index=20
- ;蜂鸣器状态
- [cmd-8]
- type=D
- index=2
- ;EEPROM 状态
- [cmd-9]
- type=D
- index=3
- ;压缩机1高压
- [cmd-10]
- type=D
- index=9
- ;压缩机2高压
- [cmd-11]
- type=D
- index=10
- ;压缩机1低压
- [cmd-12]
- type=D
- index=11
- ;压缩机2低压
- [cmd-13]
- type=D
- index=12
- ;气流故障
- [cmd-14]
- type=D
- index=13
- ;滤网堵塞
- [cmd-15]
- type=D
- index=14
- ;加热器故障
- [cmd-16]
- type=D
- index=15
- ;风机过载
- [cmd-17]
- type=D
- index=16
- ;压缩机过载
- [cmd-18]
- type=D
- index=17
- ;加湿器故障
- [cmd-19]
- type=D
- index=19
- ;总报警
- [cmd-20]
- type=D
- index=1
- ;烟感报警
- [cmd-21]
- type=D
- index=31
- ;水流故障报警
- [cmd-22]
- type=D
- index=32
- ;压缩机1
- [cmd-23]
- type=D
- index=34
- ;压缩机2
- [cmd-24]
- type=D
- index=35
- ;加热1
- [cmd-25]
- type=D
- index=36
- ;加热2
- [cmd-26]
- type=D
- index=37
- ;风机
- [cmd-27]
- type=D
- index=38
- ;去湿器
- [cmd-28]
- type=D
- index=39
- ;空调状态
- [cmd-29]
- type=D
- index=49
- ;温度
- [cmd-30]
- type=A
- index=2
- ;湿度
- [cmd-31]
- type=A
- index=1
- ;低环境温度报警
- [cmd-32]
- type=D
- index=20
- ;高环境温度报警
- [cmd-33]
- type=D
- index=21
- ;低环境湿度报警
- [cmd-34]
- type=D
- index=22
- ;高环境湿度报警
- [cmd-35]
- type=D
- index=23
- #Rs232协议命令类型
- [TYPE]
- #类型总数
- type-count=1
- #十六进制,CAREL3.0S代表CAREL3.0S协议
- type-1=CAREL3.0S
|