| 12345678910111213141516171819202122232425262728293031323334353637383940414243444546474849505152535455565758596061626364656667686970717273747576777879808182838485868788899091929394959697989910010110210310410510610710810911011111211311411511611711811912012112212312412512612712812913013113213313413513613713813914014114214314414514614714814915015115215315415515615715815916016116216316416516616716816917017117217317417517617717817918018118218318418518618718818919019119219319419519619719819920020120220320420520620720820921021121221321421521621721821922022122222322422522622722822923023123223323423523623723823924024124224324424524624724824925025125225325425525625725825926026126226326426526626726826927027127227327427527627727827928028128228328428528628728828929029129229329429529629729829930030130230330430530630730830931031131231331431531631731831932032132232332432532632732832933033133233333433533633733833934034134234334434534634734834935035135235335435535635735835936036136236336436536636736836937037137237337437537637737837938038138238338438538638738838939039139239339439539639739839940040140240340440540640740840941041141241341441541641741841942042142242342442542642742842943043143243343443543643743843944044144244344444544644744844945045145245345445545645745845946046146246346446546646746846947047147247347447547647747847948048148248348448548648748848949049149249349449549649749849950050150250350450550650750850951051151251351451551651751851952052152252352452552652752852953053153253353453553653753853954054154254354454554654754854955055155255355455555655755855956056156256356456556656756856957057157257357457557657757857958058158258358458558658758858959059159259359459559659759859960060160260360460560660760860961061161261361461561661761861962062162262362462562662762862963063163263363463563663763863964064164264364464564664764864965065165265365465565665765865966066166266366466566666766866967067167267367467567667767867968068168268368468568668768868969069169269369469569669769869970070170270370470570670770870971071171271371471571671771871972072172272372472572672772872973073173273373473573673773873974074174274374474574674774874975075175275375475575675775875976076176276376476576676776876977077177277377477577677777877978078178278378478578678778878979079179279379479579679779879980080180280380480580680780880981081181281381481581681781881982082182282382482582682782882983083183283383483583683783883984084184284384484584684784884985085185285385485585685785885986086186286386486586686786886987087187287387487587687787887988088188288388488588688788888989089189289389489589689789889990090190290390490590690790890991091191291391491591691791891992092192292392492592692792892993093193293393493593693793893994094194294394494594694794894995095195295395495595695795895996096196296396496596696796896997097197297397497597697797897998098198298398498598698798898999099199299399499599699799899910001001100210031004100510061007100810091010101110121013101410151016101710181019102010211022102310241025102610271028102910301031103210331034103510361037103810391040104110421043104410451046104710481049105010511052105310541055105610571058105910601061106210631064106510661067106810691070107110721073107410751076107710781079108010811082108310841085108610871088108910901091109210931094109510961097109810991100110111021103110411051106110711081109111011111112111311141115111611171118111911201121112211231124112511261127112811291130113111321133113411351136113711381139114011411142114311441145114611471148114911501151115211531154115511561157115811591160116111621163116411651166116711681169117011711172117311741175117611771178117911801181118211831184118511861187118811891190119111921193119411951196119711981199120012011202120312041205120612071208120912101211121212131214121512161217121812191220122112221223122412251226122712281229123012311232123312341235123612371238123912401241124212431244124512461247124812491250125112521253125412551256125712581259126012611262126312641265126612671268126912701271127212731274127512761277127812791280128112821283128412851286128712881289129012911292129312941295129612971298129913001301130213031304130513061307130813091310131113121313131413151316131713181319132013211322132313241325132613271328132913301331133213331334133513361337133813391340134113421343134413451346134713481349135013511352135313541355135613571358135913601361136213631364136513661367136813691370137113721373137413751376137713781379138013811382138313841385138613871388138913901391139213931394139513961397139813991400140114021403140414051406140714081409141014111412141314141415141614171418141914201421142214231424142514261427142814291430143114321433143414351436143714381439144014411442144314441445144614471448144914501451145214531454145514561457145814591460146114621463146414651466146714681469147014711472147314741475147614771478147914801481148214831484148514861487148814891490149114921493149414951496149714981499150015011502150315041505150615071508150915101511151215131514151515161517151815191520152115221523152415251526152715281529153015311532153315341535153615371538153915401541154215431544154515461547154815491550155115521553155415551556155715581559156015611562156315641565156615671568156915701571157215731574157515761577157815791580158115821583158415851586158715881589159015911592159315941595159615971598159916001601160216031604160516061607160816091610161116121613161416151616161716181619162016211622162316241625162616271628162916301631163216331634163516361637163816391640164116421643164416451646164716481649165016511652165316541655165616571658165916601661166216631664166516661667166816691670167116721673167416751676167716781679168016811682168316841685168616871688168916901691169216931694169516961697169816991700170117021703170417051706170717081709171017111712171317141715171617171718171917201721172217231724172517261727172817291730173117321733173417351736173717381739174017411742174317441745174617471748174917501751175217531754175517561757175817591760176117621763176417651766176717681769177017711772177317741775177617771778177917801781178217831784178517861787178817891790179117921793179417951796179717981799180018011802180318041805180618071808180918101811181218131814181518161817181818191820182118221823182418251826182718281829183018311832183318341835183618371838183918401841184218431844184518461847184818491850185118521853185418551856185718581859186018611862186318641865186618671868186918701871187218731874187518761877187818791880188118821883188418851886188718881889189018911892189318941895189618971898189919001901190219031904190519061907190819091910191119121913191419151916191719181919192019211922192319241925192619271928192919301931193219331934193519361937193819391940194119421943194419451946194719481949195019511952195319541955195619571958195919601961196219631964196519661967196819691970197119721973197419751976197719781979198019811982198319841985198619871988198919901991199219931994199519961997199819992000200120022003200420052006200720082009201020112012201320142015201620172018201920202021202220232024202520262027202820292030203120322033203420352036203720382039204020412042204320442045204620472048204920502051205220532054205520562057205820592060206120622063206420652066206720682069207020712072207320742075207620772078207920802081208220832084208520862087208820892090209120922093209420952096209720982099210021012102210321042105210621072108210921102111211221132114211521162117211821192120212121222123212421252126212721282129213021312132213321342135213621372138213921402141214221432144214521462147214821492150215121522153215421552156215721582159216021612162216321642165216621672168216921702171217221732174217521762177217821792180218121822183218421852186218721882189219021912192219321942195219621972198219922002201220222032204220522062207220822092210221122122213221422152216221722182219222022212222222322242225222622272228222922302231223222332234223522362237223822392240224122422243224422452246224722482249225022512252225322542255225622572258225922602261226222632264226522662267226822692270227122722273227422752276227722782279228022812282228322842285228622872288228922902291229222932294229522962297229822992300230123022303230423052306230723082309231023112312231323142315231623172318231923202321232223232324232523262327232823292330233123322333233423352336233723382339234023412342234323442345234623472348234923502351235223532354235523562357235823592360236123622363236423652366236723682369237023712372237323742375237623772378237923802381238223832384238523862387238823892390239123922393239423952396239723982399240024012402240324042405240624072408240924102411241224132414241524162417241824192420242124222423242424252426242724282429243024312432243324342435243624372438243924402441244224432444244524462447244824492450245124522453245424552456245724582459246024612462246324642465246624672468246924702471247224732474247524762477247824792480248124822483248424852486248724882489249024912492249324942495249624972498249925002501250225032504250525062507250825092510251125122513251425152516251725182519252025212522252325242525252625272528252925302531253225332534253525362537253825392540254125422543254425452546254725482549255025512552255325542555255625572558255925602561256225632564256525662567256825692570257125722573257425752576257725782579258025812582258325842585258625872588258925902591259225932594259525962597259825992600260126022603260426052606260726082609261026112612261326142615261626172618261926202621262226232624262526262627262826292630263126322633263426352636263726382639264026412642264326442645264626472648264926502651265226532654265526562657265826592660266126622663266426652666266726682669267026712672267326742675267626772678267926802681268226832684268526862687268826892690269126922693269426952696269726982699270027012702270327042705270627072708270927102711271227132714271527162717271827192720272127222723272427252726272727282729273027312732273327342735273627372738273927402741274227432744274527462747274827492750275127522753275427552756275727582759276027612762276327642765276627672768276927702771277227732774277527762777277827792780278127822783278427852786278727882789279027912792279327942795279627972798279928002801280228032804280528062807280828092810281128122813281428152816281728182819282028212822282328242825282628272828282928302831283228332834283528362837283828392840284128422843284428452846284728482849285028512852285328542855285628572858285928602861286228632864286528662867286828692870287128722873287428752876287728782879288028812882288328842885288628872888288928902891289228932894289528962897289828992900290129022903290429052906290729082909291029112912291329142915291629172918291929202921292229232924292529262927292829292930293129322933293429352936293729382939294029412942294329442945294629472948294929502951295229532954295529562957295829592960296129622963296429652966296729682969297029712972297329742975297629772978297929802981298229832984298529862987298829892990299129922993299429952996299729982999300030013002300330043005300630073008300930103011301230133014301530163017301830193020302130223023302430253026302730283029303030313032303330343035303630373038303930403041304230433044304530463047304830493050305130523053305430553056305730583059306030613062306330643065306630673068306930703071307230733074307530763077307830793080308130823083308430853086308730883089309030913092309330943095309630973098309931003101310231033104310531063107310831093110311131123113311431153116311731183119312031213122312331243125312631273128312931303131313231333134313531363137313831393140314131423143314431453146314731483149315031513152315331543155315631573158315931603161316231633164316531663167316831693170317131723173317431753176317731783179318031813182318331843185318631873188318931903191319231933194319531963197319831993200320132023203320432053206320732083209321032113212321332143215321632173218321932203221322232233224322532263227322832293230323132323233323432353236323732383239324032413242324332443245324632473248324932503251325232533254325532563257325832593260326132623263326432653266326732683269327032713272327332743275327632773278327932803281328232833284328532863287328832893290329132923293329432953296329732983299330033013302330333043305330633073308330933103311331233133314331533163317331833193320332133223323332433253326332733283329333033313332333333343335333633373338333933403341334233433344334533463347334833493350335133523353335433553356335733583359336033613362336333643365336633673368336933703371337233733374337533763377337833793380338133823383338433853386338733883389339033913392339333943395339633973398339934003401340234033404340534063407340834093410341134123413341434153416341734183419342034213422342334243425342634273428342934303431343234333434343534363437343834393440344134423443344434453446344734483449345034513452345334543455345634573458345934603461346234633464346534663467346834693470347134723473347434753476347734783479348034813482348334843485348634873488348934903491349234933494349534963497349834993500350135023503350435053506350735083509351035113512351335143515351635173518351935203521352235233524352535263527352835293530353135323533353435353536353735383539354035413542354335443545354635473548354935503551355235533554355535563557355835593560356135623563356435653566356735683569357035713572357335743575357635773578357935803581358235833584358535863587358835893590359135923593359435953596359735983599360036013602360336043605360636073608360936103611361236133614361536163617361836193620362136223623362436253626362736283629363036313632363336343635363636373638363936403641364236433644364536463647364836493650365136523653365436553656365736583659366036613662366336643665366636673668366936703671367236733674367536763677367836793680368136823683368436853686368736883689369036913692369336943695369636973698369937003701370237033704370537063707370837093710371137123713371437153716371737183719372037213722372337243725372637273728372937303731373237333734373537363737373837393740374137423743374437453746374737483749375037513752375337543755375637573758375937603761376237633764376537663767376837693770377137723773377437753776377737783779378037813782378337843785378637873788378937903791379237933794379537963797379837993800380138023803380438053806380738083809381038113812381338143815381638173818381938203821382238233824382538263827382838293830383138323833383438353836383738383839384038413842384338443845384638473848384938503851385238533854385538563857385838593860386138623863386438653866386738683869387038713872387338743875387638773878387938803881388238833884388538863887388838893890389138923893389438953896389738983899390039013902390339043905390639073908390939103911391239133914391539163917391839193920392139223923392439253926392739283929393039313932393339343935393639373938393939403941394239433944394539463947394839493950395139523953395439553956395739583959396039613962396339643965396639673968396939703971397239733974397539763977397839793980398139823983398439853986398739883989399039913992399339943995399639973998399940004001400240034004400540064007400840094010401140124013401440154016401740184019402040214022402340244025402640274028402940304031403240334034403540364037403840394040404140424043404440454046404740484049405040514052405340544055405640574058405940604061406240634064406540664067406840694070407140724073407440754076407740784079408040814082408340844085408640874088408940904091409240934094409540964097409840994100410141024103410441054106410741084109411041114112411341144115411641174118411941204121412241234124412541264127412841294130413141324133413441354136413741384139414041414142414341444145414641474148414941504151415241534154415541564157415841594160416141624163416441654166416741684169417041714172417341744175417641774178417941804181418241834184418541864187418841894190419141924193419441954196419741984199420042014202420342044205420642074208420942104211421242134214421542164217421842194220422142224223422442254226422742284229423042314232423342344235423642374238423942404241424242434244424542464247424842494250425142524253425442554256425742584259426042614262426342644265426642674268426942704271427242734274427542764277427842794280428142824283428442854286428742884289429042914292429342944295429642974298429943004301430243034304430543064307430843094310431143124313431443154316431743184319432043214322432343244325432643274328432943304331433243334334433543364337433843394340434143424343434443454346434743484349435043514352435343544355435643574358435943604361436243634364436543664367436843694370437143724373437443754376437743784379438043814382438343844385438643874388438943904391439243934394439543964397439843994400440144024403440444054406440744084409441044114412441344144415441644174418441944204421442244234424442544264427442844294430443144324433443444354436443744384439444044414442444344444445444644474448444944504451445244534454445544564457445844594460446144624463446444654466446744684469447044714472447344744475447644774478447944804481448244834484448544864487448844894490449144924493449444954496449744984499450045014502450345044505450645074508450945104511451245134514451545164517451845194520452145224523452445254526452745284529453045314532453345344535453645374538453945404541454245434544454545464547454845494550455145524553455445554556455745584559456045614562456345644565456645674568456945704571457245734574457545764577457845794580458145824583458445854586458745884589459045914592459345944595459645974598459946004601460246034604460546064607460846094610461146124613461446154616461746184619462046214622462346244625462646274628462946304631463246334634463546364637463846394640464146424643464446454646464746484649465046514652465346544655465646574658465946604661466246634664466546664667466846694670467146724673467446754676467746784679468046814682468346844685468646874688468946904691469246934694469546964697469846994700470147024703470447054706470747084709471047114712471347144715471647174718471947204721472247234724472547264727472847294730473147324733473447354736473747384739474047414742474347444745474647474748474947504751475247534754475547564757475847594760476147624763476447654766476747684769477047714772477347744775477647774778477947804781478247834784478547864787478847894790479147924793479447954796479747984799480048014802480348044805480648074808480948104811481248134814481548164817481848194820482148224823482448254826482748284829483048314832483348344835483648374838483948404841484248434844484548464847484848494850485148524853485448554856485748584859486048614862486348644865486648674868486948704871487248734874487548764877487848794880488148824883488448854886488748884889489048914892489348944895489648974898489949004901490249034904490549064907490849094910491149124913491449154916491749184919492049214922492349244925492649274928492949304931493249334934493549364937493849394940494149424943494449454946494749484949495049514952495349544955495649574958495949604961496249634964496549664967496849694970497149724973497449754976497749784979498049814982498349844985498649874988498949904991499249934994499549964997499849995000500150025003500450055006500750085009501050115012501350145015501650175018501950205021502250235024502550265027502850295030503150325033503450355036503750385039504050415042504350445045504650475048504950505051505250535054505550565057505850595060506150625063506450655066506750685069507050715072507350745075507650775078507950805081508250835084508550865087508850895090509150925093509450955096509750985099510051015102510351045105510651075108510951105111511251135114511551165117511851195120512151225123512451255126512751285129513051315132513351345135513651375138513951405141514251435144514551465147514851495150515151525153515451555156515751585159516051615162516351645165516651675168516951705171517251735174517551765177517851795180518151825183518451855186518751885189519051915192519351945195519651975198519952005201520252035204520552065207520852095210521152125213521452155216521752185219522052215222522352245225522652275228522952305231523252335234523552365237523852395240524152425243524452455246524752485249525052515252525352545255525652575258525952605261526252635264526552665267526852695270527152725273527452755276527752785279528052815282528352845285528652875288528952905291529252935294529552965297529852995300530153025303530453055306530753085309531053115312531353145315531653175318531953205321532253235324532553265327532853295330533153325333533453355336533753385339534053415342534353445345534653475348534953505351535253535354535553565357535853595360536153625363536453655366536753685369537053715372537353745375537653775378537953805381538253835384538553865387538853895390539153925393539453955396539753985399540054015402540354045405540654075408540954105411541254135414541554165417541854195420542154225423542454255426542754285429543054315432543354345435543654375438543954405441544254435444544554465447544854495450545154525453545454555456545754585459546054615462546354645465546654675468546954705471547254735474547554765477547854795480548154825483548454855486548754885489549054915492549354945495549654975498549955005501550255035504550555065507550855095510551155125513551455155516551755185519552055215522552355245525552655275528552955305531553255335534553555365537553855395540554155425543554455455546554755485549555055515552555355545555555655575558555955605561556255635564556555665567556855695570557155725573557455755576557755785579558055815582558355845585558655875588558955905591559255935594559555965597559855995600560156025603560456055606560756085609561056115612561356145615561656175618561956205621562256235624562556265627562856295630563156325633563456355636563756385639564056415642564356445645564656475648564956505651565256535654565556565657565856595660566156625663566456655666566756685669567056715672567356745675567656775678567956805681568256835684568556865687568856895690569156925693569456955696569756985699570057015702570357045705570657075708570957105711571257135714571557165717571857195720572157225723572457255726572757285729573057315732573357345735573657375738573957405741574257435744574557465747574857495750575157525753575457555756575757585759576057615762576357645765576657675768576957705771577257735774577557765777577857795780578157825783578457855786578757885789579057915792579357945795579657975798579958005801580258035804580558065807580858095810581158125813581458155816581758185819582058215822582358245825582658275828582958305831583258335834583558365837583858395840584158425843584458455846584758485849585058515852585358545855585658575858585958605861586258635864586558665867586858695870587158725873587458755876587758785879588058815882588358845885588658875888588958905891589258935894589558965897589858995900590159025903590459055906590759085909591059115912591359145915591659175918591959205921592259235924592559265927592859295930593159325933593459355936593759385939594059415942594359445945594659475948594959505951595259535954595559565957595859595960596159625963596459655966596759685969597059715972597359745975597659775978597959805981598259835984598559865987598859895990599159925993599459955996599759985999600060016002600360046005600660076008600960106011601260136014601560166017601860196020602160226023602460256026602760286029603060316032603360346035603660376038603960406041604260436044604560466047604860496050605160526053605460556056605760586059606060616062606360646065606660676068606960706071607260736074607560766077607860796080608160826083608460856086608760886089609060916092609360946095609660976098609961006101610261036104610561066107610861096110611161126113611461156116611761186119612061216122612361246125612661276128612961306131613261336134613561366137613861396140614161426143614461456146614761486149615061516152615361546155615661576158615961606161616261636164616561666167616861696170617161726173617461756176617761786179618061816182618361846185618661876188618961906191619261936194619561966197619861996200620162026203620462056206620762086209621062116212621362146215621662176218621962206221622262236224622562266227622862296230623162326233623462356236623762386239624062416242624362446245624662476248624962506251625262536254625562566257625862596260626162626263626462656266626762686269627062716272627362746275627662776278627962806281628262836284628562866287628862896290629162926293629462956296629762986299630063016302630363046305630663076308630963106311631263136314631563166317631863196320632163226323632463256326632763286329633063316332633363346335633663376338633963406341634263436344634563466347634863496350635163526353635463556356635763586359636063616362636363646365636663676368636963706371637263736374637563766377637863796380638163826383638463856386638763886389639063916392639363946395639663976398639964006401640264036404640564066407640864096410641164126413641464156416641764186419642064216422642364246425642664276428642964306431643264336434643564366437643864396440644164426443644464456446644764486449645064516452645364546455645664576458645964606461646264636464646564666467646864696470647164726473647464756476647764786479648064816482648364846485648664876488648964906491649264936494649564966497649864996500650165026503650465056506650765086509651065116512651365146515651665176518651965206521652265236524652565266527652865296530653165326533653465356536653765386539654065416542654365446545654665476548654965506551655265536554655565566557655865596560656165626563656465656566656765686569657065716572657365746575657665776578657965806581658265836584658565866587658865896590659165926593659465956596659765986599660066016602660366046605660666076608660966106611661266136614661566166617661866196620662166226623662466256626662766286629663066316632663366346635663666376638663966406641664266436644664566466647664866496650665166526653665466556656665766586659666066616662666366646665666666676668666966706671667266736674667566766677667866796680668166826683668466856686668766886689669066916692669366946695669666976698669967006701670267036704670567066707670867096710671167126713671467156716671767186719672067216722672367246725672667276728672967306731673267336734673567366737673867396740674167426743674467456746674767486749675067516752675367546755675667576758675967606761676267636764676567666767676867696770677167726773677467756776677767786779678067816782678367846785678667876788678967906791679267936794679567966797679867996800680168026803680468056806680768086809681068116812681368146815681668176818681968206821682268236824682568266827682868296830683168326833683468356836683768386839684068416842684368446845684668476848684968506851685268536854685568566857685868596860686168626863686468656866686768686869687068716872687368746875687668776878687968806881688268836884688568866887688868896890689168926893689468956896689768986899690069016902690369046905690669076908690969106911691269136914691569166917691869196920692169226923692469256926692769286929693069316932693369346935693669376938693969406941694269436944694569466947694869496950695169526953695469556956695769586959696069616962696369646965696669676968696969706971697269736974697569766977697869796980698169826983698469856986698769886989699069916992699369946995699669976998699970007001700270037004700570067007700870097010701170127013701470157016701770187019702070217022702370247025702670277028702970307031703270337034703570367037703870397040704170427043704470457046704770487049705070517052705370547055705670577058705970607061706270637064706570667067706870697070707170727073707470757076707770787079708070817082708370847085708670877088708970907091709270937094709570967097709870997100710171027103710471057106710771087109711071117112711371147115711671177118711971207121712271237124712571267127712871297130713171327133713471357136713771387139714071417142714371447145714671477148714971507151715271537154715571567157715871597160716171627163716471657166716771687169717071717172717371747175717671777178717971807181718271837184718571867187718871897190719171927193719471957196719771987199720072017202720372047205720672077208720972107211721272137214721572167217721872197220722172227223722472257226722772287229723072317232723372347235723672377238723972407241724272437244724572467247724872497250725172527253725472557256725772587259726072617262726372647265726672677268726972707271727272737274727572767277727872797280728172827283728472857286728772887289729072917292729372947295729672977298729973007301730273037304730573067307730873097310731173127313731473157316731773187319732073217322732373247325732673277328732973307331733273337334733573367337733873397340734173427343734473457346734773487349735073517352735373547355735673577358735973607361736273637364736573667367736873697370737173727373737473757376737773787379738073817382738373847385738673877388738973907391739273937394739573967397739873997400740174027403740474057406740774087409741074117412741374147415741674177418741974207421742274237424742574267427742874297430743174327433743474357436743774387439744074417442744374447445744674477448744974507451745274537454745574567457745874597460746174627463746474657466746774687469747074717472747374747475747674777478747974807481748274837484748574867487748874897490749174927493749474957496749774987499750075017502750375047505750675077508750975107511751275137514751575167517751875197520752175227523752475257526752775287529753075317532753375347535753675377538753975407541754275437544754575467547754875497550755175527553755475557556755775587559756075617562756375647565756675677568756975707571757275737574757575767577757875797580758175827583758475857586758775887589759075917592759375947595759675977598759976007601760276037604760576067607760876097610761176127613761476157616761776187619762076217622762376247625762676277628762976307631763276337634763576367637763876397640764176427643764476457646764776487649765076517652765376547655765676577658765976607661766276637664766576667667766876697670767176727673767476757676767776787679768076817682768376847685768676877688768976907691769276937694769576967697769876997700770177027703770477057706770777087709771077117712771377147715771677177718771977207721772277237724772577267727772877297730773177327733773477357736773777387739774077417742774377447745774677477748774977507751775277537754775577567757775877597760776177627763776477657766776777687769777077717772777377747775777677777778777977807781778277837784778577867787778877897790779177927793779477957796779777987799780078017802780378047805780678077808780978107811781278137814781578167817781878197820782178227823782478257826782778287829783078317832783378347835783678377838783978407841784278437844784578467847784878497850785178527853785478557856785778587859786078617862786378647865786678677868786978707871787278737874787578767877787878797880788178827883788478857886788778887889789078917892789378947895789678977898789979007901790279037904790579067907790879097910791179127913791479157916791779187919792079217922792379247925792679277928792979307931793279337934793579367937793879397940794179427943794479457946794779487949795079517952795379547955795679577958795979607961796279637964796579667967796879697970797179727973797479757976797779787979798079817982798379847985798679877988798979907991799279937994799579967997799879998000800180028003800480058006800780088009801080118012801380148015801680178018801980208021802280238024802580268027802880298030803180328033803480358036803780388039804080418042804380448045804680478048804980508051805280538054805580568057805880598060806180628063806480658066806780688069807080718072807380748075807680778078807980808081808280838084808580868087808880898090809180928093809480958096809780988099810081018102810381048105810681078108810981108111811281138114811581168117811881198120812181228123812481258126812781288129813081318132813381348135813681378138813981408141814281438144814581468147814881498150815181528153815481558156815781588159816081618162816381648165816681678168816981708171817281738174817581768177817881798180818181828183818481858186818781888189819081918192819381948195819681978198819982008201820282038204820582068207820882098210821182128213821482158216821782188219822082218222822382248225822682278228822982308231823282338234823582368237823882398240824182428243824482458246824782488249825082518252825382548255825682578258825982608261826282638264826582668267826882698270827182728273827482758276827782788279828082818282828382848285828682878288828982908291829282938294829582968297829882998300830183028303830483058306830783088309831083118312831383148315831683178318831983208321832283238324832583268327832883298330833183328333833483358336833783388339834083418342834383448345834683478348834983508351835283538354835583568357835883598360836183628363836483658366836783688369837083718372837383748375837683778378837983808381838283838384838583868387838883898390839183928393839483958396839783988399840084018402840384048405840684078408840984108411841284138414841584168417841884198420842184228423842484258426842784288429843084318432843384348435843684378438843984408441844284438444844584468447844884498450845184528453845484558456845784588459846084618462846384648465846684678468846984708471847284738474847584768477847884798480848184828483848484858486848784888489849084918492849384948495849684978498849985008501850285038504850585068507850885098510851185128513851485158516851785188519852085218522852385248525852685278528852985308531853285338534853585368537853885398540854185428543854485458546854785488549855085518552855385548555855685578558855985608561856285638564856585668567856885698570857185728573857485758576857785788579858085818582858385848585858685878588858985908591859285938594859585968597859885998600860186028603860486058606860786088609861086118612861386148615861686178618861986208621862286238624862586268627862886298630863186328633863486358636863786388639864086418642864386448645864686478648864986508651865286538654865586568657865886598660866186628663866486658666866786688669867086718672867386748675867686778678867986808681868286838684868586868687868886898690869186928693869486958696869786988699870087018702870387048705870687078708870987108711871287138714871587168717871887198720872187228723872487258726872787288729873087318732873387348735873687378738873987408741874287438744874587468747874887498750875187528753875487558756875787588759876087618762876387648765876687678768876987708771877287738774877587768777877887798780878187828783878487858786878787888789879087918792879387948795879687978798879988008801880288038804880588068807880888098810881188128813881488158816881788188819882088218822882388248825882688278828882988308831883288338834883588368837883888398840884188428843884488458846884788488849885088518852885388548855885688578858885988608861886288638864886588668867886888698870887188728873887488758876887788788879888088818882888388848885888688878888888988908891889288938894889588968897889888998900890189028903890489058906890789088909891089118912891389148915891689178918891989208921892289238924892589268927892889298930893189328933893489358936893789388939894089418942894389448945894689478948894989508951895289538954895589568957895889598960896189628963896489658966896789688969897089718972897389748975897689778978897989808981898289838984898589868987898889898990899189928993899489958996899789988999900090019002900390049005900690079008900990109011901290139014901590169017901890199020902190229023902490259026902790289029903090319032903390349035903690379038903990409041904290439044904590469047904890499050905190529053905490559056905790589059906090619062906390649065906690679068906990709071907290739074907590769077907890799080908190829083908490859086908790889089909090919092909390949095909690979098909991009101910291039104910591069107910891099110911191129113911491159116911791189119912091219122912391249125912691279128912991309131913291339134913591369137913891399140914191429143914491459146914791489149915091519152915391549155915691579158915991609161916291639164916591669167916891699170917191729173917491759176917791789179918091819182918391849185918691879188918991909191919291939194919591969197919891999200920192029203920492059206920792089209921092119212921392149215921692179218921992209221922292239224922592269227922892299230923192329233923492359236923792389239924092419242924392449245924692479248924992509251925292539254925592569257925892599260926192629263926492659266926792689269927092719272927392749275927692779278927992809281928292839284928592869287928892899290929192929293929492959296929792989299930093019302930393049305930693079308930993109311931293139314931593169317931893199320932193229323932493259326932793289329933093319332933393349335933693379338933993409341934293439344934593469347934893499350935193529353935493559356935793589359936093619362936393649365936693679368936993709371937293739374937593769377937893799380938193829383938493859386938793889389939093919392939393949395939693979398939994009401940294039404940594069407940894099410941194129413941494159416941794189419942094219422942394249425942694279428942994309431943294339434943594369437943894399440944194429443944494459446944794489449945094519452945394549455945694579458945994609461946294639464946594669467946894699470947194729473947494759476947794789479948094819482948394849485948694879488948994909491949294939494949594969497949894999500950195029503950495059506950795089509951095119512951395149515951695179518951995209521952295239524952595269527952895299530953195329533953495359536953795389539954095419542954395449545954695479548954995509551955295539554955595569557955895599560956195629563956495659566956795689569957095719572957395749575957695779578957995809581958295839584958595869587958895899590959195929593959495959596959795989599960096019602960396049605960696079608960996109611961296139614961596169617961896199620962196229623962496259626962796289629963096319632963396349635963696379638963996409641964296439644964596469647964896499650965196529653965496559656965796589659966096619662966396649665966696679668966996709671967296739674967596769677967896799680968196829683968496859686968796889689969096919692969396949695969696979698969997009701970297039704970597069707970897099710971197129713971497159716971797189719972097219722972397249725972697279728972997309731973297339734973597369737973897399740974197429743974497459746974797489749975097519752975397549755975697579758975997609761976297639764976597669767976897699770977197729773977497759776977797789779978097819782978397849785978697879788978997909791979297939794979597969797979897999800980198029803980498059806980798089809981098119812981398149815981698179818981998209821982298239824982598269827982898299830983198329833983498359836983798389839984098419842984398449845984698479848984998509851985298539854985598569857985898599860986198629863986498659866986798689869987098719872987398749875987698779878987998809881988298839884988598869887988898899890989198929893989498959896989798989899990099019902990399049905990699079908990999109911991299139914991599169917991899199920992199229923992499259926992799289929993099319932993399349935993699379938993999409941994299439944994599469947994899499950995199529953995499559956995799589959996099619962996399649965996699679968996999709971997299739974997599769977997899799980998199829983998499859986998799889989999099919992999399949995999699979998999910000100011000210003100041000510006100071000810009100101001110012100131001410015100161001710018100191002010021100221002310024100251002610027100281002910030100311003210033100341003510036100371003810039100401004110042100431004410045100461004710048100491005010051100521005310054100551005610057100581005910060100611006210063100641006510066100671006810069100701007110072100731007410075100761007710078100791008010081100821008310084100851008610087100881008910090100911009210093100941009510096100971009810099101001010110102101031010410105101061010710108101091011010111101121011310114101151011610117101181011910120101211012210123101241012510126101271012810129101301013110132101331013410135101361013710138101391014010141101421014310144101451014610147101481014910150101511015210153101541015510156101571015810159101601016110162101631016410165101661016710168101691017010171101721017310174101751017610177101781017910180101811018210183101841018510186101871018810189101901019110192101931019410195101961019710198101991020010201102021020310204102051020610207102081020910210102111021210213102141021510216102171021810219102201022110222102231022410225102261022710228102291023010231102321023310234102351023610237102381023910240102411024210243102441024510246102471024810249102501025110252102531025410255102561025710258102591026010261102621026310264102651026610267102681026910270102711027210273102741027510276102771027810279102801028110282102831028410285102861028710288102891029010291102921029310294102951029610297102981029910300103011030210303103041030510306103071030810309103101031110312103131031410315103161031710318103191032010321103221032310324103251032610327103281032910330103311033210333103341033510336103371033810339103401034110342103431034410345103461034710348103491035010351103521035310354103551035610357103581035910360103611036210363103641036510366103671036810369103701037110372103731037410375103761037710378103791038010381103821038310384103851038610387103881038910390103911039210393103941039510396103971039810399104001040110402104031040410405104061040710408104091041010411104121041310414104151041610417104181041910420104211042210423104241042510426104271042810429104301043110432104331043410435104361043710438104391044010441104421044310444104451044610447104481044910450104511045210453104541045510456104571045810459104601046110462104631046410465104661046710468104691047010471104721047310474104751047610477104781047910480104811048210483104841048510486104871048810489104901049110492104931049410495104961049710498104991050010501105021050310504105051050610507105081050910510105111051210513105141051510516105171051810519105201052110522105231052410525105261052710528105291053010531105321053310534105351053610537105381053910540105411054210543105441054510546105471054810549105501055110552105531055410555105561055710558105591056010561105621056310564105651056610567105681056910570105711057210573105741057510576105771057810579105801058110582105831058410585105861058710588105891059010591105921059310594105951059610597105981059910600106011060210603106041060510606106071060810609106101061110612106131061410615106161061710618106191062010621106221062310624106251062610627106281062910630106311063210633106341063510636106371063810639106401064110642106431064410645106461064710648106491065010651106521065310654106551065610657106581065910660106611066210663106641066510666106671066810669106701067110672106731067410675106761067710678106791068010681106821068310684106851068610687106881068910690106911069210693106941069510696106971069810699107001070110702107031070410705107061070710708107091071010711107121071310714107151071610717107181071910720107211072210723107241072510726107271072810729107301073110732107331073410735107361073710738107391074010741107421074310744107451074610747107481074910750107511075210753107541075510756107571075810759107601076110762107631076410765107661076710768107691077010771107721077310774107751077610777107781077910780107811078210783107841078510786107871078810789107901079110792107931079410795107961079710798107991080010801108021080310804108051080610807108081080910810108111081210813108141081510816108171081810819108201082110822108231082410825108261082710828108291083010831108321083310834108351083610837108381083910840108411084210843108441084510846108471084810849108501085110852108531085410855108561085710858108591086010861108621086310864108651086610867108681086910870108711087210873108741087510876108771087810879108801088110882108831088410885108861088710888108891089010891108921089310894108951089610897108981089910900109011090210903109041090510906109071090810909109101091110912109131091410915109161091710918109191092010921109221092310924109251092610927109281092910930109311093210933109341093510936109371093810939109401094110942109431094410945109461094710948109491095010951109521095310954109551095610957109581095910960109611096210963109641096510966109671096810969109701097110972109731097410975109761097710978109791098010981109821098310984109851098610987109881098910990109911099210993109941099510996109971099810999110001100111002110031100411005110061100711008110091101011011110121101311014110151101611017110181101911020110211102211023110241102511026110271102811029110301103111032110331103411035110361103711038110391104011041110421104311044110451104611047110481104911050110511105211053110541105511056110571105811059110601106111062110631106411065110661106711068110691107011071110721107311074110751107611077110781107911080110811108211083110841108511086110871108811089110901109111092110931109411095110961109711098110991110011101111021110311104111051110611107111081110911110111111111211113111141111511116111171111811119111201112111122111231112411125111261112711128111291113011131111321113311134111351113611137111381113911140111411114211143111441114511146111471114811149111501115111152111531115411155111561115711158111591116011161111621116311164111651116611167111681116911170111711117211173111741117511176111771117811179111801118111182111831118411185111861118711188111891119011191111921119311194111951119611197111981119911200112011120211203112041120511206112071120811209112101121111212112131121411215112161121711218112191122011221112221122311224112251122611227112281122911230112311123211233112341123511236112371123811239112401124111242112431124411245112461124711248112491125011251112521125311254112551125611257112581125911260112611126211263112641126511266112671126811269112701127111272112731127411275112761127711278112791128011281112821128311284112851128611287112881128911290112911129211293112941129511296112971129811299113001130111302113031130411305113061130711308113091131011311113121131311314113151131611317113181131911320113211132211323113241132511326113271132811329113301133111332113331133411335113361133711338113391134011341113421134311344113451134611347113481134911350113511135211353113541135511356113571135811359113601136111362113631136411365113661136711368113691137011371113721137311374113751137611377113781137911380113811138211383113841138511386113871138811389113901139111392113931139411395113961139711398113991140011401114021140311404114051140611407114081140911410114111141211413114141141511416114171141811419114201142111422114231142411425114261142711428114291143011431114321143311434114351143611437114381143911440114411144211443114441144511446114471144811449114501145111452114531145411455114561145711458114591146011461114621146311464114651146611467114681146911470114711147211473114741147511476114771147811479114801148111482114831148411485114861148711488114891149011491114921149311494114951149611497114981149911500115011150211503115041150511506115071150811509115101151111512115131151411515115161151711518115191152011521115221152311524115251152611527115281152911530115311153211533115341153511536115371153811539115401154111542115431154411545115461154711548115491155011551115521155311554115551155611557115581155911560115611156211563115641156511566115671156811569115701157111572115731157411575115761157711578115791158011581115821158311584115851158611587115881158911590115911159211593115941159511596115971159811599116001160111602116031160411605116061160711608116091161011611116121161311614116151161611617116181161911620116211162211623116241162511626116271162811629116301163111632116331163411635116361163711638116391164011641116421164311644116451164611647116481164911650116511165211653116541165511656116571165811659116601166111662116631166411665116661166711668116691167011671116721167311674116751167611677116781167911680116811168211683116841168511686116871168811689116901169111692116931169411695116961169711698116991170011701117021170311704117051170611707117081170911710117111171211713117141171511716117171171811719117201172111722117231172411725117261172711728117291173011731117321173311734117351173611737117381173911740117411174211743117441174511746117471174811749117501175111752117531175411755117561175711758117591176011761117621176311764117651176611767117681176911770117711177211773117741177511776117771177811779117801178111782117831178411785117861178711788117891179011791117921179311794117951179611797117981179911800118011180211803118041180511806118071180811809118101181111812118131181411815118161181711818118191182011821118221182311824118251182611827118281182911830118311183211833118341183511836118371183811839118401184111842118431184411845118461184711848118491185011851118521185311854118551185611857118581185911860118611186211863118641186511866118671186811869118701187111872118731187411875118761187711878118791188011881118821188311884118851188611887118881188911890118911189211893118941189511896118971189811899119001190111902119031190411905119061190711908119091191011911119121191311914119151191611917119181191911920119211192211923119241192511926119271192811929119301193111932119331193411935119361193711938119391194011941119421194311944119451194611947119481194911950119511195211953119541195511956119571195811959119601196111962119631196411965119661196711968119691197011971119721197311974119751197611977119781197911980119811198211983119841198511986119871198811989119901199111992119931199411995119961199711998119991200012001120021200312004120051200612007120081200912010120111201212013120141201512016120171201812019120201202112022120231202412025120261202712028120291203012031120321203312034120351203612037120381203912040120411204212043120441204512046120471204812049120501205112052120531205412055120561205712058120591206012061120621206312064120651206612067120681206912070120711207212073120741207512076120771207812079120801208112082120831208412085120861208712088120891209012091120921209312094120951209612097120981209912100121011210212103121041210512106121071210812109121101211112112121131211412115121161211712118121191212012121121221212312124121251212612127121281212912130121311213212133121341213512136121371213812139121401214112142121431214412145121461214712148121491215012151121521215312154121551215612157121581215912160121611216212163121641216512166121671216812169121701217112172121731217412175121761217712178121791218012181121821218312184121851218612187121881218912190121911219212193121941219512196121971219812199122001220112202122031220412205122061220712208122091221012211122121221312214122151221612217122181221912220122211222212223122241222512226122271222812229122301223112232122331223412235122361223712238122391224012241122421224312244122451224612247122481224912250122511225212253122541225512256122571225812259122601226112262122631226412265122661226712268122691227012271122721227312274122751227612277122781227912280122811228212283122841228512286122871228812289122901229112292122931229412295122961229712298122991230012301123021230312304123051230612307123081230912310123111231212313123141231512316123171231812319123201232112322123231232412325123261232712328123291233012331123321233312334123351233612337123381233912340123411234212343123441234512346123471234812349123501235112352123531235412355123561235712358123591236012361123621236312364123651236612367123681236912370123711237212373123741237512376123771237812379123801238112382123831238412385123861238712388123891239012391123921239312394123951239612397123981239912400124011240212403124041240512406124071240812409124101241112412124131241412415124161241712418124191242012421124221242312424124251242612427124281242912430124311243212433124341243512436124371243812439124401244112442124431244412445124461244712448124491245012451124521245312454124551245612457124581245912460124611246212463124641246512466124671246812469124701247112472124731247412475124761247712478124791248012481124821248312484124851248612487124881248912490124911249212493124941249512496124971249812499125001250112502125031250412505125061250712508125091251012511125121251312514125151251612517125181251912520125211252212523125241252512526125271252812529125301253112532125331253412535125361253712538125391254012541125421254312544125451254612547125481254912550125511255212553125541255512556125571255812559125601256112562125631256412565125661256712568125691257012571125721257312574125751257612577125781257912580125811258212583125841258512586125871258812589125901259112592125931259412595125961259712598125991260012601126021260312604126051260612607126081260912610126111261212613126141261512616126171261812619126201262112622126231262412625126261262712628126291263012631126321263312634126351263612637126381263912640126411264212643126441264512646126471264812649126501265112652126531265412655126561265712658126591266012661126621266312664126651266612667126681266912670126711267212673126741267512676126771267812679126801268112682126831268412685126861268712688126891269012691126921269312694126951269612697126981269912700127011270212703127041270512706127071270812709127101271112712127131271412715127161271712718127191272012721127221272312724127251272612727127281272912730127311273212733127341273512736127371273812739127401274112742127431274412745127461274712748127491275012751127521275312754127551275612757127581275912760127611276212763127641276512766127671276812769127701277112772127731277412775127761277712778127791278012781127821278312784127851278612787127881278912790127911279212793127941279512796127971279812799128001280112802128031280412805128061280712808128091281012811128121281312814128151281612817128181281912820128211282212823128241282512826128271282812829128301283112832128331283412835128361283712838128391284012841128421284312844128451284612847128481284912850128511285212853128541285512856128571285812859128601286112862128631286412865128661286712868128691287012871128721287312874128751287612877128781287912880128811288212883128841288512886128871288812889128901289112892128931289412895128961289712898128991290012901129021290312904129051290612907129081290912910129111291212913129141291512916129171291812919129201292112922129231292412925129261292712928129291293012931129321293312934129351293612937129381293912940129411294212943129441294512946129471294812949129501295112952129531295412955129561295712958129591296012961129621296312964129651296612967129681296912970129711297212973129741297512976129771297812979129801298112982129831298412985129861298712988129891299012991129921299312994129951299612997129981299913000130011300213003130041300513006130071300813009130101301113012130131301413015130161301713018130191302013021130221302313024130251302613027130281302913030130311303213033130341303513036130371303813039130401304113042130431304413045130461304713048130491305013051130521305313054130551305613057130581305913060130611306213063130641306513066130671306813069130701307113072130731307413075130761307713078130791308013081130821308313084130851308613087130881308913090130911309213093130941309513096130971309813099131001310113102131031310413105131061310713108131091311013111131121311313114131151311613117131181311913120131211312213123131241312513126131271312813129131301313113132131331313413135131361313713138131391314013141131421314313144131451314613147131481314913150131511315213153131541315513156131571315813159131601316113162131631316413165131661316713168131691317013171131721317313174131751317613177131781317913180131811318213183131841318513186131871318813189131901319113192131931319413195131961319713198131991320013201132021320313204132051320613207132081320913210132111321213213132141321513216132171321813219132201322113222132231322413225132261322713228132291323013231132321323313234132351323613237132381323913240132411324213243132441324513246132471324813249132501325113252132531325413255132561325713258132591326013261132621326313264132651326613267132681326913270132711327213273132741327513276132771327813279132801328113282132831328413285132861328713288132891329013291132921329313294132951329613297132981329913300133011330213303133041330513306133071330813309133101331113312133131331413315133161331713318133191332013321133221332313324133251332613327133281332913330133311333213333133341333513336133371333813339133401334113342133431334413345133461334713348133491335013351133521335313354133551335613357133581335913360133611336213363133641336513366133671336813369133701337113372133731337413375133761337713378133791338013381133821338313384133851338613387133881338913390133911339213393133941339513396133971339813399134001340113402134031340413405134061340713408134091341013411134121341313414134151341613417134181341913420134211342213423134241342513426134271342813429134301343113432134331343413435134361343713438134391344013441134421344313444134451344613447134481344913450134511345213453134541345513456134571345813459134601346113462134631346413465134661346713468134691347013471134721347313474134751347613477134781347913480134811348213483134841348513486134871348813489134901349113492134931349413495134961349713498134991350013501135021350313504135051350613507135081350913510135111351213513135141351513516135171351813519135201352113522135231352413525135261352713528135291353013531135321353313534135351353613537135381353913540135411354213543135441354513546135471354813549135501355113552135531355413555135561355713558135591356013561135621356313564135651356613567135681356913570135711357213573135741357513576135771357813579135801358113582135831358413585135861358713588135891359013591135921359313594135951359613597135981359913600136011360213603136041360513606136071360813609136101361113612136131361413615136161361713618136191362013621136221362313624136251362613627136281362913630136311363213633136341363513636136371363813639136401364113642136431364413645136461364713648136491365013651136521365313654136551365613657136581365913660136611366213663136641366513666136671366813669136701367113672136731367413675136761367713678136791368013681136821368313684136851368613687136881368913690136911369213693136941369513696136971369813699137001370113702137031370413705137061370713708137091371013711137121371313714137151371613717137181371913720137211372213723137241372513726137271372813729137301373113732137331373413735137361373713738137391374013741137421374313744137451374613747137481374913750137511375213753137541375513756137571375813759137601376113762137631376413765137661376713768137691377013771137721377313774137751377613777137781377913780137811378213783137841378513786137871378813789137901379113792137931379413795137961379713798137991380013801138021380313804138051380613807138081380913810138111381213813138141381513816138171381813819138201382113822138231382413825138261382713828138291383013831138321383313834138351383613837138381383913840138411384213843138441384513846138471384813849138501385113852138531385413855138561385713858138591386013861138621386313864138651386613867138681386913870138711387213873138741387513876138771387813879138801388113882138831388413885138861388713888138891389013891138921389313894138951389613897138981389913900139011390213903139041390513906139071390813909139101391113912139131391413915139161391713918139191392013921139221392313924139251392613927139281392913930139311393213933139341393513936139371393813939139401394113942139431394413945139461394713948139491395013951139521395313954139551395613957139581395913960139611396213963139641396513966139671396813969139701397113972139731397413975139761397713978139791398013981139821398313984139851398613987139881398913990139911399213993139941399513996139971399813999140001400114002140031400414005140061400714008140091401014011140121401314014140151401614017140181401914020140211402214023140241402514026140271402814029140301403114032140331403414035140361403714038140391404014041140421404314044140451404614047140481404914050140511405214053140541405514056140571405814059140601406114062140631406414065140661406714068140691407014071140721407314074140751407614077140781407914080140811408214083140841408514086140871408814089140901409114092140931409414095140961409714098140991410014101141021410314104141051410614107141081410914110141111411214113141141411514116141171411814119141201412114122141231412414125141261412714128141291413014131141321413314134141351413614137141381413914140141411414214143141441414514146141471414814149141501415114152141531415414155141561415714158141591416014161141621416314164141651416614167141681416914170141711417214173141741417514176141771417814179141801418114182141831418414185141861418714188141891419014191141921419314194141951419614197141981419914200142011420214203142041420514206142071420814209142101421114212142131421414215142161421714218142191422014221142221422314224142251422614227142281422914230142311423214233142341423514236142371423814239142401424114242142431424414245142461424714248142491425014251142521425314254142551425614257142581425914260142611426214263142641426514266142671426814269142701427114272142731427414275142761427714278142791428014281142821428314284142851428614287142881428914290142911429214293142941429514296142971429814299143001430114302143031430414305143061430714308143091431014311143121431314314143151431614317143181431914320143211432214323143241432514326143271432814329143301433114332143331433414335143361433714338143391434014341143421434314344143451434614347143481434914350143511435214353143541435514356143571435814359143601436114362143631436414365143661436714368143691437014371143721437314374143751437614377143781437914380143811438214383143841438514386143871438814389143901439114392143931439414395143961439714398143991440014401144021440314404144051440614407144081440914410144111441214413144141441514416144171441814419144201442114422144231442414425144261442714428144291443014431144321443314434144351443614437144381443914440144411444214443144441444514446144471444814449144501445114452144531445414455144561445714458144591446014461144621446314464144651446614467144681446914470144711447214473144741447514476144771447814479144801448114482144831448414485144861448714488144891449014491144921449314494144951449614497144981449914500145011450214503145041450514506145071450814509145101451114512145131451414515145161451714518145191452014521145221452314524145251452614527145281452914530145311453214533145341453514536145371453814539145401454114542145431454414545145461454714548145491455014551145521455314554145551455614557145581455914560145611456214563145641456514566145671456814569145701457114572145731457414575145761457714578145791458014581145821458314584145851458614587145881458914590145911459214593145941459514596145971459814599146001460114602146031460414605146061460714608146091461014611146121461314614146151461614617146181461914620146211462214623146241462514626146271462814629146301463114632146331463414635146361463714638146391464014641146421464314644146451464614647146481464914650146511465214653146541465514656146571465814659146601466114662146631466414665146661466714668146691467014671146721467314674146751467614677146781467914680146811468214683146841468514686146871468814689146901469114692146931469414695146961469714698146991470014701147021470314704147051470614707147081470914710147111471214713147141471514716147171471814719147201472114722147231472414725147261472714728147291473014731147321473314734147351473614737147381473914740147411474214743147441474514746147471474814749147501475114752147531475414755147561475714758147591476014761147621476314764147651476614767147681476914770147711477214773147741477514776147771477814779147801478114782147831478414785147861478714788147891479014791147921479314794147951479614797147981479914800148011480214803148041480514806148071480814809148101481114812148131481414815148161481714818148191482014821148221482314824148251482614827148281482914830148311483214833148341483514836148371483814839148401484114842148431484414845148461484714848148491485014851148521485314854148551485614857148581485914860148611486214863148641486514866148671486814869148701487114872148731487414875148761487714878148791488014881148821488314884148851488614887148881488914890148911489214893148941489514896148971489814899149001490114902149031490414905149061490714908149091491014911149121491314914149151491614917149181491914920149211492214923149241492514926149271492814929149301493114932149331493414935149361493714938149391494014941149421494314944149451494614947149481494914950149511495214953149541495514956149571495814959149601496114962149631496414965149661496714968149691497014971149721497314974149751497614977149781497914980149811498214983149841498514986149871498814989149901499114992149931499414995149961499714998149991500015001150021500315004150051500615007150081500915010150111501215013150141501515016150171501815019150201502115022150231502415025150261502715028150291503015031150321503315034150351503615037150381503915040150411504215043150441504515046150471504815049150501505115052150531505415055150561505715058150591506015061150621506315064150651506615067150681506915070150711507215073150741507515076150771507815079150801508115082150831508415085150861508715088150891509015091150921509315094150951509615097150981509915100151011510215103151041510515106151071510815109151101511115112151131511415115151161511715118151191512015121151221512315124151251512615127151281512915130151311513215133151341513515136151371513815139151401514115142151431514415145151461514715148151491515015151151521515315154151551515615157151581515915160151611516215163151641516515166151671516815169151701517115172151731517415175151761517715178151791518015181151821518315184151851518615187151881518915190151911519215193151941519515196151971519815199152001520115202152031520415205152061520715208152091521015211152121521315214152151521615217152181521915220152211522215223152241522515226152271522815229152301523115232152331523415235152361523715238152391524015241152421524315244152451524615247152481524915250152511525215253152541525515256152571525815259152601526115262152631526415265152661526715268152691527015271152721527315274152751527615277152781527915280152811528215283152841528515286152871528815289152901529115292152931529415295152961529715298152991530015301153021530315304153051530615307153081530915310153111531215313153141531515316153171531815319153201532115322153231532415325153261532715328153291533015331153321533315334153351533615337153381533915340153411534215343153441534515346153471534815349153501535115352153531535415355153561535715358153591536015361153621536315364153651536615367153681536915370153711537215373153741537515376153771537815379153801538115382153831538415385153861538715388153891539015391153921539315394153951539615397153981539915400154011540215403154041540515406154071540815409154101541115412154131541415415154161541715418154191542015421154221542315424154251542615427154281542915430154311543215433154341543515436154371543815439154401544115442154431544415445154461544715448154491545015451154521545315454154551545615457154581545915460154611546215463154641546515466154671546815469154701547115472154731547415475154761547715478154791548015481154821548315484154851548615487154881548915490154911549215493154941549515496154971549815499155001550115502155031550415505155061550715508155091551015511155121551315514155151551615517155181551915520155211552215523155241552515526155271552815529155301553115532155331553415535155361553715538155391554015541155421554315544155451554615547155481554915550155511555215553155541555515556155571555815559155601556115562155631556415565155661556715568155691557015571155721557315574155751557615577155781557915580155811558215583155841558515586155871558815589155901559115592155931559415595155961559715598155991560015601156021560315604156051560615607156081560915610156111561215613156141561515616156171561815619156201562115622156231562415625156261562715628156291563015631156321563315634156351563615637156381563915640156411564215643156441564515646156471564815649156501565115652156531565415655156561565715658156591566015661156621566315664156651566615667156681566915670156711567215673156741567515676156771567815679156801568115682156831568415685156861568715688156891569015691156921569315694156951569615697156981569915700157011570215703157041570515706157071570815709157101571115712157131571415715157161571715718157191572015721157221572315724157251572615727157281572915730157311573215733157341573515736157371573815739157401574115742157431574415745157461574715748157491575015751157521575315754157551575615757157581575915760157611576215763157641576515766157671576815769157701577115772157731577415775157761577715778157791578015781157821578315784157851578615787157881578915790157911579215793157941579515796157971579815799158001580115802158031580415805158061580715808158091581015811158121581315814158151581615817158181581915820158211582215823158241582515826158271582815829158301583115832158331583415835158361583715838158391584015841158421584315844158451584615847158481584915850158511585215853158541585515856158571585815859158601586115862158631586415865158661586715868158691587015871158721587315874158751587615877158781587915880158811588215883158841588515886158871588815889158901589115892158931589415895158961589715898158991590015901159021590315904159051590615907159081590915910159111591215913159141591515916159171591815919159201592115922159231592415925159261592715928159291593015931159321593315934159351593615937159381593915940159411594215943159441594515946159471594815949159501595115952159531595415955159561595715958159591596015961159621596315964159651596615967159681596915970159711597215973159741597515976159771597815979159801598115982159831598415985159861598715988159891599015991159921599315994159951599615997159981599916000160011600216003160041600516006160071600816009160101601116012160131601416015160161601716018160191602016021160221602316024160251602616027160281602916030160311603216033160341603516036160371603816039160401604116042160431604416045160461604716048160491605016051160521605316054160551605616057160581605916060160611606216063160641606516066160671606816069160701607116072160731607416075160761607716078160791608016081160821608316084160851608616087160881608916090160911609216093160941609516096160971609816099161001610116102161031610416105161061610716108161091611016111161121611316114161151611616117161181611916120161211612216123161241612516126161271612816129161301613116132161331613416135161361613716138161391614016141161421614316144161451614616147161481614916150161511615216153161541615516156161571615816159161601616116162161631616416165161661616716168161691617016171161721617316174161751617616177161781617916180161811618216183161841618516186161871618816189161901619116192161931619416195161961619716198161991620016201162021620316204162051620616207162081620916210162111621216213162141621516216162171621816219162201622116222162231622416225162261622716228162291623016231162321623316234162351623616237162381623916240162411624216243162441624516246162471624816249162501625116252162531625416255162561625716258162591626016261162621626316264162651626616267162681626916270162711627216273162741627516276162771627816279162801628116282162831628416285162861628716288162891629016291162921629316294162951629616297162981629916300163011630216303163041630516306163071630816309163101631116312163131631416315163161631716318163191632016321163221632316324163251632616327163281632916330163311633216333163341633516336163371633816339163401634116342163431634416345163461634716348163491635016351163521635316354163551635616357163581635916360163611636216363163641636516366163671636816369163701637116372163731637416375163761637716378163791638016381163821638316384163851638616387163881638916390163911639216393163941639516396163971639816399164001640116402164031640416405164061640716408164091641016411164121641316414164151641616417164181641916420164211642216423164241642516426164271642816429164301643116432164331643416435164361643716438164391644016441164421644316444164451644616447164481644916450164511645216453164541645516456164571645816459164601646116462164631646416465164661646716468164691647016471164721647316474164751647616477164781647916480164811648216483164841648516486164871648816489164901649116492164931649416495164961649716498164991650016501165021650316504165051650616507165081650916510165111651216513165141651516516165171651816519165201652116522165231652416525165261652716528165291653016531165321653316534165351653616537165381653916540165411654216543165441654516546165471654816549165501655116552165531655416555165561655716558165591656016561165621656316564165651656616567165681656916570165711657216573165741657516576165771657816579165801658116582165831658416585165861658716588165891659016591165921659316594165951659616597165981659916600166011660216603166041660516606166071660816609166101661116612166131661416615166161661716618166191662016621166221662316624166251662616627166281662916630166311663216633166341663516636166371663816639166401664116642166431664416645166461664716648166491665016651166521665316654166551665616657166581665916660166611666216663166641666516666166671666816669166701667116672166731667416675166761667716678166791668016681166821668316684166851668616687166881668916690166911669216693166941669516696166971669816699167001670116702167031670416705167061670716708167091671016711167121671316714167151671616717167181671916720167211672216723167241672516726167271672816729167301673116732167331673416735167361673716738167391674016741167421674316744167451674616747167481674916750167511675216753167541675516756167571675816759167601676116762167631676416765167661676716768167691677016771167721677316774167751677616777167781677916780167811678216783167841678516786167871678816789167901679116792167931679416795167961679716798167991680016801168021680316804168051680616807168081680916810168111681216813168141681516816168171681816819168201682116822168231682416825168261682716828168291683016831168321683316834168351683616837168381683916840168411684216843168441684516846168471684816849168501685116852168531685416855168561685716858168591686016861168621686316864168651686616867168681686916870168711687216873168741687516876168771687816879168801688116882168831688416885168861688716888168891689016891168921689316894168951689616897168981689916900169011690216903169041690516906169071690816909169101691116912169131691416915169161691716918169191692016921169221692316924169251692616927169281692916930169311693216933169341693516936169371693816939169401694116942169431694416945169461694716948169491695016951169521695316954169551695616957169581695916960169611696216963169641696516966169671696816969169701697116972169731697416975169761697716978169791698016981169821698316984169851698616987169881698916990169911699216993169941699516996169971699816999170001700117002170031700417005170061700717008170091701017011170121701317014170151701617017170181701917020170211702217023170241702517026170271702817029170301703117032170331703417035170361703717038170391704017041170421704317044170451704617047170481704917050170511705217053170541705517056170571705817059170601706117062170631706417065170661706717068170691707017071170721707317074170751707617077170781707917080170811708217083170841708517086170871708817089170901709117092170931709417095170961709717098170991710017101171021710317104171051710617107171081710917110171111711217113171141711517116171171711817119171201712117122171231712417125171261712717128171291713017131171321713317134171351713617137171381713917140171411714217143171441714517146171471714817149171501715117152171531715417155171561715717158171591716017161171621716317164171651716617167171681716917170171711717217173171741717517176171771717817179171801718117182171831718417185171861718717188171891719017191171921719317194171951719617197171981719917200172011720217203172041720517206172071720817209172101721117212172131721417215172161721717218172191722017221172221722317224172251722617227172281722917230172311723217233172341723517236172371723817239172401724117242172431724417245172461724717248172491725017251172521725317254172551725617257172581725917260172611726217263172641726517266172671726817269172701727117272172731727417275172761727717278172791728017281172821728317284172851728617287172881728917290172911729217293172941729517296172971729817299173001730117302173031730417305173061730717308173091731017311173121731317314173151731617317173181731917320173211732217323173241732517326173271732817329173301733117332173331733417335173361733717338173391734017341173421734317344173451734617347173481734917350173511735217353173541735517356173571735817359173601736117362173631736417365173661736717368173691737017371173721737317374173751737617377173781737917380173811738217383173841738517386173871738817389173901739117392173931739417395173961739717398173991740017401174021740317404174051740617407174081740917410174111741217413174141741517416174171741817419174201742117422174231742417425174261742717428174291743017431174321743317434174351743617437174381743917440174411744217443174441744517446174471744817449174501745117452174531745417455174561745717458174591746017461174621746317464174651746617467174681746917470174711747217473174741747517476174771747817479174801748117482174831748417485174861748717488174891749017491174921749317494174951749617497174981749917500175011750217503175041750517506175071750817509175101751117512175131751417515175161751717518175191752017521175221752317524175251752617527175281752917530175311753217533175341753517536175371753817539175401754117542175431754417545175461754717548175491755017551175521755317554175551755617557175581755917560175611756217563175641756517566175671756817569175701757117572175731757417575175761757717578175791758017581175821758317584175851758617587175881758917590175911759217593175941759517596175971759817599176001760117602176031760417605176061760717608176091761017611176121761317614176151761617617176181761917620176211762217623176241762517626176271762817629176301763117632176331763417635176361763717638176391764017641176421764317644176451764617647176481764917650176511765217653176541765517656176571765817659176601766117662176631766417665176661766717668176691767017671176721767317674176751767617677176781767917680176811768217683176841768517686176871768817689176901769117692176931769417695176961769717698176991770017701177021770317704177051770617707177081770917710177111771217713177141771517716177171771817719177201772117722177231772417725177261772717728177291773017731177321773317734177351773617737177381773917740177411774217743177441774517746177471774817749177501775117752177531775417755177561775717758177591776017761177621776317764177651776617767177681776917770177711777217773177741777517776177771777817779177801778117782177831778417785177861778717788177891779017791177921779317794177951779617797177981779917800178011780217803178041780517806178071780817809178101781117812178131781417815178161781717818178191782017821178221782317824178251782617827178281782917830178311783217833178341783517836178371783817839178401784117842178431784417845178461784717848178491785017851178521785317854178551785617857178581785917860178611786217863178641786517866178671786817869178701787117872178731787417875178761787717878178791788017881178821788317884178851788617887178881788917890178911789217893178941789517896178971789817899179001790117902179031790417905179061790717908179091791017911179121791317914179151791617917179181791917920179211792217923179241792517926179271792817929179301793117932179331793417935179361793717938179391794017941179421794317944179451794617947179481794917950179511795217953179541795517956179571795817959179601796117962179631796417965179661796717968179691797017971179721797317974179751797617977179781797917980179811798217983179841798517986179871798817989179901799117992179931799417995179961799717998179991800018001180021800318004180051800618007180081800918010180111801218013180141801518016180171801818019180201802118022180231802418025180261802718028180291803018031180321803318034180351803618037180381803918040180411804218043180441804518046180471804818049180501805118052180531805418055180561805718058180591806018061180621806318064180651806618067180681806918070180711807218073180741807518076180771807818079180801808118082180831808418085180861808718088180891809018091180921809318094180951809618097180981809918100181011810218103181041810518106181071810818109181101811118112181131811418115181161811718118181191812018121181221812318124181251812618127181281812918130181311813218133181341813518136181371813818139181401814118142181431814418145181461814718148181491815018151181521815318154181551815618157181581815918160181611816218163181641816518166181671816818169181701817118172181731817418175181761817718178181791818018181181821818318184181851818618187181881818918190181911819218193181941819518196181971819818199182001820118202182031820418205182061820718208182091821018211182121821318214182151821618217182181821918220182211822218223182241822518226182271822818229182301823118232182331823418235182361823718238182391824018241182421824318244182451824618247182481824918250182511825218253182541825518256182571825818259182601826118262182631826418265182661826718268182691827018271182721827318274182751827618277182781827918280182811828218283182841828518286182871828818289182901829118292182931829418295182961829718298182991830018301183021830318304183051830618307183081830918310183111831218313183141831518316183171831818319183201832118322183231832418325183261832718328183291833018331183321833318334183351833618337183381833918340183411834218343183441834518346183471834818349183501835118352183531835418355183561835718358183591836018361183621836318364183651836618367183681836918370183711837218373183741837518376183771837818379183801838118382183831838418385183861838718388183891839018391183921839318394183951839618397183981839918400184011840218403184041840518406184071840818409184101841118412184131841418415184161841718418184191842018421184221842318424184251842618427184281842918430184311843218433184341843518436184371843818439184401844118442184431844418445184461844718448184491845018451184521845318454184551845618457184581845918460184611846218463184641846518466184671846818469184701847118472184731847418475184761847718478184791848018481184821848318484184851848618487184881848918490184911849218493184941849518496184971849818499185001850118502185031850418505185061850718508185091851018511185121851318514185151851618517185181851918520185211852218523185241852518526185271852818529185301853118532185331853418535185361853718538185391854018541185421854318544185451854618547185481854918550185511855218553185541855518556185571855818559185601856118562185631856418565185661856718568185691857018571185721857318574185751857618577185781857918580185811858218583185841858518586185871858818589185901859118592185931859418595185961859718598185991860018601186021860318604186051860618607186081860918610186111861218613186141861518616186171861818619186201862118622186231862418625186261862718628186291863018631186321863318634186351863618637186381863918640186411864218643186441864518646186471864818649186501865118652186531865418655186561865718658186591866018661186621866318664186651866618667186681866918670186711867218673186741867518676186771867818679186801868118682186831868418685186861868718688186891869018691186921869318694186951869618697186981869918700187011870218703187041870518706187071870818709187101871118712187131871418715187161871718718187191872018721187221872318724187251872618727187281872918730187311873218733187341873518736187371873818739187401874118742187431874418745187461874718748187491875018751187521875318754187551875618757187581875918760187611876218763187641876518766187671876818769187701877118772187731877418775187761877718778187791878018781187821878318784187851878618787187881878918790187911879218793187941879518796187971879818799188001880118802188031880418805188061880718808188091881018811188121881318814188151881618817188181881918820188211882218823188241882518826188271882818829188301883118832188331883418835188361883718838188391884018841188421884318844188451884618847188481884918850188511885218853188541885518856188571885818859188601886118862188631886418865188661886718868188691887018871188721887318874188751887618877188781887918880188811888218883188841888518886188871888818889188901889118892188931889418895188961889718898188991890018901189021890318904189051890618907189081890918910189111891218913189141891518916189171891818919189201892118922189231892418925189261892718928189291893018931189321893318934189351893618937189381893918940189411894218943189441894518946189471894818949189501895118952189531895418955189561895718958189591896018961189621896318964189651896618967189681896918970189711897218973189741897518976189771897818979189801898118982189831898418985189861898718988189891899018991189921899318994189951899618997189981899919000190011900219003190041900519006190071900819009190101901119012190131901419015190161901719018190191902019021190221902319024190251902619027190281902919030190311903219033190341903519036190371903819039190401904119042190431904419045190461904719048190491905019051190521905319054190551905619057190581905919060190611906219063190641906519066190671906819069190701907119072190731907419075190761907719078190791908019081190821908319084190851908619087190881908919090190911909219093190941909519096190971909819099191001910119102191031910419105191061910719108191091911019111191121911319114191151911619117191181911919120191211912219123191241912519126191271912819129191301913119132191331913419135191361913719138191391914019141191421914319144191451914619147191481914919150191511915219153191541915519156191571915819159191601916119162191631916419165191661916719168191691917019171191721917319174191751917619177191781917919180191811918219183191841918519186191871918819189191901919119192191931919419195191961919719198191991920019201192021920319204192051920619207192081920919210192111921219213192141921519216192171921819219192201922119222192231922419225192261922719228192291923019231192321923319234192351923619237192381923919240192411924219243192441924519246192471924819249192501925119252192531925419255192561925719258192591926019261192621926319264192651926619267192681926919270192711927219273192741927519276192771927819279192801928119282192831928419285192861928719288192891929019291192921929319294192951929619297192981929919300193011930219303193041930519306193071930819309193101931119312193131931419315193161931719318193191932019321193221932319324193251932619327193281932919330193311933219333193341933519336193371933819339193401934119342193431934419345193461934719348193491935019351193521935319354193551935619357193581935919360193611936219363193641936519366193671936819369193701937119372193731937419375193761937719378193791938019381193821938319384193851938619387193881938919390193911939219393193941939519396193971939819399194001940119402194031940419405194061940719408194091941019411194121941319414194151941619417194181941919420194211942219423194241942519426194271942819429194301943119432194331943419435194361943719438194391944019441194421944319444194451944619447194481944919450194511945219453194541945519456194571945819459194601946119462194631946419465194661946719468194691947019471194721947319474194751947619477194781947919480194811948219483194841948519486194871948819489194901949119492194931949419495194961949719498194991950019501195021950319504195051950619507195081950919510195111951219513195141951519516195171951819519195201952119522195231952419525195261952719528195291953019531195321953319534195351953619537195381953919540195411954219543195441954519546195471954819549195501955119552195531955419555195561955719558195591956019561195621956319564195651956619567195681956919570195711957219573195741957519576195771957819579195801958119582195831958419585195861958719588195891959019591195921959319594195951959619597195981959919600196011960219603196041960519606196071960819609196101961119612196131961419615196161961719618196191962019621196221962319624196251962619627196281962919630196311963219633196341963519636196371963819639196401964119642196431964419645196461964719648196491965019651196521965319654196551965619657196581965919660196611966219663196641966519666196671966819669196701967119672196731967419675196761967719678196791968019681196821968319684196851968619687196881968919690196911969219693196941969519696196971969819699197001970119702197031970419705197061970719708197091971019711197121971319714197151971619717197181971919720197211972219723197241972519726197271972819729197301973119732197331973419735197361973719738197391974019741197421974319744197451974619747197481974919750197511975219753197541975519756197571975819759197601976119762197631976419765197661976719768197691977019771197721977319774197751977619777197781977919780197811978219783197841978519786197871978819789197901979119792197931979419795197961979719798197991980019801198021980319804198051980619807198081980919810198111981219813198141981519816198171981819819198201982119822198231982419825198261982719828198291983019831198321983319834198351983619837198381983919840198411984219843198441984519846198471984819849198501985119852198531985419855198561985719858198591986019861198621986319864198651986619867198681986919870198711987219873198741987519876198771987819879198801988119882198831988419885198861988719888198891989019891198921989319894198951989619897198981989919900199011990219903199041990519906199071990819909199101991119912199131991419915199161991719918199191992019921199221992319924199251992619927199281992919930199311993219933199341993519936199371993819939199401994119942199431994419945199461994719948199491995019951199521995319954199551995619957199581995919960199611996219963199641996519966199671996819969199701997119972199731997419975199761997719978199791998019981199821998319984199851998619987199881998919990199911999219993199941999519996199971999819999200002000120002200032000420005200062000720008200092001020011200122001320014200152001620017200182001920020200212002220023200242002520026200272002820029200302003120032200332003420035200362003720038200392004020041200422004320044200452004620047200482004920050200512005220053200542005520056200572005820059200602006120062200632006420065200662006720068200692007020071200722007320074200752007620077200782007920080200812008220083200842008520086200872008820089200902009120092200932009420095200962009720098200992010020101201022010320104201052010620107201082010920110201112011220113201142011520116201172011820119201202012120122201232012420125201262012720128201292013020131201322013320134201352013620137201382013920140201412014220143201442014520146201472014820149201502015120152201532015420155201562015720158201592016020161201622016320164201652016620167201682016920170201712017220173201742017520176201772017820179201802018120182201832018420185201862018720188201892019020191201922019320194201952019620197201982019920200202012020220203202042020520206202072020820209202102021120212202132021420215202162021720218202192022020221202222022320224202252022620227202282022920230202312023220233202342023520236202372023820239202402024120242202432024420245202462024720248202492025020251202522025320254202552025620257202582025920260202612026220263202642026520266202672026820269202702027120272202732027420275202762027720278202792028020281202822028320284202852028620287202882028920290202912029220293202942029520296202972029820299203002030120302203032030420305203062030720308203092031020311203122031320314203152031620317203182031920320203212032220323203242032520326203272032820329203302033120332203332033420335203362033720338203392034020341203422034320344203452034620347203482034920350203512035220353203542035520356203572035820359203602036120362203632036420365203662036720368203692037020371203722037320374203752037620377203782037920380203812038220383203842038520386203872038820389203902039120392203932039420395203962039720398203992040020401204022040320404204052040620407204082040920410204112041220413204142041520416204172041820419204202042120422204232042420425204262042720428204292043020431204322043320434204352043620437204382043920440204412044220443204442044520446204472044820449204502045120452204532045420455204562045720458204592046020461204622046320464204652046620467204682046920470204712047220473204742047520476204772047820479204802048120482204832048420485204862048720488204892049020491204922049320494204952049620497204982049920500205012050220503205042050520506205072050820509205102051120512205132051420515205162051720518205192052020521205222052320524205252052620527205282052920530205312053220533205342053520536205372053820539205402054120542205432054420545205462054720548205492055020551205522055320554205552055620557205582055920560205612056220563205642056520566205672056820569205702057120572205732057420575205762057720578205792058020581205822058320584205852058620587205882058920590205912059220593205942059520596205972059820599206002060120602206032060420605206062060720608206092061020611206122061320614206152061620617206182061920620206212062220623206242062520626206272062820629206302063120632206332063420635206362063720638206392064020641206422064320644206452064620647206482064920650206512065220653206542065520656206572065820659206602066120662206632066420665206662066720668206692067020671206722067320674206752067620677206782067920680206812068220683206842068520686206872068820689206902069120692206932069420695206962069720698206992070020701207022070320704207052070620707207082070920710207112071220713207142071520716207172071820719207202072120722207232072420725207262072720728207292073020731207322073320734207352073620737207382073920740207412074220743207442074520746207472074820749207502075120752207532075420755207562075720758207592076020761207622076320764207652076620767207682076920770207712077220773207742077520776207772077820779207802078120782207832078420785207862078720788207892079020791207922079320794207952079620797207982079920800208012080220803208042080520806208072080820809208102081120812208132081420815208162081720818208192082020821208222082320824208252082620827208282082920830208312083220833208342083520836208372083820839208402084120842208432084420845208462084720848208492085020851208522085320854208552085620857208582085920860208612086220863208642086520866208672086820869208702087120872208732087420875208762087720878208792088020881208822088320884208852088620887208882088920890208912089220893208942089520896208972089820899209002090120902209032090420905209062090720908209092091020911209122091320914209152091620917209182091920920209212092220923209242092520926209272092820929209302093120932209332093420935209362093720938209392094020941209422094320944209452094620947209482094920950209512095220953209542095520956209572095820959209602096120962209632096420965209662096720968209692097020971209722097320974209752097620977209782097920980209812098220983209842098520986209872098820989209902099120992209932099420995209962099720998209992100021001210022100321004210052100621007210082100921010210112101221013210142101521016210172101821019210202102121022210232102421025210262102721028210292103021031210322103321034210352103621037210382103921040210412104221043210442104521046210472104821049210502105121052210532105421055210562105721058210592106021061210622106321064210652106621067210682106921070210712107221073210742107521076210772107821079210802108121082210832108421085210862108721088210892109021091210922109321094210952109621097210982109921100211012110221103211042110521106211072110821109211102111121112211132111421115211162111721118211192112021121211222112321124211252112621127211282112921130211312113221133211342113521136211372113821139211402114121142211432114421145211462114721148211492115021151211522115321154211552115621157211582115921160211612116221163211642116521166211672116821169211702117121172211732117421175211762117721178211792118021181211822118321184211852118621187211882118921190211912119221193211942119521196211972119821199212002120121202212032120421205212062120721208212092121021211212122121321214212152121621217212182121921220212212122221223212242122521226212272122821229212302123121232212332123421235212362123721238212392124021241212422124321244212452124621247212482124921250212512125221253212542125521256212572125821259212602126121262212632126421265212662126721268212692127021271212722127321274212752127621277212782127921280212812128221283212842128521286212872128821289212902129121292212932129421295212962129721298212992130021301213022130321304213052130621307213082130921310213112131221313213142131521316213172131821319213202132121322213232132421325213262132721328213292133021331213322133321334213352133621337213382133921340213412134221343213442134521346213472134821349213502135121352213532135421355213562135721358213592136021361213622136321364213652136621367213682136921370213712137221373213742137521376213772137821379213802138121382213832138421385213862138721388213892139021391213922139321394213952139621397213982139921400214012140221403214042140521406214072140821409214102141121412214132141421415214162141721418214192142021421214222142321424214252142621427214282142921430214312143221433214342143521436214372143821439214402144121442214432144421445214462144721448214492145021451214522145321454214552145621457214582145921460214612146221463214642146521466214672146821469214702147121472214732147421475214762147721478214792148021481214822148321484214852148621487214882148921490214912149221493214942149521496214972149821499215002150121502215032150421505215062150721508215092151021511215122151321514215152151621517215182151921520215212152221523215242152521526215272152821529215302153121532215332153421535215362153721538215392154021541215422154321544215452154621547215482154921550215512155221553215542155521556215572155821559215602156121562215632156421565215662156721568215692157021571215722157321574215752157621577215782157921580215812158221583215842158521586215872158821589215902159121592215932159421595215962159721598215992160021601216022160321604216052160621607216082160921610216112161221613216142161521616216172161821619216202162121622216232162421625216262162721628216292163021631216322163321634216352163621637216382163921640216412164221643216442164521646216472164821649216502165121652216532165421655216562165721658216592166021661216622166321664216652166621667216682166921670216712167221673216742167521676216772167821679216802168121682216832168421685216862168721688216892169021691216922169321694216952169621697216982169921700217012170221703217042170521706217072170821709217102171121712217132171421715217162171721718217192172021721217222172321724217252172621727217282172921730217312173221733217342173521736217372173821739217402174121742217432174421745217462174721748217492175021751217522175321754217552175621757217582175921760217612176221763217642176521766217672176821769217702177121772217732177421775217762177721778217792178021781217822178321784217852178621787217882178921790217912179221793217942179521796217972179821799218002180121802218032180421805218062180721808218092181021811218122181321814218152181621817218182181921820218212182221823218242182521826218272182821829218302183121832218332183421835218362183721838218392184021841218422184321844218452184621847218482184921850218512185221853218542185521856218572185821859218602186121862218632186421865218662186721868218692187021871218722187321874218752187621877218782187921880218812188221883218842188521886218872188821889218902189121892218932189421895218962189721898218992190021901219022190321904219052190621907219082190921910219112191221913219142191521916219172191821919219202192121922219232192421925219262192721928219292193021931219322193321934219352193621937219382193921940219412194221943219442194521946219472194821949219502195121952219532195421955219562195721958219592196021961219622196321964219652196621967219682196921970219712197221973219742197521976219772197821979219802198121982219832198421985219862198721988219892199021991219922199321994219952199621997219982199922000220012200222003220042200522006220072200822009220102201122012220132201422015220162201722018220192202022021220222202322024220252202622027220282202922030220312203222033220342203522036220372203822039220402204122042220432204422045220462204722048220492205022051220522205322054220552205622057220582205922060220612206222063220642206522066220672206822069220702207122072220732207422075220762207722078220792208022081220822208322084220852208622087220882208922090220912209222093220942209522096220972209822099221002210122102221032210422105221062210722108221092211022111221122211322114221152211622117221182211922120221212212222123221242212522126221272212822129221302213122132221332213422135221362213722138221392214022141221422214322144221452214622147221482214922150221512215222153221542215522156221572215822159221602216122162221632216422165221662216722168221692217022171221722217322174221752217622177221782217922180221812218222183221842218522186221872218822189221902219122192221932219422195221962219722198221992220022201222022220322204222052220622207222082220922210222112221222213222142221522216222172221822219222202222122222222232222422225222262222722228222292223022231222322223322234222352223622237222382223922240222412224222243222442224522246222472224822249222502225122252222532225422255222562225722258222592226022261222622226322264222652226622267222682226922270222712227222273222742227522276222772227822279222802228122282222832228422285222862228722288222892229022291222922229322294222952229622297222982229922300223012230222303223042230522306223072230822309223102231122312223132231422315223162231722318223192232022321223222232322324223252232622327223282232922330223312233222333223342233522336223372233822339223402234122342223432234422345223462234722348223492235022351223522235322354223552235622357223582235922360223612236222363223642236522366223672236822369223702237122372223732237422375223762237722378223792238022381223822238322384223852238622387223882238922390223912239222393223942239522396223972239822399224002240122402224032240422405224062240722408224092241022411224122241322414224152241622417224182241922420224212242222423224242242522426224272242822429224302243122432224332243422435224362243722438224392244022441224422244322444224452244622447224482244922450224512245222453224542245522456224572245822459224602246122462224632246422465224662246722468224692247022471224722247322474224752247622477224782247922480224812248222483224842248522486224872248822489224902249122492224932249422495224962249722498224992250022501225022250322504225052250622507225082250922510225112251222513225142251522516225172251822519225202252122522225232252422525225262252722528225292253022531225322253322534225352253622537225382253922540225412254222543225442254522546225472254822549225502255122552225532255422555225562255722558225592256022561225622256322564225652256622567225682256922570225712257222573225742257522576225772257822579225802258122582225832258422585225862258722588225892259022591225922259322594225952259622597225982259922600226012260222603226042260522606226072260822609226102261122612226132261422615226162261722618226192262022621226222262322624226252262622627226282262922630226312263222633226342263522636226372263822639226402264122642226432264422645226462264722648226492265022651226522265322654226552265622657226582265922660226612266222663226642266522666226672266822669226702267122672226732267422675226762267722678226792268022681226822268322684226852268622687226882268922690226912269222693226942269522696226972269822699227002270122702227032270422705227062270722708227092271022711227122271322714227152271622717227182271922720227212272222723227242272522726227272272822729227302273122732227332273422735227362273722738227392274022741227422274322744227452274622747227482274922750227512275222753227542275522756227572275822759227602276122762227632276422765227662276722768227692277022771227722277322774227752277622777227782277922780227812278222783227842278522786227872278822789227902279122792227932279422795227962279722798227992280022801228022280322804228052280622807228082280922810228112281222813228142281522816228172281822819228202282122822228232282422825228262282722828228292283022831228322283322834228352283622837228382283922840228412284222843228442284522846228472284822849228502285122852228532285422855228562285722858228592286022861228622286322864228652286622867228682286922870228712287222873228742287522876228772287822879228802288122882228832288422885228862288722888228892289022891228922289322894228952289622897228982289922900229012290222903229042290522906229072290822909229102291122912229132291422915229162291722918229192292022921229222292322924229252292622927229282292922930229312293222933229342293522936229372293822939229402294122942229432294422945229462294722948229492295022951229522295322954229552295622957229582295922960229612296222963229642296522966229672296822969229702297122972229732297422975229762297722978229792298022981229822298322984229852298622987229882298922990229912299222993229942299522996229972299822999230002300123002230032300423005230062300723008230092301023011230122301323014230152301623017230182301923020230212302223023230242302523026230272302823029230302303123032230332303423035230362303723038230392304023041230422304323044230452304623047230482304923050230512305223053230542305523056230572305823059230602306123062230632306423065230662306723068230692307023071230722307323074230752307623077230782307923080230812308223083230842308523086230872308823089230902309123092230932309423095230962309723098230992310023101231022310323104231052310623107231082310923110231112311223113231142311523116231172311823119231202312123122231232312423125231262312723128231292313023131231322313323134231352313623137231382313923140231412314223143231442314523146231472314823149231502315123152231532315423155231562315723158231592316023161231622316323164231652316623167231682316923170231712317223173231742317523176231772317823179231802318123182231832318423185231862318723188231892319023191231922319323194231952319623197231982319923200232012320223203232042320523206232072320823209232102321123212232132321423215232162321723218232192322023221232222322323224232252322623227232282322923230232312323223233232342323523236232372323823239232402324123242232432324423245232462324723248232492325023251232522325323254232552325623257232582325923260232612326223263232642326523266232672326823269232702327123272232732327423275232762327723278232792328023281232822328323284232852328623287232882328923290232912329223293232942329523296232972329823299233002330123302233032330423305233062330723308233092331023311233122331323314233152331623317233182331923320233212332223323233242332523326233272332823329233302333123332233332333423335233362333723338233392334023341233422334323344233452334623347233482334923350233512335223353233542335523356233572335823359233602336123362233632336423365233662336723368233692337023371233722337323374233752337623377233782337923380233812338223383233842338523386233872338823389233902339123392233932339423395233962339723398233992340023401234022340323404234052340623407234082340923410234112341223413234142341523416234172341823419234202342123422234232342423425234262342723428234292343023431234322343323434234352343623437234382343923440234412344223443234442344523446234472344823449234502345123452234532345423455234562345723458234592346023461234622346323464234652346623467234682346923470234712347223473234742347523476234772347823479234802348123482234832348423485234862348723488234892349023491234922349323494234952349623497234982349923500235012350223503235042350523506235072350823509235102351123512235132351423515235162351723518235192352023521235222352323524235252352623527235282352923530235312353223533235342353523536235372353823539235402354123542235432354423545235462354723548235492355023551235522355323554235552355623557235582355923560235612356223563235642356523566235672356823569235702357123572235732357423575235762357723578235792358023581235822358323584235852358623587235882358923590235912359223593235942359523596235972359823599236002360123602236032360423605236062360723608236092361023611236122361323614236152361623617236182361923620236212362223623236242362523626236272362823629236302363123632236332363423635236362363723638236392364023641236422364323644236452364623647236482364923650236512365223653236542365523656236572365823659236602366123662236632366423665236662366723668236692367023671236722367323674236752367623677236782367923680236812368223683236842368523686236872368823689236902369123692236932369423695236962369723698236992370023701237022370323704237052370623707237082370923710237112371223713237142371523716237172371823719237202372123722237232372423725237262372723728237292373023731237322373323734237352373623737237382373923740237412374223743237442374523746237472374823749237502375123752237532375423755237562375723758237592376023761237622376323764237652376623767237682376923770237712377223773237742377523776237772377823779237802378123782237832378423785237862378723788237892379023791237922379323794237952379623797237982379923800238012380223803238042380523806238072380823809238102381123812238132381423815238162381723818238192382023821238222382323824238252382623827238282382923830238312383223833238342383523836238372383823839238402384123842238432384423845238462384723848238492385023851238522385323854238552385623857238582385923860238612386223863238642386523866238672386823869238702387123872238732387423875238762387723878238792388023881238822388323884238852388623887238882388923890238912389223893238942389523896238972389823899239002390123902239032390423905239062390723908239092391023911239122391323914239152391623917239182391923920239212392223923239242392523926239272392823929239302393123932239332393423935239362393723938239392394023941239422394323944239452394623947239482394923950239512395223953239542395523956239572395823959239602396123962239632396423965239662396723968239692397023971239722397323974239752397623977239782397923980239812398223983239842398523986239872398823989239902399123992239932399423995239962399723998239992400024001240022400324004240052400624007240082400924010240112401224013240142401524016240172401824019240202402124022240232402424025240262402724028240292403024031240322403324034240352403624037240382403924040240412404224043240442404524046240472404824049240502405124052240532405424055240562405724058240592406024061240622406324064240652406624067240682406924070240712407224073240742407524076240772407824079240802408124082240832408424085240862408724088240892409024091240922409324094240952409624097240982409924100241012410224103241042410524106241072410824109241102411124112241132411424115241162411724118241192412024121241222412324124241252412624127241282412924130241312413224133241342413524136241372413824139241402414124142241432414424145241462414724148241492415024151241522415324154241552415624157241582415924160241612416224163241642416524166241672416824169241702417124172241732417424175241762417724178241792418024181241822418324184241852418624187241882418924190241912419224193241942419524196241972419824199242002420124202242032420424205242062420724208242092421024211242122421324214242152421624217242182421924220242212422224223242242422524226242272422824229242302423124232242332423424235242362423724238242392424024241242422424324244242452424624247242482424924250242512425224253242542425524256242572425824259242602426124262242632426424265242662426724268242692427024271242722427324274242752427624277242782427924280242812428224283242842428524286242872428824289242902429124292242932429424295242962429724298242992430024301243022430324304243052430624307243082430924310243112431224313243142431524316243172431824319243202432124322243232432424325243262432724328243292433024331243322433324334243352433624337243382433924340243412434224343243442434524346243472434824349243502435124352243532435424355243562435724358243592436024361243622436324364243652436624367243682436924370243712437224373243742437524376243772437824379243802438124382243832438424385243862438724388243892439024391243922439324394243952439624397243982439924400244012440224403244042440524406244072440824409244102441124412244132441424415244162441724418244192442024421244222442324424244252442624427244282442924430244312443224433244342443524436244372443824439244402444124442244432444424445244462444724448244492445024451244522445324454244552445624457244582445924460244612446224463244642446524466244672446824469244702447124472244732447424475244762447724478244792448024481244822448324484244852448624487244882448924490244912449224493244942449524496244972449824499245002450124502245032450424505245062450724508245092451024511245122451324514245152451624517245182451924520245212452224523245242452524526245272452824529245302453124532245332453424535245362453724538245392454024541245422454324544245452454624547245482454924550245512455224553245542455524556245572455824559245602456124562245632456424565245662456724568245692457024571245722457324574245752457624577245782457924580245812458224583245842458524586245872458824589245902459124592245932459424595245962459724598245992460024601246022460324604246052460624607246082460924610246112461224613246142461524616246172461824619246202462124622246232462424625246262462724628246292463024631246322463324634246352463624637246382463924640246412464224643246442464524646246472464824649246502465124652246532465424655246562465724658246592466024661246622466324664246652466624667246682466924670246712467224673246742467524676246772467824679246802468124682246832468424685246862468724688246892469024691246922469324694246952469624697246982469924700247012470224703247042470524706247072470824709247102471124712247132471424715247162471724718247192472024721247222472324724247252472624727247282472924730247312473224733247342473524736247372473824739247402474124742247432474424745247462474724748247492475024751247522475324754247552475624757247582475924760247612476224763247642476524766247672476824769247702477124772247732477424775247762477724778247792478024781247822478324784247852478624787247882478924790247912479224793247942479524796247972479824799248002480124802248032480424805248062480724808248092481024811248122481324814248152481624817248182481924820248212482224823248242482524826248272482824829248302483124832248332483424835248362483724838248392484024841248422484324844248452484624847248482484924850248512485224853248542485524856248572485824859248602486124862248632486424865248662486724868248692487024871248722487324874248752487624877248782487924880248812488224883248842488524886248872488824889248902489124892248932489424895248962489724898248992490024901249022490324904249052490624907249082490924910249112491224913249142491524916249172491824919249202492124922249232492424925249262492724928249292493024931249322493324934249352493624937249382493924940249412494224943249442494524946249472494824949249502495124952249532495424955249562495724958249592496024961249622496324964249652496624967249682496924970249712497224973249742497524976249772497824979249802498124982249832498424985249862498724988249892499024991249922499324994249952499624997249982499925000250012500225003250042500525006250072500825009250102501125012250132501425015250162501725018250192502025021250222502325024250252502625027250282502925030250312503225033250342503525036250372503825039250402504125042250432504425045250462504725048250492505025051250522505325054250552505625057250582505925060250612506225063250642506525066250672506825069250702507125072250732507425075250762507725078250792508025081250822508325084250852508625087250882508925090250912509225093250942509525096250972509825099251002510125102251032510425105251062510725108251092511025111251122511325114251152511625117251182511925120251212512225123251242512525126251272512825129251302513125132251332513425135251362513725138251392514025141251422514325144251452514625147251482514925150251512515225153251542515525156251572515825159251602516125162251632516425165251662516725168251692517025171251722517325174251752517625177251782517925180251812518225183251842518525186251872518825189251902519125192251932519425195251962519725198251992520025201252022520325204252052520625207252082520925210252112521225213252142521525216252172521825219252202522125222252232522425225252262522725228252292523025231252322523325234252352523625237252382523925240252412524225243252442524525246252472524825249252502525125252252532525425255252562525725258252592526025261252622526325264252652526625267252682526925270252712527225273252742527525276252772527825279252802528125282252832528425285252862528725288252892529025291252922529325294252952529625297252982529925300253012530225303253042530525306253072530825309253102531125312253132531425315253162531725318253192532025321253222532325324253252532625327253282532925330253312533225333253342533525336253372533825339253402534125342253432534425345253462534725348253492535025351253522535325354253552535625357253582535925360253612536225363253642536525366253672536825369253702537125372253732537425375253762537725378253792538025381253822538325384253852538625387253882538925390253912539225393253942539525396253972539825399254002540125402254032540425405254062540725408254092541025411254122541325414254152541625417254182541925420254212542225423254242542525426254272542825429254302543125432254332543425435254362543725438254392544025441254422544325444254452544625447254482544925450254512545225453254542545525456254572545825459254602546125462254632546425465254662546725468254692547025471254722547325474254752547625477254782547925480254812548225483254842548525486254872548825489254902549125492254932549425495254962549725498254992550025501255022550325504255052550625507255082550925510255112551225513255142551525516255172551825519255202552125522255232552425525255262552725528255292553025531255322553325534255352553625537255382553925540255412554225543255442554525546255472554825549255502555125552255532555425555255562555725558255592556025561255622556325564255652556625567255682556925570255712557225573255742557525576255772557825579255802558125582255832558425585255862558725588255892559025591255922559325594255952559625597255982559925600256012560225603256042560525606256072560825609256102561125612256132561425615256162561725618256192562025621256222562325624256252562625627256282562925630256312563225633256342563525636256372563825639256402564125642256432564425645256462564725648256492565025651256522565325654256552565625657256582565925660256612566225663256642566525666256672566825669256702567125672256732567425675256762567725678256792568025681256822568325684256852568625687256882568925690256912569225693256942569525696256972569825699257002570125702257032570425705257062570725708257092571025711257122571325714257152571625717257182571925720257212572225723257242572525726257272572825729257302573125732257332573425735257362573725738257392574025741257422574325744257452574625747257482574925750257512575225753257542575525756257572575825759257602576125762257632576425765257662576725768257692577025771257722577325774257752577625777257782577925780257812578225783257842578525786257872578825789257902579125792257932579425795257962579725798257992580025801258022580325804258052580625807258082580925810258112581225813258142581525816258172581825819258202582125822258232582425825258262582725828258292583025831258322583325834258352583625837258382583925840258412584225843258442584525846258472584825849258502585125852258532585425855258562585725858258592586025861258622586325864258652586625867258682586925870258712587225873258742587525876258772587825879258802588125882258832588425885258862588725888258892589025891258922589325894258952589625897258982589925900259012590225903259042590525906259072590825909259102591125912259132591425915259162591725918259192592025921259222592325924259252592625927259282592925930259312593225933259342593525936259372593825939259402594125942259432594425945259462594725948259492595025951259522595325954259552595625957259582595925960259612596225963259642596525966259672596825969259702597125972259732597425975259762597725978259792598025981259822598325984259852598625987259882598925990259912599225993259942599525996259972599825999260002600126002260032600426005260062600726008260092601026011260122601326014260152601626017260182601926020260212602226023260242602526026260272602826029260302603126032260332603426035260362603726038260392604026041260422604326044260452604626047260482604926050260512605226053260542605526056260572605826059260602606126062260632606426065260662606726068260692607026071260722607326074260752607626077260782607926080260812608226083260842608526086260872608826089260902609126092260932609426095260962609726098260992610026101261022610326104261052610626107261082610926110261112611226113261142611526116261172611826119261202612126122261232612426125261262612726128261292613026131261322613326134261352613626137261382613926140261412614226143261442614526146261472614826149261502615126152261532615426155261562615726158261592616026161261622616326164261652616626167261682616926170261712617226173261742617526176261772617826179261802618126182261832618426185261862618726188261892619026191261922619326194261952619626197261982619926200262012620226203262042620526206262072620826209262102621126212262132621426215262162621726218262192622026221262222622326224262252622626227262282622926230262312623226233262342623526236262372623826239262402624126242262432624426245262462624726248262492625026251262522625326254262552625626257262582625926260262612626226263262642626526266262672626826269262702627126272262732627426275262762627726278262792628026281262822628326284262852628626287262882628926290262912629226293262942629526296262972629826299263002630126302263032630426305263062630726308263092631026311263122631326314263152631626317263182631926320263212632226323263242632526326263272632826329263302633126332263332633426335263362633726338263392634026341263422634326344263452634626347263482634926350263512635226353263542635526356263572635826359263602636126362263632636426365263662636726368263692637026371263722637326374263752637626377263782637926380263812638226383263842638526386263872638826389263902639126392263932639426395263962639726398263992640026401264022640326404264052640626407264082640926410264112641226413264142641526416264172641826419264202642126422264232642426425264262642726428264292643026431264322643326434264352643626437264382643926440264412644226443264442644526446264472644826449264502645126452264532645426455264562645726458264592646026461264622646326464264652646626467264682646926470264712647226473264742647526476264772647826479264802648126482264832648426485264862648726488264892649026491264922649326494264952649626497264982649926500265012650226503265042650526506265072650826509265102651126512265132651426515265162651726518265192652026521265222652326524265252652626527265282652926530265312653226533265342653526536265372653826539265402654126542265432654426545265462654726548265492655026551265522655326554265552655626557265582655926560265612656226563265642656526566265672656826569265702657126572265732657426575265762657726578265792658026581265822658326584265852658626587265882658926590265912659226593265942659526596265972659826599266002660126602266032660426605266062660726608266092661026611266122661326614266152661626617266182661926620266212662226623266242662526626266272662826629266302663126632266332663426635266362663726638266392664026641266422664326644266452664626647266482664926650266512665226653266542665526656266572665826659266602666126662266632666426665266662666726668266692667026671266722667326674266752667626677266782667926680266812668226683266842668526686266872668826689266902669126692266932669426695266962669726698266992670026701267022670326704267052670626707267082670926710267112671226713267142671526716267172671826719267202672126722267232672426725267262672726728267292673026731267322673326734267352673626737267382673926740267412674226743267442674526746267472674826749267502675126752267532675426755267562675726758267592676026761267622676326764267652676626767267682676926770267712677226773267742677526776267772677826779267802678126782267832678426785267862678726788267892679026791267922679326794267952679626797267982679926800268012680226803268042680526806268072680826809268102681126812268132681426815268162681726818268192682026821268222682326824268252682626827268282682926830268312683226833268342683526836268372683826839268402684126842268432684426845268462684726848268492685026851268522685326854268552685626857268582685926860268612686226863268642686526866268672686826869268702687126872268732687426875268762687726878268792688026881268822688326884268852688626887268882688926890268912689226893268942689526896268972689826899269002690126902269032690426905269062690726908269092691026911269122691326914269152691626917269182691926920269212692226923269242692526926269272692826929269302693126932269332693426935269362693726938269392694026941269422694326944269452694626947269482694926950269512695226953269542695526956269572695826959269602696126962269632696426965269662696726968269692697026971269722697326974269752697626977269782697926980269812698226983269842698526986269872698826989269902699126992269932699426995269962699726998269992700027001270022700327004270052700627007270082700927010270112701227013270142701527016270172701827019270202702127022270232702427025270262702727028270292703027031270322703327034270352703627037270382703927040270412704227043270442704527046270472704827049270502705127052270532705427055270562705727058270592706027061270622706327064270652706627067270682706927070270712707227073270742707527076270772707827079270802708127082270832708427085270862708727088270892709027091270922709327094270952709627097270982709927100271012710227103271042710527106271072710827109271102711127112271132711427115271162711727118271192712027121271222712327124271252712627127271282712927130271312713227133271342713527136271372713827139271402714127142271432714427145271462714727148271492715027151271522715327154271552715627157271582715927160271612716227163271642716527166271672716827169271702717127172271732717427175271762717727178271792718027181271822718327184271852718627187271882718927190271912719227193271942719527196271972719827199272002720127202272032720427205272062720727208272092721027211272122721327214272152721627217272182721927220272212722227223272242722527226272272722827229272302723127232272332723427235272362723727238272392724027241272422724327244272452724627247272482724927250272512725227253272542725527256272572725827259272602726127262272632726427265272662726727268272692727027271272722727327274272752727627277272782727927280272812728227283272842728527286272872728827289272902729127292272932729427295272962729727298272992730027301273022730327304273052730627307273082730927310273112731227313273142731527316273172731827319273202732127322273232732427325273262732727328273292733027331273322733327334273352733627337273382733927340273412734227343273442734527346273472734827349273502735127352273532735427355273562735727358273592736027361273622736327364273652736627367273682736927370273712737227373273742737527376273772737827379273802738127382273832738427385273862738727388273892739027391273922739327394273952739627397273982739927400274012740227403274042740527406274072740827409274102741127412274132741427415274162741727418274192742027421274222742327424274252742627427274282742927430274312743227433274342743527436274372743827439274402744127442274432744427445274462744727448274492745027451274522745327454274552745627457274582745927460274612746227463274642746527466274672746827469274702747127472274732747427475274762747727478274792748027481274822748327484274852748627487274882748927490274912749227493274942749527496274972749827499275002750127502275032750427505275062750727508275092751027511275122751327514275152751627517275182751927520275212752227523275242752527526275272752827529275302753127532275332753427535275362753727538275392754027541275422754327544275452754627547275482754927550275512755227553275542755527556275572755827559275602756127562275632756427565275662756727568275692757027571275722757327574275752757627577275782757927580275812758227583275842758527586275872758827589275902759127592275932759427595275962759727598275992760027601276022760327604276052760627607276082760927610276112761227613276142761527616276172761827619276202762127622276232762427625276262762727628276292763027631276322763327634276352763627637276382763927640276412764227643276442764527646276472764827649276502765127652276532765427655276562765727658276592766027661276622766327664276652766627667276682766927670276712767227673276742767527676276772767827679276802768127682276832768427685276862768727688276892769027691276922769327694276952769627697276982769927700277012770227703277042770527706277072770827709277102771127712277132771427715277162771727718277192772027721277222772327724277252772627727277282772927730277312773227733277342773527736277372773827739277402774127742277432774427745277462774727748277492775027751277522775327754277552775627757277582775927760277612776227763277642776527766277672776827769277702777127772277732777427775277762777727778277792778027781277822778327784277852778627787277882778927790277912779227793277942779527796277972779827799278002780127802278032780427805278062780727808278092781027811278122781327814278152781627817278182781927820278212782227823278242782527826278272782827829278302783127832278332783427835278362783727838278392784027841278422784327844278452784627847278482784927850278512785227853278542785527856278572785827859278602786127862278632786427865278662786727868278692787027871278722787327874278752787627877278782787927880278812788227883278842788527886278872788827889278902789127892278932789427895278962789727898278992790027901279022790327904279052790627907279082790927910279112791227913279142791527916279172791827919279202792127922279232792427925279262792727928279292793027931279322793327934279352793627937279382793927940279412794227943279442794527946279472794827949279502795127952279532795427955279562795727958279592796027961279622796327964279652796627967279682796927970279712797227973279742797527976279772797827979279802798127982279832798427985279862798727988279892799027991279922799327994279952799627997279982799928000280012800228003280042800528006280072800828009280102801128012280132801428015280162801728018280192802028021280222802328024280252802628027280282802928030280312803228033280342803528036280372803828039280402804128042280432804428045280462804728048280492805028051280522805328054280552805628057280582805928060280612806228063280642806528066280672806828069280702807128072280732807428075280762807728078280792808028081280822808328084280852808628087280882808928090280912809228093280942809528096280972809828099281002810128102281032810428105281062810728108281092811028111281122811328114281152811628117281182811928120281212812228123281242812528126281272812828129281302813128132281332813428135281362813728138281392814028141281422814328144281452814628147281482814928150281512815228153281542815528156281572815828159281602816128162281632816428165281662816728168281692817028171281722817328174281752817628177281782817928180281812818228183281842818528186281872818828189281902819128192281932819428195281962819728198281992820028201282022820328204282052820628207282082820928210282112821228213282142821528216282172821828219282202822128222282232822428225282262822728228282292823028231282322823328234282352823628237282382823928240282412824228243282442824528246282472824828249282502825128252282532825428255282562825728258282592826028261282622826328264282652826628267282682826928270282712827228273282742827528276282772827828279282802828128282282832828428285282862828728288282892829028291282922829328294282952829628297282982829928300283012830228303283042830528306283072830828309283102831128312283132831428315283162831728318283192832028321283222832328324283252832628327283282832928330283312833228333283342833528336283372833828339283402834128342283432834428345283462834728348283492835028351283522835328354283552835628357283582835928360283612836228363283642836528366283672836828369283702837128372283732837428375283762837728378283792838028381283822838328384283852838628387283882838928390283912839228393283942839528396283972839828399284002840128402284032840428405284062840728408284092841028411284122841328414284152841628417284182841928420284212842228423284242842528426284272842828429284302843128432284332843428435284362843728438284392844028441284422844328444284452844628447284482844928450284512845228453284542845528456284572845828459284602846128462284632846428465284662846728468284692847028471284722847328474284752847628477284782847928480284812848228483284842848528486284872848828489284902849128492284932849428495284962849728498284992850028501285022850328504285052850628507285082850928510285112851228513285142851528516285172851828519285202852128522285232852428525285262852728528285292853028531285322853328534285352853628537285382853928540285412854228543285442854528546285472854828549285502855128552285532855428555285562855728558285592856028561285622856328564285652856628567285682856928570285712857228573285742857528576285772857828579285802858128582285832858428585285862858728588285892859028591285922859328594285952859628597285982859928600286012860228603286042860528606286072860828609286102861128612286132861428615286162861728618286192862028621286222862328624286252862628627286282862928630286312863228633286342863528636286372863828639286402864128642286432864428645286462864728648286492865028651286522865328654286552865628657286582865928660286612866228663286642866528666286672866828669286702867128672286732867428675286762867728678286792868028681286822868328684286852868628687286882868928690286912869228693286942869528696286972869828699287002870128702287032870428705287062870728708287092871028711287122871328714287152871628717287182871928720287212872228723287242872528726287272872828729287302873128732287332873428735287362873728738287392874028741287422874328744287452874628747287482874928750287512875228753287542875528756287572875828759287602876128762287632876428765287662876728768287692877028771287722877328774287752877628777287782877928780287812878228783287842878528786287872878828789287902879128792287932879428795287962879728798287992880028801288022880328804288052880628807288082880928810288112881228813288142881528816288172881828819288202882128822288232882428825288262882728828288292883028831288322883328834288352883628837288382883928840288412884228843288442884528846288472884828849288502885128852288532885428855288562885728858288592886028861288622886328864288652886628867288682886928870288712887228873288742887528876288772887828879288802888128882288832888428885288862888728888288892889028891288922889328894288952889628897288982889928900289012890228903289042890528906289072890828909289102891128912289132891428915289162891728918289192892028921289222892328924289252892628927289282892928930289312893228933289342893528936289372893828939289402894128942289432894428945289462894728948289492895028951289522895328954289552895628957289582895928960289612896228963289642896528966289672896828969289702897128972289732897428975289762897728978289792898028981289822898328984289852898628987289882898928990289912899228993289942899528996289972899828999290002900129002290032900429005290062900729008290092901029011290122901329014290152901629017290182901929020290212902229023290242902529026290272902829029290302903129032290332903429035290362903729038290392904029041290422904329044290452904629047290482904929050290512905229053290542905529056290572905829059290602906129062290632906429065290662906729068290692907029071290722907329074290752907629077290782907929080290812908229083290842908529086290872908829089290902909129092290932909429095290962909729098290992910029101291022910329104291052910629107291082910929110291112911229113291142911529116291172911829119291202912129122291232912429125291262912729128291292913029131291322913329134291352913629137291382913929140291412914229143291442914529146291472914829149291502915129152291532915429155291562915729158291592916029161291622916329164291652916629167291682916929170291712917229173291742917529176291772917829179291802918129182291832918429185291862918729188291892919029191291922919329194291952919629197291982919929200292012920229203292042920529206292072920829209292102921129212292132921429215292162921729218292192922029221292222922329224292252922629227292282922929230292312923229233292342923529236292372923829239292402924129242292432924429245292462924729248292492925029251292522925329254292552925629257292582925929260292612926229263292642926529266292672926829269292702927129272292732927429275292762927729278292792928029281292822928329284292852928629287292882928929290292912929229293292942929529296292972929829299293002930129302293032930429305293062930729308293092931029311293122931329314293152931629317293182931929320293212932229323293242932529326293272932829329293302933129332293332933429335293362933729338293392934029341293422934329344293452934629347293482934929350293512935229353293542935529356293572935829359293602936129362293632936429365293662936729368293692937029371293722937329374293752937629377293782937929380293812938229383293842938529386293872938829389293902939129392293932939429395293962939729398293992940029401294022940329404294052940629407294082940929410294112941229413294142941529416294172941829419294202942129422294232942429425294262942729428294292943029431294322943329434294352943629437294382943929440294412944229443294442944529446294472944829449294502945129452294532945429455294562945729458294592946029461294622946329464294652946629467294682946929470294712947229473294742947529476294772947829479294802948129482294832948429485294862948729488294892949029491294922949329494294952949629497294982949929500295012950229503295042950529506295072950829509295102951129512295132951429515295162951729518295192952029521295222952329524295252952629527295282952929530295312953229533295342953529536295372953829539295402954129542295432954429545295462954729548295492955029551295522955329554295552955629557295582955929560295612956229563295642956529566295672956829569295702957129572295732957429575295762957729578295792958029581295822958329584295852958629587295882958929590295912959229593295942959529596295972959829599296002960129602296032960429605296062960729608296092961029611296122961329614296152961629617296182961929620296212962229623296242962529626296272962829629296302963129632296332963429635296362963729638296392964029641296422964329644296452964629647296482964929650296512965229653296542965529656296572965829659296602966129662296632966429665296662966729668296692967029671296722967329674296752967629677296782967929680296812968229683296842968529686296872968829689296902969129692296932969429695296962969729698296992970029701297022970329704297052970629707297082970929710297112971229713297142971529716297172971829719297202972129722297232972429725297262972729728297292973029731297322973329734297352973629737297382973929740297412974229743297442974529746297472974829749297502975129752297532975429755297562975729758297592976029761297622976329764297652976629767297682976929770297712977229773297742977529776297772977829779297802978129782297832978429785297862978729788297892979029791297922979329794297952979629797297982979929800298012980229803298042980529806298072980829809298102981129812298132981429815298162981729818298192982029821298222982329824298252982629827298282982929830298312983229833298342983529836298372983829839298402984129842298432984429845298462984729848298492985029851298522985329854298552985629857298582985929860298612986229863298642986529866298672986829869298702987129872298732987429875298762987729878298792988029881298822988329884298852988629887298882988929890298912989229893298942989529896298972989829899299002990129902299032990429905299062990729908299092991029911299122991329914299152991629917299182991929920299212992229923299242992529926299272992829929299302993129932299332993429935299362993729938299392994029941299422994329944299452994629947299482994929950299512995229953299542995529956299572995829959299602996129962299632996429965299662996729968299692997029971299722997329974299752997629977299782997929980299812998229983299842998529986299872998829989299902999129992299932999429995299962999729998299993000030001300023000330004300053000630007300083000930010300113001230013300143001530016300173001830019300203002130022300233002430025300263002730028300293003030031300323003330034300353003630037300383003930040300413004230043300443004530046300473004830049300503005130052300533005430055300563005730058300593006030061300623006330064300653006630067300683006930070300713007230073300743007530076300773007830079300803008130082300833008430085300863008730088300893009030091300923009330094300953009630097300983009930100301013010230103301043010530106301073010830109301103011130112301133011430115301163011730118301193012030121301223012330124301253012630127301283012930130301313013230133301343013530136301373013830139301403014130142301433014430145301463014730148301493015030151301523015330154301553015630157301583015930160301613016230163301643016530166301673016830169301703017130172301733017430175301763017730178301793018030181301823018330184301853018630187301883018930190301913019230193301943019530196301973019830199302003020130202302033020430205302063020730208302093021030211302123021330214302153021630217302183021930220302213022230223302243022530226302273022830229302303023130232302333023430235302363023730238302393024030241302423024330244302453024630247302483024930250302513025230253302543025530256302573025830259302603026130262302633026430265302663026730268302693027030271302723027330274302753027630277302783027930280302813028230283302843028530286302873028830289302903029130292302933029430295302963029730298302993030030301303023030330304303053030630307303083030930310303113031230313303143031530316303173031830319303203032130322303233032430325303263032730328303293033030331303323033330334303353033630337303383033930340303413034230343303443034530346303473034830349303503035130352303533035430355303563035730358303593036030361303623036330364303653036630367303683036930370303713037230373303743037530376303773037830379303803038130382303833038430385303863038730388303893039030391303923039330394303953039630397303983039930400304013040230403304043040530406304073040830409304103041130412304133041430415304163041730418304193042030421304223042330424304253042630427304283042930430304313043230433304343043530436304373043830439304403044130442304433044430445304463044730448304493045030451304523045330454304553045630457304583045930460304613046230463304643046530466304673046830469304703047130472304733047430475304763047730478304793048030481304823048330484304853048630487304883048930490304913049230493304943049530496304973049830499305003050130502305033050430505305063050730508305093051030511305123051330514305153051630517305183051930520305213052230523305243052530526305273052830529305303053130532305333053430535305363053730538305393054030541305423054330544305453054630547305483054930550305513055230553305543055530556305573055830559305603056130562305633056430565305663056730568305693057030571305723057330574305753057630577305783057930580305813058230583305843058530586305873058830589305903059130592305933059430595305963059730598305993060030601306023060330604306053060630607306083060930610306113061230613306143061530616306173061830619306203062130622306233062430625306263062730628306293063030631306323063330634306353063630637306383063930640306413064230643306443064530646306473064830649306503065130652306533065430655306563065730658306593066030661306623066330664306653066630667306683066930670306713067230673306743067530676306773067830679306803068130682306833068430685306863068730688306893069030691306923069330694306953069630697306983069930700307013070230703307043070530706307073070830709307103071130712307133071430715307163071730718307193072030721307223072330724307253072630727307283072930730307313073230733307343073530736307373073830739307403074130742307433074430745307463074730748307493075030751307523075330754307553075630757307583075930760307613076230763307643076530766307673076830769307703077130772307733077430775307763077730778307793078030781307823078330784307853078630787307883078930790307913079230793307943079530796307973079830799308003080130802308033080430805308063080730808308093081030811308123081330814308153081630817308183081930820308213082230823308243082530826308273082830829308303083130832308333083430835308363083730838308393084030841308423084330844308453084630847308483084930850308513085230853308543085530856308573085830859308603086130862308633086430865308663086730868308693087030871308723087330874308753087630877308783087930880308813088230883308843088530886308873088830889308903089130892308933089430895308963089730898308993090030901309023090330904309053090630907309083090930910309113091230913309143091530916309173091830919309203092130922309233092430925309263092730928309293093030931309323093330934309353093630937309383093930940309413094230943309443094530946309473094830949309503095130952309533095430955309563095730958309593096030961309623096330964309653096630967309683096930970309713097230973309743097530976309773097830979309803098130982309833098430985309863098730988309893099030991309923099330994309953099630997309983099931000310013100231003310043100531006310073100831009310103101131012310133101431015310163101731018310193102031021310223102331024310253102631027310283102931030310313103231033310343103531036310373103831039310403104131042310433104431045310463104731048310493105031051310523105331054310553105631057310583105931060310613106231063310643106531066310673106831069310703107131072310733107431075310763107731078310793108031081310823108331084310853108631087310883108931090310913109231093310943109531096310973109831099311003110131102311033110431105311063110731108311093111031111311123111331114311153111631117311183111931120311213112231123311243112531126311273112831129311303113131132311333113431135311363113731138311393114031141311423114331144311453114631147311483114931150311513115231153311543115531156311573115831159311603116131162311633116431165311663116731168311693117031171311723117331174311753117631177311783117931180311813118231183311843118531186311873118831189311903119131192311933119431195311963119731198311993120031201312023120331204312053120631207312083120931210312113121231213312143121531216312173121831219312203122131222312233122431225312263122731228312293123031231312323123331234312353123631237312383123931240312413124231243312443124531246312473124831249312503125131252312533125431255312563125731258312593126031261312623126331264312653126631267312683126931270312713127231273312743127531276312773127831279312803128131282312833128431285312863128731288312893129031291312923129331294312953129631297312983129931300313013130231303313043130531306313073130831309313103131131312313133131431315313163131731318313193132031321313223132331324313253132631327313283132931330313313133231333313343133531336313373133831339313403134131342313433134431345313463134731348313493135031351313523135331354313553135631357313583135931360313613136231363313643136531366313673136831369313703137131372313733137431375313763137731378313793138031381313823138331384313853138631387313883138931390313913139231393313943139531396313973139831399314003140131402314033140431405314063140731408314093141031411314123141331414314153141631417314183141931420314213142231423314243142531426314273142831429314303143131432314333143431435314363143731438314393144031441314423144331444314453144631447314483144931450314513145231453314543145531456314573145831459314603146131462314633146431465314663146731468314693147031471314723147331474314753147631477314783147931480314813148231483314843148531486314873148831489314903149131492314933149431495314963149731498314993150031501315023150331504315053150631507315083150931510315113151231513315143151531516315173151831519315203152131522315233152431525315263152731528315293153031531315323153331534315353153631537315383153931540315413154231543315443154531546315473154831549315503155131552315533155431555315563155731558315593156031561315623156331564315653156631567315683156931570315713157231573315743157531576315773157831579315803158131582315833158431585315863158731588315893159031591315923159331594315953159631597315983159931600316013160231603316043160531606316073160831609316103161131612316133161431615316163161731618316193162031621316223162331624316253162631627316283162931630316313163231633316343163531636316373163831639316403164131642316433164431645316463164731648316493165031651316523165331654316553165631657316583165931660316613166231663316643166531666316673166831669316703167131672316733167431675316763167731678316793168031681316823168331684316853168631687316883168931690316913169231693316943169531696316973169831699317003170131702317033170431705317063170731708317093171031711317123171331714317153171631717317183171931720317213172231723317243172531726317273172831729317303173131732317333173431735317363173731738317393174031741317423174331744317453174631747317483174931750317513175231753317543175531756317573175831759317603176131762317633176431765317663176731768317693177031771317723177331774317753177631777317783177931780317813178231783317843178531786317873178831789317903179131792317933179431795317963179731798317993180031801318023180331804318053180631807318083180931810318113181231813318143181531816318173181831819318203182131822318233182431825318263182731828318293183031831318323183331834318353183631837318383183931840318413184231843318443184531846318473184831849318503185131852318533185431855318563185731858318593186031861318623186331864318653186631867318683186931870318713187231873318743187531876318773187831879318803188131882318833188431885318863188731888318893189031891318923189331894318953189631897318983189931900319013190231903319043190531906319073190831909319103191131912319133191431915319163191731918319193192031921319223192331924319253192631927319283192931930319313193231933319343193531936319373193831939319403194131942319433194431945319463194731948319493195031951319523195331954319553195631957319583195931960319613196231963319643196531966319673196831969319703197131972319733197431975319763197731978319793198031981319823198331984319853198631987319883198931990319913199231993319943199531996319973199831999320003200132002320033200432005320063200732008320093201032011320123201332014320153201632017320183201932020320213202232023320243202532026320273202832029320303203132032320333203432035320363203732038320393204032041320423204332044320453204632047320483204932050320513205232053320543205532056320573205832059320603206132062320633206432065320663206732068320693207032071320723207332074320753207632077320783207932080320813208232083320843208532086320873208832089320903209132092320933209432095320963209732098320993210032101321023210332104321053210632107321083210932110321113211232113321143211532116321173211832119321203212132122321233212432125321263212732128321293213032131321323213332134321353213632137321383213932140321413214232143321443214532146321473214832149321503215132152321533215432155321563215732158321593216032161321623216332164321653216632167321683216932170321713217232173321743217532176321773217832179321803218132182321833218432185321863218732188321893219032191321923219332194321953219632197321983219932200322013220232203322043220532206322073220832209322103221132212322133221432215322163221732218322193222032221322223222332224322253222632227322283222932230322313223232233322343223532236322373223832239322403224132242322433224432245322463224732248322493225032251322523225332254322553225632257322583225932260322613226232263322643226532266322673226832269322703227132272322733227432275322763227732278322793228032281322823228332284322853228632287322883228932290322913229232293322943229532296322973229832299323003230132302323033230432305323063230732308323093231032311323123231332314323153231632317323183231932320323213232232323323243232532326323273232832329323303233132332323333233432335323363233732338323393234032341323423234332344323453234632347323483234932350323513235232353323543235532356323573235832359323603236132362323633236432365323663236732368323693237032371323723237332374323753237632377323783237932380323813238232383323843238532386323873238832389323903239132392323933239432395323963239732398323993240032401324023240332404324053240632407324083240932410324113241232413324143241532416324173241832419324203242132422324233242432425324263242732428324293243032431324323243332434324353243632437324383243932440324413244232443324443244532446324473244832449324503245132452324533245432455324563245732458324593246032461324623246332464324653246632467324683246932470324713247232473324743247532476324773247832479324803248132482324833248432485324863248732488324893249032491324923249332494324953249632497324983249932500325013250232503325043250532506325073250832509325103251132512325133251432515325163251732518325193252032521325223252332524325253252632527325283252932530325313253232533325343253532536325373253832539325403254132542325433254432545325463254732548325493255032551325523255332554325553255632557325583255932560325613256232563325643256532566325673256832569325703257132572325733257432575325763257732578325793258032581325823258332584325853258632587325883258932590325913259232593325943259532596325973259832599326003260132602326033260432605326063260732608326093261032611326123261332614326153261632617326183261932620326213262232623326243262532626326273262832629326303263132632326333263432635326363263732638326393264032641326423264332644326453264632647326483264932650326513265232653326543265532656326573265832659326603266132662326633266432665326663266732668326693267032671326723267332674326753267632677326783267932680326813268232683326843268532686326873268832689326903269132692326933269432695326963269732698326993270032701327023270332704327053270632707327083270932710327113271232713327143271532716327173271832719327203272132722327233272432725327263272732728327293273032731327323273332734327353273632737327383273932740327413274232743327443274532746327473274832749327503275132752327533275432755327563275732758327593276032761327623276332764327653276632767327683276932770327713277232773327743277532776327773277832779327803278132782327833278432785327863278732788327893279032791327923279332794327953279632797327983279932800328013280232803328043280532806328073280832809328103281132812328133281432815328163281732818328193282032821328223282332824328253282632827328283282932830328313283232833328343283532836328373283832839328403284132842328433284432845328463284732848328493285032851328523285332854328553285632857328583285932860328613286232863328643286532866328673286832869328703287132872328733287432875328763287732878328793288032881328823288332884328853288632887328883288932890328913289232893328943289532896328973289832899329003290132902329033290432905329063290732908329093291032911329123291332914329153291632917329183291932920329213292232923329243292532926329273292832929329303293132932329333293432935329363293732938329393294032941329423294332944329453294632947329483294932950329513295232953329543295532956329573295832959329603296132962329633296432965329663296732968329693297032971329723297332974329753297632977329783297932980329813298232983329843298532986329873298832989329903299132992329933299432995329963299732998329993300033001330023300333004330053300633007330083300933010330113301233013330143301533016330173301833019330203302133022330233302433025330263302733028330293303033031330323303333034330353303633037330383303933040330413304233043330443304533046330473304833049330503305133052330533305433055330563305733058330593306033061330623306333064330653306633067330683306933070330713307233073330743307533076330773307833079330803308133082330833308433085330863308733088330893309033091330923309333094330953309633097330983309933100331013310233103331043310533106331073310833109331103311133112331133311433115331163311733118331193312033121331223312333124331253312633127331283312933130331313313233133331343313533136331373313833139331403314133142331433314433145331463314733148331493315033151331523315333154331553315633157331583315933160331613316233163331643316533166331673316833169331703317133172331733317433175331763317733178331793318033181331823318333184331853318633187331883318933190331913319233193331943319533196331973319833199332003320133202332033320433205332063320733208332093321033211332123321333214332153321633217332183321933220332213322233223332243322533226332273322833229332303323133232332333323433235332363323733238332393324033241332423324333244332453324633247332483324933250332513325233253332543325533256332573325833259332603326133262332633326433265332663326733268332693327033271332723327333274332753327633277332783327933280332813328233283332843328533286332873328833289332903329133292332933329433295332963329733298332993330033301333023330333304333053330633307333083330933310333113331233313333143331533316333173331833319333203332133322333233332433325333263332733328333293333033331333323333333334333353333633337333383333933340333413334233343333443334533346333473334833349333503335133352333533335433355333563335733358333593336033361333623336333364333653336633367333683336933370333713337233373333743337533376333773337833379333803338133382333833338433385333863338733388333893339033391333923339333394333953339633397333983339933400334013340233403334043340533406334073340833409334103341133412334133341433415334163341733418334193342033421334223342333424334253342633427334283342933430334313343233433334343343533436334373343833439334403344133442334433344433445334463344733448334493345033451334523345333454334553345633457334583345933460334613346233463334643346533466334673346833469334703347133472334733347433475334763347733478334793348033481334823348333484334853348633487334883348933490334913349233493334943349533496334973349833499335003350133502335033350433505335063350733508335093351033511335123351333514335153351633517335183351933520335213352233523335243352533526335273352833529335303353133532335333353433535335363353733538335393354033541335423354333544335453354633547335483354933550335513355233553335543355533556335573355833559335603356133562335633356433565335663356733568335693357033571335723357333574335753357633577335783357933580335813358233583335843358533586335873358833589335903359133592335933359433595335963359733598335993360033601336023360333604336053360633607336083360933610336113361233613336143361533616336173361833619336203362133622336233362433625336263362733628336293363033631336323363333634336353363633637336383363933640336413364233643336443364533646336473364833649336503365133652336533365433655336563365733658336593366033661336623366333664336653366633667336683366933670336713367233673336743367533676336773367833679336803368133682336833368433685336863368733688336893369033691336923369333694336953369633697336983369933700337013370233703337043370533706337073370833709337103371133712337133371433715337163371733718337193372033721337223372333724337253372633727337283372933730337313373233733337343373533736337373373833739337403374133742337433374433745337463374733748337493375033751337523375333754337553375633757337583375933760337613376233763337643376533766337673376833769337703377133772337733377433775337763377733778337793378033781337823378333784337853378633787337883378933790337913379233793337943379533796337973379833799338003380133802338033380433805338063380733808338093381033811338123381333814338153381633817338183381933820338213382233823338243382533826338273382833829338303383133832338333383433835338363383733838338393384033841338423384333844338453384633847338483384933850338513385233853338543385533856338573385833859338603386133862338633386433865338663386733868338693387033871338723387333874338753387633877338783387933880338813388233883338843388533886338873388833889338903389133892338933389433895338963389733898338993390033901339023390333904339053390633907339083390933910339113391233913339143391533916339173391833919339203392133922339233392433925339263392733928339293393033931339323393333934339353393633937339383393933940339413394233943339443394533946339473394833949339503395133952339533395433955339563395733958339593396033961339623396333964339653396633967339683396933970339713397233973339743397533976339773397833979339803398133982339833398433985339863398733988339893399033991339923399333994339953399633997339983399934000340013400234003340043400534006340073400834009340103401134012340133401434015340163401734018340193402034021340223402334024340253402634027340283402934030340313403234033340343403534036340373403834039340403404134042340433404434045340463404734048340493405034051340523405334054340553405634057340583405934060340613406234063340643406534066340673406834069340703407134072340733407434075340763407734078340793408034081340823408334084340853408634087340883408934090340913409234093340943409534096340973409834099341003410134102341033410434105341063410734108341093411034111341123411334114341153411634117341183411934120341213412234123341243412534126341273412834129341303413134132341333413434135341363413734138341393414034141341423414334144341453414634147341483414934150341513415234153341543415534156341573415834159341603416134162341633416434165341663416734168341693417034171341723417334174341753417634177341783417934180341813418234183341843418534186341873418834189341903419134192341933419434195341963419734198341993420034201342023420334204342053420634207342083420934210342113421234213342143421534216342173421834219342203422134222342233422434225342263422734228342293423034231342323423334234342353423634237342383423934240342413424234243342443424534246342473424834249342503425134252342533425434255342563425734258342593426034261342623426334264342653426634267342683426934270342713427234273342743427534276342773427834279342803428134282342833428434285342863428734288342893429034291342923429334294342953429634297342983429934300343013430234303343043430534306343073430834309343103431134312343133431434315343163431734318343193432034321343223432334324343253432634327343283432934330343313433234333343343433534336343373433834339343403434134342343433434434345343463434734348343493435034351343523435334354343553435634357343583435934360343613436234363343643436534366343673436834369343703437134372343733437434375343763437734378343793438034381343823438334384343853438634387343883438934390343913439234393343943439534396343973439834399344003440134402344033440434405344063440734408344093441034411344123441334414344153441634417344183441934420344213442234423344243442534426344273442834429344303443134432344333443434435344363443734438344393444034441344423444334444344453444634447344483444934450344513445234453344543445534456344573445834459344603446134462344633446434465344663446734468344693447034471344723447334474344753447634477344783447934480344813448234483344843448534486344873448834489344903449134492344933449434495344963449734498344993450034501345023450334504345053450634507345083450934510345113451234513345143451534516345173451834519345203452134522345233452434525345263452734528345293453034531345323453334534345353453634537345383453934540345413454234543345443454534546345473454834549345503455134552345533455434555345563455734558345593456034561345623456334564345653456634567345683456934570345713457234573345743457534576345773457834579345803458134582345833458434585345863458734588345893459034591345923459334594345953459634597345983459934600346013460234603346043460534606346073460834609346103461134612346133461434615346163461734618346193462034621346223462334624346253462634627346283462934630346313463234633346343463534636346373463834639346403464134642346433464434645346463464734648346493465034651346523465334654346553465634657346583465934660346613466234663346643466534666346673466834669346703467134672346733467434675346763467734678346793468034681346823468334684346853468634687346883468934690346913469234693346943469534696346973469834699347003470134702347033470434705347063470734708347093471034711347123471334714347153471634717347183471934720347213472234723347243472534726347273472834729347303473134732347333473434735347363473734738347393474034741347423474334744347453474634747347483474934750347513475234753347543475534756347573475834759347603476134762347633476434765347663476734768347693477034771347723477334774347753477634777347783477934780347813478234783347843478534786347873478834789347903479134792347933479434795347963479734798347993480034801348023480334804348053480634807348083480934810348113481234813348143481534816348173481834819348203482134822348233482434825348263482734828348293483034831348323483334834348353483634837348383483934840348413484234843348443484534846348473484834849348503485134852348533485434855348563485734858348593486034861348623486334864348653486634867348683486934870348713487234873348743487534876348773487834879348803488134882348833488434885348863488734888348893489034891348923489334894348953489634897348983489934900349013490234903349043490534906349073490834909349103491134912349133491434915349163491734918349193492034921349223492334924349253492634927349283492934930349313493234933349343493534936349373493834939349403494134942349433494434945349463494734948349493495034951349523495334954349553495634957349583495934960349613496234963349643496534966349673496834969349703497134972349733497434975349763497734978349793498034981349823498334984349853498634987349883498934990349913499234993349943499534996349973499834999350003500135002350033500435005350063500735008350093501035011350123501335014350153501635017350183501935020350213502235023350243502535026350273502835029350303503135032350333503435035350363503735038350393504035041350423504335044350453504635047350483504935050350513505235053350543505535056350573505835059350603506135062350633506435065350663506735068350693507035071350723507335074350753507635077350783507935080350813508235083350843508535086350873508835089350903509135092350933509435095350963509735098350993510035101351023510335104351053510635107351083510935110351113511235113351143511535116351173511835119351203512135122351233512435125351263512735128351293513035131351323513335134351353513635137351383513935140351413514235143351443514535146351473514835149351503515135152351533515435155351563515735158351593516035161351623516335164351653516635167351683516935170351713517235173351743517535176351773517835179351803518135182351833518435185351863518735188351893519035191351923519335194351953519635197351983519935200352013520235203352043520535206352073520835209352103521135212352133521435215352163521735218352193522035221352223522335224352253522635227352283522935230352313523235233352343523535236352373523835239352403524135242352433524435245352463524735248352493525035251352523525335254352553525635257352583525935260352613526235263352643526535266352673526835269352703527135272352733527435275352763527735278352793528035281352823528335284352853528635287352883528935290352913529235293352943529535296352973529835299353003530135302353033530435305353063530735308353093531035311353123531335314353153531635317353183531935320353213532235323353243532535326353273532835329353303533135332353333533435335353363533735338353393534035341353423534335344353453534635347353483534935350353513535235353353543535535356353573535835359353603536135362353633536435365353663536735368353693537035371353723537335374353753537635377353783537935380353813538235383353843538535386353873538835389353903539135392353933539435395353963539735398353993540035401354023540335404354053540635407354083540935410354113541235413354143541535416354173541835419354203542135422354233542435425354263542735428354293543035431354323543335434354353543635437354383543935440354413544235443354443544535446354473544835449354503545135452354533545435455354563545735458354593546035461354623546335464354653546635467354683546935470354713547235473354743547535476354773547835479354803548135482354833548435485354863548735488354893549035491354923549335494354953549635497354983549935500355013550235503355043550535506355073550835509355103551135512355133551435515355163551735518355193552035521355223552335524355253552635527355283552935530355313553235533355343553535536355373553835539355403554135542355433554435545355463554735548355493555035551355523555335554355553555635557355583555935560355613556235563355643556535566355673556835569355703557135572355733557435575355763557735578355793558035581355823558335584355853558635587355883558935590355913559235593355943559535596355973559835599356003560135602356033560435605356063560735608356093561035611356123561335614356153561635617356183561935620356213562235623356243562535626356273562835629356303563135632356333563435635356363563735638356393564035641356423564335644356453564635647356483564935650356513565235653356543565535656356573565835659356603566135662356633566435665356663566735668356693567035671356723567335674356753567635677356783567935680356813568235683356843568535686356873568835689356903569135692356933569435695356963569735698356993570035701357023570335704357053570635707357083570935710357113571235713357143571535716357173571835719357203572135722357233572435725357263572735728357293573035731357323573335734357353573635737357383573935740357413574235743357443574535746357473574835749357503575135752357533575435755357563575735758357593576035761357623576335764357653576635767357683576935770357713577235773357743577535776357773577835779357803578135782357833578435785357863578735788357893579035791357923579335794357953579635797357983579935800358013580235803358043580535806358073580835809358103581135812358133581435815358163581735818358193582035821358223582335824358253582635827358283582935830358313583235833358343583535836358373583835839358403584135842358433584435845358463584735848358493585035851358523585335854358553585635857358583585935860358613586235863358643586535866358673586835869358703587135872358733587435875358763587735878358793588035881358823588335884358853588635887358883588935890358913589235893358943589535896358973589835899359003590135902359033590435905359063590735908359093591035911359123591335914359153591635917359183591935920359213592235923359243592535926359273592835929359303593135932359333593435935359363593735938359393594035941359423594335944359453594635947359483594935950359513595235953359543595535956359573595835959359603596135962359633596435965359663596735968359693597035971359723597335974359753597635977359783597935980359813598235983359843598535986359873598835989359903599135992359933599435995359963599735998359993600036001360023600336004360053600636007360083600936010360113601236013360143601536016360173601836019360203602136022360233602436025360263602736028360293603036031360323603336034360353603636037360383603936040360413604236043360443604536046360473604836049360503605136052360533605436055360563605736058360593606036061360623606336064360653606636067360683606936070360713607236073360743607536076360773607836079360803608136082360833608436085360863608736088360893609036091360923609336094360953609636097360983609936100361013610236103361043610536106361073610836109361103611136112361133611436115361163611736118361193612036121361223612336124361253612636127361283612936130361313613236133361343613536136361373613836139361403614136142361433614436145361463614736148361493615036151361523615336154361553615636157361583615936160361613616236163361643616536166361673616836169361703617136172361733617436175361763617736178361793618036181361823618336184361853618636187361883618936190361913619236193361943619536196361973619836199362003620136202362033620436205362063620736208362093621036211362123621336214362153621636217362183621936220362213622236223362243622536226362273622836229362303623136232362333623436235362363623736238362393624036241362423624336244362453624636247362483624936250362513625236253362543625536256362573625836259362603626136262362633626436265362663626736268362693627036271362723627336274362753627636277362783627936280362813628236283362843628536286362873628836289362903629136292362933629436295362963629736298362993630036301363023630336304363053630636307363083630936310363113631236313363143631536316363173631836319363203632136322363233632436325363263632736328363293633036331363323633336334363353633636337363383633936340363413634236343363443634536346363473634836349363503635136352363533635436355363563635736358363593636036361363623636336364363653636636367363683636936370363713637236373363743637536376363773637836379363803638136382363833638436385363863638736388363893639036391363923639336394363953639636397363983639936400364013640236403364043640536406364073640836409364103641136412364133641436415364163641736418364193642036421364223642336424364253642636427364283642936430364313643236433364343643536436364373643836439364403644136442364433644436445364463644736448364493645036451364523645336454364553645636457364583645936460364613646236463364643646536466364673646836469364703647136472364733647436475364763647736478364793648036481364823648336484364853648636487364883648936490364913649236493364943649536496364973649836499365003650136502365033650436505365063650736508365093651036511365123651336514365153651636517365183651936520365213652236523365243652536526365273652836529365303653136532365333653436535365363653736538365393654036541365423654336544365453654636547365483654936550365513655236553365543655536556365573655836559365603656136562365633656436565365663656736568365693657036571365723657336574365753657636577365783657936580365813658236583365843658536586365873658836589365903659136592365933659436595365963659736598365993660036601366023660336604366053660636607366083660936610366113661236613366143661536616366173661836619366203662136622366233662436625366263662736628366293663036631366323663336634366353663636637366383663936640366413664236643366443664536646366473664836649366503665136652366533665436655366563665736658366593666036661366623666336664366653666636667366683666936670366713667236673366743667536676366773667836679366803668136682366833668436685366863668736688366893669036691366923669336694366953669636697366983669936700367013670236703367043670536706367073670836709367103671136712367133671436715367163671736718367193672036721367223672336724367253672636727367283672936730367313673236733367343673536736367373673836739367403674136742367433674436745367463674736748367493675036751367523675336754367553675636757367583675936760367613676236763367643676536766367673676836769367703677136772367733677436775367763677736778367793678036781367823678336784367853678636787367883678936790367913679236793367943679536796367973679836799368003680136802368033680436805368063680736808368093681036811368123681336814368153681636817368183681936820368213682236823368243682536826368273682836829368303683136832368333683436835368363683736838368393684036841368423684336844368453684636847368483684936850368513685236853368543685536856368573685836859368603686136862368633686436865368663686736868368693687036871368723687336874368753687636877368783687936880368813688236883368843688536886368873688836889368903689136892368933689436895368963689736898368993690036901369023690336904369053690636907369083690936910369113691236913369143691536916369173691836919369203692136922369233692436925369263692736928369293693036931369323693336934369353693636937369383693936940369413694236943369443694536946369473694836949369503695136952369533695436955369563695736958369593696036961369623696336964369653696636967369683696936970369713697236973369743697536976369773697836979369803698136982369833698436985369863698736988369893699036991369923699336994369953699636997369983699937000370013700237003370043700537006370073700837009370103701137012370133701437015370163701737018370193702037021370223702337024370253702637027370283702937030370313703237033370343703537036370373703837039370403704137042370433704437045370463704737048370493705037051370523705337054370553705637057370583705937060370613706237063370643706537066370673706837069370703707137072370733707437075370763707737078370793708037081370823708337084370853708637087370883708937090370913709237093370943709537096370973709837099371003710137102371033710437105371063710737108371093711037111371123711337114371153711637117371183711937120371213712237123371243712537126371273712837129371303713137132371333713437135371363713737138371393714037141371423714337144371453714637147371483714937150371513715237153371543715537156371573715837159371603716137162371633716437165371663716737168371693717037171371723717337174371753717637177371783717937180371813718237183371843718537186371873718837189371903719137192371933719437195371963719737198371993720037201372023720337204372053720637207372083720937210372113721237213372143721537216372173721837219372203722137222372233722437225372263722737228372293723037231372323723337234372353723637237372383723937240372413724237243372443724537246372473724837249372503725137252372533725437255372563725737258372593726037261372623726337264372653726637267372683726937270372713727237273372743727537276372773727837279372803728137282372833728437285372863728737288372893729037291372923729337294372953729637297372983729937300373013730237303373043730537306373073730837309373103731137312373133731437315373163731737318373193732037321373223732337324373253732637327373283732937330373313733237333373343733537336373373733837339373403734137342373433734437345373463734737348373493735037351373523735337354373553735637357373583735937360373613736237363373643736537366373673736837369373703737137372373733737437375373763737737378373793738037381373823738337384373853738637387373883738937390373913739237393373943739537396373973739837399374003740137402374033740437405374063740737408374093741037411374123741337414374153741637417374183741937420374213742237423374243742537426374273742837429374303743137432374333743437435374363743737438374393744037441374423744337444374453744637447374483744937450374513745237453374543745537456374573745837459374603746137462374633746437465374663746737468374693747037471374723747337474374753747637477374783747937480374813748237483374843748537486374873748837489374903749137492374933749437495374963749737498374993750037501375023750337504375053750637507375083750937510375113751237513375143751537516375173751837519375203752137522375233752437525375263752737528375293753037531375323753337534375353753637537375383753937540375413754237543375443754537546375473754837549375503755137552375533755437555375563755737558375593756037561375623756337564375653756637567375683756937570375713757237573375743757537576375773757837579375803758137582375833758437585375863758737588375893759037591375923759337594375953759637597375983759937600376013760237603376043760537606376073760837609376103761137612376133761437615376163761737618376193762037621376223762337624376253762637627376283762937630376313763237633376343763537636376373763837639376403764137642376433764437645376463764737648376493765037651376523765337654376553765637657376583765937660376613766237663376643766537666376673766837669376703767137672376733767437675376763767737678376793768037681376823768337684376853768637687376883768937690376913769237693376943769537696376973769837699377003770137702377033770437705377063770737708377093771037711377123771337714377153771637717377183771937720377213772237723377243772537726377273772837729377303773137732377333773437735377363773737738377393774037741377423774337744377453774637747377483774937750377513775237753377543775537756377573775837759377603776137762377633776437765377663776737768377693777037771377723777337774377753777637777377783777937780377813778237783377843778537786377873778837789377903779137792377933779437795377963779737798377993780037801378023780337804378053780637807378083780937810378113781237813378143781537816378173781837819378203782137822378233782437825378263782737828378293783037831378323783337834378353783637837378383783937840378413784237843378443784537846378473784837849378503785137852378533785437855378563785737858378593786037861378623786337864378653786637867378683786937870378713787237873378743787537876378773787837879378803788137882378833788437885378863788737888378893789037891378923789337894378953789637897378983789937900379013790237903379043790537906379073790837909379103791137912379133791437915379163791737918379193792037921379223792337924379253792637927379283792937930379313793237933379343793537936379373793837939379403794137942379433794437945379463794737948379493795037951379523795337954379553795637957379583795937960379613796237963379643796537966379673796837969379703797137972379733797437975379763797737978379793798037981379823798337984379853798637987379883798937990379913799237993379943799537996379973799837999380003800138002380033800438005380063800738008380093801038011380123801338014380153801638017380183801938020380213802238023380243802538026380273802838029380303803138032380333803438035380363803738038380393804038041380423804338044380453804638047380483804938050380513805238053380543805538056380573805838059380603806138062380633806438065380663806738068380693807038071380723807338074380753807638077380783807938080380813808238083380843808538086380873808838089380903809138092380933809438095380963809738098380993810038101381023810338104381053810638107381083810938110381113811238113381143811538116381173811838119381203812138122381233812438125381263812738128381293813038131381323813338134381353813638137381383813938140381413814238143381443814538146381473814838149381503815138152381533815438155381563815738158381593816038161381623816338164381653816638167381683816938170381713817238173381743817538176381773817838179381803818138182381833818438185381863818738188381893819038191381923819338194381953819638197381983819938200382013820238203382043820538206382073820838209382103821138212382133821438215382163821738218382193822038221382223822338224382253822638227382283822938230382313823238233382343823538236382373823838239382403824138242382433824438245382463824738248382493825038251382523825338254382553825638257382583825938260382613826238263382643826538266382673826838269382703827138272382733827438275382763827738278382793828038281382823828338284382853828638287382883828938290382913829238293382943829538296382973829838299383003830138302383033830438305383063830738308383093831038311383123831338314383153831638317383183831938320383213832238323383243832538326383273832838329383303833138332383333833438335383363833738338383393834038341383423834338344383453834638347383483834938350383513835238353383543835538356383573835838359383603836138362383633836438365383663836738368383693837038371383723837338374383753837638377383783837938380383813838238383383843838538386383873838838389383903839138392383933839438395383963839738398383993840038401384023840338404384053840638407384083840938410384113841238413384143841538416384173841838419384203842138422384233842438425384263842738428384293843038431384323843338434384353843638437384383843938440384413844238443384443844538446384473844838449384503845138452384533845438455384563845738458384593846038461384623846338464384653846638467384683846938470384713847238473384743847538476384773847838479384803848138482384833848438485384863848738488384893849038491384923849338494384953849638497384983849938500385013850238503385043850538506385073850838509385103851138512385133851438515385163851738518385193852038521385223852338524385253852638527385283852938530385313853238533385343853538536385373853838539385403854138542385433854438545385463854738548385493855038551385523855338554385553855638557385583855938560385613856238563385643856538566385673856838569385703857138572385733857438575385763857738578385793858038581385823858338584385853858638587385883858938590385913859238593385943859538596385973859838599386003860138602386033860438605386063860738608386093861038611386123861338614386153861638617386183861938620386213862238623386243862538626386273862838629386303863138632386333863438635386363863738638386393864038641386423864338644386453864638647386483864938650386513865238653386543865538656386573865838659386603866138662386633866438665386663866738668386693867038671386723867338674386753867638677386783867938680386813868238683386843868538686386873868838689386903869138692386933869438695386963869738698386993870038701387023870338704387053870638707387083870938710387113871238713387143871538716387173871838719387203872138722387233872438725387263872738728387293873038731387323873338734387353873638737387383873938740387413874238743387443874538746387473874838749387503875138752387533875438755387563875738758387593876038761387623876338764387653876638767387683876938770387713877238773387743877538776387773877838779387803878138782387833878438785387863878738788387893879038791387923879338794387953879638797387983879938800388013880238803388043880538806388073880838809388103881138812388133881438815388163881738818388193882038821388223882338824388253882638827388283882938830388313883238833388343883538836388373883838839388403884138842388433884438845388463884738848388493885038851388523885338854388553885638857388583885938860388613886238863388643886538866388673886838869388703887138872388733887438875388763887738878388793888038881388823888338884388853888638887388883888938890388913889238893388943889538896388973889838899389003890138902389033890438905389063890738908389093891038911389123891338914389153891638917389183891938920389213892238923389243892538926389273892838929389303893138932389333893438935389363893738938389393894038941389423894338944389453894638947389483894938950389513895238953389543895538956389573895838959389603896138962389633896438965389663896738968389693897038971389723897338974389753897638977389783897938980389813898238983389843898538986389873898838989389903899138992389933899438995389963899738998389993900039001390023900339004390053900639007390083900939010390113901239013390143901539016390173901839019390203902139022390233902439025390263902739028390293903039031390323903339034390353903639037390383903939040390413904239043390443904539046390473904839049390503905139052390533905439055390563905739058390593906039061390623906339064390653906639067390683906939070390713907239073390743907539076390773907839079390803908139082390833908439085390863908739088390893909039091390923909339094390953909639097390983909939100391013910239103391043910539106391073910839109391103911139112391133911439115391163911739118391193912039121391223912339124391253912639127391283912939130391313913239133391343913539136391373913839139391403914139142391433914439145391463914739148391493915039151391523915339154391553915639157391583915939160391613916239163391643916539166391673916839169391703917139172391733917439175391763917739178391793918039181391823918339184391853918639187391883918939190391913919239193391943919539196391973919839199392003920139202392033920439205392063920739208392093921039211392123921339214392153921639217392183921939220392213922239223392243922539226392273922839229392303923139232392333923439235392363923739238392393924039241392423924339244392453924639247392483924939250392513925239253392543925539256392573925839259392603926139262392633926439265392663926739268392693927039271392723927339274392753927639277392783927939280392813928239283392843928539286392873928839289392903929139292392933929439295392963929739298392993930039301393023930339304393053930639307393083930939310393113931239313393143931539316393173931839319393203932139322393233932439325393263932739328393293933039331393323933339334393353933639337393383933939340393413934239343393443934539346393473934839349393503935139352393533935439355393563935739358393593936039361393623936339364393653936639367393683936939370393713937239373393743937539376393773937839379393803938139382393833938439385393863938739388393893939039391393923939339394393953939639397393983939939400394013940239403394043940539406394073940839409394103941139412394133941439415394163941739418394193942039421394223942339424394253942639427394283942939430394313943239433394343943539436394373943839439394403944139442394433944439445394463944739448394493945039451394523945339454394553945639457394583945939460394613946239463394643946539466394673946839469394703947139472394733947439475394763947739478394793948039481394823948339484394853948639487394883948939490394913949239493394943949539496394973949839499395003950139502395033950439505395063950739508395093951039511395123951339514395153951639517395183951939520395213952239523395243952539526395273952839529395303953139532395333953439535395363953739538395393954039541395423954339544395453954639547395483954939550395513955239553395543955539556395573955839559395603956139562395633956439565395663956739568395693957039571395723957339574395753957639577395783957939580395813958239583395843958539586395873958839589395903959139592395933959439595395963959739598395993960039601396023960339604396053960639607396083960939610396113961239613396143961539616396173961839619396203962139622396233962439625396263962739628396293963039631396323963339634396353963639637396383963939640396413964239643396443964539646396473964839649396503965139652396533965439655396563965739658396593966039661396623966339664396653966639667396683966939670396713967239673396743967539676396773967839679396803968139682396833968439685396863968739688396893969039691396923969339694396953969639697396983969939700397013970239703397043970539706397073970839709397103971139712397133971439715397163971739718397193972039721397223972339724397253972639727397283972939730397313973239733397343973539736397373973839739397403974139742397433974439745397463974739748397493975039751397523975339754397553975639757397583975939760397613976239763397643976539766397673976839769397703977139772397733977439775397763977739778397793978039781397823978339784397853978639787397883978939790397913979239793397943979539796397973979839799398003980139802398033980439805398063980739808398093981039811398123981339814398153981639817398183981939820398213982239823398243982539826398273982839829398303983139832398333983439835398363983739838398393984039841398423984339844398453984639847398483984939850398513985239853398543985539856398573985839859398603986139862398633986439865398663986739868398693987039871398723987339874398753987639877398783987939880398813988239883398843988539886398873988839889398903989139892398933989439895398963989739898398993990039901399023990339904399053990639907399083990939910399113991239913399143991539916399173991839919399203992139922399233992439925399263992739928399293993039931399323993339934399353993639937399383993939940399413994239943399443994539946399473994839949399503995139952399533995439955399563995739958399593996039961399623996339964399653996639967399683996939970399713997239973399743997539976399773997839979399803998139982399833998439985399863998739988399893999039991399923999339994399953999639997399983999940000400014000240003400044000540006400074000840009400104001140012400134001440015400164001740018400194002040021400224002340024400254002640027400284002940030400314003240033400344003540036400374003840039400404004140042400434004440045400464004740048400494005040051400524005340054400554005640057400584005940060400614006240063400644006540066400674006840069400704007140072400734007440075400764007740078400794008040081400824008340084400854008640087400884008940090400914009240093400944009540096400974009840099401004010140102401034010440105401064010740108401094011040111401124011340114401154011640117401184011940120401214012240123401244012540126401274012840129401304013140132401334013440135401364013740138401394014040141401424014340144401454014640147401484014940150401514015240153401544015540156401574015840159401604016140162401634016440165401664016740168401694017040171401724017340174401754017640177401784017940180401814018240183401844018540186401874018840189401904019140192401934019440195401964019740198401994020040201402024020340204402054020640207402084020940210402114021240213402144021540216402174021840219402204022140222402234022440225402264022740228402294023040231402324023340234402354023640237402384023940240402414024240243402444024540246402474024840249402504025140252402534025440255402564025740258402594026040261402624026340264402654026640267402684026940270402714027240273402744027540276402774027840279402804028140282402834028440285402864028740288402894029040291402924029340294402954029640297402984029940300403014030240303403044030540306403074030840309403104031140312403134031440315403164031740318403194032040321403224032340324403254032640327403284032940330403314033240333403344033540336403374033840339403404034140342403434034440345403464034740348403494035040351403524035340354403554035640357403584035940360403614036240363403644036540366403674036840369403704037140372403734037440375403764037740378403794038040381403824038340384403854038640387403884038940390403914039240393403944039540396403974039840399404004040140402404034040440405404064040740408404094041040411404124041340414404154041640417404184041940420404214042240423404244042540426404274042840429404304043140432404334043440435404364043740438404394044040441404424044340444404454044640447404484044940450404514045240453404544045540456404574045840459404604046140462404634046440465404664046740468404694047040471404724047340474404754047640477404784047940480404814048240483404844048540486404874048840489404904049140492404934049440495404964049740498404994050040501405024050340504405054050640507405084050940510405114051240513405144051540516405174051840519405204052140522405234052440525405264052740528405294053040531405324053340534405354053640537405384053940540405414054240543405444054540546405474054840549405504055140552405534055440555405564055740558405594056040561405624056340564405654056640567405684056940570405714057240573405744057540576405774057840579405804058140582405834058440585405864058740588405894059040591405924059340594405954059640597405984059940600406014060240603406044060540606406074060840609406104061140612406134061440615406164061740618406194062040621406224062340624406254062640627406284062940630406314063240633406344063540636406374063840639406404064140642406434064440645406464064740648406494065040651406524065340654406554065640657406584065940660406614066240663406644066540666406674066840669406704067140672406734067440675406764067740678406794068040681406824068340684406854068640687406884068940690406914069240693406944069540696406974069840699407004070140702407034070440705407064070740708407094071040711407124071340714407154071640717407184071940720407214072240723407244072540726407274072840729407304073140732407334073440735407364073740738407394074040741407424074340744407454074640747407484074940750407514075240753407544075540756407574075840759407604076140762407634076440765407664076740768407694077040771407724077340774407754077640777407784077940780407814078240783407844078540786407874078840789407904079140792407934079440795407964079740798407994080040801408024080340804408054080640807408084080940810408114081240813408144081540816408174081840819408204082140822408234082440825408264082740828408294083040831408324083340834408354083640837408384083940840408414084240843408444084540846408474084840849408504085140852408534085440855408564085740858408594086040861408624086340864408654086640867408684086940870408714087240873408744087540876408774087840879408804088140882408834088440885408864088740888408894089040891408924089340894408954089640897408984089940900409014090240903409044090540906409074090840909409104091140912409134091440915409164091740918409194092040921409224092340924409254092640927409284092940930409314093240933409344093540936409374093840939409404094140942409434094440945409464094740948409494095040951409524095340954409554095640957409584095940960409614096240963409644096540966409674096840969409704097140972409734097440975409764097740978409794098040981409824098340984409854098640987409884098940990409914099240993409944099540996409974099840999410004100141002410034100441005410064100741008410094101041011410124101341014410154101641017410184101941020410214102241023410244102541026410274102841029410304103141032410334103441035410364103741038410394104041041410424104341044410454104641047410484104941050410514105241053410544105541056410574105841059410604106141062410634106441065410664106741068410694107041071410724107341074410754107641077410784107941080410814108241083410844108541086410874108841089410904109141092410934109441095410964109741098410994110041101411024110341104411054110641107411084110941110411114111241113411144111541116411174111841119411204112141122411234112441125411264112741128411294113041131411324113341134411354113641137411384113941140411414114241143411444114541146411474114841149411504115141152411534115441155411564115741158411594116041161411624116341164411654116641167411684116941170411714117241173411744117541176411774117841179411804118141182411834118441185411864118741188411894119041191411924119341194411954119641197411984119941200412014120241203412044120541206412074120841209412104121141212412134121441215412164121741218412194122041221412224122341224412254122641227412284122941230412314123241233412344123541236412374123841239412404124141242412434124441245412464124741248412494125041251412524125341254412554125641257412584125941260412614126241263412644126541266412674126841269412704127141272412734127441275412764127741278412794128041281412824128341284412854128641287412884128941290412914129241293412944129541296412974129841299413004130141302413034130441305413064130741308413094131041311413124131341314413154131641317413184131941320413214132241323413244132541326413274132841329413304133141332413334133441335413364133741338413394134041341413424134341344413454134641347413484134941350413514135241353413544135541356413574135841359413604136141362413634136441365413664136741368413694137041371413724137341374413754137641377413784137941380413814138241383413844138541386413874138841389413904139141392413934139441395413964139741398413994140041401414024140341404414054140641407414084140941410414114141241413414144141541416414174141841419414204142141422414234142441425414264142741428414294143041431414324143341434414354143641437414384143941440414414144241443414444144541446414474144841449414504145141452414534145441455414564145741458414594146041461414624146341464414654146641467414684146941470414714147241473414744147541476414774147841479414804148141482414834148441485414864148741488414894149041491414924149341494414954149641497414984149941500415014150241503415044150541506415074150841509415104151141512415134151441515415164151741518415194152041521415224152341524415254152641527415284152941530415314153241533415344153541536415374153841539415404154141542415434154441545415464154741548415494155041551415524155341554415554155641557415584155941560415614156241563415644156541566415674156841569415704157141572415734157441575415764157741578415794158041581415824158341584415854158641587415884158941590415914159241593415944159541596415974159841599416004160141602416034160441605416064160741608416094161041611416124161341614416154161641617416184161941620416214162241623416244162541626416274162841629416304163141632416334163441635416364163741638416394164041641416424164341644416454164641647416484164941650416514165241653416544165541656416574165841659416604166141662416634166441665416664166741668416694167041671416724167341674416754167641677416784167941680416814168241683416844168541686416874168841689416904169141692416934169441695416964169741698416994170041701417024170341704417054170641707417084170941710417114171241713417144171541716417174171841719417204172141722417234172441725417264172741728417294173041731417324173341734417354173641737417384173941740417414174241743417444174541746417474174841749417504175141752417534175441755417564175741758417594176041761417624176341764417654176641767417684176941770417714177241773417744177541776417774177841779417804178141782417834178441785417864178741788417894179041791417924179341794417954179641797417984179941800418014180241803418044180541806418074180841809418104181141812418134181441815418164181741818418194182041821418224182341824418254182641827418284182941830418314183241833418344183541836418374183841839418404184141842418434184441845418464184741848418494185041851418524185341854418554185641857418584185941860418614186241863418644186541866418674186841869418704187141872418734187441875418764187741878418794188041881418824188341884418854188641887418884188941890418914189241893418944189541896418974189841899419004190141902419034190441905419064190741908419094191041911419124191341914419154191641917419184191941920419214192241923419244192541926419274192841929419304193141932419334193441935419364193741938419394194041941419424194341944419454194641947419484194941950419514195241953419544195541956419574195841959419604196141962419634196441965419664196741968419694197041971419724197341974419754197641977419784197941980419814198241983419844198541986419874198841989419904199141992419934199441995419964199741998419994200042001420024200342004420054200642007420084200942010420114201242013420144201542016420174201842019420204202142022420234202442025420264202742028420294203042031420324203342034420354203642037420384203942040420414204242043420444204542046420474204842049420504205142052420534205442055420564205742058420594206042061420624206342064420654206642067420684206942070420714207242073420744207542076420774207842079420804208142082420834208442085420864208742088420894209042091420924209342094420954209642097420984209942100421014210242103421044210542106421074210842109421104211142112421134211442115421164211742118421194212042121421224212342124421254212642127421284212942130421314213242133421344213542136421374213842139421404214142142421434214442145421464214742148421494215042151421524215342154421554215642157421584215942160421614216242163421644216542166421674216842169421704217142172421734217442175421764217742178421794218042181421824218342184421854218642187421884218942190421914219242193421944219542196421974219842199422004220142202422034220442205422064220742208422094221042211422124221342214422154221642217422184221942220422214222242223422244222542226422274222842229422304223142232422334223442235422364223742238422394224042241422424224342244422454224642247422484224942250422514225242253422544225542256422574225842259422604226142262422634226442265422664226742268422694227042271422724227342274422754227642277422784227942280422814228242283422844228542286422874228842289422904229142292422934229442295422964229742298422994230042301423024230342304423054230642307423084230942310423114231242313423144231542316423174231842319423204232142322423234232442325423264232742328423294233042331423324233342334423354233642337423384233942340423414234242343423444234542346423474234842349423504235142352423534235442355423564235742358423594236042361423624236342364423654236642367423684236942370423714237242373423744237542376423774237842379423804238142382423834238442385423864238742388423894239042391423924239342394423954239642397423984239942400424014240242403424044240542406424074240842409424104241142412424134241442415424164241742418424194242042421424224242342424424254242642427424284242942430424314243242433424344243542436424374243842439424404244142442424434244442445424464244742448424494245042451424524245342454424554245642457424584245942460424614246242463424644246542466424674246842469424704247142472424734247442475424764247742478424794248042481424824248342484424854248642487424884248942490424914249242493424944249542496424974249842499425004250142502425034250442505425064250742508425094251042511425124251342514425154251642517425184251942520425214252242523425244252542526425274252842529425304253142532425334253442535425364253742538425394254042541425424254342544425454254642547425484254942550425514255242553425544255542556425574255842559425604256142562425634256442565425664256742568425694257042571425724257342574425754257642577425784257942580425814258242583425844258542586425874258842589425904259142592425934259442595425964259742598425994260042601426024260342604426054260642607426084260942610426114261242613426144261542616426174261842619426204262142622426234262442625426264262742628426294263042631426324263342634426354263642637426384263942640426414264242643426444264542646426474264842649426504265142652426534265442655426564265742658426594266042661426624266342664426654266642667426684266942670426714267242673426744267542676426774267842679426804268142682426834268442685426864268742688426894269042691426924269342694426954269642697426984269942700427014270242703427044270542706427074270842709427104271142712427134271442715427164271742718427194272042721427224272342724427254272642727427284272942730427314273242733427344273542736427374273842739427404274142742427434274442745427464274742748427494275042751427524275342754427554275642757427584275942760427614276242763427644276542766427674276842769427704277142772427734277442775427764277742778427794278042781427824278342784427854278642787427884278942790427914279242793427944279542796427974279842799428004280142802428034280442805428064280742808428094281042811428124281342814428154281642817428184281942820428214282242823428244282542826428274282842829428304283142832428334283442835428364283742838428394284042841428424284342844428454284642847428484284942850428514285242853428544285542856428574285842859428604286142862428634286442865428664286742868428694287042871428724287342874428754287642877428784287942880428814288242883428844288542886428874288842889428904289142892428934289442895428964289742898428994290042901429024290342904429054290642907429084290942910429114291242913429144291542916429174291842919429204292142922429234292442925429264292742928429294293042931429324293342934429354293642937429384293942940429414294242943429444294542946429474294842949429504295142952429534295442955429564295742958429594296042961429624296342964429654296642967429684296942970429714297242973429744297542976429774297842979429804298142982429834298442985429864298742988429894299042991429924299342994429954299642997429984299943000430014300243003430044300543006430074300843009430104301143012430134301443015430164301743018430194302043021430224302343024430254302643027430284302943030430314303243033430344303543036430374303843039430404304143042430434304443045430464304743048430494305043051430524305343054430554305643057430584305943060430614306243063430644306543066430674306843069430704307143072430734307443075430764307743078430794308043081430824308343084430854308643087430884308943090430914309243093430944309543096430974309843099431004310143102431034310443105431064310743108431094311043111431124311343114431154311643117431184311943120431214312243123431244312543126431274312843129431304313143132431334313443135431364313743138431394314043141431424314343144431454314643147431484314943150431514315243153431544315543156431574315843159431604316143162431634316443165431664316743168431694317043171431724317343174431754317643177431784317943180431814318243183431844318543186431874318843189431904319143192431934319443195431964319743198431994320043201432024320343204432054320643207432084320943210432114321243213432144321543216432174321843219432204322143222432234322443225432264322743228432294323043231432324323343234432354323643237432384323943240432414324243243432444324543246432474324843249432504325143252432534325443255432564325743258432594326043261432624326343264432654326643267432684326943270432714327243273432744327543276432774327843279432804328143282432834328443285432864328743288432894329043291432924329343294432954329643297432984329943300433014330243303433044330543306433074330843309433104331143312433134331443315433164331743318433194332043321433224332343324433254332643327433284332943330433314333243333433344333543336433374333843339433404334143342433434334443345433464334743348433494335043351433524335343354433554335643357433584335943360433614336243363433644336543366433674336843369433704337143372433734337443375433764337743378433794338043381433824338343384433854338643387433884338943390433914339243393433944339543396433974339843399434004340143402434034340443405434064340743408434094341043411434124341343414434154341643417434184341943420434214342243423434244342543426434274342843429434304343143432434334343443435434364343743438434394344043441434424344343444434454344643447434484344943450434514345243453434544345543456434574345843459434604346143462434634346443465434664346743468434694347043471434724347343474434754347643477434784347943480434814348243483434844348543486434874348843489434904349143492434934349443495434964349743498434994350043501435024350343504435054350643507435084350943510435114351243513435144351543516435174351843519435204352143522435234352443525435264352743528435294353043531435324353343534435354353643537435384353943540435414354243543435444354543546435474354843549435504355143552435534355443555435564355743558435594356043561435624356343564435654356643567435684356943570435714357243573435744357543576435774357843579435804358143582435834358443585435864358743588435894359043591435924359343594435954359643597435984359943600436014360243603436044360543606436074360843609436104361143612436134361443615436164361743618436194362043621436224362343624436254362643627436284362943630436314363243633436344363543636436374363843639436404364143642436434364443645436464364743648436494365043651436524365343654436554365643657436584365943660436614366243663436644366543666436674366843669436704367143672436734367443675436764367743678436794368043681436824368343684436854368643687436884368943690436914369243693436944369543696436974369843699437004370143702437034370443705437064370743708437094371043711437124371343714437154371643717437184371943720437214372243723437244372543726437274372843729437304373143732437334373443735437364373743738437394374043741437424374343744437454374643747437484374943750437514375243753437544375543756437574375843759437604376143762437634376443765437664376743768437694377043771437724377343774437754377643777437784377943780437814378243783437844378543786437874378843789437904379143792437934379443795437964379743798437994380043801438024380343804438054380643807438084380943810438114381243813438144381543816438174381843819438204382143822438234382443825438264382743828438294383043831438324383343834438354383643837438384383943840438414384243843438444384543846438474384843849438504385143852438534385443855438564385743858438594386043861438624386343864438654386643867438684386943870438714387243873438744387543876438774387843879438804388143882438834388443885438864388743888438894389043891438924389343894438954389643897438984389943900439014390243903439044390543906439074390843909439104391143912439134391443915439164391743918439194392043921439224392343924439254392643927439284392943930439314393243933439344393543936439374393843939439404394143942439434394443945439464394743948439494395043951439524395343954439554395643957439584395943960439614396243963439644396543966439674396843969439704397143972439734397443975439764397743978439794398043981439824398343984439854398643987439884398943990439914399243993439944399543996439974399843999440004400144002440034400444005440064400744008440094401044011440124401344014440154401644017440184401944020440214402244023440244402544026440274402844029440304403144032440334403444035440364403744038440394404044041440424404344044440454404644047440484404944050440514405244053440544405544056440574405844059440604406144062440634406444065440664406744068440694407044071440724407344074440754407644077440784407944080440814408244083440844408544086440874408844089440904409144092440934409444095440964409744098440994410044101441024410344104441054410644107441084410944110441114411244113441144411544116441174411844119441204412144122441234412444125441264412744128441294413044131441324413344134441354413644137441384413944140441414414244143441444414544146441474414844149441504415144152441534415444155441564415744158441594416044161441624416344164441654416644167441684416944170441714417244173441744417544176441774417844179441804418144182441834418444185441864418744188441894419044191441924419344194441954419644197441984419944200442014420244203442044420544206442074420844209442104421144212442134421444215442164421744218442194422044221442224422344224442254422644227442284422944230442314423244233442344423544236442374423844239442404424144242442434424444245442464424744248442494425044251442524425344254442554425644257442584425944260442614426244263442644426544266442674426844269442704427144272442734427444275442764427744278442794428044281442824428344284442854428644287442884428944290442914429244293442944429544296442974429844299443004430144302443034430444305443064430744308443094431044311443124431344314443154431644317443184431944320443214432244323443244432544326443274432844329443304433144332443334433444335443364433744338443394434044341443424434344344443454434644347443484434944350443514435244353443544435544356443574435844359443604436144362443634436444365443664436744368443694437044371443724437344374443754437644377443784437944380443814438244383443844438544386443874438844389443904439144392443934439444395443964439744398443994440044401444024440344404444054440644407444084440944410444114441244413444144441544416444174441844419444204442144422444234442444425444264442744428444294443044431444324443344434444354443644437444384443944440444414444244443444444444544446444474444844449444504445144452444534445444455444564445744458444594446044461444624446344464444654446644467444684446944470444714447244473444744447544476444774447844479444804448144482444834448444485444864448744488444894449044491444924449344494444954449644497444984449944500445014450244503445044450544506445074450844509445104451144512445134451444515445164451744518445194452044521445224452344524445254452644527445284452944530445314453244533445344453544536445374453844539445404454144542445434454444545445464454744548445494455044551445524455344554445554455644557445584455944560445614456244563445644456544566445674456844569445704457144572445734457444575445764457744578445794458044581445824458344584445854458644587445884458944590445914459244593445944459544596445974459844599446004460144602446034460444605446064460744608446094461044611446124461344614446154461644617446184461944620446214462244623446244462544626446274462844629446304463144632446334463444635446364463744638446394464044641446424464344644446454464644647446484464944650446514465244653446544465544656446574465844659446604466144662446634466444665446664466744668446694467044671446724467344674446754467644677446784467944680446814468244683446844468544686446874468844689446904469144692446934469444695446964469744698446994470044701447024470344704447054470644707447084470944710447114471244713447144471544716447174471844719447204472144722447234472444725447264472744728447294473044731447324473344734447354473644737447384473944740447414474244743447444474544746447474474844749447504475144752447534475444755447564475744758447594476044761447624476344764447654476644767447684476944770447714477244773447744477544776447774477844779447804478144782447834478444785447864478744788447894479044791447924479344794447954479644797447984479944800448014480244803448044480544806448074480844809448104481144812448134481444815448164481744818448194482044821448224482344824448254482644827448284482944830448314483244833448344483544836448374483844839448404484144842448434484444845448464484744848448494485044851448524485344854448554485644857448584485944860448614486244863448644486544866448674486844869448704487144872448734487444875448764487744878448794488044881448824488344884448854488644887448884488944890448914489244893448944489544896448974489844899449004490144902449034490444905449064490744908449094491044911449124491344914449154491644917449184491944920449214492244923449244492544926449274492844929449304493144932449334493444935449364493744938449394494044941449424494344944449454494644947449484494944950449514495244953449544495544956449574495844959449604496144962449634496444965449664496744968449694497044971449724497344974449754497644977449784497944980449814498244983449844498544986449874498844989449904499144992449934499444995449964499744998449994500045001450024500345004450054500645007450084500945010450114501245013450144501545016450174501845019450204502145022450234502445025450264502745028450294503045031450324503345034450354503645037450384503945040450414504245043450444504545046450474504845049450504505145052450534505445055450564505745058450594506045061450624506345064450654506645067450684506945070450714507245073450744507545076450774507845079450804508145082450834508445085450864508745088450894509045091450924509345094450954509645097450984509945100451014510245103451044510545106451074510845109451104511145112451134511445115451164511745118451194512045121451224512345124451254512645127451284512945130451314513245133451344513545136451374513845139451404514145142451434514445145451464514745148451494515045151451524515345154451554515645157451584515945160451614516245163451644516545166451674516845169451704517145172451734517445175451764517745178451794518045181451824518345184451854518645187451884518945190451914519245193451944519545196451974519845199452004520145202452034520445205452064520745208452094521045211452124521345214452154521645217452184521945220452214522245223452244522545226452274522845229452304523145232452334523445235452364523745238452394524045241452424524345244452454524645247452484524945250452514525245253452544525545256452574525845259452604526145262452634526445265452664526745268452694527045271452724527345274452754527645277452784527945280452814528245283452844528545286452874528845289452904529145292452934529445295452964529745298452994530045301453024530345304453054530645307453084530945310453114531245313453144531545316453174531845319453204532145322453234532445325453264532745328453294533045331453324533345334453354533645337453384533945340453414534245343453444534545346453474534845349453504535145352453534535445355453564535745358453594536045361453624536345364453654536645367453684536945370453714537245373453744537545376453774537845379453804538145382453834538445385453864538745388453894539045391453924539345394453954539645397453984539945400454014540245403454044540545406454074540845409454104541145412454134541445415454164541745418454194542045421454224542345424454254542645427454284542945430454314543245433454344543545436454374543845439454404544145442454434544445445454464544745448454494545045451454524545345454454554545645457454584545945460454614546245463454644546545466454674546845469454704547145472454734547445475454764547745478454794548045481454824548345484454854548645487454884548945490454914549245493454944549545496454974549845499455004550145502455034550445505455064550745508455094551045511455124551345514455154551645517455184551945520455214552245523455244552545526455274552845529455304553145532455334553445535455364553745538455394554045541455424554345544455454554645547455484554945550455514555245553455544555545556455574555845559455604556145562455634556445565455664556745568455694557045571455724557345574455754557645577455784557945580455814558245583455844558545586455874558845589455904559145592455934559445595455964559745598455994560045601456024560345604456054560645607456084560945610456114561245613456144561545616456174561845619456204562145622456234562445625456264562745628456294563045631456324563345634456354563645637456384563945640456414564245643456444564545646456474564845649456504565145652456534565445655456564565745658456594566045661456624566345664456654566645667456684566945670456714567245673456744567545676456774567845679456804568145682456834568445685456864568745688456894569045691456924569345694456954569645697456984569945700457014570245703457044570545706457074570845709457104571145712457134571445715457164571745718457194572045721457224572345724457254572645727457284572945730457314573245733457344573545736457374573845739457404574145742457434574445745457464574745748457494575045751457524575345754457554575645757457584575945760457614576245763457644576545766457674576845769457704577145772457734577445775457764577745778457794578045781457824578345784457854578645787457884578945790457914579245793457944579545796457974579845799458004580145802458034580445805458064580745808458094581045811458124581345814458154581645817458184581945820458214582245823458244582545826458274582845829458304583145832458334583445835458364583745838458394584045841458424584345844458454584645847458484584945850458514585245853458544585545856458574585845859458604586145862458634586445865458664586745868458694587045871458724587345874458754587645877458784587945880458814588245883458844588545886458874588845889458904589145892458934589445895458964589745898458994590045901459024590345904459054590645907459084590945910459114591245913459144591545916459174591845919459204592145922459234592445925459264592745928459294593045931459324593345934459354593645937459384593945940459414594245943459444594545946459474594845949459504595145952459534595445955459564595745958459594596045961459624596345964459654596645967459684596945970459714597245973459744597545976459774597845979459804598145982459834598445985459864598745988459894599045991459924599345994459954599645997459984599946000460014600246003460044600546006460074600846009460104601146012460134601446015460164601746018460194602046021460224602346024460254602646027460284602946030460314603246033460344603546036460374603846039460404604146042460434604446045460464604746048460494605046051460524605346054460554605646057460584605946060460614606246063460644606546066460674606846069460704607146072460734607446075460764607746078460794608046081460824608346084460854608646087460884608946090460914609246093460944609546096460974609846099461004610146102461034610446105461064610746108461094611046111461124611346114461154611646117461184611946120461214612246123461244612546126461274612846129461304613146132461334613446135461364613746138461394614046141461424614346144461454614646147461484614946150461514615246153461544615546156461574615846159461604616146162461634616446165461664616746168461694617046171461724617346174461754617646177461784617946180461814618246183461844618546186461874618846189461904619146192461934619446195461964619746198461994620046201462024620346204462054620646207462084620946210462114621246213462144621546216462174621846219462204622146222462234622446225462264622746228462294623046231462324623346234462354623646237462384623946240462414624246243462444624546246462474624846249462504625146252462534625446255462564625746258462594626046261462624626346264462654626646267462684626946270462714627246273462744627546276462774627846279462804628146282462834628446285462864628746288462894629046291462924629346294462954629646297462984629946300463014630246303463044630546306463074630846309463104631146312463134631446315463164631746318463194632046321463224632346324463254632646327463284632946330463314633246333463344633546336463374633846339463404634146342463434634446345463464634746348463494635046351463524635346354463554635646357463584635946360463614636246363463644636546366463674636846369463704637146372463734637446375463764637746378463794638046381463824638346384463854638646387463884638946390463914639246393463944639546396463974639846399464004640146402464034640446405464064640746408464094641046411464124641346414464154641646417464184641946420464214642246423464244642546426464274642846429464304643146432464334643446435464364643746438464394644046441464424644346444464454644646447464484644946450464514645246453464544645546456464574645846459464604646146462464634646446465464664646746468464694647046471464724647346474464754647646477464784647946480464814648246483464844648546486464874648846489464904649146492464934649446495464964649746498464994650046501465024650346504465054650646507465084650946510465114651246513465144651546516465174651846519465204652146522465234652446525465264652746528465294653046531465324653346534465354653646537465384653946540465414654246543465444654546546465474654846549465504655146552465534655446555465564655746558465594656046561465624656346564465654656646567465684656946570465714657246573465744657546576465774657846579465804658146582465834658446585465864658746588465894659046591465924659346594465954659646597465984659946600466014660246603466044660546606466074660846609466104661146612466134661446615466164661746618466194662046621466224662346624466254662646627466284662946630466314663246633466344663546636466374663846639466404664146642466434664446645466464664746648466494665046651466524665346654466554665646657466584665946660466614666246663466644666546666466674666846669466704667146672466734667446675466764667746678466794668046681466824668346684466854668646687466884668946690466914669246693466944669546696466974669846699467004670146702467034670446705467064670746708467094671046711467124671346714467154671646717467184671946720467214672246723467244672546726467274672846729467304673146732467334673446735467364673746738467394674046741467424674346744467454674646747467484674946750467514675246753467544675546756467574675846759467604676146762467634676446765467664676746768467694677046771467724677346774467754677646777467784677946780467814678246783467844678546786467874678846789467904679146792467934679446795467964679746798467994680046801468024680346804468054680646807468084680946810468114681246813468144681546816468174681846819468204682146822468234682446825468264682746828468294683046831468324683346834468354683646837468384683946840468414684246843468444684546846468474684846849468504685146852468534685446855468564685746858468594686046861468624686346864468654686646867468684686946870468714687246873468744687546876468774687846879468804688146882468834688446885468864688746888468894689046891468924689346894468954689646897468984689946900469014690246903469044690546906469074690846909469104691146912469134691446915469164691746918469194692046921469224692346924469254692646927469284692946930469314693246933469344693546936469374693846939469404694146942469434694446945469464694746948469494695046951469524695346954469554695646957469584695946960469614696246963469644696546966469674696846969469704697146972469734697446975469764697746978469794698046981469824698346984469854698646987469884698946990469914699246993469944699546996469974699846999470004700147002470034700447005470064700747008470094701047011470124701347014470154701647017470184701947020470214702247023470244702547026470274702847029470304703147032470334703447035470364703747038470394704047041470424704347044470454704647047470484704947050470514705247053470544705547056470574705847059470604706147062470634706447065470664706747068470694707047071470724707347074470754707647077470784707947080470814708247083470844708547086470874708847089470904709147092470934709447095470964709747098470994710047101471024710347104471054710647107471084710947110471114711247113471144711547116471174711847119471204712147122471234712447125471264712747128471294713047131471324713347134471354713647137471384713947140471414714247143471444714547146471474714847149471504715147152471534715447155471564715747158471594716047161471624716347164471654716647167471684716947170471714717247173471744717547176471774717847179471804718147182471834718447185471864718747188471894719047191471924719347194471954719647197471984719947200472014720247203472044720547206472074720847209472104721147212472134721447215472164721747218472194722047221472224722347224472254722647227472284722947230472314723247233472344723547236472374723847239472404724147242472434724447245472464724747248472494725047251472524725347254472554725647257472584725947260472614726247263472644726547266472674726847269472704727147272472734727447275472764727747278472794728047281472824728347284472854728647287472884728947290472914729247293472944729547296472974729847299473004730147302473034730447305473064730747308473094731047311473124731347314473154731647317473184731947320473214732247323473244732547326473274732847329473304733147332473334733447335473364733747338473394734047341473424734347344473454734647347473484734947350473514735247353473544735547356473574735847359473604736147362473634736447365473664736747368473694737047371473724737347374473754737647377473784737947380473814738247383473844738547386473874738847389473904739147392473934739447395473964739747398473994740047401474024740347404474054740647407474084740947410474114741247413474144741547416474174741847419474204742147422474234742447425474264742747428474294743047431474324743347434474354743647437474384743947440474414744247443474444744547446474474744847449474504745147452474534745447455474564745747458474594746047461474624746347464474654746647467474684746947470474714747247473474744747547476474774747847479474804748147482474834748447485474864748747488474894749047491474924749347494474954749647497474984749947500475014750247503475044750547506475074750847509475104751147512475134751447515475164751747518475194752047521475224752347524475254752647527475284752947530475314753247533475344753547536475374753847539475404754147542475434754447545475464754747548475494755047551475524755347554475554755647557475584755947560475614756247563475644756547566475674756847569475704757147572475734757447575475764757747578475794758047581475824758347584475854758647587475884758947590475914759247593475944759547596475974759847599476004760147602476034760447605476064760747608476094761047611476124761347614476154761647617476184761947620476214762247623476244762547626476274762847629476304763147632476334763447635476364763747638476394764047641476424764347644476454764647647476484764947650476514765247653476544765547656476574765847659476604766147662476634766447665476664766747668476694767047671476724767347674476754767647677476784767947680476814768247683476844768547686476874768847689476904769147692476934769447695476964769747698476994770047701477024770347704477054770647707477084770947710477114771247713477144771547716477174771847719477204772147722477234772447725477264772747728477294773047731477324773347734477354773647737477384773947740477414774247743477444774547746477474774847749477504775147752477534775447755477564775747758477594776047761477624776347764477654776647767477684776947770477714777247773477744777547776477774777847779477804778147782477834778447785477864778747788477894779047791477924779347794477954779647797477984779947800478014780247803478044780547806478074780847809478104781147812478134781447815478164781747818478194782047821478224782347824478254782647827478284782947830478314783247833478344783547836478374783847839478404784147842478434784447845478464784747848478494785047851478524785347854478554785647857478584785947860478614786247863478644786547866478674786847869478704787147872478734787447875478764787747878478794788047881478824788347884478854788647887478884788947890478914789247893478944789547896478974789847899479004790147902479034790447905479064790747908479094791047911479124791347914479154791647917479184791947920479214792247923479244792547926479274792847929479304793147932479334793447935479364793747938479394794047941479424794347944479454794647947479484794947950479514795247953479544795547956479574795847959479604796147962479634796447965479664796747968479694797047971479724797347974479754797647977479784797947980479814798247983479844798547986479874798847989479904799147992479934799447995479964799747998479994800048001480024800348004480054800648007480084800948010480114801248013480144801548016480174801848019480204802148022480234802448025480264802748028480294803048031480324803348034480354803648037480384803948040480414804248043480444804548046480474804848049480504805148052480534805448055480564805748058480594806048061480624806348064480654806648067480684806948070480714807248073480744807548076480774807848079480804808148082480834808448085480864808748088480894809048091480924809348094480954809648097480984809948100481014810248103481044810548106481074810848109481104811148112481134811448115481164811748118481194812048121481224812348124481254812648127481284812948130481314813248133481344813548136481374813848139481404814148142481434814448145481464814748148481494815048151481524815348154481554815648157481584815948160481614816248163481644816548166481674816848169481704817148172481734817448175481764817748178481794818048181481824818348184481854818648187481884818948190481914819248193481944819548196481974819848199482004820148202482034820448205482064820748208482094821048211482124821348214482154821648217482184821948220482214822248223482244822548226482274822848229482304823148232482334823448235482364823748238482394824048241482424824348244482454824648247482484824948250482514825248253482544825548256482574825848259482604826148262482634826448265482664826748268482694827048271482724827348274482754827648277482784827948280482814828248283482844828548286482874828848289482904829148292482934829448295482964829748298482994830048301483024830348304483054830648307483084830948310483114831248313483144831548316483174831848319483204832148322483234832448325483264832748328483294833048331483324833348334483354833648337483384833948340483414834248343483444834548346483474834848349483504835148352483534835448355483564835748358483594836048361483624836348364483654836648367483684836948370483714837248373483744837548376483774837848379483804838148382483834838448385483864838748388483894839048391483924839348394483954839648397483984839948400484014840248403484044840548406484074840848409484104841148412484134841448415484164841748418484194842048421484224842348424484254842648427484284842948430484314843248433484344843548436484374843848439484404844148442484434844448445484464844748448484494845048451484524845348454484554845648457484584845948460484614846248463484644846548466484674846848469484704847148472484734847448475484764847748478484794848048481484824848348484484854848648487484884848948490484914849248493484944849548496484974849848499485004850148502485034850448505485064850748508485094851048511485124851348514485154851648517485184851948520485214852248523485244852548526485274852848529485304853148532485334853448535485364853748538485394854048541485424854348544485454854648547485484854948550485514855248553485544855548556485574855848559485604856148562485634856448565485664856748568485694857048571485724857348574485754857648577485784857948580485814858248583485844858548586485874858848589485904859148592485934859448595485964859748598485994860048601486024860348604486054860648607486084860948610486114861248613486144861548616486174861848619486204862148622486234862448625486264862748628486294863048631486324863348634486354863648637486384863948640486414864248643486444864548646486474864848649486504865148652486534865448655486564865748658486594866048661486624866348664486654866648667486684866948670486714867248673486744867548676486774867848679486804868148682486834868448685486864868748688486894869048691486924869348694486954869648697486984869948700487014870248703487044870548706487074870848709487104871148712487134871448715487164871748718487194872048721487224872348724487254872648727487284872948730487314873248733487344873548736487374873848739487404874148742487434874448745487464874748748487494875048751487524875348754487554875648757487584875948760487614876248763487644876548766487674876848769487704877148772487734877448775487764877748778487794878048781487824878348784487854878648787487884878948790487914879248793487944879548796487974879848799488004880148802488034880448805488064880748808488094881048811488124881348814488154881648817488184881948820488214882248823488244882548826488274882848829488304883148832488334883448835488364883748838488394884048841488424884348844488454884648847488484884948850488514885248853488544885548856488574885848859488604886148862488634886448865488664886748868488694887048871488724887348874488754887648877488784887948880488814888248883488844888548886488874888848889488904889148892488934889448895488964889748898488994890048901489024890348904489054890648907489084890948910489114891248913489144891548916489174891848919489204892148922489234892448925489264892748928489294893048931489324893348934489354893648937489384893948940489414894248943489444894548946489474894848949489504895148952489534895448955489564895748958489594896048961489624896348964489654896648967489684896948970489714897248973489744897548976489774897848979489804898148982489834898448985489864898748988489894899048991489924899348994489954899648997489984899949000490014900249003490044900549006490074900849009490104901149012490134901449015490164901749018490194902049021490224902349024490254902649027490284902949030490314903249033490344903549036490374903849039490404904149042490434904449045490464904749048490494905049051490524905349054490554905649057490584905949060490614906249063490644906549066490674906849069490704907149072490734907449075490764907749078490794908049081490824908349084490854908649087490884908949090490914909249093490944909549096490974909849099491004910149102491034910449105491064910749108491094911049111491124911349114491154911649117491184911949120491214912249123491244912549126491274912849129491304913149132491334913449135491364913749138491394914049141491424914349144491454914649147491484914949150491514915249153491544915549156491574915849159491604916149162491634916449165491664916749168491694917049171491724917349174491754917649177491784917949180491814918249183491844918549186491874918849189491904919149192491934919449195491964919749198491994920049201492024920349204492054920649207492084920949210492114921249213492144921549216492174921849219492204922149222492234922449225492264922749228492294923049231492324923349234492354923649237492384923949240492414924249243492444924549246492474924849249492504925149252492534925449255492564925749258492594926049261492624926349264492654926649267492684926949270492714927249273492744927549276492774927849279492804928149282492834928449285492864928749288492894929049291492924929349294492954929649297492984929949300493014930249303493044930549306493074930849309493104931149312493134931449315493164931749318493194932049321493224932349324493254932649327493284932949330493314933249333493344933549336493374933849339493404934149342493434934449345493464934749348493494935049351493524935349354493554935649357493584935949360493614936249363493644936549366493674936849369493704937149372493734937449375493764937749378493794938049381493824938349384493854938649387493884938949390493914939249393493944939549396493974939849399494004940149402494034940449405494064940749408494094941049411494124941349414494154941649417494184941949420494214942249423494244942549426494274942849429494304943149432494334943449435494364943749438494394944049441494424944349444494454944649447494484944949450494514945249453494544945549456494574945849459494604946149462494634946449465494664946749468494694947049471494724947349474494754947649477494784947949480494814948249483494844948549486494874948849489494904949149492494934949449495494964949749498494994950049501495024950349504495054950649507495084950949510495114951249513495144951549516495174951849519495204952149522495234952449525495264952749528495294953049531495324953349534495354953649537495384953949540495414954249543495444954549546495474954849549495504955149552495534955449555495564955749558495594956049561495624956349564495654956649567495684956949570495714957249573495744957549576495774957849579495804958149582495834958449585495864958749588495894959049591495924959349594495954959649597495984959949600496014960249603496044960549606496074960849609496104961149612496134961449615496164961749618496194962049621496224962349624496254962649627496284962949630496314963249633496344963549636496374963849639496404964149642496434964449645496464964749648496494965049651496524965349654496554965649657496584965949660496614966249663496644966549666496674966849669496704967149672496734967449675496764967749678496794968049681496824968349684496854968649687496884968949690496914969249693496944969549696496974969849699497004970149702497034970449705497064970749708497094971049711497124971349714497154971649717497184971949720497214972249723497244972549726497274972849729497304973149732497334973449735497364973749738497394974049741497424974349744497454974649747497484974949750497514975249753497544975549756497574975849759497604976149762497634976449765497664976749768497694977049771497724977349774497754977649777497784977949780497814978249783497844978549786497874978849789497904979149792497934979449795497964979749798497994980049801498024980349804498054980649807498084980949810498114981249813498144981549816498174981849819498204982149822498234982449825498264982749828498294983049831498324983349834498354983649837498384983949840498414984249843498444984549846498474984849849498504985149852498534985449855498564985749858498594986049861498624986349864498654986649867498684986949870498714987249873498744987549876498774987849879498804988149882498834988449885498864988749888498894989049891498924989349894498954989649897498984989949900499014990249903499044990549906499074990849909499104991149912499134991449915499164991749918499194992049921499224992349924499254992649927499284992949930499314993249933499344993549936499374993849939499404994149942499434994449945499464994749948499494995049951499524995349954499554995649957499584995949960499614996249963499644996549966499674996849969499704997149972499734997449975499764997749978499794998049981499824998349984499854998649987499884998949990499914999249993499944999549996499974999849999500005000150002500035000450005500065000750008500095001050011500125001350014500155001650017500185001950020500215002250023500245002550026500275002850029500305003150032500335003450035500365003750038500395004050041500425004350044500455004650047500485004950050500515005250053500545005550056500575005850059500605006150062500635006450065500665006750068500695007050071500725007350074500755007650077500785007950080500815008250083500845008550086500875008850089500905009150092500935009450095500965009750098500995010050101501025010350104501055010650107501085010950110501115011250113501145011550116501175011850119501205012150122501235012450125501265012750128501295013050131501325013350134501355013650137501385013950140501415014250143501445014550146501475014850149501505015150152501535015450155501565015750158501595016050161501625016350164501655016650167501685016950170501715017250173501745017550176501775017850179501805018150182501835018450185501865018750188501895019050191501925019350194501955019650197501985019950200502015020250203502045020550206502075020850209502105021150212502135021450215502165021750218502195022050221502225022350224502255022650227502285022950230502315023250233502345023550236502375023850239502405024150242502435024450245502465024750248502495025050251502525025350254502555025650257502585025950260502615026250263502645026550266502675026850269502705027150272502735027450275502765027750278502795028050281502825028350284502855028650287502885028950290502915029250293502945029550296502975029850299503005030150302503035030450305503065030750308503095031050311503125031350314503155031650317503185031950320503215032250323503245032550326503275032850329503305033150332503335033450335503365033750338503395034050341503425034350344503455034650347503485034950350503515035250353503545035550356503575035850359503605036150362503635036450365503665036750368503695037050371503725037350374503755037650377503785037950380503815038250383503845038550386503875038850389503905039150392503935039450395503965039750398503995040050401504025040350404504055040650407504085040950410504115041250413504145041550416504175041850419504205042150422504235042450425504265042750428504295043050431504325043350434504355043650437504385043950440504415044250443504445044550446504475044850449504505045150452504535045450455504565045750458504595046050461504625046350464504655046650467504685046950470504715047250473504745047550476504775047850479504805048150482504835048450485504865048750488504895049050491504925049350494504955049650497504985049950500505015050250503505045050550506505075050850509505105051150512505135051450515505165051750518505195052050521505225052350524505255052650527505285052950530505315053250533505345053550536505375053850539505405054150542505435054450545505465054750548505495055050551505525055350554505555055650557505585055950560505615056250563505645056550566505675056850569505705057150572505735057450575505765057750578505795058050581505825058350584505855058650587505885058950590505915059250593505945059550596505975059850599506005060150602506035060450605506065060750608506095061050611506125061350614506155061650617506185061950620506215062250623506245062550626506275062850629506305063150632506335063450635506365063750638506395064050641506425064350644506455064650647506485064950650506515065250653506545065550656506575065850659506605066150662506635066450665506665066750668506695067050671506725067350674506755067650677506785067950680506815068250683506845068550686506875068850689506905069150692506935069450695506965069750698506995070050701507025070350704507055070650707507085070950710507115071250713507145071550716507175071850719507205072150722507235072450725507265072750728507295073050731507325073350734507355073650737507385073950740507415074250743507445074550746507475074850749507505075150752507535075450755507565075750758507595076050761507625076350764507655076650767507685076950770507715077250773507745077550776507775077850779507805078150782507835078450785507865078750788507895079050791507925079350794507955079650797507985079950800508015080250803508045080550806508075080850809508105081150812508135081450815508165081750818508195082050821508225082350824508255082650827508285082950830508315083250833508345083550836508375083850839508405084150842508435084450845508465084750848508495085050851508525085350854508555085650857508585085950860508615086250863508645086550866508675086850869508705087150872508735087450875508765087750878508795088050881508825088350884508855088650887508885088950890508915089250893508945089550896508975089850899509005090150902509035090450905509065090750908509095091050911509125091350914509155091650917509185091950920509215092250923509245092550926509275092850929509305093150932509335093450935509365093750938509395094050941509425094350944509455094650947509485094950950509515095250953509545095550956509575095850959509605096150962509635096450965509665096750968509695097050971509725097350974509755097650977509785097950980509815098250983509845098550986509875098850989509905099150992509935099450995509965099750998509995100051001510025100351004510055100651007510085100951010510115101251013510145101551016510175101851019510205102151022510235102451025510265102751028510295103051031510325103351034510355103651037510385103951040510415104251043510445104551046510475104851049510505105151052510535105451055510565105751058510595106051061510625106351064510655106651067510685106951070510715107251073510745107551076510775107851079510805108151082510835108451085510865108751088510895109051091510925109351094510955109651097510985109951100511015110251103511045110551106511075110851109511105111151112511135111451115511165111751118511195112051121511225112351124511255112651127511285112951130511315113251133511345113551136511375113851139511405114151142511435114451145511465114751148511495115051151511525115351154511555115651157511585115951160511615116251163511645116551166511675116851169511705117151172511735117451175511765117751178511795118051181511825118351184511855118651187511885118951190511915119251193511945119551196511975119851199512005120151202512035120451205512065120751208512095121051211512125121351214512155121651217512185121951220512215122251223512245122551226512275122851229512305123151232512335123451235512365123751238512395124051241512425124351244512455124651247512485124951250512515125251253512545125551256512575125851259512605126151262512635126451265512665126751268512695127051271512725127351274512755127651277512785127951280512815128251283512845128551286512875128851289512905129151292512935129451295512965129751298512995130051301513025130351304513055130651307513085130951310513115131251313513145131551316513175131851319513205132151322513235132451325513265132751328513295133051331513325133351334513355133651337513385133951340513415134251343513445134551346513475134851349513505135151352513535135451355513565135751358513595136051361513625136351364513655136651367513685136951370513715137251373513745137551376513775137851379513805138151382513835138451385513865138751388513895139051391513925139351394513955139651397513985139951400514015140251403514045140551406514075140851409514105141151412514135141451415514165141751418514195142051421514225142351424514255142651427514285142951430514315143251433514345143551436514375143851439514405144151442514435144451445514465144751448514495145051451514525145351454514555145651457514585145951460514615146251463514645146551466514675146851469514705147151472514735147451475514765147751478514795148051481514825148351484514855148651487514885148951490514915149251493514945149551496514975149851499515005150151502515035150451505515065150751508515095151051511515125151351514515155151651517515185151951520515215152251523515245152551526515275152851529515305153151532515335153451535515365153751538515395154051541515425154351544515455154651547515485154951550515515155251553515545155551556515575155851559515605156151562515635156451565515665156751568515695157051571515725157351574515755157651577515785157951580515815158251583515845158551586515875158851589515905159151592515935159451595515965159751598515995160051601516025160351604516055160651607516085160951610516115161251613516145161551616516175161851619516205162151622516235162451625516265162751628516295163051631516325163351634516355163651637516385163951640516415164251643516445164551646516475164851649516505165151652516535165451655516565165751658516595166051661516625166351664516655166651667516685166951670516715167251673516745167551676516775167851679516805168151682516835168451685516865168751688516895169051691516925169351694516955169651697516985169951700517015170251703517045170551706517075170851709517105171151712517135171451715517165171751718517195172051721517225172351724517255172651727517285172951730517315173251733517345173551736517375173851739517405174151742517435174451745517465174751748517495175051751517525175351754517555175651757517585175951760517615176251763517645176551766517675176851769517705177151772517735177451775517765177751778517795178051781517825178351784517855178651787517885178951790517915179251793517945179551796517975179851799518005180151802518035180451805518065180751808518095181051811518125181351814518155181651817518185181951820518215182251823518245182551826518275182851829518305183151832518335183451835518365183751838518395184051841518425184351844518455184651847518485184951850518515185251853518545185551856518575185851859518605186151862518635186451865518665186751868518695187051871518725187351874518755187651877518785187951880518815188251883518845188551886518875188851889518905189151892518935189451895518965189751898518995190051901519025190351904519055190651907519085190951910519115191251913519145191551916519175191851919519205192151922519235192451925519265192751928519295193051931519325193351934519355193651937519385193951940519415194251943519445194551946519475194851949519505195151952519535195451955519565195751958519595196051961519625196351964519655196651967519685196951970519715197251973519745197551976519775197851979519805198151982519835198451985519865198751988519895199051991519925199351994519955199651997519985199952000520015200252003520045200552006520075200852009520105201152012520135201452015520165201752018520195202052021520225202352024520255202652027520285202952030520315203252033520345203552036520375203852039520405204152042520435204452045520465204752048520495205052051520525205352054520555205652057520585205952060520615206252063520645206552066520675206852069520705207152072520735207452075520765207752078520795208052081520825208352084520855208652087520885208952090520915209252093520945209552096520975209852099521005210152102521035210452105521065210752108521095211052111521125211352114521155211652117521185211952120521215212252123521245212552126521275212852129521305213152132521335213452135521365213752138521395214052141521425214352144521455214652147521485214952150521515215252153521545215552156521575215852159521605216152162521635216452165521665216752168521695217052171521725217352174521755217652177521785217952180521815218252183521845218552186521875218852189521905219152192521935219452195521965219752198521995220052201522025220352204522055220652207522085220952210522115221252213522145221552216522175221852219522205222152222522235222452225522265222752228522295223052231522325223352234522355223652237522385223952240522415224252243522445224552246522475224852249522505225152252522535225452255522565225752258522595226052261522625226352264522655226652267522685226952270522715227252273522745227552276522775227852279522805228152282522835228452285522865228752288522895229052291522925229352294522955229652297522985229952300523015230252303523045230552306523075230852309523105231152312523135231452315523165231752318523195232052321523225232352324523255232652327523285232952330523315233252333523345233552336523375233852339523405234152342523435234452345523465234752348523495235052351523525235352354523555235652357523585235952360523615236252363523645236552366523675236852369523705237152372523735237452375523765237752378523795238052381523825238352384523855238652387523885238952390523915239252393523945239552396523975239852399524005240152402524035240452405524065240752408524095241052411524125241352414524155241652417524185241952420524215242252423524245242552426524275242852429524305243152432524335243452435524365243752438524395244052441524425244352444524455244652447524485244952450524515245252453524545245552456524575245852459524605246152462524635246452465524665246752468524695247052471524725247352474524755247652477524785247952480524815248252483524845248552486524875248852489524905249152492524935249452495524965249752498524995250052501525025250352504525055250652507525085250952510525115251252513525145251552516525175251852519525205252152522525235252452525525265252752528525295253052531525325253352534525355253652537525385253952540525415254252543525445254552546525475254852549525505255152552525535255452555525565255752558525595256052561525625256352564525655256652567525685256952570525715257252573525745257552576525775257852579525805258152582525835258452585525865258752588525895259052591525925259352594525955259652597525985259952600526015260252603526045260552606526075260852609526105261152612526135261452615526165261752618526195262052621526225262352624526255262652627526285262952630526315263252633526345263552636526375263852639526405264152642526435264452645526465264752648526495265052651526525265352654526555265652657526585265952660526615266252663526645266552666526675266852669526705267152672526735267452675526765267752678526795268052681526825268352684526855268652687526885268952690526915269252693526945269552696526975269852699527005270152702527035270452705527065270752708527095271052711527125271352714527155271652717527185271952720527215272252723527245272552726527275272852729527305273152732527335273452735527365273752738527395274052741527425274352744527455274652747527485274952750527515275252753527545275552756527575275852759527605276152762527635276452765527665276752768527695277052771527725277352774527755277652777527785277952780527815278252783527845278552786527875278852789527905279152792527935279452795527965279752798527995280052801528025280352804528055280652807528085280952810528115281252813528145281552816528175281852819528205282152822528235282452825528265282752828528295283052831528325283352834528355283652837528385283952840528415284252843528445284552846528475284852849528505285152852528535285452855528565285752858528595286052861528625286352864528655286652867528685286952870528715287252873528745287552876528775287852879528805288152882528835288452885528865288752888528895289052891528925289352894528955289652897528985289952900529015290252903529045290552906529075290852909529105291152912529135291452915529165291752918529195292052921529225292352924529255292652927529285292952930529315293252933529345293552936529375293852939529405294152942529435294452945529465294752948529495295052951529525295352954529555295652957529585295952960529615296252963529645296552966529675296852969529705297152972529735297452975529765297752978529795298052981529825298352984529855298652987529885298952990529915299252993529945299552996529975299852999530005300153002530035300453005530065300753008530095301053011530125301353014530155301653017530185301953020530215302253023530245302553026530275302853029530305303153032530335303453035530365303753038530395304053041530425304353044530455304653047530485304953050530515305253053530545305553056530575305853059530605306153062530635306453065530665306753068530695307053071530725307353074530755307653077530785307953080530815308253083530845308553086530875308853089530905309153092530935309453095530965309753098530995310053101531025310353104531055310653107531085310953110531115311253113531145311553116531175311853119531205312153122531235312453125531265312753128531295313053131531325313353134531355313653137531385313953140531415314253143531445314553146531475314853149531505315153152531535315453155531565315753158531595316053161531625316353164531655316653167531685316953170531715317253173531745317553176531775317853179531805318153182531835318453185531865318753188531895319053191531925319353194531955319653197531985319953200532015320253203532045320553206532075320853209532105321153212532135321453215532165321753218532195322053221532225322353224532255322653227532285322953230532315323253233532345323553236532375323853239532405324153242532435324453245532465324753248532495325053251532525325353254532555325653257532585325953260532615326253263532645326553266532675326853269532705327153272532735327453275532765327753278532795328053281532825328353284532855328653287532885328953290532915329253293532945329553296532975329853299533005330153302533035330453305533065330753308533095331053311533125331353314533155331653317533185331953320533215332253323533245332553326533275332853329533305333153332533335333453335533365333753338533395334053341533425334353344533455334653347533485334953350533515335253353533545335553356533575335853359533605336153362533635336453365533665336753368533695337053371533725337353374533755337653377533785337953380533815338253383533845338553386533875338853389533905339153392533935339453395533965339753398533995340053401534025340353404534055340653407534085340953410534115341253413534145341553416534175341853419534205342153422534235342453425534265342753428534295343053431534325343353434534355343653437534385343953440534415344253443534445344553446534475344853449534505345153452534535345453455534565345753458534595346053461534625346353464534655346653467534685346953470534715347253473534745347553476534775347853479534805348153482534835348453485534865348753488534895349053491534925349353494534955349653497534985349953500535015350253503535045350553506535075350853509535105351153512535135351453515535165351753518535195352053521535225352353524535255352653527535285352953530535315353253533535345353553536535375353853539535405354153542535435354453545535465354753548535495355053551535525355353554535555355653557535585355953560535615356253563535645356553566535675356853569535705357153572535735357453575535765357753578535795358053581535825358353584535855358653587535885358953590535915359253593535945359553596535975359853599536005360153602536035360453605536065360753608536095361053611536125361353614536155361653617536185361953620536215362253623536245362553626536275362853629536305363153632536335363453635536365363753638536395364053641536425364353644536455364653647536485364953650536515365253653536545365553656536575365853659536605366153662536635366453665536665366753668536695367053671536725367353674536755367653677536785367953680536815368253683536845368553686536875368853689536905369153692536935369453695536965369753698536995370053701537025370353704537055370653707537085370953710537115371253713537145371553716537175371853719537205372153722537235372453725537265372753728537295373053731537325373353734537355373653737537385373953740537415374253743537445374553746537475374853749537505375153752537535375453755537565375753758537595376053761537625376353764537655376653767537685376953770537715377253773537745377553776537775377853779537805378153782537835378453785537865378753788537895379053791537925379353794537955379653797537985379953800538015380253803538045380553806538075380853809538105381153812538135381453815538165381753818538195382053821538225382353824538255382653827538285382953830538315383253833538345383553836538375383853839538405384153842538435384453845538465384753848538495385053851538525385353854538555385653857538585385953860538615386253863538645386553866538675386853869538705387153872538735387453875538765387753878538795388053881538825388353884538855388653887538885388953890538915389253893538945389553896538975389853899539005390153902539035390453905539065390753908539095391053911539125391353914539155391653917539185391953920539215392253923539245392553926539275392853929539305393153932539335393453935539365393753938539395394053941539425394353944539455394653947539485394953950539515395253953539545395553956539575395853959539605396153962539635396453965539665396753968539695397053971539725397353974539755397653977539785397953980539815398253983539845398553986539875398853989539905399153992539935399453995539965399753998539995400054001540025400354004540055400654007540085400954010540115401254013540145401554016540175401854019540205402154022540235402454025540265402754028540295403054031540325403354034540355403654037540385403954040540415404254043540445404554046540475404854049540505405154052540535405454055540565405754058540595406054061540625406354064540655406654067540685406954070540715407254073540745407554076540775407854079540805408154082540835408454085540865408754088540895409054091540925409354094540955409654097540985409954100541015410254103541045410554106541075410854109541105411154112541135411454115541165411754118541195412054121541225412354124541255412654127541285412954130541315413254133541345413554136541375413854139541405414154142541435414454145541465414754148541495415054151541525415354154541555415654157541585415954160541615416254163541645416554166541675416854169541705417154172541735417454175541765417754178541795418054181541825418354184541855418654187541885418954190541915419254193541945419554196541975419854199542005420154202542035420454205542065420754208542095421054211542125421354214542155421654217542185421954220542215422254223542245422554226542275422854229542305423154232542335423454235542365423754238542395424054241542425424354244542455424654247542485424954250542515425254253542545425554256542575425854259542605426154262542635426454265542665426754268542695427054271542725427354274542755427654277542785427954280542815428254283542845428554286542875428854289542905429154292542935429454295542965429754298542995430054301543025430354304543055430654307543085430954310543115431254313543145431554316543175431854319543205432154322543235432454325543265432754328543295433054331543325433354334543355433654337543385433954340543415434254343543445434554346543475434854349543505435154352543535435454355543565435754358543595436054361543625436354364543655436654367543685436954370543715437254373543745437554376543775437854379543805438154382543835438454385543865438754388543895439054391543925439354394543955439654397543985439954400544015440254403544045440554406544075440854409544105441154412544135441454415544165441754418544195442054421544225442354424544255442654427544285442954430544315443254433544345443554436544375443854439544405444154442544435444454445544465444754448544495445054451544525445354454544555445654457544585445954460544615446254463544645446554466544675446854469544705447154472544735447454475544765447754478544795448054481544825448354484544855448654487544885448954490544915449254493544945449554496544975449854499545005450154502545035450454505545065450754508545095451054511545125451354514545155451654517545185451954520545215452254523545245452554526545275452854529545305453154532545335453454535545365453754538545395454054541545425454354544545455454654547545485454954550545515455254553545545455554556545575455854559545605456154562545635456454565545665456754568545695457054571545725457354574545755457654577545785457954580545815458254583545845458554586545875458854589545905459154592545935459454595545965459754598545995460054601546025460354604546055460654607546085460954610546115461254613546145461554616546175461854619546205462154622546235462454625546265462754628546295463054631546325463354634546355463654637546385463954640546415464254643546445464554646546475464854649546505465154652546535465454655546565465754658546595466054661546625466354664546655466654667546685466954670546715467254673546745467554676546775467854679546805468154682546835468454685546865468754688546895469054691546925469354694546955469654697546985469954700547015470254703547045470554706547075470854709547105471154712547135471454715547165471754718547195472054721547225472354724547255472654727547285472954730547315473254733547345473554736547375473854739547405474154742547435474454745547465474754748547495475054751547525475354754547555475654757547585475954760547615476254763547645476554766547675476854769547705477154772547735477454775547765477754778547795478054781547825478354784547855478654787547885478954790547915479254793547945479554796547975479854799548005480154802548035480454805548065480754808548095481054811548125481354814548155481654817548185481954820548215482254823548245482554826548275482854829548305483154832548335483454835548365483754838548395484054841548425484354844548455484654847548485484954850548515485254853548545485554856548575485854859548605486154862548635486454865548665486754868548695487054871548725487354874548755487654877548785487954880548815488254883548845488554886548875488854889548905489154892548935489454895548965489754898548995490054901549025490354904549055490654907549085490954910549115491254913549145491554916549175491854919549205492154922549235492454925549265492754928549295493054931549325493354934549355493654937549385493954940549415494254943549445494554946549475494854949549505495154952549535495454955549565495754958549595496054961549625496354964549655496654967549685496954970549715497254973549745497554976549775497854979549805498154982549835498454985549865498754988549895499054991549925499354994549955499654997549985499955000550015500255003550045500555006550075500855009550105501155012550135501455015550165501755018550195502055021550225502355024550255502655027550285502955030550315503255033550345503555036550375503855039550405504155042550435504455045550465504755048550495505055051550525505355054550555505655057550585505955060550615506255063550645506555066550675506855069550705507155072550735507455075550765507755078550795508055081550825508355084550855508655087550885508955090550915509255093550945509555096550975509855099551005510155102551035510455105551065510755108551095511055111551125511355114551155511655117551185511955120551215512255123551245512555126551275512855129551305513155132551335513455135551365513755138551395514055141551425514355144551455514655147551485514955150551515515255153551545515555156551575515855159551605516155162551635516455165551665516755168551695517055171551725517355174551755517655177551785517955180551815518255183551845518555186551875518855189551905519155192551935519455195551965519755198551995520055201552025520355204552055520655207552085520955210552115521255213552145521555216552175521855219552205522155222552235522455225552265522755228552295523055231552325523355234552355523655237552385523955240552415524255243552445524555246552475524855249552505525155252552535525455255552565525755258552595526055261552625526355264552655526655267552685526955270552715527255273552745527555276552775527855279552805528155282552835528455285552865528755288552895529055291552925529355294552955529655297552985529955300553015530255303553045530555306553075530855309553105531155312553135531455315553165531755318553195532055321553225532355324553255532655327553285532955330553315533255333553345533555336553375533855339553405534155342553435534455345553465534755348553495535055351553525535355354553555535655357553585535955360553615536255363553645536555366553675536855369553705537155372553735537455375553765537755378553795538055381553825538355384553855538655387553885538955390553915539255393553945539555396553975539855399554005540155402554035540455405554065540755408554095541055411554125541355414554155541655417554185541955420554215542255423554245542555426554275542855429554305543155432554335543455435554365543755438554395544055441554425544355444554455544655447554485544955450554515545255453554545545555456554575545855459554605546155462554635546455465554665546755468554695547055471554725547355474554755547655477554785547955480554815548255483554845548555486554875548855489554905549155492554935549455495554965549755498554995550055501555025550355504555055550655507555085550955510555115551255513555145551555516555175551855519555205552155522555235552455525555265552755528555295553055531555325553355534555355553655537555385553955540555415554255543555445554555546555475554855549555505555155552555535555455555555565555755558555595556055561555625556355564555655556655567555685556955570555715557255573555745557555576555775557855579555805558155582555835558455585555865558755588555895559055591555925559355594555955559655597555985559955600556015560255603556045560555606556075560855609556105561155612556135561455615556165561755618556195562055621556225562355624556255562655627556285562955630556315563255633556345563555636556375563855639556405564155642556435564455645556465564755648556495565055651556525565355654556555565655657556585565955660556615566255663556645566555666556675566855669556705567155672556735567455675556765567755678556795568055681556825568355684556855568655687556885568955690556915569255693556945569555696556975569855699557005570155702557035570455705557065570755708557095571055711557125571355714557155571655717557185571955720557215572255723557245572555726557275572855729557305573155732557335573455735557365573755738557395574055741557425574355744557455574655747557485574955750557515575255753557545575555756557575575855759557605576155762557635576455765557665576755768557695577055771557725577355774557755577655777557785577955780557815578255783557845578555786557875578855789557905579155792557935579455795557965579755798557995580055801558025580355804558055580655807558085580955810558115581255813558145581555816558175581855819558205582155822558235582455825558265582755828558295583055831558325583355834558355583655837558385583955840558415584255843558445584555846558475584855849558505585155852558535585455855558565585755858558595586055861558625586355864558655586655867558685586955870558715587255873558745587555876558775587855879558805588155882558835588455885558865588755888558895589055891558925589355894558955589655897558985589955900559015590255903559045590555906559075590855909559105591155912559135591455915559165591755918559195592055921559225592355924559255592655927559285592955930559315593255933559345593555936559375593855939559405594155942559435594455945559465594755948559495595055951559525595355954559555595655957559585595955960559615596255963559645596555966559675596855969559705597155972559735597455975559765597755978559795598055981559825598355984559855598655987559885598955990559915599255993559945599555996559975599855999560005600156002560035600456005560065600756008560095601056011560125601356014560155601656017560185601956020560215602256023560245602556026560275602856029560305603156032560335603456035560365603756038560395604056041560425604356044560455604656047560485604956050560515605256053560545605556056560575605856059560605606156062560635606456065560665606756068560695607056071560725607356074560755607656077560785607956080560815608256083560845608556086560875608856089560905609156092560935609456095560965609756098560995610056101561025610356104561055610656107561085610956110561115611256113561145611556116561175611856119561205612156122561235612456125561265612756128561295613056131561325613356134561355613656137561385613956140561415614256143561445614556146561475614856149561505615156152561535615456155561565615756158561595616056161561625616356164561655616656167561685616956170561715617256173561745617556176561775617856179561805618156182561835618456185561865618756188561895619056191561925619356194561955619656197561985619956200562015620256203562045620556206562075620856209562105621156212562135621456215562165621756218562195622056221562225622356224562255622656227562285622956230562315623256233562345623556236562375623856239562405624156242562435624456245562465624756248562495625056251562525625356254562555625656257562585625956260562615626256263562645626556266562675626856269562705627156272562735627456275562765627756278562795628056281562825628356284562855628656287562885628956290562915629256293562945629556296562975629856299563005630156302563035630456305563065630756308563095631056311563125631356314563155631656317563185631956320563215632256323563245632556326563275632856329563305633156332563335633456335563365633756338563395634056341563425634356344563455634656347563485634956350563515635256353563545635556356563575635856359563605636156362563635636456365563665636756368563695637056371563725637356374563755637656377563785637956380563815638256383563845638556386563875638856389563905639156392563935639456395563965639756398563995640056401564025640356404564055640656407564085640956410564115641256413564145641556416564175641856419564205642156422564235642456425564265642756428564295643056431564325643356434564355643656437564385643956440564415644256443564445644556446564475644856449564505645156452564535645456455564565645756458564595646056461564625646356464564655646656467564685646956470564715647256473564745647556476564775647856479564805648156482564835648456485564865648756488564895649056491564925649356494564955649656497564985649956500565015650256503565045650556506565075650856509565105651156512565135651456515565165651756518565195652056521565225652356524565255652656527565285652956530565315653256533565345653556536565375653856539565405654156542565435654456545565465654756548565495655056551565525655356554565555655656557565585655956560565615656256563565645656556566565675656856569565705657156572565735657456575565765657756578565795658056581565825658356584565855658656587565885658956590565915659256593565945659556596565975659856599566005660156602566035660456605566065660756608566095661056611566125661356614566155661656617566185661956620566215662256623566245662556626566275662856629566305663156632566335663456635566365663756638566395664056641566425664356644566455664656647566485664956650566515665256653566545665556656566575665856659566605666156662566635666456665566665666756668566695667056671566725667356674566755667656677566785667956680566815668256683566845668556686566875668856689566905669156692566935669456695566965669756698566995670056701567025670356704567055670656707567085670956710567115671256713567145671556716567175671856719567205672156722567235672456725567265672756728567295673056731567325673356734567355673656737567385673956740567415674256743567445674556746567475674856749567505675156752567535675456755567565675756758567595676056761567625676356764567655676656767567685676956770567715677256773567745677556776567775677856779567805678156782567835678456785567865678756788567895679056791567925679356794567955679656797567985679956800568015680256803568045680556806568075680856809568105681156812568135681456815568165681756818568195682056821568225682356824568255682656827568285682956830568315683256833568345683556836568375683856839568405684156842568435684456845568465684756848568495685056851568525685356854568555685656857568585685956860568615686256863568645686556866568675686856869568705687156872568735687456875568765687756878568795688056881568825688356884568855688656887568885688956890568915689256893568945689556896568975689856899569005690156902569035690456905569065690756908569095691056911569125691356914569155691656917569185691956920569215692256923569245692556926569275692856929569305693156932569335693456935569365693756938569395694056941569425694356944569455694656947569485694956950569515695256953569545695556956569575695856959569605696156962569635696456965569665696756968569695697056971569725697356974569755697656977569785697956980569815698256983569845698556986569875698856989569905699156992569935699456995569965699756998569995700057001570025700357004570055700657007570085700957010570115701257013570145701557016570175701857019570205702157022570235702457025570265702757028570295703057031570325703357034570355703657037570385703957040570415704257043570445704557046570475704857049570505705157052570535705457055570565705757058570595706057061570625706357064570655706657067570685706957070570715707257073570745707557076570775707857079570805708157082570835708457085570865708757088570895709057091570925709357094570955709657097570985709957100571015710257103571045710557106571075710857109571105711157112571135711457115571165711757118571195712057121571225712357124571255712657127571285712957130571315713257133571345713557136571375713857139571405714157142571435714457145571465714757148571495715057151571525715357154571555715657157571585715957160571615716257163571645716557166571675716857169571705717157172571735717457175571765717757178571795718057181571825718357184571855718657187571885718957190571915719257193571945719557196571975719857199572005720157202572035720457205572065720757208572095721057211572125721357214572155721657217572185721957220572215722257223572245722557226572275722857229572305723157232572335723457235572365723757238572395724057241572425724357244572455724657247572485724957250572515725257253572545725557256572575725857259572605726157262572635726457265572665726757268572695727057271572725727357274572755727657277572785727957280572815728257283572845728557286572875728857289572905729157292572935729457295572965729757298572995730057301573025730357304573055730657307573085730957310573115731257313573145731557316573175731857319573205732157322573235732457325573265732757328573295733057331573325733357334573355733657337573385733957340573415734257343573445734557346573475734857349573505735157352573535735457355573565735757358573595736057361573625736357364573655736657367573685736957370573715737257373573745737557376573775737857379573805738157382573835738457385573865738757388573895739057391573925739357394573955739657397573985739957400574015740257403574045740557406574075740857409574105741157412574135741457415574165741757418574195742057421574225742357424574255742657427574285742957430574315743257433574345743557436574375743857439574405744157442574435744457445574465744757448574495745057451574525745357454574555745657457574585745957460574615746257463574645746557466574675746857469574705747157472574735747457475574765747757478574795748057481574825748357484574855748657487574885748957490574915749257493574945749557496574975749857499575005750157502575035750457505575065750757508575095751057511575125751357514575155751657517575185751957520575215752257523575245752557526575275752857529575305753157532575335753457535575365753757538575395754057541575425754357544575455754657547575485754957550575515755257553575545755557556575575755857559575605756157562575635756457565575665756757568575695757057571575725757357574575755757657577575785757957580575815758257583575845758557586575875758857589575905759157592575935759457595575965759757598575995760057601576025760357604576055760657607576085760957610576115761257613576145761557616576175761857619576205762157622576235762457625576265762757628576295763057631576325763357634576355763657637576385763957640576415764257643576445764557646576475764857649576505765157652576535765457655576565765757658576595766057661576625766357664576655766657667576685766957670576715767257673576745767557676576775767857679576805768157682576835768457685576865768757688576895769057691576925769357694576955769657697576985769957700577015770257703577045770557706577075770857709577105771157712577135771457715577165771757718577195772057721577225772357724577255772657727577285772957730577315773257733577345773557736577375773857739577405774157742577435774457745577465774757748577495775057751577525775357754577555775657757577585775957760577615776257763577645776557766577675776857769577705777157772577735777457775577765777757778577795778057781577825778357784577855778657787577885778957790577915779257793577945779557796577975779857799578005780157802578035780457805578065780757808578095781057811578125781357814578155781657817578185781957820578215782257823578245782557826578275782857829578305783157832578335783457835578365783757838578395784057841578425784357844578455784657847578485784957850578515785257853578545785557856578575785857859578605786157862578635786457865578665786757868578695787057871578725787357874578755787657877578785787957880578815788257883578845788557886578875788857889578905789157892578935789457895578965789757898578995790057901579025790357904579055790657907579085790957910579115791257913579145791557916579175791857919579205792157922579235792457925579265792757928579295793057931579325793357934579355793657937579385793957940579415794257943579445794557946579475794857949579505795157952579535795457955579565795757958579595796057961579625796357964579655796657967579685796957970579715797257973579745797557976579775797857979579805798157982579835798457985579865798757988579895799057991579925799357994579955799657997579985799958000580015800258003580045800558006580075800858009580105801158012580135801458015580165801758018580195802058021580225802358024580255802658027580285802958030580315803258033580345803558036580375803858039580405804158042580435804458045580465804758048580495805058051580525805358054580555805658057580585805958060580615806258063580645806558066580675806858069580705807158072580735807458075580765807758078580795808058081580825808358084580855808658087580885808958090580915809258093580945809558096580975809858099581005810158102581035810458105581065810758108581095811058111581125811358114581155811658117581185811958120581215812258123581245812558126581275812858129581305813158132581335813458135581365813758138581395814058141581425814358144581455814658147581485814958150581515815258153581545815558156581575815858159581605816158162581635816458165581665816758168581695817058171581725817358174581755817658177581785817958180581815818258183581845818558186581875818858189581905819158192581935819458195581965819758198581995820058201582025820358204582055820658207582085820958210582115821258213582145821558216582175821858219582205822158222582235822458225582265822758228582295823058231582325823358234582355823658237582385823958240582415824258243582445824558246582475824858249582505825158252582535825458255582565825758258582595826058261582625826358264582655826658267582685826958270582715827258273582745827558276582775827858279582805828158282582835828458285582865828758288582895829058291582925829358294582955829658297582985829958300583015830258303583045830558306583075830858309583105831158312583135831458315583165831758318583195832058321583225832358324583255832658327583285832958330583315833258333583345833558336583375833858339583405834158342583435834458345583465834758348583495835058351583525835358354583555835658357583585835958360583615836258363583645836558366583675836858369583705837158372583735837458375583765837758378583795838058381583825838358384583855838658387583885838958390583915839258393583945839558396583975839858399584005840158402584035840458405584065840758408584095841058411584125841358414584155841658417584185841958420584215842258423584245842558426584275842858429584305843158432584335843458435584365843758438584395844058441584425844358444584455844658447584485844958450584515845258453584545845558456584575845858459584605846158462584635846458465584665846758468584695847058471584725847358474584755847658477584785847958480584815848258483584845848558486584875848858489584905849158492584935849458495584965849758498584995850058501585025850358504585055850658507585085850958510585115851258513585145851558516585175851858519585205852158522585235852458525585265852758528585295853058531585325853358534585355853658537585385853958540585415854258543585445854558546585475854858549585505855158552585535855458555585565855758558585595856058561585625856358564585655856658567585685856958570585715857258573585745857558576585775857858579585805858158582585835858458585585865858758588585895859058591585925859358594585955859658597585985859958600586015860258603586045860558606586075860858609586105861158612586135861458615586165861758618586195862058621586225862358624586255862658627586285862958630586315863258633586345863558636586375863858639586405864158642586435864458645586465864758648586495865058651586525865358654586555865658657586585865958660586615866258663586645866558666586675866858669586705867158672586735867458675586765867758678586795868058681586825868358684586855868658687586885868958690586915869258693586945869558696586975869858699587005870158702587035870458705587065870758708587095871058711587125871358714587155871658717587185871958720587215872258723587245872558726587275872858729587305873158732587335873458735587365873758738587395874058741587425874358744587455874658747587485874958750587515875258753587545875558756587575875858759587605876158762587635876458765587665876758768587695877058771587725877358774587755877658777587785877958780587815878258783587845878558786587875878858789587905879158792587935879458795587965879758798587995880058801588025880358804588055880658807588085880958810588115881258813588145881558816588175881858819588205882158822588235882458825588265882758828588295883058831588325883358834588355883658837588385883958840588415884258843588445884558846588475884858849588505885158852588535885458855588565885758858588595886058861588625886358864588655886658867588685886958870588715887258873588745887558876588775887858879588805888158882588835888458885588865888758888588895889058891588925889358894588955889658897588985889958900589015890258903589045890558906589075890858909589105891158912589135891458915589165891758918589195892058921589225892358924589255892658927589285892958930589315893258933589345893558936589375893858939589405894158942589435894458945589465894758948589495895058951589525895358954589555895658957589585895958960589615896258963589645896558966589675896858969589705897158972589735897458975589765897758978589795898058981589825898358984589855898658987589885898958990589915899258993589945899558996589975899858999590005900159002590035900459005590065900759008590095901059011590125901359014590155901659017590185901959020590215902259023590245902559026590275902859029590305903159032590335903459035590365903759038590395904059041590425904359044590455904659047590485904959050590515905259053590545905559056590575905859059590605906159062590635906459065590665906759068590695907059071590725907359074590755907659077590785907959080590815908259083590845908559086590875908859089590905909159092590935909459095590965909759098590995910059101591025910359104591055910659107591085910959110591115911259113591145911559116591175911859119591205912159122591235912459125591265912759128591295913059131591325913359134591355913659137591385913959140591415914259143591445914559146591475914859149591505915159152591535915459155591565915759158591595916059161591625916359164591655916659167591685916959170591715917259173591745917559176591775917859179591805918159182591835918459185591865918759188591895919059191591925919359194591955919659197591985919959200592015920259203592045920559206592075920859209592105921159212592135921459215592165921759218592195922059221592225922359224592255922659227592285922959230592315923259233592345923559236592375923859239592405924159242592435924459245592465924759248592495925059251592525925359254592555925659257592585925959260592615926259263592645926559266592675926859269592705927159272592735927459275592765927759278592795928059281592825928359284592855928659287592885928959290592915929259293592945929559296592975929859299593005930159302593035930459305593065930759308593095931059311593125931359314593155931659317593185931959320593215932259323593245932559326593275932859329593305933159332593335933459335593365933759338593395934059341593425934359344593455934659347593485934959350593515935259353593545935559356593575935859359593605936159362593635936459365593665936759368593695937059371593725937359374593755937659377593785937959380593815938259383593845938559386593875938859389593905939159392593935939459395593965939759398593995940059401594025940359404594055940659407594085940959410594115941259413594145941559416594175941859419594205942159422594235942459425594265942759428594295943059431594325943359434594355943659437594385943959440594415944259443594445944559446594475944859449594505945159452594535945459455594565945759458594595946059461594625946359464594655946659467594685946959470594715947259473594745947559476594775947859479594805948159482594835948459485594865948759488594895949059491594925949359494594955949659497594985949959500595015950259503595045950559506595075950859509595105951159512595135951459515595165951759518595195952059521595225952359524595255952659527595285952959530595315953259533595345953559536595375953859539595405954159542595435954459545595465954759548595495955059551595525955359554595555955659557595585955959560595615956259563595645956559566595675956859569595705957159572595735957459575595765957759578595795958059581595825958359584595855958659587595885958959590595915959259593595945959559596595975959859599596005960159602596035960459605596065960759608596095961059611596125961359614596155961659617596185961959620596215962259623596245962559626596275962859629596305963159632596335963459635596365963759638596395964059641596425964359644596455964659647596485964959650596515965259653596545965559656596575965859659596605966159662596635966459665596665966759668596695967059671596725967359674596755967659677596785967959680596815968259683596845968559686596875968859689596905969159692596935969459695596965969759698596995970059701597025970359704597055970659707597085970959710597115971259713597145971559716597175971859719597205972159722597235972459725597265972759728597295973059731597325973359734597355973659737597385973959740597415974259743597445974559746597475974859749597505975159752597535975459755597565975759758597595976059761597625976359764597655976659767597685976959770597715977259773597745977559776597775977859779597805978159782597835978459785597865978759788597895979059791597925979359794597955979659797597985979959800598015980259803598045980559806598075980859809598105981159812598135981459815598165981759818598195982059821598225982359824598255982659827598285982959830598315983259833598345983559836598375983859839598405984159842598435984459845598465984759848598495985059851598525985359854598555985659857598585985959860598615986259863598645986559866598675986859869598705987159872598735987459875598765987759878598795988059881598825988359884598855988659887598885988959890598915989259893598945989559896598975989859899599005990159902599035990459905599065990759908599095991059911599125991359914599155991659917599185991959920599215992259923599245992559926599275992859929599305993159932599335993459935599365993759938599395994059941599425994359944599455994659947599485994959950599515995259953599545995559956599575995859959599605996159962599635996459965599665996759968599695997059971599725997359974599755997659977599785997959980599815998259983599845998559986599875998859989599905999159992599935999459995599965999759998599996000060001600026000360004600056000660007600086000960010600116001260013600146001560016600176001860019600206002160022600236002460025600266002760028600296003060031600326003360034600356003660037600386003960040600416004260043600446004560046600476004860049600506005160052600536005460055600566005760058600596006060061600626006360064600656006660067600686006960070600716007260073600746007560076600776007860079600806008160082600836008460085600866008760088600896009060091600926009360094600956009660097600986009960100601016010260103601046010560106601076010860109601106011160112601136011460115601166011760118601196012060121601226012360124601256012660127601286012960130601316013260133601346013560136601376013860139601406014160142601436014460145601466014760148601496015060151601526015360154601556015660157601586015960160601616016260163601646016560166601676016860169601706017160172601736017460175601766017760178601796018060181601826018360184601856018660187601886018960190601916019260193601946019560196601976019860199602006020160202602036020460205602066020760208602096021060211602126021360214602156021660217602186021960220602216022260223602246022560226602276022860229602306023160232602336023460235602366023760238602396024060241602426024360244602456024660247602486024960250602516025260253602546025560256602576025860259602606026160262602636026460265602666026760268602696027060271602726027360274602756027660277602786027960280602816028260283602846028560286602876028860289602906029160292602936029460295602966029760298602996030060301603026030360304603056030660307603086030960310603116031260313603146031560316603176031860319603206032160322603236032460325603266032760328603296033060331603326033360334603356033660337603386033960340603416034260343603446034560346603476034860349603506035160352603536035460355603566035760358603596036060361603626036360364603656036660367603686036960370603716037260373603746037560376603776037860379603806038160382603836038460385603866038760388603896039060391603926039360394603956039660397603986039960400604016040260403604046040560406604076040860409604106041160412604136041460415604166041760418604196042060421604226042360424604256042660427604286042960430604316043260433604346043560436604376043860439604406044160442604436044460445604466044760448604496045060451604526045360454604556045660457604586045960460604616046260463604646046560466604676046860469604706047160472604736047460475604766047760478604796048060481604826048360484604856048660487604886048960490604916049260493604946049560496604976049860499605006050160502605036050460505605066050760508605096051060511605126051360514605156051660517605186051960520605216052260523605246052560526605276052860529605306053160532605336053460535605366053760538605396054060541605426054360544605456054660547605486054960550605516055260553605546055560556605576055860559605606056160562605636056460565605666056760568605696057060571605726057360574605756057660577605786057960580605816058260583605846058560586605876058860589605906059160592605936059460595605966059760598605996060060601606026060360604606056060660607606086060960610606116061260613606146061560616606176061860619606206062160622606236062460625606266062760628606296063060631606326063360634606356063660637606386063960640606416064260643606446064560646606476064860649606506065160652606536065460655606566065760658606596066060661606626066360664606656066660667606686066960670606716067260673606746067560676606776067860679606806068160682606836068460685606866068760688606896069060691606926069360694606956069660697606986069960700607016070260703607046070560706607076070860709607106071160712607136071460715607166071760718607196072060721607226072360724607256072660727607286072960730607316073260733607346073560736607376073860739607406074160742607436074460745607466074760748607496075060751607526075360754607556075660757607586075960760607616076260763607646076560766607676076860769607706077160772607736077460775607766077760778607796078060781607826078360784607856078660787607886078960790607916079260793607946079560796607976079860799608006080160802608036080460805608066080760808608096081060811608126081360814608156081660817608186081960820608216082260823608246082560826608276082860829608306083160832608336083460835608366083760838608396084060841608426084360844608456084660847608486084960850608516085260853608546085560856608576085860859608606086160862608636086460865608666086760868608696087060871608726087360874608756087660877608786087960880608816088260883608846088560886608876088860889608906089160892608936089460895608966089760898608996090060901609026090360904609056090660907609086090960910609116091260913609146091560916609176091860919609206092160922609236092460925609266092760928609296093060931609326093360934609356093660937609386093960940609416094260943609446094560946609476094860949609506095160952609536095460955609566095760958609596096060961609626096360964609656096660967609686096960970609716097260973609746097560976609776097860979609806098160982609836098460985609866098760988609896099060991609926099360994609956099660997609986099961000610016100261003610046100561006610076100861009610106101161012610136101461015610166101761018610196102061021610226102361024610256102661027610286102961030610316103261033610346103561036610376103861039610406104161042610436104461045610466104761048610496105061051610526105361054610556105661057610586105961060610616106261063610646106561066610676106861069610706107161072610736107461075610766107761078610796108061081610826108361084610856108661087610886108961090610916109261093610946109561096610976109861099611006110161102611036110461105611066110761108611096111061111611126111361114611156111661117611186111961120611216112261123611246112561126611276112861129611306113161132611336113461135611366113761138611396114061141611426114361144611456114661147611486114961150611516115261153611546115561156611576115861159611606116161162611636116461165611666116761168611696117061171611726117361174611756117661177611786117961180611816118261183611846118561186611876118861189611906119161192611936119461195611966119761198611996120061201612026120361204612056120661207612086120961210612116121261213612146121561216612176121861219612206122161222612236122461225612266122761228612296123061231612326123361234612356123661237612386123961240612416124261243612446124561246612476124861249612506125161252612536125461255612566125761258612596126061261612626126361264612656126661267612686126961270612716127261273612746127561276612776127861279612806128161282612836128461285612866128761288612896129061291612926129361294612956129661297612986129961300613016130261303613046130561306613076130861309613106131161312613136131461315613166131761318613196132061321613226132361324613256132661327613286132961330613316133261333613346133561336613376133861339613406134161342613436134461345613466134761348613496135061351613526135361354613556135661357613586135961360613616136261363613646136561366613676136861369613706137161372613736137461375613766137761378613796138061381613826138361384613856138661387613886138961390613916139261393613946139561396613976139861399614006140161402614036140461405614066140761408614096141061411614126141361414614156141661417614186141961420614216142261423614246142561426614276142861429614306143161432614336143461435614366143761438614396144061441614426144361444614456144661447614486144961450614516145261453614546145561456614576145861459614606146161462614636146461465614666146761468614696147061471614726147361474614756147661477614786147961480614816148261483614846148561486614876148861489614906149161492614936149461495614966149761498614996150061501615026150361504615056150661507615086150961510615116151261513615146151561516615176151861519615206152161522615236152461525615266152761528615296153061531615326153361534615356153661537615386153961540615416154261543615446154561546615476154861549615506155161552615536155461555615566155761558615596156061561615626156361564615656156661567615686156961570615716157261573615746157561576615776157861579615806158161582615836158461585615866158761588615896159061591615926159361594615956159661597615986159961600616016160261603616046160561606616076160861609616106161161612616136161461615616166161761618616196162061621616226162361624616256162661627616286162961630616316163261633616346163561636616376163861639616406164161642616436164461645616466164761648616496165061651616526165361654616556165661657616586165961660616616166261663616646166561666616676166861669616706167161672616736167461675 |
- -- *************************************************************************
- -- AMERICAN POWER CONVERSION PowerNet-MIB
- -- *************************************************************************
- -- Copyright (c) 2009 American Power Conversion, Inc.
- -- PowerNet is a Trademark of American Power Conversion Corp.
- --
- -- Title: APC TOP LEVEL PowerNet MIB
- --
- -- Version : 3.9.8
- --
- -- Generated by script: tomib.awk
- --
- -- Input File: powernetPS.mib
- --
- -- Created: Monday, September, 14, 2009
- --
- -- Revision History:
- -- *************************************************************************
- -- - v3.2.0 Added functionality for MasterSwitch Plus
- -- - v3.3.0 Added functionality for MX28B (dcDM3) and 3-phase UPS
- -- - v3.3.2 New traps for Symmetra PX UPS
- -- 07/15/01 - v3.4.0 Added transfer switch
- -- - v3.4.3 Added functionality for External and Integrated Environmental Monitor
- -- 06/14/02 - v3.4.4 Added dcmim2(Siemens) branch, Battery Manager(Reading) traps, and
- -- Psx Traps for PDU and RM-PDU and Netlock branch/traps
- -- 12/13/02 - v3.5.0 netlock - Initial support for netlock (nl). Traps 261-265 added.
- -- rPDU - Initial support for rPDU. Traps 266-283 added.
- -- rARU - Initial support for rARU.
- -- gateway - Initial support for gateway (gw). Traps 230-260, 284-297 added.
- -- ups - upsSyncCtrlGroup and upsState sections added.
- -- 02/19/03 - v3.6.0 ups - UpsOutletGroups section added. Traps 298-299 added.
- -- smw - Traps 300-305 added.
- -- rPDU - General OID description cleanups.
- -- gw - Updated SNMP support for gw.
- -- 05/21/03 - v3.6.1 ups - Updated SNMP support for ups.
- -- ems - Environmental Management System OIDs renamed from gateway (gw).
- -- raru - Updated SNMP support for raru.
- -- 06/13/03 - v3.6.3 airFM - Initial support for airFM. Traps 306-311 added.
- -- nl - Traps 261-265 removed.
- -- 11/26/03 - v3.6.4 xPDU - Initial support for xPDU. Traps 312-344 added.
- -- airPA - Initial support for airPA. Traps 306-311 modified for airPA use.
- -- airFM - AirFMStatus OIDs cleaned up.
- -- 03/19/04 - v3.6.5 rPDU - Updated SNMP support for rPDU.
- -- airFM - AirFMGroup section added.
- -- 05/13/04 - v3.6.6 ups - Added several upsAdvBattery OIDs.
- -- ems - Added emsStatusHardwareStatus and emsHardwareState traps 345-346.
- -- aru - Trap 228 redefined to aruDeviceConfigChange.
- -- 08/04/04 - v3.6.7 ups - Added upsAdvConfigNumExternalBatteries and
- -- upsAdvConfigSimpleSignalShutdowns.
- -- ce - Custom Event traps 347-352 added.
- -- 11/22/04 - v3.6.8 ems - Many emsProbeConfig and emsProbeStatus OIDs added.
- -- ups - Traps 353-358 added.
- -- env - Traps 359-374 added.
- -- 01/26/05 - v3.6.9 battman - Initial support for battman, traps 375-380 added.
- -- xATS - Initial support for xATS, traps 381-478 added.
- -- generator - Initial support for generator.
- -- rPDU - Trap edits.
- -- xPDU - Trap edits.
- -- 05/26/05 - v3.7.0 consolePortServer - Initial support for consolePortServer (cpsAP930x).
- -- xPDU - Cleaned up many descriptions.
- -- xATS - Cleaned up many descriptions.
- -- ups - Added several upsAdvConfig OIDs.
- -- 09/28/05 - v3.8.0 modEnvMgr - Initial support for modEnvMgr (mem).
- -- rARU - Added functionality for Gen 2 ARU.
- -- ups/aru/mem - Traps 500-569 added.
- -- all - General cleanup on typos and spelling errors.
- -- 01/04/06 - v3.8.1 rARU - Added functionality for Gen 2 ARU
- -- 02/22/06 - v3.8.2 accessControl - Initial support for accessControl.
- -- Traps 570-592 added.
- -- accessPX - Initial support for accessPX.
- -- airIR - Initial support for airIR and airIRAlarms.
- -- airIRRC - Initial support for airIRRC.
- -- 05/24/06 - v3.8.4 apcLocalDisplay - Initial support for apcLocalDisplay.
- -- ups - UpsAdvOutputRedundancy, upsAdvOutputKVACapacity,
- -- upsAdvConfigBasicSignalLowBatteryDuration, and
- -- upsAdvConfigBypassPhaseLockRequired OIDs added.
- -- UpsAdvConfigMinReturnRuntime SYNTAX changed.
- -- UPS trap numbers 600-623 added.
- -- em - New emConfigProbe, emConfigContact, emStatusProbe OIDs added.
- -- iem - New iemConfigProbe, iemConfigContact, iemStatusProbe OIDs added.
- -- 08/31/06 - v3.8.5 airIRSC - Initial support for airIRSC.
- -- XPDU - XPDUBranchBreaker OIDs and xPDUBranchCurrent traps added.
- -- 11/03/06 - v3.8.6 rPDU - Updated SNMP support for rPDU.
- -- accessPX - accessPXConfigCardFormat OID added.
- -- airIRSC - airIRSCUnitStatusCompressor added.
- -- 01/03/07 - v3.8.7 airIRRP - Initial support for airIRRP100 and airIRRP500.
- -- 04/06/07 - v3.8.8 battMan - Updated SNMP support for Battery Manager,
- -- battManConfigApplication OID deprecated.
- -- airIRRP - Added HeatAssistEnable to airIRRP100 and airIRRP500.
- -- ups - Added several upsDiagSubSys OIDs.
- -- iem - Added iemStatusProbeLocation OID.
- -- all - Cleaned up version history section.
- -- 12/19/07 - v3.9.1 airFM - Added full SNMP support, deprecating some existing OIDs in
- -- favor of new structure.
- -- 12/19/07 - v3.9.2 Added new OIDs for isxModularDistribution, isxModularPdu, airInRoomPerimeter
- -- airIRGen2, symmetraPX IDs, isxServers IDs, upsAdvConfig, upsDiagSubSysNetworkComCard,
- -- memInputsCommStatus, airIRRP100GroupSetpoints. Added new SNMP Traps for
- -- ISX Modular Distribution, and xATS.
- -- 08/13/08 - v3.9.3 Added new OIDs for UPS HighPrec OIDs:
- -- upsHighPrecBattery, upsHighPrecInput, and upsHighPrecOutput.
- -- Added new OIDs for the 10kW the AIR IR Gen2:
- -- airIRG2RDT2ConfigUnitRoleOverride, airIRG2RDT2RunHoursUnit,
- -- airIRG2GroupConfigNumberofBackupUnits, airIRG2GroupConfigRuntimeBalancingEnable,
- -- and airIRG2GroupConfigLoadAssistEnable for use by 10kW application.
- -- Added new traps apcInternalCommunicationFault and apcInternalCommunicationFaultCleared
- -- for use by the SUMX application.
- -- Updated descriptions in existing OIDs.
- -- 09/25/08 - v3.9.4 Added new OIDs for Symmetra PX:
- -- upsParallelSystem, upsPhysicalLayout, upsAdvConfigMainsSetting, upsAdvConfigACWiringSetting,
- -- upsAdvConfigUpperOutputVoltTolerance, upsAdvConfigLowerOutputVoltTolerance, upsAdvConfigUpperBypassVoltTolerance
- -- upsAdvConfigLowerBypassVoltTolerance, upsAdvConfigOutofSyncBypassTransferDelay, upsAdvTestDiagnosticTime
- -- upsAdvTestDiagnosticDay, upsDiagSwitchGearBypassInputSwitchStatus, upsDiagSubFeedBreakerTable,
- -- upsDiagSubFeedBreakerTable, upsSideCarFrameLayoutTable, upsPowerFrameLayoutTable
- -- Added new OIDs for UPSs:
- -- upsBasicSystemStatus, upsAdvControlFlashAndBeep (appended new list options)
- -- Added new OIDs for the AC RP10kW:
- -- airIRG2RDT2ConfigUnitIdleOnCoolFail
- -- Added new OID for isxModularPDU device:
- -- isxModularPduDeviceTransformerPresent (appended new list option)
- -- 02/24/09 - v3.9.5 Added new OIDs for the UPS Integrated ATS product, Air IRSC product, added new Traps for UPS support
- -- and fixed MIB compilier warnings.
- -- 02/24/09 - v3.9.6 Added new Traps and mtrapargs for the ISXC Trap Notification support.
- -- ********************************************************************************************
- -- ********************************************************************************************
- -- PowerNet-MIB { iso org(3) dod(6) internet(1) private(4)
- -- enterprises(1) apc(318) }
- PowerNet-MIB DEFINITIONS ::= BEGIN
- IMPORTS
- enterprises, IpAddress, Gauge, TimeTicks FROM RFC1155-SMI
- DisplayString FROM RFC1213-MIB
- OBJECT-TYPE FROM RFC-1212
- TRAP-TYPE FROM RFC-1215;
- apc OBJECT IDENTIFIER ::= { enterprises 318 }
- products OBJECT IDENTIFIER ::= { apc 1 }
- apcmgmt OBJECT IDENTIFIER ::= { apc 2 }
- hardware OBJECT IDENTIFIER ::= { products 1 }
- software OBJECT IDENTIFIER ::= { products 2 }
- system OBJECT IDENTIFIER ::= { products 3 }
- experimental OBJECT IDENTIFIER ::= { products 4 }
- mconfig OBJECT IDENTIFIER ::= { apcmgmt 1 }
- mcontrol OBJECT IDENTIFIER ::= { apcmgmt 2 }
- mtrapargs OBJECT IDENTIFIER ::= { apcmgmt 3 }
- mfiletransfer OBJECT IDENTIFIER ::= { apcmgmt 4 }
- mconfigClock OBJECT IDENTIFIER ::= { mconfig 6 }
- mfiletransferStatus OBJECT IDENTIFIER ::= { mfiletransfer 1 }
- mfiletransferConfig OBJECT IDENTIFIER ::= { mfiletransfer 2 }
- mfiletransferControl OBJECT IDENTIFIER ::= { mfiletransfer 3 }
- mfiletransferConfigSettings OBJECT IDENTIFIER ::= { mfiletransferConfig 1 }
- mfiletransferConfigTFTP OBJECT IDENTIFIER ::= { mfiletransferConfig 2 }
- mfiletransferConfigFTP OBJECT IDENTIFIER ::= { mfiletransferConfig 3 }
- ups OBJECT IDENTIFIER ::= { hardware 1 }
- measureUps OBJECT IDENTIFIER ::= { hardware 2 }
- miniSNMPadapter OBJECT IDENTIFIER ::= { hardware 3 }
- masterswitch OBJECT IDENTIFIER ::= { hardware 4 }
- masterswitchVM OBJECT IDENTIFIER ::= { hardware 5 }
- masterswitchMSP OBJECT IDENTIFIER ::= { hardware 6 }
- dcDM3 OBJECT IDENTIFIER ::= { hardware 7 }
- automaticTransferSwitch OBJECT IDENTIFIER ::= { hardware 8 }
- dc2 OBJECT IDENTIFIER ::= { hardware 9 }
- environmentalMonitor OBJECT IDENTIFIER ::= { hardware 10 }
- netlock OBJECT IDENTIFIER ::= { hardware 11 }
- rPDU OBJECT IDENTIFIER ::= { hardware 12 }
- airConditioners OBJECT IDENTIFIER ::= { hardware 13 }
- rARU OBJECT IDENTIFIER ::= { hardware 14 }
- xPDU OBJECT IDENTIFIER ::= { hardware 15 }
- battMan OBJECT IDENTIFIER ::= { hardware 16 }
- xATS OBJECT IDENTIFIER ::= { hardware 17 }
- generator OBJECT IDENTIFIER ::= { hardware 18 }
- consolePortServer OBJECT IDENTIFIER ::= { hardware 19 }
- accessControl OBJECT IDENTIFIER ::= { hardware 20 }
- apcLocalDisplay OBJECT IDENTIFIER ::= { hardware 21 }
- isxModularDistribution OBJECT IDENTIFIER ::= { hardware 22 }
- isxModularPdu OBJECT IDENTIFIER ::= { hardware 23 }
- universalInputOutput OBJECT IDENTIFIER ::= { hardware 25 }
- powerNetSubAgent OBJECT IDENTIFIER ::= { software 1 }
- powerNetSoftwareSystem OBJECT IDENTIFIER ::= { powerNetSubAgent 1 }
- powerNetSoftwareConfig OBJECT IDENTIFIER ::= { powerNetSubAgent 2 }
- backUPS OBJECT IDENTIFIER ::= { system 1 }
- smartUPS OBJECT IDENTIFIER ::= { system 2 }
- matrixUPS OBJECT IDENTIFIER ::= { system 3 }
- masterSwitch OBJECT IDENTIFIER ::= { system 4 }
- symmetraUPS OBJECT IDENTIFIER ::= { system 5 }
- dp100E OBJECT IDENTIFIER ::= { system 6 }
- dp300E OBJECT IDENTIFIER ::= { system 7 }
- monitors OBJECT IDENTIFIER ::= { system 8 }
- redundantSwitch OBJECT IDENTIFIER ::= { system 9 }
- dcPower OBJECT IDENTIFIER ::= { system 10 }
- automaticXferSwitch OBJECT IDENTIFIER ::= { system 11 }
- netLock OBJECT IDENTIFIER ::= { system 12 }
- symmetra3PhaseUPS OBJECT IDENTIFIER ::= { system 13 }
- networkAir OBJECT IDENTIFIER ::= { system 14 }
- infraStruXurePDU OBJECT IDENTIFIER ::= { system 15 }
- ais5000UPS OBJECT IDENTIFIER ::= { system 16 }
- smartUPS3Phase OBJECT IDENTIFIER ::= { system 17 }
- battManager OBJECT IDENTIFIER ::= { system 18 }
- infraStruXureATS OBJECT IDENTIFIER ::= { system 19 }
- conPortServ OBJECT IDENTIFIER ::= { system 20 }
- gutor OBJECT IDENTIFIER ::= { system 21 }
- accControl OBJECT IDENTIFIER ::= { system 22 }
- symmetraPX OBJECT IDENTIFIER ::= { system 23 }
- isxModDistribution OBJECT IDENTIFIER ::= { system 24 }
- isxServers OBJECT IDENTIFIER ::= { system 25 }
- smartUPS2 OBJECT IDENTIFIER ::= { system 27 }
- battManIdent OBJECT IDENTIFIER ::= { battMan 1 }
- battManSystemCalib OBJECT IDENTIFIER ::= { battMan 2 }
- battManUnitCalib OBJECT IDENTIFIER ::= { battMan 3 }
- battManStringCalib OBJECT IDENTIFIER ::= { battMan 4 }
- battManBatteryCalib OBJECT IDENTIFIER ::= { battMan 5 }
- battManConfig OBJECT IDENTIFIER ::= { battMan 6 }
- battManAlarm OBJECT IDENTIFIER ::= { battMan 7 }
- battManSystemStatus OBJECT IDENTIFIER ::= { battMan 8 }
- battManStringStatus OBJECT IDENTIFIER ::= { battMan 9 }
- battManBatteryStatus OBJECT IDENTIFIER ::= { battMan 10 }
- battManInputContactStatus OBJECT IDENTIFIER ::= { battMan 11 }
- battManControl OBJECT IDENTIFIER ::= { battMan 12 }
- battManTestResults OBJECT IDENTIFIER ::= { battMan 13 }
- battManUnitStatus OBJECT IDENTIFIER ::= { battMan 14 }
- xPDUIdent OBJECT IDENTIFIER ::= { xPDU 1 }
- xPDUDevice OBJECT IDENTIFIER ::= { xPDU 2 }
- xPDUACMonitoringPoint OBJECT IDENTIFIER ::= { xPDU 3 }
- xPDUCircuitBreakers OBJECT IDENTIFIER ::= { xPDU 4 }
- xPDUInputContacts OBJECT IDENTIFIER ::= { xPDU 5 }
- xPDUOutputRelays OBJECT IDENTIFIER ::= { xPDU 6 }
- xPDUMiscGroup OBJECT IDENTIFIER ::= { xPDU 7 }
- xPDUMainInput OBJECT IDENTIFIER ::= { xPDUACMonitoringPoint 1 }
- xPDUBypassInput OBJECT IDENTIFIER ::= { xPDUACMonitoringPoint 2 }
- xPDUUPSInput OBJECT IDENTIFIER ::= { xPDUACMonitoringPoint 3 }
- xPDUSystemOutput OBJECT IDENTIFIER ::= { xPDUACMonitoringPoint 4 }
- xPDUGroundMonitorPoint OBJECT IDENTIFIER ::= { xPDUACMonitoringPoint 5 }
- xPDUSystemBreakers OBJECT IDENTIFIER ::= { xPDUCircuitBreakers 1 }
- xPDUBranchBreakers OBJECT IDENTIFIER ::= { xPDUCircuitBreakers 2 }
- xATSIdent OBJECT IDENTIFIER ::= { xATS 1 }
- xATSDevice OBJECT IDENTIFIER ::= { xATS 2 }
- xATSSwitch OBJECT IDENTIFIER ::= { xATS 3 }
- xATSACMonitoringPoint OBJECT IDENTIFIER ::= { xATS 4 }
- xATSTesting OBJECT IDENTIFIER ::= { xATS 5 }
- xATSInputContacts OBJECT IDENTIFIER ::= { xATS 6 }
- xATSOutputRelays OBJECT IDENTIFIER ::= { xATS 7 }
- xATSMisc OBJECT IDENTIFIER ::= { xATS 8 }
- xATSSwitchStatus OBJECT IDENTIFIER ::= { xATSSwitch 1 }
- xATSSwitchSettings OBJECT IDENTIFIER ::= { xATSSwitch 2 }
- xATSSwitchTimers OBJECT IDENTIFIER ::= { xATSSwitch 3 }
- xATSSwitchBlockMap OBJECT IDENTIFIER ::= { xATSSwitch 4 }
- xATSSwitchStatistics OBJECT IDENTIFIER ::= { xATSSwitch 5 }
- xATSSource1 OBJECT IDENTIFIER ::= { xATSACMonitoringPoint 1 }
- xATSSource2 OBJECT IDENTIFIER ::= { xATSACMonitoringPoint 2 }
- xATSSystemOutput OBJECT IDENTIFIER ::= { xATSACMonitoringPoint 3 }
- xATSTestingStatus OBJECT IDENTIFIER ::= { xATSTesting 1 }
- xATSTestingResults OBJECT IDENTIFIER ::= { xATSTesting 2 }
- xATSTestingSchedule OBJECT IDENTIFIER ::= { xATSTesting 3 }
- xATSTestingSimulatePowerFail OBJECT IDENTIFIER ::= { xATSTesting 4 }
- xATSGenerator OBJECT IDENTIFIER ::= { generator 1 }
- xATSGeneratorIdent OBJECT IDENTIFIER ::= { xATSGenerator 1 }
- xATSGeneratorStatus OBJECT IDENTIFIER ::= { xATSGenerator 2 }
- xATSGeneratorAdvStatus OBJECT IDENTIFIER ::= { xATSGenerator 3 }
- xATSGeneratorOutput OBJECT IDENTIFIER ::= { xATSGenerator 4 }
- xATSGeneratorSettings OBJECT IDENTIFIER ::= { xATSGenerator 5 }
- xATSGeneratorService OBJECT IDENTIFIER ::= { xATSGenerator 6 }
- xATSGeneratorFuelSystem OBJECT IDENTIFIER ::= { xATSGenerator 7 }
- cpsAP930x OBJECT IDENTIFIER ::= { consolePortServer 1 }
- cpsAP930xSys OBJECT IDENTIFIER ::= { cpsAP930x 1 }
- cpsAP930xConf OBJECT IDENTIFIER ::= { cpsAP930x 2 }
- cpsAP930xInfo OBJECT IDENTIFIER ::= { cpsAP930x 3 }
- cpsAP930xAdm OBJECT IDENTIFIER ::= { cpsAP930x 4 }
- smartUPS250 OBJECT IDENTIFIER ::= { smartUPS 1 }
- smartUPS400 OBJECT IDENTIFIER ::= { smartUPS 2 }
- smartUPS600 OBJECT IDENTIFIER ::= { smartUPS 3 }
- smartUPS900 OBJECT IDENTIFIER ::= { smartUPS 4 }
- smartUPS1250 OBJECT IDENTIFIER ::= { smartUPS 5 }
- smartUPS2000 OBJECT IDENTIFIER ::= { smartUPS 6 }
- smartUPS450 OBJECT IDENTIFIER ::= { smartUPS 7 }
- smartUPS700 OBJECT IDENTIFIER ::= { smartUPS 8 }
- smartUPS1000 OBJECT IDENTIFIER ::= { smartUPS 9 }
- smartUPS1400 OBJECT IDENTIFIER ::= { smartUPS 10 }
- smartUPS2200 OBJECT IDENTIFIER ::= { smartUPS 11 }
- smartUPS3000 OBJECT IDENTIFIER ::= { smartUPS 12 }
- smartUPS5000 OBJECT IDENTIFIER ::= { smartUPS 13 }
- smartUPS7500 OBJECT IDENTIFIER ::= { smartUPS 14 }
- smartUPS10000 OBJECT IDENTIFIER ::= { smartUPS 15 }
- smartUPS1500 OBJECT IDENTIFIER ::= { smartUPS 16 }
- smartUPS3000DSP OBJECT IDENTIFIER ::= { smartUPS 17 }
- smartUPS5000DSP OBJECT IDENTIFIER ::= { smartUPS 18 }
- smartUPS8000 OBJECT IDENTIFIER ::= { smartUPS 19 }
- matrixUPS3000 OBJECT IDENTIFIER ::= { matrixUPS 1 }
- matrixUPS5000 OBJECT IDENTIFIER ::= { matrixUPS 2 }
- masterSwitchV1 OBJECT IDENTIFIER ::= { masterSwitch 1}
- masterSwitchV2 OBJECT IDENTIFIER ::= { masterSwitch 2}
- masterSwitchVM OBJECT IDENTIFIER ::= { masterSwitch 3}
- masterSwitchMSP OBJECT IDENTIFIER ::= { masterSwitch 4}
- masterSwitchrPDU OBJECT IDENTIFIER ::= { masterSwitch 5}
- symmetraUPS4kVA OBJECT IDENTIFIER ::= { symmetraUPS 1 }
- symmetraUPS8kVA OBJECT IDENTIFIER ::= { symmetraUPS 2 }
- symmetraUPS12kVA OBJECT IDENTIFIER ::= { symmetraUPS 3 }
- symmetraUPS16kVA OBJECT IDENTIFIER ::= { symmetraUPS 4 }
- environmental OBJECT IDENTIFIER ::= { monitors 1 }
- environmentalMgtSystem OBJECT IDENTIFIER ::= { monitors 2 }
- emu2 OBJECT IDENTIFIER ::= { monitors 3 }
- mem OBJECT IDENTIFIER ::= { monitors 4 }
- dm3 OBJECT IDENTIFIER ::= { dcPower 1 }
- dcmim2 OBJECT IDENTIFIER ::= { dcPower 2 }
- symmetra3PhaseUPS40kVA OBJECT IDENTIFIER ::= { symmetra3PhaseUPS 1 }
- symmetra3PhaseUPS60kVA OBJECT IDENTIFIER ::= { symmetra3PhaseUPS 2 }
- symmetra3PhaseUPS80kVA OBJECT IDENTIFIER ::= { symmetra3PhaseUPS 3 }
- symmetra3PhaseUPS20kVA OBJECT IDENTIFIER ::= { symmetra3PhaseUPS 4 }
- airFMSeries OBJECT IDENTIFIER ::= { networkAir 1 }
- rackAirRemovalUnit OBJECT IDENTIFIER ::= { networkAir 2 }
- airPASeries OBJECT IDENTIFIER ::= { networkAir 3 }
- airIRSC100Series OBJECT IDENTIFIER ::= { networkAir 4 }
- airIRRC100Series OBJECT IDENTIFIER ::= { networkAir 5 }
- airIRRP100Series OBJECT IDENTIFIER ::= { networkAir 6 }
- airIRRP500Series OBJECT IDENTIFIER ::= { networkAir 7 }
- airIRRD100Series OBJECT IDENTIFIER ::= { networkAir 8 }
- airInRoomPerimeter OBJECT IDENTIFIER ::= { networkAir 9 }
- ais5000UPS10kVA OBJECT IDENTIFIER ::= { ais5000UPS 1 }
- ais5000UPS20kVA OBJECT IDENTIFIER ::= { ais5000UPS 2 }
- ais5000UPS30kVA OBJECT IDENTIFIER ::= { ais5000UPS 3 }
- ais5000UPS40kVA OBJECT IDENTIFIER ::= { ais5000UPS 4 }
- ais5000UPS60kVA OBJECT IDENTIFIER ::= { ais5000UPS 5 }
- ais5000UPS80kVA OBJECT IDENTIFIER ::= { ais5000UPS 6 }
- ais5000UPS100kVA OBJECT IDENTIFIER ::= { ais5000UPS 7 }
- smartUPS3Phase10kVA OBJECT IDENTIFIER ::= { smartUPS3Phase 1 }
- smartUPS3Phase15kVA OBJECT IDENTIFIER ::= { smartUPS3Phase 2 }
- smartUPS3Phase20kVA OBJECT IDENTIFIER ::= { smartUPS3Phase 3 }
- smartUPS3Phase30kVA OBJECT IDENTIFIER ::= { smartUPS3Phase 4 }
- smartUPS3Phase40kVA OBJECT IDENTIFIER ::= { smartUPS3Phase 5 }
- conPortServAP930x OBJECT IDENTIFIER ::= { conPortServ 1 }
- gutorPEW OBJECT IDENTIFIER ::= { gutor 1 }
- gutorPDW OBJECT IDENTIFIER ::= { gutor 2 }
- gutorWEW OBJECT IDENTIFIER ::= { gutor 3 }
- gutorWDW OBJECT IDENTIFIER ::= { gutor 4 }
- gutorSDC OBJECT IDENTIFIER ::= { gutor 5 }
- upsIdent OBJECT IDENTIFIER ::= { ups 1 }
- upsBattery OBJECT IDENTIFIER ::= { ups 2 }
- upsInput OBJECT IDENTIFIER ::= { ups 3 }
- upsOutput OBJECT IDENTIFIER ::= { ups 4 }
- upsConfig OBJECT IDENTIFIER ::= { ups 5 }
- upsControl OBJECT IDENTIFIER ::= { ups 6 }
- upsTest OBJECT IDENTIFIER ::= { ups 7 }
- upsComm OBJECT IDENTIFIER ::= { ups 8 }
- upsPhase OBJECT IDENTIFIER ::= { ups 9 }
- upsSyncCtrlGroup OBJECT IDENTIFIER ::= { ups 10 }
- upsState OBJECT IDENTIFIER ::= { ups 11 }
- upsOutletGroups OBJECT IDENTIFIER ::= { ups 12 }
- upsDiagnostics OBJECT IDENTIFIER ::= { ups 13 }
- upsParallelSystem OBJECT IDENTIFIER ::= { ups 14 }
- upsPhysicalLayout OBJECT IDENTIFIER ::= { ups 15 }
- upsIntegratedATS OBJECT IDENTIFIER ::= { ups 16 }
- upsBasicIdent OBJECT IDENTIFIER ::= { upsIdent 1 }
- upsAdvIdent OBJECT IDENTIFIER ::= { upsIdent 2 }
- upsBasicBattery OBJECT IDENTIFIER ::= { upsBattery 1 }
- upsAdvBattery OBJECT IDENTIFIER ::= { upsBattery 2 }
- upsHighPrecBattery OBJECT IDENTIFIER ::= { upsBattery 3 }
- upsBasicInput OBJECT IDENTIFIER ::= { upsInput 1 }
- upsAdvInput OBJECT IDENTIFIER ::= { upsInput 2 }
- upsHighPrecInput OBJECT IDENTIFIER ::= { upsInput 3 }
- upsBasicOutput OBJECT IDENTIFIER ::= { upsOutput 1 }
- upsAdvOutput OBJECT IDENTIFIER ::= { upsOutput 2 }
- upsHighPrecOutput OBJECT IDENTIFIER ::= { upsOutput 3 }
- upsBasicConfig OBJECT IDENTIFIER ::= { upsConfig 1 }
- upsAdvConfig OBJECT IDENTIFIER ::= { upsConfig 2 }
- upsBasicControl OBJECT IDENTIFIER ::= { upsControl 1 }
- upsAdvControl OBJECT IDENTIFIER ::= { upsControl 2 }
- upsBasicTest OBJECT IDENTIFIER ::= { upsTest 1 }
- upsAdvTest OBJECT IDENTIFIER ::= { upsTest 2 }
- upsPhaseResetValues OBJECT IDENTIFIER ::= { upsPhase 1 }
- upsPhaseInput OBJECT IDENTIFIER ::= { upsPhase 2 }
- upsPhaseOutput OBJECT IDENTIFIER ::= { upsPhase 3 }
- upsSyncCtrlGroupConfig OBJECT IDENTIFIER ::= { upsSyncCtrlGroup 1 }
- upsSyncCtrlGroupStatus OBJECT IDENTIFIER ::= { upsSyncCtrlGroup 2 }
- upsBasicState OBJECT IDENTIFIER ::= { upsState 1 }
- upsAdvState OBJECT IDENTIFIER ::= { upsState 2 }
- upsOutletGroupStatus OBJECT IDENTIFIER ::= { upsOutletGroups 1 }
- upsOutletGroupConfig OBJECT IDENTIFIER ::= { upsOutletGroups 2 }
- upsOutletGroupControl OBJECT IDENTIFIER ::= { upsOutletGroups 3 }
- upsDiagnosticIM OBJECT IDENTIFIER ::= { upsDiagnostics 1 }
- upsDiagnosticPowerModules OBJECT IDENTIFIER ::= { upsDiagnostics 2 }
- upsDiagnosticBatteries OBJECT IDENTIFIER ::= { upsDiagnostics 3 }
- upsDiagnosticSubsystem OBJECT IDENTIFIER ::= { upsDiagnostics 4 }
- upsDiagnosticExternalDevices OBJECT IDENTIFIER ::= { upsDiagnostics 5 }
- upsDiagnosticComBus OBJECT IDENTIFIER ::= { upsDiagnostics 6 }
- upsDiagSwitchGear OBJECT IDENTIFIER ::= { upsDiagnosticExternalDevices 1 }
- upsDiagMCCBBox OBJECT IDENTIFIER ::= { upsDiagnosticExternalDevices 2 }
- upsDiagTransformer OBJECT IDENTIFIER ::= { upsDiagnosticExternalDevices 3 }
- mUpsEnviron OBJECT IDENTIFIER ::= { measureUps 1 }
- mUpsContact OBJECT IDENTIFIER ::= { measureUps 2 }
- serialPort OBJECT IDENTIFIER ::= { miniSNMPadapter 1}
- serialPort1 OBJECT IDENTIFIER ::= { serialPort 1}
- serialPort2 OBJECT IDENTIFIER ::= { serialPort 2}
- serialPort2Config OBJECT IDENTIFIER ::= { serialPort2 1}
- serialPort2Control OBJECT IDENTIFIER ::= { serialPort2 2}
- sPDUIdent OBJECT IDENTIFIER ::= { masterswitch 1 }
- sPDUMasterControl OBJECT IDENTIFIER ::= { masterswitch 2 }
- sPDUMasterConfig OBJECT IDENTIFIER ::= { masterswitch 3 }
- sPDUOutletControl OBJECT IDENTIFIER ::= { masterswitch 4 }
- sPDUOutletConfig OBJECT IDENTIFIER ::= { masterswitch 5 }
- sPDUIdentVM OBJECT IDENTIFIER ::= { masterswitchVM 1 }
- sPDUMasterControlVM OBJECT IDENTIFIER ::= { masterswitchVM 2 }
- sPDUMasterConfigVM OBJECT IDENTIFIER ::= { masterswitchVM 3 }
- sPDUMasterStatusVM OBJECT IDENTIFIER ::= { masterswitchVM 4 }
- sPDUOutletControlVM OBJECT IDENTIFIER ::= { masterswitchVM 5 }
- sPDUOutletConfigVM OBJECT IDENTIFIER ::= { masterswitchVM 6 }
- sPDUOutletStatusVM OBJECT IDENTIFIER ::= { masterswitchVM 7 }
- sPDUIdentMSP OBJECT IDENTIFIER ::= { masterswitchMSP 1 }
- sPDUMasterControlMSP OBJECT IDENTIFIER ::= { masterswitchMSP 2 }
- sPDUMasterConfigMSP OBJECT IDENTIFIER ::= { masterswitchMSP 3 }
- sPDUMasterStatusMSP OBJECT IDENTIFIER ::= { masterswitchMSP 4 }
- sPDUOutletControlMSP OBJECT IDENTIFIER ::= { masterswitchMSP 5 }
- sPDUOutletConfigMSP OBJECT IDENTIFIER ::= { masterswitchMSP 6 }
- sPDUOutletStatusMSP OBJECT IDENTIFIER ::= { masterswitchMSP 7 }
- sPDUOutletConfigMSPall OBJECT IDENTIFIER ::= { sPDUOutletConfigMSP 1 }
- sPDUOutletConfigMSPgs OBJECT IDENTIFIER ::= { sPDUOutletConfigMSP 2 }
- sPDUOutletConfigMSPannun OBJECT IDENTIFIER ::= { sPDUOutletConfigMSP 3 }
- sPDUOutletConfigMSPmups OBJECT IDENTIFIER ::= { sPDUOutletConfigMSP 4 }
- rPDUIdent OBJECT IDENTIFIER ::= { rPDU 1 }
- rPDULoad OBJECT IDENTIFIER ::= { rPDU 2 }
- rPDUOutlet OBJECT IDENTIFIER ::= { rPDU 3 }
- rPDUPowerSupply OBJECT IDENTIFIER ::= { rPDU 4 }
- rPDUStatus OBJECT IDENTIFIER ::= { rPDU 5 }
-
- rPDULoadDevice OBJECT IDENTIFIER ::= { rPDULoad 1 }
- rPDULoadPhaseConfig OBJECT IDENTIFIER ::= { rPDULoad 2 }
- rPDULoadStatus OBJECT IDENTIFIER ::= { rPDULoad 3 }
- rPDULoadBankConfig OBJECT IDENTIFIER ::= { rPDULoad 4 }
- rPDUOutletDevice OBJECT IDENTIFIER ::= { rPDUOutlet 1 }
- rPDUOutletPhase OBJECT IDENTIFIER ::= { rPDUOutlet 2 }
- rPDUOutletControl OBJECT IDENTIFIER ::= { rPDUOutlet 3 }
- rPDUOutletConfig OBJECT IDENTIFIER ::= { rPDUOutlet 4 }
- rPDUOutletStatus OBJECT IDENTIFIER ::= { rPDUOutlet 5 }
- rPDUOutletBank OBJECT IDENTIFIER ::= { rPDUOutlet 6 }
- rPDUPowerSupplyDevice OBJECT IDENTIFIER ::= { rPDUPowerSupply 1 }
- dm3Ident OBJECT IDENTIFIER ::= { dcDM3 1 }
- dm3Config OBJECT IDENTIFIER ::= { dcDM3 2 }
- dm3Status OBJECT IDENTIFIER ::= { dcDM3 3 }
- dm3IdentSystem OBJECT IDENTIFIER ::= { dm3Ident 1}
- dm3ConfigSystem OBJECT IDENTIFIER ::= { dm3Config 1 }
- dm3ConfigLVD OBJECT IDENTIFIER ::= { dm3Config 2 }
- dm3ConfigBattery OBJECT IDENTIFIER ::= { dm3Config 3 }
- dm3ConfigPowerModules OBJECT IDENTIFIER ::= { dm3Config 4 }
- dm3ConfigRelays OBJECT IDENTIFIER ::= { dm3Config 5 }
- dm3ConfigDistribution OBJECT IDENTIFIER ::= { dm3Config 6 }
- dm3ConfigRectifier OBJECT IDENTIFIER ::= { dm3ConfigPowerModules 1 }
- dm3ConfigConverter OBJECT IDENTIFIER ::= { dm3ConfigPowerModules 2 }
- dm3ConfigRectThresh OBJECT IDENTIFIER ::= { dm3ConfigRectifier 1 }
- dm3ConfigRectAlarms OBJECT IDENTIFIER ::= { dm3ConfigRectifier 2 }
- dm3ConfigConvThresh OBJECT IDENTIFIER ::= { dm3ConfigConverter 1 }
- dm3ConfigConvAlarms OBJECT IDENTIFIER ::= { dm3ConfigConverter 2 }
- dm3ConfigOutputRelays OBJECT IDENTIFIER ::= { dm3ConfigRelays 1 }
- dm3ConfigInputRelays OBJECT IDENTIFIER ::= { dm3ConfigRelays 2 }
- dm3ConfigBreakers OBJECT IDENTIFIER ::= { dm3ConfigDistribution 1 }
- dm3ConfigFuses OBJECT IDENTIFIER ::= { dm3ConfigDistribution 2 }
- dm3StatusSystem OBJECT IDENTIFIER ::= { dm3Status 1 }
- dm3StatusAlarms OBJECT IDENTIFIER ::= { dm3Status 2 }
- dm3StatusBattery OBJECT IDENTIFIER ::= { dm3Status 3 }
- dm3StatusOEM OBJECT IDENTIFIER ::= { dm3Status 4 }
- dm3StatusLVD OBJECT IDENTIFIER ::= { dm3Status 5 }
- dm3StatusPowerModules OBJECT IDENTIFIER ::= { dm3Status 6 }
- dm3StatusRelays OBJECT IDENTIFIER ::= { dm3Status 7 }
- dm3StatusDistribution OBJECT IDENTIFIER ::= { dm3Status 8 }
- dm3StatusRectifier OBJECT IDENTIFIER ::= { dm3StatusPowerModules 1 }
- dm3StatusConverter OBJECT IDENTIFIER ::= { dm3StatusPowerModules 2 }
- dm3StatusOutputRelays OBJECT IDENTIFIER ::= { dm3StatusRelays 1 }
- dm3StatusInputRelays OBJECT IDENTIFIER ::= { dm3StatusRelays 2 }
- dm3StatusBreakers OBJECT IDENTIFIER ::= { dm3StatusDistribution 1 }
- dm3StatusFuses OBJECT IDENTIFIER ::= { dm3StatusDistribution 2 }
- atsIdent OBJECT IDENTIFIER ::= { automaticTransferSwitch 1 }
- atsCalibration OBJECT IDENTIFIER ::= { automaticTransferSwitch 2 }
- atsControl OBJECT IDENTIFIER ::= { automaticTransferSwitch 3 }
- atsConfig OBJECT IDENTIFIER ::= { automaticTransferSwitch 4 }
- atsStatus OBJECT IDENTIFIER ::= { automaticTransferSwitch 5 }
- atsCalibrationInput OBJECT IDENTIFIER ::= { atsCalibration 1 }
- atsCalibrationPowerSupply OBJECT IDENTIFIER ::= { atsCalibration 2 }
- atsCalibrationOutput OBJECT IDENTIFIER ::= { atsCalibration 3 }
- atsStatusDeviceStatus OBJECT IDENTIFIER ::= { atsStatus 1 }
- atsStatusResetValues OBJECT IDENTIFIER ::= { atsStatus 2 }
- atsStatusInput OBJECT IDENTIFIER ::= { atsStatus 3 }
- atsStatusOutput OBJECT IDENTIFIER ::= { atsStatus 4 }
- dcmim2Ident OBJECT IDENTIFIER ::= { dc2 1 }
- dcmim2Control OBJECT IDENTIFIER ::= { dc2 2 }
- dcmim2Config OBJECT IDENTIFIER ::= { dc2 3 }
- dcmim2Status OBJECT IDENTIFIER ::= { dc2 4 }
- dcmim2IdentSystem OBJECT IDENTIFIER ::= { dcmim2Ident 1 }
- dcmim2ControlSystem OBJECT IDENTIFIER ::= { dcmim2Control 1 }
- dcmim2ConfigSystem OBJECT IDENTIFIER ::= { dcmim2Config 1 }
- dcmim2ConfigBattery OBJECT IDENTIFIER ::= { dcmim2Config 2 }
- dcmim2ConfigLVD OBJECT IDENTIFIER ::= { dcmim2Config 3 }
- dcmim2StatusSystem OBJECT IDENTIFIER ::= { dcmim2Status 1 }
- dcmim2StatusRectifier OBJECT IDENTIFIER ::= { dcmim2Status 2 }
- dcmim2StatusBattery OBJECT IDENTIFIER ::= { dcmim2Status 3 }
- dcmim2StatusLVD OBJECT IDENTIFIER ::= { dcmim2Status 4 }
- dcmim2StatusAlarms OBJECT IDENTIFIER ::= { dcmim2Status 5 }
- external OBJECT IDENTIFIER ::= { environmentalMonitor 1 }
- integrated OBJECT IDENTIFIER ::= { environmentalMonitor 2 }
- envMgtSystem OBJECT IDENTIFIER ::= { environmentalMonitor 3 }
- modEnvMgr OBJECT IDENTIFIER ::= { environmentalMonitor 4 }
- emIdent OBJECT IDENTIFIER ::= { external 1 }
- emConfig OBJECT IDENTIFIER ::= { external 2 }
- emStatus OBJECT IDENTIFIER ::= { external 3 }
- iemIdent OBJECT IDENTIFIER ::= { integrated 1 }
- iemConfig OBJECT IDENTIFIER ::= { integrated 2 }
- iemStatus OBJECT IDENTIFIER ::= { integrated 3 }
- emsIdent OBJECT IDENTIFIER ::= { envMgtSystem 1 }
- emsOutputRelayControl OBJECT IDENTIFIER ::= { envMgtSystem 2 }
- emsOutletControl OBJECT IDENTIFIER ::= { envMgtSystem 3 }
- emsSensorControl OBJECT IDENTIFIER ::= { envMgtSystem 4 }
- emsAlarmDeviceControl OBJECT IDENTIFIER ::= { envMgtSystem 5 }
- emsConfig OBJECT IDENTIFIER ::= { envMgtSystem 6 }
- emsProbeConfig OBJECT IDENTIFIER ::= { envMgtSystem 7 }
- emsInputContactConfig OBJECT IDENTIFIER ::= { envMgtSystem 8 }
- emsOutputRelayConfig OBJECT IDENTIFIER ::= { envMgtSystem 9 }
- emsOutletConfig OBJECT IDENTIFIER ::= { envMgtSystem 10 }
- emsSensorConfig OBJECT IDENTIFIER ::= { envMgtSystem 11 }
- emsStatus OBJECT IDENTIFIER ::= { envMgtSystem 12 }
- emsProbeStatus OBJECT IDENTIFIER ::= { envMgtSystem 13 }
- emsInputContactStatus OBJECT IDENTIFIER ::= { envMgtSystem 14 }
- emsOutputRelayStatus OBJECT IDENTIFIER ::= { envMgtSystem 15 }
- emsOutletStatus OBJECT IDENTIFIER ::= { envMgtSystem 16 }
- emsAlarmDeviceStatus OBJECT IDENTIFIER ::= { envMgtSystem 17 }
- emsSensorStatus OBJECT IDENTIFIER ::= { envMgtSystem 18 }
- memModules OBJECT IDENTIFIER ::= { modEnvMgr 1 }
- memSensors OBJECT IDENTIFIER ::= { modEnvMgr 2 }
- memInputs OBJECT IDENTIFIER ::= { modEnvMgr 3 }
- memOutputs OBJECT IDENTIFIER ::= { modEnvMgr 4 }
- memOutlets OBJECT IDENTIFIER ::= { modEnvMgr 5 }
- memBeacons OBJECT IDENTIFIER ::= { modEnvMgr 6 }
- nlIdent OBJECT IDENTIFIER ::= { netlock 1 }
- nlStatus OBJECT IDENTIFIER ::= { netlock 2 }
- airFM OBJECT IDENTIFIER ::= { airConditioners 1 }
- airFMIdent OBJECT IDENTIFIER ::= { airFM 1 }
- airFMStatus OBJECT IDENTIFIER ::= { airFM 2 }
- airFMGroup OBJECT IDENTIFIER ::= { airFM 3 }
- airFMSystem OBJECT IDENTIFIER ::= { airFM 4 }
- airFMModule OBJECT IDENTIFIER ::= { airFM 5 }
- airFMAlarms OBJECT IDENTIFIER ::= { airFM 6 }
- airFMGroupSysRoles OBJECT IDENTIFIER ::= { airFMGroup 4 }
- airFMGroupCfg OBJECT IDENTIFIER ::= { airFMGroup 5 }
- airFMGroupLoadShare OBJECT IDENTIFIER ::= { airFMGroup 6 }
- airFMGroupFailover OBJECT IDENTIFIER ::= { airFMGroup 7 }
- airFMGroupFailoverSys OBJECT IDENTIFIER ::= { airFMGroupFailover 1 }
- airFMGroupFailoverMod OBJECT IDENTIFIER ::= { airFMGroupFailover 2 }
- airFMSysStatus OBJECT IDENTIFIER ::= { airFMSystem 1 }
- airFMSysDemands OBJECT IDENTIFIER ::= { airFMSystem 2 }
- airFMSysSetup OBJECT IDENTIFIER ::= { airFMSystem 3 }
- airFMSysConfig OBJECT IDENTIFIER ::= { airFMSystem 4 }
- airFMSysCooling OBJECT IDENTIFIER ::= { airFMSystem 5 }
- airFMSysHumidify OBJECT IDENTIFIER ::= { airFMSystem 6 }
- airFMSysDehumidify OBJECT IDENTIFIER ::= { airFMSystem 7 }
- airFMSysReheat OBJECT IDENTIFIER ::= { airFMSystem 8 }
- airFMSysThresholds OBJECT IDENTIFIER ::= { airFMSystem 9 }
- airFMSysInputs OBJECT IDENTIFIER ::= { airFMSystem 10 }
- airFMSysOutputs OBJECT IDENTIFIER ::= { airFMSystem 11 }
- airFMSysAlarmMap OBJECT IDENTIFIER ::= { airFMSystem 12 }
- airFMSysAlarmMapSys OBJECT IDENTIFIER ::= { airFMSysAlarmMap 1 }
- airFMSysAlarmMapMainMod OBJECT IDENTIFIER ::= { airFMSysAlarmMap 2 }
- airFMSysAlarmMapExpMod1 OBJECT IDENTIFIER ::= { airFMSysAlarmMap 3 }
- airFMSysAlarmMapExpMod2 OBJECT IDENTIFIER ::= { airFMSysAlarmMap 4 }
- airFMSysAlarmMapInput OBJECT IDENTIFIER ::= { airFMSysAlarmMap 5 }
- airFMSysAlarmMapOutput OBJECT IDENTIFIER ::= { airFMSysAlarmMap 6 }
- airFMModIdent OBJECT IDENTIFIER ::= { airFMModule 1 }
- airFMModStatus OBJECT IDENTIFIER ::= { airFMModule 2 }
- airFMModProperties OBJECT IDENTIFIER ::= { airFMModule 3 }
- airFMModCooling OBJECT IDENTIFIER ::= { airFMModule 4 }
- airFMModHumidity OBJECT IDENTIFIER ::= { airFMModule 5 }
- airFMModBlower1 OBJECT IDENTIFIER ::= { airFMModule 6 }
- airFMModBlower2 OBJECT IDENTIFIER ::= { airFMModule 7 }
- airFMModRunHours OBJECT IDENTIFIER ::= { airFMModule 8 }
- airFMModServIntervals OBJECT IDENTIFIER ::= { airFMModule 9 }
- airFMModServIntResets OBJECT IDENTIFIER ::= { airFMModule 10 }
- airPA OBJECT IDENTIFIER ::= { airConditioners 2 }
- airPAIdent OBJECT IDENTIFIER ::= { airPA 1 }
- airPAStatus OBJECT IDENTIFIER ::= { airPA 2 }
- airIR OBJECT IDENTIFIER ::= { airConditioners 3 }
- airIRAlarms OBJECT IDENTIFIER ::= { airIR 1 }
- airIRRC OBJECT IDENTIFIER ::= { airIR 2 }
- airIRRP OBJECT IDENTIFIER ::= { airIR 3 }
- airIRSC OBJECT IDENTIFIER ::= { airIR 4 }
- airIRRCGroup OBJECT IDENTIFIER ::= { airIRRC 1 }
- airIRRCUnit OBJECT IDENTIFIER ::= { airIRRC 2 }
-
- airIRRCGroupStatus OBJECT IDENTIFIER ::= { airIRRCGroup 1 }
- airIRRCGroupSetpoints OBJECT IDENTIFIER ::= { airIRRCGroup 2 }
- airIRRCGroupConfig OBJECT IDENTIFIER ::= { airIRRCGroup 3 }
- airIRRCUnitIdent OBJECT IDENTIFIER ::= { airIRRCUnit 1 }
- airIRRCUnitStatus OBJECT IDENTIFIER ::= { airIRRCUnit 2 }
- airIRRCUnitRunHours OBJECT IDENTIFIER ::= { airIRRCUnit 3 }
- airIRRCUnitServiceIntervals OBJECT IDENTIFIER ::= { airIRRCUnit 4 }
- airIRRCUnitThresholds OBJECT IDENTIFIER ::= { airIRRCUnit 5 }
- airIRRCUnitConfig OBJECT IDENTIFIER ::= { airIRRCUnit 6 }
- -- Series 100 DX Air Conditioners
- airIRRP100 OBJECT IDENTIFIER ::= { airIRRP 1 }
- -- Series 500 CW Air Conditioners
- airIRRP500 OBJECT IDENTIFIER ::= { airIRRP 2 }
- airIRRP100Group OBJECT IDENTIFIER ::= { airIRRP100 1 }
- airIRRP100Unit OBJECT IDENTIFIER ::= { airIRRP100 2 }
- airIRRP100GroupStatus OBJECT IDENTIFIER ::= { airIRRP100Group 1 }
- airIRRP100GroupSetpoints OBJECT IDENTIFIER ::= { airIRRP100Group 2 }
- airIRRP100GroupConfig OBJECT IDENTIFIER ::= { airIRRP100Group 3 }
- airIRRP100UnitIdent OBJECT IDENTIFIER ::= { airIRRP100Unit 1 }
- airIRRP100UnitStatus OBJECT IDENTIFIER ::= { airIRRP100Unit 2 }
- airIRRP100UnitRunHours OBJECT IDENTIFIER ::= { airIRRP100Unit 3 }
- airIRRP100UnitServiceIntervals OBJECT IDENTIFIER ::= { airIRRP100Unit 4 }
- airIRRP100UnitThresholds OBJECT IDENTIFIER ::= { airIRRP100Unit 5 }
- airIRRP100UnitConfig OBJECT IDENTIFIER ::= { airIRRP100Unit 6 }
-
- airIRRP500Group OBJECT IDENTIFIER ::= { airIRRP500 1 }
- airIRRP500Unit OBJECT IDENTIFIER ::= { airIRRP500 2 }
- airIRRP500GroupStatus OBJECT IDENTIFIER ::= { airIRRP500Group 1 }
- airIRRP500GroupSetpoints OBJECT IDENTIFIER ::= { airIRRP500Group 2 }
- airIRRP500GroupConfig OBJECT IDENTIFIER ::= { airIRRP500Group 3 }
- airIRRP500UnitIdent OBJECT IDENTIFIER ::= { airIRRP500Unit 1 }
- airIRRP500UnitStatus OBJECT IDENTIFIER ::= { airIRRP500Unit 2 }
- airIRRP500UnitRunHours OBJECT IDENTIFIER ::= { airIRRP500Unit 3 }
- airIRRP500UnitServiceIntervals OBJECT IDENTIFIER ::= { airIRRP500Unit 4 }
- airIRRP500UnitThresholds OBJECT IDENTIFIER ::= { airIRRP500Unit 5 }
- airIRRP500UnitConfig OBJECT IDENTIFIER ::= { airIRRP500Unit 6 }
- airIRSCUnit OBJECT IDENTIFIER ::= { airIRSC 1 }
-
- airIRSCUnitIdent OBJECT IDENTIFIER ::= { airIRSCUnit 1 }
- airIRSCUnitStatus OBJECT IDENTIFIER ::= { airIRSCUnit 2 }
- airIRSCUnitRunHours OBJECT IDENTIFIER ::= { airIRSCUnit 3 }
- airIRSCUnitServiceIntervals OBJECT IDENTIFIER ::= { airIRSCUnit 4 }
- airIRSCUnitThresholds OBJECT IDENTIFIER ::= { airIRSCUnit 5 }
- airIRSCUnitSetpoints OBJECT IDENTIFIER ::= { airIRSCUnit 6 }
- airIRSCUnitConfig OBJECT IDENTIFIER ::= { airIRSCUnit 7 }
- airIRSCGroup OBJECT IDENTIFIER ::= { airIRSC 2 }
- airIRSCGroupStatus OBJECT IDENTIFIER ::= { airIRSCGroup 1 }
- airIRSCGroupSetpoints OBJECT IDENTIFIER ::= { airIRSCGroup 2 }
- airIRSCGroupConfig OBJECT IDENTIFIER ::= { airIRSCGroup 3 }
- airIRGen2 OBJECT IDENTIFIER ::= { airConditioners 4 }
- airIRG2Ident OBJECT IDENTIFIER ::= { airIRGen2 1 }
- airIRG2Group OBJECT IDENTIFIER ::= { airIRGen2 2 }
- airIRG2Alarms OBJECT IDENTIFIER ::= { airIRGen2 3 }
- airIRG2RC OBJECT IDENTIFIER ::= { airIRGen2 4 }
- airIRG2RD OBJECT IDENTIFIER ::= { airIRGen2 5 }
- airIRG2SC OBJECT IDENTIFIER ::= { airIRGen2 6 }
- airIRG2RA OBJECT IDENTIFIER ::= { airIRGen2 7 }
- -- airIR Gen2 Group data
- airIRG2GroupStatus OBJECT IDENTIFIER ::= { airIRG2Group 1 }
- airIRG2GroupSetpoints OBJECT IDENTIFIER ::= { airIRG2Group 2 }
- airIRG2GroupConfig OBJECT IDENTIFIER ::= { airIRG2Group 3 }
- -- airIR Gen2 RD Unit data
- airIRG2RDType1 OBJECT IDENTIFIER ::= { airIRG2RD 1 }
- airIRG2RDType2 OBJECT IDENTIFIER ::= { airIRG2RD 2 }
- airIRG2RDT2Status OBJECT IDENTIFIER ::= { airIRG2RDType2 1 }
- airIRG2RDT2RunHours OBJECT IDENTIFIER ::= { airIRG2RDType2 2 }
- airIRG2RDT2ServiceIntervals OBJECT IDENTIFIER ::= { airIRG2RDType2 3 }
- airIRG2RDT2Thresholds OBJECT IDENTIFIER ::= { airIRG2RDType2 4 }
- airIRG2RDT2Setpoints OBJECT IDENTIFIER ::= { airIRG2RDType2 5 }
- airIRG2RDT2Config OBJECT IDENTIFIER ::= { airIRG2RDType2 6 }
- airInRoom OBJECT IDENTIFIER ::= { airConditioners 5 }
- airIRmIdent OBJECT IDENTIFIER ::= { airInRoom 1 }
- airIRmAlarms OBJECT IDENTIFIER ::= { airInRoom 2 }
- airIRmPerimeter OBJECT IDENTIFIER ::= { airInRoom 3 }
- airIRmPmCommon1 OBJECT IDENTIFIER ::= { airIRmPerimeter 2 }
- airIRmPmCommon2 OBJECT IDENTIFIER ::= { airIRmPerimeter 3 }
- airIRmPmCommon3 OBJECT IDENTIFIER ::= { airIRmPerimeter 4 }
- airIRmPmCommon4 OBJECT IDENTIFIER ::= { airIRmPerimeter 5 }
- airIRmPmCommon5 OBJECT IDENTIFIER ::= { airIRmPerimeter 6 }
- airIRmPmCompressor1 OBJECT IDENTIFIER ::= { airIRmPerimeter 7 }
- airIRmPmCompressor2 OBJECT IDENTIFIER ::= { airIRmPerimeter 8 }
- airIRmPmSuctionValve1 OBJECT IDENTIFIER ::= { airIRmPerimeter 9 }
- airIRmPmSuctionValve2 OBJECT IDENTIFIER ::= { airIRmPerimeter 10 }
- airIRmPmEheating1 OBJECT IDENTIFIER ::= { airIRmPerimeter 11 }
- airIRmPmEheating2 OBJECT IDENTIFIER ::= { airIRmPerimeter 12 }
- airIRmPmEheating3 OBJECT IDENTIFIER ::= { airIRmPerimeter 13 }
- airIRmPmEheating4 OBJECT IDENTIFIER ::= { airIRmPerimeter 14 }
- airIRmPmGECWvalve OBJECT IDENTIFIER ::= { airIRmPerimeter 15 }
- airIRmPmGvalve OBJECT IDENTIFIER ::= { airIRmPerimeter 16 }
- airIRmPmDrycooler1 OBJECT IDENTIFIER ::= { airIRmPerimeter 17 }
- airIRmPmDrycooler2 OBJECT IDENTIFIER ::= { airIRmPerimeter 18 }
- airIRmPmDrycooler3 OBJECT IDENTIFIER ::= { airIRmPerimeter 19 }
- airIRmPmDrycooler4 OBJECT IDENTIFIER ::= { airIRmPerimeter 20 }
- airIRmPmPump1 OBJECT IDENTIFIER ::= { airIRmPerimeter 21 }
- airIRmPmPump2 OBJECT IDENTIFIER ::= { airIRmPerimeter 22 }
- airIRmPmPump3 OBJECT IDENTIFIER ::= { airIRmPerimeter 23 }
- airIRmPmPump4 OBJECT IDENTIFIER ::= { airIRmPerimeter 24 }
- airIRmPmHotgasHeating OBJECT IDENTIFIER ::= { airIRmPerimeter 25 }
- airIRmPmPWWHeating OBJECT IDENTIFIER ::= { airIRmPerimeter 26 }
- airIRmPmHumidifier1 OBJECT IDENTIFIER ::= { airIRmPerimeter 27 }
- airIRmPmHumidifier2 OBJECT IDENTIFIER ::= { airIRmPerimeter 28 }
- -- Skipping 29 and 30.
- airIRmPmDehumidification OBJECT IDENTIFIER ::= { airIRmPerimeter 31 }
- airIRmPmFan1 OBJECT IDENTIFIER ::= { airIRmPerimeter 32 }
- airIRmPmFan2 OBJECT IDENTIFIER ::= { airIRmPerimeter 33 }
- airIRmPmFan3 OBJECT IDENTIFIER ::= { airIRmPerimeter 34 }
- airIRmPmLouver1 OBJECT IDENTIFIER ::= { airIRmPerimeter 35 }
- airIRmPmLouver2 OBJECT IDENTIFIER ::= { airIRmPerimeter 36 }
- airIRmPmLouver3 OBJECT IDENTIFIER ::= { airIRmPerimeter 37 }
- airIRmPmAuxAlarm1 OBJECT IDENTIFIER ::= { airIRmPerimeter 38 }
- airIRmPmAuxAlarm2 OBJECT IDENTIFIER ::= { airIRmPerimeter 39 }
- airIRmPmAuxAlarm3 OBJECT IDENTIFIER ::= { airIRmPerimeter 40 }
- airIRmPmAuxAlarm4 OBJECT IDENTIFIER ::= { airIRmPerimeter 41 }
- airIRmPmAuxAlarm5 OBJECT IDENTIFIER ::= { airIRmPerimeter 42 }
- airIRmPmAlarmBits OBJECT IDENTIFIER ::= { airIRmPerimeter 43 }
- airIRmPmMyZone OBJECT IDENTIFIER ::= { airIRmPerimeter 44 }
- airIRmPmGlobalZoneData OBJECT IDENTIFIER ::= { airIRmPerimeter 45 }
- rARUIdent OBJECT IDENTIFIER ::= { rARU 1 }
- rARUConfig OBJECT IDENTIFIER ::= { rARU 2 }
- rARUStatus OBJECT IDENTIFIER ::= { rARU 3 }
- rARUFanStatus OBJECT IDENTIFIER ::= { rARU 4 }
- rARUPower OBJECT IDENTIFIER ::= { rARU 5 }
- rARUSensors OBJECT IDENTIFIER ::= { rARU 6 }
- accessPX OBJECT IDENTIFIER ::= { accessControl 1 }
- accessPXIdent OBJECT IDENTIFIER ::= { accessPX 1 }
- accessPXConfig OBJECT IDENTIFIER ::= { accessPX 2 }
- accessPXConfigFront OBJECT IDENTIFIER ::= { accessPX 3 }
- accessPXStatusFront OBJECT IDENTIFIER ::= { accessPX 4 }
- accessPXConfigRear OBJECT IDENTIFIER ::= { accessPX 5 }
- accessPXStatusRear OBJECT IDENTIFIER ::= { accessPX 6 }
- accessPXConfigBeacon OBJECT IDENTIFIER ::= { accessPX 7 }
- accessPXStatusBeacon OBJECT IDENTIFIER ::= { accessPX 8 }
- apcLocalDisplayIdent OBJECT IDENTIFIER ::= { apcLocalDisplay 1 }
- apcLocalDisplayConfig OBJECT IDENTIFIER ::= { apcLocalDisplay 2 }
- accPX OBJECT IDENTIFIER ::= { accControl 1 }
- isxModularPduIdent OBJECT IDENTIFIER ::= { isxModularPdu 1 }
- isxModularPduDevice OBJECT IDENTIFIER ::= { isxModularPdu 2 }
- isxModularPduStatus OBJECT IDENTIFIER ::= { isxModularPdu 3 }
- symmetraPx48kVA OBJECT IDENTIFIER ::= { symmetraPX 1 }
- symmetraPx160kVA OBJECT IDENTIFIER ::= { symmetraPX 2 }
- symmetraPx250kVA OBJECT IDENTIFIER ::= { symmetraPX 3 }
- symmetraPx500kVA OBJECT IDENTIFIER ::= { symmetraPX 4 }
- isx24ModuleHalfRackPdu OBJECT IDENTIFIER ::= { isxModDistribution 1 }
- isx6ModuleRackPdu OBJECT IDENTIFIER ::= { isxModDistribution 2 }
- isxModularDistInfo OBJECT IDENTIFIER ::= { isxModularDistribution 1 }
- isxModularDistModules OBJECT IDENTIFIER ::= { isxModularDistribution 2 }
- isxModularDistSubFeeds OBJECT IDENTIFIER ::= { isxModularDistribution 3 }
- isxModularDistTotals OBJECT IDENTIFIER ::= { isxModularDistribution 4 }
- isxModularDistSysVoltage OBJECT IDENTIFIER ::= { isxModularDistTotals 1 }
- isxModularDistSysCurrent OBJECT IDENTIFIER ::= { isxModularDistTotals 2 }
- isxModularDistSysPower OBJECT IDENTIFIER ::= { isxModularDistTotals 3 }
- isxcBasic OBJECT IDENTIFIER ::= { isxServers 1 }
- isxcStandard OBJECT IDENTIFIER ::= { isxServers 2 }
- isxcEnterprise OBJECT IDENTIFIER ::= { isxServers 3 }
- uioSensor OBJECT IDENTIFIER ::= { universalInputOutput 1 }
- uioInputContact OBJECT IDENTIFIER ::= { universalInputOutput 2 }
- uioOutputRelay OBJECT IDENTIFIER ::= { universalInputOutput 3 }
- -- object types
- -- the products group
- -- the experimental group
- -- the apcmgmt group
- -- the mconfig group
- mconfigNumTrapReceivers OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of managers to send traps to."
- ::= { mconfig 1 }
- mconfigTrapReceiverTable OBJECT-TYPE
- SYNTAX SEQUENCE OF MconfigTrapReceiverEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "A list of managers to send traps to. The number of
- entries is given by the value of mconfigNumTrapReceivers.
- Maximum number of Trap Receivers is four."
- ::= { mconfig 2 }
- mconfigTrapReceiverEntry OBJECT-TYPE
- SYNTAX MconfigTrapReceiverEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The managers to send traps to."
- INDEX { trapIndex}
- ::= { mconfigTrapReceiverTable 1 }
- MconfigTrapReceiverEntry ::=
- SEQUENCE {
- trapIndex
- INTEGER,
- receiverAddr
- IpAddress,
- communityString
- DisplayString,
- severity
- INTEGER,
- acceptThisReceiver
- INTEGER,
- receiveTrapType
- INTEGER
- }
- trapIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to a trap receiver entry."
- ::= { mconfigTrapReceiverEntry 1 }
- receiverAddr OBJECT-TYPE
- SYNTAX IpAddress
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The IP address of the manager to send a trap to."
- ::= { mconfigTrapReceiverEntry 2 }
- communityString OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The community name to use in the trap when
- sent to the manager."
- ::= { mconfigTrapReceiverEntry 3 }
- severity OBJECT-TYPE
- SYNTAX INTEGER {
- information(1),
- warning(2),
- severe(3)
- }
- ACCESS read-only
- STATUS obsolete
- DESCRIPTION
- "The severity threshold of traps to send to the manager.
- traps are labeled in severity as informational(1), warning(2),
- severe(3). Only traps of equal or greater severity than
- this value are sent to the manager."
- ::= { mconfigTrapReceiverEntry 4 }
- acceptThisReceiver OBJECT-TYPE
- SYNTAX INTEGER {
- yes (1),
- no (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The value of yes(1) indicates that trap generation for this manager is enabled.
- The value of no(2) indicates that trap generation for this manager is disabled"
- ::= { mconfigTrapReceiverEntry 5 }
- receiveTrapType OBJECT-TYPE
- SYNTAX INTEGER {
- powernet (1),
- ietf (2),
- both (3)
- }
- ACCESS read-only
- STATUS obsolete
- DESCRIPTION
- "Type of trap."
- ::= { mconfigTrapReceiverEntry 6 }
- mconfigBOOTPEnabled OBJECT-TYPE
- SYNTAX INTEGER {
- yes (1),
- no (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The value of yes(1) indicates the PowerNet Adapter is configured to
- obtain its IP configuration parameters from a BOOTP server.
-
- The value of no(2) indicates adapter will assume IP configuration parameters
- values saved in adapter's eeprom, which was originally configured at local
- console."
- ::= { mconfig 3 }
- mconfigTFTPServerIP OBJECT-TYPE
- SYNTAX IpAddress
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The IP address of TFTP server. If mconfigBOOTPEnabled is yes(1), then this IP address
- is provided by BOOTP server and not allowed to be modified; otherwise, this IP address
- can be modified.
-
- Before using TFTP to load new code image, the image file should be placed in proper
- directory of the specified TFTP server. This OID is only supported by AP9605, AP9205,
- and AP9603 PowerNet SNMP Adapters."
- ::= { mconfig 4 }
- newCodeAuthentViaTFTP OBJECT-TYPE
- SYNTAX INTEGER {
- unknown (1),
- validNewAgentCodeImage (2),
- sameAgentCodeImage (3),
- invalidAgentCodeImage (4)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Once mcontrolRestartAgent is set to loadAndExecuteNewAgent (3), PowerNet adapter will
- start to load the remote image file, for authentication only, instead of saving the code
- into flash memory. Only if a validNewAgentCodeImage (1) is found will the agent reboot
- the PowerNet adapter and invoke the loader to load and save new code into the flash memory.
- Otherwise, the current agent code will continue to run.
-
- This OID shows the result of the above authentication process.
- validNewAgentCodeImage (1) means the code image on TFTP server
- is a valid APC agent code and is different version from the current agent.
- Once agent identifies this, loader will start to update flash memory with
- the new agent code.
-
- sameAgentCodeImage (2) means the code image on TFTP server is exactly the
- same as the currently running agent. Currently running agent will not invoke
- loader to load the same again.
-
- invalidAgentCodeImage (3) means the code image on TFTP server is NOT a valid
- APC agent code. Thus, current agent will not load it into the flash memory.
-
- The value of this OID will be associated with TRAP codeImageAuthentDone.
- This OID is only supported by AP9605, AP9205, and AP9603 PowerNet SNMP Adapters."
-
- ::= { mconfig 5 }
- mconfigClockDate OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The current date in the mm/dd/yyyy format. Example: 01/01/2000."
- ::= { mconfigClock 1 }
- mconfigClockTime OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The current time in the hh:mm:ss am/pm format. Example: 12:00:00 am."
- ::= { mconfigClock 2 }
- mcontrolRestartAgent OBJECT-TYPE
- SYNTAX INTEGER {
- restartCurrentAgent (1),
- continueCurrentAgent (2),
- loadAndExecuteNewAgent (3),
- restartWithoutAgent (4),
- resetNetworkAndRestart (5),
- resetNetworkLeaveModeAndRestart (6)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Setting this OID to restartCurrentAgent (1) will restart the same SNMP
- agent code currently saved in flash memory. Setting this OID to
- loadAndExecuteNewAgent (3) will enable adapter to load a new agent code
- into the flash memory and start to execute this new agent code.
- Bootp/tftp is the default protocol. loadAndExecuteNewAgent is only
- supported by AP9605, AP9205, and AP9603 PowerNet SNMP Adapters. Setting
- this OID to restartWithoutAgent (4) will restart the system and not
- start the agent. The subsequent time the system restarts the agent will
- also automatically restart. Setting this OID to
- resetNetworkAndRestart (5) will set the Boot Mode, IP Address, Subnet
- Mask, and Default Gateway to defaults, expire any existing DHCP lease
- and then restart the system. Setting this OID to
- resetNetworkLeaveModeAndRestart (6) will leave the Boot Mode at the
- current setting, set the IP Address, Subnet Mask, and Default Gateway to
- defaults, expire any existing DHCP lease and then restart the system."
- ::= { mcontrol 1 }
- -- The mtrapargs group
- -- These OIDs allows APC traps to be sent with additional arguments
- -- which may not be defined in the APC MIB.
-
- mtrapargsInteger OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID allows APC traps to be sent with an integer argument
- that my not be defined in the APC MIB.
-
- A get of this OID will return 0."
- ::= { mtrapargs 1 }
- mtrapargsIpAddress OBJECT-TYPE
- SYNTAX IpAddress
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID allows APC traps to be sent with an IP address argument
- that my not be defined in the APC MIB.
-
- A get of this OID will return 0.0.0.0."
- ::= { mtrapargs 2 }
- mtrapargsString OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID allows APC traps to be sent with an octet string argument
- that my not be defined in the APC MIB.
-
- A get of this OID will return a NULL string."
- ::= { mtrapargs 3 }
- mtrapargsGauge OBJECT-TYPE
- SYNTAX Gauge
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID allows APC traps to be sent with a Gauge argument
- that my not be defined in the APC MIB.
-
- A get of this OID will return 0."
- ::= { mtrapargs 4 }
- mtrapargsTimeTicks OBJECT-TYPE
- SYNTAX TimeTicks
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID allows APC traps to be sent with a TimeTicks argument
- that my not be defined in the APC MIB.
-
- A get of this OID will return 0."
- ::= { mtrapargs 5 }
- mtrapargsInteger02 OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID allows APC traps to be sent with an integer argument
- that my not be defined in the APC MIB.
-
- A get of this OID will return 0."
- ::= { mtrapargs 6 }
- mtrapargsInteger03 OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID allows APC traps to be sent with an integer argument
- that my not be defined in the APC MIB.
-
- A get of this OID will return 0."
- ::= { mtrapargs 7 }
- mtrapargsIpAddress02 OBJECT-TYPE
- SYNTAX IpAddress
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID allows APC traps to be sent with an IP address argument
- that my not be defined in the APC MIB.
-
- A get of this OID will return 0.0.0.0."
- ::= { mtrapargs 8 }
- mtrapargsIpAddress03 OBJECT-TYPE
- SYNTAX IpAddress
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID allows APC traps to be sent with an IP address argument
- that my not be defined in the APC MIB.
-
- A get of this OID will return 0.0.0.0."
- ::= { mtrapargs 9 }
-
- mtrapargsString02 OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID allows APC traps to be sent with an octet string argument
- that my not be defined in the APC MIB.
-
- A get of this OID will return a NULL string."
- ::= { mtrapargs 10 }
- mtrapargsString03 OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID allows APC traps to be sent with an octet string argument
- that my not be defined in the APC MIB.
-
- A get of this OID will return a NULL string."
- ::= { mtrapargs 11 }
- mtrapargsGauge02 OBJECT-TYPE
- SYNTAX Gauge
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID allows APC traps to be sent with a Gauge argument
- that my not be defined in the APC MIB.
-
- A get of this OID will return 0."
- ::= { mtrapargs 12 }
- mtrapargsGauge03 OBJECT-TYPE
- SYNTAX Gauge
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID allows APC traps to be sent with a Gauge argument
- that my not be defined in the APC MIB.
-
- A get of this OID will return 0."
- ::= { mtrapargs 13 }
- mtrapargsTimeTicks02 OBJECT-TYPE
- SYNTAX TimeTicks
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID allows APC traps to be sent with a TimeTicks argument
- that my not be defined in the APC MIB.
-
- A get of this OID will return 0."
- ::= { mtrapargs 14 }
- mtrapargsTimeTicks03 OBJECT-TYPE
- SYNTAX TimeTicks
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID allows APC traps to be sent with a TimeTicks argument
- that my not be defined in the APC MIB.
-
- A get of this OID will return 0."
- ::= { mtrapargs 15 }
- mtrapargsString04 OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID allows APC traps to be sent with an octet string argument
- that my not be defined in the APC MIB.
-
- A get of this OID will return a NULL string."
- ::= { mtrapargs 16 }
- mtrapargsString05 OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID allows APC traps to be sent with an octet string argument
- that my not be defined in the APC MIB.
-
- A get of this OID will return a NULL string."
- ::= { mtrapargs 17 }
- mtrapargsInteger04 OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID allows APC traps to be sent with an integer argument
- that my not be defined in the APC MIB.
-
- A get of this OID will return 0."
- ::= { mtrapargs 18 }
- mtrapargsInteger05 OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID allows APC traps to be sent with an integer argument
- that my not be defined in the APC MIB.
-
- A get of this OID will return 0."
- ::= { mtrapargs 19 }
- mtrapargsString06 OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID allows APC traps to be sent with an octet string argument
- that my not be defined in the APC MIB.
-
- A get of this OID will return a NULL string."
- ::= { mtrapargs 20 }
- mtrapargsString07 OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID allows APC traps to be sent with an octet string argument
- that my not be defined in the APC MIB.
-
- A get of this OID will return a NULL string."
- ::= { mtrapargs 21 }
- mtrapargsString08 OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID allows APC traps to be sent with an octet string argument
- that my not be defined in the APC MIB.
-
- A get of this OID will return a NULL string."
- ::= { mtrapargs 22 }
- mtrapargsOctetString OBJECT-TYPE
- SYNTAX OCTET STRING
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID allows APC traps to be sent with an octet string argument
- that my not be defined in the APC MIB.
-
- A get of this OID will return a NULL string."
- ::= { mtrapargs 23 }
- mtrapargsOctetString02 OBJECT-TYPE
- SYNTAX OCTET STRING
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID allows APC traps to be sent with an octet string argument
- that my not be defined in the APC MIB.
-
- A get of this OID will return a NULL string."
- ::= { mtrapargs 24 }
- mtrapargsOctetString03 OBJECT-TYPE
- SYNTAX OCTET STRING
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID allows APC traps to be sent with an octet string argument
- that my not be defined in the APC MIB.
-
- A get of this OID will return a NULL string."
- ::= { mtrapargs 25 }
- mtrapargsOctetString04 OBJECT-TYPE
- SYNTAX OCTET STRING
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID allows APC traps to be sent with an octet string argument
- that my not be defined in the APC MIB.
-
- A get of this OID will return a NULL string."
- ::= { mtrapargs 26 }
- mtrapargsOctetString05 OBJECT-TYPE
- SYNTAX OCTET STRING
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID allows APC traps to be sent with an octet string argument
- that my not be defined in the APC MIB.
-
- A get of this OID will return a NULL string."
- ::= { mtrapargs 27 }
- mtrapargsOctetString06 OBJECT-TYPE
- SYNTAX OCTET STRING
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID allows APC traps to be sent with an octet string argument
- that my not be defined in the APC MIB.
-
- A get of this OID will return a NULL string."
- ::= { mtrapargs 28 }
- mtrapargsOctetString07 OBJECT-TYPE
- SYNTAX OCTET STRING
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID allows APC traps to be sent with an octet string argument
- that my not be defined in the APC MIB.
-
- A get of this OID will return a NULL string."
- ::= { mtrapargs 29 }
- mtrapargsOctetString08 OBJECT-TYPE
- SYNTAX OCTET STRING
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID allows APC traps to be sent with an octet string argument
- that my not be defined in the APC MIB.
-
- A get of this OID will return a NULL string."
- ::= { mtrapargs 30 }
- -- the mfiletransfer group
- -- the mfiletransferStatus group
- mfiletransferStatusLastTransferResult OBJECT-TYPE
- SYNTAX INTEGER {
- lastFileTransferResultSuccessful (1),
- lastFileTransferResultNotAvailable (2),
- lastFileTransferResultFailureUnknown (3),
- lastFileTransferResultFailureServerInaccessible (4),
- lastFileTransferResultFailureServerAccessDenied (5),
- lastFileTransferResultFailureFileNotFound (6),
- lastFileTransferResultFailureFileTypeUnknown (7),
- lastFileTransferResultFailureFileCorrupted (8)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Once mfiletransferControlInitiateFileTransfer is set to a value other than doNotInitiateFileTransfer
- a file transfer of mfiletransferConfigSettingsFilename will be attempted from either a TFTP or FTP
- server.
-
- This OID shows the last attempted file transfer result.
- lastFileTransferResultSuccessful (1) means the file transfer was successful.
- lastFileTransferResultNotAvailable (2) means that there have been no previous file transfers.
- lastFileTransferResultFailureUnknown (3) means that the last file transfer failed for an unknown reason.
- lastFileTransferResultFailureServerInaccessible (4) means that the TFTP or FTP server could not be found on the network.
- lastFileTransferResultFailureServerAccessDenied (5) means that the TFTP or FTP server denied access.
- lastFileTransferResultFailureFileNotFound (6) means that the file could not be located.
- lastFileTransferResultFailureFileTypeUnknown (7) means the file was examined, but the contents were unknown.
- lastFileTransferResultFailureFileCorrupt (8) means the transferred file was corrupt."
-
- ::= { mfiletransferStatus 1 }
-
- -- the mfiletransferConfig group
- -- the mfiletransferConfigSettings group
- mfiletransferConfigSettingsFilename OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The path and name of the file to transfer using the mfiletransferControlInitiateFileTransfer OID.
- If the file to transfer exists in the default server directory then the path may be omitted."
- ::= { mfiletransferConfigSettings 1 }
- -- the mfiletransferConfigTFTP group
- mfiletransferConfigTFTPServerAddress OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The IP Address in dotted decimal notation of the TFTP server involved in the file transfer."
- ::= { mfiletransferConfigTFTP 1 }
- -- the mfiletransferConfigFTP group
- mfiletransferConfigFTPServerAddress OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The IP Address in dotted decimal notation of the FTP server involved in the file transfer."
- ::= { mfiletransferConfigFTP 1 }
- mfiletransferConfigFTPServerUser OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The user identification for logging into the FTP server specified with mfiletransferConfigFTPServerAddress."
- ::= { mfiletransferConfigFTP 2 }
- mfiletransferConfigFTPServerPassword OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The password for logging into the FTP server specified with mfiletransferConfigFTPServerAddress."
- ::= { mfiletransferConfigFTP 3 }
- -- the mfiletransferControl group
- mfiletransferControlInitiateFileTransfer OBJECT-TYPE
- SYNTAX INTEGER {
- doNotInitiateFileTransfer (1),
- initiateFileTransferDownloadViaTFTP (2),
- initiateFileTransferDownloadViaFTP (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Setting this OID to doNotInitiateFileTransfer (1) will do nothing.
-
- Setting this OID to initiateFileTransferDownloadViaTFTP (2) will attempt to transfer the file named in
- mfiletransferConfigSettingsFilename from the TFTP Server identified in mfiletransferConfigTFTPAddress.
-
- Setting this OID to initiateFileTransferDownloadViaFTP (3) will attempt to transfer the file named in
- mfiletransferConfigSettingsFilename from the FTP Server identified in mfiletransferConfigFTPAddress
- using mfiletransferConfigFTPUser and mfiletransferConfigFTPPassword for the FTP Server login process."
- ::= { mfiletransferControl 1 }
- -- the battManIdent group
- battManIdentProductName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The name of the battery manager."
- ::= { battManIdent 1 }
- battManIdentHardwareRev OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The battery manager network interface hardware revision.
- This value is set at the factory."
- ::= { battManIdent 2 }
- battManIdentFirmwareRev OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The battery manager network interface firmware revision.
- This value is set at the factory and can change with firmware update."
- ::= { battManIdent 3 }
- battManIdentDateOfManufacture OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The date the battery manager was manufactured in mm/dd/yyyy format.
- This value is set at the factory."
- ::= { battManIdent 4 }
-
- battManIdentModelNumber OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The battery manager model number character string.
- This value is set at the factory."
- ::= { battManIdent 5 }
- battManIdentSerialNumber OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The battery manager serial number character string.
- This value is set at the factory."
- ::= { battManIdent 6 }
- -- the battManCalib group
- -- system calibration
- battManOhmicValueCorrectionFactor OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The system ohmic value correction factor in percent."
- ::= { battManSystemCalib 1 }
- -- unit calibration
- battManUnitCalibTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the battManUnitCalibTable."
- ::= { battManUnitCalib 1 }
-
- battManUnitCalibTable OBJECT-TYPE
- SYNTAX SEQUENCE OF BattManUnitCalibEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting calibration information from each unit in the system."
- ::= { battManUnitCalib 2 }
-
- battManUnitCalibEntry OBJECT-TYPE
- SYNTAX BattManUnitCalibEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The unit to get data from."
- INDEX { battManUnitCalibIndex }
- ::= { battManUnitCalibTable 1 }
-
- BattManUnitCalibEntry ::=
- SEQUENCE {
- battManUnitCalibIndex INTEGER,
- battManUnitSerialNumber DisplayString,
- battManBatteryVoltageZeroCalib INTEGER,
- battManBatteryVoltageSpanCalib INTEGER
- }
- battManUnitCalibIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Index of unit calibration entries in the table."
- ::= { battManUnitCalibEntry 1 }
- battManUnitSerialNumber OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The serial number of the unit."
- ::= { battManUnitCalibEntry 2 }
- battManBatteryVoltageZeroCalib OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The unit battery voltage zero calibration in millivolts."
- ::= { battManUnitCalibEntry 3 }
- battManBatteryVoltageSpanCalib OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The unit battery voltage span calibration in percent."
- ::= { battManUnitCalibEntry 4 }
- -- string calibration table
- battManStringCalibTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the battManStringCalibTable."
- ::= { battManStringCalib 1 }
-
- battManStringCalibTable OBJECT-TYPE
- SYNTAX SEQUENCE OF BattManStringCalibEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting calibration information from each string in the system."
- ::= { battManStringCalib 2 }
-
- battManStringCalibEntry OBJECT-TYPE
- SYNTAX BattManStringCalibEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The string to get data from."
- INDEX { battManStringCalibIndex }
- ::= { battManStringCalibTable 1 }
-
- BattManStringCalibEntry ::=
- SEQUENCE {
- battManStringCalibIndex INTEGER,
- battManDCCurrentZeroCalib INTEGER,
- battManACCurrentZeroCalib INTEGER,
- battManProbeRange INTEGER
- }
- battManStringCalibIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Index of string calibration entries in the table."
- ::= { battManStringCalibEntry 1 }
- battManDCCurrentZeroCalib OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The string DC current zero calibration in tenths of amps."
- ::= { battManStringCalibEntry 2 }
- battManACCurrentZeroCalib OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The string AC current zero calibration in tenths of amps."
- ::= { battManStringCalibEntry 3 }
- battManProbeRange OBJECT-TYPE
- SYNTAX INTEGER {
- amps1000 (1),
- amps500 (2),
- amps100 (3),
- amps200 (4),
- amps2000 (5)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The string probe range in amps."
- ::= { battManStringCalibEntry 4 }
- --string 1 battery calibration table
- battManString1BatteryCalibTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the battManString1BatteryCalibTable."
- ::= { battManBatteryCalib 1 }
-
- battManString1BatteryCalibTable OBJECT-TYPE
- SYNTAX SEQUENCE OF BattManString1BatteryCalibEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting calibration information from each battery in String 1."
- ::= { battManBatteryCalib 2 }
-
- battManString1BatteryCalibEntry OBJECT-TYPE
- SYNTAX BattManString1BatteryCalibEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The string to get data from."
- INDEX { battManString1BatteryCalibIndex }
- ::= { battManString1BatteryCalibTable 1 }
-
- BattManString1BatteryCalibEntry ::=
- SEQUENCE {
- battManString1BatteryCalibIndex INTEGER,
- battManString1BatteryInterTierOhmicValue INTEGER
- }
- battManString1BatteryCalibIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Index of battery calibration entries in the table."
- ::= { battManString1BatteryCalibEntry 1 }
- battManString1BatteryInterTierOhmicValue OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The battery inter-tier ohmic value in ohms. This corresponds to the ohmic
- value for the positive terminal of the battery."
- ::= { battManString1BatteryCalibEntry 2 }
- --string 2 battery calibration table
- battManString2BatteryCalibTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the battManString2BatteryCalibTable."
- ::= { battManBatteryCalib 3 }
-
- battManString2BatteryCalibTable OBJECT-TYPE
- SYNTAX SEQUENCE OF BattManString2BatteryCalibEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting calibration information from each battery in String 2."
- ::= { battManBatteryCalib 4 }
-
- battManString2BatteryCalibEntry OBJECT-TYPE
- SYNTAX BattManString2BatteryCalibEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The string to get data from."
- INDEX { battManString2BatteryCalibIndex }
- ::= { battManString2BatteryCalibTable 1 }
-
- BattManString2BatteryCalibEntry ::=
- SEQUENCE {
- battManString2BatteryCalibIndex INTEGER,
- battManString2BatteryInterTierOhmicValue INTEGER
- }
- battManString2BatteryCalibIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Index of battery calibration entries in the table."
- ::= { battManString2BatteryCalibEntry 1 }
- battManString2BatteryInterTierOhmicValue OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The battery inter-tier ohmic value in ohms."
- ::= { battManString2BatteryCalibEntry 2 }
- -- the battManConfig group
- battManConfigApplication OBJECT-TYPE
- SYNTAX INTEGER {
- silcon (1),
- other (2)
- }
- ACCESS read-write
- STATUS deprecated
- DESCRIPTION
- "This OID has been deprecated."
- ::= { battManConfig 1 }
- battManConfigBatteryChemistry OBJECT-TYPE
- SYNTAX INTEGER {
- leadAcid (1),
- nickel-Cadmium (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The battery chemistry of the monitored batteries:
- LeadAcid(1) Lead Acid or
- Nickel-Cadmium(2) Nickel-Cadmium."
- ::= { battManConfig 2 }
- battManConfigBatteryAHCapacity OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The amp hour capacity of the monitored batteries 5-2000 AH."
- ::= { battManConfig 3 }
- battManConfigNumberofStrings OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The number of strings in the battery manager system."
- ::= { battManConfig 4 }
- battManConfigBatteriesperString OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The number of batteries per string."
- ::= { battManConfig 5 }
- battManConfigCellsperBattery OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The number of cells per battery (1 - 6 for lead-acid, 1 - 2 for NiCd."
- ::= { battManConfig 6 }
- battManConfigMinCellVoltage OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The minimum battery cell voltage alarm limit in millivolts DC."
- ::= { battManConfig 7 }
- battManConfigMaxCellVoltage OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The maximum battery cell voltage alarm limit in millivolts DC."
- ::= { battManConfig 8 }
- battManConfigMaxPilotTempF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The maximum pilot battery temperature alarm limit in tenths of degrees Fahrenheit."
- ::= { battManConfig 9 }
- battManConfigMaxPilotTempC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The maximum pilot battery temperature alarm limit in tenths of degrees Celsius."
- ::= { battManConfig 10 }
- battManConfigMaxAmbientTempF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The maximum ambient temperature alarm limit in tenths of degrees Fahrenheit."
- ::= { battManConfig 11 }
- battManConfigMaxAmbientTempC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The maximum ambient temperature alarm limit in tenths of degrees Celsius."
- ::= { battManConfig 12 }
- battManConfigMinAmbientTempF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The Minimum Ambient Temperature alarm limit in tenths of degrees Fahrenheit."
- ::= { battManConfig 13 }
- battManConfigMinAmbientTempC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The Minimum Ambient Temperature alarm limit in tenths of degrees Celsius."
- ::= { battManConfig 14 }
- battManConfigMaxRippleCurrent OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The maximum ripple current alarm limit for the monitored battery
- strings in percent of AH capacity."
- ::= { battManConfig 15 }
- battManConfigMaxCurrentAcceptanceDeviation OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The maximum current acceptance deviation alarm limit in percent."
- ::= { battManConfig 16 }
- battManConfigMonitorWireLength OBJECT-TYPE
- SYNTAX INTEGER {
- fiftyFeetOrLess (1),
- moreThanFiftyFeet (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The monitor wire length:
- fiftyFeetOrLess (1) indicates that the wire length is less than or equal to 50 feet.
- moreThanFiftyFeet (2) indicates that the wire length is greater than 50 feet."
- ::= { battManConfig 17 }
- battManConfigDischargeVoltageAlarmLevel OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The discharge voltage alarm level in percent."
- ::= { battManConfig 18 }
- battManConfigAutoAnnunciatorReset OBJECT-TYPE
- SYNTAX INTEGER {
- disabled (1),
- enabled (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The annunciator output signal reset method:
- disabled(1) means the annunciator signal output will be reset when the reset button is pressed.
- enabled(2) means the annunciator will stop signaling when all alarm conditions clear."
- ::= { battManConfig 19 }
- battManConfigSuspendCellVoltage OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "This is used along with the number of cells per battery
- and the number of batteries per string to determine if
- a battery string has violated the low voltage limit. If
- so, the Battery Management System will enter suspend mode.
- Measured in millivolts DC"
- ::= { battManConfig 20 }
- battManConfigOhmicTestWaitTime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The amount of time in seconds after a discharge event before
- data will be collected for the ohmic value calculation."
- ::= { battManConfig 21 }
- battManConfigNumberOfBoosts OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The number of consecutive times the Battery Management
- System applies a charge to each battery during a boost
- cycle. Batteries with a Rated Battery AH Capacity
- less than or equal to 120 AH will always have a value
- of one for Number of Boosts."
- ::= { battManConfig 22 }
- -- the battManAlarm group
- battManAlarmManagementController OBJECT-TYPE
- SYNTAX INTEGER {
- normal (1),
- alarm (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The Management Controller Alarm is :
- normal(1) no alarm conditions identified
- alarm(2) an alarm condition exists."
- ::= { battManAlarm 1 }
- battManAlarmBatteries OBJECT-TYPE
- SYNTAX INTEGER {
- normal (1),
- alarm (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The Batteries Alarm is :
- normal(1) no alarm conditions identified
- alarm(2) an alarm condition exists."
- ::= { battManAlarm 2 }
- battManAlarmCharger OBJECT-TYPE
- SYNTAX INTEGER {
- normal (1),
- alarm (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The Charger Alarm is :
- normal(1) no alarm conditions identified
- alarm(2) an alarm condition exists."
- ::= { battManAlarm 3 }
- battManAlarmEnvironment OBJECT-TYPE
- SYNTAX INTEGER {
- normal (1),
- alarm (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The Environment Alarm is :
- normal(1) no alarm conditions identified
- alarm(2) an alarm condition exists."
- ::= { battManAlarm 4 }
- -- the battManSystemStatus group
- -- These are system wide parameters
- battManSystemAmbientTempC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The system ambient temperature in tenths of degrees Celsius."
- ::= { battManSystemStatus 1 }
- battManSystemAmbientTempF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The system ambient temperature in tenths of degrees Fahrenheit."
- ::= { battManSystemStatus 2 }
- battManSystemPilotTempC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The system pilot temperature in tenths of degrees Celsius."
- ::= { battManSystemStatus 3 }
- battManSystemPilotTempF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The system pilot temperature in tenths of degrees Fahrenheit."
- ::= { battManSystemStatus 4 }
- battManSystemAmbientHighTempAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- normal (1),
- alarm (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "When set to alarm(2), indicates that the system has a high temperature alarm."
- ::= { battManSystemStatus 5 }
- battManSystemAmbientLowTempAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- normal (1),
- alarm (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "When set to alarm(2), indicates that the system has a low temperature alarm."
- ::= { battManSystemStatus 6 }
- battManSystemPilotBatteryHighTempAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- normal (1),
- alarm (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "When set to alarm(2), indicates that the system has a pilot battery high temperature alarm."
- ::= { battManSystemStatus 7 }
- battManSystemPilotProbeDisconnected OBJECT-TYPE
- SYNTAX INTEGER {
- normal (1),
- alarm (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "When set to alarm(2), indicates that the system pilot probe is disconnected."
- ::= { battManSystemStatus 8 }
- battManSystemAmbientProbeDisconnected OBJECT-TYPE
- SYNTAX INTEGER {
- normal (1),
- alarm (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "When set to alarm(2), indicates that the system ambient probe is disconnected."
- ::= { battManSystemStatus 9 }
- battManSystemConfigurationInvalid OBJECT-TYPE
- SYNTAX INTEGER {
- normal (1),
- alarm (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "When set to alarm(2), indicates that the system is not configured correctly."
- ::= { battManSystemStatus 10 }
- battManSystemSuspendVoltage OBJECT-TYPE
- SYNTAX INTEGER {
- normal (1),
- alarm (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "When set to alarm(2), indicates that the system has suspended voltage scans."
- ::= { battManSystemStatus 11 }
- -- This is a table of input contact parameters
- battManInputContactTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the battManInputContactTable."
- ::= { battManInputContactStatus 1 }
- battManInputContactTable OBJECT-TYPE
- SYNTAX SEQUENCE OF BattManInputContactEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting information from each contact
- in the system. "
- ::= { battManInputContactStatus 2 }
- battManInputContactEntry OBJECT-TYPE
- SYNTAX BattManInputContactEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The contact to get data from."
- INDEX { battManInputContactIndex }
- ::= { battManInputContactTable 1 }
- BattManInputContactEntry ::=
- SEQUENCE {
- battManInputContactIndex INTEGER,
- battManInputContactName DisplayString,
- battManInputContactAlarmState INTEGER,
- battManInputContactState INTEGER,
- battManInputContactNormalState INTEGER,
- battManInputContactAlarmDelay INTEGER
- }
-
- battManInputContactIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Index of contact entries in the table."
- ::= { battManInputContactEntry 1 }
- battManInputContactName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The name of the input contact."
- ::= { battManInputContactEntry 2 }
- battManInputContactAlarmState OBJECT-TYPE
- SYNTAX INTEGER {
- normal (1),
- alarm (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "When set to alarm(2), indicates that the alarm condition is active for this contact."
- ::= { battManInputContactEntry 3 }
- battManInputContactState OBJECT-TYPE
- SYNTAX INTEGER {
- open (1),
- closed (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "When set to open(1), the input contact is in the open state.
- When set to closed(2), the input contact is in the closed state."
- ::= { battManInputContactEntry 4 }
- battManInputContactNormalState OBJECT-TYPE
- SYNTAX INTEGER {
- open (1),
- closed (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "When set to open(1), the input contact is normally open.
- When set to closed(2), the input contact is normally closed."
- ::= { battManInputContactEntry 5 }
- battManInputContactAlarmDelay OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The input contact alarm delay time in seconds."
- ::= { battManInputContactEntry 6 }
- -- This is a table of battery string parameters
- battManStringTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the battManStringTable."
- ::= { battManStringStatus 1 }
- battManStringTable OBJECT-TYPE
- SYNTAX SEQUENCE OF BattManStringEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting information from each string
- in the system. "
- ::= { battManStringStatus 2 }
- battManStringEntry OBJECT-TYPE
- SYNTAX BattManStringEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The string to get data from."
- INDEX { battManStringIndex }
- ::= { battManStringTable 1 }
- BattManStringEntry ::=
- SEQUENCE {
- battManStringIndex INTEGER,
- battManStringCurrent INTEGER,
- battManStringRippleCurrent INTEGER,
- battManStringChargerHighVoltageAlarm INTEGER,
- battManStringChargerLowVoltageAlarm INTEGER,
- battManStringCurrentProbeDisconnected INTEGER,
- battManStringOnBattery INTEGER,
- battManStringHighRippleCurrent INTEGER,
- battManStringVoltage INTEGER,
- battManStringDischargeLess5Seconds INTEGER,
- battManStringDischarge5to10Seconds INTEGER,
- battManStringDischarge10to60Seconds INTEGER,
- battManStringDischargeMore60Seconds INTEGER
- }
-
- battManStringIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Index of string entries in the table."
- ::= { battManStringEntry 1 }
- battManStringCurrent OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The string current in tenths of amps."
- ::= { battManStringEntry 2 }
- battManStringRippleCurrent OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The string ripple current in tenths of amps."
- ::= { battManStringEntry 3 }
- battManStringChargerHighVoltageAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- normal (1),
- alarm (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "When set to alarm(2), indicates that the string charger has a high voltage alarm."
- ::= { battManStringEntry 4 }
- battManStringChargerLowVoltageAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- normal (1),
- alarm (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "When set to alarm(2), indicates that the string charger has a low voltage alarm."
- ::= { battManStringEntry 5 }
- battManStringCurrentProbeDisconnected OBJECT-TYPE
- SYNTAX INTEGER {
- normal (1),
- alarm (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "When set to alarm(2), indicates that the string charger probe is disconnected."
- ::= { battManStringEntry 6 }
- battManStringOnBattery OBJECT-TYPE
- SYNTAX INTEGER {
- normal (1),
- alarm (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "When set to alarm(2), indicates that the string is in the on-battery state."
- ::= { battManStringEntry 7 }
- battManStringHighRippleCurrent OBJECT-TYPE
- SYNTAX INTEGER {
- normal (1),
- alarm (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "When set to alarm(2), indicates that the string has a high ripple current."
- ::= { battManStringEntry 8 }
- battManStringVoltage OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The sum of the voltages for all of the batteries on a
- string in millivolts DC."
- ::= { battManStringEntry 9 }
- battManStringDischargeLess5Seconds OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of recorded discharges lasting less than
- 5 seconds."
- ::= { battManStringEntry 10 }
- battManStringDischarge5to10Seconds OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of recorded discharges lasting between 5
- and 10 seconds."
- ::= { battManStringEntry 11 }
- battManStringDischarge10to60Seconds OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of recorded discharges lasting between 10
- and 60 seconds."
- ::= { battManStringEntry 12 }
- battManStringDischargeMore60Seconds OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of recorded discharges lasting more than
- 60 seconds (1 minute)."
- ::= { battManStringEntry 13 }
- -- the battManString1BatteryStatus group
- battManString1BatteryTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the battManString1BatteryTable."
- ::= { battManBatteryStatus 1 }
- battManString1BatteryTable OBJECT-TYPE
- SYNTAX SEQUENCE OF BattManString1BatteryEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting information from each string
- in the system. "
- ::= { battManBatteryStatus 2 }
- battManString1BatteryEntry OBJECT-TYPE
- SYNTAX BattManString1BatteryEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The string to get data from."
- INDEX { battManString1BatteryIndex }
- ::= { battManString1BatteryTable 1 }
- BattManString1BatteryEntry ::=
- SEQUENCE {
- battManString1BatteryIndex INTEGER,
- battManString1BatteryVoltage INTEGER,
- battManString1BatteryLowestVoltage INTEGER,
- battManString1BatteryCellShorted INTEGER,
- battManString1BatteryOpenFuseOrConnection INTEGER,
- battManString1BatteryLowCapacity INTEGER,
- battManString1BatteryHighOhmicValue INTEGER,
- battManString1BatteryThermalRunaway INTEGER,
- battManString1BatteryDryout INTEGER,
- battManString1BatteryUserHighVoltageAlarm INTEGER,
- battManString1BatteryUserLowVoltageAlarm INTEGER,
- battManString1BatteryChemHighVoltageAlarm INTEGER,
- battManString1BatteryChemLowVoltageAlarm INTEGER,
- battManString1BatteryOpenCell INTEGER
- }
-
- battManString1BatteryIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Index of string entries in the table."
- ::= { battManString1BatteryEntry 1 }
- battManString1BatteryVoltage OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The battery voltage in millivolts DC."
- ::= { battManString1BatteryEntry 2 }
-
- battManString1BatteryLowestVoltage OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The lowest battery discharge voltage during the last power event in millivolts DC."
- ::= { battManString1BatteryEntry 3 }
-
- battManString1BatteryCellShorted OBJECT-TYPE
- SYNTAX INTEGER {
- normal (1),
- alarm (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "When set to alarm(2), indicates that a battery cell is shorted."
- ::= { battManString1BatteryEntry 4 }
- battManString1BatteryOpenFuseOrConnection OBJECT-TYPE
- SYNTAX INTEGER {
- normal (1),
- alarm (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "When set to alarm(2), indicates that a fuse or connection is open."
- ::= { battManString1BatteryEntry 5 }
- battManString1BatteryLowCapacity OBJECT-TYPE
- SYNTAX INTEGER {
- normal (1),
- alarm (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "When set to alarm(2), indicates a battery has low capacity."
- ::= { battManString1BatteryEntry 6 }
- battManString1BatteryHighOhmicValue OBJECT-TYPE
- SYNTAX INTEGER {
- normal (1),
- alarm (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "When set to alarm(2), indicates a battery has a high ohmic value."
- ::= { battManString1BatteryEntry 7 }
- battManString1BatteryThermalRunaway OBJECT-TYPE
- SYNTAX INTEGER {
- normal (1),
- alarm (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "When set to alarm(2), indicates a battery has a thermal runaway condition."
- ::= { battManString1BatteryEntry 8 }
- battManString1BatteryDryout OBJECT-TYPE
- SYNTAX INTEGER {
- normal (1),
- alarm (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "When set to alarm(2), indicates a battery has a dryout condition."
- ::= { battManString1BatteryEntry 9 }
- battManString1BatteryUserHighVoltageAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- normal (1),
- alarm (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "When set to alarm(2), indicates a battery has violated
- the user level high voltage limit."
- ::= { battManString1BatteryEntry 10 }
- battManString1BatteryUserLowVoltageAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- normal (1),
- alarm (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "When set to alarm(2), indicates a battery has violated
- the user level low voltage limit."
- ::= { battManString1BatteryEntry 11 }
- battManString1BatteryChemHighVoltageAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- normal (1),
- alarm (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "When set to alarm(2), indicates a battery has violated
- the chemistry level high voltage limit."
- ::= { battManString1BatteryEntry 12 }
- battManString1BatteryChemLowVoltageAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- normal (1),
- alarm (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "When set to alarm(2), indicates a battery has violated
- the chemistry level low voltage limit."
- ::= { battManString1BatteryEntry 13 }
- battManString1BatteryOpenCell OBJECT-TYPE
- SYNTAX INTEGER {
- normal (1),
- alarm (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "When set to alarm(2), indicates the battery has an open
- cell or an inter-connection is abnormal."
- ::= { battManString1BatteryEntry 14 }
- -- the battManString2BatteryStatus group
- battManString2BatteryTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the battManString2BatteryTable."
- ::= { battManBatteryStatus 3 }
- battManString2BatteryTable OBJECT-TYPE
- SYNTAX SEQUENCE OF BattManString2BatteryEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting information from each string
- in the system. "
- ::= { battManBatteryStatus 4 }
- battManString2BatteryEntry OBJECT-TYPE
- SYNTAX BattManString2BatteryEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The string to get data from."
- INDEX { battManString2BatteryIndex }
- ::= { battManString2BatteryTable 1 }
- BattManString2BatteryEntry ::=
- SEQUENCE {
- battManString2BatteryIndex INTEGER,
- battManString2BatteryVoltage INTEGER,
- battManString2BatteryLowestVoltage INTEGER,
- battManString2BatteryCellShorted INTEGER,
- battManString2BatteryOpenFuseOrConnection INTEGER,
- battManString2BatteryLowCapacity INTEGER,
- battManString2BatteryHighOhmicValue INTEGER,
- battManString2BatteryThermalRunaway INTEGER,
- battManString2BatteryDryout INTEGER,
- battManString2BatteryUserHighVoltageAlarm INTEGER,
- battManString2BatteryUserLowVoltageAlarm INTEGER,
- battManString2BatteryChemHighVoltageAlarm INTEGER,
- battManString2BatteryChemLowVoltageAlarm INTEGER,
- battManString2BatteryOpenCell INTEGER
- }
-
- battManString2BatteryIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Index of string entries in the table."
- ::= { battManString2BatteryEntry 1 }
- battManString2BatteryVoltage OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The battery voltage in millivolts DC."
- ::= { battManString2BatteryEntry 2 }
-
- battManString2BatteryLowestVoltage OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The lowest battery discharge voltage during the last power event in millivolts DC."
- ::= { battManString2BatteryEntry 3 }
-
- battManString2BatteryCellShorted OBJECT-TYPE
- SYNTAX INTEGER {
- normal (1),
- alarm (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "When set to alarm(2), indicates that a battery cell is shorted."
- ::= { battManString2BatteryEntry 4 }
- battManString2BatteryOpenFuseOrConnection OBJECT-TYPE
- SYNTAX INTEGER {
- normal (1),
- alarm (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "When set to alarm(2), indicates that a fuse or connection is open."
- ::= { battManString2BatteryEntry 5 }
- battManString2BatteryLowCapacity OBJECT-TYPE
- SYNTAX INTEGER {
- normal (1),
- alarm (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "When set to alarm(2), indicates a battery has low capacity."
- ::= { battManString2BatteryEntry 6 }
- battManString2BatteryHighOhmicValue OBJECT-TYPE
- SYNTAX INTEGER {
- normal (1),
- alarm (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "When set to alarm(2), indicates a battery has a high ohmic value."
- ::= { battManString2BatteryEntry 7 }
- battManString2BatteryThermalRunaway OBJECT-TYPE
- SYNTAX INTEGER {
- normal (1),
- alarm (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "When set to alarm(2), indicates a battery has a thermal runaway condition."
- ::= { battManString2BatteryEntry 8 }
- battManString2BatteryDryout OBJECT-TYPE
- SYNTAX INTEGER {
- normal (1),
- alarm (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "When set to alarm(2), indicates a battery has a dryout condition."
- ::= { battManString2BatteryEntry 9 }
- battManString2BatteryUserHighVoltageAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- normal (1),
- alarm (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "When set to alarm(2), indicates a battery has violated
- the user level high voltage limit."
- ::= { battManString2BatteryEntry 10 }
- battManString2BatteryUserLowVoltageAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- normal (1),
- alarm (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "When set to alarm(2), indicates a battery has violated
- the user level low voltage limit."
- ::= { battManString2BatteryEntry 11 }
- battManString2BatteryChemHighVoltageAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- normal (1),
- alarm (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "When set to alarm(2), indicates a battery has violated
- the chemistry level high voltage limit."
- ::= { battManString2BatteryEntry 12 }
- battManString2BatteryChemLowVoltageAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- normal (1),
- alarm (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "When set to alarm(2), indicates a battery has violated
- the chemistry level low voltage limit."
- ::= { battManString2BatteryEntry 13 }
- battManString2BatteryOpenCell OBJECT-TYPE
- SYNTAX INTEGER {
- normal (1),
- alarm (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "When set to alarm(2), indicates the battery has an open
- cell or an inter-connection is abnormal."
- ::= { battManString2BatteryEntry 14 }
- -- battery manager control group
- battManRemoteAnnunciatorReset OBJECT-TYPE
- SYNTAX INTEGER {
- noOperation (1),
- reset (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Setting this OID to reset(2) will reset the user interface annunciator.
- Getting this OID will do nothing and return the noOperation(1) value."
- ::= { battManControl 1 }
- battManResetChargeCurrentDeviationBenchmark OBJECT-TYPE
- SYNTAX INTEGER {
- noOperation (1),
- reset (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Setting this OID to reset(2) will reset the charge current deviation benchmark.
- Getting this OID will do nothing and return the noOperation(1) value."
- ::= { battManControl 2 }
- battManResetLowestDischargeVoltages OBJECT-TYPE
- SYNTAX INTEGER {
- noOperation (1),
- reset (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Setting this OID to reset(2) will reset the lowest discharge voltages.
- Getting this OID will do nothing and return the noOperation(1) value."
- ::= { battManControl 3 }
- battManResetDischargeCounters OBJECT-TYPE
- SYNTAX INTEGER {
- noOperation (1),
- reset (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Setting this OID to reset(2) will reset all discharge event counters.
- Getting this OID will do nothing and return the noOperation(1) value."
- ::= { battManControl 4 }
- -- the battManTestResults group
- --string 1 test results table
- battManString1OhmicValueLastDischargeInfo OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Informational text showing the date/time, load, and pilot temperature for the string
- during the last discharge when ohmic values were recorded."
- ::= { battManTestResults 1 }
- battManString1OhmicValueTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the battManString1OhmicValueTable."
- ::= { battManTestResults 2 }
-
- battManString1OhmicValueTable OBJECT-TYPE
- SYNTAX SEQUENCE OF BattManString1OhmicValueEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting ohmic value information from each battery in String 1."
- ::= { battManTestResults 3 }
-
- battManString1OhmicValueEntry OBJECT-TYPE
- SYNTAX BattManString1OhmicValueEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The string to get data from."
- INDEX { battManString1OhmicValueIndex }
- ::= { battManString1OhmicValueTable 1 }
-
- BattManString1OhmicValueEntry ::=
- SEQUENCE {
- battManString1OhmicValueIndex INTEGER,
- battManString1OhmicValueData INTEGER
- }
- battManString1OhmicValueIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The battery number."
- ::= { battManString1OhmicValueEntry 1 }
- battManString1OhmicValueData OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The battery inter-tier ohmic value in ohms.
- Note: Zero or negative values are invalid and may indicate
- faulty calibration of ohmic value correction factors."
- ::= { battManString1OhmicValueEntry 2 }
- battManString1ResponseTestChangeTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the battManString1ResponseTestChangeTable."
- ::= { battManTestResults 4 }
-
- battManString1ResponseTestChangeTable OBJECT-TYPE
- SYNTAX SEQUENCE OF BattManString1ResponseTestChangeEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting response test change information from each battery in String 1."
- ::= { battManTestResults 5 }
-
- battManString1ResponseTestChangeEntry OBJECT-TYPE
- SYNTAX BattManString1ResponseTestChangeEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The string to get data from."
- INDEX { battManString1ResponseTestChangeIndex }
- ::= { battManString1ResponseTestChangeTable 1 }
-
- BattManString1ResponseTestChangeEntry ::=
- SEQUENCE {
- battManString1ResponseTestChangeIndex INTEGER,
- battManString1ResponseTestChangeData INTEGER
- }
- battManString1ResponseTestChangeIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Index of the entries in the table."
- ::= { battManString1ResponseTestChangeEntry 1 }
- battManString1ResponseTestChangeData OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The battery response test change in percent."
- ::= { battManString1ResponseTestChangeEntry 2 }
- battManString2OhmicValueLastDischargeInfo OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Informational text showing the date/time, load, and pilot temperature for the string
- during the last discharge when ohmic values were recorded."
- ::= { battManTestResults 6 }
- battManString2OhmicValueTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the battManString2OhmicValueTable."
- ::= { battManTestResults 7 }
-
- battManString2OhmicValueTable OBJECT-TYPE
- SYNTAX SEQUENCE OF BattManString2OhmicValueEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting ohmic value information from each battery in String 2."
- ::= { battManTestResults 8 }
-
- battManString2OhmicValueEntry OBJECT-TYPE
- SYNTAX BattManString2OhmicValueEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The string to get data from."
- INDEX { battManString2OhmicValueIndex }
- ::= { battManString2OhmicValueTable 1 }
-
- BattManString2OhmicValueEntry ::=
- SEQUENCE {
- battManString2OhmicValueIndex INTEGER,
- battManString2OhmicValueData INTEGER
- }
- battManString2OhmicValueIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Index of battery calibration entries in the table."
- ::= { battManString2OhmicValueEntry 1 }
- battManString2OhmicValueData OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The battery inter-tier ohmic value in ohms.
- Note: Zero or negative values are invalid and may indicate
- faulty calibration of ohmic value correction factors."
- ::= { battManString2OhmicValueEntry 2 }
- battManString2ResponseTestChangeTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the battManString2ResponseTestChangeTable."
- ::= { battManTestResults 9 }
-
- battManString2ResponseTestChangeTable OBJECT-TYPE
- SYNTAX SEQUENCE OF BattManString2ResponseTestChangeEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting response test change information from each battery in String 2."
- ::= { battManTestResults 10 }
-
- battManString2ResponseTestChangeEntry OBJECT-TYPE
- SYNTAX BattManString2ResponseTestChangeEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The string to get data from."
- INDEX { battManString2ResponseTestChangeIndex }
- ::= { battManString2ResponseTestChangeTable 1 }
-
- BattManString2ResponseTestChangeEntry ::=
- SEQUENCE {
- battManString2ResponseTestChangeIndex INTEGER,
- battManString2ResponseTestChangeData INTEGER
- }
- battManString2ResponseTestChangeIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Index of the entries in the table."
- ::= { battManString2ResponseTestChangeEntry 1 }
- battManString2ResponseTestChangeData OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The battery response test change in percent."
- ::= { battManString2ResponseTestChangeEntry 2 }
- -- battManUnitStatus
- battManUnitStatusTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the battManUnitStatusTable."
- ::= { battManUnitStatus 1 }
-
- battManUnitStatusTable OBJECT-TYPE
- SYNTAX SEQUENCE OF BattManUnitStatusEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting status information from each unit in the system."
- ::= { battManUnitStatus 2 }
-
- battManUnitStatusEntry OBJECT-TYPE
- SYNTAX BattManUnitStatusEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The unit to get data from."
- INDEX { battManUnitStatusIndex }
- ::= { battManUnitStatusTable 1 }
-
- BattManUnitStatusEntry ::=
- SEQUENCE {
- battManUnitStatusIndex INTEGER,
- battManUnitStatusSerialNumber DisplayString,
- battManUnitHardwareRev INTEGER,
- battManUnitFirmwareRev INTEGER,
- battManUnitCommLoss INTEGER,
- battManUnitRelayStuck INTEGER
- }
- battManUnitStatusIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Index of unit status entries in the table."
- ::= { battManUnitStatusEntry 1 }
- battManUnitStatusSerialNumber OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The battery manager unit serial number character string.
- This value is set at the factory."
- ::= { battManUnitStatusEntry 2 }
- battManUnitHardwareRev OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The battery manager unit hardware revision.
- This value is set at the factory."
- ::= { battManUnitStatusEntry 3 }
- battManUnitFirmwareRev OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The battery manager unit firmware revision.
- This value is set at the factory and can change with firmware update."
- ::= { battManUnitStatusEntry 4 }
- battManUnitCommLoss OBJECT-TYPE
- SYNTAX INTEGER {
- normal (1),
- alarm (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "When set to alarm(2), indicates the system has lost
- communication with the unit."
- ::= { battManUnitStatusEntry 5 }
- battManUnitRelayStuck OBJECT-TYPE
- SYNTAX INTEGER {
- normal (1),
- alarm (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "When set to alarm(2), indicates the unit monitor relay
- is stuck."
- ::= { battManUnitStatusEntry 6 }
- -- the xPDUIdent group
- xPDUIdentProductName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The name of the PDU."
- ::= { xPDUIdent 1 }
- xPDUIdentHardwareRev OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The hardware revision of the PDU.
- This value is set at the factory."
- ::= { xPDUIdent 2 }
- xPDUIdentFirmwareAppRev OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "An ID string identifying the application firmware revision of the PDU."
- ::= { xPDUIdent 3 }
- xPDUIdentFirmwareAppOSRev OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "An ID string identifying the application operating system firmware revision of the PDU."
- ::= { xPDUIdent 4 }
- xPDUIdentFirmwareControllerRev OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "An ID string identifying the PDU controller firmware revision."
- ::= { xPDUIdent 5 }
- xPDUIdentDateOfManufacture OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The date when the PDU was manufactured in mm/dd/yyyy format.
- This value is set at the factory."
- ::= { xPDUIdent 6 }
-
- xPDUIdentModelNumber OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the model number of
- the PDU. This value is set at the factory."
- ::= { xPDUIdent 7 }
- xPDUIdentSerialNumber OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the serial number of
- the PDU. This value is set at the factory."
- ::= { xPDUIdent 8 }
- -- the xPDUDevice group
- xPDUDeviceNominalMainInputVoltage OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The nominal main input voltage to the PDU.
- Measured in Volts, line-to-line for a delta service or
- line-to-neutral for a wye service."
- ::= { xPDUDevice 1 }
- xPDUDeviceServiceType OBJECT-TYPE
- SYNTAX INTEGER {
- delta (1),
- wye (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The type of utility input to the PDU. Either 3 wires (delta), or 4 wires (wye)."
- ::= { xPDUDevice 2 }
- xPDUDeviceNominalOutputVoltage OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The nominal line-to-neutral output voltage to the load measured in Volts."
- ::= { xPDUDevice 3 }
- xPDUDeviceMainInputBreakerRating OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The rating of the main input breaker measured in Amps."
- ::= { xPDUDevice 4 }
- xPDUDevicePanelBreakerRating OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The rating of the panel breaker measured in Amps."
- ::= { xPDUDevice 5 }
- xPDUDeviceTransformerPresent OBJECT-TYPE
- SYNTAX INTEGER {
- notPresent (1),
- present (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Indicates whether or not a transformer is installed in the PDU."
- ::= { xPDUDevice 6 }
- xPDUDeviceLoadTieBreakerPresent OBJECT-TYPE
- SYNTAX INTEGER {
- notPresent (1),
- present (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Indicates whether or not a load tie breaker is installed in the PDU."
- ::= { xPDUDevice 7 }
- xPDUDeviceLoadTestPortPresent OBJECT-TYPE
- SYNTAX INTEGER {
- notPresent (1),
- present (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Indicates whether or not a load test port is installed in the PDU."
- ::= { xPDUDevice 8 }
- xPDUDeviceFusesPresent OBJECT-TYPE
- SYNTAX INTEGER {
- notPresent (1),
- present (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Indicates whether or not the UPS feed from the PDU includes fuses."
- ::= { xPDUDevice 9 }
- xPDUDeviceFansPresent OBJECT-TYPE
- SYNTAX INTEGER {
- notPresent (1),
- present (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Indicates whether or not cooling fans are installed in the PDU."
- ::= { xPDUDevice 10 }
- xPDUDeviceBypassInputPresent OBJECT-TYPE
- SYNTAX INTEGER {
- notPresent (1),
- present (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Indicates whether or not the PDU is equipped with a second feed for
- the UPS's bypass input."
- ::= { xPDUDevice 11 }
- xPDUDeviceCrossTieOutputPresent OBJECT-TYPE
- SYNTAX INTEGER {
- notPresent (1),
- present (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Indicates whether or not the PDU is equipped with a cross-tie output."
- ::= { xPDUDevice 12 }
- xPDUDeviceEarthGroundMonitorPresent OBJECT-TYPE
- SYNTAX INTEGER {
- notPresent (1),
- present (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Indicates whether or not the PDU can provide ground current measurements."
- ::= { xPDUDevice 13 }
- xPDUDeviceInfraStruXureType OBJECT-TYPE
- SYNTAX INTEGER {
- typeB (1),
- typeC (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Indicates the configuration of this PDU system.
- Type-B PDU is in a distributed UPS system and has bypass capabilities.
- Type-C PDU receives power from a larger central UPS."
- ::= { xPDUDevice 14 }
- -- Main Input
- xPDUMainInputOverVoltThreshold OBJECT-TYPE
- SYNTAX INTEGER (0..30)
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Threshold above which an input over voltage condition will be generated.
- Specified as percent deviation from nominal."
- ::= { xPDUMainInput 1 }
- xPDUMainInputUnderVoltThreshold OBJECT-TYPE
- SYNTAX INTEGER (0..30)
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Threshold below which an input under voltage condition will be generated.
- Specified as percent deviation from nominal.
- A value of zero indicates that the threshold is disabled."
- ::= { xPDUMainInput 2 }
- -- Main Input Voltage Table
- xPDUMainInputVoltageTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of Main input voltage entries."
- ::= { xPDUMainInput 3 }
- xPDUMainInputVoltagePhaseTable OBJECT-TYPE
- SYNTAX SEQUENCE OF XPDUMainInputVoltagePhaseEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "A list of input voltage table entries. The number of
- entries are the phase entries.
- The number of entries is contained in the
- xPDUMainInputVoltageTableSize OID."
- ::= { xPDUMainInput 4 }
- xPDUMainInputVoltagePhaseEntry OBJECT-TYPE
- SYNTAX XPDUMainInputVoltagePhaseEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "An entry containing information applicable to a
- particular main input voltage phase."
- INDEX { xPDUMainInputVoltagePhaseIndex }
- ::= { xPDUMainInputVoltagePhaseTable 1 }
- XPDUMainInputVoltagePhaseEntry ::= SEQUENCE {
- xPDUMainInputVoltagePhaseIndex INTEGER,
- xPDUMainInputVoltageLtoL INTEGER,
- xPDUMainInputVoltageLtoN INTEGER
- }
- xPDUMainInputVoltagePhaseIndex OBJECT-TYPE
- SYNTAX INTEGER{
- phase1(1),
- phase2(2),
- phase3(3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Description of each input phase entry in the table."
- ::= { xPDUMainInputVoltagePhaseEntry 1 }
- xPDUMainInputVoltageLtoL OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Line-to-line PDU input voltage when an isolation transformer is present,
- or -1 if no transformer present in this PDU. Measured in tenths of Volts."
- ::= { xPDUMainInputVoltagePhaseEntry 2 }
- xPDUMainInputVoltageLtoN OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Line-to-neutral PDU input voltage when an isolation transformer is not present,
- or -1 if a transformer is present in this PDU. Measured in tenths of Volts."
- ::= { xPDUMainInputVoltagePhaseEntry 3 }
- xPDUBypassInputOverVoltThreshold OBJECT-TYPE
- SYNTAX INTEGER (0..30)
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Threshold above which a bypass input over voltage condition will be generated.
- Specified as percent deviation from nominal."
- ::= { xPDUBypassInput 1 }
- xPDUBypassInputUnderVoltThreshold OBJECT-TYPE
- SYNTAX INTEGER (0..30)
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Threshold below which an bypass input under voltage condition will be generated.
- Specified as percent deviation from nominal.
- A value of zero indicates that the threshold is disabled."
- ::= { xPDUBypassInput 2 }
- -- Bypass Input Voltage Table
- xPDUBypassInputVoltagePhaseTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of bypass input voltage entries."
- ::= { xPDUBypassInput 3 }
-
- xPDUBypassInputVoltagePhaseTable OBJECT-TYPE
- SYNTAX SEQUENCE OF XPDUBypassInputVoltagePhaseEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "A list of output table entries. The number of
- entries are the phase entries.
- The number of entries is contained in the
- xPDUBypassInputVoltagePhaseTableSize OID."
- ::= { xPDUBypassInput 4 }
- xPDUBypassInputVoltagePhaseEntry OBJECT-TYPE
- SYNTAX XPDUBypassInputVoltagePhaseEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "An entry containing information applicable to a
- particular bypass input voltage phase."
- INDEX { xPDUBypassInputVoltagePhaseIndex }
- ::= { xPDUBypassInputVoltagePhaseTable 1 }
- XPDUBypassInputVoltagePhaseEntry ::= SEQUENCE {
- xPDUBypassInputVoltagePhaseIndex INTEGER,
- xPDUBypassInputVoltageLtoL INTEGER,
- xPDUBypassInputVoltageLtoN INTEGER
- }
- xPDUBypassInputVoltagePhaseIndex OBJECT-TYPE
- SYNTAX INTEGER{
- phase1(1),
- phase2(2),
- phase3(3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Index of each bypass input phase entry in the table."
- ::= { xPDUBypassInputVoltagePhaseEntry 1 }
- xPDUBypassInputVoltageLtoL OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Line-to-line bypass input voltage, or -1 if no bypass
- feed is present in this PDU. Measured in tenths of Volts."
- ::= { xPDUBypassInputVoltagePhaseEntry 2 }
- xPDUBypassInputVoltageLtoN OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Line-to-neutral bypass input voltage, or -1 if no bypass
- feed is present in this PDU. Measured in tenths of Volts."
- ::= { xPDUBypassInputVoltagePhaseEntry 3 }
- -- UPS Input Table
- xPDUUPSInputVoltagePhaseTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of UPS input voltage entries."
- ::= { xPDUUPSInput 1 }
-
- xPDUUPSInputVoltagePhaseTable OBJECT-TYPE
- SYNTAX SEQUENCE OF XPDUUPSInputVoltagePhaseEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "A list of UPS input table entries. The number of
- entries are the phase entries.
- The number of entries is contained in the
- xPDUUPSInputVoltagePhaseTableSize OID."
- ::= { xPDUUPSInput 2 }
- xPDUUPSInputVoltagePhaseEntry OBJECT-TYPE
- SYNTAX XPDUUPSInputVoltagePhaseEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "An entry containing information applicable to a
- particular UPS input voltage phase."
- INDEX { xPDUUPSInputVoltagePhaseIndex }
- ::= { xPDUUPSInputVoltagePhaseTable 1 }
- XPDUUPSInputVoltagePhaseEntry ::= SEQUENCE {
- xPDUUPSInputVoltagePhaseIndex INTEGER,
- xPDUUPSInputVoltageLtoNPresent INTEGER
- }
- xPDUUPSInputVoltagePhaseIndex OBJECT-TYPE
- SYNTAX INTEGER{
- phase1(1),
- phase2(2),
- phase3(3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Description of each UPS input phase entry in the table."
- ::= { xPDUUPSInputVoltagePhaseEntry 1 }
- xPDUUPSInputVoltageLtoNPresent OBJECT-TYPE
- SYNTAX INTEGER {
- notPresent (1),
- present (2),
- unknown (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Indicates whether or not voltage is present at the UPS feed."
- ::= { xPDUUPSInputVoltagePhaseEntry 2 }
- -- System Output
- xPDUSystemOutputFrequency OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The system output frequency in tenths of Hertz."
- ::= { xPDUSystemOutput 1 }
- xPDUSystemOutputNeutralCurrent OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Shows the neutral current measured at the system output in tenths of Amps."
- ::= { xPDUSystemOutput 2 }
- xPDUSystemOutputTotalPower OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Shows the total system output power in tenths of kW."
- ::= { xPDUSystemOutput 3 }
- xPDUSystemOutputTotalApparentPower OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Shows the total system output power in tenths of kVA."
- ::= { xPDUSystemOutput 4 }
- xPDUSystemOutputTotalPowerFactor OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Indicates the total power factor of the system output.
- A value of 100 representing a unity power factor (1.00).
- Measured in hundredths."
- ::= { xPDUSystemOutput 5 }
- xPDUSystemOutputFrequencyTolerance OBJECT-TYPE
- SYNTAX INTEGER{
- freqToleranceOff (1),
- freqTolerancePointTwo (2),
- freqTolerancePointFive (3),
- freqToleranceOne (4),
- freqToleranceOnePointFive (5),
- freqToleranceTwo (6),
- freqToleranceThree (7),
- freqToleranceFour (8),
- freqToleranceFive (9),
- freqToleranceNine (10)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Shows the circuit panel output frequency tolerance in Hertz."
- ::= { xPDUSystemOutput 6 }
- xPDUSystemOutputMaxKWPower OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Defines 100% load in kW.
- Purpose is to set to match UPS capabilities."
- ::= { xPDUSystemOutput 7 }
- xPDUSystemOutputOverVoltThreshold OBJECT-TYPE
- SYNTAX INTEGER (0..30)
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Threshold above which an output over voltage condition will be generated.
- Specified as percent deviation from nominal."
- ::= { xPDUSystemOutput 8 }
- xPDUSystemOutputUnderVoltThreshold OBJECT-TYPE
- SYNTAX INTEGER (0..30)
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Threshold below which an output under voltage condition will be generated.
- Specified as percent deviation from nominal.
- A value of zero indicates that the threshold is disabled."
- ::= { xPDUSystemOutput 9 }
- xPDUSystemOutputOverCurrentThreshold OBJECT-TYPE
- SYNTAX INTEGER (0..100)
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Threshold above which an over current condition will be generated.
- Specified as a percent of the panel breaker rating.
- A value of zero indicates that the threshold is disabled."
- ::= { xPDUSystemOutput 10 }
- xPDUSystemOutputOverCurrentNeutralThreshold OBJECT-TYPE
- SYNTAX INTEGER (0..100)
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Threshold above which an Over current neutral condition will be generated.
- Specified as a percent of the panel breaker rating.
- A value of zero indicates that the threshold is disabled."
- ::= { xPDUSystemOutput 11 }
- xPDUSystemOutputUnderCurrentThreshold OBJECT-TYPE
- SYNTAX INTEGER (0..100)
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Threshold below which an under current condition will be generated.
- Specified as a percent of the panel breaker rating.
- A value of zero indicates that the threshold is disabled."
- ::= { xPDUSystemOutput 12 }
- xPDUSystemOutputTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of System Output phase entries."
- ::= { xPDUSystemOutput 13 }
-
- xPDUSystemOutputPhaseTable OBJECT-TYPE
- SYNTAX SEQUENCE OF XPDUSystemOutputPhaseEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "A list of system output table entries.
- The number of entries is contained in the
- xPDUSystemOutputTableSize OID."
- ::= { xPDUSystemOutput 14 }
- xPDUSystemOutputPhaseEntry OBJECT-TYPE
- SYNTAX XPDUSystemOutputPhaseEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "An entry containing information applicable to a
- particular system output phase."
- INDEX { xPDUSystemOutputPhaseIndex }
- ::= { xPDUSystemOutputPhaseTable 1 }
- XPDUSystemOutputPhaseEntry ::= SEQUENCE {
- xPDUSystemOutputPhaseIndex INTEGER,
- xPDUSystemOutputVoltageLtoL INTEGER,
- xPDUSystemOutputVoltageLtoN INTEGER,
- xPDUSystemOutputPhaseCurrent INTEGER,
- xPDUSystemOutputPower INTEGER,
- xPDUSystemOutputApparentPower INTEGER,
- xPDUSystemOutputPowerFactor INTEGER
- }
- xPDUSystemOutputPhaseIndex OBJECT-TYPE
- SYNTAX INTEGER{
- phase1(1),
- phase2(2),
- phase3(3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Description of each output phase entry in the table."
- ::= { xPDUSystemOutputPhaseEntry 1 }
- xPDUSystemOutputVoltageLtoL OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Line-to-line system output voltage available at the circuit panel.
- Measured in tenths of Volts."
- ::= { xPDUSystemOutputPhaseEntry 2 }
- xPDUSystemOutputVoltageLtoN OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Line-to-neutral system output voltage available at the circuit panel.
- Measured in tenths of Volts."
- ::= { xPDUSystemOutputPhaseEntry 3 }
- xPDUSystemOutputPhaseCurrent OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "System load current per phase. Measured in tenths of Amps."
- ::= { xPDUSystemOutputPhaseEntry 4 }
- xPDUSystemOutputPower OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "System output power per phase. Measured in tenths of kW."
- ::= { xPDUSystemOutputPhaseEntry 5 }
- xPDUSystemOutputApparentPower OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "System output power per phase. Measured in tenths of kVA."
- ::= { xPDUSystemOutputPhaseEntry 6 }
- xPDUSystemOutputPowerFactor OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Indicates the Power Factor of the system output per phase.
- A value of 100 representing a unity Power Factor (1.00).
- Measured in hundredths."
- ::= { xPDUSystemOutputPhaseEntry 7 }
- xPDUGroundCurrent OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Shows the current measured in the earth ground conductor.
- Measured in tenths of Amps, or -1 if not available."
- ::= { xPDUGroundMonitorPoint 1 }
- xPDUGroundCurrentThreshold OBJECT-TYPE
- SYNTAX INTEGER (0..50)
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Threshold above which a ground current over current
- condition will be generated. Specified in tenths of Amps."
- ::= { xPDUGroundMonitorPoint 2 }
- -- System Breakers
- xPDUSystemBreakerTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of system breaker entries."
- ::= { xPDUSystemBreakers 1 }
-
- xPDUSystemBreakerTable OBJECT-TYPE
- SYNTAX SEQUENCE OF XPDUSystemBreakerEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "A list of system breaker entries.
- The number of entries is contained in the
- xPDUSystemBreakerTableSize OID."
- ::= { xPDUSystemBreakers 2 }
- xPDUSystemBreakerEntry OBJECT-TYPE
- SYNTAX XPDUSystemBreakerEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "An entry containing information applicable to a
- particular system breaker."
- INDEX { xPDUSystemBreakerTableIndex }
- ::= { xPDUSystemBreakerTable 1 }
- XPDUSystemBreakerEntry ::= SEQUENCE {
- xPDUSystemBreakerTableIndex INTEGER,
- xPDUSystemBreakerDescription DisplayString,
- xPDUSystemBreakerPosition INTEGER
- }
- xPDUSystemBreakerTableIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Index of system breaker entries in the table."
- ::= { xPDUSystemBreakerEntry 1 }
- xPDUSystemBreakerDescription OBJECT-TYPE
- SYNTAX DisplayString (SIZE (0..79))
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A brief description of the system breakers."
- ::= { xPDUSystemBreakerEntry 2 }
- xPDUSystemBreakerPosition OBJECT-TYPE
- SYNTAX INTEGER {
- open (1),
- closed (2),
- unknown (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Indicates whether this breaker is open(1) or closed(2)."
- ::= { xPDUSystemBreakerEntry 3 }
- -- Branch Breakers (Breaker Panel)
- xPDUNumOfBranchBreakers OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of branch breakers (panel positions) in the Panel.
- returns 42 for a 1-panel or 84 for a 2-panel system."
- ::= { xPDUBranchBreakers 1 }
- -- Branch Breakers Table
- xPDUBranchBreakerTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of branch breaker entries determined by the xPDUNumOfBranchBreakers OID."
- ::= { xPDUBranchBreakers 2 }
-
- xPDUBranchBreakerTable OBJECT-TYPE
- SYNTAX SEQUENCE OF XPDUBranchBreakerEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "A list of branch breaker table entries. The
- number of entries is given by the value of xPDUBranchBreakerTableSize
- The number of entries is contained in the xPDUBranchBreakerTableSize OID."
- ::= { xPDUBranchBreakers 3 }
- xPDUBranchBreakerEntry OBJECT-TYPE
- SYNTAX XPDUBranchBreakerEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "An entry containing information applicable to a
- particular branch breaker (panel position)."
- INDEX { xPDUBranchBreakerTableIndex }
- ::= { xPDUBranchBreakerTable 1 }
- XPDUBranchBreakerEntry ::= SEQUENCE {
- xPDUBranchBreakerTableIndex INTEGER,
- xPDUBranchBreakerRating INTEGER,
- xPDUBranchBreakerRDPFeed INTEGER,
- xPDUBranchBreakerTieIndicator INTEGER,
- xPDUBranchBreakerCurrent INTEGER,
- xPDUBranchBreakerOverCurrentThreshold INTEGER,
- xPDUBranchBreakerUnderCurrentThreshold INTEGER,
- xPDUBranchBreakerMaxCurrentThreshold INTEGER,
- xPDUBranchBreakerMinCurrentThreshold INTEGER,
- xPDUBranchBreakerName DisplayString,
- xPDUBranchBreakerLocation DisplayString
- }
- xPDUBranchBreakerTableIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Index of branch breaker entries in the table."
- ::= { xPDUBranchBreakerEntry 1 }
- xPDUBranchBreakerRating OBJECT-TYPE
- SYNTAX INTEGER (0..100)
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Indicates current rating of this breaker.
- 0=Breaker is not present.
- 1=Earth leakage connection.
- 2=Neutral connection.
- A value greater than 2 indicates breaker current rating in Amps.
- A value above 60 Amp will signify a remote feed.
- The xPDUBranchBreakerRDPFeed OID will indicate which breakers are
- configured as a remote drop.
- Note: When setting branch circuit thresholds/ratings for an entry,
- all positions tied (see the xPDUBranchBreakerTieIndicator OID)
- to this entry will inherit the new threshold/rating."
- ::= { xPDUBranchBreakerEntry 2 }
- xPDUBranchBreakerRDPFeed OBJECT-TYPE
- SYNTAX INTEGER {
- remoteDistribution (1),
- noRemoteDistribution (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Indicates that a breaker position is feeding a remote
- distribution panel."
- ::= { xPDUBranchBreakerEntry 3 }
- xPDUBranchBreakerTieIndicator OBJECT-TYPE
- SYNTAX INTEGER {
- breakerUnTied (1),
- breakerTied (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Indicates whether or not the breaker in this position
- is logically associated with the breaker immediately below it.
- This setting is used grouping the breakers feeding
- a multi-pole branch circuit.
- Note: When setting an entry's branch breaker tie indicator to breakerTied,
- all the positions that are tied to this breaker will take on the rating
- and thresholds for this entry of the table."
- ::= { xPDUBranchBreakerEntry 4 }
- xPDUBranchBreakerCurrent OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Indicates the branch current in tenths of Amps or -1 when not available."
- ::= { xPDUBranchBreakerEntry 5 }
- xPDUBranchBreakerOverCurrentThreshold OBJECT-TYPE
- SYNTAX INTEGER (0..100)
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Threshold above which a branch circuit high current
- condition will be generated.
- Specified as a percent of the branch breaker rating.
- A value of zero indicates that the threshold is disabled.
- Note: When setting branch circuit thresholds/ratings for an entry,
- all positions tied (see the xPDUBranchBreakerTieIndicator OID)
- to this entry will inherit the new threshold/rating."
- ::= { xPDUBranchBreakerEntry 6 }
- xPDUBranchBreakerUnderCurrentThreshold OBJECT-TYPE
- SYNTAX INTEGER (0..100)
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Threshold below which a branch circuit low current
- condition will be generated.
- Specified as a percent of the branch breaker rating.
- A value of zero indicates that the threshold is disabled.
- Note: When setting branch circuit thresholds/ratings for an entry,
- all positions tied (see the xPDUBranchBreakerTieIndicator OID)
- to this entry will inherit the new threshold/rating."
- ::= { xPDUBranchBreakerEntry 7 }
- xPDUBranchBreakerMaxCurrentThreshold OBJECT-TYPE
- SYNTAX INTEGER (0..100)
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Threshold above which a branch circuit maximum current
- condition will be generated.
- Specified as a percent of the branch breaker rating.
- A value of zero indicates that the threshold is disabled.
- Note: When setting branch circuit thresholds/ratings for an entry,
- all positions tied (see the xPDUBranchBreakerTieIndicator OID)
- to this entry will inherit the new threshold/rating."
- ::= { xPDUBranchBreakerEntry 8 }
- xPDUBranchBreakerMinCurrentThreshold OBJECT-TYPE
- SYNTAX INTEGER (0..100)
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Threshold below which a branch circuit minimum current
- condition will be generated.
- Specified as a percent of the branch breaker rating.
- A value of zero indicates that the threshold is disabled.
- Note: When setting branch circuit thresholds/ratings for an entry,
- all positions tied (see the xPDUBranchBreakerTieIndicator OID)
- to this entry will inherit the new threshold/rating."
- ::= { xPDUBranchBreakerEntry 9 }
- xPDUBranchBreakerName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The description of the purpose/use of the breaker."
- ::= { xPDUBranchBreakerEntry 10 }
- xPDUBranchBreakerLocation OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The description of the location of the breaker."
- ::= { xPDUBranchBreakerEntry 11 }
- -- the xPDUInputContacts group
- xPDUInputContactNumContacts OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of contacts supported by the PDU."
- ::= { xPDUInputContacts 1 }
- xPDUInputContactTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of input contact entries."
- ::= { xPDUInputContacts 2 }
- xPDUInputContactTable OBJECT-TYPE
- SYNTAX SEQUENCE OF XPDUInputContactEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "A list of contacts supported by the PDU.
- The number of entries is contained in the
- xPDUInputContactTableSize OID."
- ::= { xPDUInputContacts 3 }
- xPDUInputContactEntry OBJECT-TYPE
- SYNTAX XPDUInputContactEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "A contact entry containing information for a given contact."
- INDEX { xPDUInputContactNumber }
- ::= { xPDUInputContactTable 1 }
- XPDUInputContactEntry ::=
- SEQUENCE {
- xPDUInputContactNumber INTEGER,
- xPDUInputContactName DisplayString,
- xPDUInputContactNormalState INTEGER,
- xPDUInputContactCurrentState INTEGER
- }
- xPDUInputContactNumber OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "An index identifying the contact on the PDU."
- ::= { xPDUInputContactEntry 1 }
- xPDUInputContactName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The description of the purpose/use of the contact."
- ::= { xPDUInputContactEntry 2 }
- xPDUInputContactNormalState OBJECT-TYPE
- SYNTAX INTEGER {
- open (1),
- closed (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The normal operating position of the contact."
- ::= { xPDUInputContactEntry 3 }
- xPDUInputContactCurrentState OBJECT-TYPE
- SYNTAX INTEGER {
- open (1),
- closed (2),
- unknown (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This value indicates the current state of the contact."
- ::= { xPDUInputContactEntry 4 }
- -- the xPDUOutputRelays group
- xPDUOutputRelaysNumRelays OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of output relays supported by the PDU."
- ::= { xPDUOutputRelays 1 }
- xPDUOutputRelaysTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of output relay entries."
- ::= { xPDUOutputRelays 2 }
- xPDUOutputRelayTable OBJECT-TYPE
- SYNTAX SEQUENCE OF XPDUOutputRelayEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "A list of output relays supported by the PDU.
- The number of entries is contained in the
- xPDUOutputRelayTableSize OID."
- ::= { xPDUOutputRelays 3 }
- xPDUOutputRelayEntry OBJECT-TYPE
- SYNTAX XPDUOutputRelayEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "A output relay entry containing information for a given contact."
- INDEX { xPDUOutputRelayNumber }
- ::= { xPDUOutputRelayTable 1 }
- XPDUOutputRelayEntry ::=
- SEQUENCE {
- xPDUOutputRelayNumber INTEGER,
- xPDUOutputRelayName DisplayString,
- xPDUOutputRelayNormalState INTEGER,
- xPDUOutputRelayCurrentState INTEGER
- }
- xPDUOutputRelayNumber OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "An index identifying the output relay on the PDU."
- ::= { xPDUOutputRelayEntry 1 }
- xPDUOutputRelayName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The description of the purpose/use of the output relay."
- ::= { xPDUOutputRelayEntry 2 }
- xPDUOutputRelayNormalState OBJECT-TYPE
- SYNTAX INTEGER {
- open (1),
- closed (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The normal operating position of the output relay."
- ::= { xPDUOutputRelayEntry 3 }
- xPDUOutputRelayCurrentState OBJECT-TYPE
- SYNTAX INTEGER {
- open (1),
- closed (2),
- unknown (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This value indicates the current state of the output relay."
- ::= { xPDUOutputRelayEntry 4 }
- -- the xPDUMiscGroup
- xPDUEPOMode OBJECT-TYPE
- SYNTAX INTEGER {
- armed (1),
- disarmed (2),
- unknown (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Indicates whether the EPO System is armed(1) or disarmed(2)."
- ::= { xPDUMiscGroup 1 }
- xPDUTransformTempStatus OBJECT-TYPE
- SYNTAX INTEGER {
- normal (1),
- overtemp (2),
- noTransformerPresent (3),
- unknown (4)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Indicates if the PDU's isolation transformer is over temperature."
- ::= { xPDUMiscGroup 2 }
- xPDUCoolingFanStatus OBJECT-TYPE
- SYNTAX INTEGER {
- normal (1),
- failed (2),
- noCoolingFansPresent (3),
- unknown (4)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Indicates if one or more of the PDU's cooling fans have failed."
- ::= { xPDUMiscGroup 3 }
- -- The xATSIdent group
- xATSIdentProductName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The name of the transfer switch unit."
- ::= { xATSIdent 1 }
- xATSIdentHardwareRev OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The hardware revision of the transfer switch.
- This value is set at the factory."
- ::= { xATSIdent 2 }
- xATSIdentFirmwareAppRev OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "An ID string identifying the application firmware revision of the transfer switch."
- ::= { xATSIdent 3 }
- xATSIdentFirmwareAppOSRev OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "An ID string identifying the application operating system firmware revision of the transfer switch."
- ::= { xATSIdent 4 }
- xATSIdentFirmwareControllerRev OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "An ID string identifying the transfer switch controller firmware revision."
- ::= { xATSIdent 5 }
- xATSIdentDateOfManufacture OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The date when the transfer switch was manufactured in mm/dd/yyyy format.
- This value is set at the factory."
- ::= { xATSIdent 6 }
-
- xATSIdentModelNumber OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the model number of the transfer switch.
- This value is set at the factory."
- ::= { xATSIdent 7 }
- xATSIdentSerialNumber OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the serial number of the transfer switch.
- This value is set at the factory."
- ::= { xATSIdent 8 }
- -- The xATSDevice group
- xATSDeviceServiceType OBJECT-TYPE
- SYNTAX INTEGER {
- threeWire (1),
- fourWire (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The type of utility input to the transfer switch.
- Either 3 wires (delta), or 4 wires (wye)."
- ::= { xATSDevice 1 }
- xATSDeviceNominalVoltage OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The nominal line-to-neutral system voltage.
- Measured in Volts, line-to-line for a 3-wire service or
- line-to-neutral for a 4-wire service. -1 if not available."
- ::= { xATSDevice 2 }
- xATSDeviceNominalFrequency OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The nominal system frequency. Measured in tenths of Hertz.
- -1 if not available."
- ::= { xATSDevice 3 }
- xATSDeviceTransferSwitchRating OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The rating of the transfer switch.
- Measured in Amps."
- ::= { xATSDevice 4 }
- xATSDeviceDCBackUpPresent OBJECT-TYPE
- SYNTAX INTEGER{
- yes (1),
- no (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Indicates if a DC backup is present or not."
- ::= { xATSDevice 5 }
- -- The xATS Switch Status group
- xATSSwitchStatusSelectedSource OBJECT-TYPE
- SYNTAX INTEGER{
- none (1),
- source1 (2),
- source2 (3),
- fault (4),
- unknown (5)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The source which is currently selected, i.e. supplying power to the load."
- ::= { xATSSwitchStatus 1 }
-
- xATSSwitchStatusOperationalMode OBJECT-TYPE
- SYNTAX INTEGER{
- automatic (1),
- notInAutoAbnormal (2),
- notInAuto (3),
- unknown (4)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The current operating mode of the transfer switch. When the ATS is in
- automatic mode, generator starting and ATS transferring is all done automatically
- as needed based on the state of source 1. Automatic operation is halted when the
- ATS is in either of the notInAuto modes.
- A mode of notInAuto indicates that the automatic operation switch is in the
- disabled position, as indicated by the xATSSwitchStatusAutomaticOperationSwitch OID.
- The notInAutoAbnormal condition indicates that an abnormal
- condition has caused the transfer switch to halt automatic operation.
- In this case, traps can indicate the exact problem. In the case of
- notInAutoAbnormal, refer to the operation manual for details
- on how debug the condition and restore automatic operation."
- ::= { xATSSwitchStatus 2 }
- xATSSwitchStatusAutomaticOperationSwitch OBJECT-TYPE
- SYNTAX INTEGER{
- disabled (1),
- enabled (2),
- unknown (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The position of the automatic operation switch on the front of the transfer switch."
- ::= { xATSSwitchStatus 3 }
- xATSSwitchStatusEngineStartSignal OBJECT-TYPE
- SYNTAX INTEGER{
- run (1),
- stop (2),
- unknown (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The position of the Start/Stop contact which signals the generator
- engine to start/run. When the ATS is in automatic mode,
- generator starting/stopping is under ATS control."
- ::= { xATSSwitchStatus 4 }
- -- The xATS Switch Setting group
- xATSSwitchSettingsLowVoltageTransferPoint OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The lowest acceptable voltage condition at source 1.
- When any phase of source 1 is lower than this voltage,
- source quality is considered bad and the generator run signal
- is asserted to begin generator operation.
- Specified in volts, line-to-line for a 3-wire service or
- line-to-neutral for a 4-wire service.
- -1 if not available."
- ::= { xATSSwitchSettings 1 }
- xATSSwitchSettingsHighVoltageTransferPoint OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The highest acceptable voltage condition at source 1.
- When any phase of source 1 is greater than this voltage,
- source quality is considered bad and the generator run signal
- is asserted to begin generator operation.
- Specified in volts, line-to-line for a 3-wire service or
- line-to-neutral for a 4-wire service.
- -1 if not available."
- ::= { xATSSwitchSettings 2 }
- xATSSwitchSettingsMaxFrequencyDeviation OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The maximum acceptable frequency deviation condition from nominal at source 1.
- When source 1 frequency is outside the specified range,
- source quality is considered bad and the generator run signal
- is asserted to begin generator operation.
- Specified in tenths of Hertz above or below nominal.
- A value of zero indicates that frequency is ignored when
- determining source quality.
- -1 if not available."
- ::= { xATSSwitchSettings 3 }
- xATSSwitchSettingsMinPhaseBalance OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The minimum required phase balance at source 1.
- When the percentage difference between the minimum and maximum
- phase voltage measurements at source 1 is greater than this value,
- source quality is considered bad and the generator run signal
- is asserted to begin generator operation.
- Specified as a percentage. A value of zero indicates that phase balance
- is ignored when determining source quality. -1 if not available."
- ::= { xATSSwitchSettings 4 }
- xATSSwitchSettingsNominalRotation OBJECT-TYPE
- SYNTAX INTEGER{
- abc (1),
- cba (2),
- any (3),
- unknown (4)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The nominal phase rotation (or phase sequence) required by the load.
- For certain types of equipment, such as rotating machinery, phase rotation
- is critical for proper operation as it determines the direction which motors
- will rotate (clockwise or counterclockwise).
- Source quality will be seen as bad if the rotation measured at that
- ATS input does not match this setting.
- If this setting is set to any, phase rotation is ignored."
- ::= { xATSSwitchSettings 5 }
- xATSSwitchSettingsAllowClosedTransfer OBJECT-TYPE
- SYNTAX INTEGER{
- yes (1),
- no (2),
- unknown (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "This setting enables seamless (closed) transfers between sources.
- When possible, both source 1 and source 2 are closed to the output
- for a brief time. If closed transfer is not possible within the amount
- of time specified by the xATSSwitchSettingsMaxSyncTime OID,
- an open transfer will be executed."
- ::= { xATSSwitchSettings 6 }
- xATSSwitchSettingsMaxSyncTime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "When attempting/seeking to perform a closed transfer, this setting defines
- the maximum time allowed before the transfer switch will give up and perform
- an open transfer. Specified in seconds.
- -1 if not available."
- ::= { xATSSwitchSettings 7 }
- xATSSwitchSettingsNeutralTransferTime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "This setting defines how long both source 1 and source 2 will be
- disconnected from the output, during an open transfer.
- Specified in seconds.
- -1 if not available."
- ::= { xATSSwitchSettings 8 }
- xATSSwitchSettingsClearLatchedAlarms OBJECT-TYPE
- SYNTAX INTEGER{
- yes (1),
- no (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Clears any latched alarm conditions."
- ::= { xATSSwitchSettings 9 }
-
- xATSSwitchSettingsSetToFactoryDefaults OBJECT-TYPE
- SYNTAX INTEGER{
- yes (1),
- no (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Sets all transfer switch settings to factory default values."
- ::= { xATSSwitchSettings 10 }
- -- The xATSSwitchTimers group
- xATSSwitchTimersTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of transfer switch timer entries."
- ::= { xATSSwitchTimers 1 }
- xATSSwitchTimersTable OBJECT-TYPE
- SYNTAX SEQUENCE OF XATSSwitchTimersEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "A list of timers supported by ATS.
- The number of entries is contained in the xATSSwitchTimersTableSize OID."
- ::= { xATSSwitchTimers 2 }
- xATSSwitchTimersEntry OBJECT-TYPE
- SYNTAX XATSSwitchTimersEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "An entry containing information about an individual ATS timer."
- INDEX { xATSSwitchTimersIndex }
- ::= { xATSSwitchTimersTable 1 }
- XATSSwitchTimersEntry ::=
- SEQUENCE {
- xATSSwitchTimersIndex INTEGER,
- xATSSwitchTimersName DisplayString,
- xATSSwitchTimersAbort INTEGER,
- xATSSwitchTimersStatus INTEGER,
- xATSSwitchTimersRemainingTime INTEGER,
- xATSSwitchTimersDelaySetting INTEGER
- }
- xATSSwitchTimersIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Index of timer entries in the table."
- ::= { xATSSwitchTimersEntry 1 }
- xATSSwitchTimersName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Name of the individual timer.Refer to ATS operation manual,
- or on-line help, for detailed descriptions of ATS timers."
- ::= { xATSSwitchTimersEntry 2 }
- xATSSwitchTimersAbort OBJECT-TYPE
- SYNTAX INTEGER{
- yes (1),
- no (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "This aborts the individual timer."
- ::= { xATSSwitchTimersEntry 3 }
- xATSSwitchTimersStatus OBJECT-TYPE
- SYNTAX INTEGER{
- inactive (1),
- active (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The status of the individual timer. Designates whether this timer
- entry is currently running or inactive."
- ::= { xATSSwitchTimersEntry 4 }
-
- xATSSwitchTimersRemainingTime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The time remaining for this timer entry.
- Specified in seconds."
- ::= { xATSSwitchTimersEntry 5 }
- xATSSwitchTimersDelaySetting OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The delay settings associated with this timer entry.
- When this timer entry is active, the timer value must exceed this setting
- before the ATS behavior associated with this timer is executed.
- Refer to ATS operation manual, or on-line help, for detailed
- descriptions of ATS timers."
- ::= { xATSSwitchTimersEntry 6 }
- -- The xATSSwitchBlockMap group
- xATSSwitchBlockMapTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of blocking map entries, or how many ATS actions can be blocked."
- ::= { xATSSwitchBlockMap 1 }
- xATSSwitchBlockMapTable OBJECT-TYPE
- SYNTAX SEQUENCE OF XATSSwitchBlockMapEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "A list of blocking maps supported by the ATS.
- The number of entries is contained in the xATSSwitchBlockMapTableSize OID."
- ::= { xATSSwitchBlockMap 2 }
- xATSSwitchBlockMapEntry OBJECT-TYPE
- SYNTAX XATSSwitchBlockMapEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "An entry containing information about a specific ATS blocking map."
- INDEX { xATSSwitchBlockMapIndex }
- ::= { xATSSwitchBlockMapTable 1 }
- XATSSwitchBlockMapEntry ::=
- SEQUENCE {
- xATSSwitchBlockMapIndex INTEGER,
- xATSSwitchBlockMapName DisplayString,
- xATSSwitchBlockMapStatus INTEGER,
- xATSSwitchBlockMapSetting INTEGER
- }
- xATSSwitchBlockMapIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Index of blocking map entries in the table."
- ::= { xATSSwitchBlockMapEntry 1 }
- xATSSwitchBlockMapName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A string describing the ATS action to be blocked."
- ::= { xATSSwitchBlockMapEntry 2 }
-
- xATSSwitchBlockMapStatus OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Represents the status of this blocking map entry, in bit-mapped format.
- A non-zero value indicates that this entry's ATS action is currently being blocked.
- The bit(s) set indicate which input(s) are causing the blocking (bit0, bit1, etc).
- bit 0 - Contact 1
- bit 1 - Contact 2
- bit 2 - Contact 3
- bit 3 - Contact 4."
- ::= { xATSSwitchBlockMapEntry 3 }
- xATSSwitchBlockMapSetting OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "This setting designates the inputs that block the ATS action
- The mapping is specified as a bit-field, where each bit set indicates
- the input that blocks the ATS action associated with the entry.
- bit 0 - Contact 1
- bit 1 - Contact 2
- bit 2 - Contact 3
- bit 3 - Contact 4."
- ::= { xATSSwitchBlockMapEntry 4 }
- -- The xATSSwitchStatistics group
- xATSSwitchStatisticsTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of transfer switch statistics entries."
- ::= { xATSSwitchStatistics 1 }
- xATSSwitchStatisticsTable OBJECT-TYPE
- SYNTAX SEQUENCE OF XATSSwitchStatisticsEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "A list of statistics supported by ATS.
- The number of entries is contained in the xATSSwitchStatisticsTableSize OID."
- ::= { xATSSwitchStatistics 2 }
- xATSSwitchStatisticsEntry OBJECT-TYPE
- SYNTAX XATSSwitchStatisticsEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "An entry containing information about an individual ATS statistic."
- INDEX { xATSSwitchStatisticsIndex }
- ::= { xATSSwitchStatisticsTable 1 }
- XATSSwitchStatisticsEntry ::=
- SEQUENCE {
- xATSSwitchStatisticsIndex INTEGER,
- xATSSwitchStatisticsName DisplayString,
- xATSSwitchStatisticsValue DisplayString,
- xATSSwitchStatisticsReset INTEGER
- }
- xATSSwitchStatisticsIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Index of ATS statistics entries in the table."
- ::= { xATSSwitchStatisticsEntry 1 }
- xATSSwitchStatisticsName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This is the name of the ATS statistic associated with this entry."
- ::= { xATSSwitchStatisticsEntry 2 }
- xATSSwitchStatisticsValue OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This is the value of the ATS statistic associated with this entry."
- ::= { xATSSwitchStatisticsEntry 3 }
- xATSSwitchStatisticsReset OBJECT-TYPE
- SYNTAX INTEGER{
- yes (1),
- no (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "This will reset the individual ATS statistic associated with this entry."
- ::= { xATSSwitchStatisticsEntry 4 }
- -- The xATS Source 1 group
- xATSSource1Name OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "String used to identify source 1."
- ::= { xATSSource1 1 }
- xATSSource1Position OBJECT-TYPE
- SYNTAX INTEGER{
- open (1),
- closed (2),
- tripped (3),
- unknown (4)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The current position of the switch at source 1."
- ::= { xATSSource1 2 }
- xATSSource1Frequency OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The frequency at source 1 in tenths of Hertz.
- -1 if unavailable."
- ::= { xATSSource1 3 }
- xATSSource1Quality OBJECT-TYPE
- SYNTAX INTEGER{
- sourceGood (1),
- lowVoltage (2),
- highVoltage (3),
- phaseImbalance (4),
- freqOutOfRange (5),
- badRotation (6),
- unknown (7)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The current line quality of source 1."
- ::= { xATSSource1 4 }
- xATSSource1Rotation OBJECT-TYPE
- SYNTAX INTEGER{
- abc (1),
- cba (2),
- unknown (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The phase rotation measured at the source 1 input of the ATS.
- The sequence is a reference to the order in which the three phases
- pass the zero-crossing boundary in time."
- ::= { xATSSource1 5 }
- xATSSource1TableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of input voltage entries at the source 1 input of the ATS."
- ::= { xATSSource1 6 }
- xATSSource1PhaseTable OBJECT-TYPE
- SYNTAX SEQUENCE OF XATSSource1PhaseEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "A list of voltage table entries for source 1. The number of
- entries are the phase entries. The number of entries is contained in the
- xATSSource1TableSize OID."
- ::= { xATSSource1 7 }
- xATSSource1PhaseEntry OBJECT-TYPE
- SYNTAX XATSSource1PhaseEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "An entry containing information applicable to a
- particular input voltage phase at the source 1 input of the ATS."
- INDEX { xATSSource1Index }
- ::= { xATSSource1PhaseTable 1 }
- XATSSource1PhaseEntry ::= SEQUENCE {
- xATSSource1Index INTEGER,
- xATSSource1VoltageLtoL INTEGER,
- xATSSource1VoltageLtoN INTEGER
- }
- xATSSource1Index OBJECT-TYPE
- SYNTAX INTEGER{
- phase1(1),
- phase2(2),
- phase3(3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Description of each phase utilized at source 1."
- ::= { xATSSource1PhaseEntry 1 }
- xATSSource1VoltageLtoL OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Source 1 line-to-line input voltage.
- Measured in tenths of Volts."
- ::= { xATSSource1PhaseEntry 2 }
- xATSSource1VoltageLtoN OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Source 1 line-to-neutral input voltage.
- Measured in tenths of Volts. -1 for a 3-wire service type."
- ::= { xATSSource1PhaseEntry 3 }
- -- The xATS Source 2 group
- xATSSource2Name OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "String used to identify source 2."
- ::= { xATSSource2 1 }
- xATSSource2Position OBJECT-TYPE
- SYNTAX INTEGER{
- open (1),
- closed (2),
- tripped (3),
- unknown (4)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The current position of the switch at source 2."
- ::= { xATSSource2 2 }
- xATSSource2Frequency OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The frequency at source 2 in tenths of Hertz.
- -1 if not available."
- ::= { xATSSource2 3 }
- xATSSource2Quality OBJECT-TYPE
- SYNTAX INTEGER{
- sourceGood (1),
- lowVoltage (2),
- highVoltage (3),
- phaseImbalance (4),
- freqOutOfRange (5),
- badRotation (6),
- unknown (7)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The current line quality of source 2."
- ::= { xATSSource2 4 }
- xATSSource2Rotation OBJECT-TYPE
- SYNTAX INTEGER{
- abc (1),
- cba (2),
- unknown (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The phase rotation measured at the source 2 input of the ATS.
- -1 if not available."
- ::= { xATSSource2 5 }
- xATSSource2TableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of input voltage entries at the source 2 input of the ATS."
- ::= { xATSSource2 6 }
- xATSSource2PhaseTable OBJECT-TYPE
- SYNTAX SEQUENCE OF XATSSource2PhaseEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "A list of voltage table entries for the source 2. The number of
- entries are the phase entries. The number of entries is contained in the
- xATSSource2TableSize OID."
- ::= { xATSSource2 7 }
- xATSSource2PhaseEntry OBJECT-TYPE
- SYNTAX XATSSource2PhaseEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "An entry containing information applicable to a
- particular input voltage phase at the source 2 input of the ATS."
- INDEX { xATSSource2Index }
- ::= { xATSSource2PhaseTable 1 }
- XATSSource2PhaseEntry ::= SEQUENCE {
- xATSSource2Index INTEGER,
- xATSSource2VoltageLtoL INTEGER,
- xATSSource2VoltageLtoN INTEGER
- }
- xATSSource2Index OBJECT-TYPE
- SYNTAX INTEGER{
- phase1(1),
- phase2(2),
- phase3(3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Description of each phase utilized at the source 2."
- ::= { xATSSource2PhaseEntry 1 }
- xATSSource2VoltageLtoL OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Source 2 line-to-line input voltage.
- Measured in tenths of Volts."
- ::= { xATSSource2PhaseEntry 2 }
- xATSSource2VoltageLtoN OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Source 2 line-to-neutral input voltage.
- Measured in tenths of Volts. -1 for a 3-wire service type."
- ::= { xATSSource2PhaseEntry 3 }
- -- The xATSSystemOutput
- xATSSystemOutputFrequency OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The system output frequency in tenths of Hertz."
- ::= { xATSSystemOutput 1 }
- xATSSystemOutputTotalPower OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Shows the total system output power in tenths of kW."
- ::= { xATSSystemOutput 2 }
- xATSSystemOutputTotalApparentPower OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Shows the total system output power in tenths of kVA."
- ::= { xATSSystemOutput 3 }
- xATSSystemOutputTotalPowerFactor OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Indicates the total power factor of the system output.
- A value of 100 representing a unity power factor (1.00)
- Specified in hundredths."
- ::= { xATSSystemOutput 4 }
- xATSSystemOutputFrequencyTolerance OBJECT-TYPE
- SYNTAX INTEGER{
- freqToleranceOff (1),
- freqTolerancePointTwo (2),
- freqTolerancePointFive (3),
- freqToleranceOne (4),
- freqToleranceOnePointFive (5),
- freqToleranceTwo (6),
- freqToleranceThree (7),
- freqToleranceFour (8),
- freqToleranceFive (9),
- freqToleranceNine (10)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Shows the panel output frequency tolerance in +/- Hertz."
- ::= { xATSSystemOutput 5 }
- xATSSystemOutputOverVoltThreshold OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Threshold above which an output over voltage condition will be generated.
- Specified as tenths of percent deviation from nominal.
- A value of zero indicates that the threshold is disabled."
- ::= { xATSSystemOutput 6 }
- xATSSystemOutputUnderVoltThreshold OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Threshold below which an output under voltage condition will be generated.
- Specified as tenths of percent deviation from nominal.
- A value of zero indicates that the threshold is disabled."
- ::= { xATSSystemOutput 7 }
- xATSSystemOutputOverCurrentThreshold OBJECT-TYPE
- SYNTAX INTEGER (0..100)
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Threshold above which an over current condition will be generated.
- Specified as a percent of the transfer switch rating (xATSDeviceTransferSwitchRating OID).
- A value of zero indicates that the threshold is disabled."
- ::= { xATSSystemOutput 8 }
- xATSSystemOutputUnderCurrentThreshold OBJECT-TYPE
- SYNTAX INTEGER (0..100)
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Threshold below which an under current condition will be generated.
- Specified as a percent of the transfer switch rating (xATSDeviceTransferSwitchRating OID).
- A value of zero indicates that the threshold is disabled."
- ::= { xATSSystemOutput 9 }
- xATSSystemOutputAlarmDelayThreshold OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Delay the generation of an output alarm.
- Specified in seconds."
- ::= { xATSSystemOutput 10 }
- xATSSystemOutputTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of system output phase entries."
- ::= { xATSSystemOutput 11 }
-
- xATSSystemOutputPhaseTable OBJECT-TYPE
- SYNTAX SEQUENCE OF XATSSystemOutputPhaseEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "A list of system output table entries.
- The number of entries is contained in the xATSSystemOutputTableSize OID."
- ::= { xATSSystemOutput 12 }
- xATSSystemOutputPhaseEntry OBJECT-TYPE
- SYNTAX XATSSystemOutputPhaseEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "An entry containing information applicable to a
- particular system output phase."
- INDEX { xATSSystemOutputPhaseIndex }
- ::= { xATSSystemOutputPhaseTable 1 }
- XATSSystemOutputPhaseEntry ::= SEQUENCE {
- xATSSystemOutputPhaseIndex INTEGER,
- xATSSystemOutputVoltageLtoL INTEGER,
- xATSSystemOutputVoltageLtoN INTEGER,
- xATSSystemOutputPhaseCurrent INTEGER,
- xATSSystemOutputPower INTEGER,
- xATSSystemOutputApparentPower INTEGER,
- xATSSystemOutputPowerFactor INTEGER
- }
- xATSSystemOutputPhaseIndex OBJECT-TYPE
- SYNTAX INTEGER{
- phase1(1),
- phase2(2),
- phase3(3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Description of each system output phase utilized in this device."
- ::= { xATSSystemOutputPhaseEntry 1 }
- xATSSystemOutputVoltageLtoL OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Line-to-line system output voltage available at the circuit panel.
- Measured in tenths of Volts. -1 if not available."
- ::= { xATSSystemOutputPhaseEntry 2 }
- xATSSystemOutputVoltageLtoN OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Line-to-neutral system output voltage available at the circuit panel.
- Measured in tenths of Volts. -1 for a 3-wire service type or if not available."
- ::= { xATSSystemOutputPhaseEntry 3 }
- xATSSystemOutputPhaseCurrent OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "System load current per phase. Measured in Amps.
- -1 if not available."
- ::= { xATSSystemOutputPhaseEntry 4 }
- xATSSystemOutputPower OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "System output power per phase. Measured in tenths of kW."
- ::= { xATSSystemOutputPhaseEntry 5 }
- xATSSystemOutputApparentPower OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "system output power per phase. Measured in tenths of kVA."
- ::= { xATSSystemOutputPhaseEntry 6 }
- xATSSystemOutputPowerFactor OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "indicates the power factor of the system output per phase.
- A value of 100 representing a unity power factor (1.00).
- Measured in hundredths."
- ::= { xATSSystemOutputPhaseEntry 7 }
- -- xATS TestingStatus group
- xATSTestingStatusSelectTestProcess OBJECT-TYPE
- SYNTAX INTEGER {
- engineStartTest (1),
- systemLoadTest (2),
- generatorHoldTest (3),
- cancelTest (4)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Type of tests that can be selected when no test has been scheduled.
- engineStartTest and systemLoadTest may be selected when no tests
- are running. Tests that are selected may be canceled manually."
- ::= { xATSTestingStatus 1 }
-
- xATSTestingStatusTestStatus OBJECT-TYPE
- SYNTAX INTEGER {
- noTestInProcess (1),
- testPending (2),
- startingEngine (3),
- engineWarmingUp (4),
- awaitingTransferToS2 (5),
- testingWithLoad (6),
- awaitingRetransferToS1 (7),
- testingWithoutLoad (8),
- stoppingEngine (9),
- holdingOnGenerator (10)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The present system test status/state."
- ::= { xATSTestingStatus 2 }
- xATSTestingStatusProfileWarmupTime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The amount of time that the generator will warm up during a test.
- This is portion of the test when the xATSTestingStatusTestStatus
- OID returns the value engineWarmingUp.
- Specified in seconds."
- ::= { xATSTestingStatus 3 }
- xATSTestingStatusProfileLoadedTime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The amount of time that ATS will apply the system load to the generator
- during a system load test.
- This is portion of the test when the xATSTestingStatusTestStatus
- OID returns the value testingWithLoad.
- Specified in minutes."
- ::= { xATSTestingStatus 4 }
- xATSTestingStatusProfileUnloadedTime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The amount of time that the generator will run following the warm up
- portion of a start test, or the loaded portion of a load test.
- This is portion of the test when the xATSTestingStatusTestStatus
- OID returns the value testingWithoutLoad.
- Specified in seconds."
- ::= { xATSTestingStatus 5 }
- -- xATS TestingResults group
- xATSTestingResultsLastDateOfTest OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Date of the last test that was performed, either scheduled or manual.
- Test results are available in the xATSTestingResultsLastResult OID.
- Specified in the dd/mm/yyyy format, or 'none' if not available."
- ::= { xATSTestingResults 1 }
- xATSTestingResultsLastResult OBJECT-TYPE
- SYNTAX INTEGER {
- noResultsAvailable (1),
- startTestPassed (2),
- loadTestPassed (3),
- startSignalFailure (4),
- failedGenNotInAuto (5),
- failedGenEmerStop (6),
- failedGenShutdown (7),
- failedGenDidNotStart (8),
- failedS2NeverGood (9),
- genFailedDuringWarmup (10),
- failureOnXferToS1 (11),
- genFailedLoaded (12),
- failureOnRexferToS2 (13),
- failedOnCooldown (14),
- genFailedToStop (15),
- failedAtsInternalFault (16),
- failedAtsNotInAuto (17),
- canceledManualTest (18),
- canceledScheduledTest (19)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The result of the last ATS/generator system test."
- ::= { xATSTestingResults 2 }
- xATSTestingResultsTestLastTestTime OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Time of day at which the last test was performed, either scheduled or manual.
- Test results are available in the xATSTestingResultsLastResult OID.
- Specified in the hh:mm:ss format, or 'none' if not available."
- ::= { xATSTestingResults 3 }
- xATSTestingResultsLastCrankDuration OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The time spent cranking the generator before it started during the last test.
- Specified in seconds, or -1 if not available."
- ::= { xATSTestingResults 4 }
-
- xATSTestingResultsLastWarmupDuration OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The time spent in the engineWarmingUp state during the last system test.
- Specified in seconds, or -1 if not available."
- ::= { xATSTestingResults 5 }
- xATSTestingResultsLastLoadedDuration OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The time spent in the testingWithLoad state during the last system test.
- Specified in seconds, or -1 if not available."
- ::= { xATSTestingResults 6 }
- xATSTestingResultsLastUnloadedDuration OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The time spent in the testingWithoutLoad state during the last system test.
- Specified in seconds, or -1 if not available."
- ::= { xATSTestingResults 7 }
- -- xATS TestingSchedule group
- xATSTestingScheduleFrequency OBJECT-TYPE
- SYNTAX INTEGER {
- never (1),
- daily (2),
- weekly (3),
- monthly (4)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The frequency of running scheduled tests."
- ::= { xATSTestingSchedule 1 }
- xATSTestingScheduleTestDay OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The desired day for the scheduled test. This object applies only
- when the xATSTestingScheduleFrequency OID is set to weekly or monthly.
- For weekly test frequency, the string is the day the test will be run.
- For monthly test frequency, the string indicates the day,
- and the instance within the month.
- For example, for monthly frequency: 2nd Sunday, 3rd Monday, 4th Tuesday,
- for weekly frequency: Sunday, Monday, Tuesday."
- ::= { xATSTestingSchedule 2 }
- xATSTestingScheduleTestTime OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The time of day that the scheduled test will occur.
- Specified in the format hh:mm."
- ::= { xATSTestingSchedule 3 }
- xATSTestingScheduleTestWithLoadInterval OBJECT-TYPE
- SYNTAX INTEGER {
- applyLoadEveryTest (1),
- neverApplyLoad (2),
- applyLoadMonthly (3),
- applyLoadMonthlyDetailed (4)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "This setting specifies which system tests should include applying the
- load to the generator. The applyLoadMonthlyDetailed entry
- in the list will apply load once, for each month represented in the
- xATSTestingScheduleTestWithLoadSelectMonth OID."
- ::= { xATSTestingSchedule 4 }
- xATSTestingScheduleTestWithLoadSelectMonth OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The detailed selection for testing with load on a month-by-month basis.
- This object is applicable when the xATSTestingScheduleTestWithLoadInterval
- is set to applyLoadMonthlyDetailed. Otherwise this selection will be ignored.
- Format for this string is a comma-separated entry of months.
- For example: Jan,Mar,Dec.
- The string will return 'No Months Scheduled' if no months have been selected."
- ::= { xATSTestingSchedule 5 }
- xATSTestingScheduleNextTestDate OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The date of the next scheduled test, in the format dd-mmm-yyyy."
- ::= { xATSTestingSchedule 6 }
- -- xATSTestingSimulatePowerFail group
- xATSTestingSimulatePowerFailTest OBJECT-TYPE
- SYNTAX INTEGER{
- cancelSimulation (1),
- fiveSecondsSimulation (2),
- tenSecondsSimulation (3),
- thirtySecondsSimulation (4),
- oneMinuteSimulation (5),
- threeMinutesSimulation (6),
- fiveMinutesSimulation (7),
- tenMinutesSimulation (8)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "This object executes a simulated power failure for the duration indicated.
- Simulation can be aborted by selecting cancelSimulation."
- ::= { xATSTestingSimulatePowerFail 1 }
- xATSTestingSimulatePowerFailTimeRemaining OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Indicates the time remaining in seconds, for a simulated power failure.
- a value of zero indicates that simulated power failure is not active."
- ::= { xATSTestingSimulatePowerFail 2 }
- -- The xATS Input Contact group
- xATSInputContactNumContacts OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of contacts supported by the ATS."
- ::= { xATSInputContacts 1 }
- xATSInputContactTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of input contact entries."
- ::= { xATSInputContacts 2 }
- xATSInputContactTable OBJECT-TYPE
- SYNTAX SEQUENCE OF XATSInputContactEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "A list of contacts supported by the ATS.
- The number of entries is contained in the
- xATSInputContactTableSize OID."
- ::= { xATSInputContacts 3 }
- xATSInputContactEntry OBJECT-TYPE
- SYNTAX XATSInputContactEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "A contact entry containing information for a given contact."
- INDEX { xATSInputContactNumber }
- ::= { xATSInputContactTable 1 }
- XATSInputContactEntry ::=
- SEQUENCE {
- xATSInputContactNumber INTEGER,
- xATSInputContactName DisplayString,
- xATSInputContactNormalState INTEGER,
- xATSInputContactCurrentState INTEGER
- }
- xATSInputContactNumber OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "An index identifying the contact on the ATS."
- ::= { xATSInputContactEntry 1 }
- xATSInputContactName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The description of the purpose/use of the contact."
- ::= { xATSInputContactEntry 2 }
- xATSInputContactNormalState OBJECT-TYPE
- SYNTAX INTEGER {
- open (1),
- closed (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The normal operating position of the contact."
- ::= { xATSInputContactEntry 3 }
- xATSInputContactCurrentState OBJECT-TYPE
- SYNTAX INTEGER {
- open (1),
- closed (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This value indicates the current state of the contact."
- ::= { xATSInputContactEntry 4 }
- -- the xATS OutputRelays group
- xATSOutputRelayNumRelays OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of output relays supported by the ATS."
- ::= { xATSOutputRelays 1 }
- xATSOutputRelayTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of output relay entries."
- ::= { xATSOutputRelays 2 }
- xATSOutputRelayTable OBJECT-TYPE
- SYNTAX SEQUENCE OF XATSOutputRelayEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "A list of output relays supported by the ATS.
- The number of entries is contained in the
- xATSOutputRelayTableSize OID."
- ::= { xATSOutputRelays 3 }
- xATSOutputRelayEntry OBJECT-TYPE
- SYNTAX XATSOutputRelayEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "A output relay entry containing information for a given contact."
- INDEX { xATSOutputRelayNumber }
- ::= { xATSOutputRelayTable 1 }
- XATSOutputRelayEntry ::=
- SEQUENCE {
- xATSOutputRelayNumber INTEGER,
- xATSOutputRelayName DisplayString,
- xATSOutputRelayNormalState INTEGER,
- xATSOutputRelayCurrentState INTEGER
- }
- xATSOutputRelayNumber OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "An index identifying the output relay on the ATS."
- ::= { xATSOutputRelayEntry 1 }
- xATSOutputRelayName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The description of the purpose/use of the output relay."
- ::= { xATSOutputRelayEntry 2 }
- xATSOutputRelayNormalState OBJECT-TYPE
- SYNTAX INTEGER {
- open (1),
- closed (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The normal operating position of the output relay."
- ::= { xATSOutputRelayEntry 3 }
- xATSOutputRelayCurrentState OBJECT-TYPE
- SYNTAX INTEGER {
- open (1),
- closed (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This value indicates the current state of the output relay."
- ::= { xATSOutputRelayEntry 4 }
- -- The xATS Generator Ident group
- xATSGeneratorIdentModelNumber OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the model number of the generator.
- This value is set at the factory."
- ::= { xATSGeneratorIdent 1 }
- xATSGeneratorIdentSerialNumber OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the serial number of the generator.
- This value is set at the factory."
- ::= { xATSGeneratorIdent 2 }
- xATSGeneratorIdentDateofManufacture OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying when the generator was manufactured in mm/dd/yyyy format.
- This value is set at the factory."
- ::= { xATSGeneratorIdent 3 }
- xATSGeneratorIdentVoltageConfiguration OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The voltage for which the generator's alternator is designed.
- Specified in Volts line-to-line."
- ::= { xATSGeneratorIdent 4 }
- xATSGeneratorIdentMaxPowerRating OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The max power rating of the generator. Specified in kW."
- ::= { xATSGeneratorIdent 5 }
- xATSGeneratorIdentAlternatorFrequency OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The frequency for which the generator's alternator is designed.
- Specified in Hertz."
- ::= { xATSGeneratorIdent 6 }
- -- The xATS Generator Status group
- xATSGeneratorStatusGeneratorName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The name or label for the generator connected to the source 2 of the ATS."
- ::= { xATSGeneratorStatus 1 }
-
- xATSGeneratorStatusOperational OBJECT-TYPE
- SYNTAX INTEGER{
- nocomm (1),
- off (2),
- ready (3),
- starting (4),
- idle (5),
- running (6),
- normalStop (7),
- emergencyStop (8),
- notInAuto (9),
- shutdown (10),
- unknown (11)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The operational status of the generator. unavailable when unrecognized status is received."
- ::= { xATSGeneratorStatus 2 }
- xATSGeneratorStatusModeSwitchPosition OBJECT-TYPE
- SYNTAX INTEGER{
- off (1),
- manual (2),
- automatic (3),
- unknown (4)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The position of the generator's auto-mode switch.
- In automatic mode, the generator is started and stopped via the
- remote start contact, which has state indicated in the
- xATSGeneratorStatusRemoteStart OID.
- In manual mode generator start/stop control is via local command only.
- Off prevents the generator from running."
- ::= { xATSGeneratorStatus 3 }
- xATSGeneratorStatusRemoteStart OBJECT-TYPE
- SYNTAX INTEGER{
- stop (1),
- run (2),
- unknown (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The status of the generator's remote start contact, which is
- provided as an output from the transfer switch to start/stop the
- generator when in automatic mode."
- ::= { xATSGeneratorStatus 4 }
- -- The xATS Generator Advanced Status group
- xATSGeneratorAdvStatusBatteryVoltage OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The voltage of the generator's starting battery.
- Measured in tenths of VDC, or -1 if not available."
- ::= { xATSGeneratorAdvStatus 1 }
- xATSGeneratorAdvStatusOilPressure OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The generator's engine oil pressure.
- Measured in tenths of Psi or kPa, based on the
- value of the xATSGeneratorSettingsMetricUnit OID,
- or -1 if not available."
- ::= { xATSGeneratorAdvStatus 2 }
- xATSGeneratorAdvStatusCoolantTemperature OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Current coolant temperature in the generator.
- Measured in degrees Celsius or Fahrenheit, based on the
- value of the xATSGeneratorSettingsMetricUnit OID,
- or -1 if not available."
- ::= { xATSGeneratorAdvStatus 3 }
- xATSGeneratorAdvStatusEngineRPM OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Current engine speed of the generator.
- Measured in RPM, or -1 if not available."
- ::= { xATSGeneratorAdvStatus 4 }
- xATSGeneratorAdvStatusOilLevel OBJECT-TYPE
- SYNTAX INTEGER{
- ok (1),
- low (2),
- unknown (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Indicates adequate oil level in the generator."
- ::= { xATSGeneratorAdvStatus 5 }
- xATSGeneratorAdvStatusCoolantLevel OBJECT-TYPE
- SYNTAX INTEGER{
- ok (1),
- low (2),
- unknown (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Indicates adequate coolant level in the generator."
- ::= { xATSGeneratorAdvStatus 6 }
- -- The xATS Generator Output group
- xATSGeneratorOutputFrequency OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The output frequency of the generator.
- Measured in tenths of Hertz, or -1 if not available."
- ::= { xATSGeneratorOutput 1 }
- xATSGeneratorOutputTotalPower OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The total output power of the generator.
- Measured in tenths of tenths of kW, or -1 if not available."
- ::= { xATSGeneratorOutput 2 }
- xATSGeneratorOutputTotalApparentPower OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The total output power of the generator.
- Measured in tenths of kVA, or -1 if not available."
- ::= { xATSGeneratorOutput 3 }
-
- xATSGeneratorOutputTotalPowerFactor OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Indicates the total load power factor of the generator.
- A value of 100 representing a unity power factor (1.00),
- or -1 when if not available."
- ::= { xATSGeneratorOutput 4 }
-
- xATSGeneratorOutputTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of generator output phase entries."
- ::= { xATSGeneratorOutput 5 }
- xATSGeneratorOutputPhaseTable OBJECT-TYPE
- SYNTAX SEQUENCE OF XATSGeneratorOutputPhaseEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "A list of generator output table entries.
- The number of entries is contained in the xATSGeneratorOutputTableSize OID."
- ::= { xATSGeneratorOutput 6 }
- xATSGeneratorOutputPhaseEntry OBJECT-TYPE
- SYNTAX XATSGeneratorOutputPhaseEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "An entry containing information applicable to a
- particular generator output phase."
- INDEX { xATSGeneratorOutputPhaseIndex }
- ::= { xATSGeneratorOutputPhaseTable 1 }
- XATSGeneratorOutputPhaseEntry ::= SEQUENCE {
- xATSGeneratorOutputPhaseIndex INTEGER,
- xATSGeneratorOutputVoltageLtoL INTEGER,
- xATSGeneratorOutputVoltageLtoN INTEGER,
- xATSGeneratorOutputPhaseCurrent INTEGER,
- xATSGeneratorOutputPower INTEGER,
- xATSGeneratorOutputApparentPower INTEGER,
- xATSGeneratorOutputPowerFactor INTEGER
- }
- xATSGeneratorOutputPhaseIndex OBJECT-TYPE
- SYNTAX INTEGER{
- phase1(1),
- phase2(2),
- phase3(3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Description of each generator output phase utilized in this device."
- ::= { xATSGeneratorOutputPhaseEntry 1 }
- xATSGeneratorOutputVoltageLtoL OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Line-to-line generator output voltage.
- Measured in Volts, or -1 if not available."
- ::= { xATSGeneratorOutputPhaseEntry 2 }
- xATSGeneratorOutputVoltageLtoN OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Line-to-neutral generator output voltage.
- Measured in volts, or -1 if not available."
- ::= { xATSGeneratorOutputPhaseEntry 3 }
- xATSGeneratorOutputPhaseCurrent OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Generator load current per phase.
- Measured in Amps, or -1 if not available."
- ::= { xATSGeneratorOutputPhaseEntry 4 }
- xATSGeneratorOutputPower OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Generator output power per phase.
- Measured in tenths of kW, or -1 if not available."
- ::= { xATSGeneratorOutputPhaseEntry 5 }
- xATSGeneratorOutputApparentPower OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Generator output power per phase.
- Measured in tenths of kVA, or -1 if not available."
- ::= { xATSGeneratorOutputPhaseEntry 6 }
- xATSGeneratorOutputPowerFactor OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Indicates the load power factor of the generator output per phase.
- A value of 100 representing a unity power factor (1.00),
- or -1 if not available."
- ::= { xATSGeneratorOutputPhaseEntry 7 }
- -- xATS Generator Settings group
- xATSGeneratorSettingsVoltageAdjust OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The voltage adjust of the generator.
- Specified in volts line-to-line,
- or -1 if not available."
- ::= { xATSGeneratorSettings 1 }
- xATSGeneratorSettingsFrequencyAdjust OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The frequency adjust of the generator.
- Specified in tenths of Hertz."
- ::= { xATSGeneratorSettings 2 }
- xATSGeneratorSettingsStartDelay OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The delay, in seconds, after the remote run signal is activated
- before the generator's engine will be cranked to start,
- or -1 if not available."
- ::= { xATSGeneratorSettings 3 }
- xATSGeneratorSettingsStopDelay OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The delay, in seconds, before the generator will stop
- after the remote run signal is deactivated,
- or -1 if not available."
- ::= { xATSGeneratorSettings 4 }
- xATSGeneratorSettingsCrankCycleEnable OBJECT-TYPE
- SYNTAX INTEGER{
- disabled (1),
- enabled (2),
- unknown (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "When Crank Cycle is enabled, the engine will be cranked up to the time
- specified by the xATSGeneratorSettingsCrankTime OID.
- If the generator's engine does not start, there will be a pause as
- specified by the xATSGeneratorSettingsCrankRestTime OID before the
- engine will be cranked again. This cycle is repeated as specified by
- the xATSGeneratorSettingsNumberCrank OID.
- When crank cycle is disabled, the generator's engine will be
- cranked continuously until it starts."
- ::= { xATSGeneratorSettings 5 }
- xATSGeneratorSettingsCrankTime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The duration of engine cranking, in seconds, when starting the generator.
- Applicable when the xATSGeneratorSettingsCrankCycleEnable OID is enabled.
- -1 if not available."
- ::= { xATSGeneratorSettings 6 }
- xATSGeneratorSettingsCrankRestTime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The pause duration, in seconds, following an unsuccessful attempt to start the generator.
- Applicable when the xATSGeneratorSettingsCrankCycleEnable OID is enabled.
- -1 if not available."
- ::= { xATSGeneratorSettings 7 }
- xATSGeneratorSettingsNumberCrank OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of failed crank attempts before giving up on starting the generator.
- Applicable when the xATSGeneratorSettingsCrankCycleEnable OID is enabled.
- -1 if not available."
- ::= { xATSGeneratorSettings 8 }
- xATSGeneratorSettingsMetricUnit OBJECT-TYPE
- SYNTAX INTEGER{
- disabled (1),
- enabled (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Specifies the use of metric units in generator related OIDs, as well
- as on all other interfaces including the generator's local interface."
- ::= { xATSGeneratorSettings 9 }
- -- xATS generator service group
- xATSGeneratorServiceTotalRunHoursLifetime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Total time that the generator engine has been run,
- over the life of the generator. Measured in hours.
- -1 if not available."
- ::= { xATSGeneratorService 1 }
- xATSGeneratorServiceEngineStartsLifetime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Number of engine starts over the life of the generator.
- -1 if not available."
- ::= { xATSGeneratorService 2 }
- xATSGeneratorServiceTotalkWhLifetime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Total kWh of operation over the life of the generator.
- -1 if not available."
- ::= { xATSGeneratorService 3 }
- xATSGeneratorServiceTotalRunHoursSinceMaintenance OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Total time that the generator engine has been run,
- since last service maintenance. Measured in tenths of hours.
- -1 if not available."
- ::= { xATSGeneratorService 4 }
- xATSGeneratorServiceEngineStartsSinceMaintenance OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Number of engine starts since last service maintenance.
- -1 if not available."
- ::= { xATSGeneratorService 5 }
- xATSGeneratorServiceTotalkWhMaintenance OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Total kWh of operation since last service maintenance.
- -1 if not available."
- ::= { xATSGeneratorService 6 }
- xATSGeneratorServiceResetRecord OBJECT-TYPE
- SYNTAX INTEGER{
- yes (1),
- no (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Resets the engine start counter, engine run-hours, and kWh values that have
- accumulated in the generator since last maintenance.
- Also, the last service date will be reset to the current system date, and
- any service alarms will be cleared."
- ::= { xATSGeneratorService 7 }
- xATSGeneratorServiceRecordResetDate OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Date at which the generator's service record was reset, in dd-mmm-yyyy format."
- ::= { xATSGeneratorService 8 }
- xATSGeneratorServiceNextServiceDate OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Date at which the next generator service is due in dd-mmm-yyyy format.
- Based on the xATSGeneratorServiceCalendarIntervalThreshold OID
- or '' if the calendar-based threshold is set to off."
- ::= { xATSGeneratorService 9 }
-
- xATSGeneratorServiceRunHoursUntilServiceDate OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Run hours until the next generator service is due, in hours.
- Based on the xATSGeneratorServiceRunHoursThreshold OID
- or -1 if the run hour-based threshold is set to off."
- ::= { xATSGeneratorService 10 }
-
- xATSGeneratorServiceRunHoursThreshold OBJECT-TYPE
- SYNTAX INTEGER{
- disabled (1),
- runThreshold100Hours (2),
- runThreshold150Hours (3),
- runThreshold200Hours (4),
- runThreshold250Hours (5),
- runThreshold300Hours (6),
- runThreshold400Hours (7),
- runThreshold500Hours (8)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Run hour-based service interval. When the run-hours since
- service surpasses this threshold, generator service is due."
- ::= { xATSGeneratorService 11 }
- xATSGeneratorServiceCalendarIntervalThreshold OBJECT-TYPE
- SYNTAX INTEGER{
- disabled (1),
- interval1month (2),
- interval2month (3),
- interval3month (4),
- interval6month (5),
- intervalyearly (6)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Calendar-based service interval. When the next service date,
- as indicated by the xATSGeneratorServiceNextServiceDate OID
- is in the past, generator is due for service."
- ::= { xATSGeneratorService 12 }
- -- The xATS Generator Fuel system group
- xATSGeneratorFuelSystemType OBJECT-TYPE
- SYNTAX INTEGER{
- diesel (1),
- propane (2),
- naturalGas (3),
- unknown (4)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The type of fuel used by the generator."
- ::= { xATSGeneratorFuelSystem 1 }
- xATSGeneratorFuelSystemTankSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Size of the generator's fuel tank.
- Specified in gallons or liters, based on the value of the
- xATSGeneratorSettingsMetricUnit OID, or -1 if not available."
- ::= { xATSGeneratorFuelSystem 2 }
- xATSGeneratorFuelSystemFuelLevel OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Fuel remaining in the generator tank.
- Measured in percent of tank fill, or -1 if not available."
- ::= { xATSGeneratorFuelSystem 3 }
- xATSGeneratorFuelSystemRuntimePower OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The power value used in the runtime remaining calculation.
- Measured in tenths of kW, or -1 if not available."
- ::= { xATSGeneratorFuelSystem 4 }
- xATSGeneratorFuelSystemEstimatedRunTime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "An estimate of available runtime for the generator, based on
- available fuel as specified in the xATSGeneratorFuelSystemFuelLevel OID
- and kW load as specified in the xATSGeneratorFuelSystemRuntimePower OID.
- Measured in tenths of hours, or -1 if not available."
- ::= { xATSGeneratorFuelSystem 5 }
-
- xATSGeneratorFuelSystemLowRunTimeThreshold OBJECT-TYPE
- SYNTAX INTEGER{
- disabled (1),
- oneHour (2),
- twoHours (3),
- threeHours (4),
- fourHours (5),
- fiveHours (6),
- sixHours (7),
- twelveHours (8),
- oneDay (9),
- twoDays (10),
- threeDays (11),
- fourDays (12),
- fiveDays (13),
- sixDays (14),
- sevenDays (15)
-
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Threshold below which a low runtime alarm will exist."
- ::= { xATSGeneratorFuelSystem 6 }
- xATSGeneratorFuelSystemVeryLowRunTimeThreshold OBJECT-TYPE
- SYNTAX INTEGER{
- disabled (1),
- oneHour (2),
- twoHours (3),
- threeHours (4),
- fourHours (5),
- fiveHours (6),
- sixHours (7),
- twelveHours (8),
- oneDay (9),
- twoDays (10),
- threeDays (11),
- fourDays (12),
- fiveDays (13),
- sixDays (14),
- sevenDays (15)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Threshold below which a very low runtime alarm will exist."
- ::= { xATSGeneratorFuelSystem 7 }
- xATSGeneratorFuelSystemLowFuelLevelThreshold OBJECT-TYPE
- SYNTAX INTEGER (0..100)
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Threshold below which a low fuel alarm will exist, with a value of 0 indicating disabled.
- Specified as percent of tank fill."
- ::= { xATSGeneratorFuelSystem 8 }
- xATSGeneratorFuelSystemVeryLowFuelLevelThreshold OBJECT-TYPE
- SYNTAX INTEGER (0..100)
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Threshold below which a very low fuel alarm will exist, with a value of 0 indicating disabled.
- Specified as percent of tank fill."
- ::= { xATSGeneratorFuelSystem 9 }
- -- The console Port Server AP930x system group
- apCPSpname OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION "The product's name."
- ::= { cpsAP930xSys 1 }
- apCPSversion OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION "The firmware's version."
- ::= {cpsAP930xSys 2}
- apCPSPower OBJECT IDENTIFIER ::= { cpsAP930xSys 3 }
- apCPSPwNum OBJECT-TYPE
- SYNTAX Integer32
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION "The number of the power supplies."
- ::= { apCPSPower 1 }
- apCPSPw1 OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION "State of the first power supply.
- 0 will indicate not installed,
- 1 will indicate power ON,
- 2 will indicate power OFF."
- ::= { apCPSPower 2 }
- apCPSPw2 OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION "State of the second power supply.
- 0 will indicate not installed,
- 1 will indicate power ON,
- 2 will indicate power OFF."
- ::= { apCPSPower 3 }
- apCPSPcmcia OBJECT IDENTIFIER ::= {cpsAP930xSys 4}
- apCPSNPcmcia OBJECT-TYPE
- SYNTAX Integer32
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION "Number of PCMCIA cards available."
- ::= { apCPSPcmcia 1 }
- cpsCardIdentTable OBJECT-TYPE
- SYNTAX SEQUENCE OF CpsCardIdentEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION "A table of PCMCIA card identifications."
- ::= { apCPSPcmcia 2 }
- cpsCardIdentEntry OBJECT-TYPE
- SYNTAX CpsCardIdentEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION "Identification information for a PCMCIA card."
- INDEX { cpsCardIdentIndex }
- ::= { cpsCardIdentTable 1 }
- CpsCardIdentEntry ::= SEQUENCE {
- cpsCardIdentIndex Integer32,
- cpsCardIdentProd DisplayString,
- cpsCardIdentMan DisplayString ,
- cpsCardIdentFunc DisplayString,
- cpsCardIdentPCI DisplayString
- }
- cpsCardIdentIndex OBJECT-TYPE
- SYNTAX Integer32
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION "Number to identify the socket Card."
- ::= { cpsCardIdentEntry 1 }
- cpsCardIdentProd OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION "Product identification string."
- ::= { cpsCardIdentEntry 2 }
- cpsCardIdentMan OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION "Manufacturer ID code."
- ::= { cpsCardIdentEntry 3 }
- cpsCardIdentFunc OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION "Function ID code."
- ::= { cpsCardIdentEntry 4 }
- cpsCardIdentPCI OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION "PCI ID"
- ::= { cpsCardIdentEntry 5 }
- cpsCardConfTable OBJECT-TYPE
- SYNTAX SEQUENCE OF CpsCardConfEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION "A table of socket configuration information."
- ::= { apCPSPcmcia 3 }
- cpsCardConfEntry OBJECT-TYPE
- SYNTAX CpsCardConfEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION "Configuration information for a socket."
- INDEX { cpsCardConfIndex }
- ::= { cpsCardConfTable 1 }
- CpsCardConfEntry ::= SEQUENCE {
- cpsCardConfIndex Integer32,
- cpsCardConfPower DisplayString,
- cpsCardConfType DisplayString,
- cpsCardConfInter DisplayString,
- cpsCardConfFunc DisplayString,
- cpsCardConfCardv DisplayString,
- cpsCardConfPort1 DisplayString,
- cpsCardConfPort2 DisplayString
- }
- cpsCardConfIndex OBJECT-TYPE
- SYNTAX Integer32
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION "Number to identify the socket PCMCIA."
- ::= { cpsCardConfEntry 1 }
- cpsCardConfPower OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION "Power Settings."
- ::= { cpsCardConfEntry 2 }
- cpsCardConfType OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION "Interface Type."
- ::= { cpsCardConfEntry 3 }
- cpsCardConfInter OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION "Interrupt number."
- ::= { cpsCardConfEntry 4 }
- cpsCardConfFunc OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION "Function."
- ::= { cpsCardConfEntry 5 }
- cpsCardConfCardv OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION "Card values."
- ::= { cpsCardConfEntry 6 }
- cpsCardConfPort1 OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION "I/O Port 1."
- ::= { cpsCardConfEntry 7 }
- cpsCardConfPort2 OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION "I/O Port 2."
- ::= { cpsCardConfEntry 8 }
- cpsCardStatusTable OBJECT-TYPE
- SYNTAX SEQUENCE OF CpsCardStatusEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION "A table of current socket status information."
- ::= { apCPSPcmcia 4 }
- cpsCardStatusEntry OBJECT-TYPE
- SYNTAX CpsCardStatusEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION "Current status information for a socket."
- INDEX { cpsCardStatusIndex }
- ::= { cpsCardStatusTable 1 }
- CpsCardStatusEntry ::= SEQUENCE {
- cpsCardStatusIndex Integer32,
- cpsCardStatusCard DisplayString,
- cpsCardStatusFunc DisplayString
- }
- cpsCardStatusIndex OBJECT-TYPE
- SYNTAX Integer32(0..2)
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION "Number to identify the socket PCMCIA."
- ::= { cpsCardStatusEntry 1 }
- cpsCardStatusCard OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION "Current Card State."
- ::= { cpsCardStatusEntry 2 }
- cpsCardStatusFunc OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION "Current Function."
- ::= { cpsCardStatusEntry 3 }
- apCPSFlashSize OBJECT-TYPE
- SYNTAX Integer32
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION "Total amount of flash memory in Mbytes."
- ::= {cpsAP930xSys 5}
- apCPSRAMSize OBJECT-TYPE
- SYNTAX Integer32
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION "Total amount of RAM in Mbytes."
- ::= {cpsAP930xSys 6}
- apCPSCPUfreq OBJECT-TYPE
- SYNTAX Integer32
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION "CPU clock in MHz."
- ::= {cpsAP930xSys 7}
- apCPSDevId OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION "The product's identifier."
- ::= { cpsAP930xSys 8 }
- -- The console Port Server AP930x configuration group
- cpsHostName OBJECT-TYPE
- SYNTAX DisplayString (SIZE (0..40))
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "The Host Name."
- ::= { cpsAP930xConf 1 }
- cpsConsoleBanner OBJECT-TYPE
- SYNTAX DisplayString (SIZE (0..255))
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "The console banner."
- ::= { cpsAP930xConf 2 }
- cpsMotd OBJECT-TYPE
- SYNTAX DisplayString (SIZE (0..255))
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "The motd message."
- ::= { cpsAP930xConf 3 }
- cpsEthItf OBJECT IDENTIFIER ::= { cpsAP930xConf 4 }
- cpsEthDhcpc OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "0 will indicate DHCP inactive,
- 1 will indicate DHCP active,
- 2 will indicate DHCP active and the last parameter is saved."
- ::= { cpsEthItf 1 }
- cpsEthIPaddr OBJECT-TYPE
- SYNTAX IpAddress
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "This is the IP address of the Ethernet Interface."
- ::= { cpsEthItf 2 }
- cpsEthIPmask OBJECT-TYPE
- SYNTAX IpAddress
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "The mask for the Ethernet network."
- ::= { cpsEthItf 3 }
- cpsEthMTU OBJECT-TYPE
- SYNTAX Integer32
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "The Maximum Transmission Unit size, which determines
- whether packets should be broken up."
- ::= { cpsEthItf 4 }
- cpsEthIPaddr2 OBJECT-TYPE
- SYNTAX IpAddress
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "The Ethernet secondary IP address."
- ::= { cpsEthItf 5 }
- cpsEthIPmask2 OBJECT-TYPE
- SYNTAX IpAddress
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "The Ethernet secondary IP mask."
- ::= { cpsEthItf 6 }
- cpsNameService OBJECT IDENTIFIER ::= { cpsAP930xConf 5 }
- cpsResolverOrder OBJECT-TYPE
- SYNTAX DisplayString (SIZE (0..15))
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "Specifies how host lookups are to be performed.
- Valid values : empty, 'hosts', 'bind', 'hosts, bind',
- 'bind, hosts' "
- ::= { cpsNameService 1 }
-
- cpsMultipleIP OBJECT-TYPE
- SYNTAX DisplayString (SIZE (0..3))
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "Valid values are ON or OFF. If set to ON, the resolve
- library will return all valid addresses for a host
- that appears in the /etc/hosts file, instead of only
- the first. "
- ::= { cpsNameService 2 }
- cpsDNSserv OBJECT IDENTIFIER ::= { cpsNameService 3 }
- cpsDNSpriserv OBJECT-TYPE
- SYNTAX IpAddress
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "Internet Address (in dot notation) of primary name
- server that the resolver should query."
- ::= { cpsDNSserv 1 }
-
- cpsDNSsecserv OBJECT-TYPE
- SYNTAX IpAddress
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "Internet Address (in dot notation) of secondary name
- server that the resolver should query."
- ::= { cpsDNSserv 2 }
- cpsDNSdomain OBJECT-TYPE
- SYNTAX DisplayString (SIZE (0..40))
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "Local domain name."
- ::= { cpsDNSserv 3 }
- cpsSerialPortConf OBJECT IDENTIFIER ::= { cpsAP930xConf 6 }
- cpsSerialGlobal OBJECT IDENTIFIER ::= { cpsSerialPortConf 1 }
- cpsSerialInclude OBJECT-TYPE
- SYNTAX DisplayString (SIZE (0..40))
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "File used in centralized management."
- ::= { cpsSerialGlobal 1 }
- cpsSerialNFS OBJECT-TYPE
- SYNTAX DisplayString (SIZE (0..50))
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "Remote Network File System where data buffering will be
- written instead of the default directory '/var/run/DB'."
- ::= { cpsSerialGlobal 2 }
- cpsSerialLockDir OBJECT-TYPE
- SYNTAX DisplayString (SIZE (0..50))
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "The lock directory."
- ::= { cpsSerialGlobal 3 }
- cpsSerialRlogin OBJECT-TYPE
- SYNTAX DisplayString (SIZE (0..50))
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "Location of the rlogin binary that accepts the -i flag."
- ::= { cpsSerialGlobal 4 }
- cpsSerialPppd OBJECT-TYPE
- SYNTAX DisplayString (SIZE (0..50))
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "Location of the pppd binary."
- ::= { cpsSerialGlobal 5 }
- cpsSerialTelnet OBJECT-TYPE
- SYNTAX DisplayString (SIZE (0..50))
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "Location of the telnet application."
- ::= { cpsSerialGlobal 6 }
- cpsSerialSsh OBJECT-TYPE
- SYNTAX DisplayString (SIZE (0..50))
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "Location of the ssh application."
- ::= { cpsSerialGlobal 7 }
- cpsSerialLocalLogins OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "This parameter is only necessary when authentication is
- being performed for a port.
- This is useful if the Radius authentication server is down.
- 0 indicates OFF,
- 1 indicates ON."
- ::= { cpsSerialGlobal 8 }
- cpsSerialFacility OBJECT-TYPE
- SYNTAX Integer32
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "This value (0-7) is the Local facility sent to the syslog daemon."
- ::= { cpsSerialGlobal 9 }
- cpsSerialDBFacility OBJECT-TYPE
- SYNTAX Integer32
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "This value (0-7) is the Local facility sent to the syslog daemon."
- ::= { cpsSerialGlobal 10 }
- cpsSerialGroupTable OBJECT-TYPE
- SYNTAX SEQUENCE OF CpsSerialGroupEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION ""
- ::= { cpsSerialGlobal 11 }
- cpsSerialGroupEntry OBJECT-TYPE
- SYNTAX CpsSerialGroupEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION ""
- INDEX { cpsSerialGroupIndex }
- ::= { cpsSerialGroupTable 1 }
- CpsSerialGroupEntry ::= SEQUENCE {
- cpsSerialGroupIndex INTEGER,
- cpsSerialGroupName DisplayString,
- cpsSerialGroupUsers DisplayString
- }
- cpsSerialGroupIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION "Number to identify the group."
- ::= { cpsSerialGroupEntry 1 }
- cpsSerialGroupName OBJECT-TYPE
- SYNTAX DisplayString (SIZE (0..20))
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "The group name."
- ::= { cpsSerialGroupEntry 2 }
- cpsSerialGroupUsers OBJECT-TYPE
- SYNTAX DisplayString (SIZE (0..80))
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "The user's names."
- ::= { cpsSerialGroupEntry 3 }
- cpsSerialSpec OBJECT IDENTIFIER ::= { cpsSerialPortConf 2 }
- cpsSerialPortTable OBJECT-TYPE
- SYNTAX SEQUENCE OF CpsSerialPortEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION "This is the specific configuration per serial port."
- ::= { cpsSerialSpec 1 }
- cpsSerialPortEntry OBJECT-TYPE
- SYNTAX CpsSerialPortEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION "One particular serial port configuration."
- INDEX { cpsSerialPortNumber }
- ::= { cpsSerialPortTable 1 }
- CpsSerialPortEntry ::= SEQUENCE {
- cpsSerialPortNumber INTEGER, -- 0 == all. X == ttyX sX.
- cpsSerialPortTty DisplayString, -- associate device
- cpsSerialPortName DisplayString, -- alias name
- cpsSerialPortSpeed Integer32, -- physical port configuration
- cpsSerialPortDataSize Integer32,
- cpsSerialPortStopBits Integer32,
- cpsSerialPortParity DisplayString,
- cpsSerialPortFlowCtrl DisplayString,
- cpsSerialPortDTRdelay Integer32,
- cpsSerialPortDCDCtrl INTEGER,
- cpsSerialPortLogUtmp INTEGER, -- log into UTMP
- cpsSerialPortLogWtmp INTEGER, -- log into WTMP
- cpsSerialPortLogform DisplayString,
- cpsSerialPortAuthtype DisplayString, -- authentication type
- cpsSerialPortAuthSrv1 IpAddress, -- IP address of the primary authentication server
- cpsSerialPortAccSrv1 IpAddress, -- IP address of the primary accounting server
- cpsSerialPortAuthTmo Integer32, -- time out per authentication query
- cpsSerialPortAuthRetr Integer32, -- authentication number of retries
- cpsSerialPortAuthSrv2 IpAddress, -- IP address of the secondary authentication server
- cpsSerialPortAccSrv2 IpAddress, -- IP address of the secondary accounting server
- cpsSerialPortAuthSecret DisplayString, -- secret used in authentication
- cpsSerialPortAuthRadP INTEGER, -- accept RADIUS' user without password
- cpsSerialPortAuthAcc DisplayString, -- access restriction on Users
- cpsSerialPortProtocol DisplayString, -- Profile
- cpsSerialPortRemoteIP DisplayString, -- remote IP address
- cpsSerialPortSocketPort DisplayString, -- number of socket port
- cpsSerialPortRemHost IpAddress, -- IP address of the remote Host
- cpsSerialPortBanner DisplayString, -- Banner
- cpsSerialPortPrompt DisplayString, -- Login prompt
- cpsSerialPortTermType DisplayString, -- terminal type
- cpsSerialPortAutomUsr DisplayString, -- automatic user
- cpsSerialPortNetMask IpAddress, -- net mask
- cpsSerialPortPppMtu Integer32,
- cpsSerialPortPppMru Integer32,
- cpsSerialPortPppOptions DisplayString,
- cpsSerialPortPppFoption DisplayString,
- cpsSerialPortModemChat DisplayString, -- initchat send to modem
- cpsSerialPortSttyCmd DisplayString,
- cpsSerialPortSockTx Integer32, -- socket transmission interval
- cpsSerialPortSockPoll Integer32, -- socket polling interval
- cpsSerialPortSockIdle Integer32, -- socket idle timeout
- cpsSerialPortDBsize Integer32, -- maximum size of the data buffering file
- cpsSerialPortDBtime INTEGER, -- data buffering with/without timestamp
- cpsSerialPortDBmode DisplayString, -- data bufferinf mode circ or line
- cpsSerialPortDBsyslog Integer32, -- size of the data send to syslog
- cpsSerialPortDBmenu INTEGER, -- menu of the data buffering
- cpsSerialPortDBalarm INTEGER, -- use alarm generating feature
- cpsSerialPortSSHbreak DisplayString, -- break sequence (SSH)
- cpsSerialPortSniffSess DisplayString, -- sniff session type
- cpsSerialPortSniffAdm DisplayString, -- admin users to sniff
- cpsSerialPortSniffEsc DisplayString, -- escape char to sniff session
- cpsSerialPortSniffMsess DisplayString, -- multiple session
- cpsSerialPortTelnetMode INTEGER, -- telnet client mode
- cpsSerialPortSysBufSess INTEGER, -- syslog buffering at all times
- cpsSerialPortLFSuppress INTEGER, -- LF suppression in socket_server session
- cpsSerialPortAutoInput DisplayString, -- Input string to auto answer
- cpsSerialPortAutoOutput DisplayString, -- Output string to auto answer
- cpsSerialPortBreakInterval Integer32 -- Break interval (in ms)
- }
- cpsSerialPortNumber OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION "Number to identify the serial port. Value 0 is ALL."
- ::= { cpsSerialPortEntry 1 }
- cpsSerialPortTty OBJECT-TYPE
- SYNTAX DisplayString (SIZE (0..25))
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "The device name for the serial port."
- ::= { cpsSerialPortEntry 2 }
- cpsSerialPortName OBJECT-TYPE
- SYNTAX DisplayString (SIZE (0..40))
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "Alias name given to the server connected to the serial port."
- ::= { cpsSerialPortEntry 3 }
- cpsSerialPortSpeed OBJECT-TYPE
- SYNTAX Integer32
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "The speed of the serial port.
- Supported values are:
- 50, 75, 110, 134, 150, 200, 300, 600,
- 1200, 1800, 2400, 4800, 9600, 14400, 19200,
- 28800, 38400, 57600, 115200, 230400, and 460800"
- ::= { cpsSerialPortEntry 4 }
- cpsSerialPortDataSize OBJECT-TYPE
- SYNTAX Integer32 (4..8)
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "The data size for the serial port."
- ::= { cpsSerialPortEntry 5 }
- cpsSerialPortStopBits OBJECT-TYPE
- SYNTAX Integer32 (0..2)
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "The number of stop bits for the serial port."
- ::= { cpsSerialPortEntry 6 }
- cpsSerialPortParity OBJECT-TYPE
- SYNTAX DisplayString (SIZE (0..5))
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "The parity for the serial port."
- ::= { cpsSerialPortEntry 7 }
- cpsSerialPortFlowCtrl OBJECT-TYPE
- SYNTAX DisplayString (SIZE (0..5))
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "The flow control for the serial port."
- ::= { cpsSerialPortEntry 8 }
- cpsSerialPortDTRdelay OBJECT-TYPE
- SYNTAX Integer32
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "This specifies how long (in milliseconds) a DTR signal
- will be turned off before it is turned on again."
- ::= { cpsSerialPortEntry 9 }
- cpsSerialPortDCDCtrl OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "DCD signal controls the connection request.
- 0 will indicate nocontrol,
- 1 will indicate control."
- ::= { cpsSerialPortEntry 10 }
- cpsSerialPortLogUtmp OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "Update the login records in /var/run/utmp file.
- 0 will indicate inactive,
- 1 will indicate active."
- ::= { cpsSerialPortEntry 11 }
- cpsSerialPortLogWtmp OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "Update the login records in /var/run/wtmp file.
- 0 will indicate inactive,
- 1 will indicate active."
- ::= { cpsSerialPortEntry 12 }
- cpsSerialPortLogform OBJECT-TYPE
- SYNTAX DisplayString (SIZE (0..40))
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "This is the format to write the login record."
- ::= { cpsSerialPortEntry 13 }
- cpsSerialPortAuthtype OBJECT-TYPE
- SYNTAX DisplayString (SIZE (0..25))
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "Authentication type."
- ::= { cpsSerialPortEntry 14 }
- cpsSerialPortAuthSrv1 OBJECT-TYPE
- SYNTAX IpAddress
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "IP address of the primary authentication server."
- ::= { cpsSerialPortEntry 15 }
- cpsSerialPortAccSrv1 OBJECT-TYPE
- SYNTAX IpAddress
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "IP address of the primary accounting server."
- ::= { cpsSerialPortEntry 16 }
- cpsSerialPortAuthTmo OBJECT-TYPE
- SYNTAX Integer32
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "This is the timeout (in seconds) for the authentication
- query to be answered."
- ::= { cpsSerialPortEntry 17 }
- cpsSerialPortAuthRetr OBJECT-TYPE
- SYNTAX Integer32
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "This defines the number of times each server is tried
- before another is contacted."
- ::= { cpsSerialPortEntry 18 }
- cpsSerialPortAuthSrv2 OBJECT-TYPE
- SYNTAX IpAddress
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "IP address of the secondary authentication server."
- ::= { cpsSerialPortEntry 19 }
- cpsSerialPortAccSrv2 OBJECT-TYPE
- SYNTAX IpAddress
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "IP address of the secondary accounting server."
- ::= { cpsSerialPortEntry 20 }
- cpsSerialPortAuthSecret OBJECT-TYPE
- SYNTAX DisplayString (SIZE (0..40))
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "This is the shared secret with authentication servers."
- ::= { cpsSerialPortEntry 21 }
- cpsSerialPortAuthRadP OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "Radius state.
- 0 will indicate inactive,
- 1 will indicate active."
- ::= { cpsSerialPortEntry 22 }
- cpsSerialPortAuthAcc OBJECT-TYPE
- SYNTAX DisplayString (SIZE (0..40))
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "Access restriction."
- ::= { cpsSerialPortEntry 23 }
- cpsSerialPortProtocol OBJECT-TYPE
- SYNTAX DisplayString (SIZE (0..40))
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "Defines the serial port's protocol."
- ::= { cpsSerialPortEntry 24 }
- cpsSerialPortRemoteIP OBJECT-TYPE
- SYNTAX DisplayString (SIZE (0..20))
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "This is the default IP address of the serial port."
- ::= { cpsSerialPortEntry 25 }
- cpsSerialPortSocketPort OBJECT-TYPE
- SYNTAX DisplayString (SIZE (0..10))
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "This defines an alternative labeling system for the serial port."
- ::= { cpsSerialPortEntry 26 }
- cpsSerialPortRemHost OBJECT-TYPE
- SYNTAX IpAddress
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "The IP address of the host to which the serial port will connect."
- ::= { cpsSerialPortEntry 27 }
- cpsSerialPortBanner OBJECT-TYPE
- SYNTAX DisplayString (SIZE (0..250))
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "This defines the banner."
- ::= { cpsSerialPortEntry 28 }
- cpsSerialPortPrompt OBJECT-TYPE
- SYNTAX DisplayString (SIZE (0..250))
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "This defines the login prompt to the serial port."
- ::= { cpsSerialPortEntry 29 }
- cpsSerialPortTermType OBJECT-TYPE
- SYNTAX DisplayString (SIZE (0..20))
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "This defines the terminal type."
- ::= { cpsSerialPortEntry 30 }
- cpsSerialPortAutomUsr OBJECT-TYPE
- SYNTAX DisplayString (SIZE (0..40))
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "This defines the automatic user."
- ::= { cpsSerialPortEntry 31 }
- cpsSerialPortNetMask OBJECT-TYPE
- SYNTAX IpAddress
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "The network mask used in dial in connection."
- ::= { cpsSerialPortEntry 32 }
- cpsSerialPortPppMtu OBJECT-TYPE
- SYNTAX Integer32
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "The PPP MTU - dial in connection."
- ::= { cpsSerialPortEntry 33 }
- cpsSerialPortPppMru OBJECT-TYPE
- SYNTAX Integer32
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "The PPP MRU - dial in connection."
- ::= { cpsSerialPortEntry 34 }
- cpsSerialPortPppOptions OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "The PPP options when the PPP session is autodetected."
- ::= { cpsSerialPortEntry 35 }
- cpsSerialPortPppFoption OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "The PPP forced options when the user has already been authenticated."
- ::= { cpsSerialPortEntry 36 }
- cpsSerialPortModemChat OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "The initchat send to modem connected."
- ::= { cpsSerialPortEntry 37 }
- cpsSerialPortSttyCmd OBJECT-TYPE
- SYNTAX DisplayString (SIZE (0..180))
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "The tty settings after socket connection is established."
- ::= { cpsSerialPortEntry 38 }
- cpsSerialPortSockTx OBJECT-TYPE
- SYNTAX Integer32
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "Defines the delay (in milliseconds) before transmission to
- the Ethernet of data received through a serial port."
- ::= { cpsSerialPortEntry 39 }
- cpsSerialPortSockPoll OBJECT-TYPE
- SYNTAX Integer32
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "Keep-alive timer (milliseconds) for the TCP connection."
- ::= { cpsSerialPortEntry 40 }
- cpsSerialPortSockIdle OBJECT-TYPE
- SYNTAX Integer32
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "The idle timeout in seconds."
- ::= { cpsSerialPortEntry 41 }
- cpsSerialPortDBsize OBJECT-TYPE
- SYNTAX Integer32
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "Maximum size of the data buffering file."
- ::= { cpsSerialPortEntry 42 }
- cpsSerialPortDBtime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "Timestamp in data buffering.
- 0 will indicate inactive,
- 1 will indicate active."
- ::= { cpsSerialPortEntry 43 }
- cpsSerialPortDBmode OBJECT-TYPE
- SYNTAX DisplayString (SIZE (0..5))
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "Data buffering mode : circ or line."
- ::= { cpsSerialPortEntry 44 }
- cpsSerialPortDBsyslog OBJECT-TYPE
- SYNTAX Integer32
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "Size of the data buffer sent to syslog."
- ::= { cpsSerialPortEntry 45 }
- cpsSerialPortDBmenu OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "Menu type for data buffering.
- 0 will indicate display Menu,
- 1 will indicate inactive,
- 2 will indicate DB,
- 3 will indicate Parc."
- ::= { cpsSerialPortEntry 46 }
- cpsSerialPortDBalarm OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "Alarm generation status.
- 0 will indicate inactive,
- 1 will indicate active."
- ::= { cpsSerialPortEntry 47 }
- cpsSerialPortSSHbreak OBJECT-TYPE
- SYNTAX DisplayString (SIZE (0..16))
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "Break sequence - ssh session."
- ::= { cpsSerialPortEntry 48 }
- cpsSerialPortSniffSess OBJECT-TYPE
- SYNTAX DisplayString (SIZE (0..5))
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "Sniff session type."
- ::= { cpsSerialPortEntry 49 }
- cpsSerialPortSniffAdm OBJECT-TYPE
- SYNTAX DisplayString (SIZE (0..40))
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "List of admin users allowed to sniff session."
- ::= { cpsSerialPortEntry 50 }
- cpsSerialPortSniffEsc OBJECT-TYPE
- SYNTAX DisplayString (SIZE (0..6))
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "Escape sequence used in sniff session."
- ::= { cpsSerialPortEntry 51 }
- cpsSerialPortSniffMsess OBJECT-TYPE
- SYNTAX DisplayString (SIZE (0..20))
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION ""
- ::= { cpsSerialPortEntry 52 }
- cpsSerialPortTelnetMode OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "Mode negotiated by client telnet with the server.
- 0 will indicate text,
- 1 will indicate binary."
- ::= { cpsSerialPortEntry 53 }
- cpsSerialPortSysBufSess OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "Syslog Buffering at all times.
- 0 will indicate yes,
- 1 will indicate no."
- ::= { cpsSerialPortEntry 54 }
- cpsSerialPortLFSuppress OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "LF suppression in socket_server session.
- 0 will indicate inactive,
- 1 will indicate active."
- ::= { cpsSerialPortEntry 55 }
- cpsSerialPortAutoInput OBJECT-TYPE
- SYNTAX DisplayString (SIZE (0..40))
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "Input string used for auto answer."
- ::= { cpsSerialPortEntry 56 }
- cpsSerialPortAutoOutput OBJECT-TYPE
- SYNTAX DisplayString (SIZE (0..40))
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "Output string used for auto answer."
- ::= { cpsSerialPortEntry 57 }
- cpsSerialPortBreakInterval OBJECT-TYPE
- SYNTAX Integer32
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "The break interval in milliseconds."
- ::= { cpsSerialPortEntry 58 }
- -- The console Port Server AP930x information group
- cpsInfoSerialPortTable OBJECT-TYPE
- SYNTAX SEQUENCE OF CpsInfoSerialPortEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION "This is the information of the specific serial port."
- ::= { cpsAP930xInfo 1 }
- cpsInfoSerialPortEntry OBJECT-TYPE
- SYNTAX CpsInfoSerialPortEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION "One particular serial port."
- INDEX { cpsInfoSerialPortNumber }
- ::= { cpsInfoSerialPortTable 1 }
- CpsInfoSerialPortEntry ::= SEQUENCE {
- cpsInfoSerialPortNumber INTEGER, -- X == ttyX sX.
- cpsInfoSerialPortTty DisplayString, -- associate device
- cpsInfoSerialPortName DisplayString, -- alias name
- cpsInfoSerialPortSpeed Integer32,
- cpsInfoSerialPortTxBytes Integer32,
- cpsInfoSerialPortRXBytes Integer32,
- cpsInfoSerialPortErrFrame Integer32,
- cpsInfoSerialPortErrParity Integer32,
- cpsInfoSerialPortErrBreaks Integer32,
- cpsInfoSerialPortErrOverrun Integer32,
- cpsInfoSerialPortSigDTR INTEGER,
- cpsInfoSerialPortSigCD INTEGER,
- cpsInfoSerialPortSigDSR INTEGER,
- cpsInfoSerialPortSigRTS INTEGER,
- cpsInfoSerialPortSigCTS INTEGER,
- cpsInfoSerialPortSigRI INTEGER
- }
- cpsInfoSerialPortNumber OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION "Number to identify the serial port."
- ::= { cpsInfoSerialPortEntry 1 }
- cpsInfoSerialPortTty OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION "The device name for the serial port."
- ::= { cpsInfoSerialPortEntry 2 }
- cpsInfoSerialPortName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION "Alias name given to the server connected to the serial port."
- ::= { cpsInfoSerialPortEntry 3 }
- cpsInfoSerialPortSpeed OBJECT-TYPE
- SYNTAX Integer32
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION "The speed for serial port."
- ::= { cpsInfoSerialPortEntry 4 }
- cpsInfoSerialPortTxBytes OBJECT-TYPE
- SYNTAX Integer32
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION "The number of transmitted bytes by the serial port."
- ::= { cpsInfoSerialPortEntry 5 }
- cpsInfoSerialPortRXBytes OBJECT-TYPE
- SYNTAX Integer32
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION "The number of received bytes by the serial port."
- ::= { cpsInfoSerialPortEntry 6 }
- cpsInfoSerialPortErrFrame OBJECT-TYPE
- SYNTAX Integer32
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION "The number of frame errors."
- ::= { cpsInfoSerialPortEntry 7 }
- cpsInfoSerialPortErrParity OBJECT-TYPE
- SYNTAX Integer32
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION "The number of parity errors."
- ::= { cpsInfoSerialPortEntry 8 }
- cpsInfoSerialPortErrBreaks OBJECT-TYPE
- SYNTAX Integer32
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION "The number of breaks errors."
- ::= { cpsInfoSerialPortEntry 9 }
- cpsInfoSerialPortErrOverrun OBJECT-TYPE
- SYNTAX Integer32
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION "The number of overrun errors."
- ::= { cpsInfoSerialPortEntry 10 }
- cpsInfoSerialPortSigDTR OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION "The state of the DTR signal.
- 0 will indicate down,
- 1 will indicate up."
- ::= { cpsInfoSerialPortEntry 11 }
- cpsInfoSerialPortSigCD OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION "The state of the DCD signal.
- 0 will indicate down,
- 1 will indicate up."
- ::= { cpsInfoSerialPortEntry 12 }
- cpsInfoSerialPortSigDSR OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION "The state of the DSR signal.
- 0 will indicate down,
- 1 will indicate up."
- ::= { cpsInfoSerialPortEntry 13 }
- cpsInfoSerialPortSigRTS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION "The state of the RTS signal.
- 0 will indicate down,
- 1 will indicate up."
- ::= { cpsInfoSerialPortEntry 14 }
- cpsInfoSerialPortSigCTS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION "The state of the CTS signal.
- 0 will indicate down,
- 1 will indicate up."
- ::= { cpsInfoSerialPortEntry 15 }
- cpsInfoSerialPortSigRI OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION "The state of the RI signal.
- 0 will indicate down,
- 1 will indicate up."
- ::= { cpsInfoSerialPortEntry 16 }
- -- The console Port Server AP930x administrative group
- apCPSSave OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "Exec saveconf command.
- 0 will indicate don't save,
- 1 will indicate save."
- ::= { cpsAP930xAdm 1 }
-
- apCPSSerialHUP OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION "Exec signal_ras hup command.
- 0 will indicate no restart,
- 1 will indicate restart."
- ::= { cpsAP930xAdm 2 }
- -- the access PX group
- accessPXIdentAlarmStatus OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Access PX alarm status
- 1 = Normal
- 2 = Warning
- 3 = Critical."
- ::= { accessPXIdent 1 }
- accessPXIdentProductNumber OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The product number of the Access PX."
- ::= { accessPXIdent 2 }
- accessPXIdentHardwareRev OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The hardware revision number of the Access PX."
- ::= { accessPXIdent 3 }
- accessPXIdentDateOfManufacture OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The date of manufacture of the Access PX."
- ::= { accessPXIdent 4 }
- accessPXIdentSerialNumber OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The serial number of the Access PX."
- ::= { accessPXIdent 5 }
- accessPXConfigCardReaderEnableDisableAction OBJECT-TYPE
- SYNTAX INTEGER {
- disabled (1),
- enable (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Action to disable/enable the card reader."
- ::= { accessPXConfig 1 }
- accessPXConfigAutoRelockTime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Time (10 - 60) in seconds when the door will automatically relock
- after it has been unlocked and the handle has not been opened."
- ::= { accessPXConfig 2 }
- accessPXConfigCardFormat OBJECT-TYPE
- SYNTAX INTEGER {
- hidStd26 (1),
- hid37Bit (2),
- hid37BitWithFacility (3),
- hidCorp1000 (4)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Indicates and controls the HID card format.
- NOTE: This OID is only valid for HID systems."
- ::= { accessPXConfig 3 }
- accessPXConfigFrontDoorLockControl OBJECT-TYPE
- SYNTAX INTEGER {
- unlock (1),
- lock (2),
- notInstalledReadOnly (3),
- disconnectedReadOnly (4)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Control action (unlock, lock) for the front door. Setting this OID
- will unlock or lock the front door. Getting this OID will respond
- with the current state of the front door lock which could be
- 1 = unlocked,
- 2 = locked,
- 3 = not installed,
- 4 = disconnected."
- ::= { accessPXConfigFront 1 }
- accessPXConfigFrontDoorMaxOpenTime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Time in minutes, (1 - 120), that the front door can be
- allowed to remain open without generating an alarm condition."
- ::= { accessPXConfigFront 2 }
- accessPXStatusFrontDoorLock OBJECT-TYPE
- SYNTAX INTEGER {
- unlocked (1),
- locked (2),
- notInstalled (3),
- disconnected (4)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Present state of the front door lock: unlocked, locked,
- not installed, or disconnected."
- ::= { accessPXStatusFront 1 }
- accessPXStatusFrontDoor OBJECT-TYPE
- SYNTAX INTEGER {
- open (1),
- closed (2),
- notInstalled (3),
- disconnected (4)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Present state of the front door: open, closed,
- not installed, or disconnected."
- ::= { accessPXStatusFront 2 }
- accessPXStatusFrontDoorHandle OBJECT-TYPE
- SYNTAX INTEGER {
- open (1),
- closed (2),
- notInstalled (3),
- disconnected (4)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Present state of the front door handle: open, closed,
- not installed, or disconnected."
- ::= { accessPXStatusFront 3 }
- accessPXStatusFrontDoorMaxOpenTime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Time in minutes, (1 - 120), that the front door can be
- allowed to remain open without generating an alarm condition."
- ::= { accessPXStatusFront 4 }
- accessPXStatusFrontDoorAlarmStatus OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Front door alarm status
- 1 = Normal
- 2 = Warning
- 3 = Critical
- 4 = Front door not installed."
- ::= { accessPXStatusFront 5 }
- accessPXConfigRearDoorLockControl OBJECT-TYPE
- SYNTAX INTEGER {
- unlock (1),
- lock (2),
- notInstalledReadOnly (3),
- disconnectedReadOnly (4)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Control action (unlock, lock) for the rear door. Setting this OID
- will unlock or lock the rear door. Getting this OID will respond
- with the current state of the rear door lock which could be
- 1 = unlocked,
- 2 = locked,
- 3 = not installed,
- 4 = disconnected."
- ::= { accessPXConfigRear 1 }
- accessPXConfigRearDoorMaxOpenTime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Time in minutes, (1 - 120), that the rear door can be
- allowed to remain open without generating an alarm condition."
- ::= { accessPXConfigRear 2 }
- accessPXStatusRearDoorLock OBJECT-TYPE
- SYNTAX INTEGER {
- unlocked (1),
- locked (2),
- notInstalled (3),
- disconnected (4)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Present state of the rear door lock: unlocked, locked,
- not installed, or disconnected."
- ::= { accessPXStatusRear 1 }
- accessPXStatusRearDoor OBJECT-TYPE
- SYNTAX INTEGER {
- open (1),
- closed (2),
- notInstalled (3),
- disconnected (4)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Present state of the rear door: open, closed,
- not installed, or disconnected."
- ::= { accessPXStatusRear 2 }
- accessPXStatusRearDoorHandle OBJECT-TYPE
- SYNTAX INTEGER {
- open (1),
- closed (2),
- notInstalled (3),
- disconnected (4)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Present state of the rear door handle: open, closed,
- not installed, or disconnected."
- ::= { accessPXStatusRear 3 }
- accessPXStatusRearDoorMaxOpenTime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Time in minutes, (1 - 120), that the rear door can be
- allowed to remain open without generating an alarm condition."
- ::= { accessPXStatusRear 4 }
- accessPXStatusRearDoorAlarmStatus OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Rear door alarm status
- 1 = Normal
- 2 = Warning
- 3 = Critical
- 4 = Rear door not installed."
- ::= { accessPXStatusRear 5 }
- accessPXConfigBeaconName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "A descriptive name for the Beacon."
- ::= { accessPXConfigBeacon 1 }
- accessPXConfigBeaconLocation OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "A descriptive name for the location of the Beacon."
- ::= { accessPXConfigBeacon 2 }
- accessPXConfigBeaconAction OBJECT-TYPE
- SYNTAX INTEGER {
- turnOff (1),
- turnOn (2),
- notInstalledReadOnly (3),
- disconnectedReadOnly (4)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Control action (turnOff, turnOn) for the beacon. Setting this OID
- will turn the beacon off or on. Getting this OID will respond
- with the current state which could be
- 1 = off,
- 2 = on,
- 3 = not installed,
- 4 = disconnected."
- ::= { accessPXConfigBeacon 3 }
- accessPXStatusBeaconName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The name of the beacon."
- ::= { accessPXStatusBeacon 1 }
- accessPXStatusBeaconLocation OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The name of the location of the beacon."
- ::= { accessPXStatusBeacon 2 }
- accessPXStatusBeaconCurrentState OBJECT-TYPE
- SYNTAX INTEGER {
- off (1),
- on (2),
- notInstalled (3),
- disconnected (4)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The current state of the beacon: off, on,
- not installed, or disconnected."
- ::= { accessPXStatusBeacon 3 }
- -- the apcLocalDisplay group
- apcLocalDisplayIdentDisplayType OBJECT-TYPE
- SYNTAX INTEGER {
- noDisplayFound (1),
- powerviewRM (2),
- powerviewWW (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Numeric value used to identify the type of display in use."
- ::= { apcLocalDisplayIdent 1 }
- apcLocalDisplayIdentModelNumber OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The model number of the local display."
- ::= { apcLocalDisplayIdent 2 }
- apcLocalDisplayIdentFirmwareRev OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The firmware revision number of the local display."
- ::= { apcLocalDisplayIdent 3 }
- apcLocalDisplayIdentOptions OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A display-specific string identifying options in the local display."
- ::= { apcLocalDisplayIdent 4 }
- apcLocalDisplayIdentDateOfManufacture OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The date of manufacture of the local display, if available."
- ::= { apcLocalDisplayIdent 5 }
- apcLocalDisplayIdentSerialNumber OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The serial number of the local display, if available."
- ::= { apcLocalDisplayIdent 6 }
- apcLocalDisplayConfigAlarmBeeper OBJECT-TYPE
- SYNTAX INTEGER {
- beeperDisabled (1),
- beeperEnabled (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The alarm beeper setting for the local display.
- When enabled, the alarm beeper will begin to sound whenever
- there a new alarm becomes active. The alarm beeper will continue to
- periodically sound until a key is pressed on the display."
- ::= { apcLocalDisplayConfig 1 }
- apcLocalDisplayConfigBeeperVolume OBJECT-TYPE
- SYNTAX INTEGER {
- beeperDisabled (1),
- beeperLow (2),
- beeperMedium (3),
- beeperHigh (4)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The volume setting of the beeper on the local display."
- ::= { apcLocalDisplayConfig 2 }
- apcLocalDisplayConfigCheckLogIndicator OBJECT-TYPE
- SYNTAX INTEGER {
- checklogNotPresent (1),
- checklogDisabled (2),
- checklogInformational (3),
- checklogWarning (4),
- checklogCritical (5)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The minimum level event severity level required to illuminate
- the check log light on the local display.
- notPresent (1) indicates that the display does not have a check log light."
- ::= { apcLocalDisplayConfig 3 }
- apcLocalDisplayConfigKeyClick OBJECT-TYPE
- SYNTAX INTEGER {
- keyclickDisabled (1),
- keyclickEnabled (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The key click setting of the local display."
- ::= { apcLocalDisplayConfig 4 }
- apcLocalDisplayConfigContrast OBJECT-TYPE
- SYNTAX INTEGER {
- contrast1 (1),
- contrast2 (2),
- contrast3 (3),
- contrast4 (4),
- contrast5 (5),
- contrast6 (6),
- contrast7 (7),
- contrast8 (8)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The contrast level of the local display."
- ::= { apcLocalDisplayConfig 5 }
- -- the software group
- -- the powerNetSubAgent group
- -- the powerNetSoftwareSystem group
-
- powerNetSoftwareSystemDescription OBJECT-TYPE
- SYNTAX DisplayString (SIZE (0..79))
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A brief description of the PowerNet sub-agent."
- ::= { powerNetSoftwareSystem 1 }
- powerNetSoftwareOid OBJECT-TYPE
- SYNTAX OBJECT IDENTIFIER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The object identifier of the PowerNet sub-agent."
- ::= { powerNetSoftwareSystem 2 }
- -- powerNetSmuxPeer OBJECT IDENTIFIER ::= { powerNetSoftwareOid 1 }
- -- powerNetDPIPeer OBJECT IDENTIFIER ::= { powerNetSoftwareOid 2 }
- powerNetSoftwareSystemUpTime OBJECT-TYPE
- SYNTAX TimeTicks
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The time that the sub-agent has been running."
- ::= { powerNetSoftwareSystem 3 }
- -- powerNetSoftwareConfig group
- powerNetSoftwareTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of software modules supporting the UPS."
- ::= { powerNetSoftwareConfig 1 }
- powerNetSoftwareTable OBJECT-TYPE
- SYNTAX SEQUENCE OF PowerNetSoftwareEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "A list of the software monitoring the UPS."
- ::= { powerNetSoftwareConfig 2 }
- powerNetSoftwareEntry OBJECT-TYPE
- SYNTAX PowerNetSoftwareEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "An entry containing information on a software module."
- INDEX { moduleNumber }
- ::= { powerNetSoftwareTable 1 }
- PowerNetSoftwareEntry ::=
- SEQUENCE {
- moduleNumber
- INTEGER,
- moduleName
- DisplayString,
- moduleVersion
- DisplayString,
- moduleDate
- DisplayString
- }
- moduleNumber OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index into the Software Entry Table"
- ::= { powerNetSoftwareEntry 1 }
- moduleName OBJECT-TYPE
- SYNTAX DisplayString (SIZE (0..79))
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The name of the software module."
- ::= { powerNetSoftwareEntry 2 }
- moduleVersion OBJECT-TYPE
- SYNTAX DisplayString (SIZE (0..8))
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The version of the software module."
- ::= { powerNetSoftwareEntry 3 }
- moduleDate OBJECT-TYPE
- SYNTAX DisplayString (SIZE (0..9))
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The date of the software module represented as mm-dd-yy."
- ::= { powerNetSoftwareEntry 4 }
- -- the ups group
- -- the upsIdent group
- -- the upsBasicIdent
- upsBasicIdentModel OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The UPS model name (e.g. 'APC Smart-UPS 600')."
- ::= { upsBasicIdent 1 }
- upsBasicIdentName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "An 8 byte ID string identifying the UPS. This object
- can be set by the administrator."
- ::= { upsBasicIdent 2 }
- -- the upsAdvIdent group
- upsAdvIdentFirmwareRevision OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The firmware revision of the UPS system's microprocessor."
- ::= { upsAdvIdent 1 }
- upsAdvIdentDateOfManufacture OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The date when the UPS was manufactured in mm/dd/yy (or yyyy) format."
- ::= { upsAdvIdent 2 }
- upsAdvIdentSerialNumber OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "An 8-character string identifying the serial number of
- the UPS internal microprocessor. This number is set at
- the factory. NOTE: This number does NOT correspond to
- the serial number on the rear of the UPS."
- ::= { upsAdvIdent 3 }
- upsAdvIdentFirmwareRevision2 OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The firmware revision of a UPS system co-microprocessor."
- ::= { upsAdvIdent 4 }
- upsAdvIdentSkuNumber OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The SKU number of a UPS system."
- ::= { upsAdvIdent 5 }
- -- the upsBattery group
- -- the upsBasicBattery group
- upsBasicBatteryStatus OBJECT-TYPE
- SYNTAX INTEGER {
- unknown(1),
- batteryNormal(2),
- batteryLow(3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The status of the UPS batteries. A batteryLow(3)
- value indicates the UPS will be unable to sustain the
- current load, and its services will be lost if power is
- not restored. The amount of run time in reserve at the
- time of low battery can be configured by the
- upsAdvConfigLowBatteryRunTime."
- ::= { upsBasicBattery 1 }
- upsBasicBatteryTimeOnBattery OBJECT-TYPE
- SYNTAX TimeTicks
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The elapsed time since the UPS has switched to battery
- power."
- ::= { upsBasicBattery 2 }
- upsBasicBatteryLastReplaceDate OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The date when the UPS system's batteries were last replaced
- in mm/dd/yy (or yyyy) format. For Smart-UPS models, this value
- is originally set in the factory. When the UPS batteries
- are replaced, this value should be reset by the administrator."
- ::= { upsBasicBattery 3 }
- -- the upsAdvBattery group
- upsAdvBatteryCapacity OBJECT-TYPE
- SYNTAX Gauge
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The remaining battery capacity expressed in
- percent of full capacity."
- ::= { upsAdvBattery 1 }
- upsAdvBatteryTemperature OBJECT-TYPE
- SYNTAX Gauge
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The current internal UPS temperature expressed in
- Celsius."
- ::= { upsAdvBattery 2 }
- upsAdvBatteryRunTimeRemaining OBJECT-TYPE
- SYNTAX TimeTicks
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The UPS battery run time remaining before battery
- exhaustion."
- ::= { upsAdvBattery 3 }
- upsAdvBatteryReplaceIndicator OBJECT-TYPE
- SYNTAX INTEGER {
- noBatteryNeedsReplacing(1),
- batteryNeedsReplacing(2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Indicates whether the UPS batteries need replacing."
- ::= { upsAdvBattery 4 }
- upsAdvBatteryNumOfBattPacks OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of external battery packs connected to the UPS. If
- the UPS does not use smart cells then the agent reports
- ERROR_NO_SUCH_NAME."
- ::= { upsAdvBattery 5 }
- upsAdvBatteryNumOfBadBattPacks OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of external battery packs connected to the UPS that
- are defective. If the UPS does not use smart cells then the
- agent reports ERROR_NO_SUCH_NAME."
- ::= { upsAdvBattery 6 }
- upsAdvBatteryNominalVoltage OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The nominal battery voltage in Volts."
- ::= { upsAdvBattery 7 }
- upsAdvBatteryActualVoltage OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The actual battery bus voltage in Volts."
- ::= { upsAdvBattery 8 }
- upsAdvBatteryCurrent OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The battery current in Amps."
- ::= { upsAdvBattery 9 }
- upsAdvTotalDCCurrent OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The total DC current in Amps."
- ::= { upsAdvBattery 10 }
- -- the upsHighPrecBattery group
- upsHighPrecBatteryCapacity OBJECT-TYPE
- SYNTAX Gauge
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The remaining battery capacity expressed in
- tenths of percent of full capacity."
- ::= { upsHighPrecBattery 1 }
- upsHighPrecBatteryTemperature OBJECT-TYPE
- SYNTAX Gauge
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The current internal UPS temperature expressed in
- tenths of degrees Celsius."
- ::= { upsHighPrecBattery 2 }
- upsHighPrecBatteryNominalVoltage OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The nominal battery voltage in tenths of Volts."
- ::= { upsHighPrecBattery 3 }
- upsHighPrecBatteryActualVoltage OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The actual battery bus voltage in tenths of Volts."
- ::= { upsHighPrecBattery 4 }
- upsHighPrecBatteryCurrent OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The battery current in tenths of Amps."
- ::= { upsHighPrecBattery 5 }
- upsHighPrecTotalDCCurrent OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The total DC current in tenths of Amps."
- ::= { upsHighPrecBattery 6 }
- -- the upsBasicInput group
- upsBasicInputPhase OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The current AC input phase."
- ::= { upsBasicInput 1 }
- -- the upsAdvInput group
- upsAdvInputLineVoltage OBJECT-TYPE
- SYNTAX Gauge
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The current utility line voltage in VAC."
- ::= { upsAdvInput 1 }
- upsAdvInputMaxLineVoltage OBJECT-TYPE
- SYNTAX Gauge
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The maximum utility line voltage in VAC over the
- previous 1 minute period."
- ::= { upsAdvInput 2 }
- upsAdvInputMinLineVoltage OBJECT-TYPE
- SYNTAX Gauge
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The minimum utility line voltage in VAC over the
- previous 1 minute period."
- ::= { upsAdvInput 3 }
- upsAdvInputFrequency OBJECT-TYPE
- SYNTAX Gauge
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The current input frequency to the UPS system in Hz."
- ::= { upsAdvInput 4 }
- upsAdvInputLineFailCause OBJECT-TYPE
- SYNTAX INTEGER {
- noTransfer(1),
- highLineVoltage(2),
- brownout(3),
- blackout(4),
- smallMomentarySag(5),
- deepMomentarySag(6),
- smallMomentarySpike(7),
- largeMomentarySpike(8),
- selfTest(9),
- rateOfVoltageChange(10)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The reason for the occurrence of the last transfer to UPS
- battery power. The variable is set to:
- - noTransfer(1) -- if there is no transfer yet.
- - highLineVoltage(2) -- if the transfer to battery is caused
- by an over voltage greater than the high transfer voltage.
- - brownout(3) -- if the duration of the outage is greater than
- five seconds and the line voltage is between 40% of the
- rated output voltage and the low transfer voltage.
- - blackout(4) -- if the duration of the outage is greater than five
- seconds and the line voltage is between 40% of the rated
- output voltage and ground.
- - smallMomentarySag(5) -- if the duration of the outage is less
- than five seconds and the line voltage is between 40% of the
- rated output voltage and the low transfer voltage.
- - deepMomentarySag(6) -- if the duration of the outage is less
- than five seconds and the line voltage is between 40% of the
- rated output voltage and ground. The variable is set to
- - smallMomentarySpike(7) -- if the line failure is caused by a
- rate of change of input voltage less than ten volts per cycle.
- - largeMomentarySpike(8) -- if the line failure is caused by
- a rate of change of input voltage greater than ten volts per cycle.
- - selfTest(9) -- if the UPS was commanded to do a self test.
- - rateOfVoltageChange(10) -- if the failure is due to the rate of change of
- the line voltage."
- ::= { upsAdvInput 5 }
- -- the upsHighPrecInput group
- upsHighPrecInputLineVoltage OBJECT-TYPE
- SYNTAX Gauge
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The current utility line voltage in tenths of VAC."
- ::= { upsHighPrecInput 1 }
- upsHighPrecInputMaxLineVoltage OBJECT-TYPE
- SYNTAX Gauge
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The maximum utility line voltage in tenths of VAC over the
- previous 1 minute period."
- ::= { upsHighPrecInput 2 }
- upsHighPrecInputMinLineVoltage OBJECT-TYPE
- SYNTAX Gauge
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The minimum utility line voltage in tenths of VAC over the
- previous 1 minute period."
- ::= { upsHighPrecInput 3 }
- upsHighPrecInputFrequency OBJECT-TYPE
- SYNTAX Gauge
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The current input frequency to the UPS system in tenths of Hz."
- ::= { upsHighPrecInput 4 }
- -- the upsBasicOutput group
- upsBasicOutputStatus OBJECT-TYPE
- SYNTAX INTEGER {
- unknown(1),
- onLine(2),
- onBattery(3),
- onSmartBoost(4),
- timedSleeping(5),
- softwareBypass(6),
- off(7),
- rebooting(8),
- switchedBypass(9),
- hardwareFailureBypass(10),
- sleepingUntilPowerReturn(11),
- onSmartTrim(12)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The current state of the UPS. If the UPS is unable
- to determine the state of the UPS this variable is set
- to unknown(1)."
- ::= { upsBasicOutput 1 }
- upsBasicOutputPhase OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The current output phase."
- ::= { upsBasicOutput 2 }
- upsBasicSystemStatus OBJECT-TYPE
- SYNTAX INTEGER {
- unknown(1),
- onLine(2),
- onBattery(3),
- onSmartBoost(4),
- timedSleeping(5),
- softwareBypass(6),
- off(7),
- rebooting(8),
- switchedBypass(9),
- hardwareFailureBypass(10),
- sleepingUntilPowerReturn(11),
- onSmartTrim(12)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Current state for the whole system (UPS and surrounding breakers)
- If unable to determine the state of the system
- this variable is set to unknown(1)."
- ::= { upsBasicOutput 3 }
- -- the upsAdvOutput group
- upsAdvOutputVoltage OBJECT-TYPE
- SYNTAX Gauge
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The output voltage of the UPS system in VAC."
- ::= { upsAdvOutput 1 }
- upsAdvOutputFrequency OBJECT-TYPE
- SYNTAX Gauge
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The current output frequency of the UPS system in Hz."
- ::= { upsAdvOutput 2 }
- upsAdvOutputLoad OBJECT-TYPE
- SYNTAX Gauge
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The current UPS load expressed in percent
- of rated capacity."
- ::= { upsAdvOutput 3 }
- upsAdvOutputCurrent OBJECT-TYPE
- SYNTAX Gauge
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The current in amperes drawn by the load on the UPS."
- ::= { upsAdvOutput 4 }
- upsAdvOutputRedundancy OBJECT-TYPE
- SYNTAX Gauge
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of power modules which can fail or be
- removed without causing the UPS to generate a Minimum
- Redundancy Lost event."
- ::= { upsAdvOutput 5 }
- upsAdvOutputKVACapacity OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The maximum load that this UPS can support."
- ::= { upsAdvOutput 6 }
- -- the upsHighPrecOutput group
- upsHighPrecOutputVoltage OBJECT-TYPE
- SYNTAX Gauge
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The output voltage of the UPS system in tenths of VAC."
- ::= { upsHighPrecOutput 1 }
- upsHighPrecOutputFrequency OBJECT-TYPE
- SYNTAX Gauge
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The current output frequency of the UPS system in tenths of Hz."
- ::= { upsHighPrecOutput 2 }
- upsHighPrecOutputLoad OBJECT-TYPE
- SYNTAX Gauge
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The current UPS load expressed in tenths of percent
- of rated capacity."
- ::= { upsHighPrecOutput 3 }
- upsHighPrecOutputCurrent OBJECT-TYPE
- SYNTAX Gauge
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The current in tenths of amperes drawn by the load on the UPS."
- ::= { upsHighPrecOutput 4 }
- -- the upsBasicConfig group
- upsBasicConfigNumDevices OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of devices that are plugged into the UPS."
- ::= { upsBasicConfig 1 }
- upsBasicConfigDeviceTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsBasicConfigDeviceEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "A list of devices that are plugged into the UPS.
- The number of entries is given by the value of
- upsBasicConfigNumDevices."
- ::= { upsBasicConfig 2 }
- upsBasicConfigDeviceEntry OBJECT-TYPE
- SYNTAX UpsBasicConfigDeviceEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The devices plugged in to the UPS."
- INDEX { deviceIndex }
- ::= { upsBasicConfigDeviceTable 1 }
- UpsBasicConfigDeviceEntry ::=
- SEQUENCE {
- deviceIndex
- INTEGER,
- deviceName
- DisplayString,
- vaRating
- INTEGER,
- acceptThisDevice
- INTEGER
- }
- deviceIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index of the device that is plugged into the UPS."
- ::= { upsBasicConfigDeviceEntry 1 }
- deviceName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The name/description of the device plugged into the UPS."
- ::= { upsBasicConfigDeviceEntry 2 }
- vaRating OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The volt-amp rating of the device plugged into the UPS."
- ::= { upsBasicConfigDeviceEntry 3 }
- acceptThisDevice OBJECT-TYPE
- SYNTAX INTEGER {
- yes(1),
- no(2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "An entry is added if yes, the entry is deleted if no."
- ::= { upsBasicConfigDeviceEntry 4 }
- -- the upsAdvConfig group
- upsAdvConfigRatedOutputVoltage OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The nominal output voltage from the UPS in VAC.
- For a list of allowed values supported by your UPS model,
- see the UPS User's Manual.
-
- If a value other than a supported value is provided in a
- set request, the UPS interprets it as the next lower
- acceptable value. If the provided value is lower than
- the lowest acceptable value, the lowest acceptable
- value is used."
- ::= { upsAdvConfig 1 }
- upsAdvConfigHighTransferVolt OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The maximum line voltage in VAC allowed before the
- UPS system transfers to battery backup.
- For a list of allowed values supported by your UPS model,
- see the UPS User's Manual.
- If a value other than a supported value is provided in a
- set request, the UPS interprets it as a the next higher
- acceptable value. If the provided value is higher than
- the highest acceptable value, the highest acceptable
- value is used."
- ::= { upsAdvConfig 2 }
- upsAdvConfigLowTransferVolt OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The minimum line voltage in VAC allowed before the
- UPS system transfers to battery backup.
-
- For a list of allowed values supported by your UPS model,
- see the UPS User's Manual.
- If a value other than a supported value is provided in a
- set request, the UPS interprets it as the next lower
- acceptable value. If the provided value is lower than
- the lowest acceptable value, the lowest acceptable
- value is used."
- ::= { upsAdvConfig 3 }
- upsAdvConfigAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- timed(1),
- atLowBattery(2),
- never(3),
- mute(4)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "A flag indicating how the UPS should handle audible
- line fail alarms:
- timed(1): UPS alarm will sound after a preset timed duration starting
- from the line fail condition (see OID upsAdvConfigAlarmTimer for the
- alarm timer value)
- atLowBattery(2): UPS alarm will sound when the UPS has reached a Low
- Battery condition during a line fail
- never(3): Disables the UPS audible alarm
- mute(4): Mutes the current alarm for some UPSs only when it is in an
- alarm state and will return to the previously configured option when
- the UPS recovers from the alarm condition"
- ::= { upsAdvConfig 4 }
- upsAdvConfigAlarmTimer OBJECT-TYPE
- SYNTAX TimeTicks
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The time after initial line failure at which the UPS
- begins emitting audible alarms (beeping). This timer is
- observed only if the value of extControlAlarm is timed(2).
- Allowed values are 0 or 30 seconds.
- If a value other than a supported value is provided in a
- set request, the UPS interprets it as a the next lower
- acceptable value. If the provided value is lower than
- the lowest acceptable value, the lowest acceptable
- value is used."
- ::= { upsAdvConfig 5 }
- upsAdvConfigMinReturnCapacity OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The minimum battery capacity required before the UPS will
- return from a low battery shutdown condition. The capacity is
- measured from 0% battery capacity (or Low Battery) as a percent
- of full capacity (100%). In other words, the UPS will not re-energize
- the output until the battery has charged so that its' capacity is equal
- to this value.
-
- For a list of allowed values supported by your UPS model,
- see the UPS User's Manual.
- If a value other than a supported value is provided in a
- set request, the UPS interprets it as a the next higher
- acceptable value. If the provided value is higher than
- the highest acceptable value, the highest acceptable
- value is used."
- ::= { upsAdvConfig 6 }
- upsAdvConfigSensitivity OBJECT-TYPE
- SYNTAX INTEGER {
- auto(1),
- low(2),
- medium(3),
- high(4)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The sensitivity of the UPS to utility line abnormalities
- or noises."
- ::= { upsAdvConfig 7 }
- upsAdvConfigLowBatteryRunTime OBJECT-TYPE
- SYNTAX TimeTicks
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The desired run time of the UPS, in seconds, once the
- low battery condition is reached. During this time the UPS will
- produce a constant warning tone which can not be disabled.
-
- For a list of allowed values supported by your UPS model,
- see the UPS User's Manual.
- If a value other than a supported value is provided in a set
- request, the UPS interprets the value as the next higher
- acceptable value. If the provided value is higher than the
- highest acceptable value, the highest acceptable value is used."
- ::= { upsAdvConfig 8 }
- upsAdvConfigReturnDelay OBJECT-TYPE
- SYNTAX TimeTicks
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The delay in seconds after utility line power returns
- before the UPS will turn on. This value is also used
- when the UPS comes out of a reboot and before the UPS
- wakes up from 'sleep' mode.
- For a list of allowed values supported by your UPS model,
- see the UPS User's Manual.
-
- If a value other than a supported value is provided in a
- set request, the UPS interprets it as a the next higher
- acceptable value. If the provided value is higher than
- the highest acceptable value, the highest acceptable
- value is used."
- ::= { upsAdvConfig 9 }
- upsAdvConfigShutoffDelay OBJECT-TYPE
- SYNTAX TimeTicks
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The delay in seconds the UPS remains on after being told
- to turn off.
- For a list of allowed values supported by your UPS model,
- see the UPS User's Manual.
- If a value other than a supported value is provided in a
- set request, the UPS interprets it as a the next higher
- acceptable value. If the provided value is higher than
- the highest acceptable value, the highest acceptable
- value is used."
- ::= { upsAdvConfig 10 }
- upsAdvConfigUpsSleepTime OBJECT-TYPE
- SYNTAX TimeTicks
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The time in seconds for the UPS to go to 'sleep' when
- instructed. When in sleep mode, the UPS will not provide
- output power regardless of the input line state. Once the
- specified time has elapsed, output power will be restored.
- This is a configuration setting. The UPS will not go to
- sleep until told to do so by the manager from a management
- station.
-
- Any input value is allowed, however the UPS only recognizes
- 1/10 of an hour increments. The provided value will be
- rounded to the closest 1/10 of an hour with one exception:
- Any value entered between 1 and 540 seconds will be rounded
- to 360 seconds (or 6 minutes)."
- ::= { upsAdvConfig 11 }
- upsAdvConfigSetEEPROMDefaults OBJECT-TYPE
- SYNTAX INTEGER {
- noSetEEPROMDefaults(1),
- setEEPROMDefaults(2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "WRITE: Resets the UPS EEPROM variables to default values.
- READ: returns 0"
- ::= { upsAdvConfig 12 }
- upsAdvConfigDipSwitchTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsAdvConfigDipSwitchEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Current settings of UPS dip switches."
- ::= { upsAdvConfig 13 }
- upsAdvConfigDipSwitchEntry OBJECT-TYPE
- SYNTAX UpsAdvConfigDipSwitchEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The current setting of one dip switch."
- INDEX { dipSwitchIndex }
- ::= { upsAdvConfigDipSwitchTable 1 }
- UpsAdvConfigDipSwitchEntry ::=
- SEQUENCE {
- dipSwitchIndex
- INTEGER,
- dipSwitchStatus
- INTEGER
- }
- dipSwitchIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index of a UPS dip switch."
- ::= { upsAdvConfigDipSwitchEntry 1 }
- dipSwitchStatus OBJECT-TYPE
- SYNTAX INTEGER {
- on(1),
- off(2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The setting of a UPS dip switch."
- ::= { upsAdvConfigDipSwitchEntry 2 }
- upsAdvConfigBattExhaustThresh OBJECT-TYPE
- SYNTAX TimeTicks
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The number of seconds prior to battery exhaustion when the
- UPS will switch off power to its load."
- ::= { upsAdvConfig 14 }
- upsAdvConfigPassword OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The password entered at the UPS front panel to enable local
- configuration of the EEProm. If the password is disabled or
- is not supported, then the agent returns a null string."
- ::= { upsAdvConfig 15 }
- upsAdvConfigAllowedSetTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsAdvConfigAllowedSetEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The table listing the allowed values for all discrete
- configurable UPS variables."
- ::= { upsAdvConfig 16 }
- upsAdvConfigAllowedSetEntry OBJECT-TYPE
- SYNTAX UpsAdvConfigAllowedSetEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The table entry for a configurable UPS variable."
- INDEX { apcUpsConfigFieldIndex }
- ::= { upsAdvConfigAllowedSetTable 1 }
- UpsAdvConfigAllowedSetEntry ::= SEQUENCE {
- apcUpsConfigFieldIndex INTEGER,
- apcUpsConfigFieldOID OBJECT IDENTIFIER,
- apcUpsConfigFieldValueRange DisplayString
- }
- apcUpsConfigFieldIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to an eeprom field entry."
- ::= { upsAdvConfigAllowedSetEntry 1 }
- apcUpsConfigFieldOID OBJECT-TYPE
- SYNTAX OBJECT IDENTIFIER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The OID of the current configurable value."
- ::= { upsAdvConfigAllowedSetEntry 2 }
- apcUpsConfigFieldValueRange OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The discrete set of allowed values of a configurable
- register. Individual values are delimited by a comma."
- ::= { upsAdvConfigAllowedSetEntry 3 }
- upsAdvConfigBattCabAmpHour OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Configure the amp-hour setting of the UPS battery cabinet."
- ::= { upsAdvConfig 17 }
- upsAdvConfigPositionSelector OBJECT-TYPE
- SYNTAX INTEGER {
- unknown (1),
- rack (2),
- tower (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Configure UPS position selector. If the UPS doesn't
- support this configuration it will report unknown (1).
- The positions are either rack (2) for rack mounted or
- tower (3) for tower unit."
- ::= { upsAdvConfig 18 }
- upsAdvConfigOutputFreqRange OBJECT-TYPE
- SYNTAX INTEGER {
- unknown (1),
- freqRangeAUTO (2),
- freqRange60Var1 (3),
- freqRange60Var3 (4),
- freqRange50Var1 (5),
- freqRange50Var3 (6),
- freqRange60Var10 (7),
- freqRange50Var10 (8),
- freqRange60Var1dot0 (9),
- freqRange50Var1dot0 (10)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Configure the output frequency tolerance range.
- unknown(1) indicates the output frequency is unknown.
- freqRangeAUTO(2) configure the output frequency range for automatic.
- freqRange60Var1(3) configure the output frequency range for 60 +/- 0.1 Hz
- freqRange60Var3(4) configure the output frequency range for 60 +/- 3.0 Hz
- freqRange50Var1(5) configure the output frequency range for 50 +/- 0.1 Hz
- freqRange50Var3(6) configure the output frequency range for 50 +/- 3.0 Hz
- freqRange60Var10(7) configure the output frequency range for 60 +/- 10 Hz
- freqRange50Var10(8) configure the output frequency range for 50 +/- 10 Hz
- freqRange60Var1dot0(9) configure the output frequency range for 60 +/- 1.0 Hz
- freqRange50Var1dot0(10) configure the output frequency range for 50 +/- 1.0 Hz
-
- For a list of allowed values supported by your UPS model,
- see the UPS User's Manual."
- ::= { upsAdvConfig 19 }
- upsAdvConfigUPSFail OBJECT-TYPE
- SYNTAX INTEGER {
- unknown (1),
- gotoBypass (2),
- dropLoad (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Configure the UPS fail action. If UPS fails,
- and frequency or voltage is out of range it will either
- GotoBypass (2) or DropLoad (3). This OID will report
- unknown (1) if it is not supported feature or option."
- ::= { upsAdvConfig 20 }
- upsAdvConfigAlarmRedundancy OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Configure settings of UPS alarm if the redundancy is
- under the current redundancy. Use 0 for never."
- ::= { upsAdvConfig 21 }
- upsAdvConfigAlarmLoadOver OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Configure settings of UPS alarm if the load is
- over the current load in kVA. Use -1 for never."
- ::= { upsAdvConfig 22 }
- upsAdvConfigAlarmRuntimeUnder OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Configure settings of UPS alarm if the runtime is
- under the current time of minutes. Use -1 for never."
- ::= { upsAdvConfig 23 }
- upsAdvConfigVoutReporting OBJECT-TYPE
- SYNTAX INTEGER {
- unknown (1),
- voutAUTO (2),
- vout208 (3),
- vout240 (4)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Configure the way the UPS scales its output voltage readings.
- unknown(1) indicates the Vout Reporting is unknown.
- voutAUTO(2) configure the Vout Reporting for automatic scaling.
- vout208(3) configure the Vout Reporting for 208 Volts.
- vout240(4) configure the Vout Reporting for 240 Volts."
- ::= { upsAdvConfig 24 }
- upsAdvConfigNumExternalBatteries OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Configure the number of external batteries connected to the UPS."
- ::= { upsAdvConfig 25 }
- upsAdvConfigSimpleSignalShutdowns OBJECT-TYPE
- SYNTAX INTEGER {
- unknown (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Configure Simple Signal shutdown commands from the Simple Signal
- port to be issued to the UPS.
- unknown(1) indicates the Simple Signal Shutdown setting is unknown.
- disabled(2) configure to disable Simple Signal Shutdowns.
- enabled(3) configure to enable Simple Signal Shutdowns."
- ::= { upsAdvConfig 26 }
- upsAdvConfigMaxShutdownTime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The maximum amount of time for server shutdown to complete before a
- UPS shutdown occurs."
- ::= { upsAdvConfig 27 }
- upsAsiUpsControlServerRequestShutdown OBJECT-TYPE
- SYNTAX INTEGER {
- serverShutdownOff (1),
- serverShutdownReboot (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Start a server shutdown sequence:
- serverShutdownOff: Shutdown server and turn off UPS
- serverShutdownReboot: Shutdown server and turn reboot UPS."
- ::= { upsAdvConfig 28 }
- upsAdvConfigMinReturnRuntime OBJECT-TYPE
- SYNTAX TimeTicks
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The minimum amount of run time in seconds required before the output will be
- turned on, using power calculation captured at start of last shutdown."
- ::= { upsAdvConfig 29 }
- upsAdvConfigBasicSignalLowBatteryDuration OBJECT-TYPE
- SYNTAX TimeTicks
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The duration of runtime in seconds during an on-battery condition at which
- the UPS will signal the basic low battery shutdown condition."
- ::= { upsAdvConfig 30 }
- upsAdvConfigBypassPhaseLockRequired OBJECT-TYPE
- SYNTAX INTEGER {
- unknown (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Sets the condition for when bypass is an acceptable mode of operation as a
- requirement."
- ::= { upsAdvConfig 31 }
- upsAdvConfigOutputFreqSlewRate OBJECT-TYPE
- SYNTAX INTEGER {
- unknown (1),
- slewRateQuarterHzPerSec (2),
- slewRateHalfHzPerSec (3),
- slewRate1HzPerSec (4),
- slewRate2HzPerSec (5),
- slewRate4HzPerSec (6),
- slewRate6HzPerSec (7)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The rate at which the UPS will change its output frequency
- in response to utility frequency changes."
- ::= { upsAdvConfig 32 }
- upsAdvConfigChargerLevel OBJECT-TYPE
- SYNTAX INTEGER {
- unknown (1),
- low (2),
- high (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Sets the rate at which the UPS charges its batteries."
- ::= { upsAdvConfig 33 }
- upsAdvConfigBypassToleranceSetting OBJECT-TYPE
- SYNTAX INTEGER {
- unknown (1),
- wide (2),
- medium (3),
- narrow (4),
- custom (5)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "This setting allows selecting from standard bypass tolerance configurations to suit their situation."
- ::= { upsAdvConfig 34 }
- upsAdvConfigMainsSetting OBJECT-TYPE
- SYNTAX INTEGER {
- singleinput (1),
- dualinput (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Configure the type of mains supply system.
- singleinput (1) indicates a single supply system.
- dualinput (2) indicates a dual supply system. "
- ::= { upsAdvConfig 35 }
- upsAdvConfigACWiringSetting OBJECT-TYPE
- SYNTAX INTEGER {
- threewire (1),
- fourwire (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Configure the AC wiring of the system.
- threewire (1) indicates 3 wire system configuration.
- fourwire (2) indicates 4 wire system configuration. "
- ::= { upsAdvConfig 36 }
- upsAdvConfigUpperOutputVoltTolerance OBJECT-TYPE
- SYNTAX INTEGER (0..100)
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Upper tolerance of the output RMS voltage before transferring to bypass.
- Expressed as percent of nominal voltage."
- ::= { upsAdvConfig 37 }
- upsAdvConfigLowerOutputVoltTolerance OBJECT-TYPE
- SYNTAX INTEGER (0..100)
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Lower tolerance of the output RMS voltage before transferring to bypass.
- Expressed as percent of nominal voltage."
- ::= { upsAdvConfig 38 }
- upsAdvConfigUpperBypassVoltTolerance OBJECT-TYPE
- SYNTAX INTEGER (0..100)
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Upper tolerance of the bypass voltage that allows transfer to bypass by user.
- Expressed as percent of nominal voltage."
- ::= { upsAdvConfig 39 }
- upsAdvConfigLowerBypassVoltTolerance OBJECT-TYPE
- SYNTAX INTEGER (0..100)
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Lower tolerance of the bypass voltage that allows transfer to bypass by user.
- Expressed as percent of nominal voltage."
- ::= { upsAdvConfig 40 }
- upsAdvConfigOutofSyncBypassTransferDelay OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Configure the time (in milliseconds), indicating the gap in output voltage
- if an asynchronous transfer to bypass needs to occur."
- ::= { upsAdvConfig 41 }
- -- the upsSyncCtrlGroupConfig group
- upsSCGMembershipGroupNumber OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The SCG Membership Group number (MGN) is a 16-bit number allowing
- up to 65534 separate groups that can be identified and distinguished
- per IP subnet. Zero and 65535 are not used. The MGN is used in all
- communication between members of the SCG and a Network Management Card
- (NMC) will listen and only respond to commands sent to it using its
- configured SCG ID."
- ::= { upsSyncCtrlGroupConfig 1 }
- upsSCGActiveMembershipStatus OBJECT-TYPE
- SYNTAX INTEGER {
- enabledSCG (1),
- disabledSCG (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Membership in the configured SCG can be enabled and
- disabled. If an NMC is configured for an SCG, but
- has its membership disabled, all synchronized control commands
- received will be ignored."
- ::= { upsSyncCtrlGroupConfig 2 }
-
- upsSCGPowerSynchronizationDelayTime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The Power Synchronization Delay Time (PSD) setting is the maximum
- number of seconds an SCG Initiator will wait for all SCG members to
- recover utility power before completing the reboot sequence of a
- reboot or sleep command. If all SCG members are ready to proceed,
- no additional delay is introduced."
- ::= { upsSyncCtrlGroupConfig 3 }
- upsSCGReturnBatteryCapacityOffset OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "A reboot command uses the Initiator's Return battery Capacity (RBC) to control
- when the SCG completes this operation. In a Normal Control Operation (NCC) the
- UPS will only complete the reboot if RBC is reached. Due to normal battery
- charge rate variations it may be desirable for the Followers to complete the
- reboot if they are within some range of the Initiator's RBC when the Initiator
- is prepared (charged to RBC) to complete the reboot. The Return Battery
- Capacity Offset (RBCO) defines a percent battery capacity subtracted from an
- RBC above which a Follower's battery must be charged for it to complete a
- reboot. For example, if the Initiator's RBC is 50% and the Initiator's RBCO is
- 5% then a Follower's battery capacity is within range if it is greater or equal
- to 45% (50% - 5%) at the time when the Initiator tries to complete the reboot
- command. The default RBCO is 10%. "
- ::= { upsSyncCtrlGroupConfig 4 }
-
- upsSCGMultiCastIP OBJECT-TYPE
- SYNTAX IpAddress
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The MultiCast IP address of the SCG Group."
- ::= { upsSyncCtrlGroupConfig 5 }
-
- -- the upsSyncCtrlGroupStatus group
- upsSCGNumOfGroupMembers OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of active, communicating members in the Sync Control Group (SCG).
- This variable indicates the number of rows in the SCG Status Table."
- ::= { upsSyncCtrlGroupStatus 1 }
- -- Sync Control Group Status Table
- upsSCGStatusTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsSCGStatusEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "A list of SCG status table entries. The number of entries
- is given by the value of upsSCGNumOfGroupMembers."
- ::= { upsSyncCtrlGroupStatus 2 }
- upsSCGStatusEntry OBJECT-TYPE
- SYNTAX UpsSCGStatusEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "An entry containing information applicable to a
- particular SCG Member."
- INDEX { upsSCGStatusTableIndex }
- ::= { upsSCGStatusTable 1 }
- UpsSCGStatusEntry ::= SEQUENCE {
- upsSCGStatusTableIndex INTEGER,
- upsSCGMemberIP IpAddress,
- upsSCGACInputStatus INTEGER,
- upsSCGACOutputStatus INTEGER
- }
- upsSCGStatusTableIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index of a status entry for an active, communicating SCG member."
- ::= { upsSCGStatusEntry 1 }
- upsSCGMemberIP OBJECT-TYPE
- SYNTAX IpAddress
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The IP address of an active, communicating SCG Member."
- ::= { upsSCGStatusEntry 2 }
- upsSCGACInputStatus OBJECT-TYPE
- SYNTAX INTEGER {
- acInGood(1),
- acInBad(2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID indicates the AC Input Status of the SCG Member.
- acInGood(1) indicates the AC Input is within tolerance.
- acInBad(2) indicates the AC Input is not within tolerance."
- ::= { upsSCGStatusEntry 3 }
- upsSCGACOutputStatus OBJECT-TYPE
- SYNTAX INTEGER {
- acOutOn(1),
- acOutOff(2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID indicates the AC Output Status of the SCG Member.
- acOutOn(1) indicates the UPS output is providing power to the load.
- acOutOff(2) indicates the UPS output is not providing power to the load. "
- ::= { upsSCGStatusEntry 4 }
- -- the upsBasicState group
- upsBasicStateOutputState OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "An ASCII string containing the 64 flags representing
- the current state(s) of the UPS. If the Network Card
- is unable to determine the state of the UPS, this
- variable is set to 'UNKNOWN'.
- The flags are numbered 1 to 64, read from left to
- right. The flags are defined as follows:
-
- Flag 1: Abnormal Condition Present
- Flag 2: On Battery
- Flag 3: Low Battery
- Flag 4: On Line
-
- Flag 5: Replace Battery
- Flag 6: Serial Communication Established
- Flag 7: AVR Boost Active
- Flag 8: AVR Trim Active
-
- Flag 9: Overload
- Flag 10: Runtime Calibration
- Flag 11: Batteries Discharged
- Flag 12: Manual Bypass
-
- Flag 13: Software Bypass
- Flag 14: In Bypass due to Internal Fault
- Flag 15: In Bypass due to Supply Failure
- Flag 16: In Bypass due to Fan Failure
-
- Flag 17: Sleeping on a Timer
- Flag 18: Sleeping until Utility Power Returns
- Flag 19: On
- Flag 20: Rebooting
-
- Flag 21: Battery Communication Lost
- Flag 22: Graceful Shutdown Initiated
- Flag 23: Smart Boost or Smart Trim Fault
- Flag 24: Bad Output Voltage
- Flag 25: Battery Charger Failure
- Flag 26: High Battery Temperature
- Flag 27: Warning Battery Temperature
- Flag 28: Critical Battery Temperature
- Flag 29: Self Test In Progress
- Flag 30: Low Battery / On Battery
- Flag 31: Graceful Shutdown Issued by Upstream Device
- Flag 32: Graceful Shutdown Issued by Downstream Device
- Flag 33: No Batteries Attached
- Flag 34: Synchronized Command is in Progress
- Flag 35: Synchronized Sleeping Command is in Progress
- Flag 36: Synchronized Rebooting Command is in Progress
- Flag 37: Inverter DC Imbalance
- Flag 38: Transfer Relay Failure
- Flag 39: Shutdown or Unable to Transfer
- Flag 40: Low Battery Shutdown
- Flag 41: Electronic Unit Fan Failure
- Flag 42: Main Relay Failure
- Flag 43: Bypass Relay Failure
- Flag 44: Temporary Bypass
- Flag 45: High Internal Temperature
- Flag 46: Battery Temperature Sensor Fault
- Flag 47: Input Out of Range for Bypass
- Flag 48: DC Bus Overvoltage
- Flag 49: PFC Failure
- Flag 50: Critical Hardware Fault
- Flag 51: <Not Used>
- Flag 52: <Not Used>
-
- Flag 53: <Not Used>
- Flag 54: <Not Used>
- Flag 55: <Not Used>
- Flag 56: <Not Used>
-
- Flag 57: <Not Used>
- Flag 58: <Not Used>
- Flag 59: <Not Used>
- Flag 60: <Not Used>
-
- Flag 61: <Not Used>
- Flag 62: <Not Used>
- Flag 63: <Not Used>
- Flag 64: <Not Used>"
- ::= { upsBasicState 1 }
- -- the upsAdvState group
- upsAdvStateAbnormalConditions OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "An ASCII string containing the 32 flags representing
- the current active UPS faults. If the Network Card
- is unable to determine the values of the flags, this
- variable is set to 'UNKNOWN'. If this variable is not
- supported by the connected UPS, this variable is set to
- 'NOT SUPPORTED'.
-
- The flags are numbered from 1 to 32, and read from left to
- right. The flags are defined as follows:
- Flag 1: Power Module Failure
- Flag 2: Main Intelligence Module Failure
- Flag 3: Redundant Intelligence Module Failure
- Flag 4: Battery Failure
-
- Flag 5: Load(kVA) Alarm Threshold Violation
- Flag 6: Redundancy Lost
- Flag 7: Redundancy Below Alarm Threshold
- Flag 8: Bypass not in Range; Either Frequency or Voltage
-
- Flag 9: Bypass Contactor Stuck in Bypass Condition
- Flag 10: Bypass Contactor Stuck in On-Line Condition
- Flag 11: In Bypass due to an Internal Fault
- Flag 12: In Bypass due to an Overload
-
- Flag 13: In Maintenance Bypass
- Flag 14: Input Circuit Braker Tripped Open
- Flag 15: System Level Fan Failure
- Flag 16: Redundant Intelligent Module in Control
-
- Flag 17: IIC Inter-Module Communication Failure
- Flag 18: No Working Power Modules
- Flag 19: Load Shutdown From Bypass; Input Frequency
- Flag 20: Runtime Below Alarm Threshold
-
- Flag 21: Extended Run Frame Fault
- Flag 22: Output Voltage out of Range
- Flag 23: UPS Not Synchronized
- Flag 24: No Batteries Installed
-
- Flag 25: Battery Voltage High
- Flag 26: UPS Specific Fault Detected
- Flag 27: Site Wiring Fault
- Flag 28: Backfeed Protection Relay Opened
-
- Flag 29: <Not Used>
- Flag 30: <Not Used>
- Flag 31: <Not Used>
- Flag 32: <Not Used>"
- ::= { upsAdvState 1 }
- upsAdvStateSymmetra3PhaseSpecificFaults OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "An ASCII string containing the 64 flags representing
- the current active UPS specific faults for the Symmetra
- 3-Phase UPS models. If the Network Card is unable to
- determine the values of the flags, this variable is set
- to 'UNKNOWN'. If the connected UPS does not use this
- variable, it is set to 'NOT SUPPORTED'.
-
- The flags are numbered from 1 to 64, and read from left
- to right. The bits are defined as follows:
-
- Flag 1: External Switch Gear Failure
- Flag 2: External Transformer Over Temperature
- Flag 3: External DC Circuit Breaker Tripped
- Flag 4: System Power Supply Failure
-
- Flag 5: Battery Monitor Card Failure
- Flag 6: Battery Monitor Card Removed
- Flag 7: XR Communication Card Failure
- Flag 8: XR Communication Card Removed
-
- Flag 9: External Switch Gear Monitoring Card Failure
- Flag 10: External Switch Gear Monitoring Card Removed
- Flag 11: Internal DC Circuit Breaker Tripped
- Flag 12: Static Bypass Switch Failure
-
- Flag 13: System EEPROM Removed
- Flag 14: System EEPROM Failure
- Flag 15: UPS in Forced Bypass
- Flag 16: Static Bypass Switch Module Removed
-
- Flag 17: System Start-Up Configuration Fault
- Flag 18: Battery Charger Shutdown Externally
- Flag 19: <Not Used>
- Flag 20: <Not Used>
-
- Flag 21: <Not Used>
- Flag 22: <Not Used>
- Flag 23: <Not Used>
- Flag 24: <Not Used>
-
- Flag 25: <Not Used>
- Flag 26: <Not Used>
- Flag 27: <Not Used>
- Flag 28: <Not Used>
-
- Flag 29: <Not Used>
- Flag 30: <Not Used>
- Flag 31: <Not Used>
- Flag 32: <Not Used>
-
- Flag 33: <Not Used>
- Flag 34: <Not Used>
- Flag 35: <Not Used>
- Flag 36: <Not Used>
-
- Flag 37: <Not Used>
- Flag 38: <Not Used>
- Flag 39: <Not Used>
- Flag 40: <Not Used>
-
- Flag 41: <Not Used>
- Flag 42: <Not Used>
- Flag 43: <Not Used>
- Flag 44: <Not Used>
-
- Flag 45: <Not Used>
- Flag 46: <Not Used>
- Flag 47: <Not Used>
- Flag 48: <Not Used>
-
- Flag 49: <Not Used>
- Flag 50: <Not Used>
- Flag 51: <Not Used>
- Flag 52: <Not Used>
-
- Flag 53: <Not Used>
- Flag 54: <Not Used>
- Flag 55: <Not Used>
- Flag 56: <Not Used>
-
- Flag 57: <Not Used>
- Flag 58: <Not Used>
- Flag 59: <Not Used>
- Flag 60: <Not Used>
-
- Flag 61: <Not Used>
- Flag 62: <Not Used>
- Flag 63: <Not Used>
- Flag 64: <Not Used>"
- ::= { upsAdvState 2 }
- upsAdvStateDP300ESpecificFaults OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "An ASCII string containing the 64 flags representing
- the current active UPS specific faults for the Silcon
- DP300E UPS models. If the Network Card is unable to
- determine the values of the flags, this variable is set
- to 'UNKNOWN'. If the connected UPS does not use this
- variable, it is set to 'NOT SUPPORTED'.
-
- The flags are numbered from 1 to 64, and read from left
- to right. The bits are defined as follows:
-
- Flag 1: Peak Current Limiter Active
- Flag 2: Bypass Power Supply Fault
- Flag 3: Delta Current Limiter Active
- Flag 4: Fan Fault
-
- Flag 5: High DC warning
- Flag 6: Inverter Voltage Error
- Flag 7: Parallel Synchronization Error
- Flag 8: Second Power Supply Fault
-
- Flag 9: Internal Power Supply Fault
- Flag 10: <Not Used>
- Flag 11: <Not Used>
- Flag 12: <Not Used>
-
- Flag 13: <Not Used>
- Flag 14: Bypass Static Switch High Temperature
- Flag 15: High Battery Temperature
- Flag 16: Battery Weak
-
- Flag 17: <Not Used>
- Flag 18: System Locked in Operation Mode
- Flag 19: RAM1 Memory Write Error
- Flag 20: Memory Write Error
-
- Flag 21: Communication to VQ Bypass Lost
- Flag 22: Communication to VQ Output Lost
- Flag 23: Communication to DMU Lost
- Flag 24: Communication to Controller Lost
-
- Flag 25: Communication to Parallel IF Lost
- Flag 26: External Shutdown Accepted
- Flag 27: DC Capacitor Charge Error
- Flag 28: Communication to VQ Mains Lost
-
- Flag 29: Bypass Synchronization Error
- Flag 30: Charge Error
- Flag 31: SII Aux Input Activiated
- Flag 32: <Not Used>
-
- Flag 33: Blown Inverter Fuse
- Flag 34: Blown Rectifier Fuse
- Flag 35: Auxilliary 1 Fault
- Flag 36: <Not Used>
-
- Flag 37: <Not Used>
- Flag 38: <Not Used>
- Flag 39: <Not Used>
- Flag 40: <Not Used>
-
- Flag 41: <Not Used>
- Flag 42: <Not Used>
- Flag 43: <Not Used>
- Flag 44: <Not Used>
-
- Flag 45: <Not Used>
- Flag 46: High Temperature Charger Magnetic
- Flag 47: <Not Used>
- Flag 48: Battery Monitor Warning
-
- Flag 49: Battery Monitor Alarm
- Flag 50: <Not Used>
- Flag 51: <Not Used>
- Flag 52: <Not Used>
-
- Flag 53: TSM 1/2/3 Temperature Shutdown
- Flag 54: Charger 0/30 Temperature Warning
- Flag 55: Charger 0/30 Temperature Shutdown
- Flag 56: High Output Voltage
-
- Flag 57: SSW Temperature Over 90
- Flag 58: <Not Used>
- Flag 59: Low Current Failure In AC Capacitors
- Flag 60: <Not Used>
-
- Flag 61: Advanced Battery Management Not Installed
- Flag 62: <Not Used>
- Flag 63: <Not Used>
- Flag 64: <Not Used>"
- ::= { upsAdvState 3 }
- upsAdvStateSymmetraSpecificFaults OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "An ASCII string containing the 64 flags representing
- the current active UPS specific faults for the Symmetra
- UPS models. If the Network Card is unable to determine
- the values of the flags, this variable is set to 'UNKNOWN'.
- If the connected UPS does not use this variable, it is
- set to 'NOT SUPPORTED'.
-
- The flags are numbered from 1 to 64, and read from left
- to right. The bits are defined as follows:
-
- Flag 1: System Fault
- Flag 2: Bypass Relay Fault
- Flag 3: Power Module Turn Off Failure
- Flag 4: Frame Identification Fault
-
- Flag 5: <Not Used>
- Flag 6: <Not Used>
- Flag 7: <Not Used>
- Flag 8: <Not Used>
-
- Flag 9: <Not Used>
- Flag 10: <Not Used>
- Flag 11: <Not Used>
- Flag 12: <Not Used>
-
- Flag 13: <Not Used>
- Flag 14: <Not Used>
- Flag 15: <Not Used>
- Flag 16: <Not Used>
-
- Flag 17: <Not Used>
- Flag 18: <Not Used>
- Flag 19: <Not Used>
- Flag 20: <Not Used>
-
- Flag 21: <Not Used>
- Flag 22: <Not Used>
- Flag 23: <Not Used>
- Flag 24: <Not Used>
-
- Flag 25: <Not Used>
- Flag 26: <Not Used>
- Flag 27: <Not Used>
- Flag 28: <Not Used>
-
- Flag 29: <Not Used>
- Flag 30: <Not Used>
- Flag 31: <Not Used>
- Flag 32: <Not Used>
-
- Flag 33: <Not Used>
- Flag 34: <Not Used>
- Flag 35: <Not Used>
- Flag 36: <Not Used>
-
- Flag 37: <Not Used>
- Flag 38: <Not Used>
- Flag 39: <Not Used>
- Flag 40: <Not Used>
-
- Flag 41: <Not Used>
- Flag 42: <Not Used>
- Flag 43: <Not Used>
- Flag 44: <Not Used>
-
- Flag 45: <Not Used>
- Flag 46: <Not Used>
- Flag 47: <Not Used>
- Flag 48: <Not Used>
-
- Flag 49: <Not Used>
- Flag 50: <Not Used>
- Flag 51: <Not Used>
- Flag 52: <Not Used>
-
- Flag 53: <Not Used>
- Flag 54: <Not Used>
- Flag 55: <Not Used>
- Flag 56: <Not Used>
-
- Flag 57: <Not Used>
- Flag 58: <Not Used>
- Flag 59: <Not Used>
- Flag 60: <Not Used>
-
- Flag 61: <Not Used>
- Flag 62: <Not Used>
- Flag 63: <Not Used>
- Flag 64: <Not Used>"
- ::= { upsAdvState 4 }
- upsAdvStateSmartUPSSpecificFaults OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "An ASCII string containing the 64 flags representing
- the current active UPS specific faults for the Smart-UPS
- UPS models. If the Network Card is unable to determine
- the values of the flags, this variable is set to
- 'UNKNOWN'. If the connected UPS does not use this
- variable, it is set to 'NOT SUPPORTED'.
-
- The flags are numbered from 1 to 64, and read from left
- to right. The bits are defined as follows:
-
- Flag 1: EPO Switch Activated
- Flag 2: Static Bypass Switch Fault
- Flag 3: System Configuration Fault
- Flag 4: Power Supply Unit Fault
-
- Flag 5: Weak Battery
- Flag 6: High Battery Temperature
- Flag 7: Internal Mechanical Bypass
- Flag 8: Loss Of Parallel Redundancy
-
- Flag 9: Parallel Bus Communication Fault on Cable 1
- Flag 10: Parallel Bus Communication Fault on Cable 2
- Flag 11: Auxiliary Bus Communication Fault
- Flag 12: Parallel Bus Termination Fault on Cable 1
-
- Flag 13: Parallel Bus Termination Fault on Cable 2
- Flag 14: Auxiliary Bus Termination Fault
- Flag 15: No Master Present In The Parallel System
- Flag 16: Overload on a Parallel Unit
-
- Flag 17: Parallel Configuration Fault
- Flag 18: <Not Used>
- Flag 19: <Not Used>
- Flag 20: <Not Used>
-
- Flag 21: <Not Used>
- Flag 22: <Not Used>
- Flag 23: <Not Used>
- Flag 24: <Not Used>
-
- Flag 25: <Not Used>
- Flag 26: <Not Used>
- Flag 27: <Not Used>
- Flag 28: <Not Used>
-
- Flag 29: <Not Used>
- Flag 30: <Not Used>
- Flag 31: <Not Used>
- Flag 32: <Not Used>
-
- Flag 33: <Not Used>
- Flag 34: <Not Used>
- Flag 35: <Not Used>
- Flag 36: <Not Used>
-
- Flag 37: <Not Used>
- Flag 38: <Not Used>
- Flag 39: <Not Used>
- Flag 40: <Not Used>
-
- Flag 41: <Not Used>
- Flag 42: <Not Used>
- Flag 43: <Not Used>
- Flag 44: <Not Used>
-
- Flag 45: <Not Used>
- Flag 46: <Not Used>
- Flag 47: <Not Used>
- Flag 48: <Not Used>
-
- Flag 49: <Not Used>
- Flag 50: <Not Used>
- Flag 51: <Not Used>
- Flag 52: <Not Used>
-
- Flag 53: <Not Used>
- Flag 54: <Not Used>
- Flag 55: <Not Used>
- Flag 56: <Not Used>
-
- Flag 57: <Not Used>
- Flag 58: <Not Used>
- Flag 59: <Not Used>
- Flag 60: <Not Used>
-
- Flag 61: <Not Used>
- Flag 62: <Not Used>
- Flag 63: <Not Used>
- Flag 64: <Not Used>"
- ::= { upsAdvState 5 }
- upsAdvStateSystemMessages OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "An ASCII string containing the 3 digit Decimal code
- representing the current active message from the
- System Message Register. Each code should remain active
- for a minimum of 15 seconds. However, in the worst case
- scenario, a code could be cleared after only 5 seconds.
- It is recommended that this object be polled at least
- once every 4 seconds in order to get the most accurate
- representation of the current UPS System Message. If the
- Network Card is unable to determine the value of the
- System Message Register, this variable is set to
- 'UNKNOWN'."
- ::= { upsAdvState 6 }
- -- the upsBasicControl group
- upsBasicControlConserveBattery OBJECT-TYPE
- SYNTAX INTEGER {
- noTurnOffUps(1),
- turnOffUpsToConserveBattery(2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Setting this variable to turnUpsOffToConserveBattery(2)
- causes a UPS on battery to be put into 'sleep' mode. The
- UPS will turn back on when utility power is restored.
- Attempting to turn off a UPS that is not on battery will
- result in a badValue error.
- Setting this value to noTurnOffUps(1) has no
- effect.
- The value noTurnOffUps(1) will always be returned
- when the variable is read."
- ::= { upsBasicControl 1 }
- -- the upsAdvControl group
- upsAdvControlUpsOff OBJECT-TYPE
- SYNTAX INTEGER {
- noTurnUpsOff(1),
- turnUpsOff(2),
- turnUpsOffGracefully(3),
- turnUpsSyncGroupOff(4),
- turnUpsSyncGroupOffAfterDelay(5),
- turnUpsSyncGroupOffGracefully(6)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Setting this variable to turnUpsOff(2) causes
- the UPS to shut off. When in this state, the UPS
- will not provide output power regardless of the input
- line state.
- Setting this variable to turnUpsOffGracefully(3) causes
- the UPS to shut off after a delay period. This allows the
- host to shut down in a graceful manner. When in this state,
- the UPS will not provide output power regardless of the
- input line state.
-
- If this UPS is an active member of a Synchronized
- Control Group (SCG) the turnUpsSyncGroupOff(4) command
- will perform a Synchronized Turn Off of all active Group
- members regardless of their current AC output status.
-
- If this UPS is an active member of a Synchronized
- Control Group (SCG) the turnUpsSyncGroupOffAfterDelay(5)
- command will perform a Synchronized Turn Off After Delay
- of all active Group members regardless of their current
- AC output status. This unit's Shutdown Delay will be used
- to execute the Turn Off After Delay command.
-
- If this UPS is an active member of an SCG, the
- turnUpsSyncGroupOffGracefully(6) command will perform a
- Synchronized Turn Off Gracefully of all active Group
- members regardless of their current AC output status.
- This unit's Maximum Shutdown Time and Shutdown Delay will
- be used to execute the Turn Off Gracefully command.
-
- Setting this value to noTurnUpsOff(1) has no
- effect.
- The value noTurnUpsOff(1) will always be returned
- when the variable is read."
- ::= { upsAdvControl 1 }
- upsAdvControlRebootShutdownUps OBJECT-TYPE
- SYNTAX INTEGER {
- noRebootShutdownUps(1),
- rebootShutdownUps(2),
- rebootShutdownUpsGracefully(3),
- rebootShutdownSyncGroupUps(4),
- rebootShutdownSyncGroupUpsGracefully(5)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Setting this variable to rebootShutdownUps(2) causes the UPS
- to shut off and turn back on (as long as good AC input power
- is available, otherwise the UPS will remain off until good AC
- input power is available).
-
- Setting this variable to rebootShutdownUpsGracefully(3) causes
- the UPS to shut off after a delay period and then turn back
- on. This allows the host to shut down in a graceful manner.
-
- If this UPS is an active member of a Synchronized Control
- Group (SCG) the rebootShutdownSyncGroupUps(4) command will
- perform a Synchronized Reboot of all active Group members
- regardless of their current AC output status. If applicable,
- this unit's Power Synchronization Delay, Shutdown Delay,
- Return Delay, Return Battery Capacity, and Return Battery
- Capacity Offset will be used to execute the Reboot command.
-
- If this UPS is an active member of a SCG the
- rebootShutdownSyncGroupUpsGracefully(5) command will perform
- a Synchronized Reboot of all active Group members regardless
- of their current AC output status. If applicable, this unit's
- Power Synchronization Delay, Maximum Shutdown Time, Shutdown
- Delay, Return Delay, Return Battery Capacity, and Return
- Battery Capacity Offset will be used to execute the Reboot
- command.
-
- Setting this value to noRebootShutdownUps(1) has no effect.
-
- The value noRebootShutdownUps(1) will always be returned when
- the variable is read."
- ::= { upsAdvControl 2 }
- upsAdvControlUpsSleep OBJECT-TYPE
- SYNTAX INTEGER {
- noPutUpsToSleep(1),
- putUpsToSleep(2),
- putUpsToSleepGracefully(3),
- putUpsSyncGroupToSleep(4),
- putUpsSyncGroupToSleepGracefully(5)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Setting this variable to putUpsToSleep(2) causes
- the UPS to go to sleep for the time specified by
- upsAdvConfigUpsSleepTime.
-
- Setting this variable to putUpsToSleepGracefully(3)
- causes the UPS to go to sleep for the time specified
- by upsAdvConfigUpsSleepTime after a delay period.
- This allows the host to shut down in a graceful manner.
- If this UPS is an active member of a Synchronized Control
- Group (SCG), the putUpsSyncGroupToSleep(4) command will perform
- a Synchronized Sleep of all active Group members regardless
- of their current AC output status. This unit's Power
- Synchronization Delay, Shutdown Delay, Sleep Time,
- and Return Delay will be used to execute the sleep command.
-
- If this UPS is an active member of a SCG the
- putUpsSyncGroupToSleepGracefully(5) command will perform a
- Synchronized Sleep Gracefully of all active Group members
- regardless of their current AC output status. This unit's
- Power Synchronization Delay, Maximum Shutdown Time, Shutdown
- Delay, Sleep Time, and Return Delay to execute the sleep
- command.
- When in sleep mode, the UPS will not provide output
- power regardless of the input line state. Once the
- specified time has elapsed, output power will be
- restored.
-
- Setting this value to noPutUpsToSleep(1) has no
- effect.
-
- The value noPutUpsToSleep(1) will always be returned
- when the variable is read."
- ::= { upsAdvControl 3 }
- upsAdvControlSimulatePowerFail OBJECT-TYPE
- SYNTAX INTEGER {
- noSimulatePowerFailure(1),
- simulatePowerFailure(2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Setting this variable to simulatePowerFailure(2) causes
- the UPS switch to battery power.
- Setting this value to noSimulatePowerFailure(1) has no
- effect.
- The value noSimulatePowerFailure(1) will always be returned
- when the variable is read."
- ::= { upsAdvControl 4 }
- upsAdvControlFlashAndBeep OBJECT-TYPE
- SYNTAX INTEGER {
- noFlashAndBeep(1),
- flashAndBeep(2),
- flashAndBeepSyncGroup(3),
- flashAndBeepCont(4),
- flashAndBeepCancel(5)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Setting this variable to flashAndBeep(2) causes the
- UPS to beep and simultaneously turn on the UPS front
- panel lights (Smart-UPS only).
- If this UPS is an active member of a Synchronized Control
- Group (SCG), the flashAndBeepSyncGroup(3) command will
- Flash and Beep all active Group members regardless of
- current AC output status.
- Setting this value to noFlashAndBeep(1) has no
- effect.
-
- Setting this value to flashAndBeepCont (4) commandcauses
- the UPS to beep and light the front panel lights until
- the flashAndBeepCancel (5) command is received.
- The value noFlashAndBeep(1) will always be returned
- when the variable is read."
- ::= { upsAdvControl 5 }
- upsAdvControlTurnOnUPS OBJECT-TYPE
- SYNTAX INTEGER {
- noTurnOnUPS(1),
- turnOnUPS(2),
- turnOnUPSSyncGroup(3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Setting this variable to turnOnUPS(2) causes the
- UPS to be turned on immediately.
- If this UPS is an active member of a Synchronized Control
- Group (SCG), the turnOnUPSSyncGroup(3) command will perform
- a Synchronized Turn On of all active Group members
- regardless of their current AC output status.
-
- Setting this value to noTurnOnUPS(1) has no
- effect.
- The value noTurnOnUPS(1) will always be returned
- when the variable is read."
- ::= { upsAdvControl 6 }
- upsAdvControlBypassSwitch OBJECT-TYPE
- SYNTAX INTEGER {
- noBypassSwitch (1),
- switchToBypass (2),
- switchOutOfBypass(3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "This switch puts the UPS in or out of bypass mode."
- ::= { upsAdvControl 7 }
- upsAdvControlRebootUpsWithOrWithoutAC OBJECT-TYPE
- SYNTAX INTEGER {
- noRebootUpsWithOrWithoutAC (1),
- rebootUpsImmediatelyWithOrWithoutAC (2),
- rebootUpsDelayedWithOrWithoutAC (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Setting this variable to rebootUpsImmediatelyWithOrWithoutAC (2)
- causes the UPS to turn off immediately, wait for a minimum time
- (typically 8 seconds), and then turn back on regardless of the
- AC input power on the UPS. Any supported switched outlet
- groups will be turned off immediately but will turned on based
- on their individual settings (to allow on sequencing).
-
- Setting this variable to rebootUpsDelayedWithOrWithoutAC (3)
- causes the UPS to turn off after a delay period, wait for a
- minimum time (typically 8 seconds), and then turn back on
- regardless of the AC input power on the UPS. Any supported
- switched outlet groups will be turned off and on based on their
- individual settings (to allow off and/or on sequencing).
-
- Setting this value to noRebootUpsWithOrWithoutAC (1) has no
- effect.
-
- The value noRebootUpsWithOrWithoutAC (1) will always be
- returned when the variable is read."
- ::= { upsAdvControl 8 }
- upsAdvControlFirmwareUpdate OBJECT-TYPE
- SYNTAX INTEGER {
- noFirmwareUpdate (1),
- firmwareUpdate (2),
- updateInProcess (3),
- updateSuccessful (4),
- updateFailed (5)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Setting this variable to firmwareUpdate(2) causes the
- UPS to begin a firmware update if possible.
-
- Setting this value to noFirmwareUpdate(1) will clear the
- previous results, if any, or otherwise has no effect.
-
- Reading this variable will return noFirmwareUpdate(1) when
- the UPS firmware has not been updated (or previous results
- have been cleared), updateInProcess(3) when the UPS firmware
- is being updated, updateSuccessful(4) when the UPS firmware
- has been successfully updated, or updateFailed(5) if the UPS
- firmware update failed."
- ::= { upsAdvControl 9 }
- -- the upsTest group
- -- the upsBasicTest group
- -- the upsAdvTest group
- upsAdvTestDiagnosticSchedule OBJECT-TYPE
- SYNTAX INTEGER {
- unknown(1),
- biweekly(2),
- weekly(3),
- atTurnOn(4),
- never(5),
- fourWeeks(6),
- twelveWeeks(7),
- biweeklySinceLastTest(8),
- weeklySinceLastTest(9)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The UPS system's automatic battery test schedule."
- ::= { upsAdvTest 1 }
- upsAdvTestDiagnostics OBJECT-TYPE
- SYNTAX INTEGER {
- noTestDiagnostics(1),
- testDiagnostics(2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Setting this variable to testDiagnostics(2) causes
- the UPS to perform a diagnostic self test.
-
- Setting this value to noTestDiagnostics(1) has no
- effect.
-
- The value noTestDiagnostics(1) will always be returned
- when the variable is read."
- ::= { upsAdvTest 2 }
- upsAdvTestDiagnosticsResults OBJECT-TYPE
- SYNTAX INTEGER {
- ok(1),
- failed(2),
- invalidTest(3),
- testInProgress(4)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The results of the last UPS diagnostics test performed."
- ::= { upsAdvTest 3 }
- upsAdvTestLastDiagnosticsDate OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The date the last UPS diagnostics test was performed in
- mm/dd/yy format."
- ::= { upsAdvTest 4 }
- upsAdvTestRuntimeCalibration OBJECT-TYPE
- SYNTAX INTEGER {
- noPerformCalibration(1),
- performCalibration(2),
- cancelCurrentCalibration(3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Setting this variable to performCalibration(2) causes
- the UPS to discharge to calibrate the UPS.
- The test will only start if the battery capacity is 100%.
- The test runs until capacity is less than 25%.
-
- Setting this variable to cancelCurrentCalibration(3)
- after setting performCalibration(2) will cancel the
- current discharge.
-
- Setting this variable to noPerformCalibration(1)
- will have no effect.
-
- The value noPerformCalibration(1) will always be returned
- when the variable is read.
-
- The result of the calibration will be saved in
- upsAdvTestCalibrationResult."
- ::= { upsAdvTest 5 }
- upsAdvTestCalibrationResults OBJECT-TYPE
- SYNTAX INTEGER {
- ok(1),
- invalidCalibration(2),
- calibrationInProgress(3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The results of the last runtime calibration.
-
- Value ok(1) means a successful runtime calibration.
-
- Value invalidCalibration(2) indicates last calibration did
- not take place since the battery capacity was below
- 100%.
-
- Value calibrationInProgress(3) means a calibration
- is occurring now. "
- ::= { upsAdvTest 6 }
- upsAdvTestCalibrationDate OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The date the last UPS runtime calibration was
- performed in mm/dd/yy format."
- ::= { upsAdvTest 7 }
- upsAdvTestDiagnosticTime OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The time of the day to perform automatic battery test.
- Expressed in 24 hour notation - hh:mm."
- ::= { upsAdvTest 8 }
- upsAdvTestDiagnosticDay OBJECT-TYPE
- SYNTAX INTEGER {
- monday (1),
- tuesday (2),
- wednesday (3),
- thursday (4),
- friday (5),
- saturday (6),
- sunday (7)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The day of the week to perform automatic battery test."
- ::= { upsAdvTest 9 }
- -- the upsComm group
- upsCommStatus OBJECT-TYPE
- SYNTAX INTEGER {
- ok(1),
- noComm(2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The status of agent's communication with UPS. "
- ::= { upsComm 1 }
- -- the measureUps group
- -- the Environ group
- mUpsEnvironAmbientTemperature OBJECT-TYPE
- SYNTAX Gauge
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The ambient temperature in Celsius for Probe 1."
- ::= { mUpsEnviron 1 }
- mUpsEnvironRelativeHumidity OBJECT-TYPE
- SYNTAX Gauge
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The relative humidity as a percentage for Probe 1."
- ::= { mUpsEnviron 2 }
- mUpsEnvironAmbientTemperature2 OBJECT-TYPE
- SYNTAX Gauge
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The ambient temperature in Celsius for Probe 2."
- ::= { mUpsEnviron 3 }
- mUpsEnvironRelativeHumidity2 OBJECT-TYPE
- SYNTAX Gauge
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The relative humidity as a percentage for Probe 2."
- ::= { mUpsEnviron 4 }
- -- the mUpsContact group
- mUpsContactNumContacts OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of contacts supported by the Measure-UPS."
- ::= { mUpsContact 1 }
- mUpsContactTable OBJECT-TYPE
- SYNTAX SEQUENCE OF MUpsContactEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "A list of contacts supported by the Measure-UPS."
- ::= { mUpsContact 2 }
- mUpsContactEntry OBJECT-TYPE
- SYNTAX MUpsContactEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "A contact entry containing information for a given contact."
- INDEX { contactNumber }
- ::= { mUpsContactTable 1 }
- MUpsContactEntry ::=
- SEQUENCE {
- contactNumber
- INTEGER,
- normalState
- INTEGER,
- description
- DisplayString,
- monitoringStatus
- INTEGER,
- currentStatus
- INTEGER
- }
- contactNumber OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "An index identifying the contact on the Measure-UPS."
- ::= { mUpsContactEntry 1 }
- normalState OBJECT-TYPE
- SYNTAX INTEGER {
- unknown(1),
- open(2),
- closed(3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The normal operating position of the contact. If the normal
- operating position cannot be set then it is controlled via the
- dip switch on the Measure-UPS and is therefore read-only."
- ::= { mUpsContactEntry 2 }
- description OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The description of the purpose/use of the contact."
- ::= { mUpsContactEntry 3 }
- monitoringStatus OBJECT-TYPE
- SYNTAX INTEGER {
- unknown(1),
- enabled(2),
- disabled(3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "A flag indicating whether this contact is
- monitored, or not."
- ::= { mUpsContactEntry 4 }
- currentStatus OBJECT-TYPE
- SYNTAX INTEGER {
- unknown(1),
- noFault(2),
- fault(3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This value indicates the current state of the contact.
- If the contact is not in its normal state. This value
- is set to fault(2)."
- ::= { mUpsContactEntry 5 }
- -- Three Phase Group
- --
- -- Reset Max/Min Values Group
- --
- upsPhaseResetMaxMinValues OBJECT-TYPE
- SYNTAX INTEGER {
- none (1),
- reset (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Reset the maximum and minimum UPS values:
- upsPhaseInputMaxVoltage, upsPhaseInputMinVoltage,
- upsPhaseInputMaxCurrent, upsPhaseInputMinCurrent,
- upsPhaseInputMaxPower, upsPhaseInputMinPower,
- upsPhaseOutputMaxCurrent, upsPhaseOutputMinCurrent,
- upsPhaseOutputMaxLoad, upsPhaseOutputMinLoad,
- upsPhaseOutputMaxPercentLoad, upsPhaseOutputMinPercentLoad,
- upsPhaseOutputMaxPower, upsPhaseOutputMinPower,
- upsPhaseOutputMaxPercentPower, upsPhaseOutputMinPercentPower."
- ::= { upsPhaseResetValues 1 }
- --
- -- Input Group
- --
- -- Number of Inputs
- upsPhaseNumInputs OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of input feeds to this device.
- This variable indicates the number of rows in the
- input table."
- ::= { upsPhaseInput 1 }
- -- Input Table
- upsPhaseInputTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsPhaseInputEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "A list of input table entries. The number of entries
- is given by the value of upsPhaseNumInputs."
- ::= { upsPhaseInput 2 }
- upsPhaseInputEntry OBJECT-TYPE
- SYNTAX UpsPhaseInputEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "An entry containing information applicable to a
- particular input."
- INDEX { upsPhaseInputTableIndex }
- ::= { upsPhaseInputTable 1 }
- UpsPhaseInputEntry ::= SEQUENCE {
- upsPhaseInputTableIndex INTEGER,
- upsPhaseNumInputPhases INTEGER,
- upsPhaseInputVoltageOrientation INTEGER,
- upsPhaseInputFrequency INTEGER,
- upsPhaseInputType INTEGER,
- upsPhaseInputName DisplayString
- }
- upsPhaseInputTableIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The input identifier."
- ::= { upsPhaseInputEntry 1 }
- upsPhaseNumInputPhases OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of input phases utilized in this
- device. The sum of all the upsPhaseNumInputPhases
- variable indicates the number of rows in the
- input phase table."
- ::= { upsPhaseInputEntry 2 }
- upsPhaseInputVoltageOrientation OBJECT-TYPE
- SYNTAX INTEGER {
- unknown(1),
- singlePhase(2),
- splitPhase(3),
- threePhasePhaseToNeutral(4),
- threePhasePhaseToPhase(5)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The input voltage orientation:
- 1: unknown for this UPS
- 2: singlePhase - phase 1 voltage is between Phase 1
- and Neutral.
- 3: splitPhase - phase 1 voltage is between Phase 1 and
- Neutral; phase 2 voltage is between Phase 2 and Neutral;
- phase 3 voltage is between Phase 1 and Phase 2.
- 4: threePhasePhaseToNeutral - phase 1 voltage is between
- Phase 1 and Neutral; phase 2 voltage is between Phase 2
- and Neutral; phase 3 voltage is between Phase 3 and
- Neutral.
- 5: threePhasePhaseToPhase - phase 1 voltage is between
- Phase 1 and Phase 2; phase 2 voltage is between Phase 2
- and Phase 3; phase 3 voltage is between Phase 3 and
- Phase 1."
- ::= { upsPhaseInputEntry 3 }
- upsPhaseInputFrequency OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The input frequency in 0.1 Hertz, or -1 if it's unsupported
- by this UPS."
- ::= { upsPhaseInputEntry 4 }
- upsPhaseInputType OBJECT-TYPE
- SYNTAX INTEGER {
- unknown(1),
- main(2),
- bypass(3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The input type."
- ::= { upsPhaseInputEntry 5 }
- upsPhaseInputName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "A name given to a particular input."
- ::= { upsPhaseInputEntry 6 }
- -- Input Phase Table
- upsPhaseInputPhaseTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsPhaseInputPhaseEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "A list of input table entries. The number of entries
- is given by the sum of the upsPhaseNumInputPhases."
- ::= { upsPhaseInput 3 }
- upsPhaseInputPhaseEntry OBJECT-TYPE
- SYNTAX UpsPhaseInputPhaseEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "An entry containing information applicable to a
- particular input phase."
- INDEX { upsPhaseInputPhaseTableIndex, upsPhaseInputPhaseIndex }
- ::= { upsPhaseInputPhaseTable 1 }
- UpsPhaseInputPhaseEntry ::= SEQUENCE {
- upsPhaseInputPhaseTableIndex INTEGER,
- upsPhaseInputPhaseIndex INTEGER,
- upsPhaseInputVoltage INTEGER,
- upsPhaseInputMaxVoltage INTEGER,
- upsPhaseInputMinVoltage INTEGER,
- upsPhaseInputCurrent INTEGER,
- upsPhaseInputMaxCurrent INTEGER,
- upsPhaseInputMinCurrent INTEGER,
- upsPhaseInputPower INTEGER,
- upsPhaseInputMaxPower INTEGER,
- upsPhaseInputMinPower INTEGER
- }
- upsPhaseInputPhaseTableIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The input identifier."
- ::= { upsPhaseInputPhaseEntry 1 }
- upsPhaseInputPhaseIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The input phase identifier."
- ::= { upsPhaseInputPhaseEntry 2 }
- upsPhaseInputVoltage OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The input voltage in VAC, or -1 if it's unsupported
- by this UPS."
- ::= { upsPhaseInputPhaseEntry 3 }
- upsPhaseInputMaxVoltage OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The maximum input voltage in VAC measured
- since the last reset (upsPhaseResetMaxMinValues), or
- -1 if it's unsupported by this UPS.
- Sampled every 30 seconds."
- ::= { upsPhaseInputPhaseEntry 4 }
- upsPhaseInputMinVoltage OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The minimum input voltage in VAC measured
- since the last reset (upsPhaseResetMaxMinValues), or
- -1 if it's unsupported by this UPS.
- Sampled every 30 seconds."
- ::= { upsPhaseInputPhaseEntry 5 }
- upsPhaseInputCurrent OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The input current in 0.1 amperes, or -1 if it's
- unsupported by this UPS."
- ::= { upsPhaseInputPhaseEntry 6 }
- upsPhaseInputMaxCurrent OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The maximum input current in 0.1 amperes measured
- since the last reset (upsPhaseResetMaxMinValues), or
- -1 if it's unsupported by this UPS.
- Sampled every 30 seconds."
- ::= { upsPhaseInputPhaseEntry 7 }
- upsPhaseInputMinCurrent OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The minimum input current in 0.1 amperes measured
- since the last reset (upsPhaseResetMaxMinValues), or
- -1 if it's unsupported by this UPS.
- Sampled every 30 seconds."
- ::= { upsPhaseInputPhaseEntry 8 }
- upsPhaseInputPower OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The input power in Watts, or -1 if it's unsupported
- by this UPS."
- ::= { upsPhaseInputPhaseEntry 9 }
- upsPhaseInputMaxPower OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The maximum input power in Watts measured
- since the last reset (upsPhaseResetMaxMinValues), or
- -1 if it's unsupported by this UPS.
- Sampled every 30 seconds."
- ::= { upsPhaseInputPhaseEntry 10 }
- upsPhaseInputMinPower OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The minimum input power in Watts measured
- since the last reset (upsPhaseResetMaxMinValues), or
- -1 if it's unsupported by this UPS.
- Sampled every 30 seconds."
- ::= { upsPhaseInputPhaseEntry 11 }
- --
- -- The Output group.
- --
- -- Number of Outputs
- upsPhaseNumOutputs OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of output feeds to this device.
- This variable indicates the number of rows in the
- output table."
- ::= { upsPhaseOutput 1 }
- -- Output Table
- upsPhaseOutputTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsPhaseOutputEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "A list of output table entries. The number of entries
- is given by the value of upsOutputNumPhases."
- ::= { upsPhaseOutput 2 }
- upsPhaseOutputEntry OBJECT-TYPE
- SYNTAX UpsPhaseOutputEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "An entry containing information applicable to a
- particular output."
- INDEX { upsPhaseOutputTableIndex }
- ::= { upsPhaseOutputTable 1 }
- UpsPhaseOutputEntry ::= SEQUENCE {
- upsPhaseOutputTableIndex INTEGER,
- upsPhaseNumOutputPhases INTEGER,
- upsPhaseOutputVoltageOrientation INTEGER,
- upsPhaseOutputFrequency INTEGER
- }
- upsPhaseOutputTableIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The output identifier."
- ::= { upsPhaseOutputEntry 1 }
- upsPhaseNumOutputPhases OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of output phases utilized in this
- device. The sum of all the upsPhaseNumOutputPhases
- variable indicates the number of rows in the
- output phase table."
- ::= { upsPhaseOutputEntry 2 }
- upsPhaseOutputVoltageOrientation OBJECT-TYPE
- SYNTAX INTEGER {
- unknown(1),
- singlePhase(2),
- splitPhase(3),
- threePhasePhaseToNeutral(4),
- threePhasePhaseToPhase(5)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The output voltage orientation:
- 1: unknown for this UPS
- 2: singlePhase - phase 1 voltage is between Phase 1
- and Neutral.
- 3: splitPhase - phase 1 voltage is between Phase 1 and
- Neutral; phase 2 voltage is between Phase 2 and Neutral;
- phase 3 voltage is between Phase 1 and Phase 2.
- 4: threePhasePhaseToNeutral - phase 1 voltage is between
- Phase 1 and Neutral; phase 2 voltage is between Phase 2
- and Neutral; phase 3 voltage is between Phase 3 and
- Neutral.
- 5: threePhasePhaseToPhase - phase 1 voltage is between
- Phase 1 and Phase 2; phase 2 voltage is between Phase 2
- and Phase 3; phase 3 voltage is between Phase 3 and
- Phase 1."
- ::= { upsPhaseOutputEntry 3 }
- upsPhaseOutputFrequency OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The output frequency in 0.1 Hertz, or -1 if it's
- unsupported by this UPS."
- ::= { upsPhaseOutputEntry 4 }
- -- Output Phase Table
- upsPhaseOutputPhaseTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsPhaseOutputPhaseEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "A list of output table entries. The number of
- entries is given by the sum of the upsPhaseNumOutputPhases."
- ::= { upsPhaseOutput 3 }
- upsPhaseOutputPhaseEntry OBJECT-TYPE
- SYNTAX UpsPhaseOutputPhaseEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "An entry containing information applicable to a
- particular output phase."
- INDEX { upsPhaseOutputPhaseTableIndex, upsPhaseOutputPhaseIndex }
- ::= { upsPhaseOutputPhaseTable 1 }
- UpsPhaseOutputPhaseEntry ::= SEQUENCE {
- upsPhaseOutputPhaseTableIndex INTEGER,
- upsPhaseOutputPhaseIndex INTEGER,
- upsPhaseOutputVoltage INTEGER,
- upsPhaseOutputCurrent INTEGER,
- upsPhaseOutputMaxCurrent INTEGER,
- upsPhaseOutputMinCurrent INTEGER,
- upsPhaseOutputLoad INTEGER,
- upsPhaseOutputMaxLoad INTEGER,
- upsPhaseOutputMinLoad INTEGER,
- upsPhaseOutputPercentLoad INTEGER,
- upsPhaseOutputMaxPercentLoad INTEGER,
- upsPhaseOutputMinPercentLoad INTEGER,
- upsPhaseOutputPower INTEGER,
- upsPhaseOutputMaxPower INTEGER,
- upsPhaseOutputMinPower INTEGER,
- upsPhaseOutputPercentPower INTEGER,
- upsPhaseOutputMaxPercentPower INTEGER,
- upsPhaseOutputMinPercentPower INTEGER
- }
- upsPhaseOutputPhaseTableIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The output identifier."
- ::= { upsPhaseOutputPhaseEntry 1 }
- upsPhaseOutputPhaseIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The output phase identifier."
- ::= { upsPhaseOutputPhaseEntry 2 }
- upsPhaseOutputVoltage OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The output voltage in VAC, or -1 if it's unsupported
- by this UPS."
- ::= { upsPhaseOutputPhaseEntry 3 }
- upsPhaseOutputCurrent OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The output current in 0.1 amperes drawn
- by the load on the UPS, or -1 if it's unsupported
- by this UPS."
- ::= { upsPhaseOutputPhaseEntry 4 }
- upsPhaseOutputMaxCurrent OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The maximum output current in 0.1 amperes measured
- since the last reset (upsPhaseResetMaxMinValues), or
- -1 if it's unsupported by this UPS.
- Sampled every 30 seconds."
- ::= { upsPhaseOutputPhaseEntry 5 }
- upsPhaseOutputMinCurrent OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The minimum output current in 0.1 amperes measured
- since the last reset (upsPhaseResetMaxMinValues), or
- -1 if it's unsupported by this UPS.
- Sampled every 30 seconds."
- ::= { upsPhaseOutputPhaseEntry 6 }
- upsPhaseOutputLoad OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The output load in VA, or -1 if it's unsupported
- by this UPS."
- ::= { upsPhaseOutputPhaseEntry 7 }
- upsPhaseOutputMaxLoad OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The maximum output load in VA measured
- since the last reset (upsPhaseResetMaxMinValues), or
- -1 if it's unsupported by this UPS.
- Sampled every 30 seconds."
- ::= { upsPhaseOutputPhaseEntry 8 }
- upsPhaseOutputMinLoad OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The minimum output load in VA measured
- since the last reset (upsPhaseResetMaxMinValues), or
- -1 if it's unsupported by this UPS.
- Sampled every 30 seconds."
- ::= { upsPhaseOutputPhaseEntry 9 }
- upsPhaseOutputPercentLoad OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The percentage of the UPS load capacity in VA at
- redundancy @ (n + x) presently being used on this
- output phase, or -1 if it's unsupported by this UPS."
- ::= { upsPhaseOutputPhaseEntry 10 }
- upsPhaseOutputMaxPercentLoad OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The maximum percentage of the UPS load capacity in
- VA measured at redundancy @ (n + x) presently
- being used on this output phase since the last reset
- (upsPhaseResetMaxMinValues), or -1 if it's unsupported
- by this UPS. Sampled every 30 seconds."
- ::= { upsPhaseOutputPhaseEntry 11 }
- upsPhaseOutputMinPercentLoad OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The minimum percentage of the UPS load capacity in
- VA measured at redundancy @ (n + x) presently
- being used on this output phase since the last reset
- (upsPhaseResetMaxMinValues), or -1 if it's unsupported
- by this UPS. Sampled every 30 seconds."
- ::= { upsPhaseOutputPhaseEntry 12 }
- upsPhaseOutputPower OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The output power in Watts, or -1 if it's
- unsupported by this UPS."
- ::= { upsPhaseOutputPhaseEntry 13 }
- upsPhaseOutputMaxPower OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The maximum output power in Watts measured
- since the last reset (upsPhaseResetMaxMinValues), or
- -1 if it's unsupported by this UPS.
- Sampled every 30 seconds."
- ::= { upsPhaseOutputPhaseEntry 14 }
- upsPhaseOutputMinPower OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The minimum output power in Watts measured
- since the last reset (upsPhaseResetMaxMinValues), or
- -1 if it's unsupported by this UPS.
- Sampled every 30 seconds."
- ::= { upsPhaseOutputPhaseEntry 15 }
- upsPhaseOutputPercentPower OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The percentage of the UPS power capacity in Watts at
- redundancy @ (n + x) presently being used on this
- output phase, or -1 if it's unsupported by this UPS."
- ::= { upsPhaseOutputPhaseEntry 16 }
- upsPhaseOutputMaxPercentPower OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The maximum percentage of the UPS power capacity
- in Watts measured at redundancy @ (n + x) presently
- being used on this output phase since the last
- reset (upsPhaseResetMaxMinValues), or -1 if it's
- unsupported by this UPS. Sampled every 30 seconds."
- ::= { upsPhaseOutputPhaseEntry 17 }
- upsPhaseOutputMinPercentPower OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The maximum percentage of the UPS power capacity
- in Watts measured at redundancy @ (n + x) presently
- being used on this output phase since the last
- reset (upsPhaseResetMaxMinValues), or -1 if it's
- unsupported by this UPS. Sampled every 30 seconds."
- ::= { upsPhaseOutputPhaseEntry 18 }
- -- the upsOutletGroupStatus group
- upsOutletGroupStatusTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of outlet groups for the UPS."
- ::= { upsOutletGroupStatus 1 }
- upsOutletGroupStatusTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsOutletGroupStatusEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting status of the outlet groups. The number of
- entries is contained in the upsOutletGroupStatusTableSize OID."
- ::= { upsOutletGroupStatus 2 }
- upsOutletGroupStatusEntry OBJECT-TYPE
- SYNTAX UpsOutletGroupStatusEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The outlet group status to get."
- INDEX { upsOutletGroupStatusIndex}
- ::= { upsOutletGroupStatusTable 1 }
- UpsOutletGroupStatusEntry ::=
- SEQUENCE {
- upsOutletGroupStatusIndex INTEGER,
- upsOutletGroupStatusName DisplayString,
- upsOutletGroupStatusGroupState INTEGER,
- upsOutletGroupStatusCommandPending INTEGER,
- upsOutletGroupStatusOutletType INTEGER
- }
- upsOutletGroupStatusIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the outlet group entry."
- ::= { upsOutletGroupStatusEntry 1 }
- upsOutletGroupStatusName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The name of the outlet group. This OID is provided
- for informational purposes only. This value is set
- by the upsOutletGroupConfigName OID."
- ::= { upsOutletGroupStatusEntry 2 }
- upsOutletGroupStatusGroupState OBJECT-TYPE
- SYNTAX INTEGER {
- upsOutletGroupStatusOn (1),
- upsOutletGroupStatusOff (2),
- upsOutletGroupStatusUnknown (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this variable will return the outlet group state. If the outlet
- group is on, the upsOutletGroupStatusOn (1) value will be returned. If
- the outlet group is off, the upsOutletGroupStatusOff (2) value will be
- returned. If the state of the outlet group cannot be determined, the
- upsOutletGroupStatusUnknown (3) value will be returned."
- ::= { upsOutletGroupStatusEntry 3 }
- upsOutletGroupStatusCommandPending OBJECT-TYPE
- SYNTAX INTEGER {
- upsOutletGroupCommandPending (1),
- upsOutletGroupNoCommandPending (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this variable will return the command pending
- state of the outlet group. If a command is pending on the
- outlet group, the upsOutletGroupCommandPending (1) value
- will be returned. If there is not a command pending
- on the outlet group, the upsOutletGroupNoCommandPending (2)
- will be returned."
- ::= { upsOutletGroupStatusEntry 4 }
- upsOutletGroupStatusOutletType OBJECT-TYPE
- SYNTAX INTEGER {
- upsSwitchedOutletGroup (1),
- upsMainOutletGroup (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this variable will return the type of outlet group.
- If present in the system, the main outlet group is
- 'unswitched' and must be on in order for any of the switched
- outlet groups to be on. Conversely, if the main outlet group
- is off, all the switched outlet groups must also be off.
- Therefore, any commands made to the main outlet group that
- turn it off will also be applied to all switched outlet
- groups that are on, unless the state of a switched outlet
- group prevents it, in which case the command will fail."
- ::= { upsOutletGroupStatusEntry 5 }
- -- the upsOutletGroupConfig group
- upsOutletGroupConfigTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of outlet groups for the UPS."
- ::= { upsOutletGroupConfig 1 }
- upsOutletGroupConfigTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsOutletGroupConfigEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The list of outlet groups to configure. The number of entries
- is defined by the upsOutletGroupConfigTableSize OID."
- ::= { upsOutletGroupConfig 2 }
- upsOutletGroupConfigEntry OBJECT-TYPE
- SYNTAX UpsOutletGroupConfigEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The outlet groups to configure."
- INDEX { upsOutletGroupConfigIndex}
- ::= { upsOutletGroupConfigTable 1 }
- UpsOutletGroupConfigEntry ::=
- SEQUENCE {
- upsOutletGroupConfigIndex INTEGER,
- upsOutletGroupConfigName DisplayString,
- upsOutletGroupConfigPowerOnDelay INTEGER,
- upsOutletGroupConfigPowerOffDelay INTEGER,
- upsOutletGroupConfigRebootDuration INTEGER,
- upsOutletGroupConfigMinReturnRuntime INTEGER,
- upsOutletGroupConfigOutletType INTEGER,
- upsOutletGroupConfigLoadShedControlSkipOffDelay INTEGER,
- upsOutletGroupConfigLoadShedControlAutoRestart INTEGER,
- upsOutletGroupConfigLoadShedControlTimeOnBattery INTEGER,
- upsOutletGroupConfigLoadShedControlRuntimeRemaining INTEGER,
- upsOutletGroupConfigLoadShedControlInOverload INTEGER,
- upsOutletGroupConfigLoadShedTimeOnBattery INTEGER,
- upsOutletGroupConfigLoadShedRuntimeRemaining INTEGER
- }
- upsOutletGroupConfigIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the outlet group entry."
- ::= { upsOutletGroupConfigEntry 1 }
- upsOutletGroupConfigName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The name of the outlet group."
- ::= { upsOutletGroupConfigEntry 2 }
-
- upsOutletGroupConfigPowerOnDelay OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The amount of time (seconds) the outlet group will delay
- powering on when the delayed on, reboot, or shutdown command is
- applied. Allowed values vary by UPS model. The value of -1 is
- used for Never if supported by the UPS and the outlet group."
- ::= { upsOutletGroupConfigEntry 3 }
- upsOutletGroupConfigPowerOffDelay OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The amount of time (seconds) the outlet group will delay
- powering off when the delayed off, reboot, or shutdown command is
- applied. Allowed values vary by UPS model. The value of -1 is
- used for Never if supported by the UPS and the outlet group."
- ::= { upsOutletGroupConfigEntry 4 }
- upsOutletGroupConfigRebootDuration OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "During a reboot sequence, power is turned off and then
- back on. This OID defines the amount of time to wait
- (seconds) after turning the power off, at the start
- of the sequence, before initiating the power on sequence.
- Allowed values vary by UPS model."
- ::= { upsOutletGroupConfigEntry 5 }
- upsOutletGroupConfigMinReturnRuntime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "In an Outlet Group shutdown sequence, the Outlet Group cycles
- power off then on. This OID defines the minimum amount of UPS
- runtime (seconds) that is required in order to power the
- Outlet Group on. Allowed values vary by UPS model."
- ::= { upsOutletGroupConfigEntry 6 }
- upsOutletGroupConfigOutletType OBJECT-TYPE
- SYNTAX INTEGER {
- upsSwitchedOutletGroup (1),
- upsMainOutletGroup (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this variable will return the type of outlet group.
- If present in the system, the main outlet group is
- 'unswitched' and must be on in order for any of the switched
- outlet groups to be on. Conversely, if the main outlet group
- is off, all the switched outlet groups must also be off.
- Therefore, any commands made to the main outlet group that
- turn it off will also be applied to all switched outlet
- groups that are on, unless the state of a switched outlet
- group prevents it, in which case the command will fail."
- ::= { upsOutletGroupConfigEntry 7 }
- upsOutletGroupConfigLoadShedControlSkipOffDelay OBJECT-TYPE
- SYNTAX INTEGER {
- upsOutletGroupConfigSkipOffDelay (1),
- upsOutletGroupConfigUseOffDelay (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Configures whether the outlet group's off delay setting
- (upsOutletGroupConfigPowerOffDelay) will be used in a load
- shedding situation, where applicable."
- ::= { upsOutletGroupConfigEntry 8 }
- upsOutletGroupConfigLoadShedControlAutoRestart OBJECT-TYPE
- SYNTAX INTEGER {
- upsOutletGroupConfigAutoRestart (1),
- upsOutletGroupConfigManualRestart (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Configures whether the outlet group will automatically restart
- after a load shedding situation, where applicable."
- ::= { upsOutletGroupConfigEntry 9 }
- upsOutletGroupConfigLoadShedControlTimeOnBattery OBJECT-TYPE
- SYNTAX INTEGER {
- upsOutletGroupConfigDisableTimeOnBatteryLoadShed (1),
- upsOutletGroupConfigEnableTimeOnBatteryLoadShed (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Configures whether the outlet group will load shed (turn off)
- after the UPS's time on battery has exceeded the
- upsOutletGroupConfigLoadShedTimeOnBattery OID setting. The
- settings for upsOutletGroupConfigLoadShedControlSkipOffDelay
- and upsOutletGroupConfigLoadShedControlAutoRestart are valid
- for this load shed condition."
- ::= { upsOutletGroupConfigEntry 10 }
- upsOutletGroupConfigLoadShedControlRuntimeRemaining OBJECT-TYPE
- SYNTAX INTEGER {
- upsOutletGroupConfigDisableRuntimeRemainingLoadShed (1),
- upsOutletGroupConfigEnableRuntimeRemainingLoadShed (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Configures whether the outlet group will load shed (turn off)
- when the UPS is on battery and the remaining runtime is less
- than the upsOutletGroupConfigLoadShedRuntimeRemaining OID
- setting. The settings for
- upsOutletGroupConfigLoadShedControlSkipOffDelay and
- upsOutletGroupConfigLoadShedControlAutoRestart are valid for
- this load shed condition."
- ::= { upsOutletGroupConfigEntry 11 }
- upsOutletGroupConfigLoadShedControlInOverload OBJECT-TYPE
- SYNTAX INTEGER {
- upsOutletGroupConfigDisableInOverloadLoadShed (1),
- upsOutletGroupConfigEnableInOverloadLoadShed (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Configures whether the outlet group will load shed (turn off)
- when the UPS is in an overload condition. The setting for
- upsOutletGroupConfigLoadShedControlSkipOffDelay is valid for
- this load shed condition. Returns -1 if not supported by this
- outlet group."
- ::= { upsOutletGroupConfigEntry 12 }
- upsOutletGroupConfigLoadShedTimeOnBattery OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "When the UPS has been on battery for more time than this
- value, the outlet group will turn off if this condition is
- enabled by the upsOutletGroupConfigLoadShedControlTimeOnBattery
- OID. Allowed values vary by UPS model."
- ::= { upsOutletGroupConfigEntry 13 }
- upsOutletGroupConfigLoadShedRuntimeRemaining OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "When the runtime remaining is less than this value, the outlet
- group will turn off if this condition is enabled by the
- upsOutletGroupConfigLoadShedControlRuntimeRemaining OID.
- Allowed values vary by UPS model."
- ::= { upsOutletGroupConfigEntry 14 }
- -- the upsOutletGroupControl group
- upsOutletGroupControlTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of outlet groups for the UPS."
- ::= { upsOutletGroupControl 1 }
- upsOutletGroupControlTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsOutletGroupControlEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for control of individual outlet groups. The number of
- entries is contained in the upsOutletGroupControlTableSize OID."
- ::= { upsOutletGroupControl 2 }
- upsOutletGroupControlEntry OBJECT-TYPE
- SYNTAX UpsOutletGroupControlEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The outlet group to control."
- INDEX { upsOutletGroupControlIndex}
- ::= { upsOutletGroupControlTable 1 }
- UpsOutletGroupControlEntry ::=
- SEQUENCE {
- upsOutletGroupControlIndex INTEGER,
- upsOutletGroupControlName DisplayString,
- upsOutletGroupControlCommand INTEGER,
- upsOutletGroupControlOutletType INTEGER
- }
- upsOutletGroupControlIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the outlet group entry."
- ::= { upsOutletGroupControlEntry 1 }
- upsOutletGroupControlName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The name of the outlet group. This OID is provided
- for informational purposes only. This value is set
- by the upsOutletGroupConfigName OID."
- ::= { upsOutletGroupControlEntry 2 }
-
- upsOutletGroupControlCommand OBJECT-TYPE
- SYNTAX INTEGER {
- upsOutletGroupImmediateOn (1),
- upsOutletGroupImmediateOff (2),
- upsOutletGroupImmediateRebootWithOrWithoutAC (3),
- upsOutletGroupDelayedOn (4),
- upsOutletGroupDelayedOff (5),
- upsOutletGroupDelayedRebootWithOrWithoutAC (6),
- upsOutletGroupCancelPendingCommand (7),
- upsOutletGroupControlUnknown (8),
- upsOutletGroupImmediateRebootShutdown (9),
- upsOutletGroupDelayedRebootShutdown (10)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Getting this variable will return the outlet group state. If the outlet
- group is on, the upsOutletGroupImmediateOn (1) value will be returned. If
- the outlet group is off, the upsOutletGroupImmediateOff (2) value will be
- returned.
-
- If the state of the outlet group cannot be determined, the
- upsOutletGroupControlUnknown (8) value will be returned.
-
- Setting this variable to upsOutletGroupImmediateOn (1) will turn the
- outlet group on immediately.
-
- Setting this variable to upsOutletGroupImmediateOff (2) will turn the
- outlet group off immediately.
-
- Setting this variable to upsOutletGroupImmediateRebootWithOrWithoutAC (3)
- will turn the outlet group off immediately, wait the
- upsOutletGroupConfigRebootDuration OID time, wait the
- upsOutletGroupConfigPowerOnDelay OID, and then turn the outlet group on
- regardless of the AC input power on the UPS.
-
- Setting this variable to upsOutletGroupDelayedOn (4) will turn the outlet
- group on after the upsOutletGroupConfigPowerOnDelay OID has elapsed.
-
- Setting this variable to upsOutletGroupDelayedOff (5) will turn the outlet
- group off after the upsOutletGroupConfigPowerOffDelay OID has elapsed.
-
- Setting this variable to upsOutletGroupDelayedRebootWithOrWithoutAC (6)
- will turn the outlet group off after the upsOutletGroupConfigPowerOffDelay
- OID has elapsed, wait the upsOutletGroupConfigRebootDuration OID time, wait
- the upsOutletGroupConfigPowerOnDelay OID, and then turn the outlet group
- on regardless of the AC input power on the UPS.
-
- Setting this variable to upsOutletGroupCancelPendingCommand (7) will
- cause any pending command to this outlet group to be canceled.
-
- Setting this variable to upsOutletGroupImmediateRebootShutdown (9) will
- turn the outlet group off immediately, wait for the AC power to be okay
- (a minimum of the upsOutletGroupConfigRebootDuration OID time), wait the
- upsOutletGroupConfigPowerOnDelay OID time, and then turn the outlet
- group on.
-
- Setting this variable to upsOutletGroupDelayedRebootShutdown (10) will
- turn the outlet group off after the upsOutletGroupConfigPowerOffDelay OID
- has elapsed, wait for the AC power to be okay (a minimum of the
- upsOutletGroupConfigRebootDuration OID time), wait the
- upsOutletGroupConfigPowerOnDelay OID time, and then turn the outlet
- group on.
-
- In systems with a main outlet group, commands to the main outlet group must
- be performed with caution. It may be clearer to use the ups control commands
- available from upsAdvControl... OIDs. If any command is made to the main
- outlet group that will turn it off, one of two things will happen:
- 1) If any switched outlet group is in a state that prevents this command
- from occurring on the main outlet group, the command will be rejected. Note
- that a switched outlet group being on without a command in progress is not a
- state that normally prevents the command.
- 2) The command will be accepted and applied to the main outlet group and all
- switched outlet groups that are on.
-
- There is one additional special case for systems with a main outlet group.
- If the main outlet group is off and a switched outlet group is commanded to
- turn on, the on command will be applied to both the main outlet group and
- that switched outlet group."
- ::= { upsOutletGroupControlEntry 3 }
- upsOutletGroupControlOutletType OBJECT-TYPE
- SYNTAX INTEGER {
- upsSwitchedOutletGroup (1),
- upsMainOutletGroup (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this variable will return the type of outlet group.
- If present in the system, the main outlet group is
- 'unswitched' and must be on in order for any of the switched
- outlet groups to be on. Conversely, if the main outlet group
- is off, all the switched outlet groups must also be off.
- Therefore, any commands made to the main outlet group that
- turn it off will also be applied to all switched outlet
- groups that are on, unless the state of a switched outlet
- group prevents it, in which case the command will fail."
- ::= { upsOutletGroupControlEntry 4 }
- -- the upsDiagnosticIM group
- upsDiagIMTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of Intelligence Modules in or attached to the UPS."
- ::= { upsDiagnosticIM 1 }
- upsDiagIMTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsDiagIMEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for diagnostics of individual Intelligence Modules. The number of
- entries is contained in the upsDiagIMTableSize OID."
- ::= { upsDiagnosticIM 2 }
- upsDiagIMEntry OBJECT-TYPE
- SYNTAX UpsDiagIMEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The diagnostics and information of an Intelligence Module."
- INDEX { upsDiagIMIndex}
- ::= { upsDiagIMTable 1 }
- UpsDiagIMEntry ::=
- SEQUENCE {
- upsDiagIMIndex INTEGER,
- upsDiagIMType INTEGER,
- upsDiagIMStatus INTEGER,
- upsDiagIMFirmwareRev DisplayString,
- upsDiagIMSlaveFirmwareRev DisplayString,
- upsDiagIMHardwareRev DisplayString,
- upsDiagIMSerialNum DisplayString,
- upsDiagIMManufactureDate DisplayString
- }
- upsDiagIMIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the Intelligence Module entry."
- ::= { upsDiagIMEntry 1 }
- upsDiagIMType OBJECT-TYPE
- SYNTAX INTEGER {
- imUnknown (1),
- imMIM (2),
- imRIM (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The type of the Intelligence Module.
- imUnknown(1) indicates the IM type is unknown.
- imMIM(2) indicates the IM type is a Main Intelligence Module.
- imRIM(3) indicates the IM type is Redundant Intelligence Module."
- ::= { upsDiagIMEntry 2 }
-
- upsDiagIMStatus OBJECT-TYPE
- SYNTAX INTEGER {
- unknown (1),
- notInstalled (2),
- offOk (3),
- onOk (4),
- offFail (5),
- onFail (6),
- lostComm (7)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The status of the Intelligence Module.
- unknown(1) indicates the device status is unknown.
- notInstalled(2) indicates the device is not installed.
- offOk(3) indicates the device status is off and OK.
- onOk(4) indicates the device status is on and OK.
- offFail(5) indicates the device status is off and failed.
- onFail(6) indicates the device status is on and failed.
- lostComm(7) indicates the device has lost communication."
- ::= { upsDiagIMEntry 3 }
-
- upsDiagIMFirmwareRev OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The firmware revision of the Intelligence Module."
- ::= { upsDiagIMEntry 4 }
-
- upsDiagIMSlaveFirmwareRev OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The slave firmware revision of the Intelligence Module."
- ::= { upsDiagIMEntry 5 }
-
- upsDiagIMHardwareRev OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The hardware revision of the Intelligence Module."
- ::= { upsDiagIMEntry 6 }
-
- upsDiagIMSerialNum OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The serial number of the Intelligence Module."
- ::= { upsDiagIMEntry 7 }
-
- upsDiagIMManufactureDate OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The manufacture date of the Intelligence Module."
- ::= { upsDiagIMEntry 8 }
-
- -- the upsDiagnosticPowerModules group
- upsDiagPMTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The maximum number of Power Modules supported by the UPS."
- ::= { upsDiagnosticPowerModules 1 }
- upsDiagPMTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsDiagPMEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for diagnostics of Individual Power modules. The number of
- entries is contained in the upsDiagPMTableSize OID."
- ::= { upsDiagnosticPowerModules 2 }
- upsDiagPMEntry OBJECT-TYPE
- SYNTAX UpsDiagPMEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The diagnostics of an Power Module."
- INDEX { upsDiagPMIndex}
- ::= { upsDiagPMTable 1 }
- UpsDiagPMEntry ::=
- SEQUENCE {
- upsDiagPMIndex INTEGER,
- upsDiagPMStatus INTEGER,
- upsDiagPMFirmwareRev DisplayString,
- upsDiagPMHardwareRev DisplayString,
- upsDiagPMSerialNum DisplayString,
- upsDiagPMManufactureDate DisplayString
- }
- upsDiagPMIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the Power Module entry."
- ::= { upsDiagPMEntry 1 }
-
- upsDiagPMStatus OBJECT-TYPE
- SYNTAX INTEGER {
- unknown (1),
- notInstalled (2),
- offOk (3),
- onOk (4),
- offFail (5),
- onFail (6),
- lostComm (7)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The status of the Power Module.
- unknown(1) indicates the device status is unknown.
- notInstalled(2) indicates the device is not installed.
- offOk(3) indicates the device status is off and OK.
- onOk(4) indicates the device status is on and OK.
- offFail(5) indicates the device status is off and failed.
- onFail(6) indicates the device status is on and failed.
- lostComm(7) indicates the device has lost communication."
- ::= { upsDiagPMEntry 2 }
-
- upsDiagPMFirmwareRev OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The firmware revision of the Power Module."
- ::= { upsDiagPMEntry 3 }
-
- upsDiagPMHardwareRev OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The hardware revision of the Power Module."
- ::= { upsDiagPMEntry 4 }
-
- upsDiagPMSerialNum OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The serial number of the Power Module."
- ::= { upsDiagPMEntry 5 }
-
- upsDiagPMManufactureDate OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The manufacture date of the Power Module."
- ::= { upsDiagPMEntry 6 }
- -- the upsDiagnosticBatteries group
- upsDiagBatteryTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The maximum number of batteries supported by the UPS."
- ::= { upsDiagnosticBatteries 1 }
- upsDiagBatteryTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsDiagBatteryEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for diagnostics of individual batteries. The number of
- entries is contained in the upsDiagBattTableSize OID."
- ::= { upsDiagnosticBatteries 2 }
- upsDiagBatteryEntry OBJECT-TYPE
- SYNTAX UpsDiagBatteryEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The diagnostics of a battery."
- INDEX { upsDiagBatteryIndex}
- ::= { upsDiagBatteryTable 1 }
- UpsDiagBatteryEntry ::=
- SEQUENCE {
- upsDiagBatteryFrameIndex INTEGER,
- upsDiagBatteryIndex INTEGER,
- upsDiagBatteryStatus INTEGER,
- upsDiagBatterySerialNumber DisplayString,
- upsDiagBatteryFirmwareRev DisplayString,
- upsDiagBatteryManufactureDate DisplayString,
- upsDiagBatteryType DisplayString
- }
- upsDiagBatteryFrameIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the battery frame entry.
- Frame 0 indicates the Main frame. Extended Run (XR) frames
- start from index 1."
- ::= { upsDiagBatteryEntry 1 }
-
- upsDiagBatteryIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the battery entry."
- ::= { upsDiagBatteryEntry 2 }
-
- upsDiagBatteryStatus OBJECT-TYPE
- SYNTAX INTEGER {
- unknown (1),
- notInstalled (2),
- ok (3),
- failed (4),
- highTemperature (5),
- replaceImmediately (6),
- lowCapacity (7)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The status of the battery.
- unknown(1) indicates the device status is unknown.
- notInstalled(2) indicates the device is not installed.
- ok(3) indicates the battery status is OK.
- failed(4) indicates the battery status is failed.
- highTemperature(5) indicates the battery has a high temperature condition.
- replaceImmediately(6) indicates the battery must be replaced immediately.
- lowCapacity(7) indicates the battery has a low capacity."
- ::= { upsDiagBatteryEntry 3 }
-
- upsDiagBatterySerialNumber OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The serial number of the battery."
- ::= { upsDiagBatteryEntry 4 }
-
- upsDiagBatteryFirmwareRev OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The firmware revision of the battery."
- ::= { upsDiagBatteryEntry 5 }
-
- upsDiagBatteryManufactureDate OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The manufacture date of the battery."
- ::= { upsDiagBatteryEntry 6 }
-
- upsDiagBatteryType OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The battery type or rating for the battery."
- ::= { upsDiagBatteryEntry 7 }
-
- -- the upsDiagnosticSubsystem group
- upsDiagSubSysFrameTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of frames attached to the UPS including the Main frame."
- ::= { upsDiagnosticSubsystem 1 }
- upsDiagSubSysFrameTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsDiagSubSysFrameEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for diagnostics of individual XR Frames."
- ::= { upsDiagnosticSubsystem 2 }
- upsDiagSubSysFrameEntry OBJECT-TYPE
- SYNTAX UpsDiagSubSysFrameEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The diagnostics of an XR Frame."
- INDEX { upsDiagSubSysFrameIndex}
- ::= { upsDiagSubSysFrameTable 1 }
- UpsDiagSubSysFrameEntry ::=
- SEQUENCE {
- upsDiagSubSysFrameIndex INTEGER,
- upsDiagSubSysFrameType INTEGER,
- upsDiagSubSysFrameFirmwareRev DisplayString,
- upsDiagSubSysFrameHardwareRev DisplayString,
- upsDiagSubSysFrameSerialNum DisplayString,
- upsDiagSubSysFrameManufactureDate DisplayString
- }
- upsDiagSubSysFrameIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The frame index entry."
- ::= { upsDiagSubSysFrameEntry 1 }
-
- upsDiagSubSysFrameType OBJECT-TYPE
- SYNTAX INTEGER {
- unknown (1),
- notInstalled (2),
- frameTypeMain (3),
- frameTypeXR (4),
- frameTypeLXR (5)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The type of Frame.
- unknown(1) indicates the device status is unknown.
- notInstalled(2) indicates the device is not installed.
- frameTypeMain(3) indicates the frame type is the Main Frame.
- frameTypeXR(4) indicates the frame type is an XR Frame.
- frameTypeLXR(5) indicates the frame type is an LXR Frame."
- ::= { upsDiagSubSysFrameEntry 2 }
-
- upsDiagSubSysFrameFirmwareRev OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The firmware revision of the frame."
- ::= { upsDiagSubSysFrameEntry 3 }
-
- upsDiagSubSysFrameHardwareRev OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The hardware revision of the frame."
- ::= { upsDiagSubSysFrameEntry 4 }
-
- upsDiagSubSysFrameSerialNum OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The serial number of the frame."
- ::= { upsDiagSubSysFrameEntry 5 }
-
- upsDiagSubSysFrameManufactureDate OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The manufacture date of the frame."
- ::= { upsDiagSubSysFrameEntry 6 }
-
- upsDiagSubSysIntBypSwitchTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of Internal Bypass switches attached to the UPS."
- ::= { upsDiagnosticSubsystem 3 }
- upsDiagSubSysIntBypSwitchTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsDiagSubSysIntBypSwitchEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for diagnostics of the Internal Bypass Switch."
- ::= { upsDiagnosticSubsystem 4 }
- upsDiagSubSysIntBypSwitchEntry OBJECT-TYPE
- SYNTAX UpsDiagSubSysIntBypSwitchEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The diagnostics of the Internal Bypass Switch."
- INDEX { upsDiagSubSysIntBypSwitchIndex}
- ::= { upsDiagSubSysIntBypSwitchTable 1 }
- UpsDiagSubSysIntBypSwitchEntry ::=
- SEQUENCE {
- upsDiagSubSysIntBypSwitchFrameIndex INTEGER,
- upsDiagSubSysIntBypSwitchIndex INTEGER,
- upsDiagSubSysIntBypSwitchStatus INTEGER,
- upsDiagSubSysIntBypSwitchFirmwareRev DisplayString,
- upsDiagSubSysIntBypSwitchHardwareRev DisplayString,
- upsDiagSubSysIntBypSwitchSerialNum DisplayString,
- upsDiagSubSysIntBypSwitchManufactureDate DisplayString
- }
- upsDiagSubSysIntBypSwitchFrameIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The frame index entry."
- ::= { upsDiagSubSysIntBypSwitchEntry 1 }
-
- upsDiagSubSysIntBypSwitchIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The Internal Bypass Switch index entry."
- ::= { upsDiagSubSysIntBypSwitchEntry 2 }
-
- upsDiagSubSysIntBypSwitchStatus OBJECT-TYPE
- SYNTAX INTEGER {
- unknown (1),
- notInstalled (2),
- offOk (3),
- onOk (4),
- offFail (5),
- onFail (6),
- lostComm (7)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The Internal Bypass Switch status.
- unknown(1) indicates the device status is unknown.
- notInstalled(2) indicates the device is not installed.
- offOk(3) indicates the device status is off and OK.
- onOk(4) indicates the device status is on and OK.
- offFail(5) indicates the device status is off and failed.
- onFail(6) indicates the device status is on and failed.
- lostComm(7) indicates the device has lost communication."
- ::= { upsDiagSubSysIntBypSwitchEntry 3 }
-
- upsDiagSubSysIntBypSwitchFirmwareRev OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The firmware revision of the Internal Bypass Switch."
- ::= { upsDiagSubSysIntBypSwitchEntry 4 }
-
- upsDiagSubSysIntBypSwitchHardwareRev OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The hardware revision of the Internal Bypass Switch."
- ::= { upsDiagSubSysIntBypSwitchEntry 5 }
-
- upsDiagSubSysIntBypSwitchSerialNum OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The serial number of the Internal Bypass Switch."
- ::= { upsDiagSubSysIntBypSwitchEntry 6 }
-
- upsDiagSubSysIntBypSwitchManufactureDate OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The manufacture date of the Internal Bypass Switch."
- ::= { upsDiagSubSysIntBypSwitchEntry 7 }
-
- upsDiagSubSysBattMonitorTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of Battery Monitor Boards attached to the UPS."
- ::= { upsDiagnosticSubsystem 5 }
- upsDiagSubSysBattMonitorTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsDiagSubSysBattMonitorEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for diagnostics of the Battery Monitor Board."
- ::= { upsDiagnosticSubsystem 6 }
- upsDiagSubSysBattMonitorEntry OBJECT-TYPE
- SYNTAX UpsDiagSubSysBattMonitorEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The diagnostics of the Battery Monitor Board."
- INDEX { upsDiagSubSysBattMonitorIndex}
- ::= { upsDiagSubSysBattMonitorTable 1 }
- UpsDiagSubSysBattMonitorEntry ::=
- SEQUENCE {
- upsDiagSubSysBattMonitorFrameIndex INTEGER,
- upsDiagSubSysBattMonitorIndex INTEGER,
- upsDiagSubSysBattMonitorStatus INTEGER,
- upsDiagSubSysBattMonitorFirmwareRev DisplayString,
- upsDiagSubSysBattMonitorHardwareRev DisplayString,
- upsDiagSubSysBattMonitorSerialNum DisplayString,
- upsDiagSubSysBattMonitorManufactureDate DisplayString
- }
- upsDiagSubSysBattMonitorFrameIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The frame index entry."
- ::= { upsDiagSubSysBattMonitorEntry 1 }
-
- upsDiagSubSysBattMonitorIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index of the Battery Monitor Board."
- ::= { upsDiagSubSysBattMonitorEntry 2 }
-
- upsDiagSubSysBattMonitorStatus OBJECT-TYPE
- SYNTAX INTEGER {
- unknown (1),
- notInstalled (2),
- offOk (3),
- onOk (4),
- offFail (5),
- onFail (6),
- lostComm (7)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The status of the Battery Monitor Board.
- unknown(1) indicates the device status is unknown.
- notInstalled(2) indicates the device is not installed.
- offOk(3) indicates the device status is off and OK.
- onOk(4) indicates the device status is on and OK.
- offFail(5) indicates the device status is off and failed.
- onFail(6) indicates the device status is on and failed.
- lostComm(7) indicates the device has lost communication."
- ::= { upsDiagSubSysBattMonitorEntry 3 }
-
- upsDiagSubSysBattMonitorFirmwareRev OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The firmware revision of the Battery Monitor Board."
- ::= { upsDiagSubSysBattMonitorEntry 4 }
-
- upsDiagSubSysBattMonitorHardwareRev OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The hardware revision of the Battery Monitor Board."
- ::= { upsDiagSubSysBattMonitorEntry 5 }
-
- upsDiagSubSysBattMonitorSerialNum OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The serial number of the Battery Monitor Board."
- ::= { upsDiagSubSysBattMonitorEntry 6 }
-
- upsDiagSubSysBattMonitorManufactureDate OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The date of the manufacture for the Battery Monitor Board."
- ::= { upsDiagSubSysBattMonitorEntry 7 }
-
- upsDiagSubSysExternalSwitchGearTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of External Switch Gears attached to the UPS."
- ::= { upsDiagnosticSubsystem 7 }
- upsDiagSubSysExternalSwitchGearTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsDiagSubSysExternalSwitchGearEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for diagnostics of the individual External Switch Gear."
- ::= { upsDiagnosticSubsystem 8 }
- upsDiagSubSysExternalSwitchGearEntry OBJECT-TYPE
- SYNTAX UpsDiagSubSysExternalSwitchGearEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The diagnostics of an individual External Switch Gear."
- INDEX { upsDiagSubSysExternalSwitchGearIndex}
- ::= { upsDiagSubSysExternalSwitchGearTable 1 }
- UpsDiagSubSysExternalSwitchGearEntry ::=
- SEQUENCE {
- upsDiagSubSysExternalSwitchGearFrameIndex INTEGER,
- upsDiagSubSysExternalSwitchGearIndex INTEGER,
- upsDiagSubSysExternalSwitchGearStatus INTEGER,
- upsDiagSubSysExternalSwitchGearFirmwareRev DisplayString,
- upsDiagSubSysExternalSwitchGearHardwareRev DisplayString,
- upsDiagSubSysExternalSwitchGearSerialNum DisplayString,
- upsDiagSubSysExternalSwitchGearManufactureDate DisplayString
- }
- upsDiagSubSysExternalSwitchGearFrameIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The frame index entry."
- ::= { upsDiagSubSysExternalSwitchGearEntry 1 }
-
- upsDiagSubSysExternalSwitchGearIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index of the External Switch Gear."
- ::= { upsDiagSubSysExternalSwitchGearEntry 2 }
-
- upsDiagSubSysExternalSwitchGearStatus OBJECT-TYPE
- SYNTAX INTEGER {
- unknown (1),
- notInstalled (2),
- offOk (3),
- onOk (4),
- offFail (5),
- onFail (6),
- lostComm (7)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The status of the External Switch Gear.
- unknown(1) indicates the device status is unknown.
- notInstalled(2) indicates the device is not installed.
- offOk(3) indicates the device status is off and OK.
- onOk(4) indicates the device status is on and OK.
- offFail(5) indicates the device status is off and failed.
- onFail(6) indicates the device status is on and failed.
- lostComm(7) indicates the device has lost communication."
- ::= { upsDiagSubSysExternalSwitchGearEntry 3 }
-
- upsDiagSubSysExternalSwitchGearFirmwareRev OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The firmware revision of the External Switch Gear monitor card."
- ::= { upsDiagSubSysExternalSwitchGearEntry 4 }
-
- upsDiagSubSysExternalSwitchGearHardwareRev OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The hardware revision of the External Switch Gear monitor card."
- ::= { upsDiagSubSysExternalSwitchGearEntry 5 }
-
- upsDiagSubSysExternalSwitchGearSerialNum OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The serial number of the External Switch Gear monitor card."
- ::= { upsDiagSubSysExternalSwitchGearEntry 6 }
-
- upsDiagSubSysExternalSwitchGearManufactureDate OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The date of the manufacture for the External Switch Gear monitor card."
- ::= { upsDiagSubSysExternalSwitchGearEntry 7 }
- upsDiagSubSysDisplayInterfaceCardTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of Display Interface Cards attached to the UPS."
- ::= { upsDiagnosticSubsystem 9 }
- upsDiagSubSysDisplayInterfaceCardTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsDiagSubSysDisplayInterfaceCardEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for diagnostics of individual Display Interface Cards."
- ::= { upsDiagnosticSubsystem 10 }
- upsDiagSubSysDisplayInterfaceCardEntry OBJECT-TYPE
- SYNTAX UpsDiagSubSysDisplayInterfaceCardEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The diagnostics of a Display Interface Card."
- INDEX { upsDiagSubSysDisplayInterfaceCardIndex}
- ::= { upsDiagSubSysDisplayInterfaceCardTable 1 }
- UpsDiagSubSysDisplayInterfaceCardEntry ::=
- SEQUENCE {
- upsDiagSubSysDisplayInterfaceCardFrameIndex INTEGER,
- upsDiagSubSysDisplayInterfaceCardIndex INTEGER,
- upsDiagSubSysDisplayInterfaceCardStatus INTEGER
- }
- upsDiagSubSysDisplayInterfaceCardFrameIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The frame index entry."
- ::= { upsDiagSubSysDisplayInterfaceCardEntry 1 }
-
- upsDiagSubSysDisplayInterfaceCardIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index of the Display Interface Card."
- ::= { upsDiagSubSysDisplayInterfaceCardEntry 2 }
-
- upsDiagSubSysDisplayInterfaceCardStatus OBJECT-TYPE
- SYNTAX INTEGER {
- unknown (1),
- notInstalled (2),
- offOk (3),
- onOk (4),
- offFail (5),
- onFail (6),
- lostComm (7)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The status of the Display Interface Card.
- unknown(1) indicates the device status is unknown.
- notInstalled(2) indicates the device is not installed.
- offOk(3) indicates the device status is off and OK.
- onOk(4) indicates the device status is on and OK.
- offFail(5) indicates the device status is off and failed.
- onFail(6) indicates the device status is on and failed.
- lostComm(7) indicates the device has lost communication."
- ::= { upsDiagSubSysDisplayInterfaceCardEntry 3 }
-
- upsDiagSubSysDCCircuitBreakerTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of DC Circuit Breakers attached to the UPS."
- ::= { upsDiagnosticSubsystem 11 }
- upsDiagSubSysDCCircuitBreakerTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsDiagSubSysDCCircuitBreakerEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for diagnostics of individual DC Circuit Breakers."
- ::= { upsDiagnosticSubsystem 12 }
- upsDiagSubSysDCCircuitBreakerEntry OBJECT-TYPE
- SYNTAX UpsDiagSubSysDCCircuitBreakerEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The diagnostics of a DC Circuit Breaker."
- INDEX { upsDiagSubSysDCCircuitBreakerIndex}
- ::= { upsDiagSubSysDCCircuitBreakerTable 1 }
- UpsDiagSubSysDCCircuitBreakerEntry ::=
- SEQUENCE {
- upsDiagSubSysDCCircuitBreakerFrameIndex INTEGER,
- upsDiagSubSysDCCircuitBreakerIndex INTEGER,
- upsDiagSubSysDCCircuitBreakerStatus INTEGER
- }
- upsDiagSubSysDCCircuitBreakerFrameIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The frame index entry."
- ::= { upsDiagSubSysDCCircuitBreakerEntry 1 }
-
- upsDiagSubSysDCCircuitBreakerIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index of the DC Circuit Breaker."
- ::= { upsDiagSubSysDCCircuitBreakerEntry 2 }
-
- upsDiagSubSysDCCircuitBreakerStatus OBJECT-TYPE
- SYNTAX INTEGER {
- unknown (1),
- notInstalled (2),
- opened (3),
- closed (4)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The status of the DC Circuit Breaker.
- unknown(1) indicates the circuit breaker status is unknown.
- notInstalled(2) indicates the circuit breaker is not installed.
- opened(3) indicates the circuit breaker is opened.
- closed(4) indicates the circuit breaker is closed."
- ::= { upsDiagSubSysDCCircuitBreakerEntry 3 }
-
- upsDiagSubSysSystemPowerSupplyTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of System Power Supplies attached to the UPS."
- ::= { upsDiagnosticSubsystem 13 }
- upsDiagSubSysSystemPowerSupplyTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsDiagSubSysSystemPowerSupplyEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for diagnostics of individual System Power Supplies."
- ::= { upsDiagnosticSubsystem 14 }
- upsDiagSubSysSystemPowerSupplyEntry OBJECT-TYPE
- SYNTAX UpsDiagSubSysSystemPowerSupplyEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The diagnostics of a System Power Supply."
- INDEX { upsDiagSubSysSystemPowerSupplyIndex}
- ::= { upsDiagSubSysSystemPowerSupplyTable 1 }
- UpsDiagSubSysSystemPowerSupplyEntry ::=
- SEQUENCE {
- upsDiagSubSysSystemPowerSupplyFrameIndex INTEGER,
- upsDiagSubSysSystemPowerSupplyIndex INTEGER,
- upsDiagSubSysSystemPowerSupplyStatus INTEGER,
- upsDiagSubSysSystemPowerSupplyFirmwareRev DisplayString,
- upsDiagSubSysSystemPowerSupplyHardwareRev DisplayString,
- upsDiagSubSysSystemPowerSupplySerialNum DisplayString,
- upsDiagSubSysSystemPowerSupplyManufactureDate DisplayString
- }
- upsDiagSubSysSystemPowerSupplyFrameIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The frame index entry."
- ::= { upsDiagSubSysSystemPowerSupplyEntry 1 }
-
- upsDiagSubSysSystemPowerSupplyIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index of a System Power Supply."
- ::= { upsDiagSubSysSystemPowerSupplyEntry 2 }
-
- upsDiagSubSysSystemPowerSupplyStatus OBJECT-TYPE
- SYNTAX INTEGER {
- unknown (1),
- notInstalled (2),
- offOk (3),
- onOk (4),
- offFail (5),
- onFail (6),
- lostComm (7)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The status of the System Power Supply.
- unknown(1) indicates the device status is unknown.
- notInstalled(2) indicates the device is not installed.
- offOk(3) indicates the device status is off and OK.
- onOk(4) indicates the device status is on and OK.
- offFail(5) indicates the device status is off and failed.
- onFail(6) indicates the device status is on and failed.
- lostComm(7) indicates the device has lost communication."
- ::= { upsDiagSubSysSystemPowerSupplyEntry 3 }
-
- upsDiagSubSysSystemPowerSupplyFirmwareRev OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The firmware revision of the System Power Supply monitor card."
- ::= { upsDiagSubSysSystemPowerSupplyEntry 4 }
-
- upsDiagSubSysSystemPowerSupplyHardwareRev OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The hardware revision of the System Power Supply monitor card."
- ::= { upsDiagSubSysSystemPowerSupplyEntry 5 }
-
- upsDiagSubSysSystemPowerSupplySerialNum OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The serial number of the System Power Supply monitor card."
- ::= { upsDiagSubSysSystemPowerSupplyEntry 6 }
-
- upsDiagSubSysSystemPowerSupplyManufactureDate OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The date of the manufacture for the System Power Supply monitor card."
- ::= { upsDiagSubSysSystemPowerSupplyEntry 7 }
- upsDiagSubSysXRCommunicationCardTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of XR Communication Cards attached to the UPS."
- ::= { upsDiagnosticSubsystem 15 }
- upsDiagSubSysXRCommunicationCardTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsDiagSubSysXRCommunicationCardEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for diagnostics of individual XR Communication Cards."
- ::= { upsDiagnosticSubsystem 16 }
- upsDiagSubSysXRCommunicationCardEntry OBJECT-TYPE
- SYNTAX UpsDiagSubSysXRCommunicationCardEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The diagnostics of an XR Communication Card."
- INDEX { upsDiagSubSysXRCommunicationCardIndex}
- ::= { upsDiagSubSysXRCommunicationCardTable 1 }
- UpsDiagSubSysXRCommunicationCardEntry ::=
- SEQUENCE {
- upsDiagSubSysXRCommunicationCardFrameIndex INTEGER,
- upsDiagSubSysXRCommunicationCardIndex INTEGER,
- upsDiagSubSysXRCommunicationCardStatus INTEGER,
- upsDiagSubSysXRCommunicationCardFirmwareRev DisplayString,
- upsDiagSubSysXRCommunicationCardSerialNum DisplayString
-
- }
- upsDiagSubSysXRCommunicationCardFrameIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The frame index entry."
- ::= { upsDiagSubSysXRCommunicationCardEntry 1 }
-
- upsDiagSubSysXRCommunicationCardIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index of an XR Communication Card."
- ::= { upsDiagSubSysXRCommunicationCardEntry 2 }
-
- upsDiagSubSysXRCommunicationCardStatus OBJECT-TYPE
- SYNTAX INTEGER {
- unknown (1),
- notInstalled (2),
- offOk (3),
- onOk (4),
- offFail (5),
- onFail (6),
- lostComm (7)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The status of the XR Communication Card.
- unknown(1) indicates the device status is unknown.
- notInstalled(2) indicates the device is not installed.
- offOk(3) indicates the device status is off and OK.
- onOk(4) indicates the device status is on and OK.
- offFail(5) indicates the device status is off and failed.
- onFail(6) indicates the device status is on and failed.
- lostComm(7) indicates the device has lost communication."
- ::= { upsDiagSubSysXRCommunicationCardEntry 3 }
- upsDiagSubSysXRCommunicationCardFirmwareRev OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The firmware revision of the XR Communication card."
- ::= { upsDiagSubSysXRCommunicationCardEntry 4 }
-
- upsDiagSubSysXRCommunicationCardSerialNum OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The serial number of the XR Communication card."
- ::= { upsDiagSubSysXRCommunicationCardEntry 5 }
- upsDiagSubSysExternalPowerFrameBoardTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of External Power Frame Boards attached to the UPS."
- ::= { upsDiagnosticSubsystem 17 }
- upsDiagSubSysExternalPowerFrameBoardTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsDiagSubSysExternalPowerFrameBoardEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for diagnostics of individual External Power Frame Boards."
- ::= { upsDiagnosticSubsystem 18 }
- upsDiagSubSysExternalPowerFrameBoardEntry OBJECT-TYPE
- SYNTAX UpsDiagSubSysExternalPowerFrameBoardEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The diagnostics of an External Power Frame Board."
- INDEX { upsDiagSubSysExternalPowerFrameBoardIndex}
- ::= { upsDiagSubSysExternalPowerFrameBoardTable 1 }
- UpsDiagSubSysExternalPowerFrameBoardEntry ::=
- SEQUENCE {
- upsDiagSubSysExternalPowerFrameBoardFrameIndex INTEGER,
- upsDiagSubSysExternalPowerFrameBoardIndex INTEGER,
- upsDiagSubSysExternalPowerFrameBoardStatus INTEGER
- }
- upsDiagSubSysExternalPowerFrameBoardFrameIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The frame index entry."
- ::= { upsDiagSubSysExternalPowerFrameBoardEntry 1 }
-
- upsDiagSubSysExternalPowerFrameBoardIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index of an External Power Frame Board."
- ::= { upsDiagSubSysExternalPowerFrameBoardEntry 2 }
-
- upsDiagSubSysExternalPowerFrameBoardStatus OBJECT-TYPE
- SYNTAX INTEGER {
- unknown (1),
- notInstalled (2),
- offOk (3),
- onOk (4),
- offFail (5),
- onFail (6),
- lostComm (7)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The status of the External Power Frame Board.
- unknown(1) indicates the device status is unknown.
- notInstalled(2) indicates the device is not installed.
- offOk(3) indicates the device status is off and OK.
- onOk(4) indicates the device status is on and OK.
- offFail(5) indicates the device status is off and failed.
- onFail(6) indicates the device status is on and failed.
- lostComm(7) indicates the device has lost communication."
- ::= { upsDiagSubSysExternalPowerFrameBoardEntry 3 }
-
- upsDiagSubSysChargerTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of Chargers attached to the UPS."
- ::= { upsDiagnosticSubsystem 19 }
- upsDiagSubSysChargerTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsDiagSubSysChargerEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for diagnostics of individual chargers."
- ::= { upsDiagnosticSubsystem 20 }
- upsDiagSubSysChargerEntry OBJECT-TYPE
- SYNTAX UpsDiagSubSysChargerEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The diagnostics of a charger."
- INDEX { upsDiagSubSysChargerIndex}
- ::= { upsDiagSubSysChargerTable 1 }
- UpsDiagSubSysChargerEntry ::=
- SEQUENCE {
- upsDiagSubSysChargerFrameIndex INTEGER,
- upsDiagSubSysChargerIndex INTEGER,
- upsDiagSubSysChargerStatus INTEGER
- }
- upsDiagSubSysChargerFrameIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The frame index entry."
- ::= { upsDiagSubSysChargerEntry 1 }
-
- upsDiagSubSysChargerIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index of a charger."
- ::= { upsDiagSubSysChargerEntry 2 }
-
- upsDiagSubSysChargerStatus OBJECT-TYPE
- SYNTAX INTEGER {
- unknown (1),
- notInstalled (2),
- offOk (3),
- onOk (4),
- offFail (5),
- onFail (6),
- lostComm (7)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The status of the Charger.
- unknown(1) indicates the device status is unknown.
- notInstalled(2) indicates the device is not installed.
- offOk(3) indicates the device status is off and OK.
- onOk(4) indicates the device status is on and OK.
- offFail(5) indicates the device status is off and failed.
- onFail(6) indicates the device status is on and failed.
- lostComm(7) indicates the device has lost communication."
- ::= { upsDiagSubSysChargerEntry 3 }
-
- upsDiagSubSysInverterTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of Inverters attached to the UPS."
- ::= { upsDiagnosticSubsystem 21 }
- upsDiagSubSysInverterTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsDiagSubSysInverterEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for diagnostics of individual Inverters."
- ::= { upsDiagnosticSubsystem 22 }
- upsDiagSubSysInverterEntry OBJECT-TYPE
- SYNTAX UpsDiagSubSysInverterEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The diagnostics of an Inverter."
- INDEX { upsDiagSubSysInverterIndex}
- ::= { upsDiagSubSysInverterTable 1 }
- UpsDiagSubSysInverterEntry ::=
- SEQUENCE {
- upsDiagSubSysInverterFrameIndex INTEGER,
- upsDiagSubSysInverterIndex INTEGER,
- upsDiagSubSysInverterStatus INTEGER,
- upsDiagSubSysInverterFirmwareRev DisplayString,
- upsDiagSubSysInverterHardwareRev DisplayString,
- upsDiagSubSysInverterSerialNum DisplayString,
- upsDiagSubSysInverterManufactureDate DisplayString
- }
- upsDiagSubSysInverterFrameIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The frame index entry."
- ::= { upsDiagSubSysInverterEntry 1 }
-
- upsDiagSubSysInverterIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index of an Inverter."
- ::= { upsDiagSubSysInverterEntry 2 }
-
- upsDiagSubSysInverterStatus OBJECT-TYPE
- SYNTAX INTEGER {
- unknown (1),
- notInstalled (2),
- offOk (3),
- onOk (4),
- offFail (5),
- onFail (6),
- lostComm (7)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The status of the Inverter.
- unknown(1) indicates the device status is unknown.
- notInstalled(2) indicates the device is not installed.
- offOk(3) indicates the device status is off and OK.
- onOk(4) indicates the device status is on and OK.
- offFail(5) indicates the device status is off and failed.
- onFail(6) indicates the device status is on and failed.
- lostComm(7) indicates the device has lost communication."
- ::= { upsDiagSubSysInverterEntry 3 }
-
- upsDiagSubSysInverterFirmwareRev OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The firmware revision of the Inverter monitor."
- ::= { upsDiagSubSysInverterEntry 4 }
-
- upsDiagSubSysInverterHardwareRev OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The hardware revision of the Inverter monitor."
- ::= { upsDiagSubSysInverterEntry 5 }
-
- upsDiagSubSysInverterSerialNum OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The serial number of the Inverter monitor."
- ::= { upsDiagSubSysInverterEntry 6 }
-
- upsDiagSubSysInverterManufactureDate OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The date of manufacture for the Inverter monitor."
- ::= { upsDiagSubSysInverterEntry 7 }
- upsDiagSubSysPowerFactorCorrectionTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of Power Factor Correction devices attached to the UPS."
- ::= { upsDiagnosticSubsystem 23 }
- upsDiagSubSysPowerFactorCorrectionTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsDiagSubSysPowerFactorCorrectionEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for diagnostics of individual PowerFactorCorrections."
- ::= { upsDiagnosticSubsystem 24 }
- upsDiagSubSysPowerFactorCorrectionEntry OBJECT-TYPE
- SYNTAX UpsDiagSubSysPowerFactorCorrectionEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The diagnostics of a Power Factor Correction."
- INDEX { upsDiagSubSysPowerFactorCorrectionIndex}
- ::= { upsDiagSubSysPowerFactorCorrectionTable 1 }
- UpsDiagSubSysPowerFactorCorrectionEntry ::=
- SEQUENCE {
- upsDiagSubSysPowerFactorCorrectionFrameIndex INTEGER,
- upsDiagSubSysPowerFactorCorrectionIndex INTEGER,
- upsDiagSubSysPowerFactorCorrectionStatus INTEGER,
- upsDiagSubSysPowerFactorCorrectionFirmwareRev DisplayString,
- upsDiagSubSysPowerFactorCorrectionHardwareRev DisplayString,
- upsDiagSubSysPowerFactorCorrectionSerialNum DisplayString,
- upsDiagSubSysPowerFactorCorrectionManufactureDate DisplayString
- }
- upsDiagSubSysPowerFactorCorrectionFrameIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The frame index entry."
- ::= { upsDiagSubSysPowerFactorCorrectionEntry 1 }
-
- upsDiagSubSysPowerFactorCorrectionIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index of a Power Factor Correction."
- ::= { upsDiagSubSysPowerFactorCorrectionEntry 2 }
-
- upsDiagSubSysPowerFactorCorrectionStatus OBJECT-TYPE
- SYNTAX INTEGER {
- unknown (1),
- notInstalled (2),
- offOk (3),
- onOk (4),
- offFail (5),
- onFail (6),
- lostComm (7)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The status of the Power Factor Correction.
- unknown(1) indicates the device status is unknown.
- notInstalled(2) indicates the device is not installed.
- offOk(3) indicates the device status is off and OK.
- onOk(4) indicates the device status is on and OK.
- offFail(5) indicates the device status is off and failed.
- onFail(6) indicates the device status is on and failed.
- lostComm(7) indicates the device has lost communication."
- ::= { upsDiagSubSysPowerFactorCorrectionEntry 3 }
-
- upsDiagSubSysPowerFactorCorrectionFirmwareRev OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The firmware revision of the Power Factor Correction monitor."
- ::= { upsDiagSubSysPowerFactorCorrectionEntry 4 }
-
- upsDiagSubSysPowerFactorCorrectionHardwareRev OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The hardware revision of the Power Factor Correction monitor."
- ::= { upsDiagSubSysPowerFactorCorrectionEntry 5 }
-
- upsDiagSubSysPowerFactorCorrectionSerialNum OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The serial number of the Power Factor Correction monitor."
- ::= { upsDiagSubSysPowerFactorCorrectionEntry 6 }
-
- upsDiagSubSysPowerFactorCorrectionManufactureDate OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The date of the manufacture for the Power Factor Correction monitor."
- ::= { upsDiagSubSysPowerFactorCorrectionEntry 7 }
- upsDiagSubSysNetworkComCardTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of Network Communication Cards attached to the UPS."
- ::= { upsDiagnosticSubsystem 25 }
- upsDiagSubSysNetworkComCardTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsDiagSubSysNetworkComCardEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting diagnostics information of an individual Network Communication Card."
- ::= { upsDiagnosticSubsystem 26 }
- upsDiagSubSysNetworkComCardEntry OBJECT-TYPE
- SYNTAX UpsDiagSubSysNetworkComCardEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The diagnostics of a Network Communication Card."
- INDEX { upsDiagSubSysNetworkComCardIndex}
- ::= { upsDiagSubSysNetworkComCardTable 1 }
- UpsDiagSubSysNetworkComCardEntry ::=
- SEQUENCE {
- upsDiagSubSysNetworkComCardIndex INTEGER,
- upsDiagSubSysNetworkComCardModelNumber DisplayString,
- upsDiagSubSysNetworkComCardSerialNumber DisplayString,
- upsDiagSubSysNetworkComCardDateOfManufacture DisplayString,
- upsDiagSubSysNetworkComCardHardwareRev DisplayString,
- upsDiagSubSysNetworkComCardFirmwareAppRev DisplayString,
- upsDiagSubSysNetworkComCardFirmwareAppOSRev DisplayString
- }
- upsDiagSubSysNetworkComCardIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The UPS network and display interface communication card index entry."
- ::= { upsDiagSubSysNetworkComCardEntry 1 }
- upsDiagSubSysNetworkComCardModelNumber OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the model number of the UPS network and display interface communication card.
- This value is set at the factory."
- ::= { upsDiagSubSysNetworkComCardEntry 2 }
- upsDiagSubSysNetworkComCardSerialNumber OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the serial number of the UPS network and display interface communication card.
- This value is set at the factory."
- ::= { upsDiagSubSysNetworkComCardEntry 3 }
- upsDiagSubSysNetworkComCardDateOfManufacture OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The date when the UPS network and display interface communication card was manufactured in mm/dd/yyyy format.
- This value is set at the factory."
- ::= { upsDiagSubSysNetworkComCardEntry 4 }
- upsDiagSubSysNetworkComCardHardwareRev OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The hardware revision of the UPS network and display interface communication card.
- This value is set at the factory."
- ::= { upsDiagSubSysNetworkComCardEntry 5 }
- upsDiagSubSysNetworkComCardFirmwareAppRev OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "An ID string identifying the application firmware revision of the
- UPS network and display interface communication card."
- ::= { upsDiagSubSysNetworkComCardEntry 6 }
- upsDiagSubSysNetworkComCardFirmwareAppOSRev OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "An ID string identifying the application operating system firmware revision of the
- UPS network and display interface communication card."
- ::= { upsDiagSubSysNetworkComCardEntry 7 }
- -- the upsDiagnosticExternalDevices group
- upsDiagSwitchGearStatus OBJECT-TYPE
- SYNTAX INTEGER {
- unknown (1),
- notInstalled (2),
- ok (3),
- fail (4),
- lostComm (5),
- overtemp (6)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The status of the Switch Gear.
- unknown(1) indicates the device status is unknown.
- notInstalled(2) indicates the device is not installed.
- ok(3) indicates the device status is OK.
- fail(4) indicates the device status has failed.
- lostComm(5) indicates the device has lost communication.
- overtemp(6) indicates the device has an over temperature condition."
- ::= { upsDiagSwitchGear 1 }
-
- upsDiagSwitchGearInputSwitchStatus OBJECT-TYPE
- SYNTAX INTEGER {
- unknown (1),
- notInstalled (2),
- opened (3),
- closed (4)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The status of the Switch Gear Input Switch.
- unknown(1) indicates the switch status is unknown.
- notInstalled(2) indicates the switch is not installed.
- opened(3) indicates the switch is opened.
- closed(4) indicates the switch is closed."
- ::= { upsDiagSwitchGear 2 }
- upsDiagSwitchGearOutputSwitchStatus OBJECT-TYPE
- SYNTAX INTEGER {
- unknown (1),
- notInstalled (2),
- opened (3),
- closed (4)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The status of the Switch Gear Output Switch.
- unknown(1) indicates the switch status is unknown.
- notInstalled(2) indicates the switch is not installed.
- opened(3) indicates the switch is opened.
- closed(4) indicates the switch is closed."
- ::= { upsDiagSwitchGear 3 }
- upsDiagSwitchGearBypassSwitchStatus OBJECT-TYPE
- SYNTAX INTEGER {
- unknown (1),
- notInstalled (2),
- opened (3),
- closed (4)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The status of the Switch Gear Bypass Switch.
- unknown(1) indicates the switch status is unknown.
- notInstalled(2) indicates the switch is not installed.
- opened(3) indicates the switch is opened.
- closed(4) indicates the switch is closed."
- ::= { upsDiagSwitchGear 4 }
- upsDiagSwitchGearBypassInputSwitchStatus OBJECT-TYPE
- SYNTAX INTEGER {
- unknown (1),
- notInstalled (2),
- opened (3),
- closed (4)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The status of the Switch Gear Bypass Input Switch.
- unknown(1) indicates the switch status is unknown.
- notInstalled(2) indicates the switch is not installed.
- opened(3) indicates the switch is opened.
- closed(4) indicates the switch is closed."
- ::= { upsDiagSwitchGear 5 }
- upsDiagSwitchGearBreakerTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of switchgear breakers attached to the UPS."
- ::= { upsDiagSwitchGear 6 }
- upsDiagSwitchGearBreakerTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsDiagSwitchGearBreakerEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Switchgear breaker table."
- ::= { upsDiagSwitchGear 7 }
- upsDiagSwitchGearBreakerEntry OBJECT-TYPE
- SYNTAX UpsDiagSwitchGearBreakerEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "A list of switchgear breakers."
- INDEX { switchgearBreakerIndex }
- ::= { upsDiagSwitchGearBreakerTable 1 }
- UpsDiagSwitchGearBreakerEntry ::=
- SEQUENCE {
- switchgearBreakerIndex
- INTEGER,
- switchgearBreakerPresent
- INTEGER,
- switchgearBreakerName
- DisplayString
- }
- switchgearBreakerIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index of the switchgear breaker."
- ::= { upsDiagSwitchGearBreakerEntry 1 }
- switchgearBreakerPresent OBJECT-TYPE
- SYNTAX INTEGER {
- notPresent (1),
- present (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Indicates if the switchgear breaker is present.
- notPresent (1) indicates that the breaker is not present.
- present (2) indicates that the breaker is present."
- ::= { upsDiagSwitchGearBreakerEntry 2 }
- switchgearBreakerName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The name of the switchgear breaker."
- ::= { upsDiagSwitchGearBreakerEntry 3 }
- upsDiagSubFeedBreakerTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of subfeed breakers attached to the UPS."
- ::= { upsDiagSwitchGear 8 }
- upsDiagSubFeedBreakerTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsDiagSubFeedBreakerEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Subfeed breaker table."
- ::= { upsDiagSwitchGear 9 }
- upsDiagSubFeedBreakerEntry OBJECT-TYPE
- SYNTAX UpsDiagSubFeedBreakerEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "A list of subfeed breakers."
- INDEX { subfeedBreakerIndex }
- ::= { upsDiagSubFeedBreakerTable 1 }
- UpsDiagSubFeedBreakerEntry ::=
- SEQUENCE {
- subfeedBreakerIndex
- INTEGER,
- subfeedBreakerPresent
- INTEGER,
- subfeedBreakerRating
- INTEGER,
- subfeedBreakerUpperAcceptPowerWarning
- INTEGER
- }
- subfeedBreakerIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index of the subfeed breakers."
- ::= { upsDiagSubFeedBreakerEntry 1 }
- subfeedBreakerPresent OBJECT-TYPE
- SYNTAX INTEGER {
- notPresent (1),
- present (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Indicates if the subfeed breaker is present.
- notPresent (1) indicates that the breaker is not present.
- present (2) indicates that the breaker is present."
- ::= { upsDiagSubFeedBreakerEntry 2 }
- subfeedBreakerRating OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The current rating of the installed subfeed breaker."
- ::= { upsDiagSubFeedBreakerEntry 3 }
- subfeedBreakerUpperAcceptPowerWarning OBJECT-TYPE
- SYNTAX INTEGER (0..100)
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The maximum acceptable load before warning is issued.
- Expressed as percent of the subfeed breaker rating."
- ::= { upsDiagSubFeedBreakerEntry 4 }
- upsDiagMCCBBoxStatus OBJECT-TYPE
- SYNTAX INTEGER {
- unknown (1),
- notInstalled (2),
- opened (3),
- closed (4)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The status of the MCCB Box (Molded Case Circuit Breaker Box) external device.
- unknown(1) indicates the device status is unknown.
- notInstalled(2) indicates the device is not installed.
- opened(3) indicates the circuit is opened.
- closed(4) indicates the circuit is closed."
- ::= { upsDiagMCCBBox 1 }
- upsDiagTransformerStatus OBJECT-TYPE
- SYNTAX INTEGER {
- unknown (1),
- notInstalled (2),
- ok (3),
- fail (4),
- lostComm (5),
- overtemp (6),
- opened (7),
- closed (8)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The status of the External Transformer.
- unknown(1) indicates the device status is unknown.
- notInstalled(2) indicates the device is not installed.
- ok(3) indicates the device status is OK.
- fail(4) indicates the device status has failed.
- lostComm(5) indicates the device has lost communication.
- overtemp(6) indicates the device has an over temperature condition.
- opened(7) indicates the circuit is opened.
- closed(8) indicates the circuit is closed."
- ::= { upsDiagTransformer 1 }
- -- the upsDiagnosticComBus group
- upsDiagComBusInternalMIMStatus OBJECT-TYPE
- SYNTAX INTEGER {
- unknown (1),
- notInstalled (2),
- ok (3),
- lostComm (4),
- rxFailure (5),
- txFailure (6)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The status of the internal MIM communication bus.
- unknown(1) indicates the device status is unknown.
- notInstalled(2) indicates the device is not installed.
- ok(3) indicates the device status is OK.
- lostComm(4) indicates the device has lost communication.
- rxFailure(5) indicates the device has a receive failure.
- txFailure(6) indicates the device has a transmit failure."
- ::= { upsDiagnosticComBus 1 }
- upsDiagComBusInternalRIMStatus OBJECT-TYPE
- SYNTAX INTEGER {
- unknown (1),
- notInstalled (2),
- ok (3),
- lostComm (4),
- rxFailure (5),
- txFailure (6)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The status of the internal RIM communication bus.
- unknown(1) indicates the device status is unknown.
- notInstalled(2) indicates the device is not installed.
- ok(3) indicates the device status is OK.
- lostComm(4) indicates the device has lost communication.
- rxFailure(5) indicates the device has a receive failure.
- txFailure(6) indicates the device has a transmit failure."
- ::= { upsDiagnosticComBus 2 }
- upsDiagComBusMIMtoRIMStatus OBJECT-TYPE
- SYNTAX INTEGER {
- unknown (1),
- notInstalled (2),
- ok (3),
- lostComm (4),
- rxFailure (5),
- txFailure (6)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The status of the MIM to RIM communication bus.
- unknown(1) indicates the device status is unknown.
- notInstalled(2) indicates the device is not installed.
- ok(3) indicates the device status is OK.
- lostComm(4) indicates the device has lost communication.
- rxFailure(5) indicates the device has a receive failure.
- txFailure(6) indicates the device has a transmit failure."
- ::= { upsDiagnosticComBus 3 }
- upsDiagComBusExternalMIMStatus OBJECT-TYPE
- SYNTAX INTEGER {
- unknown (1),
- notInstalled (2),
- ok (3),
- lostComm (4),
- rxFailure (5),
- txFailure (6)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The status of the external MIM communication bus.
- unknown(1) indicates the device status is unknown.
- notInstalled(2) indicates the device is not installed.
- ok(3) indicates the device status is OK.
- lostComm(4) indicates the device has lost communication.
- rxFailure(5) indicates the device has a receive failure.
- txFailure(6) indicates the device has a transmit failure."
- ::= { upsDiagnosticComBus 4 }
- upsDiagComBusExternalRIMStatus OBJECT-TYPE
- SYNTAX INTEGER {
- unknown (1),
- notInstalled (2),
- ok (3),
- lostComm (4),
- rxFailure (5),
- txFailure (6)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The status of the external RIM communication bus.
- unknown(1) indicates the device status is unknown.
- notInstalled(2) indicates the device is not installed.
- ok(3) indicates the device status is OK.
- lostComm(4) indicates the device has lost communication.
- rxFailure(5) indicates the device has a receive failure.
- txFailure(6) indicates the device has a transmit failure."
- ::= { upsDiagnosticComBus 5 }
- -- the upsParallelSystem group
- upsParallelSysLocalAddress OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Defines the UPS ID number in the parallel system."
- ::= { upsParallelSystem 1 }
- upsParallelSysRemoteAddress OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Defines the total number of UPSs in parallel."
- ::= { upsParallelSystem 2 }
- upsParallelSysRedundancy OBJECT-TYPE
- SYNTAX INTEGER {
- nplus0 (1),
- nplus1 (2),
- nplus2 (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The redundancy warning level for paralleled UPS
- nplus0 (1) indicates that there are no redundant units.
- nplus1 (2) indicates that there is one redundant unit.
- nplus2 (3) indicates that there are two redundant units."
- ::= { upsParallelSystem 3 }
- -- the upsPhysicalLayout group
- upsIOFrameLayoutPositionID OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Defines the position ID of UPS frame."
- ::= { upsPhysicalLayout 1 }
- upsBottomFeedFrameLayoutPositionID OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Defines the position ID of bottom feed frame."
- ::= { upsPhysicalLayout 2 }
- upsSwitchGearLayoutPositionID OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Defines the position ID of switchgear."
- ::= { upsPhysicalLayout 3 }
- -- the upsBatteryFrameLayoutTable subgroup
- upsBatteryFrameLayoutTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of battery frames."
- ::= { upsPhysicalLayout 4 }
- upsBatteryFrameLayoutTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsBatteryFrameLayoutEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Battery frame layout position ID table."
- ::= { upsPhysicalLayout 5 }
- upsBatteryFrameLayoutEntry OBJECT-TYPE
- SYNTAX UpsBatteryFrameLayoutEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "A list of layout position IDs of battery frames."
- INDEX { batteryFrameIndex }
- ::= { upsBatteryFrameLayoutTable 1 }
- UpsBatteryFrameLayoutEntry ::=
- SEQUENCE {
- batteryFrameIndex
- INTEGER,
- batteryFramePositionID
- INTEGER
- }
- batteryFrameIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index of the battery frame."
- ::= { upsBatteryFrameLayoutEntry 1 }
- batteryFramePositionID OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Defines the position ID of each of the battery frames in the row."
- ::= { upsBatteryFrameLayoutEntry 2 }
- -- the upsSideCarFrameLayoutTable subgroup
- upsSideCarFrameLayoutTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of sidecar frames."
- ::= { upsPhysicalLayout 6 }
- upsSideCarFrameLayoutTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsSideCarFrameLayoutEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Sidecar frame layout position ID table."
- ::= { upsPhysicalLayout 7 }
- upsSideCarFrameLayoutEntry OBJECT-TYPE
- SYNTAX UpsSideCarFrameLayoutEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "A list of sidecar frame layout position IDs."
- INDEX { sideCarFrameIndex }
- ::= { upsSideCarFrameLayoutTable 1 }
- UpsSideCarFrameLayoutEntry ::=
- SEQUENCE {
- sideCarFrameIndex
- INTEGER,
- sideCarFramePositionID
- INTEGER
- }
- sideCarFrameIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index of the sidecar frame."
- ::= { upsSideCarFrameLayoutEntry 1 }
- sideCarFramePositionID OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Defines the position ID of each of the sidecar frames in the row."
- ::= { upsSideCarFrameLayoutEntry 2 }
- -- the upsPowerFrameLayoutTable subgroup
- upsPowerFrameLayoutTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of power frames."
- ::= { upsPhysicalLayout 8 }
- upsPowerFrameLayoutTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsPowerFrameLayoutEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Power frame layout position ID table."
- ::= { upsPhysicalLayout 9 }
- upsPowerFrameLayoutEntry OBJECT-TYPE
- SYNTAX UpsPowerFrameLayoutEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "A list of power frame layout position IDs."
- INDEX { powerFrameIndex }
- ::= { upsPowerFrameLayoutTable 1 }
- UpsPowerFrameLayoutEntry ::=
- SEQUENCE {
- powerFrameIndex
- INTEGER,
- powerFramePositionID
- INTEGER
- }
- powerFrameIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index of the power frame."
- ::= { upsPowerFrameLayoutEntry 1 }
- powerFramePositionID OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Defines the position ID of each of the power frames in the row."
- ::= { upsPowerFrameLayoutEntry 2 }
- -- the upsIntegratedATS group
- upsIntegratedATSSelectedSource OBJECT-TYPE
- SYNTAX INTEGER {
- noSourceSelected (1),
- unknown (2),
- sourceA (3),
- sourceB (4)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The source which is currently selected by the ATS to supply the UPS."
- ::= { upsIntegratedATS 1 }
- upsIntegratedATSPreferredSource OBJECT-TYPE
- SYNTAX INTEGER {
- upsIntegratedATSNoSourcePreference (1),
- upsIntegratedATSPreferSourceA (2),
- upsIntegratedATSPreferSourceB (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The preferred source of power when both sources are OK."
- ::= { upsIntegratedATS 2 }
- upsIntegratedATSUpsReturnStaggering OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "This is a delay factor applied to the retransfer of this UPS with integrated ATS.
- When mulitple UPSes are in use from a single source, each UPS can have a unique delay value,
- which will reduce inrush by preventing all UPSes from transferring at the same time."
- ::= { upsIntegratedATS 3 }
- upsIntegratedATSSourceTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of input sources for this integrated ATS."
- ::= { upsIntegratedATS 4 }
- upsIntegratedATSSourceTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsIntegratedATSSourceEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting status and settings for the ATS input sources.
- The number of entries is contained in the upsIntegratedATSSourceTableSize OID."
- ::= { upsIntegratedATS 5 }
- upsIntegratedATSSourceEntry OBJECT-TYPE
- SYNTAX UpsIntegratedATSSourceEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The input source status to get."
- INDEX { upsIntegratedATSSourceIndex}
- ::= { upsIntegratedATSSourceTable 1 }
- UpsIntegratedATSSourceEntry ::=
- SEQUENCE {
- upsIntegratedATSSourceIndex INTEGER,
- upsIntegratedATSSourceName DisplayString,
- upsIntegratedATSSourceStatus INTEGER,
- upsIntegratedATSLineFailDelay INTEGER,
- upsIntegratedATSLineStabilityDelay INTEGER
- }
- upsIntegratedATSSourceIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the input source entry."
- ::= { upsIntegratedATSSourceEntry 1 }
- upsIntegratedATSSourceName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The name of the input source. This OID is provided
- for informational purposes only."
- ::= { upsIntegratedATSSourceEntry 2 }
- upsIntegratedATSSourceStatus OBJECT-TYPE
- SYNTAX INTEGER {
- upsIntegratedATSSourceGood (1),
- upsIntegratedATSSourceBad (2),
- upsIntegratedATSSourceUnknown (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this variable will return the input source status."
- ::= { upsIntegratedATSSourceEntry 3 }
- upsIntegratedATSLineFailDelay OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The delay between a selected input source becoming bad, and the ATS switching away from that source.
- This delay is used to make sure that the line has truly failed before the ATS will be switched.
- Specified in seconds."
- ::= { upsIntegratedATSSourceEntry 4 }
- upsIntegratedATSLineStabilityDelay OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The delay between an unselected input source becoming good, and the ATS switching to that source.
- This delay is used to make sure that the line has truly returned before the ATS will be switched.
- Specified in seconds."
- ::= { upsIntegratedATSSourceEntry 5 }
- -- the serialPort2Config group
- serialPort2Mode OBJECT-TYPE
- SYNTAX INTEGER {
- localConsole(1),
- passthrough(2)
- }
- ACCESS read-write
- STATUS obsolete
- DESCRIPTION
- "Setting this variable to passthrough will enable mini's port2
- behave like a UPS port. Choosing localConsole will enable the port
- to be used as local console."
- ::= { serialPort2Config 1 }
- -- the serialPort2Control group
- setPulseOnTXD OBJECT-TYPE
- SYNTAX INTEGER {
- noSetPulseOnTXD(1),
- setPulseOnTXD(2),
- setTXDLow(3),
- setTXDHigh(4)
- }
- ACCESS read-write
- STATUS obsolete
- DESCRIPTION
- "Setting this variable to setPulseOnTXD(2)
- causes adapter to generate a PULSE on TXD pin of serial port 2.
- The duration in the prototype implementation will be 1 second.
- Setting this value to noSetPulseOnTXD(1) has no
- effect.
-
- The value noSetPulseOnTXD(1) will always be returned
- when the variable is read.
- Setting this value to setTXDLow(3), or setTXDHigh(4) will keep TXD
- always low or high respectively."
- ::= { serialPort2Control 1 }
- -- the sPDUIdent group
- sPDUIdentHardwareRev OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The hardware revision of the PDU. This value
- is set at the factory."
- ::= { sPDUIdent 1 }
- sPDUIdentFirmwareRev OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "An 8 byte ID string identifying the PDU firmware revision.
- This value is set at the factory."
- ::= { sPDUIdent 2 }
- sPDUIdentDateOfManufacture OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The date when the PDU was manufactured in mm/dd/yy format.
- This value is set at the factory. The year 2000 will be
- represented by 00."
- ::= { sPDUIdent 3 }
-
- sPDUIdentModelNumber OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A 10-character string identifying the model number of
- the PDU internal. This value is set at the factory."
- ::= { sPDUIdent 4 }
- sPDUIdentSerialNumber OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A 12-character string identifying the serial number of
- the PDU internal microprocessor. This value is set at
- the factory."
- ::= { sPDUIdent 5 }
-
- -- the sPDUMasterControl group
- sPDUMasterControlSwitch OBJECT-TYPE
- SYNTAX INTEGER {
- turnAllOnNow (1),
- turnAllOnSequence (2),
- turnAllOffNow (3),
- rebootAllNow (4),
- rebootAllSequence (5),
- noCommand (6),
- turnAllOffSequence (7)
- }
-
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Setting this OID to turnAllOnNow (1) will turn all outlets
- on immediately.
-
- Setting this OID to turnAllOnSequence (2) will turn all outlets
- on as defined by each outlet's sPDUOutletPowerOnTime OID value.
-
- Setting this OID to turnAllOff (3) will turn all outlets
- off immediately.
-
- Setting this OID to rebootAllNow (4) will reboot all outlets
- immediately.
-
- For MasterSwitch firmware version 1.X, setting this OID to
- rebootAllSequence (5) reboots all outlets, with power returned
- to the outlets in the sequence defined by each outlet's
- sPDUOutletPowerOnTime OID value.
-
- For MasterSwitch firmware version 2.X, setting this OID to
- rebootAllSequence (5) will cause a turnAllOffSequence to be performed.
- Once all outlets are off, the MasterSwitch will then delay the
- sPDUMasterConfigReboot OID time, and then perform a turnAllOnSequence.
- For MasterSwitch firmware version 2.X, setting this OID to
- turnAllOffSequence (7) will turn all outlets off as defined by
- each outlet's sPDUOutletPowerOffTime OID value.
-
- For MasterSwitch firmware version 1.X, setting this OID to
- turnAllOffSequence (7) will have no effect.
- Getting this OID will return the noCommand (6) value."
-
- ::= { sPDUMasterControl 1 }
-
- sPDUMasterState OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will cause the status of all outlets to be
- returned. This OID is provided for informational purposes only.
- To change the outlet state, the user should use the sPDUOutletCtl
- OID in the sPDUOutletControlTable.
- The format of the data returned is a character string consisting
- of the word 'On' if the outlet is on or 'Off' if the outlet is
- off. At least one space will delimit each outlet entry in the
- string.
-
- If the outlet states are unknown, the character string 'Unknown'
- will be returned. This signifies that there is an inconsistency
- in the PDU. In the rare case that this should happen, the user
- is advised to shut down all equipment powered by the PDU and
- then cycle the PDU's power. This will put the PDU in a consistent
- state."
-
- ::= { sPDUMasterControl 2 }
- sPDUMasterPending OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will cause the command pending status of all outlets to be returned.
- The format of the data returned is a character string consisting
- of the word 'Yes' if a command is pending for the outlet or 'No'
- if there is no command pending for the outlet. At least one
- space will delimit each outlet entry in the string.
-
- If the pending states are unknown, the character string 'Unknown'
- will be returned. This signifies that there is an inconsistency
- in the PDU. In the rare case that this should happen, the user
- is advised to shut down all equipment powered by the PDU and then
- cycle the PDU's power. This will put the PDU in a consistent state."
- ::= { sPDUMasterControl 3 }
- -- the sPDUMasterConfig group
-
- sPDUMasterConfigPowerOn OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- " The amount of delay, in seconds, between when
- power is provided to the PDU and when the PDU
- provides basic master power to the outlets.
-
- Allowed values are:
- -1 never apply power automatically.
- 0 apply power immediately.
- 15 apply power in 15 seconds.
- 30 apply power in 30 seconds.
- 45 apply power in 45 seconds.
- 60 apply power in 60 seconds (1 minute).
- 120 apply power in 120 seconds (2 minutes).
- 300 apply power in 300 seconds (5 minutes).
-
- If a value other than a supported value is provided in a
- set request, the PDU interprets it as the next lower
- acceptable value. If the provided value is lower than
- the lowest acceptable value, the lowest acceptable
- value is used."
-
- ::= { sPDUMasterConfig 1 }
- sPDUMasterConfigReboot OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "During a reboot sequence, power is turned off and then
- back on. This OID defines the amount of time to wait,
- in seconds, after turning the power off, at the start
- of the sequence, before turning power back on, at the
- end of the reboot sequence.
-
- Allowed values are:
-
- 5 wait 5 seconds between off/on.
- 10 wait 10 seconds between off/on.
- 15 wait 15 seconds between off/on.
- 20 wait 20 seconds between off/on.
- 30 wait 30 seconds between off/on.
- 45 wait 45 seconds between off/on.
- 60 wait 60 seconds (1 minute) between off/on.
-
- If a value other than a supported value is provided in a
- set request, the PDU interprets it as the next lower
- acceptable value. If the provided value is lower than
- the lowest acceptable value, the lowest acceptable
- value is used.
- This OID is read-only for the MasterSwitch version 2.X and is the
- maximum sPDUOutletRebootDuration OID of the individual outlets."
-
- ::= { sPDUMasterConfig 2 }
-
- sPDUMasterConfigPDUName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The name of the PDU."
- ::= { sPDUMasterConfig 3 }
- -- the sPDUOutletControl group
- sPDUOutletControlTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of outlets for the PDU."
- ::= { sPDUOutletControl 1 }
-
- sPDUOutletControlTable OBJECT-TYPE
- SYNTAX SEQUENCE OF SPDUOutletControlEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for control of individual outlet switches. The number of
- entries is contained in the sPDUOutletControlTableSize OID."
- ::= { sPDUOutletControl 2 }
- sPDUOutletControlEntry OBJECT-TYPE
- SYNTAX SPDUOutletControlEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The outlets to control."
- INDEX { sPDUOutletControlIndex}
- ::= { sPDUOutletControlTable 1 }
- SPDUOutletControlEntry ::=
- SEQUENCE {
- sPDUOutletControlIndex INTEGER,
- sPDUOutletPending INTEGER,
- sPDUOutletCtl INTEGER,
- sPDUOutletCtlName DisplayString
- }
- sPDUOutletControlIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the outlet entry."
- ::= { sPDUOutletControlEntry 1 }
-
- sPDUOutletPending OBJECT-TYPE
- SYNTAX INTEGER{
- commandPending (1),
- noCommandPending (2),
- commandPendingUnknown (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Reports whether the current outlet has a pending command.
-
- If the commandPendingUnknown (3) value is returned, all
- devices powered by the PDU should be shut down. The PDU's
- power should then be cycled to clear this condition."
-
- ::= { sPDUOutletControlEntry 2 }
-
- sPDUOutletCtl OBJECT-TYPE
- SYNTAX INTEGER {
- outletOn (1),
- outletOff (2),
- outletReboot (3),
- outletUnknown (4),
- outletOnWithDelay (5),
- outletOffWithDelay (6),
- outletRebootWithDelay (7)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Getting this variable will return the outlet state. If
- the outlet is on, the outletOn (1) value will be returned.
- If the outlet is off, the outletOff (2) value will be
- returned.
-
- If the state of the outlet cannot be determined, the
- outletUnknown (4) value will be returned. If the
- outletUnknown condition should occur, all devices
- powered by the PDU should be shut down. The PDU's power
- should then be cycled to clear this condition.
-
- Setting this variable to outletOn (1) will turn the outlet on.
-
- Setting this variable to outletOff (2) will turn the outlet off.
- Setting this variable to outletReboot (3) will reboot the outlet.
-
- Setting this variable to outletOnWithDelay (5) will turn the outlet on
- after the sPDUOutletPowerOnTime OID has elapsed. This option is not
- valid for MasterSwitch firmware version 1.X.
- Setting this variable to outletOffWithDelay (6) will turn the outlet off
- after the sPDUOutletPowerOffTime OID has elapsed. This option is not valid
- for MasterSwitch firmware version 1.X.
- Setting this variable to outletRebootWithDelay (7) will turn the outlet off
- after the sPDUOutletPowerOffTime OID has elapsed, wait the sPDUOutletRebootDuration
- OID time, then turn the outlet back on.
- This option is not valid for MasterSwitch firmware version 1.X."
- ::= { sPDUOutletControlEntry 3 }
- sPDUOutletCtlName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The name of the outlet. Maximum size is 20 characters.
- This OID is provided for informational purposes only.
- This value is set by the sPDUOutletName OID."
-
- ::= { sPDUOutletControlEntry 4 }
- -- the sPDUOutletConfig group
- sPDUOutletConfigTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of outlets for the PDU."
- ::= { sPDUOutletConfig 1 }
- sPDUOutletConfigTable OBJECT-TYPE
- SYNTAX SEQUENCE OF SPDUOutletConfigEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The list of outlets to configure. The number of
- entries is defined by the sPDUOutletConfigTableSize
- OID."
-
- ::= { sPDUOutletConfig 2 }
- sPDUOutletConfigEntry OBJECT-TYPE
- SYNTAX SPDUOutletConfigEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The outlets to control."
- INDEX { sPDUOutletConfigIndex}
- ::= { sPDUOutletConfigTable 1 }
- SPDUOutletConfigEntry ::=
- SEQUENCE {
- sPDUOutletConfigIndex INTEGER,
- sPDUOutletPowerOnTime INTEGER,
- sPDUOutletName DisplayString,
- sPDUOutletPowerOffTime INTEGER,
- sPDUOutletRebootDuration INTEGER
- }
- sPDUOutletConfigIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the outlet entry."
- ::= { sPDUOutletConfigEntry 1 }
-
- sPDUOutletPowerOnTime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The amount of time (in seconds) the outlet will delay
- powering on when the MasterSwitch is powered on.
-
- Allowed values are:
-
- -1 never power on automatically.
- 0 power on with the Master Switch.
- 15 power on 15 seconds after the MasterSwitch has power applied.
- 30 power on 30 seconds after the MasterSwitch has power applied.
- 45 power on 45 seconds after the MasterSwitch has power applied.
- 60 power on 60 seconds (1 minute) after the MasterSwitch has power applied.
- 120 power on 120 seconds (2 minutes) after the MasterSwitch has power applied.
- 300 power on 300 seconds (5 minutes) after the MasterSwitch has power applied.
-
- If a value other than a supported value is provided in a
- set request, the PDU interprets it as the next lower
- acceptable value. If the provided value is lower than
- the lowest acceptable value, the lowest acceptable
- value is used."
- ::= { sPDUOutletConfigEntry 2 }
-
- sPDUOutletName OBJECT-TYPE
- SYNTAX DisplayString ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The name of the outlet. Maximum size is 20 characters."
- ::= { sPDUOutletConfigEntry 3 }
- sPDUOutletPowerOffTime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The amount of time (in seconds) the outlet will delay
- powering off.
-
- Allowed values are:
-
- -1 never power off automatically.
- 0 power off with the MasterSwitch.
- 15 power off 15 seconds after being commanded.
- 30 power off 30 seconds after being commanded.
- 45 power off 45 seconds after being commanded.
- 60 power off 60 seconds (1 minute) after being commanded.
- 120 power off 120 seconds (2 minutes) after being commanded.
- 300 power off 300 seconds (5 minutes) after being commanded.
-
- If a value other than a supported value is provided in a
- set request, the PDU interprets it as the next lower
- acceptable value. If the provided value is lower than
- the lowest acceptable value, the lowest acceptable
- value is used.
-
- This OID is not available for MasterSwitch firmware version 1.X."
- ::= { sPDUOutletConfigEntry 4 }
- sPDUOutletRebootDuration OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "During a reboot sequence, power is turned off and then
- back on. This OID defines the amount of time to wait,
- in seconds, after turning the power off, at the start
- of the sequence, before turning power back on, at the
- end of the reboot sequence.
-
- Allowed values are:
-
- 5 wait 5 seconds between off/on.
- 10 wait 10 seconds between off/on.
- 15 wait 15 seconds between off/on.
- 20 wait 20 seconds between off/on.
- 30 wait 30 seconds between off/on.
- 45 wait 45 seconds between off/on.
- 60 wait 60 seconds (1 minute) between off/on.
-
- If a value other than a supported value is provided in a
- set request, the PDU interprets it as the next lower
- acceptable value. If the provided value is lower than
- the lowest acceptable value, the lowest acceptable
- value is used.
- This OID is not available for MasterSwitch firmware version 1.X."
-
- ::= { sPDUOutletConfigEntry 5 }
- -- the sPDUIdentVM group
- sPDUIdentVMTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of MasterSwitch VMs controllable
- by this IP address."
- ::= { sPDUIdentVM 1 }
-
- sPDUIdentVMTable OBJECT-TYPE
- SYNTAX SEQUENCE OF SPDUIdentVMEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for query of the individual MasterSwitch VMs.
- The number of entries is contained in the
- sPDUIdentVMTableSize OID."
- ::= { sPDUIdentVM 2 }
- sPDUIdentVMEntry OBJECT-TYPE
- SYNTAX SPDUIdentVMEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The MasterSwitch VMs to query."
- INDEX { sPDUIdentVMIndex}
- ::= { sPDUIdentVMTable 1 }
- SPDUIdentVMEntry ::=
- SEQUENCE {
- sPDUIdentVMIndex INTEGER,
- sPDUIdentNameVM DisplayString,
- sPDUIdentHardwareRevVM DisplayString,
- sPDUIdentFirmwareRevVM DisplayString,
- sPDUIdentDateOfManufactureVM DisplayString,
- sPDUIdentModelNumberVM DisplayString,
- sPDUIdentSerialNumberVM DisplayString
- }
- sPDUIdentVMIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the MasterSwitch VM entry."
- ::= { sPDUIdentVMEntry 1 }
- sPDUIdentNameVM OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A 23-character string identifying the
- MasterSwitch VM. "
- ::= { sPDUIdentVMEntry 2 }
- sPDUIdentHardwareRevVM OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The hardware version of the MasterSwitch VM.
- This value is set at the factory."
- ::= { sPDUIdentVMEntry 3 }
- sPDUIdentFirmwareRevVM OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "An 6-character ID string identifying the MasterSwitch VM
- firmware version. This value is set at the factory."
- ::= { sPDUIdentVMEntry 4 }
- sPDUIdentDateOfManufactureVM OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The date when the MasterSwitch VM was manufactured in mm/dd/yyyy format.
- This value is set at the factory. "
- ::= { sPDUIdentVMEntry 5 }
-
- sPDUIdentModelNumberVM OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A 17-character string identifying the model number of
- the MasterSwitch VM. This value is set at the factory."
- ::= { sPDUIdentVMEntry 6 }
- sPDUIdentSerialNumberVM OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A 17-character string identifying the serial number of
- the MasterSwitch VM. This value is set at the factory."
- ::= { sPDUIdentVMEntry 7 }
-
- -- the sPDUMasterControlVM group
- sPDUMasterControlVMTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of MasterSwitch VMs controllable
- by this IP address."
- ::= { sPDUMasterControlVM 1 }
-
- sPDUMasterControlVMTable OBJECT-TYPE
- SYNTAX SEQUENCE OF SPDUMasterControlVMEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for control of the individual MasterSwitch VMs.
- The number of entries is contained in the
- sPDUMasterControlVMTableSize OID."
- ::= { sPDUMasterControlVM 2 }
- sPDUMasterControlVMEntry OBJECT-TYPE
- SYNTAX SPDUMasterControlVMEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The MasterSwitch VMs to control."
- INDEX { sPDUMasterControlVMIndex}
- ::= { sPDUMasterControlVMTable 1 }
- SPDUMasterControlVMEntry ::=
- SEQUENCE {
- sPDUMasterControlVMIndex INTEGER,
- sPDUMasterControlVMName DisplayString,
- sPDUMasterControlVMCommand INTEGER
- }
- sPDUMasterControlVMIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the MasterSwitch VM entry."
- ::= { sPDUMasterControlVMEntry 1 }
- sPDUMasterControlVMName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The name of the MasterSwitch VM. The maximum
- value is 23 characters. The name is set by
- using the sPDUMasterConfigVMName OID."
- ::= { sPDUMasterControlVMEntry 2 }
- sPDUMasterControlVMCommand OBJECT-TYPE
- SYNTAX INTEGER {
- noCommandAllVM (1),
- immediateAllOnVM (2),
- immediateAllOffVM (3),
- immediateAllRebootVM (4),
- delayedAllOnVM (5),
- delayedAllOffVM (6),
- sequencedAllRebootVM (7),
- delayedAllRebootVM (8),
- delayedSequenceAllRebootVM (9),
- cancelAllPendingCommandsVM (10),
- audioAlarmMute (11)
- }
-
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Setting this OID to immediateAllOnVM (2) will turn all outlets
- on immediately.
-
- Setting this OID to immediateAllOffVM (3) will turn all outlets
- off immediately.
-
- Setting this OID to immediateAllRebootVM (4) will reboot all outlets
- immediately.
- Setting this OID to delayedAllOnVM (5) will turn all outlets on as
- defined by each outlet's sPDUOutletConfigVMPowerOnTime OID value.
-
- Setting this OID to delayedAllOffVM (6) will turn all outlets
- off as defined by each outlet's sPDUOutletConfigVMPowerOffTime OID value.
-
- Setting this OID to sequencedAllRebootVM (7) will cause a
- immediateAllOffVM command to be performed. The MasterSwitch VM will
- then delay the sPDUMasterStatusVMRebootDuration OID time, and then
- perform a delayedAllOnVM command.
- Setting this OID to delayedAllRebootVM (8) will cause a delayedAllOffVM
- command to be performed. Each outlet will then wait its
- sPDUOutletConfigVMRebootDuration before returning power to the outlet.
-
- Setting this OID to delayedSequenceAllRebootVM (9) will cause a
- delayedAllOffVM command to be performed. Once all outlets are off,
- the MasterSwitch VM will then delay the sPDUMasterStatusVMRebootDuration
- OID time, and then perform a delayedAllOnVM command.
-
- Setting this OID to cancelAllPendingCommandsVM (10) will cause all pending
- commands on the MasterSwitch VM to be canceled.
-
- Setting this OID to audioAlarmMute (11) will temporarily silence the audible
- alarm for the duration of the current overload condition. The audible alarm
- will be activated on subsequent overload alarms.
- Getting this OID will return the noCommandAllVM (1) value."
- ::= { sPDUMasterControlVMEntry 3 }
- -- the sPDUMasterConfigVM group
- sPDUMasterConfigVMTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of MasterSwitch VMs configurable
- by this IP address."
- ::= { sPDUMasterConfigVM 1 }
-
- sPDUMasterConfigVMTable OBJECT-TYPE
- SYNTAX SEQUENCE OF SPDUMasterConfigVMEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for configuration of the individual MasterSwitch VMs.
- The number of entries is contained in the
- sPDUMasterConfigVMTableSize OID."
- ::= { sPDUMasterConfigVM 2 }
- sPDUMasterConfigVMEntry OBJECT-TYPE
- SYNTAX SPDUMasterConfigVMEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The MasterSwitch VMs to configure."
- INDEX { sPDUMasterConfigVMIndex}
- ::= { sPDUMasterConfigVMTable 1 }
- SPDUMasterConfigVMEntry ::=
- SEQUENCE {
- sPDUMasterConfigVMIndex INTEGER,
- sPDUMasterConfigVMName DisplayString,
- sPDUMasterConfigVMColdstartDelay INTEGER,
- sPDUMasterConfigVMAudioAlarmActivated INTEGER,
- sPDUMasterConfigVMHighLoadWarningThreshold INTEGER,
- sPDUMasterConfigVMLowLoadWarningThreshold INTEGER,
- sPDUMasterConfigVMOverloadRestriction INTEGER
- }
-
- sPDUMasterConfigVMIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the MasterSwitch VM entry."
- ::= { sPDUMasterConfigVMEntry 1 }
- sPDUMasterConfigVMName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The name of the MasterSwitch VM. Maximum size is 23 characters."
- ::= { sPDUMasterConfigVMEntry 2 }
- sPDUMasterConfigVMColdstartDelay OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- " The amount of delay, in seconds, between when
- power is provided to the MasterSwitch VM and
- when the MasterSwitch VM provides basic master
- power to the outlets.
-
- Allowed values are:
- -1 never apply power automatically.
- 0 apply power immediately.
- 15 apply power in 15 seconds.
- 30 apply power in 30 seconds.
- 45 apply power in 45 seconds.
- 60 apply power in 60 seconds (1 minute).
- 120 apply power in 120 seconds (2 minutes).
- 300 apply power in 300 seconds (5 minutes).
-
- If a value other than a supported value is provided in a
- set request, the MasterSwitch VM interprets it as the next lower
- acceptable value. If the provided value is lower than
- the lowest acceptable value, the lowest acceptable
- value is used."
- ::= { sPDUMasterConfigVMEntry 3 }
- sPDUMasterConfigVMAudioAlarmActivated OBJECT-TYPE
- SYNTAX INTEGER {
- audioAlarmActiveNever (1),
- audioAlarmActiveOnOverload (2),
- audioAlarmActiveOnOverloadImminent (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Setting this OID to audioAlarmActiveNever (1) will disable
- the audio alarm on the MasterSwitch VM.
-
- Setting this OID to audioAlarmActiveOnOverload (2) will
- activate the audio alarm on the MasterSwitch VM when an
- overload condition is present.
- Setting this OID to audioAlarmActiveOnOverloadImminent (3)
- will activate the audio alarm on the MasterSwitch VM when
- the load on the MasterSwitch VM has surpassed the
- sPDUMasterConfigVMHighLoadWarningThreshold OID value."
- ::= { sPDUMasterConfigVMEntry 4 }
-
- sPDUMasterConfigVMHighLoadWarningThreshold OBJECT-TYPE
- SYNTAX INTEGER (0..100)
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "A threshold that indicates the power consumption of
- the load is nearing an overload condition. It is
- represented as a percentage of full load."
- ::= { sPDUMasterConfigVMEntry 5 }
- sPDUMasterConfigVMLowLoadWarningThreshold OBJECT-TYPE
- SYNTAX INTEGER (0..100)
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "A threshold that indicates the power consumption of
- the load is nearing a low consumption condition. It is
- represented as a percentage of full load."
- ::= { sPDUMasterConfigVMEntry 6 }
- sPDUMasterConfigVMOverloadRestriction OBJECT-TYPE
- SYNTAX INTEGER {
- alwaysAllowTurnON (1),
- restrictOnWarning (2),
- restrictOnOverload (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "This OID controls the behavior of the MasterSwitch VM
- when an overload condition is possible and additional
- outlets are requested to be turned on.
- Setting this OID to alwaysAllowTurnON (1) will always allow
- the outlets to turn on.
-
- Setting this OID to restrictOnWarning (2) will not allow
- outlets to turn on if the sPDUMasterConfigVMHighLoadWarningThreshold
- OID is exceeded.
-
- Setting this OID to restrictOnOverload (3) will not allow
- outlets to turn on if the MasterSwitch Vm is in an
- overload condition."
- ::= { sPDUMasterConfigVMEntry 7 }
- -- the sPDUMasterStatusVM group
- sPDUMasterStatusVMTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of MasterSwitch VMs at
- this IP address."
- ::= { sPDUMasterStatusVM 1 }
-
- sPDUMasterStatusVMTable OBJECT-TYPE
- SYNTAX SEQUENCE OF SPDUMasterStatusVMEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for gathering of status from the individual
- MasterSwitch VMs. The number of entries is contained
- in the sPDUMasterStatusVMTableSize OID."
- ::= { sPDUMasterStatusVM 2 }
- sPDUMasterStatusVMEntry OBJECT-TYPE
- SYNTAX SPDUMasterStatusVMEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The MasterSwitch VMs to gather status from."
- INDEX { sPDUMasterStatusVMIndex}
- ::= { sPDUMasterStatusVMTable 1 }
- SPDUMasterStatusVMEntry ::=
- SEQUENCE {
- sPDUMasterStatusVMIndex INTEGER,
- sPDUMasterStatusVMName DisplayString,
- sPDUMasterStatusVMCommandPending INTEGER,
- sPDUMasterStatusVMOverloadCondition INTEGER,
- sPDUMasterStatusVMLowLoadCondition INTEGER,
- sPDUMasterStatusVMCurrentLoad INTEGER,
- sPDUMasterStatusVMMaxLoad INTEGER,
- sPDUMasterStatusVMOutletCount INTEGER,
- sPDUMasterStatusVMRebootDuration INTEGER
- }
-
- sPDUMasterStatusVMIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the MasterSwitch VM entry."
- ::= { sPDUMasterStatusVMEntry 1 }
- sPDUMasterStatusVMName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The name of the MasterSwitch VM. Maximum size is 23 characters."
- ::= { sPDUMasterStatusVMEntry 2 }
- sPDUMasterStatusVMCommandPending OBJECT-TYPE
- SYNTAX INTEGER {
- commandPendingMasterTrueVM (1),
- commandPendingMasterFalseVM (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return commandPendingMasterTrueVM (1)
- if the MasterSwitch VM has a pending command on any of its
- outlets.
- commandPendingMasterFalseVM (2) will be returned if there are
- no pending commands."
- ::= { sPDUMasterStatusVMEntry 3 }
- sPDUMasterStatusVMOverloadCondition OBJECT-TYPE
- SYNTAX INTEGER {
- overloadConditionTrueVM (1),
- overloadConditionFalseVM (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return overloadConditionTrueVM (1)
- if the sPDUMasterConfigVMHighLoadWarningThreshold OID is
- violated.
- overloadConditionFalseVM (2) will be returned if the
- sPDUMasterConfigVMHighLoadWarningThreshold OID is not
- violated."
- ::= { sPDUMasterStatusVMEntry 4 }
- sPDUMasterStatusVMLowLoadCondition OBJECT-TYPE
- SYNTAX INTEGER {
- lowLoadConditionTrueVM (1),
- lowLoadConditionFalseVM (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return lowLoadConditionTrueVM (1)
- if the sPDUMasterConfigVMLowLoadWarningThreshold OID is
- violated.
- lowLoadConditionFalseVM (2) will be returned if the
- sPDUMasterConfigVMHighLoadWarningThreshold OID is not
- violated. "
- ::= { sPDUMasterStatusVMEntry 5 }
- sPDUMasterStatusVMCurrentLoad OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return the total amount of power
- being consumed by the load. It is represented as a
- percentage of full load."
- ::= { sPDUMasterStatusVMEntry 6 }
- sPDUMasterStatusVMMaxLoad OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return the total amount of power
- that this MasterSwitch VM can provide. It is represented
- in Amps."
- ::= { sPDUMasterStatusVMEntry 7 }
- sPDUMasterStatusVMOutletCount OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return the number of controllable
- outlets for this MasterSwitch VM."
- ::= { sPDUMasterStatusVMEntry 8 }
- sPDUMasterStatusVMRebootDuration OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return the largest
- sPDUOutletConfigVMRebootDuration OID time
- for this MasterSwitch VM."
- ::= { sPDUMasterStatusVMEntry 9 }
- -- the sPDUOutletControlVM group
-
- sPDUOutletControlVMTable OBJECT-TYPE
- SYNTAX SEQUENCE OF SPDUOutletControlVMEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for control of individual outlet switches. The number of
- entries is contained in the sPDUMasterStatusOutletCount OID."
- ::= { sPDUOutletControlVM 1 }
- sPDUOutletControlVMEntry OBJECT-TYPE
- SYNTAX SPDUOutletControlVMEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The outlets to control."
- INDEX { sPDUOutletControlVMIndex, sPDUOutletControlVMOutletIndex }
- ::= { sPDUOutletControlVMTable 1 }
- SPDUOutletControlVMEntry ::=
- SEQUENCE {
- sPDUOutletControlVMIndex INTEGER,
- sPDUOutletControlVMName DisplayString,
- sPDUOutletControlVMOutletIndex INTEGER,
- sPDUOutletControlVMOutletName DisplayString,
- sPDUOutletControlVMOutletCommand INTEGER
- }
- sPDUOutletControlVMIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the MasterSwitch VM."
- ::= { sPDUOutletControlVMEntry 1 }
- sPDUOutletControlVMName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The name of the MasterSwitch VM. Maximum size is 23 characters.
- This OID is provided for informational purposes only."
- ::= { sPDUOutletControlVMEntry 2 }
- sPDUOutletControlVMOutletIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the outlet entry."
- ::= { sPDUOutletControlVMEntry 3 }
-
- sPDUOutletControlVMOutletName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The name of the outlet. Maximum size is 23 characters.
- This OID is provided for informational purposes only."
- ::= { sPDUOutletControlVMEntry 4 }
- sPDUOutletControlVMOutletCommand OBJECT-TYPE
- SYNTAX INTEGER {
- immediateOnVM (1),
- immediateOffVM (2),
- immediateRebootVM (3),
- delayedOnVM (4),
- delayedOffVM (5),
- delayedRebootVM (6),
- cancelPendingCommandVM (7)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Getting this variable will return the outlet state. If
- the outlet is on, the immediateOnVM (1) value will be returned.
- If the outlet is off, the immediateOffVM (2) value will be
- returned.
-
-
- Setting this variable to immediateOnVM (1) will immediately turn the outlet on.
-
- Setting this variable to immediateOffVM (2) will immediately turn the outlet off.
- Setting this variable to immediateRebootVM (3) will immediately reboot the outlet.
-
- Setting this variable to delayedOnVM (4) will turn the outlet on
- after the sPDUOutletConfigVMPowerOnTime OID time has elapsed.
- Setting this variable to delayedOffVM (5) will turn the outlet off
- after the sPDUOutletConfigVMPowerOffTime OID time has elapsed.
- Setting this variable to delayedRebootVM (6) will cause the
- MasterSwitch VM to perform a delayedOffVM command, wait the
- sPDUOutletConfigVMRebootDuration OID time, and then perform the
- immediateOnVM command.
-
- Setting this variable to cancelPendingCommandVM (7) will cause any
- pending command to this outlet to be canceled."
- ::= { sPDUOutletControlVMEntry 5 }
- -- the sPDUOutletConfigVM group
-
- sPDUOutletConfigVMTable OBJECT-TYPE
- SYNTAX SEQUENCE OF SPDUOutletConfigVMEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for configuration of individual outlets. The number of
- entries is contained in the sPDUMasterStatusOutletCount OID."
- ::= { sPDUOutletConfigVM 1 }
- sPDUOutletConfigVMEntry OBJECT-TYPE
- SYNTAX SPDUOutletConfigVMEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The outlets to configure."
- INDEX { sPDUOutletConfigVMIndex, sPDUOutletConfigVMOutletIndex }
- ::= { sPDUOutletConfigVMTable 1 }
- SPDUOutletConfigVMEntry ::=
- SEQUENCE {
- sPDUOutletConfigVMIndex INTEGER,
- sPDUOutletConfigVMName DisplayString,
- sPDUOutletConfigVMOutletIndex INTEGER,
- sPDUOutletConfigVMOutletName DisplayString,
- sPDUOutletConfigVMPowerOnTime INTEGER,
- sPDUOutletConfigVMPowerOffTime INTEGER,
- sPDUOutletConfigVMRebootDuration INTEGER
- }
- sPDUOutletConfigVMIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the MasterSwitch VM."
- ::= { sPDUOutletConfigVMEntry 1 }
- sPDUOutletConfigVMName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The name of the MasterSwitch VM. Maximum size is 23 characters."
- ::= { sPDUOutletConfigVMEntry 2 }
- sPDUOutletConfigVMOutletIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the outlet entry."
- ::= { sPDUOutletConfigVMEntry 3 }
-
- sPDUOutletConfigVMOutletName OBJECT-TYPE
- SYNTAX DisplayString ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The name of the outlet. Maximum size is 23 characters."
- ::= { sPDUOutletConfigVMEntry 4 }
- sPDUOutletConfigVMPowerOnTime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The amount of time (in seconds) the outlet will delay
- powering on at coldstart or when a command that requires
- a turn-on delay is issued.
-
- Allowed values are:
-
- -1 never power on.
- 0 power on immediately.
- 15 power on 15 seconds after being commanded.
- 30 power on 30 seconds after being commanded.
- 45 power on 45 seconds after being commanded.
- 60 power on 60 seconds (1 minute) after being commanded.
- 120 power on 120 seconds (2 minutes) after being commanded.
- 300 power on 300 seconds (5 minutes) after being commanded.
-
- If a value other than a supported value is provided in a
- set request, the MasterSwitch VM interprets it as the next lower
- acceptable value. If the provided value is lower than
- the lowest acceptable value, the lowest acceptable
- value is used."
- ::= { sPDUOutletConfigVMEntry 5 }
-
- sPDUOutletConfigVMPowerOffTime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The amount of time (in seconds) the outlet will delay
- powering off when a command that requires
- a turn-off delay is issued.
-
- Allowed values are:
-
- -1 never power off automatically.
- 0 power off immediately.
- 15 power off 15 seconds after being commanded.
- 30 power off 30 seconds after being commanded.
- 45 power off 45 seconds after being commanded.
- 60 power off 60 seconds (1 minute) after being commanded.
- 120 power off 120 seconds (2 minutes) after being commanded.
- 300 power off 300 seconds (5 minutes) after being commanded.
-
- If a value other than a supported value is provided in a
- set request, the MasterSwitch VM interprets it as the next lower
- acceptable value. If the provided value is lower than
- the lowest acceptable value, the lowest acceptable
- value is used."
- ::= { sPDUOutletConfigVMEntry 6 }
- sPDUOutletConfigVMRebootDuration OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "During a reboot sequence, power is turned off and then
- back on. This OID defines the amount of time to wait,
- in seconds, after turning the power off, at the start
- of the sequence, before turning power back on, at the
- end of the reboot sequence.
-
- Allowed values are:
-
- 5 wait 5 seconds between off/on.
- 10 wait 10 seconds between off/on.
- 15 wait 15 seconds between off/on.
- 20 wait 20 seconds between off/on.
- 30 wait 30 seconds between off/on.
- 45 wait 45 seconds between off/on.
- 60 wait 60 seconds (1 minute) between off/on.
-
- If a value other than a supported value is provided in a
- set request, the MasterSwitch VM interprets it as the next lower
- acceptable value. If the provided value is lower than
- the lowest acceptable value, the lowest acceptable
- value is used."
- ::= { sPDUOutletConfigVMEntry 7 }
- -- the sPDUOutletStatusVM group
-
- sPDUOutletStatusVMTable OBJECT-TYPE
- SYNTAX SEQUENCE OF SPDUOutletStatusVMEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting of status of individual outlets. The number of
- entries is contained in the sPDUMasterStatusOutletCount OID."
- ::= { sPDUOutletStatusVM 1 }
- sPDUOutletStatusVMEntry OBJECT-TYPE
- SYNTAX SPDUOutletStatusVMEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The outlets to gather status from."
- INDEX { sPDUOutletStatusVMIndex, sPDUOutletStatusVMOutletIndex }
- ::= { sPDUOutletStatusVMTable 1 }
- SPDUOutletStatusVMEntry ::=
- SEQUENCE {
- sPDUOutletStatusVMIndex INTEGER,
- sPDUOutletStatusVMName DisplayString,
- sPDUOutletStatusVMOutletIndex INTEGER,
- sPDUOutletStatusVMOutletName DisplayString,
- sPDUOutletStatusVMOutletState INTEGER,
- sPDUOutletStatusVMCommandPending INTEGER
- }
- sPDUOutletStatusVMIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the MasterSwitch VM."
- ::= { sPDUOutletStatusVMEntry 1 }
- sPDUOutletStatusVMName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The name of the MasterSwitch VM. Maximum size is 23 characters."
- ::= { sPDUOutletStatusVMEntry 2 }
- sPDUOutletStatusVMOutletIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the outlet entry."
- ::= { sPDUOutletStatusVMEntry 3 }
-
- sPDUOutletStatusVMOutletName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The name of the outlet. Maximum size is 23 characters."
- ::= { sPDUOutletStatusVMEntry 4 }
- sPDUOutletStatusVMOutletState OBJECT-TYPE
- SYNTAX INTEGER {
- outletStatusVMOn (1),
- outletStatusVMOff (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this variable will return the outlet state. If
- the outlet is on, the outletStatusOnVM (1) value will be returned.
- If the outlet is off, the outletStatusOffVM (2) value will be
- returned. "
- ::= { sPDUOutletStatusVMEntry 5 }
- sPDUOutletStatusVMCommandPending OBJECT-TYPE
- SYNTAX INTEGER {
- outletStatusVMCommandPending (1),
- outletStatusVMNoCommandPending (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this variable will return the command pending
- state of the outlet. If a command is pending on the
- outlet, the outletStatusVMCommandPending (1) value
- will be returned. If there is not a command pending
- on the outlet, the outletStatusVMNoCommandPending (2)
- will be returned."
- ::= { sPDUOutletStatusVMEntry 6 }
- -- the sPDUIdentMSP group
- sPDUIdentMSPTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of MasterSwitch pluses controllable
- by this IP address."
- ::= { sPDUIdentMSP 1 }
-
- sPDUIdentMSPTable OBJECT-TYPE
- SYNTAX SEQUENCE OF SPDUIdentMSPEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for query of the individual MasterSwitch pluses.
- The number of entries is contained in the
- sPDUIdentMSPTableSize OID."
- ::= { sPDUIdentMSP 2 }
- sPDUIdentMSPEntry OBJECT-TYPE
- SYNTAX SPDUIdentMSPEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The MasterSwitch pluses to query."
- INDEX { sPDUIdentMSPIndex}
- ::= { sPDUIdentMSPTable 1 }
- SPDUIdentMSPEntry ::=
- SEQUENCE {
- sPDUIdentMSPIndex INTEGER,
- sPDUIdentNameMSP DisplayString,
- sPDUIdentHardwareRevMSP DisplayString,
- sPDUIdentFirmwareRevMSP DisplayString,
- sPDUIdentDateOfManufactureMSP DisplayString,
- sPDUIdentModelNumberMSP DisplayString,
- sPDUIdentSerialNumberMSP DisplayString
- }
- sPDUIdentMSPIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the MasterSwitch plus entry."
- ::= { sPDUIdentMSPEntry 1 }
- sPDUIdentNameMSP OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The name of the MasterSwitch plus. The maximum
- value is 23 characters. The name is set by
- using the sPDUMasterConfigMSPName OID."
- ::= { sPDUIdentMSPEntry 2 }
- sPDUIdentHardwareRevMSP OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The hardware version of the MasterSwitch plus.
- This value is set at the factory."
- ::= { sPDUIdentMSPEntry 3 }
- sPDUIdentFirmwareRevMSP OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "An 6-character ID string identifying the MasterSwitch plus
- firmware version. This value is set at the factory."
- ::= { sPDUIdentMSPEntry 4 }
- sPDUIdentDateOfManufactureMSP OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The date when the MasterSwitch plus was manufactured in mm/dd/yyyy format.
- This value is set at the factory. "
- ::= { sPDUIdentMSPEntry 5 }
-
- sPDUIdentModelNumberMSP OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A 17-character string identifying the model number of
- the MasterSwitch plus. This value is set at the factory."
- ::= { sPDUIdentMSPEntry 6 }
- sPDUIdentSerialNumberMSP OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A 17-character string identifying the serial number of
- the MasterSwitch plus. This value is set at the factory."
- ::= { sPDUIdentMSPEntry 7 }
-
- -- the sPDUMasterControlMSP group
- sPDUMasterControlMSPTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of MasterSwitch pluses controllable
- by this IP address."
- ::= { sPDUMasterControlMSP 1 }
- sPDUMasterControlMSPTable OBJECT-TYPE
- SYNTAX SEQUENCE OF SPDUMasterControlMSPEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for control of the individual MasterSwitch pluses.
- The number of entries is contained in the
- sPDUMasterControlMSPTableSize OID."
- ::= { sPDUMasterControlMSP 2 }
- sPDUMasterControlMSPEntry OBJECT-TYPE
- SYNTAX SPDUMasterControlMSPEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The MasterSwitch pluses to control."
- INDEX { sPDUMasterControlMSPIndex}
- ::= { sPDUMasterControlMSPTable 1 }
- SPDUMasterControlMSPEntry ::=
- SEQUENCE {
- sPDUMasterControlMSPIndex INTEGER,
- sPDUMasterControlMSPName DisplayString,
- sPDUMasterControlMSPCommand INTEGER
- }
- sPDUMasterControlMSPIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the MasterSwitch plus entry."
- ::= { sPDUMasterControlMSPEntry 1 }
- sPDUMasterControlMSPName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The name of the MasterSwitch plus. The maximum
- value is 23 characters. The name is set by
- using the sPDUMasterConfigMSPName OID."
- ::= { sPDUMasterControlMSPEntry 2 }
- sPDUMasterControlMSPCommand OBJECT-TYPE
- SYNTAX INTEGER {
- noCommandAllMSP (1),
- immediateAllOnMSP (2),
- sequencedAllOnMSP (3),
- immediateAllOffMSP (4),
- gracefulAllRebootMSP (5),
- immediateAllRebootMSP (6),
- gracefulAllShutdownMSP (7),
- overrideAllBatCapThreshMSP (8),
- cancelAllPendingCommandsMSP (9),
- restoreFactoryDefaultsMSP (10)
- }
-
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Setting this OID to immediateAllOnMSP (2) will turn all outlets
- on immediately.
-
- Setting this OID to sequencedAllOnMSP (3) will turn all outlets
- on as defined by each outlet's sPDUOutletConfigMSPPowerOnDelay OID value.
- Setting this OID to immediateAllOffMSP (4) will turn all outlets
- off immediately.
-
- Setting this OID to gracefulAllRebootMSP (5) will reboot all outlets
- (after the device running PowerChute confirms shutdown) as defined
- by each outlet's sPDUOutletConfigMSPRebootDuration OID time value.
- Setting this OID to immediateAllRebootMSP (6) will reboot all outlets
- immediately.
- Setting this OID to gracefulAllShutdownMSP (7) will shutdown all outlets
- (after the device running PowerChute confirms shutdown) as defined
- by each outlet's sPDUOutletConfigMSPPowerOffDelay OID time value. Each
- outlet will then turn on after the sum of its
- sPDUOutletConfigMSPRestartDelay and sPDUOutletConfigMSPPowerOnDelay OID
- values.
- Setting this OID to overrideAllBatCapThreshMSP (8) will cause the
- outlet to ignore the Battery Capacity Threshold and proceed turning on
- the outlets as defined by each outlet's sPDUOutletConfigMSPPowerOnDelay
- OID value.
-
- Setting this OID to cancelAllPendingCommandsMSP (9) will cause all pending
- commands on the MasterSwitch plus to be canceled.
- Setting this OID to restoreFactoryDefaultsMSP (10) will cause the settings of
- the MasterSwitch plus to be restored to the factory defaults.
- Getting this OID will return the noCommandAllMSP (1) value."
- ::= { sPDUMasterControlMSPEntry 3 }
- -- the sPDUMasterConfigMSP group
- sPDUMasterConfigMSPTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of MasterSwitch pluses configurable
- by this IP address."
- ::= { sPDUMasterConfigMSP 1 }
-
- sPDUMasterConfigMSPTable OBJECT-TYPE
- SYNTAX SEQUENCE OF SPDUMasterConfigMSPEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for configuration of the individual MasterSwitch pluses.
- The number of entries is contained in the
- sPDUMasterConfigMSPTableSize OID."
- ::= { sPDUMasterConfigMSP 2 }
- sPDUMasterConfigMSPEntry OBJECT-TYPE
- SYNTAX SPDUMasterConfigMSPEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The MasterSwitch pluses to configure."
- INDEX { sPDUMasterConfigMSPIndex}
- ::= { sPDUMasterConfigMSPTable 1 }
- SPDUMasterConfigMSPEntry ::=
- SEQUENCE {
- sPDUMasterConfigMSPIndex INTEGER,
- sPDUMasterConfigMSPName DisplayString,
- sPDUMasterConfigMSPPowerOnTimeDelay INTEGER,
- sPDUMasterConfigMSPManualButton INTEGER
- }
-
- sPDUMasterConfigMSPIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the MasterSwitch plus entry."
- ::= { sPDUMasterConfigMSPEntry 1 }
- sPDUMasterConfigMSPName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The name of the MasterSwitch plus. Maximum size is 23 characters."
- ::= { sPDUMasterConfigMSPEntry 2 }
- sPDUMasterConfigMSPPowerOnTimeDelay OBJECT-TYPE
- SYNTAX INTEGER (0..9999)
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- " The amount of delay, in seconds, between when
- power is provided to the MasterSwitch plus and
- when the MasterSwitch plus provides basic master
- power to the outlets.
-
- Allowed values are:
- 0 - 9999 seconds (0 - 2hrs, 46 mins, 39 secs).
- 0 indicates to apply power immediately."
- ::= { sPDUMasterConfigMSPEntry 3 }
-
- sPDUMasterConfigMSPManualButton OBJECT-TYPE
- SYNTAX INTEGER {
- manualButtonDisabled (1),
- manualButtonEnabled (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Setting this OID to manualButtonDisabled (1) will disable
- the manual button on the MasterSwitch plus.
- Setting this OID to manualButtonEnabled (2) will enable
- the manual button on the MasterSwitch plus."
- ::= { sPDUMasterConfigMSPEntry 4 }
-
- -- the sPDUMasterStatusMSP group
- sPDUMasterStatusMSPTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of MasterSwitch pluses at
- this IP address."
- ::= { sPDUMasterStatusMSP 1 }
-
- sPDUMasterStatusMSPTable OBJECT-TYPE
- SYNTAX SEQUENCE OF SPDUMasterStatusMSPEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for gathering of status from the individual
- MasterSwitch pluses. The number of entries is contained
- in the sPDUMasterStatusMSPTableSize OID."
- ::= { sPDUMasterStatusMSP 2 }
- sPDUMasterStatusMSPEntry OBJECT-TYPE
- SYNTAX SPDUMasterStatusMSPEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The MasterSwitch pluses to gather status from."
- INDEX { sPDUMasterStatusMSPIndex}
- ::= { sPDUMasterStatusMSPTable 1 }
- SPDUMasterStatusMSPEntry ::=
- SEQUENCE {
- sPDUMasterStatusMSPIndex INTEGER,
- sPDUMasterStatusMSPName DisplayString,
- sPDUMasterStatusMSPOutletCount INTEGER
- }
-
- sPDUMasterStatusMSPIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the MasterSwitch plus entry."
- ::= { sPDUMasterStatusMSPEntry 1 }
- sPDUMasterStatusMSPName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The name of the MasterSwitch plus. The maximum
- value is 23 characters. The name is set by
- using the sPDUMasterConfigMSPName OID."
- ::= { sPDUMasterStatusMSPEntry 2 }
- sPDUMasterStatusMSPOutletCount OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return the number of controllable
- outlets for this MasterSwitch plus."
- ::= { sPDUMasterStatusMSPEntry 3 }
- -- the sPDUOutletControlMSP group
-
- sPDUOutletControlMSPTable OBJECT-TYPE
- SYNTAX SEQUENCE OF SPDUOutletControlMSPEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for control of individual outlet switches. The number of
- entries is contained in the sPDUMasterStatusMSPOutletCount OID."
- ::= { sPDUOutletControlMSP 1 }
- sPDUOutletControlMSPEntry OBJECT-TYPE
- SYNTAX SPDUOutletControlMSPEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The outlets to control."
- INDEX { sPDUOutletControlMSPIndex, sPDUOutletControlMSPOutletIndex }
- ::= { sPDUOutletControlMSPTable 1 }
- SPDUOutletControlMSPEntry ::=
- SEQUENCE {
- sPDUOutletControlMSPIndex INTEGER,
- sPDUOutletControlMSPName DisplayString,
- sPDUOutletControlMSPOutletIndex INTEGER,
- sPDUOutletControlMSPOutletName DisplayString,
- sPDUOutletControlMSPOutletCommand INTEGER
- }
- sPDUOutletControlMSPIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the MasterSwitch plus."
- ::= { sPDUOutletControlMSPEntry 1 }
- sPDUOutletControlMSPName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The name of the MasterSwitch plus. The maximum
- value is 23 characters. The name is set by
- using the sPDUMasterConfigMSPName OID."
- ::= { sPDUOutletControlMSPEntry 2 }
- sPDUOutletControlMSPOutletIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the outlet entry."
- ::= { sPDUOutletControlMSPEntry 3 }
-
- sPDUOutletControlMSPOutletName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The name of the outlet. The maximum size is
- 23 characters. The name is set by using the
- sPDUOutletConfigMSPallOutletName OID.
- This OID is provided for informational purposes only."
- ::= { sPDUOutletControlMSPEntry 4 }
- sPDUOutletControlMSPOutletCommand OBJECT-TYPE
- SYNTAX INTEGER {
- immediateOnMSP (1),
- delayedOnMSP (2),
- immediateOffMSP (3),
- gracefulRebootMSP (4),
- immediateRebootMSP (5),
- gracefulshutdownMSP (6),
- overrideBatCapThreshMSP (7),
- cancelPendingCommandMSP (8)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Getting this variable will return the outlet state. If
- the outlet is on, the immediateOnMSP (1) value will be returned.
- If the outlet is off, the immediateOffMSP (3) value will be
- returned.
-
- Setting this variable to immediateOnMSP (1) will immediately turn the outlet on.
-
- Setting this variable to delayedOnMSP (2) will turn the outlet on
- after the sPDUOutletConfigMSPPowerOnDelay OID time has elapsed.
- Setting this variable to immediateOffMSP (3) will immediately turn the outlet off.
- Setting this variable to gracefulRebootMSP (4) will cause the outlet to wait for
- device confirmation (if applicable) and then turn the outlet off after the
- sPDUOutletConfigMSPPowerOffDelay OID time has elapsed. The outlet will then turn
- on after the sPDUOutletConfigMSPRebootDuration OID time has elapsed.
- Setting this variable to immediateRebootMSP (5) will immediately reboot the outlet.
- Setting this variable to gracefulshutdownMSP (6) will cause the outlet to wait for
- device confirmation (if applicable) and then turn the outlet off after the
- sPDUOutletConfigMSPPowerOffDelay OID time has elapsed. The outlet will then turn
- on after the sum of the sPDUOutletConfigMSPRestartTime OID time and the
- sPDUOutletConfigMSPPowerOnDelay OID time has elapsed.
-
- Setting this variable to overrideBatCapThreshMSP (7) will cause the outlet to
- ignore the Battery Capacity Threshold and proceed waiting on the
- sPDUOutletConfigMSPPowerOnDelay OID time before turning the outlet on.
-
- Setting this variable to cancelPendingCommandMSP (8) will cause any
- pending command to this outlet to be canceled."
- ::= { sPDUOutletControlMSPEntry 5 }
- -- the sPDUOutletConfigMSPall group
-
- sPDUOutletConfigMSPallTable OBJECT-TYPE
- SYNTAX SEQUENCE OF SPDUOutletConfigMSPallEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for configuration of individual outlets. The number of
- entries is contained in the sPDUMasterStatusMSPOutletCount OID."
- ::= { sPDUOutletConfigMSPall 1 }
- sPDUOutletConfigMSPallEntry OBJECT-TYPE
- SYNTAX SPDUOutletConfigMSPallEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The outlets to configure."
- INDEX { sPDUOutletConfigMSPallIndex, sPDUOutletConfigMSPallOutletIndex }
- ::= { sPDUOutletConfigMSPallTable 1 }
- SPDUOutletConfigMSPallEntry ::=
- SEQUENCE {
- sPDUOutletConfigMSPallIndex INTEGER,
- sPDUOutletConfigMSPallName DisplayString,
- sPDUOutletConfigMSPallOutletIndex INTEGER,
- sPDUOutletConfigMSPallOutletName DisplayString,
- sPDUOutletConfigMSPallOutletCtrlMode INTEGER
- }
- sPDUOutletConfigMSPallIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the MasterSwitch plus."
- ::= { sPDUOutletConfigMSPallEntry 1 }
- sPDUOutletConfigMSPallName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The name of the MasterSwitch plus. The maximum
- value is 23 characters. The name is set by
- using the sPDUMasterConfigMSPName OID."
- ::= { sPDUOutletConfigMSPallEntry 2 }
- sPDUOutletConfigMSPallOutletIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the outlet entry."
- ::= { sPDUOutletConfigMSPallEntry 3 }
-
- sPDUOutletConfigMSPallOutletName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The name of the outlet. Maximum size is 23 characters."
- ::= { sPDUOutletConfigMSPallEntry 4 }
- sPDUOutletConfigMSPallOutletCtrlMode OBJECT-TYPE
- SYNTAX INTEGER {
- modeGracefulShutdown (1),
- modeAnnunciator (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Setting this OID to modeGracefulShutdown (1) will put this
- outlet into the Graceful Shutdown control mode.
- Setting this OID to modeAnnunciator (2) will put this outlet
- into the Annunciator control mode."
- ::= { sPDUOutletConfigMSPallEntry 5 }
- -- the sPDUOutConfigMSPgs group
- sPDUOutletConfigMSPgsTable OBJECT-TYPE
- SYNTAX SEQUENCE OF SPDUOutletConfigMSPgsEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for configuration of individual outlets. The number of
- entries is contained in the sPDUMasterStatusMSPOutletCount OID."
- ::= { sPDUOutletConfigMSPgs 1 }
- sPDUOutletConfigMSPgsEntry OBJECT-TYPE
- SYNTAX SPDUOutletConfigMSPgsEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The outlets to configure."
- INDEX { sPDUOutletConfigMSPgsIndex, sPDUOutletConfigMSPgsOutletIndex }
- ::= { sPDUOutletConfigMSPgsTable 1 }
- SPDUOutletConfigMSPgsEntry ::=
- SEQUENCE {
- sPDUOutletConfigMSPgsIndex INTEGER,
- sPDUOutletConfigMSPgsName DisplayString,
- sPDUOutletConfigMSPgsOutletIndex INTEGER,
- sPDUOutletConfigMSPgsOutletName DisplayString,
- sPDUOutletConfigMSPgsOutletCtrlMode INTEGER,
- sPDUOutletConfigMSPgsDeviceConfirm INTEGER,
- sPDUOutletConfigMSPgsLowBattWarning INTEGER,
- sPDUOutletConfigMSPgsLowBattMult INTEGER,
- sPDUOutletConfigMSPgsRestartDelay INTEGER,
- sPDUOutletConfigMSPgsPowerOnDelay INTEGER,
- sPDUOutletConfigMSPgsPowerOffDelay INTEGER,
- sPDUOutletConfigMSPgsBattCapThresh INTEGER,
- sPDUOutletConfigMSPgsRebootDuration INTEGER
- }
- sPDUOutletConfigMSPgsIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the MasterSwitch plus."
- ::= { sPDUOutletConfigMSPgsEntry 1 }
- sPDUOutletConfigMSPgsName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The name of the MasterSwitch plus. The maximum
- value is 23 characters. The name is set by
- using the sPDUMasterConfigMSPName OID."
- ::= { sPDUOutletConfigMSPgsEntry 2 }
- sPDUOutletConfigMSPgsOutletIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the outlet entry."
- ::= { sPDUOutletConfigMSPgsEntry 3 }
- sPDUOutletConfigMSPgsOutletName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The name of the outlet. The maximum size is
- 23 characters. The name is set by using the
- sPDUOutletConfigMSPallOutletName OID.
- This OID is provided for informational purposes only."
- ::= { sPDUOutletConfigMSPgsEntry 4 }
- sPDUOutletConfigMSPgsOutletCtrlMode OBJECT-TYPE
- SYNTAX INTEGER {
- modeGracefulShutdown (1),
- modeAnnunciator (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The Control Mode of the outlet.
- This OID is provided for informational purposes only."
- ::= { sPDUOutletConfigMSPgsEntry 5 }
- sPDUOutletConfigMSPgsDeviceConfirm OBJECT-TYPE
- SYNTAX INTEGER {
- deviceConfirmNo (1),
- deviceConfirmYes (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Setting this OID to deviceConfirmNo (1) cause the outlet to
- NOT wait for device confirmation while performing graceful
- operations.
- Setting this OID to deviceConfirmYes (2) cause the outlet to
- wait for device confirmation while performing graceful
- operations."
- ::= { sPDUOutletConfigMSPgsEntry 6 }
- sPDUOutletConfigMSPgsLowBattWarning OBJECT-TYPE
- SYNTAX INTEGER (-2..9999)
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- " The amount of delay, in 6 second intervals, between
- when the UPS goes on battery and the power down sequence for
- the outlet is initiated.
-
- Allowed values are:
- -2 - Never initiate the power down sequence on low battery warning.
- -1 - Initiate power down sequence based on remaining runtime.
- 1 - 9999 six second intervals (6 secs - 16hrs, 39 mins, 54 secs).
- 0 indicates to immediately initiate power down sequence on low
- battery warning."
- ::= { sPDUOutletConfigMSPgsEntry 7 }
-
- sPDUOutletConfigMSPgsLowBattMult OBJECT-TYPE
- SYNTAX INTEGER (1..7)
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- " Only applicable if sPDUOutletConfigMSPgsLowBattWarning OID is
- set to -1 (On Runtime Remaining).
-
- Allows you to set the value to stagger the shutdown sequence of the outlets.
- 1 provides the longest delay (the outlet to shutoff first), and 7 would
- provide the shortest delay (the outlet to shut off last).
-
- Allowed values are:
- 1 - 7."
- ::= { sPDUOutletConfigMSPgsEntry 8 }
- sPDUOutletConfigMSPgsRestartDelay OBJECT-TYPE
- SYNTAX INTEGER (-1..9999)
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- " The amount of delay, in 6 minute intervals, between
- when the outlet is turned off and the outlet is turned back on
- when performing a Graceful Shutdown.
-
- Allowed values are:
- -1 - Never turn outlet back on after a Graceful shutdown.
- 0 - 9999 six minute intervals (0 - 999hrs, 54 mins)."
- ::= { sPDUOutletConfigMSPgsEntry 9 }
- sPDUOutletConfigMSPgsPowerOnDelay OBJECT-TYPE
- SYNTAX INTEGER (-1..9999)
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- " The amount of delay, in seconds, between the UPS entering
- normal (on-line) state and the outlet being powered on.
-
- Allowed values are:
- -1 - Remain Off when the UPS enters the on-line state.
- 0 - 9999 seconds (0 - 2 hrs, 46 mins, 39 secs)."
- ::= { sPDUOutletConfigMSPgsEntry 10 }
- sPDUOutletConfigMSPgsPowerOffDelay OBJECT-TYPE
- SYNTAX INTEGER (0..9999)
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- " The amount of delay, in seconds, between when the server
- shuts down and the outlet is powered off.
-
- Allowed values are:
- 0 - 9999 seconds (0 - 2 hrs, 46 mins, 39 secs)."
- ::= { sPDUOutletConfigMSPgsEntry 11 }
-
- sPDUOutletConfigMSPgsBattCapThresh OBJECT-TYPE
- SYNTAX INTEGER (0..100)
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- " The minimum battery capacity, as a percent (0-100%), required
- of the UPS before an outlet will be allowed to power on.
-
- Allowed values are:
- 0 - 100 percent."
- ::= { sPDUOutletConfigMSPgsEntry 12 }
- sPDUOutletConfigMSPgsRebootDuration OBJECT-TYPE
- SYNTAX INTEGER (0..9999)
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- " The amount of delay, in seconds, from outlet off until
- outlet on during a reboot.
-
- Allowed values are:
- 0 - 9999 seconds (0 - 2 hrs, 46 mins, 39 secs)."
- ::= { sPDUOutletConfigMSPgsEntry 13 }
- -- the sPDUOutConfigMSPannun group
- sPDUOutletConfigMSPannunTable OBJECT-TYPE
- SYNTAX SEQUENCE OF SPDUOutletConfigMSPannunEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for configuration of individual outlets. The number of
- entries is contained in the sPDUMasterStatusMSPOutletCount OID."
- ::= { sPDUOutletConfigMSPannun 1 }
- sPDUOutletConfigMSPannunEntry OBJECT-TYPE
- SYNTAX SPDUOutletConfigMSPannunEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The outlets to configure."
- INDEX { sPDUOutletConfigMSPannunIndex, sPDUOutletConfigMSPannunOutletIndex }
- ::= { sPDUOutletConfigMSPannunTable 1 }
- SPDUOutletConfigMSPannunEntry ::=
- SEQUENCE {
- sPDUOutletConfigMSPannunIndex INTEGER,
- sPDUOutletConfigMSPannunName DisplayString,
- sPDUOutletConfigMSPannunOutletIndex INTEGER,
- sPDUOutletConfigMSPannunOutletName DisplayString,
- sPDUOutletConfigMSPannunOutletCtrlMode INTEGER,
- sPDUOutletConfigMSPannunInitialState INTEGER,
- sPDUOutletConfigMSPannunAlarmActionDly INTEGER
- }
- sPDUOutletConfigMSPannunIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the MasterSwitch plus."
- ::= { sPDUOutletConfigMSPannunEntry 1 }
- sPDUOutletConfigMSPannunName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The name of the MasterSwitch plus. The maximum
- value is 23 characters. The name is set by
- using the sPDUMasterConfigMSPName OID."
- ::= { sPDUOutletConfigMSPannunEntry 2 }
- sPDUOutletConfigMSPannunOutletIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the outlet entry."
- ::= { sPDUOutletConfigMSPannunEntry 3 }
- sPDUOutletConfigMSPannunOutletName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The name of the outlet. The maximum size is
- 23 characters. The name is set by using the
- sPDUOutletConfigMSPallOutletName OID.
- This OID is provided for informational purposes only."
- ::= { sPDUOutletConfigMSPannunEntry 4 }
- sPDUOutletConfigMSPannunOutletCtrlMode OBJECT-TYPE
- SYNTAX INTEGER {
- modeGracefulShutdown (1),
- modeAnnunciator (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The Control Mode of the outlet.
- This OID is provided for informational purposes only."
- ::= { sPDUOutletConfigMSPannunEntry 5 }
- sPDUOutletConfigMSPannunInitialState OBJECT-TYPE
- SYNTAX INTEGER {
- initialStateOff (1),
- initialStateOn (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Setting this OID to initialStateOff (1) causes the outlet
- to default to off when in the non-alarmed condition.
- Setting this OID to initialStateOn (2) causes the outlet
- to default to on when in the non-alarmed condition."
- ::= { sPDUOutletConfigMSPannunEntry 6 }
- sPDUOutletConfigMSPannunAlarmActionDly OBJECT-TYPE
- SYNTAX INTEGER (0..9999)
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- " The amount of time, in seconds, that an enabled Measure-UPS
- alarm must be asserted before an alarm condition is recognized.
-
- Allowed values are:
- 0 - 9999 seconds (0 - 2 hrs, 46 mins, 39 secs)."
- ::= { sPDUOutletConfigMSPannunEntry 7 }
- -- the sPDUOutConfigMSPmups group
- sPDUOutletConfigMSPmupsTable OBJECT-TYPE
- SYNTAX SEQUENCE OF SPDUOutletConfigMSPmupsEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for configuration of individual outlets. The number of
- entries is contained in the sPDUMasterStatusMSPOutletCount OID."
- ::= { sPDUOutletConfigMSPmups 1 }
- sPDUOutletConfigMSPmupsEntry OBJECT-TYPE
- SYNTAX SPDUOutletConfigMSPmupsEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The outlets to configure."
- INDEX { sPDUOutletConfigMSPmupsIndex, sPDUOutletConfigMSPmupsOutletIndex }
- ::= { sPDUOutletConfigMSPmupsTable 1 }
- SPDUOutletConfigMSPmupsEntry ::=
- SEQUENCE {
- sPDUOutletConfigMSPmupsIndex INTEGER,
- sPDUOutletConfigMSPmupsName DisplayString,
- sPDUOutletConfigMSPmupsOutletIndex INTEGER,
- sPDUOutletConfigMSPmupsOutletName DisplayString,
- sPDUOutletConfigMSPmupsZone1 INTEGER,
- sPDUOutletConfigMSPmupsZone2 INTEGER,
- sPDUOutletConfigMSPmupsZone3 INTEGER,
- sPDUOutletConfigMSPmupsZone4 INTEGER,
- sPDUOutletConfigMSPmupsP1LowHum INTEGER,
- sPDUOutletConfigMSPmupsP1HiHum INTEGER,
- sPDUOutletConfigMSPmupsP1LowTemp INTEGER,
- sPDUOutletConfigMSPmupsP1HiTemp INTEGER,
- sPDUOutletConfigMSPmupsP2LowHum INTEGER,
- sPDUOutletConfigMSPmupsP2HiHum INTEGER,
- sPDUOutletConfigMSPmupsP2LowTemp INTEGER,
- sPDUOutletConfigMSPmupsP2HiTemp INTEGER
- }
- sPDUOutletConfigMSPmupsIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the MasterSwitch plus."
- ::= { sPDUOutletConfigMSPmupsEntry 1 }
- sPDUOutletConfigMSPmupsName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The name of the MasterSwitch plus. The maximum
- value is 23 characters. The name is set by
- using the sPDUMasterConfigMSPName OID."
- ::= { sPDUOutletConfigMSPmupsEntry 2 }
- sPDUOutletConfigMSPmupsOutletIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the outlet entry."
- ::= { sPDUOutletConfigMSPmupsEntry 3 }
- sPDUOutletConfigMSPmupsOutletName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The name of the outlet. The maximum size is
- 23 characters. The name is set by using the
- sPDUOutletConfigMSPallOutletName OID.
- This OID is provided for informational purposes only."
- ::= { sPDUOutletConfigMSPmupsEntry 4 }
- sPDUOutletConfigMSPmupsZone1 OBJECT-TYPE
- SYNTAX INTEGER {
- disableAlarm (1),
- enableAlarm (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Setting this OID to disableAlarm (1) disables the
- Zone 1 alarm for this outlet.
- Setting this OID to enableAlarm (2) enables the
- Zone 1 alarm for this outlet."
- ::= { sPDUOutletConfigMSPmupsEntry 5 }
- sPDUOutletConfigMSPmupsZone2 OBJECT-TYPE
- SYNTAX INTEGER {
- disableAlarm (1),
- enableAlarm (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Setting this OID to disableAlarm (1) disables the
- Zone 2 alarm for this outlet.
- Setting this OID to enableAlarm (2) enables the
- Zone 2 alarm for this outlet."
- ::= { sPDUOutletConfigMSPmupsEntry 6 }
- sPDUOutletConfigMSPmupsZone3 OBJECT-TYPE
- SYNTAX INTEGER {
- disableAlarm (1),
- enableAlarm (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Setting this OID to disableAlarm (1) disables the
- Zone 3 alarm for this outlet.
- Setting this OID to enableAlarm (2) enables the
- Zone 3 alarm for this outlet."
- ::= { sPDUOutletConfigMSPmupsEntry 7 }
- sPDUOutletConfigMSPmupsZone4 OBJECT-TYPE
- SYNTAX INTEGER {
- disableAlarm (1),
- enableAlarm (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Setting this OID to disableAlarm (1) disables the
- Zone 4 alarm for this outlet.
- Setting this OID to enableAlarm (2) enables the
- Zone 4 alarm for this outlet."
- ::= { sPDUOutletConfigMSPmupsEntry 8 }
- sPDUOutletConfigMSPmupsP1LowHum OBJECT-TYPE
- SYNTAX INTEGER {
- disableAlarm (1),
- enableAlarm (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Setting this OID to disableAlarm (1) disables the
- Probe 1 low humidity alarm for this outlet.
- Setting this OID to enableAlarm (2) enables the
- Probe 1 low humidity alarm for this outlet."
- ::= { sPDUOutletConfigMSPmupsEntry 9 }
- sPDUOutletConfigMSPmupsP1HiHum OBJECT-TYPE
- SYNTAX INTEGER {
- disableAlarm (1),
- enableAlarm (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Setting this OID to disableAlarm (1) disables the
- Probe 1 high humidity alarm for this outlet.
- Setting this OID to enableAlarm (2) enables the
- Probe 1 high humidity alarm for this outlet."
- ::= { sPDUOutletConfigMSPmupsEntry 10 }
- sPDUOutletConfigMSPmupsP1LowTemp OBJECT-TYPE
- SYNTAX INTEGER {
- disableAlarm (1),
- enableAlarm (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Setting this OID to disableAlarm (1) disables the
- Probe 1 low temperature alarm for this outlet.
- Setting this OID to enableAlarm (2) enables the
- Probe 1 low temperature alarm for this outlet."
- ::= { sPDUOutletConfigMSPmupsEntry 11 }
- sPDUOutletConfigMSPmupsP1HiTemp OBJECT-TYPE
- SYNTAX INTEGER {
- disableAlarm (1),
- enableAlarm (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Setting this OID to disableAlarm (1) disables the
- Probe 1 high temperature alarm for this outlet.
- Setting this OID to enableAlarm (2) enables the
- Probe 1 high temperature alarm for this outlet."
- ::= { sPDUOutletConfigMSPmupsEntry 12 }
- sPDUOutletConfigMSPmupsP2LowHum OBJECT-TYPE
- SYNTAX INTEGER {
- disableAlarm (1),
- enableAlarm (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Setting this OID to disableAlarm (1) disables the
- Probe 2 low humidity alarm for this outlet.
- Setting this OID to enableAlarm (2) enables the
- Probe 2 low humidity alarm for this outlet."
- ::= { sPDUOutletConfigMSPmupsEntry 13 }
- sPDUOutletConfigMSPmupsP2HiHum OBJECT-TYPE
- SYNTAX INTEGER {
- disableAlarm (1),
- enableAlarm (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Setting this OID to disableAlarm (1) disables the
- Probe 2 high humidity alarm for this outlet.
- Setting this OID to enableAlarm (2) enables the
- Probe 2 high humidity alarm for this outlet."
- ::= { sPDUOutletConfigMSPmupsEntry 14 }
- sPDUOutletConfigMSPmupsP2LowTemp OBJECT-TYPE
- SYNTAX INTEGER {
- disableAlarm (1),
- enableAlarm (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Setting this OID to disableAlarm (1) disables the
- Probe 2 low temperature alarm for this outlet.
- Setting this OID to enableAlarm (2) enables the
- Probe 2 low temperature alarm for this outlet."
- ::= { sPDUOutletConfigMSPmupsEntry 15 }
- sPDUOutletConfigMSPmupsP2HiTemp OBJECT-TYPE
- SYNTAX INTEGER {
- disableAlarm (1),
- enableAlarm (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Setting this OID to disableAlarm (1) disables the
- Probe 2 high temperature alarm for this outlet.
- Setting this OID to enableAlarm (2) enables the
- Probe 2 high temperature alarm for this outlet."
- ::= { sPDUOutletConfigMSPmupsEntry 16 }
- -- the sPDUOutletStatusMSP group
-
- sPDUOutletStatusMSPTable OBJECT-TYPE
- SYNTAX SEQUENCE OF SPDUOutletStatusMSPEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting of status of individual outlets. The number of
- entries is contained in the sPDUMasterStatusOutletCount OID."
- ::= { sPDUOutletStatusMSP 1 }
- sPDUOutletStatusMSPEntry OBJECT-TYPE
- SYNTAX SPDUOutletStatusMSPEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The outlets to gather status from."
- INDEX { sPDUOutletStatusMSPIndex, sPDUOutletStatusMSPOutletIndex }
- ::= { sPDUOutletStatusMSPTable 1 }
- SPDUOutletStatusMSPEntry ::=
- SEQUENCE {
- sPDUOutletStatusMSPIndex INTEGER,
- sPDUOutletStatusMSPName DisplayString,
- sPDUOutletStatusMSPOutletIndex INTEGER,
- sPDUOutletStatusMSPOutletName DisplayString,
- sPDUOutletStatusMSPOutletState INTEGER,
- sPDUOutletStatusMSPCommandPending INTEGER,
- sPDUOutletStatusMSPOutletCtrlMode INTEGER
- }
- sPDUOutletStatusMSPIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the MasterSwitch MSP."
- ::= { sPDUOutletStatusMSPEntry 1 }
- sPDUOutletStatusMSPName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The name of the MasterSwitch plus. The maximum
- value is 23 characters. The name is set by
- using the sPDUMasterConfigMSPName OID."
- ::= { sPDUOutletStatusMSPEntry 2 }
- sPDUOutletStatusMSPOutletIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the outlet entry."
- ::= { sPDUOutletStatusMSPEntry 3 }
-
- sPDUOutletStatusMSPOutletName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The name of the outlet. The maximum size is
- 23 characters. The name is set by using the
- sPDUOutletConfigMSPallOutletName OID.
- This OID is provided for informational purposes only."
- ::= { sPDUOutletStatusMSPEntry 4 }
- sPDUOutletStatusMSPOutletState OBJECT-TYPE
- SYNTAX INTEGER {
- outletStatusMSPOn (1),
- outletStatusMSPOff (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this variable will return the outlet state. If
- the outlet is on, the outletStatusMSPOn (1) value will be returned.
- If the outlet is off, the outletStatusMSPOff (2) value will be
- returned. "
- ::= { sPDUOutletStatusMSPEntry 5 }
- sPDUOutletStatusMSPCommandPending OBJECT-TYPE
- SYNTAX INTEGER {
- outletStatusMSPCommandPending (1),
- outletStatusMSPNoCommandPending (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this variable will return the command pending
- state of the outlet. If a command is pending on the
- outlet, the outletStatusMSPCommandPending (1) value
- will be returned. If there is not a command pending
- on the outlet, the outletStatusMSPNoCommandPending (2)
- will be returned."
- ::= { sPDUOutletStatusMSPEntry 6 }
- sPDUOutletStatusMSPOutletCtrlMode OBJECT-TYPE
- SYNTAX INTEGER {
- modeGracefulShutdown (1),
- modeAnnunciator (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The Control Mode of the outlet.
- This OID is provided for informational purposes only."
- ::= { sPDUOutletStatusMSPEntry 7 }
- -- the rPDUIdent group
- rPDUIdentName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The name of the Rack PDU.
- The maximum string size is device dependent."
- ::= { rPDUIdent 1 }
- rPDUIdentHardwareRev OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The hardware revision of the Rack PDU.
- This value is set at the factory."
- ::= { rPDUIdent 2 }
- rPDUIdentFirmwareRev OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "An 8-byte ID string identifying the Rack PDU firmware revision.
- This value is set at the factory."
- ::= { rPDUIdent 3 }
- rPDUIdentDateOfManufacture OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The date when the Rack PDU was manufactured in mm/dd/yyyy format.
- This value is set at the factory. The year 2000 will be
- represented by 00."
- ::= { rPDUIdent 4 }
-
- rPDUIdentModelNumber OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A 10-character string identifying the model number of
- the Rack PDU. This value is set at the factory."
- ::= { rPDUIdent 5 }
- rPDUIdentSerialNumber OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A 12-character string identifying the serial number of
- the Rack PDU. This value is set at the factory."
- ::= { rPDUIdent 6 }
- rPDUIdentDeviceRating OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return the electrical rating of the device."
- ::= { rPDUIdent 7 }
- rPDUIdentDeviceNumOutlets OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return the number of outlets contained in the device."
- ::= { rPDUIdent 8 }
- rPDUIdentDeviceNumPhases OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return the number of phases supported by the device."
- ::= { rPDUIdent 9 }
- rPDUIdentDeviceNumBreakers OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return the number of circuit breakers supported by the device.
- This is the same as the number of banks of outlets.
- 0 will be returned if the unit has no phase breakers. "
- ::= { rPDUIdent 10 }
- rPDUIdentDeviceBreakerRating OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return rating of the circuit breakers
- on the device in Amps if it has any."
- ::= { rPDUIdent 11 }
- rPDUIdentDeviceOrientation OBJECT-TYPE
- SYNTAX INTEGER {
- orientHorizontal (1),
- orientVertical (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return the intended physical orientation of the device.
-
- OrientHorizonatal(1) indicates Horizontal.
- OrientVertical(2) indicates Vertical."
- ::= { rPDUIdent 12 }
-
- rPDUIdentDeviceOutletLayout OBJECT-TYPE
- SYNTAX INTEGER {
- seqPhaseToNeutral (1),
- seqPhaseToPhase (2),
- seqPhToNeu21PhToPh (3),
- seqPhToPhGrouped (4),
- seqPhToNGrouped (5),
- seqPToN1516PToPGrouped (6)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return outlet layout for the device.
-
- SeqPhaseToNeutral(1) indicates outlet layout as follows:
- 1:1-N,2:2-N,3:3-N,4:1-N,5:2-N,...
- SeqPhaseToPhase(2) indicates outlet layout as follows:
- 1:1-2,2:2-3,3:3-1,4:1-2,5:2-3,...
- SeqPhToNeu21PhToPh(3) indicates outlet layout as follows:
- 1:1-N,2:2-N...21:3-N,22:1-2,23:2-3,24:3-1,...
- SeqPhToPhGrouped(4) indicates outlet layout as follows:
- Otlts1-8::(3-1),Otlts9-16::(2-3),Otlts17-24::(1-2).
- SeqPhToNGrouped(5) indicates outlet layout as follows:
- Otlts1-[X-1]::(1-N),OtltsX-[Y-1]::(2-N),OtltsY-[Z-1]::(3-N).
- SeqPToN1516PToPGrouped(6) indicates outlet layout as follows:
- Otlts1-14::(1-2),Otlts15-16::(1-N),OtltsX-[Y-1]::(2-3),OtltsY-[Z-1]::(3-1)"
- ::= { rPDUIdent 13 }
- rPDUIdentDeviceDisplayOrientation OBJECT-TYPE
- SYNTAX INTEGER {
- displayNormal (1),
- displayReverse (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return the intended physical orientation of the Seven-Segment Display.
-
- Normal(1) indicates Normal.
- Reverse(2)indicates Upside-Down."
- ::= { rPDUIdent 14 }
- rPDUIdentDeviceLinetoLineVoltage OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Getting/Setting this OID will return/set the Line to Line Volatage.
- The valid range is between 0V to 440V"
- ::= { rPDUIdent 15 }
- rPDUIdentDevicePowerWatts OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return the Power in Watts."
- ::= { rPDUIdent 16 }
- rPDUIdentDevicePowerFactor OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Getting/setting this OID will return/set the
- Power Factor in thousanths (1000 is power factor of 1).
- Valid range is from 0 to 1000."
-
- ::= { rPDUIdent 17 }
- rPDUIdentDevicePowerVA OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return the Power in VA."
- ::= { rPDUIdent 18 }
- -- the rPDULoadDevice group
- rPDULoadDevMaxPhaseLoad OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return the maximum rated power
- that each phase of the Rack PDU can provide. It is
- represented in Amps.
- 0 will be returned if the unit is banked."
- ::= { rPDULoadDevice 1 }
- rPDULoadDevNumPhases OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of phases available with this Rack PDU."
- ::= { rPDULoadDevice 2 }
- rPDULoadDevMaxBankLoad OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return the maximum rated power
- that a bank of the Rack PDU can provide. It is
- represented in Amps.
-
- 0 will be returned if the device does not have any banks."
-
- ::= { rPDULoadDevice 3 }
- rPDULoadDevNumBanks OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of banks of outlets available with this Rack PDU.
- A bank of outlets has a unique circuit breaker for a subset
- of the total number of outlets on the rPDU.
- 0 will be returned if the unit has no banks."
- ::= { rPDULoadDevice 4 }
-
- rPDULoadDevBankTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The size of the Bank Table."
- ::= { rPDULoadDevice 5 }
-
- rPDULoadDevBankTable OBJECT-TYPE
- SYNTAX SEQUENCE OF RPDULoadDevBankEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting the Bank Max Load in the Rack PDU."
- ::= { rPDULoadDevice 6 }
- rPDULoadDevBankEntry OBJECT-TYPE
- SYNTAX RPDULoadDevBankEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The Rack PDU Banks Access."
- INDEX { rPDULoadDevBankIndex}
- ::= { rPDULoadDevBankTable 1 }
- RPDULoadDevBankEntry ::=
- SEQUENCE {
- rPDULoadDevBankIndex INTEGER,
- rPDULoadDevBankNumber INTEGER,
- rPDULoadDevBankMaxLoad INTEGER
- }
- rPDULoadDevBankIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the Rack PDU bank entry."
- ::= { rPDULoadDevBankEntry 1 }
- rPDULoadDevBankNumber OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return the bank number."
-
- ::= { rPDULoadDevBankEntry 2 }
- rPDULoadDevBankMaxLoad OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return the maximum rated power
- that each bank of the Rack PDU can provide. It is
- represented in Amps."
-
- ::= { rPDULoadDevBankEntry 3 }
- rPDULoadDevMaxOutletTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The size of the Outlet Table."
- ::= { rPDULoadDevice 7 }
-
-
- rPDULoadDevMaxOutletTable OBJECT-TYPE
- SYNTAX SEQUENCE OF RPDULoadDevMaxOutletEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting the Max Outlet Load in an Outlet Monitored Rack PDU."
- ::= { rPDULoadDevice 8 }
- rPDULoadDevMaxOutletEntry OBJECT-TYPE
- SYNTAX RPDULoadDevMaxOutletEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "This gives access to Max Outlet Load of an Outlet Monitored Rack PDU"
- INDEX { rPDULoadDevOutletIndex}
- ::= { rPDULoadDevMaxOutletTable 1 }
- RPDULoadDevMaxOutletEntry ::=
- SEQUENCE {
- rPDULoadDevOutletIndex INTEGER,
- rPDULoadDevOutletNumber INTEGER,
- rPDULoadDevMaxOutletLoad INTEGER
- }
- rPDULoadDevOutletIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the Outlet Monitored Rack PDU Max Outlet Load entry."
- ::= { rPDULoadDevMaxOutletEntry 1 }
- rPDULoadDevOutletNumber OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return the Outlet number."
- ::= { rPDULoadDevMaxOutletEntry 2 }
-
- rPDULoadDevMaxOutletLoad OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return the maximum rated power
- that each Outlet of an Outlet Monitored Rack PDU can provide. It is
- represented in Amps. "
- ::= { rPDULoadDevMaxOutletEntry 3 }
- -- the rPDULoadPhaseConfig group
- rPDULoadPhaseConfigTable OBJECT-TYPE
- SYNTAX SEQUENCE OF RPDULoadPhaseConfigEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for configuration of each Rack PDU phase.
- The number of entries is contained in the
- rPDULoadDevNumPhases OID."
- ::= { rPDULoadPhaseConfig 1 }
- rPDULoadPhaseConfigEntry OBJECT-TYPE
- SYNTAX RPDULoadPhaseConfigEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The Rack PDU phase to configure."
- INDEX { rPDULoadPhaseConfigIndex}
- ::= { rPDULoadPhaseConfigTable 1 }
- RPDULoadPhaseConfigEntry ::=
- SEQUENCE {
- rPDULoadPhaseConfigIndex INTEGER,
- rPDULoadPhaseConfigLowLoadThreshold INTEGER,
- rPDULoadPhaseConfigNearOverloadThreshold INTEGER,
- rPDULoadPhaseConfigOverloadThreshold INTEGER,
- rPDULoadPhaseConfigAlarm INTEGER
- }
- rPDULoadPhaseConfigIndex OBJECT-TYPE
- SYNTAX INTEGER {
- phase1 (1),
- phase2 (2),
- phase3 (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the Rack PDU phase entry."
- ::= { rPDULoadPhaseConfigEntry 1 }
- rPDULoadPhaseConfigLowLoadThreshold OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "A threshold that indicates the power consumption of
- the load is nearing a low consumption condition. It is
- represented in Amps. A warning will be issued when the
- load is less than the threshold value.
-
- A threshold value of 0 Amps effectively disables this
- warning.
-
- Maximum value must be less than the value returned
- by the rPDULoadPhaseConfigNearOverloadThreshold OID."
- ::= { rPDULoadPhaseConfigEntry 2 }
- rPDULoadPhaseConfigNearOverloadThreshold OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "A threshold that indicates the power consumption of
- the load is nearing an overload condition. It is
- represented in Amps. A warning will be issued when the
- load is greater than or equal to the threshold value.
-
- Minimum value must be greater than the value returned by
- the rPDULoadPhaseConfigLowLoadThreshold OID.
-
- Maximum value must be less than or equal to the value
- returned by the rPDULoadPhaseConfigOverloadThreshold OID."
- ::= { rPDULoadPhaseConfigEntry 3 }
- rPDULoadPhaseConfigOverloadThreshold OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "A threshold that indicates the power consumption of
- the load has entered an overload condition. It is
- represented in Amps. A warning will be issued when the
- load is greater than or equal to the threshold value.
-
- Minimum value must be greater than or equal to the value
- returned by the rPDULoadPhaseConfigNearOverloadThreshold OID.
-
- Maximum value must be less than or equal to the value
- returned by the rPDULoadDevMaxPhaseLoad OID."
- ::= { rPDULoadPhaseConfigEntry 4 }
- rPDULoadPhaseConfigAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- noLoadAlarm (1),
- underCurrentAlarm (2),
- nearOverCurrentAlarm (3),
- overCurrentAlarm (4)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return the current Phase Alarm."
- ::= { rPDULoadPhaseConfigEntry 5 }
- -- the rPDULoadStatus group
- rPDULoadStatusTable OBJECT-TYPE
- SYNTAX SEQUENCE OF RPDULoadStatusEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting of status of each Rack PDU phase/bank.
- The number of entries is calculated by adding
- the number of phases (rPDULoadDevNumPhases OID) and
- the number of banks of outlets (rPDULoadDevNumBanks)
- Number of entries = #phases + #banks.
- NOTE: If a device has phase and bank information, all phase information
- shall precede the bank information. If a device has total information,
- it shall precede both the bank and the phase information."
- ::= { rPDULoadStatus 1 }
- rPDULoadStatusEntry OBJECT-TYPE
- SYNTAX RPDULoadStatusEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The Rack PDU phase/bank to gather status from."
- INDEX { rPDULoadStatusIndex}
- ::= { rPDULoadStatusTable 1 }
- RPDULoadStatusEntry ::=
- SEQUENCE {
- rPDULoadStatusIndex INTEGER,
- rPDULoadStatusLoad Gauge,
- rPDULoadStatusLoadState INTEGER,
- rPDULoadStatusPhaseNumber INTEGER,
- rPDULoadStatusBankNumber INTEGER
- }
- rPDULoadStatusIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the Rack PDU phase/bank entry. All phase information will precede
- any bank information"
- ::= { rPDULoadStatusEntry 1 }
- rPDULoadStatusLoad OBJECT-TYPE
- SYNTAX Gauge
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return the phase/bank load measured
- in tenths of Amps."
- ::= { rPDULoadStatusEntry 2 }
- rPDULoadStatusLoadState OBJECT-TYPE
- SYNTAX INTEGER {
- phaseLoadNormal (1),
- phaseLoadLow (2),
- phaseLoadNearOverload (3),
- phaseLoadOverload (4)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return the phase/bank load state.
-
- phaseLoadNormal(1) indicates that the phase/bank is
- operating properly within the rPDULoadConfigLowLoadThreshold
- and rPDULoadConfigNearOverloadThreshold OID values.
-
- phaseLoadLow(2) indicates that the phase/bank load has
- dropped below the rPDULoadConfigLowLoadThreshold OID value.
- An SNMP trap will occur when this state is entered or cleared.
-
- phaseLoadNearOverload(3) indicates that the phase/bank load
- is greater than or equal to the
- rPDULoadConfigNearOverloadThreshold OID value.
- An SNMP trap will occur when this state is entered or cleared.
-
- phaseLoadOverload(4) indicates that the phase/bank load is
- greater than or equal to the rPDULoadConfigOverloadThreshold
- OID value.
- An SNMP trap will occur when this state is entered or cleared."
- ::= { rPDULoadStatusEntry 3 }
- rPDULoadStatusPhaseNumber OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The phase number to which this record refers."
- ::= { rPDULoadStatusEntry 4 }
- rPDULoadStatusBankNumber OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The bank number to which this record refers. A value of 0 will be returned if
- any bank is not present or if it is phase related."
- ::= { rPDULoadStatusEntry 5 }
-
-
- -- the rPDULoadBankConfig group
- rPDULoadBankConfigTable OBJECT-TYPE
- SYNTAX SEQUENCE OF RPDULoadBankConfigEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for configuration of each Rack PDU bank.
- The number of entries is contained in the
- rPDULoadDevNumBanks OID."
- ::= { rPDULoadBankConfig 1 }
- rPDULoadBankConfigEntry OBJECT-TYPE
- SYNTAX RPDULoadBankConfigEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The Rack PDU bank to configure."
- INDEX { rPDULoadBankConfigIndex}
- ::= { rPDULoadBankConfigTable 1 }
- RPDULoadBankConfigEntry ::=
- SEQUENCE {
- rPDULoadBankConfigIndex INTEGER,
- rPDULoadBankConfigLowLoadThreshold INTEGER,
- rPDULoadBankConfigNearOverloadThreshold INTEGER,
- rPDULoadBankConfigOverloadThreshold INTEGER,
- rPDULoadBankConfigAlarm INTEGER
- }
- rPDULoadBankConfigIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the Rack PDU bank entry."
- ::= { rPDULoadBankConfigEntry 1 }
- rPDULoadBankConfigLowLoadThreshold OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "A threshold that indicates the power consumption of
- the load is nearing a low consumption condition. It is
- represented in Amps. A warning will be issued when the
- load is less than the threshold value.
-
- A threshold value of 0 Amps effectively disables this
- warning.
-
- Maximum value must be less than the value returned
- by the rPDULoadBankConfigNearOverloadThreshold OID."
- ::= { rPDULoadBankConfigEntry 2 }
- rPDULoadBankConfigNearOverloadThreshold OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "A threshold that indicates the power consumption of
- the load is nearing an overload condition. It is
- represented in Amps. A warning will be issued when the
- load is greater than or equal to the threshold value.
-
- Minimum value must be greater than the value returned by
- the rPDULoadBankConfigLowLoadThreshold OID.
-
- Maximum value must be less than or equal to the value
- returned by the rPDULoadBankConfigOverloadThreshold OID."
- ::= { rPDULoadBankConfigEntry 3 }
- rPDULoadBankConfigOverloadThreshold OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "A threshold that indicates the power consumption of
- the load has entered an overload condition. It is
- represented in Amps. A warning will be issued when the
- load is greater than or equal to the threshold value.
-
- Minimum value must be greater than or equal to the value
- returned by the rPDULoadBankConfigNearOverloadThreshold OID.
-
- Maximum value must be less than or equal to the value
- returned by the rPDULoadDevMaxBankLoad OID."
- ::= { rPDULoadBankConfigEntry 4 }
- rPDULoadBankConfigAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- noLoadAlarm (1),
- underCurrentAlarm (2),
- nearOverCurrentAlarm (3),
- overCurrentAlarm (4)
-
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- " Getting this OID will return the current Bank Alarm."
- ::= { rPDULoadBankConfigEntry 5 }
- -- the rPDUOutletDevice group
- rPDUOutletDevCommand OBJECT-TYPE
- SYNTAX INTEGER {
- noCommandAll (1),
- immediateAllOn (2),
- immediateAllOff (3),
- immediateAllReboot (4),
- delayedAllOn (5),
- delayedAllOff (6),
- delayedAllReboot (7),
- cancelAllPendingCommands (8)
- }
-
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Setting this OID to immediateAllOn (2) will turn all outlets
- on immediately.
-
- Setting this OID to immediateAllOff (3) will turn all outlets
- off immediately.
-
- Setting this OID to immediateAllReboot (4) will reboot all outlets
- immediately.
- Setting this OID to delayedAllOn (5) will turn all outlets on as
- defined by each outlet's rPDUOutletConfigPowerOnTime OID value.
-
- Setting this OID to delayedAllOff (6) will turn all outlets
- off as defined by each outlet's rPDUOutletConfigPowerOffTime OID value.
-
- Setting this OID to delayedAllReboot (7) will cause a
- delayedAllOff command to be performed. Once all outlets are off,
- the Switched Rack PDU will then delay the largest
- rPDUOutletConfigRebootDuration OID time, and then perform a
- delayedAllOn command.
-
- Setting this OID to cancelAllPendingCommands (8) will cause all pending
- commands on the Switched Rack PDU to be canceled.
- Getting this OID will return the noCommandAll (1) value."
- ::= { rPDUOutletDevice 1 }
- rPDUOutletDevColdstartDelay OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The amount of delay, in seconds, between when
- power is provided to the Switched Rack PDU and
- when the Switched Rack PDU provides basic master
- power to the outlets.
-
- Allowed values are:
- -1 - never apply power automatically.
- 0 - apply power immediately.
- 1 to 300 - delay up to 300 seconds (5 minutes)."
- ::= { rPDUOutletDevice 2 }
- rPDUOutletDevNumCntrlOutlets OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of controlled outlets on this Switched Rack PDU."
- ::= { rPDUOutletDevice 3 }
- rPDUOutletDevNumTotalOutlets OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The total number of outlets on this Rack PDU."
- ::= { rPDUOutletDevice 4 }
- rPDUOutletDevMonitoredOutlets OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The total number of monitored outlets on this Rack PDU."
- ::= { rPDUOutletDevice 5 }
-
- -- the rPDUOutletPhase group
- rPDUOutletPhaseTable OBJECT-TYPE
- SYNTAX SEQUENCE OF RPDUOutletPhaseEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for management of outlets on a per phase basis."
- ::= { rPDUOutletPhase 1 }
- rPDUOutletPhaseEntry OBJECT-TYPE
- SYNTAX RPDUOutletPhaseEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The phase to manage."
- INDEX { rPDUOutletPhaseIndex}
- ::= { rPDUOutletPhaseTable 1 }
- RPDUOutletPhaseEntry ::=
- SEQUENCE {
- rPDUOutletPhaseIndex INTEGER,
- rPDUOutletPhaseOverloadRestriction INTEGER
- }
- rPDUOutletPhaseIndex OBJECT-TYPE
- SYNTAX INTEGER {
- phase1 (1),
- phase2 (2),
- phase3 (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the Switched Rack PDU phase entry."
- ::= { rPDUOutletPhaseEntry 1 }
- rPDUOutletPhaseOverloadRestriction OBJECT-TYPE
- SYNTAX INTEGER {
- alwaysAllowTurnON (1),
- restrictOnNearOverload (2),
- restrictOnOverload (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "This OID controls the behavior of a Switched Rack PDU
- phase when an overload condition is possible and
- additional outlets are requested to be turned on.
- Setting this OID to alwaysAllowTurnON (1) will always allow
- the outlets on the corresponding phase to turn on.
-
- Setting this OID to restrictOnNearOverload (2) will not allow
- outlets on the corresponding phase to turn on if the
- rPDULoadConfigNearOverloadThreshold OID is exceeded.
-
- Setting this OID to restrictOnOverload (3) will not allow
- outlets on the corresponding phase to turn on if the
- rPDULoadConfigOverloadThreshold OID is exceeded."
- ::= { rPDUOutletPhaseEntry 2 }
- -- the rPDUOutletControl group
- rPDUOutletControlTable OBJECT-TYPE
- SYNTAX SEQUENCE OF RPDUOutletControlEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for control of the individual outlets.
- The number of entries is contained in the
- rPDUOutletDevNumCntrlOutlets OID."
- ::= { rPDUOutletControl 1 }
- rPDUOutletControlEntry OBJECT-TYPE
- SYNTAX RPDUOutletControlEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The outlet to control."
- INDEX { rPDUOutletControlIndex}
- ::= { rPDUOutletControlTable 1 }
- RPDUOutletControlEntry ::=
- SEQUENCE {
- rPDUOutletControlIndex INTEGER,
- rPDUOutletControlOutletName DisplayString,
- rPDUOutletControlOutletPhase INTEGER,
- rPDUOutletControlOutletCommand INTEGER,
- rPDUOutletControlOutletBank INTEGER
- }
- rPDUOutletControlIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the outlet entry."
- ::= { rPDUOutletControlEntry 1 }
-
- rPDUOutletControlOutletName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The name of the outlet. The maximum string size is device dependent.
- An error will be returned if the set request exceeds the max size.
- This OID is provided for informational purposes only."
- ::= { rPDUOutletControlEntry 2 }
- rPDUOutletControlOutletPhase OBJECT-TYPE
- SYNTAX INTEGER {
- phase1 (1),
- phase2 (2),
- phase3 (3),
- phase1-2 (4),
- phase2-3 (5),
- phase3-1 (6)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The phase/s associated with this outlet.
-
- For single phase devices, this object will always
- return phase1(1).
-
- For 3-phase devices, this object will return phase1 (1),
- phase2 (2), or phase3 (3) for outlets tied to a single
- phase. For outlets tied to two phases, this object will
- return phase1-2 (4) for phases 1 and 2, phase2-3 (5) for
- phases 2 and 3, and phase3-1 (6) for phases 3 and 1."
- ::= { rPDUOutletControlEntry 3 }
- rPDUOutletControlOutletCommand OBJECT-TYPE
- SYNTAX INTEGER {
- immediateOn (1),
- immediateOff (2),
- immediateReboot (3),
- delayedOn (4),
- delayedOff (5),
- delayedReboot (6),
- cancelPendingCommand (7)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Getting this variable will return the outlet state. If
- the outlet is on, the immediateOn (1) value will be returned.
- If the outlet is off, the immediateOff (2) value will be
- returned.
-
-
- Setting this variable to immediateOn (1) will immediately turn
- the outlet on.
-
- Setting this variable to immediateOff (2) will immediately turn
- the outlet off.
- Setting this variable to immediateReboot (3) will immediately
- reboot the outlet.
-
- Setting this variable to delayedOn (4) will turn the outlet on
- after the rPDUOutletConfigPowerOnTime OID time has elapsed.
- Setting this variable to delayedOff (5) will turn the outlet off
- after the rPDUOutletConfigPowerOffTime OID time has elapsed.
- Setting this variable to delayedReboot (6) will cause the
- Switched Rack PDU to perform a delayedOff command, wait the
- rPDUOutletConfigRebootDuration OID time, and then perform a
- delayedOn command.
-
- Setting this variable to cancelPendingCommand (7) will cause any
- pending command to this outlet to be canceled."
- ::= { rPDUOutletControlEntry 4 }
- rPDUOutletControlOutletBank OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The bank associated with this outlet."
- ::= { rPDUOutletControlEntry 5 }
- -- the rPDUOutletConfig group
- rPDUOutletConfigTable OBJECT-TYPE
- SYNTAX SEQUENCE OF RPDUOutletConfigEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for configuration of individual outlets. The number of
- entries is contained in the rPDUOutletDevNumCntrlOutlets OID."
- ::= { rPDUOutletConfig 1 }
- rPDUOutletConfigEntry OBJECT-TYPE
- SYNTAX RPDUOutletConfigEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The outlet to configure."
- INDEX { rPDUOutletConfigIndex}
- ::= { rPDUOutletConfigTable 1 }
- RPDUOutletConfigEntry ::=
- SEQUENCE {
- rPDUOutletConfigIndex INTEGER,
- rPDUOutletConfigOutletName DisplayString,
- rPDUOutletConfigOutletPhase INTEGER,
- rPDUOutletConfigPowerOnTime INTEGER,
- rPDUOutletConfigPowerOffTime INTEGER,
- rPDUOutletConfigRebootDuration INTEGER,
- rPDUOutletConfigOutletBank INTEGER
- }
- rPDUOutletConfigIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the outlet entry."
- ::= { rPDUOutletConfigEntry 1 }
-
- rPDUOutletConfigOutletName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The name of the outlet. The maximum string size is device dependent.
- An error will be returned if the set request exceeds the max size."
- ::= { rPDUOutletConfigEntry 2 }
- rPDUOutletConfigOutletPhase OBJECT-TYPE
- SYNTAX INTEGER {
- phase1 (1),
- phase2 (2),
- phase3 (3),
- phase1-2 (4),
- phase2-3 (5),
- phase3-1 (6)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The phase/s associated with this outlet.
-
- For single phase devices, this object will always
- return phase1(1).
-
- For 3-phase devices, this object will return phase1 (1),
- phase2 (2), or phase3 (3) for outlets tied to a single
- phase. For outlets tied to two phases, this object will
- return phase1-2 (4) for phases 1 and 2, phase2-3 (5) for
- phases 2 and 3, and phase3-1 (6) for phases 3 and 1."
- ::= { rPDUOutletConfigEntry 3 }
- rPDUOutletConfigPowerOnTime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The amount of time (in seconds) the outlet will delay
- powering on at coldstart or when a command that requires
- a turn-on delay is issued.
-
- Allowed values are:
- -1 - never power on.
- 0 - power on immediately.
- 1 to 7200 - power on up to 7200 seconds after being
- commanded."
- ::= { rPDUOutletConfigEntry 4 }
- rPDUOutletConfigPowerOffTime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The amount of time (in seconds) the outlet will delay
- powering off when a command that requires
- a turn-off delay is issued.
- Allowed values are:
- -1 - never power off.
- 0 - power off immediately.
- 1 to 7200 - power off up to 7200 seconds after being
- commanded."
- ::= { rPDUOutletConfigEntry 5 }
- rPDUOutletConfigRebootDuration OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "During a reboot sequence, power is turned off and then
- back on. This OID defines the amount of time to wait,
- in seconds, after turning the power off, at the start
- of the sequence, before turning power back on, at the
- end of the reboot sequence.
-
- Allowed range is any value between 5 and 60 seconds (1 minute)."
- ::= { rPDUOutletConfigEntry 6 }
- rPDUOutletConfigOutletBank OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The bank associated with this outlet."
- ::= { rPDUOutletConfigEntry 7 }
- -- Monitored Outlets table
- rPDUOutletConfigMonitoredTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The size of the Outlet Config Monitored Table"
- ::= { rPDUOutletConfig 2 }
- rPDUOutletConfigMonitoredTable OBJECT-TYPE
- SYNTAX SEQUENCE OF RPDUOutletConfigMonitoredEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting/setting of outlet thresholds of an Outlet Monitored Rack PDU."
- ::= { rPDUOutletConfig 3 }
-
- rPDUOutletConfigMonitoredEntry OBJECT-TYPE
- SYNTAX RPDUOutletConfigMonitoredEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "This gives access to Monitored Outlet entries"
- INDEX { rPDUOutletConfigMonitoredIndex }
- ::= { rPDUOutletConfigMonitoredTable 1 }
- RPDUOutletConfigMonitoredEntry ::=
- SEQUENCE {
- rPDUOutletConfigMonitoredIndex INTEGER,
- rPDUOutletConfigMonitoredName DisplayString,
- rPDUOutletConfigMonitoredNumber INTEGER,
- rPDUOutletConfigMonitoredLowLoadThreshold INTEGER,
- rPDUOutletConfigMonitoredNearOverloadThreshold INTEGER,
- rPDUOutletConfigMonitoredOverloadThreshold INTEGER
- }
-
- rPDUOutletConfigMonitoredIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the RACK PDU Phase entry."
- ::= { rPDUOutletConfigMonitoredEntry 1 }
-
- rPDUOutletConfigMonitoredName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The name of the Monitored Outlet. The maximum string size is device dependent.
- An error will be returned if the set request exceeds the max size."
- ::= { rPDUOutletConfigMonitoredEntry 2 }
- rPDUOutletConfigMonitoredNumber OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The outlet number of an Outlet Monitored RACK PDU."
- ::= { rPDUOutletConfigMonitoredEntry 3 }
- rPDUOutletConfigMonitoredLowLoadThreshold OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "A threshold that indicates the power consumption of
- the load is nearing a low consumption condition. It is
- represented in Amps. A warning will be issued when the
- load is less than the threshold value.
-
- A threshold value of 0 Amps effectively disables this
- warning.
-
- Maximum value must be less than the value returned
- by the rPDUOutletConfigMonitoredNearOverloadThreshold OID.
-
- 0 will be returned if the unit is not Outlet Monitored Rack PDU."
- ::= { rPDUOutletConfigMonitoredEntry 4 }
- rPDUOutletConfigMonitoredNearOverloadThreshold OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "A threshold that indicates the power consumption of
- the load is nearing an overload condition. It is
- represented in Amps. A warning will be issued when the
- load is greater than or equal to the threshold value.
-
- Minimum value must be greater than the value returned by
- the rPDUOutletConfigMonitoredLowLoadThreshold OID.
-
- Maximum value must be less than or equal to the value
- returned by the rPDUOutletConfigMonitoredOverloadThreshold OID.
- 0 will be returned if the unit is not Outlet Monitored Rack PDU."
- ::= { rPDUOutletConfigMonitoredEntry 5 }
- rPDUOutletConfigMonitoredOverloadThreshold OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "A threshold that indicates the power consumption of
- the load has entered an overload condition. It is
- represented in Amps. A warning will be issued when the
- load is greater than or equal to the threshold value.
-
- Minimum value must be greater than or equal to the value
- returned by the rPDUOutletConfigMonitoredNearOverloadThreshold OID.
-
- Maximum value must be less than or equal to the value
- returned by the rPDULoadDevMaxOutletLoad OID.
- 0 will be returned if the unit is not Outlet Monitored Rack PDU."
- ::= { rPDUOutletConfigMonitoredEntry 6 }
- -- the rPDUOutletStatus group
- rPDUOutletStatusTable OBJECT-TYPE
- SYNTAX SEQUENCE OF RPDUOutletStatusEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting of status of individual outlets. The number of
- entries is contained in the rPDUOutletDevNumCntrlOutlets OID."
- ::= { rPDUOutletStatus 1 }
- rPDUOutletStatusEntry OBJECT-TYPE
- SYNTAX RPDUOutletStatusEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The outlet to gather status from."
- INDEX { rPDUOutletStatusIndex}
- ::= { rPDUOutletStatusTable 1 }
- RPDUOutletStatusEntry ::=
- SEQUENCE {
- rPDUOutletStatusIndex INTEGER,
- rPDUOutletStatusOutletName DisplayString,
- rPDUOutletStatusOutletPhase INTEGER,
- rPDUOutletStatusOutletState INTEGER,
- rPDUOutletStatusCommandPending INTEGER,
- rPDUOutletStatusOutletBank INTEGER,
- rPDUOutletStatusLoad Gauge
- }
- rPDUOutletStatusIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the outlet entry."
- ::= { rPDUOutletStatusEntry 1 }
-
- rPDUOutletStatusOutletName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The name of the outlet. The maximum string size is device dependent.
- This OID is provided for informational purposes only."
- ::= { rPDUOutletStatusEntry 2 }
- rPDUOutletStatusOutletPhase OBJECT-TYPE
- SYNTAX INTEGER {
- phase1 (1),
- phase2 (2),
- phase3 (3),
- phase1-2 (4),
- phase2-3 (5),
- phase3-1 (6)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The phase/s associated with this outlet.
-
- For single phase devices, this object will always
- return phase1(1).
-
- For 3-phase devices, this object will return phase1 (1),
- phase2 (2), or phase3 (3) for outlets tied to a single
- phase. For outlets tied to two phases, this object will
- return phase1-2 (4) for phases 1 and 2, phase2-3 (5) for
- phases 2 and 3, and phase3-1 (6) for phases 3 and 1."
- ::= { rPDUOutletStatusEntry 3 }
- rPDUOutletStatusOutletState OBJECT-TYPE
- SYNTAX INTEGER {
- outletStatusOn (1),
- outletStatusOff (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this variable will return the outlet state. If
- the outlet is on, the outletStatusOn (1) value will be returned.
- If the outlet is off, the outletStatusOff (2) value will be
- returned."
- ::= { rPDUOutletStatusEntry 4 }
- rPDUOutletStatusCommandPending OBJECT-TYPE
- SYNTAX INTEGER {
- outletStatusCommandPending (1),
- outletStatusNoCommandPending (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this variable will return the command pending
- state of the outlet. If a command is pending on the
- outlet, the outletStatusCommandPending (1) value
- will be returned. If there is not a command pending
- on the outlet, the outletStatusNoCommandPending (2)
- will be returned."
- ::= { rPDUOutletStatusEntry 5 }
- rPDUOutletStatusOutletBank OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The bank associated with this outlet."
- ::= { rPDUOutletStatusEntry 6 }
- rPDUOutletStatusLoad OBJECT-TYPE
- SYNTAX Gauge
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return the measured Outlet load for an Outlet Monitored Rack PDU
- in tenths of Amps."
- ::= { rPDUOutletStatusEntry 7 }
- -- the rPDUOutletBank group
- rPDUOutletBankTable OBJECT-TYPE
- SYNTAX SEQUENCE OF RPDUOutletBankEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for management of outlets on a per bank basis."
- ::= { rPDUOutletBank 1 }
- rPDUOutletBankEntry OBJECT-TYPE
- SYNTAX RPDUOutletBankEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The bank to manage."
- INDEX { rPDUOutletBankIndex}
- ::= { rPDUOutletBankTable 1 }
- RPDUOutletBankEntry ::=
- SEQUENCE {
- rPDUOutletBankIndex INTEGER,
- rPDUOutletBankOverloadRestriction INTEGER
- }
- rPDUOutletBankIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the Switched Rack PDU bank entry."
- ::= { rPDUOutletBankEntry 1 }
- rPDUOutletBankOverloadRestriction OBJECT-TYPE
- SYNTAX INTEGER {
- alwaysAllowTurnON (1),
- restrictOnNearOverload (2),
- restrictOnOverload (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "This OID controls the behavior of a Switched Rack PDU
- bank when an overload condition is possible and
- additional outlets are requested to be turned on.
- Setting this OID to alwaysAllowTurnON (1) will always allow
- the outlets on the corresponding bank to turn on.
-
- Setting this OID to restrictOnNearOverload (2) will not allow
- outlets on the corresponding bank to turn on if the
- rPDULoadBankConfigNearOverloadThreshold OID is exceeded.
-
- Setting this OID to restrictOnOverload (3) will not allow
- outlets on the corresponding bank to turn on if the
- rPDULoadBankConfigOverloadThreshold OID is exceeded."
- ::= { rPDUOutletBankEntry 2 }
- -- the rPDUPowerSupplyDevice group
- rPDUPowerSupply1Status OBJECT-TYPE
- SYNTAX INTEGER {
- powerSupplyOneOk (1),
- powerSupplyOneFailed (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return powerSupply1Ok(1) if power
- supply 1 is functioning normally. If not functioning normally,
- this OID will return powerSupply1Failed(2)."
- ::= { rPDUPowerSupplyDevice 1 }
- rPDUPowerSupply2Status OBJECT-TYPE
- SYNTAX INTEGER {
- powerSupplyTwoOk (1),
- powerSupplyTwoFailed (2),
- powerSupplyTwoNotPresent (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return powerSupply2Ok(1) if power
- supply 2 is functioning normally. If not functioning normally,
- this OID will return powerSupply2Failed(2).
- Metered Rack PDUs do not have a redundant powersupply."
-
- ::= { rPDUPowerSupplyDevice 2 }
- rPDUPowerSupplyAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- allAvailablePowerSuppliesOK (1),
- powerSupplyOneFailed (2),
- powerSupplyTwoFailed (3),
- powerSupplyOneandTwoFailed (4)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return powerSupply Alarm"
- ::= { rPDUPowerSupplyDevice 3 }
- -- the rPDUStatus group
- rPDUStatusBankTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The size of the Status Bank Table"
- ::= { rPDUStatus 1 }
- rPDUStatusBankTable OBJECT-TYPE
- SYNTAX SEQUENCE OF RPDUStatusBankEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting of status of each Rack PDU Bank"
- ::= { rPDUStatus 2 }
-
- rPDUStatusBankEntry OBJECT-TYPE
- SYNTAX RPDUStatusBankEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "This gives access to Bank entries"
- INDEX { rPDUStatusBankIndex }
- ::= { rPDUStatusBankTable 1 }
- RPDUStatusBankEntry ::=
- SEQUENCE {
- rPDUStatusBankIndex INTEGER,
- rPDUStatusBankNumber INTEGER,
- rPDUStatusBankState INTEGER
- }
-
- rPDUStatusBankIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the RACK PDU Bank entry."
- ::= { rPDUStatusBankEntry 1 }
-
- rPDUStatusBankNumber OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return the bank number."
- ::= { rPDUStatusBankEntry 2 }
-
- rPDUStatusBankState OBJECT-TYPE
- SYNTAX INTEGER {
- bankLoadNormal (1),
- bankLoadLow (2),
- bankLoadNearOverload (3),
- bankLoadOverload (4)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return the bank load state.
-
- bankLoadNormal(1) indicates that the bank is
- operating properly within the rPDULoadBankConfigLowLoadThreshold
- and rPDULoadBankConfigNearOverloadThreshold OID values.
-
- bankLoadLow(2) indicates that the bank load has
- dropped below the rPDULoadBankConfigLowLoadThreshold OID value.
- An SNMP trap will occur when this state is entered or cleared.
-
- bankLoadNearOverload(3) indicates that the bank load
- is greater than or equal to the
- rPDULoadBankConfigNearOverloadThreshold OID value.
- An SNMP trap will occur when this state is entered or cleared.
-
- bankLoadOverload(4) indicates that the bank load is
- greater than or equal to the rPDULoadBankConfigOverloadThreshold
- OID value.
- An SNMP trap will occur when this state is entered or cleared."
- ::= { rPDUStatusBankEntry 3 }
-
- -- Phase status table
- rPDUStatusPhaseTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The size of the Status Phase Table"
- ::= { rPDUStatus 3 }
- rPDUStatusPhaseTable OBJECT-TYPE
- SYNTAX SEQUENCE OF RPDUStatusPhaseEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting of status of each Rack PDU Phase"
- ::= { rPDUStatus 4 }
-
- rPDUStatusPhaseEntry OBJECT-TYPE
- SYNTAX RPDUStatusPhaseEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "This gives access to Phase entries"
- INDEX { rPDUStatusPhaseIndex }
- ::= { rPDUStatusPhaseTable 1 }
- RPDUStatusPhaseEntry ::=
- SEQUENCE {
- rPDUStatusPhaseIndex INTEGER,
- rPDUStatusPhaseNumber INTEGER,
- rPDUStatusPhaseState INTEGER
- }
-
- rPDUStatusPhaseIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the RACK PDU Phase entry."
- ::= { rPDUStatusPhaseEntry 1 }
-
- rPDUStatusPhaseNumber OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return the phase number."
- ::= { rPDUStatusPhaseEntry 2 }
-
- rPDUStatusPhaseState OBJECT-TYPE
- SYNTAX INTEGER {
- phaseLoadNormal (1),
- phaseLoadLow (2),
- phaseLoadNearOverload (3),
- phaseLoadOverload (4)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return the Phase load state.
-
- phaseLoadNormal(1) indicates that the Phase is
- operating properly within the rPDULoadPhaseConfigLowLoadThreshold
- and rPDULoadPhaseConfigNearOverloadThreshold OID values.
-
- phaseLoadLow(2) indicates that the Phase load has
- dropped below the rPDULoadPhaseConfigLowLoadThreshold OID value.
- An SNMP trap will occur when this state is entered or cleared.
-
- phaseLoadNearOverload(3) indicates that the Phase load
- is greater than or equal to the
- rPDULoadPhaseConfigNearOverloadThreshold OID value.
- An SNMP trap will occur when this state is entered or cleared.
-
- phaseLoadOverload(4) indicates that the Phase load is
- greater than or equal to the rPDULoadPhaseConfigOverloadThreshold
- OID value.
- An SNMP trap will occur when this state is entered or cleared."
- ::= { rPDUStatusPhaseEntry 3 }
- -- Outlet status table
- rPDUStatusOutletTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The size of the Status Outlet Table"
- ::= { rPDUStatus 5 }
- rPDUStatusOutletTable OBJECT-TYPE
- SYNTAX SEQUENCE OF RPDUStatusOutletEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting of status of each Outlet of an Outlet Monitored Rack PDU."
- ::= { rPDUStatus 6 }
-
- rPDUStatusOutletEntry OBJECT-TYPE
- SYNTAX RPDUStatusOutletEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "This gives access to Outlet entries"
- INDEX { rPDUStatusOutletIndex }
- ::= { rPDUStatusOutletTable 1 }
- RPDUStatusOutletEntry ::=
- SEQUENCE {
- rPDUStatusOutletIndex INTEGER,
- rPDUStatusOutletNumber INTEGER,
- rPDUStatusOutletState INTEGER
- }
-
- rPDUStatusOutletIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the RACK PDU Outlet entry."
- ::= { rPDUStatusOutletEntry 1 }
-
- rPDUStatusOutletNumber OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return the Outlet number."
- ::= { rPDUStatusOutletEntry 2 }
-
- rPDUStatusOutletState OBJECT-TYPE
- SYNTAX INTEGER {
- outletLoadNormal (1),
- outletLoadLow (2),
- outletLoadNearOverload (3),
- outletLoadOverload (4)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return the Outlet load state.
-
- outletLoadNormal(1) indicates that the Outlet is
- operating properly within the rPDUOutletConfigMonitoredLowLoadThreshold
- and rPDUOutletConfigMonitoredNearOverloadThreshold OID values.
-
- outletLoadLow(2) indicates that the Outlet load has
- dropped below the rPDUOutletConfigMonitoredLowLoadThreshold OID value.
- An SNMP trap will occur when this state is entered or cleared.
-
- outletLoadNearOverload(3) indicates that the Outlet load
- is greater than or equal to the
- rPDUOutletConfigMonitoredNearOverloadThreshold OID value.
- An SNMP trap will occur when this state is entered or cleared.
-
- outletLoadOverload(4) indicates that the Outlet load is
- greater than or equal to the rPDUOutletConfigMonitoredOverloadThreshold
- OID value.
- An SNMP trap will occur when this state is entered or cleared."
- ::= { rPDUStatusOutletEntry 3 }
- -- the dm3IdentSystem group
-
- dm3IdentSysDescriptionTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of DC description records."
- ::= { dm3IdentSystem 1 }
- dm3IdentSysDescriptionTable OBJECT-TYPE
- SYNTAX SEQUENCE OF Dm3IdentSysDescriptionEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for accessing description records of the powerplant. The number of
- entries is contained in the dm3IdentSysDescriptionTableSize OID."
- ::= { dm3IdentSystem 2 }
- dm3IdentSysDescriptionEntry OBJECT-TYPE
- SYNTAX Dm3IdentSysDescriptionEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The powerplant description record to reference."
- INDEX { dm3IdentSysDescriptionIndex }
- ::= { dm3IdentSysDescriptionTable 1 }
-
- Dm3IdentSysDescriptionEntry ::=
- SEQUENCE {
- dm3IdentSysDescriptionIndex INTEGER,
- dm3IdentSysDescriptionText DisplayString
- }
- dm3IdentSysDescriptionIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the DC powerplant description record."
- ::= { dm3IdentSysDescriptionEntry 1 }
- dm3IdentSysDescriptionText OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A 16 character text field describing the DC power plant device.
- This field can be configured from the dm3ConfigSysDescriptionText OID."
- ::= { dm3IdentSysDescriptionEntry 2 }
- dm3IdentSysModel OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Model type of the DC power plant."
- ::= { dm3IdentSystem 3 }
- dm3IdentSysCntrlRev OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Integer representation of the hardware revision of the Master Controller board."
- ::= { dm3IdentSystem 4 }
- dm3IdentSysFWVersion OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Integer representation of the power plant Master Controller firmware revision."
- ::= { dm3IdentSystem 5 }
-
- -- the dm3ConfigSystem group
- dm3ConfigSysDescriptionTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of DC description records."
- ::= { dm3ConfigSystem 1 }
- dm3ConfigSysDescriptionTable OBJECT-TYPE
- SYNTAX SEQUENCE OF Dm3ConfigSysDescriptionEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for accessing description records of the powerplant. The number of
- entries is contained in the dm3ConfigSysDescriptionTableSize OID."
- ::= { dm3ConfigSystem 2 }
- dm3ConfigSysDescriptionEntry OBJECT-TYPE
- SYNTAX Dm3ConfigSysDescriptionEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The powerplant description record to reference."
- INDEX { dm3ConfigSysDescriptionIndex }
- ::= { dm3ConfigSysDescriptionTable 1 }
-
- Dm3ConfigSysDescriptionEntry ::=
- SEQUENCE {
- dm3ConfigSysDescriptionIndex INTEGER,
- dm3ConfigSysDescriptionText DisplayString
- }
- dm3ConfigSysDescriptionIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the DC powerplant description record."
- ::= { dm3ConfigSysDescriptionEntry 1 }
- dm3ConfigSysDescriptionText OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "16 character text field describing the DC power plant device."
- ::= { dm3ConfigSysDescriptionEntry 2 }
- dm3ConfigSysHighTempThresh OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Ambient high temperature threshold. Temperature sensor located on Master
- Controller board.
- Values are represented in thousandths of a degree.
- Units are displayed in the scale shown in
- the 'dm3StatusSysTempUnits' OID (Celsius or Fahrenheit).
-
- Attempts to set the value above or below the acceptable range of the powerplant
- will cause the value to be set at the high or low point of the range respectively."
- ::= { dm3ConfigSystem 3 }
- dm3ConfigSysHighTempAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- alarmIgnore (1),
- alarmRelay1 (2),
- alarmRelay2 (3),
- alarmRelay3 (4),
- alarmRelay4 (5),
- alarmRelay5 (6),
- alarmRelay6 (7),
- alarmMinor (8),
- alarmMajor (9)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "For the System High Temperature Alarm;
- Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
- Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
- alarm condition.
- Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
- alarm condition.
- Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
- alarm condition."
- ::= { dm3ConfigSystem 4 }
-
- dm3ConfigSysLowTempThresh OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Ambient low temperature threshold. Temperature sensor located on Master
- Controller board.
-
- Values are represented in thousandths of a degree.
- Units are displayed in the scale shown in
- the 'dm3StatusSysTempUnits' OID (Celsius or Fahrenheit).
- Attempts to set the value above or below the acceptable range of the powerplant
- will cause the value to be set at the high or low point of the range respectively."
- ::= { dm3ConfigSystem 5 }
-
- dm3ConfigSysLowTempAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- alarmIgnore (1),
- alarmRelay1 (2),
- alarmRelay2 (3),
- alarmRelay3 (4),
- alarmRelay4 (5),
- alarmRelay5 (6),
- alarmRelay6 (7),
- alarmMinor (8),
- alarmMajor (9)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "For the System Low Temperature Alarm;
- Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
- Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
- alarm condition.
- Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
- alarm condition.
- Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
- alarm condition."
- ::= { dm3ConfigSystem 6 }
- dm3ConfigSysHardwareTempAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- alarmIgnore (1),
- alarmRelay1 (2),
- alarmRelay2 (3),
- alarmRelay3 (4),
- alarmRelay4 (5),
- alarmRelay5 (6),
- alarmRelay6 (7),
- alarmMinor (8),
- alarmMajor (9)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "For the System Hardware Temperature Alarm;
- Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
- Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
- alarm condition.
- Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
- alarm condition.
- Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
- alarm condition."
- ::= { dm3ConfigSystem 7 }
- dm3ConfigSysRemoteAccess OBJECT-TYPE
- SYNTAX INTEGER {
- accessEnabled (1),
- accessDisabled (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "
- This OID is used to disable remote write access to the power plant.
- Setting this OID to accessEnabled (1) will have no affect.
- Setting this OID to accessDisabled (2) will disable the ability to
- remotely configure the DC powerplant.
-
- Once remote access is disabled, it can only be restored from the front
- panel of the DC power plant."
- ::= { dm3ConfigSystem 8 }
-
- -- the dm3ConfigLVD group
- dm3ConfigLVDTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of DC powerplant LVDs controllable
- by this IP address."
- ::= { dm3ConfigLVD 1 }
- dm3ConfigLVDTable OBJECT-TYPE
- SYNTAX SEQUENCE OF Dm3ConfigLVDEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for accessing settings of the LVDs. The number of
- entries is contained in the dm3ConfigLVDTableSize OID."
- ::= { dm3ConfigLVD 2 }
- dm3ConfigLVDEntry OBJECT-TYPE
- SYNTAX Dm3ConfigLVDEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The LVD to configure."
- INDEX { dm3ConfigLVDIndex }
- ::= { dm3ConfigLVDTable 1 }
-
- Dm3ConfigLVDEntry ::=
- SEQUENCE {
- dm3ConfigLVDIndex INTEGER,
- dm3ConfigLVDName DisplayString,
- dm3ConfigLVDEnable INTEGER,
- dm3ConfigLVDTripThresh INTEGER,
- dm3ConfigLVDResetThresh INTEGER,
- dm3ConfigLVDOpenAlarm INTEGER,
- dm3ConfigLVDHWAlarm INTEGER
- }
-
- dm3ConfigLVDIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the DC powerplant LVD."
- ::= { dm3ConfigLVDEntry 1 }
- dm3ConfigLVDName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The name of the LVD. The maximum value is 16 characters."
- ::= { dm3ConfigLVDEntry 2 }
-
- dm3ConfigLVDEnable OBJECT-TYPE
- SYNTAX INTEGER {
- enabledYes (1),
- enabledNo (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "This OID is used to control and indicate if the LVD is on or off.
- Setting this OID to enabledYes (1) will enable (turn on) the LVD.
- Setting this OID to enabledNo (2) will disable (turn off) the LVD."
- ::= { dm3ConfigLVDEntry 3 }
- dm3ConfigLVDTripThresh OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "LVD Trip threshold. If voltage exceeds threshold, the LVD will trip.
-
- Values are represented in thousandths of Volts (mV).
- Attempts to set the value above or below the acceptable range of the powerplant
- will cause the value to be set at the high or low point of the range respectively."
- ::= { dm3ConfigLVDEntry 4 }
- dm3ConfigLVDResetThresh OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "LVD Reset threshold. If voltage exceeds threshold, the LVD will reset.
-
- Values are represented in thousandths of Volts (mV).
- Attempts to set the value above or below the acceptable range of the powerplant
- will cause the value to be set at the high or low point of the range respectively."
- ::= { dm3ConfigLVDEntry 5 }
-
- dm3ConfigLVDOpenAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- alarmIgnore (1),
- alarmRelay1 (2),
- alarmRelay2 (3),
- alarmRelay3 (4),
- alarmRelay4 (5),
- alarmRelay5 (6),
- alarmRelay6 (7),
- alarmMinor (8),
- alarmMajor (9)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "For the LVD Open Alarm;
- Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
- Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
- alarm condition.
- Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
- alarm condition.
- Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
- alarm condition."
- ::= { dm3ConfigLVDEntry 6 }
-
- dm3ConfigLVDHWAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- alarmIgnore (1),
- alarmRelay1 (2),
- alarmRelay2 (3),
- alarmRelay3 (4),
- alarmRelay4 (5),
- alarmRelay5 (6),
- alarmRelay6 (7),
- alarmMinor (8),
- alarmMajor (9)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "For the LVD Hardware Alarm;
- Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
- Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
- alarm condition.
- Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
- alarm condition.
- Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
- alarm condition."
- ::= { dm3ConfigLVDEntry 7 }
- -- the dm3ConfigBattery group
- dm3ConfigBattFloatVolt OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Battery Float Voltage. This setting controls the power plant voltage.
-
- Values are represented in thousandths of Volts (mV).
- Attempts to set the value above or below the acceptable range of the powerplant
- will cause the value to be set at the high or low point of the range respectively."
- ::= { dm3ConfigBattery 1 }
- dm3ConfigBattMaxRecharge OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Battery Maximum Recharge Rate. This setting controls the battery max
- recharge rate. The value is based on C/20 for 240 AHr battery string.
-
- Values are represented in thousandths of Amps (mA).
- Attempts to set the value above or below the acceptable range of the powerplant
- will cause the value to be set at the high or low point of the range respectively."
- ::= { dm3ConfigBattery 2 }
- dm3ConfigBattDischargeThresh OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Battery discharge threshold. If battery output current exceeds threshold
- a battery discharge alarm will occur.
-
- Values are represented in thousandths of Amps (mA).
- Attempts to set the value above or below the acceptable range of the powerplant
- will cause the value to be set at the high or low point of the range respectively."
- ::= { dm3ConfigBattery 3 }
-
- dm3ConfigBattDischargeAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- alarmIgnore (1),
- alarmRelay1 (2),
- alarmRelay2 (3),
- alarmRelay3 (4),
- alarmRelay4 (5),
- alarmRelay5 (6),
- alarmRelay6 (7),
- alarmMinor (8),
- alarmMajor (9)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "For the Battery Discharge Alarm;
- Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
- Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
- alarm condition.
- Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
- alarm condition.
- Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
- alarm condition."
- ::= { dm3ConfigBattery 4 }
- dm3ConfigBattHighVoltThresh OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Battery high voltage threshold. If system battery voltage exceeds threshold
- a battery high voltage alarm will occur.
-
- Values are represented in thousandths of Volts (mV).
- Attempts to set the value above or below the acceptable range of the powerplant
- will cause the value to be set at the high or low point of the range respectively."
- ::= { dm3ConfigBattery 5 }
-
- dm3ConfigBattHighVoltAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- alarmIgnore (1),
- alarmRelay1 (2),
- alarmRelay2 (3),
- alarmRelay3 (4),
- alarmRelay4 (5),
- alarmRelay5 (6),
- alarmRelay6 (7),
- alarmMinor (8),
- alarmMajor (9)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "For the Battery High Voltage Alarm;
- Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
- Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
- alarm condition.
- Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
- alarm condition.
- Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
- alarm condition."
- ::= { dm3ConfigBattery 6 }
-
- dm3ConfigBattLowVoltThresh OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Battery low voltage threshold. If system battery voltage is under threshold
- a battery low voltage alarm will occur.
-
- Values are represented in thousandths of Volts (mV).
- Attempts to set the value above or below the acceptable range of the powerplant
- will cause the value to be set at the high or low point of the range respectively."
- ::= { dm3ConfigBattery 7 }
-
- dm3ConfigBattLowVoltAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- alarmIgnore (1),
- alarmRelay1 (2),
- alarmRelay2 (3),
- alarmRelay3 (4),
- alarmRelay4 (5),
- alarmRelay5 (6),
- alarmRelay6 (7),
- alarmMinor (8),
- alarmMajor (9)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "For the Battery Low Voltage Alarm;
- Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
- Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
- alarm condition.
- Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
- alarm condition.
- Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
- alarm condition."
- ::= { dm3ConfigBattery 8 }
-
- dm3ConfigBattHighTempThresh OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Battery high temperature threshold. If system battery temperature exceeds threshold
- a battery high temperature alarm will occur.
-
- Values are represented in thousandths of a degree.
- Units are displayed in the scale shown in
- the 'dm3StatusSysTempUnits' OID (Celsius or Fahrenheit).
- Attempts to set the value above or below the acceptable range of the powerplant
- will cause the value to be set at the high or low point of the range respectively."
-
- ::= { dm3ConfigBattery 9 }
-
- dm3ConfigBattHighTempAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- alarmIgnore (1),
- alarmRelay1 (2),
- alarmRelay2 (3),
- alarmRelay3 (4),
- alarmRelay4 (5),
- alarmRelay5 (6),
- alarmRelay6 (7),
- alarmMinor (8),
- alarmMajor (9)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "For the Battery High Temperature Alarm;
- Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
- Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
- alarm condition.
- Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
- alarm condition.
- Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
- alarm condition."
- ::= { dm3ConfigBattery 10 }
-
- dm3ConfigBattLowTempThresh OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Battery low temperature threshold. If system battery temperature is under threshold
- a battery low temperature alarm will occur.
-
- Values are represented in thousandths of a degree.
- Units are displayed in the scale shown in
- the 'dm3StatusSysTempUnits' OID (Celsius or Fahrenheit).
- Attempts to set the value above or below the acceptable range of the powerplant
- will cause the value to be set at the high or low point of the range respectively."
-
- ::= { dm3ConfigBattery 11 }
-
- dm3ConfigBattLowTempAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- alarmIgnore (1),
- alarmRelay1 (2),
- alarmRelay2 (3),
- alarmRelay3 (4),
- alarmRelay4 (5),
- alarmRelay5 (6),
- alarmRelay6 (7),
- alarmMinor (8),
- alarmMajor (9)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "For the Battery Low Temperature Alarm;
- Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
- Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
- alarm condition.
- Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
- alarm condition.
- Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
- alarm condition."
- ::= { dm3ConfigBattery 12 }
- dm3ConfigBattAmpHour OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Battery Amp-Hour Size. Units are thousandths of Amp hours (mAHr).
- Attempts to set the value above or below the acceptable range of the powerplant
- will cause the value to be set at the high or low point of the range respectively."
- ::= { dm3ConfigBattery 13 }
- dm3ConfigCompMethod OBJECT-TYPE
- SYNTAX INTEGER {
- tempcompOn (1),
- tempcompOff (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "This OID is used to configure and get the state of the battery
- temperature compensation.
-
- Setting this OID to tempcompOn (1) will enable/turn on the battery temperature compensation.
- Setting this OID to tempcompOff (2) will disable/turn off the battery temperature compensation."
- ::= { dm3ConfigBattery 14 }
- dm3ConfigCompTempCoeff OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Compensation Temperature Coefficient. (uV/degC/cell).
-
- Units are presented in microvolts.
- Attempts to set the value above or below the acceptable range of the powerplant
- will cause the value to be set at the high or low point of the range respectively."
- ::= { dm3ConfigBattery 15 }
- dm3ConfigHighKneeTemp OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "High Knee for temperature compensation: Compensation temperature coefficient
- becomes 0mV/degC/cell.
-
- Values are represented in thousandths of degrees Celsius.
- Attempts to set the value above or below the acceptable range of the powerplant
- will cause the value to be set at the high or low point of the range respectively."
- ::= { dm3ConfigBattery 16 }
- dm3ConfigLowKneeTemp OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Low Knee for temperature compensation: Compensation temperature coefficient
- becomes 0mV/degC/cell.
-
- Values are represented in thousandths of degrees Celsius.
- Attempts to set the value above or below the acceptable range of the powerplant
- will cause the value to be set at the high or low point of the range respectively."
- ::= { dm3ConfigBattery 17 }
-
- dm3ConfigBattHwCurrentAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- alarmIgnore (1),
- alarmRelay1 (2),
- alarmRelay2 (3),
- alarmRelay3 (4),
- alarmRelay4 (5),
- alarmRelay5 (6),
- alarmRelay6 (7),
- alarmMinor (8),
- alarmMajor (9)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "For the Battery Current Hardware Alarm (indicating current is outside realistic
- limits, or a possible measurement fault;
- Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
- Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
- alarm condition.
- Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
- alarm condition.
- Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
- alarm condition."
- ::= { dm3ConfigBattery 18 }
-
- dm3ConfigBattHwTempAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- alarmIgnore (1),
- alarmRelay1 (2),
- alarmRelay2 (3),
- alarmRelay3 (4),
- alarmRelay4 (5),
- alarmRelay5 (6),
- alarmRelay6 (7),
- alarmMinor (8),
- alarmMajor (9)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "For the Battery Temperature Hardware Alarm (indicating temperature is outside realistic
- limits, or a possible measurement fault;
- Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
- Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
- alarm condition.
- Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
- alarm condition.
- Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
- alarm condition."
- ::= { dm3ConfigBattery 19 }
- -- the dm3ConfigRectThresh group
- dm3ConfigRectHighVoltThresh OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Rectifier high voltage threshold. If rectifier voltage exceeds threshold
- a rectifier high voltage alarm will occur.
-
- Values are represented in thousandths of Volts (mV).
- Attempts to set the value above or below the acceptable range of the powerplant
- will cause the value to be set at the high or low point of the range respectively."
- ::= { dm3ConfigRectThresh 1 }
- dm3ConfigRectLowVoltThresh OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Rectifier low voltage threshold. If rectifier voltage is under threshold
- a rectifier low voltage alarm will occur.
-
- Values are represented in thousandths of Volts (mV).
- Attempts to set the value above or below the acceptable range of the powerplant
- will cause the value to be set at the high or low point of the range respectively."
- ::= { dm3ConfigRectThresh 2 }
- dm3ConfigRectFailSafe OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Rectifier Fail Safe point. This OID represents the value sent to rectifier controllers
- to use in the event of communications loss with the Master Controller or Master Controller
- board failure.
-
- Values are represented in thousandths of Volts (mV).
- Attempts to set the value above or below the acceptable range of the powerplant
- will cause the value to be set at the high or low point of the range respectively."
- ::= { dm3ConfigRectThresh 3 }
- dm3ConfigRectFailComm OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Rectifier Communication Fail timeout. This OID represents the time interval in which there is no
- communication between the rectifier and the master controller at which the rectifier will reset
- all its values to default.
-
- Values are represented in hundredths of Seconds.
- Attempts to set the value above or below the acceptable range of the powerplant
- will cause the value to be set at the high or low point of the range respectively."
- ::= { dm3ConfigRectThresh 4 }
- -- the dm3ConfigRectAlarms group
- dm3ConfigRectHighVoltAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- alarmIgnore (1),
- alarmRelay1 (2),
- alarmRelay2 (3),
- alarmRelay3 (4),
- alarmRelay4 (5),
- alarmRelay5 (6),
- alarmRelay6 (7),
- alarmMinor (8),
- alarmMajor (9)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "For the Rectifier High Voltage Alarm;
- Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
- Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
- alarm condition.
- Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
- alarm condition.
- Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
- alarm condition."
- ::= { dm3ConfigRectAlarms 1 }
- dm3ConfigRectLowVoltAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- alarmIgnore (1),
- alarmRelay1 (2),
- alarmRelay2 (3),
- alarmRelay3 (4),
- alarmRelay4 (5),
- alarmRelay5 (6),
- alarmRelay6 (7),
- alarmMinor (8),
- alarmMajor (9)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "For the Rectifier Low Voltage Alarm;
- Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
- Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
- alarm condition.
- Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
- alarm condition.
- Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
- alarm condition."
- ::= { dm3ConfigRectAlarms 2 }
-
- dm3ConfigRectConfigAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- alarmIgnore (1),
- alarmRelay1 (2),
- alarmRelay2 (3),
- alarmRelay3 (4),
- alarmRelay4 (5),
- alarmRelay5 (6),
- alarmRelay6 (7),
- alarmMinor (8),
- alarmMajor (9)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "This alarm is activated when a new rectifier is detected;
- Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
- Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
- alarm condition.
- Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
- alarm condition.
- Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
- alarm condition."
- ::= { dm3ConfigRectAlarms 3 }
-
- dm3ConfigRect1ofNAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- alarmIgnore (1),
- alarmRelay1 (2),
- alarmRelay2 (3),
- alarmRelay3 (4),
- alarmRelay4 (5),
- alarmRelay5 (6),
- alarmRelay6 (7),
- alarmMinor (8),
- alarmMajor (9)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "This setting indicates the action if ONE rectifier of a N+1 system has failed;
- Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
- Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
- alarm condition.
- Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
- alarm condition.
- Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
- alarm condition."
- ::= { dm3ConfigRectAlarms 4 }
- dm3ConfigRect2ofNAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- alarmIgnore (1),
- alarmRelay1 (2),
- alarmRelay2 (3),
- alarmRelay3 (4),
- alarmRelay4 (5),
- alarmRelay5 (6),
- alarmRelay6 (7),
- alarmMinor (8),
- alarmMajor (9)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "This setting indicates the action if TWO OR MORE rectifiers of a N+1 system have failed;
- Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
- Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
- alarm condition.
- Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
- alarm condition.
- Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
- alarm condition."
- ::= { dm3ConfigRectAlarms 5 }
- dm3ConfigRectDiagAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- alarmIgnore (1),
- alarmRelay1 (2),
- alarmRelay2 (3),
- alarmRelay3 (4),
- alarmRelay4 (5),
- alarmRelay5 (6),
- alarmRelay6 (7),
- alarmMinor (8),
- alarmMajor (9),
- alarmNofN (10)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "For the Rectifier Controller Diagnostics Alarm;
- Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
- Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
- alarm condition.
- Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
- alarm condition.
- Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
- alarm condition.
- Setting this OID to alarmNofN (10) causes the alarm specified in the dm3ConfigRect1ofNAlarm OID
- to be activated if ONE rectifier fails in an N+1 system. It causes the alarm specified in the
- dm3ConfigRect2ofNAlarm OID to be activated if TWO OR MORE rectifiers fail in an N+1 system."
- ::= { dm3ConfigRectAlarms 6 }
- dm3ConfigRectImbalanceAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- alarmIgnore (1),
- alarmRelay1 (2),
- alarmRelay2 (3),
- alarmRelay3 (4),
- alarmRelay4 (5),
- alarmRelay5 (6),
- alarmRelay6 (7),
- alarmMinor (8),
- alarmMajor (9)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "For the Rectifier Imbalance Alarm;
- Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
- Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
- alarm condition.
- Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
- alarm condition.
- Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
- alarm condition."
- ::= { dm3ConfigRectAlarms 7 }
- dm3ConfigRectCurrLimitAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- alarmIgnore (1),
- alarmRelay1 (2),
- alarmRelay2 (3),
- alarmRelay3 (4),
- alarmRelay4 (5),
- alarmRelay5 (6),
- alarmRelay6 (7),
- alarmMinor (8),
- alarmMajor (9),
- alarmNofN (10)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "For the Rectifier Current Limit Alarm (indicating rectifier in the Current Limit state);
- Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
- Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
- alarm condition.
- Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
- alarm condition.
- Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
- alarm condition.
- Setting this OID to alarmNofN (10) causes the alarm specified in the dm3ConfigRect1ofNAlarm OID
- to be activated if ONE rectifier fails in an N+1 system. It causes the alarm specified in the
- dm3ConfigRect2ofNAlarm OID to be activated if TWO OR MORE rectifiers fail in an N+1 system."
- ::= { dm3ConfigRectAlarms 8 }
- dm3ConfigRectStandbyAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- alarmIgnore (1),
- alarmRelay1 (2),
- alarmRelay2 (3),
- alarmRelay3 (4),
- alarmRelay4 (5),
- alarmRelay5 (6),
- alarmRelay6 (7),
- alarmMinor (8),
- alarmMajor (9),
- alarmNofN (10)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "For the Rectifier Standby Alarm (indicating output DC has been turned off);
- Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
- Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
- alarm condition.
- Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
- alarm condition.
- Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
- alarm condition.
- Setting this OID to alarmNofN (10) causes the alarm specified in the dm3ConfigRect1ofNAlarm OID
- to be activated if ONE rectifier fails in an N+1 system. It causes the alarm specified in the
- dm3ConfigRect2ofNAlarm OID to be activated if TWO OR MORE rectifiers fail in an N+1 system."
- ::= { dm3ConfigRectAlarms 9 }
-
- dm3ConfigRectFanFailAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- alarmIgnore (1),
- alarmRelay1 (2),
- alarmRelay2 (3),
- alarmRelay3 (4),
- alarmRelay4 (5),
- alarmRelay5 (6),
- alarmRelay6 (7),
- alarmMinor (8),
- alarmMajor (9),
- alarmNofN (10)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "For the Rectifier Fan Fail Alarm;
- Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
- Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
- alarm condition.
- Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
- alarm condition.
- Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
- alarm condition.
- Setting this OID to alarmNofN (10) causes the alarm specified in the dm3ConfigRect1ofNAlarm OID
- to be activated if ONE rectifier fails in an N+1 system. It causes the alarm specified in the
- dm3ConfigRect2ofNAlarm OID to be activated if TWO OR MORE rectifiers fail in an N+1 system."
- ::= { dm3ConfigRectAlarms 10 }
- dm3ConfigRectFailAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- alarmIgnore (1),
- alarmRelay1 (2),
- alarmRelay2 (3),
- alarmRelay3 (4),
- alarmRelay4 (5),
- alarmRelay5 (6),
- alarmRelay6 (7),
- alarmMinor (8),
- alarmMajor (9),
- alarmNofN (10)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "For the Rectifier Fail Alarm;
- Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
- Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
- alarm condition.
- Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
- alarm condition.
- Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
- alarm condition.
- Setting this OID to alarmNofN (10) causes the alarm specified in the dm3ConfigRect1ofNAlarm OID
- to be activated if ONE rectifier fails in an N+1 system. It causes the alarm specified in the
- dm3ConfigRect2ofNAlarm OID to be activated if TWO OR MORE rectifiers fail in an N+1 system."
- ::= { dm3ConfigRectAlarms 11 }
- dm3ConfigRectHwVoltAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- alarmIgnore (1),
- alarmRelay1 (2),
- alarmRelay2 (3),
- alarmRelay3 (4),
- alarmRelay4 (5),
- alarmRelay5 (6),
- alarmRelay6 (7),
- alarmMinor (8),
- alarmMajor (9)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "For the Rectifier Hardware Voltage Alarm (indicating voltage outside realistic limits,
- or a possible measurement fault);
- Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
- Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
- alarm condition.
- Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
- alarm condition.
- Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
- alarm condition."
- ::= { dm3ConfigRectAlarms 12 }
- -- the dm3ConfigConvThresh group
- dm3ConfigConvHighVoltThresh OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Converter high voltage threshold. If converter voltage exceeds threshold
- a converter high voltage alarm will occur.
-
- Values are represented in thousandths of Volts (mV).
- Attempts to set the value above or below the acceptable range of the powerplant
- will cause the value to be set at the high or low point of the range respectively."
- ::= { dm3ConfigConvThresh 1 }
-
- dm3ConfigConvLowVoltThresh OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Converter low voltage threshold. If converter voltage exceeds threshold
- a converter low voltage alarm will occur.
-
- Values are represented in thousandths of Volts (mV).
- Attempts to set the value above or below the acceptable range of the powerplant
- will cause the value to be set at the high or low point of the range respectively."
- ::= { dm3ConfigConvThresh 2 }
- dm3ConfigConvFailSafe OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Converter Fail Safe point. This OID represents the value sent to converter controllers
- to use in the event of communications loss with the Master Controller or Master Controller
- board failure.
-
- Values are represented in thousandths of Volts (mV).
- Attempts to set the value above or below the acceptable range of the powerplant
- will cause the value to be set at the high or low point of the range respectively."
- ::= { dm3ConfigConvThresh 3 }
- dm3ConfigConvSetPoint OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Converter Set point. This OID represents the initial set point used in the
- voltage control loop.
-
- Units are thousandths of Volts (mV).
- Attempts to set the value above or below the acceptable range of the powerplant
- will cause the value to be set at the high or low point of the range respectively."
- ::= { dm3ConfigConvThresh 4 }
- dm3ConfigConvFailMax OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Converter Fail Maximum limit. This OID represents the value sent to the converter
- controllers to define the maximum set point allowed.
-
- Units are thousandths of Volts (mV).
- Attempts to set the value above or below the acceptable range of the powerplant
- will cause the value to be set at the high or low point of the range respectively."
- ::= { dm3ConfigConvThresh 5 }
- dm3ConfigConvFailMin OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Converter Fail Minimum limit. This OID represents the value sent to the converter
- controllers to define the minimum set point allowed.
-
- Units are thousandths of Volts (mV).
- Attempts to set the value above or below the acceptable range of the powerplant
- will cause the value to be set at the high or low point of the range respectively."
- ::= { dm3ConfigConvThresh 6 }
- dm3ConfigConvFailComm OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Converter Communication Fail timeout. This OID represents the time interval in which there is no
- communication between the converter and the master controller at which the converter will reset
- all its values to default.
-
- Values are represented in hundredths of Seconds.
- Attempts to set the value above or below the acceptable range of the powerplant
- will cause the value to be set at the high or low point of the range respectively."
- ::= { dm3ConfigConvThresh 7 }
- -- the dm3ConfigConvAlarms group
- dm3ConfigConvHighVoltAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- alarmIgnore (1),
- alarmRelay1 (2),
- alarmRelay2 (3),
- alarmRelay3 (4),
- alarmRelay4 (5),
- alarmRelay5 (6),
- alarmRelay6 (7),
- alarmMinor (8),
- alarmMajor (9)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "For the Converter High Voltage Alarm;
- Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
- Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
- alarm condition.
- Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
- alarm condition.
- Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
- alarm condition."
- ::= { dm3ConfigConvAlarms 1 }
- dm3ConfigConvLowVoltAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- alarmIgnore (1),
- alarmRelay1 (2),
- alarmRelay2 (3),
- alarmRelay3 (4),
- alarmRelay4 (5),
- alarmRelay5 (6),
- alarmRelay6 (7),
- alarmMinor (8),
- alarmMajor (9)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "For the Converter Low Voltage Alarm;
- Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
- Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
- alarm condition.
- Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
- alarm condition.
- Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
- alarm condition."
- ::= { dm3ConfigConvAlarms 2 }
- dm3ConfigConvConfigAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- alarmIgnore (1),
- alarmRelay1 (2),
- alarmRelay2 (3),
- alarmRelay3 (4),
- alarmRelay4 (5),
- alarmRelay5 (6),
- alarmRelay6 (7),
- alarmMinor (8),
- alarmMajor (9)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "For the Converter Configuration Alarm (indicating a new converter has been detected);
- Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
- Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
- alarm condition.
- Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
- alarm condition.
- Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
- alarm condition."
- ::= { dm3ConfigConvAlarms 3 }
- dm3ConfigConv1ofNAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- alarmIgnore (1),
- alarmRelay1 (2),
- alarmRelay2 (3),
- alarmRelay3 (4),
- alarmRelay4 (5),
- alarmRelay5 (6),
- alarmRelay6 (7),
- alarmMinor (8),
- alarmMajor (9)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "For the Converter 1ofN Alarm (indicating action if ONE converter of a N+1 system has failed);
- Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
- Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
- alarm condition.
- Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
- alarm condition.
- Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
- alarm condition."
- ::= { dm3ConfigConvAlarms 4 }
- dm3ConfigConv2ofNAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- alarmIgnore (1),
- alarmRelay1 (2),
- alarmRelay2 (3),
- alarmRelay3 (4),
- alarmRelay4 (5),
- alarmRelay5 (6),
- alarmRelay6 (7),
- alarmMinor (8),
- alarmMajor (9)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "For the Converter 2ofN Alarm (indicating action if TWO OR MORE converters of a N+1 system has failed);
- Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
- Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
- alarm condition.
- Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
- alarm condition.
- Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
- alarm condition."
- ::= { dm3ConfigConvAlarms 5 }
- dm3ConfigConvDiagAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- alarmIgnore (1),
- alarmRelay1 (2),
- alarmRelay2 (3),
- alarmRelay3 (4),
- alarmRelay4 (5),
- alarmRelay5 (6),
- alarmRelay6 (7),
- alarmMinor (8),
- alarmMajor (9),
- alarmNofN (10)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "For the Converter Diagnostics Alarm;
- Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
- Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
- alarm condition.
- Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
- alarm condition.
- Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
- alarm condition.
- Setting this OID to alarmNofN (10) causes the alarm specified in the dm3ConfigConv1ofNAlarm OID
- to be activated if ONE converter fails in an N+1 system. It causes the alarm specified in the
- dm3ConfigConv2ofNAlarm OID to be activated if TWO OR MORE converters fail in an N+1 system."
- ::= { dm3ConfigConvAlarms 6 }
- dm3ConfigConvImbalanceAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- alarmIgnore (1),
- alarmRelay1 (2),
- alarmRelay2 (3),
- alarmRelay3 (4),
- alarmRelay4 (5),
- alarmRelay5 (6),
- alarmRelay6 (7),
- alarmMinor (8),
- alarmMajor (9),
- alarmNofN (10)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "For the Converter Imbalance Alarm;
- Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
- Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
- alarm condition.
- Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
- alarm condition.
- Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
- alarm condition.
- Setting this OID to alarmNofN (10) causes the alarm specified in the dm3ConfigConv1ofNAlarm OID
- to be activated if ONE converter fails in an N+1 system. It causes the alarm specified in the
- dm3ConfigConv2ofNAlarm OID to be activated if TWO OR MORE converters fail in an N+1 system."
- ::= { dm3ConfigConvAlarms 7 }
- dm3ConfigConvCurrLimitAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- alarmIgnore (1),
- alarmRelay1 (2),
- alarmRelay2 (3),
- alarmRelay3 (4),
- alarmRelay4 (5),
- alarmRelay5 (6),
- alarmRelay6 (7),
- alarmMinor (8),
- alarmMajor (9),
- alarmNofN (10)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "For the Converter Current Limit Alarm (indicating the converter is in the Current Limit state);
- Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
- Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
- alarm condition.
- Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
- alarm condition.
- Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
- alarm condition.
- Setting this OID to alarmNofN (10) causes the alarm specified in the dm3ConfigConv1ofNAlarm OID
- to be activated if ONE converter fails in an N+1 system. It causes the alarm specified in the
- dm3ConfigConv2ofNAlarm OID to be activated if TWO OR MORE converters fail in an N+1 system."
- ::= { dm3ConfigConvAlarms 8 }
- dm3ConfigConvStandbyAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- alarmIgnore (1),
- alarmRelay1 (2),
- alarmRelay2 (3),
- alarmRelay3 (4),
- alarmRelay4 (5),
- alarmRelay5 (6),
- alarmRelay6 (7),
- alarmMinor (8),
- alarmMajor (9),
- alarmNofN (10)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "For the Converter Standby Alarm (indicating the converter is in the Standby state);
- Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
- Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
- alarm condition.
- Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
- alarm condition.
- Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
- alarm condition.
- Setting this OID to alarmNofN (10) causes the alarm specified in the dm3ConfigConv1ofNAlarm OID
- to be activated if ONE converter fails in an N+1 system. It causes the alarm specified in the
- dm3ConfigConv2ofNAlarm OID to be activated if TWO OR MORE converters fail in an N+1 system."
- ::= { dm3ConfigConvAlarms 9 }
- dm3ConfigConvFanFailAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- alarmIgnore (1),
- alarmRelay1 (2),
- alarmRelay2 (3),
- alarmRelay3 (4),
- alarmRelay4 (5),
- alarmRelay5 (6),
- alarmRelay6 (7),
- alarmMinor (8),
- alarmMajor (9),
- alarmNofN (10)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "For the Converter Fan Fail Alarm;
- Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
- Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
- alarm condition.
- Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
- alarm condition.
- Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
- alarm condition.
- Setting this OID to alarmNofN (10) causes the alarm specified in the dm3ConfigConv1ofNAlarm OID
- to be activated if ONE converter fails in an N+1 system. It causes the alarm specified in the
- dm3ConfigConv2ofNAlarm OID to be activated if TWO OR MORE converters fail in an N+1 system."
- ::= { dm3ConfigConvAlarms 10 }
-
- dm3ConfigConvFailAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- alarmIgnore (1),
- alarmRelay1 (2),
- alarmRelay2 (3),
- alarmRelay3 (4),
- alarmRelay4 (5),
- alarmRelay5 (6),
- alarmRelay6 (7),
- alarmMinor (8),
- alarmMajor (9),
- alarmNofN (10)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "For the Converter Fail Alarm;
- Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
- Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
- alarm condition.
- Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
- alarm condition.
- Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
- alarm condition.
- Setting this OID to alarmNofN (10) causes the alarm specified in the dm3ConfigConv1ofNAlarm OID
- to be activated if ONE converter fails in an N+1 system. It causes the alarm specified in the
- dm3ConfigConv2ofNAlarm OID to be activated if TWO OR MORE converters fail in an N+1 system."
- ::= { dm3ConfigConvAlarms 11 }
-
- dm3ConfigConvHwVoltAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- alarmIgnore (1),
- alarmRelay1 (2),
- alarmRelay2 (3),
- alarmRelay3 (4),
- alarmRelay4 (5),
- alarmRelay5 (6),
- alarmRelay6 (7),
- alarmMinor (8),
- alarmMajor (9),
- alarmNofN (10)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "For the Converter Voltage Alarm (indicating voltage outside realistic limits, or a
- possible measurement fault);
- Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
- Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
- alarm condition.
- Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
- alarm condition.
- Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
- alarm condition.
- Setting this OID to alarmNofN (10) causes the alarm specified in the dm3ConfigConv1ofNAlarm OID
- to be activated if ONE converter fails in an N+1 system. It causes the alarm specified in the
- dm3ConfigConv2ofNAlarm OID to be activated if TWO OR MORE converters fail in an N+1 system."
- ::= { dm3ConfigConvAlarms 12 }
- -- the dm3ConfigOutputRelays group
- dm3ConfigOutRlyTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of DC powerplant Output Relays controllable
- by this IP address."
- ::= { dm3ConfigOutputRelays 1 }
- dm3ConfigOutRlyTable OBJECT-TYPE
- SYNTAX SEQUENCE OF Dm3ConfigOutRlyEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for accessing settings of the Output Relays. The number of
- entries is contained in the dm3ConfigOutRlyTableSize OID."
- ::= { dm3ConfigOutputRelays 2 }
-
- dm3ConfigOutRlyEntry OBJECT-TYPE
- SYNTAX Dm3ConfigOutRlyEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The output relay to configure."
- INDEX { dm3ConfigOutRlyIndex }
- ::= { dm3ConfigOutRlyTable 1 }
-
- Dm3ConfigOutRlyEntry ::=
- SEQUENCE {
- dm3ConfigOutRlyIndex INTEGER,
- dm3ConfigOutRlyName DisplayString,
- dm3ConfigOutRlyDelay INTEGER,
- dm3ConfigOutRlyAlarm INTEGER
- }
-
- dm3ConfigOutRlyIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the DC powerplant output relay."
- ::= { dm3ConfigOutRlyEntry 1 }
-
- dm3ConfigOutRlyName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The name of the output relay. The maximum value is 16 characters."
- ::= { dm3ConfigOutRlyEntry 2 }
-
- dm3ConfigOutRlyDelay OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Output Relay Delay. This OID represents the time delay from the initiation of an
- output relay action to when the output relay action does occur. If the alarm condition
- disappears before the end of the delay, no action will occur. Delay for Major
- and Minor alarms is not configurable and is always set to 0.
-
- Values are represented in hundredths of seconds.
- Attempts to set the value above or below the acceptable range of the powerplant
- will cause the value to be set at the high or low point of the range respectively."
- ::= { dm3ConfigOutRlyEntry 3 }
-
- dm3ConfigOutRlyAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- alarmIgnore (1),
- alarmRelay1 (2),
- alarmRelay2 (3),
- alarmRelay3 (4),
- alarmRelay4 (5),
- alarmRelay5 (6),
- alarmRelay6 (7),
- alarmMinor (8),
- alarmMajor (9)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Output Relay Alarm. This setting indicates what action to perform in the event of
- an output relay alarm condition;
- Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
- Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
- alarm condition.
- Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
- alarm condition.
- Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
- alarm condition.
-
- Relay Alarm for Major and Minor alarms is not configurable and is always set to
- alarmMajor and alarmMinor respectively."
- ::= { dm3ConfigOutRlyEntry 4 }
- -- the dm3ConfigInputRelays group
- dm3ConfigInRlyTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of DC powerplant Input Relays controllable
- by this IP address."
- ::= { dm3ConfigInputRelays 1 }
- dm3ConfigInRlyTable OBJECT-TYPE
- SYNTAX SEQUENCE OF Dm3ConfigInRlyEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for accessing settings of the Input Relays. The number of
- entries is contained in the dm3ConfigInRlyTableSize OID."
- ::= { dm3ConfigInputRelays 2 }
- dm3ConfigInRlyEntry OBJECT-TYPE
- SYNTAX Dm3ConfigInRlyEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The input relay to configure."
- INDEX { dm3ConfigInRlyIndex }
- ::= { dm3ConfigInRlyTable 1 }
-
- Dm3ConfigInRlyEntry ::=
- SEQUENCE {
- dm3ConfigInRlyIndex INTEGER,
- dm3ConfigInRlyName DisplayString,
- dm3ConfigInRlyDelay INTEGER,
- dm3ConfigInRlyAlarm INTEGER
- }
-
- dm3ConfigInRlyIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the DC powerplant input relay."
- ::= { dm3ConfigInRlyEntry 1 }
-
- dm3ConfigInRlyName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The name of the input relay. The maximum value is 16 characters."
- ::= { dm3ConfigInRlyEntry 2 }
-
- dm3ConfigInRlyDelay OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Input Relay Delay. This OID represents the time delay from the initiation of an
- input relay action to when the input relay action does occur. If the alarm condition
- disappears before the end of the delay, no action will occur.
-
- Values are represented in hundredths of seconds.
- Attempts to set the value above or below the acceptable range of the powerplant
- will cause the value to be set at the high or low point of the range respectively."
- ::= { dm3ConfigInRlyEntry 3 }
-
- dm3ConfigInRlyAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- alarmIgnore (1),
- alarmRelay1 (2),
- alarmRelay2 (3),
- alarmRelay3 (4),
- alarmRelay4 (5),
- alarmRelay5 (6),
- alarmRelay6 (7),
- alarmMinor (8),
- alarmMajor (9)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Input Relay Alarm. This setting indicates what action to perform in the event of
- an input relay alarm condition;
- Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
- Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
- alarm condition.
- Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
- alarm condition.
- Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
- alarm condition."
- ::= { dm3ConfigInRlyEntry 4 }
- -- the dm3ConfigBreakers group
- dm3ConfigBreakersTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of DC powerplant circuit breakers controllable
- by this IP address."
- ::= { dm3ConfigBreakers 1 }
- dm3ConfigBreakersTable OBJECT-TYPE
- SYNTAX SEQUENCE OF Dm3ConfigBreakersEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for accessing settings of the circuit breakers. The number of
- entries is contained in the dm3ConfigBreakersTableSize OID."
- ::= { dm3ConfigBreakers 2 }
- dm3ConfigBreakersEntry OBJECT-TYPE
- SYNTAX Dm3ConfigBreakersEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The circuit breaker to configure."
- INDEX { dm3ConfigBreakersIndex }
- ::= { dm3ConfigBreakersTable 1 }
-
- Dm3ConfigBreakersEntry ::=
- SEQUENCE {
- dm3ConfigBreakersIndex INTEGER,
- dm3ConfigBreakersName DisplayString,
- dm3ConfigBreakersAlarm INTEGER
- }
-
- dm3ConfigBreakersIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the DC powerplant circuit breaker."
- ::= { dm3ConfigBreakersEntry 1 }
-
- dm3ConfigBreakersName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The name of the circuit breaker. The maximum value is 16 characters."
- ::= { dm3ConfigBreakersEntry 2 }
-
- dm3ConfigBreakersAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- alarmIgnore (1),
- alarmRelay1 (2),
- alarmRelay2 (3),
- alarmRelay3 (4),
- alarmRelay4 (5),
- alarmRelay5 (6),
- alarmRelay6 (7),
- alarmMinor (8),
- alarmMajor (9)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Circuit Breaker Alarm. This setting indicates what action to perform in the event of
- a circuit breaker alarm condition;
- Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
- Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
- alarm condition.
- Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
- alarm condition.
- Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
- alarm condition."
- ::= { dm3ConfigBreakersEntry 3 }
- -- the dm3ConfigFuses group
- dm3ConfigFusesTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of DC powerplant Fuses controllable
- by this IP address."
- ::= { dm3ConfigFuses 1 }
- dm3ConfigFusesTable OBJECT-TYPE
- SYNTAX SEQUENCE OF Dm3ConfigFusesEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for accessing settings of the Fuses. The number of
- entries is contained in the dm3ConfigFusesTableSize OID."
- ::= { dm3ConfigFuses 2 }
-
- dm3ConfigFusesEntry OBJECT-TYPE
- SYNTAX Dm3ConfigFusesEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The fuse to configure."
- INDEX { dm3ConfigFusesIndex }
- ::= { dm3ConfigFusesTable 1 }
-
- Dm3ConfigFusesEntry ::=
- SEQUENCE {
- dm3ConfigFusesIndex INTEGER,
- dm3ConfigFusesName DisplayString,
- dm3ConfigFusesAlarm INTEGER
- }
-
- dm3ConfigFusesIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the DC powerplant fuse."
- ::= { dm3ConfigFusesEntry 1 }
-
- dm3ConfigFusesName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The name of the fuse. The maximum value is 16 characters."
- ::= { dm3ConfigFusesEntry 2 }
-
- dm3ConfigFusesAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- alarmIgnore (1),
- alarmRelay1 (2),
- alarmRelay2 (3),
- alarmRelay3 (4),
- alarmRelay4 (5),
- alarmRelay5 (6),
- alarmRelay6 (7),
- alarmMinor (8),
- alarmMajor (9)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Fuses Alarm. This setting indicates what action to perform in the event of
- a Fuse alarm condition;
- Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
- Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
- alarm condition.
- Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
- alarm condition.
- Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
- alarm condition.
- Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
- alarm condition."
- ::= { dm3ConfigFusesEntry 3 }
- -- the dm3StatusSystem group
- dm3StatusSystemTemp OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "System temperature based on sensor on Master Controller PCB.
- Values are represented in thousandths of a degree.
- Units are displayed in the scale shown in
- the 'dm3StatusSysTempUnits' OID (Celsius or Fahrenheit)."
- ::= { dm3StatusSystem 1 }
- dm3StatusSystemStart OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Time stamp at DC powerplant initialization.
- The time is represented as MMM,DD,YYYY,HH:MM:SS."
- ::= { dm3StatusSystem 2 }
- dm3StatusSysRemoteAccess OBJECT-TYPE
- SYNTAX INTEGER {
- accessEnabled (1),
- accessDisabled (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Remote Access indicator
- This setting indicates if configuration (write) access to the powerplant is enabled or
- disabled at the powerplant level.
- This value will be accessEnabled (1) if remote configuration is enabled, and
- accessDisabled (2) if remote configuration is disabled."
- ::= { dm3StatusSystem 3 }
- dm3StatusSysSecurityLevel OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This variable shows the current active security access level of controller. This
- can only be changed directly from the front panel."
- ::= { dm3StatusSystem 4 }
- dm3StatusSysTempSanity OBJECT-TYPE
- SYNTAX INTEGER{
- saneYES (1),
- saneNO (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "System temperature sanity indicator. Indicates if the system temperature is
- reasonable. Reasonable is defined based on powerplant type. A value of saneYes (1)
- indicates temperature is reasonable, a value of saneNo (2) indicates it is not."
- ::= { dm3StatusSystem 5 }
- dm3StatusSysAlarmState OBJECT-TYPE
- SYNTAX INTEGER{
- alarmMinor (1),
- alarmMajor (2),
- alarmBoth (3),
- alarmNone (4)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "System Alarm State. Reflects the alarm status of the overall DC system.
- If a minor alarm is present, the value will be alarmMinor(1).
- If a major alarm is present, the value will be alarmMajor(2).
- If both minor and a major alarm is present, the value will be alarmBoth(3).
- If no alarm is present, the value will be alarmNone(4)."
- ::= { dm3StatusSystem 6 }
- dm3StatusSysTempUnits OBJECT-TYPE
- SYNTAX INTEGER {
- celsius(1),
- fahrenheit(2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The temperature scale used to display the temperature
- in the DC system, Celsius(1) or Fahrenheit(2).
- This setting is based on the system preferences
- configuration in the agent."
- ::= { dm3StatusSystem 7 }
- -- the dm3StatusAlarms group
- dm3StatusAlarmsTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of DC powerplant alarms viewable
- by this IP address."
- ::= { dm3StatusAlarms 1 }
- dm3StatusAlarmsTable OBJECT-TYPE
- SYNTAX SEQUENCE OF Dm3StatusAlarmsEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for accessing system alarms. The number of
- entries is contained in the dm3StatusAlarmsTableSize OID."
- ::= { dm3StatusAlarms 2 }
- dm3StatusAlarmsEntry OBJECT-TYPE
- SYNTAX Dm3StatusAlarmsEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The alarm to display."
- INDEX { dm3StatusAlarmsIndex }
- ::= { dm3StatusAlarmsTable 1 }
-
- Dm3StatusAlarmsEntry ::=
- SEQUENCE {
- dm3StatusAlarmsIndex INTEGER,
- dm3StatusAlarmsText DisplayString
- }
- dm3StatusAlarmsIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index of the system alarm."
- ::= { dm3StatusAlarmsEntry 1 }
-
- dm3StatusAlarmsText OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The 16 character text describing the active alarm condition."
- ::= { dm3StatusAlarmsEntry 2 }
-
- -- the dm3StatusBattery group
- dm3StatusBattCurrent OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Battery Current: This OID shows the battery current in thousandths of Amps (mA)."
- ::= { dm3StatusBattery 1 }
- dm3StatusBattTemp OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Battery Temperature:
-
- Values are represented in thousandths of a degree.
- Units are displayed in the scale shown in
- the 'dm3StatusSysTempUnits' OID (Celsius or Fahrenheit)."
- ::= { dm3StatusBattery 2 }
- dm3StatusBattCurrentSanity OBJECT-TYPE
- SYNTAX INTEGER{
- saneYES (1),
- saneNO (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Battery current sanity indicator. Indicates if the battery current is
- reasonable. Reasonable is defined based on powerplant type. A value of saneYes (1)
- indicates current is reasonable, a value of saneNo (2) indicates it is not."
- ::= { dm3StatusBattery 3 }
- dm3StatusBattTempSanity OBJECT-TYPE
- SYNTAX INTEGER{
- saneYES (1),
- saneNO (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Battery temperature sanity indicator. Indicates if the battery temperature is
- reasonable. Reasonable is defined based on powerplant type. A value of saneYes (1)
- indicates temperature is reasonable, a value of saneNo (2) indicates it is not."
- ::= { dm3StatusBattery 4 }
- -- the dm3StatusOEM group
- dm3StatusOEMrectOffset OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID shows the rectifier offset value in thousandths of Volts (mV)."
- ::= { dm3StatusOEM 1 }
- dm3StatusOEMrectGain OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID shows the rectifier gain value in thousandths of Volts (mV/V)."
- ::= { dm3StatusOEM 2 }
- dm3StatusOEMconvOffset OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID shows the converter offset value in thousandths of Volts (mV)."
- ::= { dm3StatusOEM 3 }
- dm3StatusOEMconvGain OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID shows the converter gain value in thousandths of Volts (mV/V)."
- ::= { dm3StatusOEM 4 }
- dm3StatusOEMshuntOffset OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID shows the shunt offset value in thousandths of Amps (mA)."
- ::= { dm3StatusOEM 5 }
- dm3StatusOEMshuntGain OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID shows the shunt gain value in thousandths of Amps (mA/A)."
- ::= { dm3StatusOEM 6 }
- -- the dm3StatusLVD group
- dm3StatusLVDTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of DC powerplant LVDs viewable
- by this IP address."
- ::= { dm3StatusLVD 1 }
- dm3StatusLVDTable OBJECT-TYPE
- SYNTAX SEQUENCE OF Dm3StatusLVDEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for accessing settings of the LVDs. The number of
- entries is contained in the dm3StatusLVDTableSize OID."
- ::= { dm3StatusLVD 2 }
-
- dm3StatusLVDEntry OBJECT-TYPE
- SYNTAX Dm3StatusLVDEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The LVD to gather status from."
- INDEX { dm3StatusLVDIndex }
- ::= { dm3StatusLVDTable 1 }
-
- Dm3StatusLVDEntry ::=
- SEQUENCE {
- dm3StatusLVDIndex INTEGER,
- dm3StatusLVDName DisplayString,
- dm3StatusLVDState INTEGER,
- dm3StatusLVDHwFault INTEGER
- }
-
- dm3StatusLVDIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the DC powerplant LVD."
- ::= { dm3StatusLVDEntry 1 }
-
- dm3StatusLVDName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The name of the LVD. The maximum size is
- 16 characters. The name is set by using the
- dm3ConfigLVDName OID.
- This OID is provided for informational purposes only."
- ::= { dm3StatusLVDEntry 2 }
-
- dm3StatusLVDState OBJECT-TYPE
- SYNTAX INTEGER {
- statusClosed (1),
- statusOpened (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return statusClosed (1) if the LVD is closed.
- statusOpened (2) will be returned if the LVD is opened."
- ::= { dm3StatusLVDEntry 3 }
- dm3StatusLVDHwFault OBJECT-TYPE
- SYNTAX INTEGER {
- statusFault (1),
- statusNofault (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return statusFault (1) if the LVD is faulted.
- statusNofault (2) will be returned if the LVD is not faulted."
- ::= { dm3StatusLVDEntry 4 }
- -- the dm3StatusRectifier group
- dm3StatusRectTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of DC powerplant rectifiers viewable
- by this IP address."
- ::= { dm3StatusRectifier 1 }
- dm3StatusRectTable OBJECT-TYPE
- SYNTAX SEQUENCE OF Dm3StatusRectEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for accessing settings of the rectifiers. The number of
- entries is contained in the dm3StatusRectTableSize OID."
- ::= { dm3StatusRectifier 2 }
- dm3StatusRectEntry OBJECT-TYPE
- SYNTAX Dm3StatusRectEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The rectifier to gather status from."
- INDEX { dm3StatusRectIndex }
- ::= { dm3StatusRectTable 1 }
-
- Dm3StatusRectEntry ::=
- SEQUENCE {
- dm3StatusRectIndex INTEGER,
- dm3StatusRectID INTEGER,
- dm3StatusRectDesc DisplayString,
- dm3StatusRectCurrent INTEGER,
- dm3StatusRectCurrentLimit INTEGER,
- dm3StatusRectStandby INTEGER,
- dm3StatusRectFanFail INTEGER,
- dm3StatusRectFail INTEGER,
- dm3StatusRectDevType INTEGER,
- dm3StatusRectPhyAddr INTEGER,
- dm3StatusRectCfg INTEGER,
- dm3StatusRectPcbRev INTEGER,
- dm3StatusRectFwVer INTEGER,
- dm3StatusRectPresent INTEGER,
- dm3StatusRectDiagPass INTEGER,
- dm3StatusRectState INTEGER
- }
- dm3StatusRectIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the DC powerplant rectifier."
- ::= { dm3StatusRectEntry 1 }
- dm3StatusRectID OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID shows the rectifier ID. This enumerates the number of the rectifier within
- a group of rectifiers."
- ::= { dm3StatusRectEntry 2 }
- dm3StatusRectDesc OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID shows the 16-character rectifier description."
- ::= { dm3StatusRectEntry 3 }
- dm3StatusRectCurrent OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID shows the rectifier current in thousandths of Amps (mA)."
- ::= { dm3StatusRectEntry 4 }
- dm3StatusRectCurrentLimit OBJECT-TYPE
- SYNTAX INTEGER {
- statusTrue (1),
- statusFalse (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return statusTrue (1) if the rectifier is in the Current Limit state.
- statusFalse (2) will be returned if the rectifier is not in the Current Limit state."
- ::= { dm3StatusRectEntry 5 }
- dm3StatusRectStandby OBJECT-TYPE
- SYNTAX INTEGER {
- statusTrue (1),
- statusFalse (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return statusTrue (1) if the rectifier is in the Standby state.
- statusFalse (2) will be returned if the rectifier is not in the Standby state."
- ::= { dm3StatusRectEntry 6 }
- dm3StatusRectFanFail OBJECT-TYPE
- SYNTAX INTEGER {
- statusTrue (1),
- statusFalse (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return statusTrue (1) if the rectifier Fan has failed.
- statusFalse (2) will be returned if the rectifier Fan has not failed."
- ::= { dm3StatusRectEntry 7 }
- dm3StatusRectFail OBJECT-TYPE
- SYNTAX INTEGER {
- statusTrue (1),
- statusFalse (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return statusTrue (1) if the rectifier has failed.
- statusFalse (2) will be returned if the rectifier has not failed."
- ::= { dm3StatusRectEntry 8 }
- dm3StatusRectDevType OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID shows the rectifier device type."
- ::= { dm3StatusRectEntry 9 }
- dm3StatusRectPhyAddr OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID shows the rectifier physical address (the address on the bus)."
- ::= { dm3StatusRectEntry 10 }
- dm3StatusRectCfg OBJECT-TYPE
- SYNTAX INTEGER {
- statusTrue (1),
- statusFalse (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return statusTrue (1) if the rectifier is present after
- power-up or set-configuration.
- statusFalse (2) will be returned if the rectifier is not configured."
- ::= { dm3StatusRectEntry 11 }
- dm3StatusRectPcbRev OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID shows the rectifier device PCB serial number."
- ::= { dm3StatusRectEntry 12 }
- dm3StatusRectFwVer OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID shows the rectifier device firmware revision."
- ::= { dm3StatusRectEntry 13 }
- dm3StatusRectPresent OBJECT-TYPE
- SYNTAX INTEGER {
- statusTrue (1),
- statusFalse (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return statusTrue (1) if the rectifier is present.
- statusFalse (2) will be returned if the rectifier is not present."
- ::= { dm3StatusRectEntry 14 }
- dm3StatusRectDiagPass OBJECT-TYPE
- SYNTAX INTEGER {
- statusTrue (1),
- statusFalse (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return statusTrue (1) if the rectifier diagnostics have passed.
- statusFalse (2) will be returned if the rectifier diagnostics have not passed."
- ::= { dm3StatusRectEntry 15 }
- dm3StatusRectState OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID shows the rectifier device state as defined by the device status register."
- ::= { dm3StatusRectEntry 16 }
- dm3StatusSysRectVoltSanity OBJECT-TYPE
- SYNTAX INTEGER {
- saneYES (1),
- saneNO (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Rectifier voltage sanity indicator. Indicates if the rectifier voltage is
- reasonable. Reasonable is defined based on powerplant type. A value of saneYes (1)
- indicates voltage is reasonable, a value of saneNo (2) indicates it is not."
- ::= { dm3StatusRectifier 3 }
- dm3StatusSysRectAvailable OBJECT-TYPE
- SYNTAX INTEGER {
- statusTrue (1),
- statusFalse (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return statusTrue (1) if the rectifier is available.
- statusFalse (2) will be returned if the rectifier is not available."
- ::= { dm3StatusRectifier 4 }
- dm3StatusSysRectType OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID shows the type of rectifier the system has. There can only be a single type of
- rectifier in the power plant"
- ::= { dm3StatusRectifier 5 }
- dm3StatusSysRectVoltage OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID shows the system level rectifier voltage in thousandths of Volts (mV)."
- ::= { dm3StatusRectifier 6 }
- dm3StatusSysRectCurrent OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID shows the system level rectifier current in thousandths of Amps (mA)."
- ::= { dm3StatusRectifier 7 }
- -- the dm3StatusConverter group
- dm3StatusConvTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of DC powerplant converters viewable
- by this IP address."
- ::= { dm3StatusConverter 1 }
- dm3StatusConvTable OBJECT-TYPE
- SYNTAX SEQUENCE OF Dm3StatusConvEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for viewing status of the converters. The number of
- entries is contained in the dm3StatusConvTableSize OID."
- ::= { dm3StatusConverter 2 }
-
- dm3StatusConvEntry OBJECT-TYPE
- SYNTAX Dm3StatusConvEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The converter to gather status from."
- INDEX { dm3StatusConvIndex }
- ::= { dm3StatusConvTable 1 }
-
- Dm3StatusConvEntry ::=
- SEQUENCE {
- dm3StatusConvIndex INTEGER,
- dm3StatusConvID INTEGER,
- dm3StatusConvDesc DisplayString,
- dm3StatusConvCurrent INTEGER,
- dm3StatusConvCurrentLimit INTEGER,
- dm3StatusConvStandby INTEGER,
- dm3StatusConvFanFail INTEGER,
- dm3StatusConvFail INTEGER,
- dm3StatusConvDevType INTEGER,
- dm3StatusConvPhyAddr INTEGER,
- dm3StatusConvCfg INTEGER,
- dm3StatusConvPcbRev INTEGER,
- dm3StatusConvFwVer INTEGER,
- dm3StatusConvPresent INTEGER,
- dm3StatusConvDiagPass INTEGER,
- dm3StatusConvState INTEGER
- }
- dm3StatusConvIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the DC powerplant converter."
- ::= { dm3StatusConvEntry 1 }
-
- dm3StatusConvID OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID shows the converter ID. This enumerates the number of the converter within
- a group of converters."
- ::= { dm3StatusConvEntry 2 }
- dm3StatusConvDesc OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID shows the 16 character converter description."
- ::= { dm3StatusConvEntry 3 }
- dm3StatusConvCurrent OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID shows the converter current in thousandths of Amps (mA)."
- ::= { dm3StatusConvEntry 4 }
- dm3StatusConvCurrentLimit OBJECT-TYPE
- SYNTAX INTEGER {
- statusTrue (1),
- statusFalse (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return statusTrue (1) if the converter is in the Current Limit state.
- statusFalse (2) will be returned if the converter is not in the Current Limit state."
- ::= { dm3StatusConvEntry 5 }
- dm3StatusConvStandby OBJECT-TYPE
- SYNTAX INTEGER {
- statusTrue (1),
- statusFalse (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return statusTrue (1) if the converter is in the Standby state.
- statusFalse (2) will be returned if the converter is not in the Standby state."
- ::= { dm3StatusConvEntry 6 }
- dm3StatusConvFanFail OBJECT-TYPE
- SYNTAX INTEGER {
- statusTrue (1),
- statusFalse (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return statusTrue (1) if the converter Fan has failed.
- statusFalse (2) will be returned if the converter Fan has not failed."
- ::= { dm3StatusConvEntry 7 }
- dm3StatusConvFail OBJECT-TYPE
- SYNTAX INTEGER {
- statusTrue (1),
- statusFalse (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return statusTrue (1) if the converter has failed.
- statusFalse (2) will be returned if the converter has not failed."
- ::= { dm3StatusConvEntry 8 }
- dm3StatusConvDevType OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID shows the converter device type."
- ::= { dm3StatusConvEntry 9 }
- dm3StatusConvPhyAddr OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID shows the converter physical address (the address on the bus)."
- ::= { dm3StatusConvEntry 10 }
- dm3StatusConvCfg OBJECT-TYPE
- SYNTAX INTEGER {
- statusTrue (1),
- statusFalse (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return statusTrue (1) if the converter is present after
- power-up or set-configuration.
- statusFalse (2) will be returned if the converter is not configured."
- ::= { dm3StatusConvEntry 11 }
- dm3StatusConvPcbRev OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID shows the converter device PCB serial number."
- ::= { dm3StatusConvEntry 12 }
- dm3StatusConvFwVer OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID shows the converter device firmware version."
- ::= { dm3StatusConvEntry 13 }
- dm3StatusConvPresent OBJECT-TYPE
- SYNTAX INTEGER {
- statusTrue (1),
- statusFalse (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return statusTrue (1) if the converter is present.
- statusFalse (2) will be returned if the converter is not present."
- ::= { dm3StatusConvEntry 14 }
- dm3StatusConvDiagPass OBJECT-TYPE
- SYNTAX INTEGER {
- statusTrue (1),
- statusFalse (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return statusTrue (1) if the converter diagnostics have passed.
- statusFalse (2) will be returned if the converter diagnostics have not passed."
- ::= { dm3StatusConvEntry 15 }
- dm3StatusConvState OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID shows the converter state as defined by the device status register."
- ::= { dm3StatusConvEntry 16 }
- dm3StatusSysConvVoltSanity OBJECT-TYPE
- SYNTAX INTEGER{
- saneYES (1),
- saneNO (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Converter voltage sanity indicator. Indicates if the converter voltage is
- reasonable. Reasonable is defined based on powerplant type. A value of saneYes (1)
- indicates voltage is reasonable, a value of saneNo (2) indicates it is not."
- ::= { dm3StatusConverter 3 }
-
- dm3StatusSysConvAvailable OBJECT-TYPE
- SYNTAX INTEGER {
- statusTrue (1),
- statusFalse (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return statusTrue (1) if the converter is available.
- statusFalse (2) will be returned if the converter is not available."
- ::= { dm3StatusConverter 4 }
-
- dm3StatusSysConvType OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID shows the converter type."
- ::= { dm3StatusConverter 5 }
-
- dm3StatusSysConvVoltage OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID shows the system level converter voltage in thousandths of volts (mV)."
- ::= { dm3StatusConverter 6 }
-
- dm3StatusSysConvCurrent OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID shows the system level converter current in thousandths of Amps (mA)."
- ::= { dm3StatusConverter 7 }
- -- the dm3StatusOutputRelays group
- dm3StatusOutRlyTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of DC powerplant output relays viewable
- by this IP address."
- ::= { dm3StatusOutputRelays 1 }
- dm3StatusOutRlyTable OBJECT-TYPE
- SYNTAX SEQUENCE OF Dm3StatusOutRlyEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for viewing status of the output relays. The number of
- entries is contained in the dm3StatusOutRlyTableSize OID."
- ::= { dm3StatusOutputRelays 2 }
-
- dm3StatusOutRlyEntry OBJECT-TYPE
- SYNTAX Dm3StatusOutRlyEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The output relay to gather status from."
- INDEX { dm3StatusOutRlyIndex }
- ::= { dm3StatusOutRlyTable 1 }
- Dm3StatusOutRlyEntry ::=
- SEQUENCE {
- dm3StatusOutRlyIndex INTEGER,
- dm3StatusOutRlyName DisplayString,
- dm3StatusOutRlyStatus INTEGER
- }
-
- dm3StatusOutRlyIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the DC powerplant output relay."
- ::= { dm3StatusOutRlyEntry 1 }
-
- dm3StatusOutRlyName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The name of the output relay. The maximum size is
- 16 characters. The name is set by using the
- dm3ConfigOutRlyName OID.
- This OID is provided for informational purposes only."
- ::= { dm3StatusOutRlyEntry 2 }
-
- dm3StatusOutRlyStatus OBJECT-TYPE
- SYNTAX INTEGER {
- statusOn (1),
- statusOff (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return statusOn (1) if the output relay is enabled/on.
- statusOff (2) will be returned if the output relay is disabled/off."
- ::= { dm3StatusOutRlyEntry 3 }
- -- the dm3StatusInputRelays group
- dm3StatusInRlyTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of DC powerplant input relays viewable
- by this IP address."
- ::= { dm3StatusInputRelays 1 }
- dm3StatusInRlyTable OBJECT-TYPE
- SYNTAX SEQUENCE OF Dm3StatusInRlyEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for viewing status of the input relays. The number of
- entries is contained in the dm3StatusInRlyTableSize OID."
- ::= { dm3StatusInputRelays 2 }
-
- dm3StatusInRlyEntry OBJECT-TYPE
- SYNTAX Dm3StatusInRlyEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The input relays to gather status from."
- INDEX { dm3StatusInRlyIndex }
- ::= { dm3StatusInRlyTable 1 }
-
- Dm3StatusInRlyEntry ::=
- SEQUENCE {
- dm3StatusInRlyIndex INTEGER,
- dm3StatusInRlyName DisplayString,
- dm3StatusInRlyStatus INTEGER
- }
-
- dm3StatusInRlyIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the DC powerplant input relay."
- ::= { dm3StatusInRlyEntry 1 }
-
- dm3StatusInRlyName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The name of the input relay. The maximum size is
- 16 characters. The name is set by using the
- dm3ConfigInRlyName OID.
- This OID is provided for informational purposes only."
- ::= { dm3StatusInRlyEntry 2 }
-
- dm3StatusInRlyStatus OBJECT-TYPE
- SYNTAX INTEGER {
- statusOn (1),
- statusOff (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return statusOn (1) if the input relay is enabled/on.
- statusOff (2) will be returned if the input relay is disabled/off."
- ::= { dm3StatusInRlyEntry 3 }
- -- the dm3StatusBreakers group
- dm3StatusBreakersTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of DC powerplant circuit breakers viewable
- by this IP address."
- ::= { dm3StatusBreakers 1 }
- dm3StatusBreakersTable OBJECT-TYPE
- SYNTAX SEQUENCE OF Dm3StatusBreakersEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for viewing status of the circuit breakers. The number of
- entries is contained in the dm3StatusBreakersTableSize OID."
- ::= { dm3StatusBreakers 2 }
- dm3StatusBreakersEntry OBJECT-TYPE
- SYNTAX Dm3StatusBreakersEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The circuit breaker to gather status from."
- INDEX { dm3StatusBreakersIndex }
- ::= { dm3StatusBreakersTable 1 }
- Dm3StatusBreakersEntry ::=
- SEQUENCE {
- dm3StatusBreakersIndex INTEGER,
- dm3StatusBreakersName DisplayString,
- dm3StatusBreakersStatus INTEGER
- }
-
- dm3StatusBreakersIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the DC powerplant circuit breaker."
- ::= { dm3StatusBreakersEntry 1 }
-
- dm3StatusBreakersName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The name of the circuit breaker. The maximum size is
- 16 characters. The name is set by using the
- dm3ConfigBreakersName OID.
- This OID is provided for informational purposes only."
- ::= { dm3StatusBreakersEntry 2 }
-
- dm3StatusBreakersStatus OBJECT-TYPE
- SYNTAX INTEGER {
- statusClosed (1),
- statusOpen (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return statusClosed (1) if the circuit breaker is closed.
- statusOpen (2) will be returned if the circuit breaker is open."
- ::= { dm3StatusBreakersEntry 3 }
-
- -- the dm3StatusFuses group
- dm3StatusFusesTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of DC powerplant fuses controllable
- by this IP address."
- ::= { dm3StatusFuses 1 }
- dm3StatusFusesTable OBJECT-TYPE
- SYNTAX SEQUENCE OF Dm3StatusFusesEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for viewing status of the fuses. The number of
- entries is contained in the dm3StatusFusesTableSize OID."
- ::= { dm3StatusFuses 2 }
-
- dm3StatusFusesEntry OBJECT-TYPE
- SYNTAX Dm3StatusFusesEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The fuse to gather status from."
- INDEX { dm3StatusFusesIndex }
- ::= { dm3StatusFusesTable 1 }
-
- Dm3StatusFusesEntry ::=
- SEQUENCE {
- dm3StatusFusesIndex INTEGER,
- dm3StatusFusesName DisplayString,
- dm3StatusFusesStatus INTEGER
- }
- dm3StatusFusesIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the DC powerplant fuse."
- ::= { dm3StatusFusesEntry 1 }
-
- dm3StatusFusesName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The name of the fuse. The maximum size is
- 16 characters. The name is set by using the
- dm3ConfigFuseName OID.
- This OID is provided for informational purposes only."
- ::= { dm3StatusFusesEntry 2 }
- dm3StatusFusesStatus OBJECT-TYPE
- SYNTAX INTEGER {
- statusClosed (1),
- statusOpen (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return statusClosed (1) if the fuse is closed.
- statusOpen (2) will be returned if the fuse is open."
- ::= { dm3StatusFusesEntry 3 }
- -- the atsIdent group
- atsIdentHardwareRev OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The hardware revision of the Automatic Transfer Switch.
- This value is set at the factory."
- ::= { atsIdent 1 }
- atsIdentFirmwareRev OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A string identifying the Automatic Transfer Switch
- firmware revision."
- ::= { atsIdent 2 }
- atsIdentFirmwareDate OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The date of release for this Automatic Transfer Switch
- firmware revision. "
- ::= { atsIdent 3 }
- atsIdentDateOfManufacture OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The date when the Automatic Transfer Switch was manufactured in mm/dd/yyyy format.
- This value is set at the factory. "
- ::= { atsIdent 4 }
-
- atsIdentModelNumber OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A string identifying the model number of the Automatic Transfer Switch.
- This value is set at the factory."
- ::= { atsIdent 5 }
- atsIdentSerialNumber OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A string identifying the serial number of
- the Automatic Transfer Switch. This value is set at the factory."
- ::= { atsIdent 6 }
- atsIdentNominalLineVoltage OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "RMS Utility Voltage measured in Volts."
- ::= { atsIdent 7 }
- atsIdentNominalLineFrequency OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Utility Power Frequency measured in Hertz."
- ::= { atsIdent 8 }
- atsIdentDeviceRating OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This gives the device rating in Amps"
- ::= { atsIdent 9 }
-
- -- the atsCalibration group
-
- -- Input Voltage Calibration Factor table
- atsCalibrationNumInputs OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of inputs to this device."
- ::= { atsCalibrationInput 1 }
- atsCalibrationNumInputPhases OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of phases per input for this device."
- ::= { atsCalibrationInput 2 }
- atsCalibrationInputPhaseTable OBJECT-TYPE
- SYNTAX SEQUENCE OF ATSCalibrationInputPhaseEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The number of phases per input line to this device."
- ::= { atsCalibrationInput 3 }
- atsCalibrationInputPhaseEntry OBJECT-TYPE
- SYNTAX ATSCalibrationInputPhaseEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "An entry containing calibration information applicable to a
- particular input phase."
- INDEX { atsCalibrationInputTableIndex, atsCalibrationInputPhaseTableIndex }
- ::= { atsCalibrationInputPhaseTable 1 }
- ATSCalibrationInputPhaseEntry ::= SEQUENCE {
- atsCalibrationInputTableIndex INTEGER,
- atsCalibrationInputPhaseTableIndex INTEGER,
- atsLineVoltageCalibrationFactor INTEGER
- }
- atsCalibrationInputTableIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The input identifier."
- ::= { atsCalibrationInputPhaseEntry 1 }
- atsCalibrationInputPhaseTableIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The input phase identifier."
- ::= { atsCalibrationInputPhaseEntry 2 }
- atsLineVoltageCalibrationFactor OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The Line Voltage Calibration factor.
- This value is set at the factory."
- ::= { atsCalibrationInputPhaseEntry 3 }
- -- Power Supply Voltage Calibration table
- atsCalibrationPowerSupplyVoltages OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of power supply voltages supported by this device.
- This variable indicates the number of rows in the
- atsCalibrationPowerSupplyTable."
- ::= { atsCalibrationPowerSupply 1 }
- atsCalibrationPowerSupplyVoltageTable OBJECT-TYPE
- SYNTAX SEQUENCE OF ATSCalibrationPowerSupplyVoltageEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "A list of Power Supply table entries."
- ::= { atsCalibrationPowerSupply 2 }
- atsCalibrationPowerSupplyVoltageEntry OBJECT-TYPE
- SYNTAX ATSCalibrationPowerSupplyVoltageEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "An entry containing information applicable to a
- particular Power Supply Voltage."
- INDEX { atsCalibrationPowerSupplyVoltageTableIndex }
- ::= { atsCalibrationPowerSupplyVoltageTable 1 }
- ATSCalibrationPowerSupplyVoltageEntry ::= SEQUENCE {
- atsCalibrationPowerSupplyVoltageTableIndex INTEGER,
- atsCalibrationPowerSupplyVoltage INTEGER,
- atsPowerSupplyVoltageCalibrationFactor INTEGER
- }
- atsCalibrationPowerSupplyVoltageTableIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The power supply voltage identifier."
- ::= { atsCalibrationPowerSupplyVoltageEntry 1 }
- atsCalibrationPowerSupplyVoltage OBJECT-TYPE
- SYNTAX INTEGER {
- powerSupply24V(1),
- powerSupply12V(2),
- powerSupply(3),
- powerSupply24VSourceB(4),
- powerSupplyMinus12V(5)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This value describes the power supply voltage of
- 24V Source A, 24V Source B, +12V, -12V and 5V."
- ::= { atsCalibrationPowerSupplyVoltageEntry 2 }
- atsPowerSupplyVoltageCalibrationFactor OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The Line Voltage Calibration factor.
- This value is set at the factory."
- ::= { atsCalibrationPowerSupplyVoltageEntry 3 }
- -- Output Current Calibration table
- atsCalibrationNumOutputs OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of output lines from this device.
- This variable indicates the number of rows in the
- atsCalibrationOutputTable."
- ::= { atsCalibrationOutput 1 }
- atsCalibrationNumOutputPhases OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of output phases utilized in this
- device."
- ::= { atsCalibrationOutput 2 }
- atsCalibrationOutputTable OBJECT-TYPE
- SYNTAX SEQUENCE OF ATSCalibrationOutputEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "A list of output table entries."
- ::= { atsCalibrationOutput 3 }
- atsCalibrationOutputEntry OBJECT-TYPE
- SYNTAX ATSCalibrationOutputEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "An entry containing information applicable to a
- particular output."
- INDEX { atsCalibrationOutputTableIndex, atsCalibrationOutputPhasesTableIndex }
- ::= { atsCalibrationOutputTable 1 }
- ATSCalibrationOutputEntry ::= SEQUENCE {
- atsCalibrationOutputTableIndex INTEGER,
- atsCalibrationOutputPhasesTableIndex INTEGER,
- atsOutputCurrentCalibrationFactor INTEGER
- }
- atsCalibrationOutputTableIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The output identifier."
- ::= { atsCalibrationOutputEntry 1 }
- atsCalibrationOutputPhasesTableIndex OBJECT-TYPE
- SYNTAX INTEGER{
- phase1(1),
- phase2(2),
- phase3(3),
- neutral(4)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Description of each calibration factor for each
- output phase utilized in this device and one for neutral. "
- ::= { atsCalibrationOutputEntry 2 }
- atsOutputCurrentCalibrationFactor OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The output current calibration factor measured in Amps."
- ::= { atsCalibrationOutputEntry 3 }
- -- the atsControl group
-
- atsControlResetATS OBJECT-TYPE
- SYNTAX INTEGER {
- none(1),
- reset(2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Setting this variable will cause the Automatic Transfer Switch to
- perform a power-on reset."
- ::= { atsControl 1 }
- atsControlClearAllAlarms OBJECT-TYPE
- SYNTAX INTEGER {
- none(1),
- clear(2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Setting this variable will clear all alarms in the Automatic Transfer Switch.
- Returns (-1) if unsupported."
- ::= { atsControl 2 }
-
- -- the atsConfig group
-
- atsConfigProductName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "A configurable character string."
- ::= { atsConfig 1 }
-
- atsConfigPreferredSource OBJECT-TYPE
- SYNTAX INTEGER {
- sourceA(1),
- sourceB(2),
- none(3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "This variable returns the preferred source of power when both sources are OK."
- ::= { atsConfig 2 }
- atsConfigFrontPanelLockout OBJECT-TYPE
- SYNTAX INTEGER {
- disableFrontPanel(1),
- enableFrontPanel(2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Setting this variable to disableFrontPanel(1), prevents source
- preference configuration of the Automatic Transfer Switch via the
- Front Panel.
- Setting this variable to enableFrontPanel(2)allows, source preference
- configuration of the Automatic Transfer Switch via the Front Panel."
- ::= { atsConfig 3 }
- atsConfigVoltageSensitivity OBJECT-TYPE
- SYNTAX INTEGER {
- high(1),
- low(2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "This variable defines the sensitivity to changes in voltage:
- high(1) for best protection, low(2) for frequent small line
- voltage changes."
- ::= { atsConfig 4 }
- atsConfigTransferVoltageRange OBJECT-TYPE
- SYNTAX INTEGER {
- wide(1),
- medium(2),
- narrow(3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "This variable defines the range of acceptable voltage from a power source.
- If the voltage measured from the selected input source is not within this
- range, the Automatic Transfer Switch will switch over (transfer) to the
- alternate power source."
- ::= { atsConfig 5 }
- atsConfigCurrentLimit OBJECT-TYPE
- SYNTAX INTEGER (0..20)
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The threshold (in Amps) at which an Over Current Alarm will be generated.
- This OID returns the overload threshold value of the
- OID atsConfigPhaseOverLoadThreshold for the 1U ATS and
- OID atsConfigBankOverLoadThreshold of total for the 2U ATS.
- Setting this OID does not have any impact on the device."
- ::= { atsConfig 6 }
- atsConfigResetValues OBJECT-TYPE
- SYNTAX INTEGER {
- none(1),
- reset(2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Resets the ATS configuration to its default values.
- Returns (-1) if not supported."
- ::= { atsConfig 7 }
- atsConfigLineVRMS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "To configure the input RMS voltage."
-
- ::= { atsConfig 8 }
- atsConfigLineVRMSNarrowLimit OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "To configure the Line VRMS Narrow Limit."
-
- ::= { atsConfig 9 }
- atsConfigLineVRMSMediumLimit OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "To configure the Line VRMS Medium Limit."
-
- ::= { atsConfig 10 }
- atsConfigLineVRMSWideLimit OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "To configure the Line VRMS Wide Limit."
-
- ::= { atsConfig 11 }
- atsConfigFrequencyDeviation OBJECT-TYPE
- SYNTAX INTEGER {
- one(1),
- two(2),
- three(3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "To configure the frequency deviation."
-
- ::= { atsConfig 12 }
- -- Bank table
- atsConfigBankTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The size of the bank table."
- ::= { atsConfig 13 }
-
-
- atsConfigBankTable OBJECT-TYPE
- SYNTAX SEQUENCE OF ATSConfigBankEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for configuration of each ATS bank."
- ::= { atsConfig 14 }
- atsConfigBankEntry OBJECT-TYPE
- SYNTAX ATSConfigBankEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "This gives access to bank current threshold"
- INDEX { atsConfigBankTableIndex }
- ::= { atsConfigBankTable 1 }
- ATSConfigBankEntry ::=
- SEQUENCE {
- atsConfigBankTableIndex INTEGER,
- atsConfigBank INTEGER,
- atsConfigBankLowLoadThreshold INTEGER,
- atsConfigBankNearOverLoadThreshold INTEGER,
- atsConfigBankOverLoadThreshold INTEGER
- }
- atsConfigBankTableIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "An index to the bank table entry."
- ::= { atsConfigBankEntry 1 }
- atsConfigBank OBJECT-TYPE
- SYNTAX INTEGER {
- total (1),
- bank1 (2),
- bank2 (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The bank number of an ATS"
- ::= { atsConfigBankEntry 2 }
- atsConfigBankLowLoadThreshold OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "A threshold that indicates the current drawn is nearing
- a low consumption condition. It is represented in Amps.
- A warning will be issued when the load is less than the
- threshold value.
-
- A threshold value of 0 Amps disables this warning.
-
- Maximum value must be less than the value returned
- by the atsConfigBankNearOverLoadThreshold OID."
- ::= { atsConfigBankEntry 3 }
- atsConfigBankNearOverLoadThreshold OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "A threshold that indicates the current drawn is nearing
- an overload condition. It is represented in Amps.
- A warning will be issued when the load is greater than
- or equal to the threshold value.
-
- Minimum value must be greater than the value returned by
- the atsConfigBankLowLoadThreshold OID.
-
- Maximum value must be less than or equal to the value
- returned by the atsConfigBankOverLoadThreshold OID."
- ::= { atsConfigBankEntry 4 }
- atsConfigBankOverLoadThreshold OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "A threshold that indicates the current drawn has entered
- an overload condition. It is represented in Amps.
- A warning will be issued when the load is greater than or
- equal to the threshold value.
-
- Minimum value must be greater than or equal to the value
- returned by the atsConfigBankNearOverLoadThreshold OID.
-
- Maximum value must be less than or equal to the value returned by
- atsIdentDeviceRating OID."
- ::= { atsConfigBankEntry 5 }
- -- Phase table
- atsConfigPhaseTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The size of the phase table."
- ::= { atsConfig 15 }
-
-
- atsConfigPhaseTable OBJECT-TYPE
- SYNTAX SEQUENCE OF ATSConfigPhaseEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for configuration of each ATS phase."
- ::= { atsConfig 16 }
- atsConfigPhaseEntry OBJECT-TYPE
- SYNTAX ATSConfigPhaseEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "This gives access to phase threshold"
- INDEX { atsConfigPhaseTableIndex }
- ::= { atsConfigPhaseTable 1 }
- ATSConfigPhaseEntry ::=
- SEQUENCE {
- atsConfigPhaseTableIndex INTEGER,
- atsConfigPhase INTEGER,
- atsConfigPhaseLowLoadThreshold INTEGER,
- atsConfigPhaseNearOverLoadThreshold INTEGER,
- atsConfigPhaseOverLoadThreshold INTEGER
- }
- atsConfigPhaseTableIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the phase table entry."
- ::= { atsConfigPhaseEntry 1 }
- atsConfigPhase OBJECT-TYPE
- SYNTAX INTEGER {
- phase1 (1),
- phase2 (2),
- phase3 (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The phase number of an ATS"
- ::= { atsConfigPhaseEntry 2 }
- atsConfigPhaseLowLoadThreshold OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "A threshold that indicates the current drawn is nearing
- a low consumption condition. It is represented in Amps.
- A warning will be issued when the load is less than the
- threshold value.
-
- A threshold value of 0 Amps disables this warning.
-
- Maximum value must be less than the value returned
- by the atsConfigPhaseNearOverLoadThreshold OID."
- ::= { atsConfigPhaseEntry 3 }
- atsConfigPhaseNearOverLoadThreshold OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "A threshold that indicates the current drawn is nearing
- an overload condition. It is represented in Amps.
- A warning will be issued when the load is greater than
- or equal to the threshold value.
-
- Minimum value must be greater than the value returned by
- the atsConfigPhaseLowLoadThreshold OID.
-
- Maximum value must be less than or equal to the value
- returned by the atsConfigPhaseOverLoadThreshold OID."
- ::= { atsConfigPhaseEntry 4 }
- atsConfigPhaseOverLoadThreshold OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "A threshold that indicates the current drawn has entered
- an overload condition. It is represented in Amps.
- A warning will be issued when the load is greater than or
- equal to the threshold value.
-
- Minimum value must be greater than or equal to the value
- returned by the atsConfigPhaseNearOverLoadThreshold OID.
-
- Maximum value must be less than or equal to the value
- returned by atsIdentDeviceRating OID."
- ::= { atsConfigPhaseEntry 5 }
- -- the atsStatus group
- atsStatusCommStatus OBJECT-TYPE
- SYNTAX INTEGER {
- atsNeverDiscovered(1),
- atsCommEstablished(2),
- atsCommLost(3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This variable returns the current communication status
- of the Automatic Transfer Switch. "
- ::= { atsStatusDeviceStatus 1 }
- atsStatusSelectedSource OBJECT-TYPE
- SYNTAX INTEGER {
- sourceA(1),
- sourceB(2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This variable returns the current source of power. "
- ::= { atsStatusDeviceStatus 2 }
- atsStatusRedundancyState OBJECT-TYPE
- SYNTAX INTEGER {
- atsRedundancyLost(1),
- atsFullyRedundant(2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This variable returns the current redundancy state of the ATS.
- atsRedundancyLost(1) indicates that the ATS is unable to
- switch over to the alternate power source if the current source fails.
- atsFullyRedundant(2) indicates that the ATS will switch over to
- the alternate power source if the current source fails."
- ::= { atsStatusDeviceStatus 3 }
- atsStatusOverCurrentState OBJECT-TYPE
- SYNTAX INTEGER {
- atsOverCurrent(1),
- atsCurrentOK(2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This variable returns the output current state of the ATS.
- atsOverCurrent(1) indicates that the ATS has exceeded the output
- current threshold and will not allow a switch over to the alternate power
- source if the current source fails.
- atsCurrentOK(2) indicates that the output current is below the
- output current threshold.
- This OID returns the value of the OID atsOutputPhaseState for the 1U ATS and
- OID atsOutputBankState for the 2U ATS."
- ::= { atsStatusDeviceStatus 4 }
- atsStatus5VPowerSupply OBJECT-TYPE
- SYNTAX INTEGER {
- atsPowerSupplyFailure(1),
- atsPowerSupplyOK(2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This variable returns the present state of the ATS 5V power supply.
- atsPowerSupplyFailure(1) indicates the 5V power supply has failed
- and that the ATS serial port Configuration Menu is not accessible .
- atsPowerSupplyOK(2) indicates that the ATS 5V power supply
- is operating within tolerance."
- ::= { atsStatusDeviceStatus 5 }
- atsStatus24VPowerSupply OBJECT-TYPE
- SYNTAX INTEGER {
- atsPowerSupplyFailure(1),
- atsPowerSupplyOK(2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This variable returns the present state of the ATS 24V power supply for Source A.
- atsPowerSupplyFailure(1) indicates the 24V power supply has failed
- and the ATS is unable to switch over to the alternate power source if
- the current source fails.
- atsPowerSupplyOK(2) indicates that the ATS 24V power supply
- is operating within tolerance."
- ::= { atsStatusDeviceStatus 6 }
- atsStatus24VSourceBPowerSupply OBJECT-TYPE
- SYNTAX INTEGER {
- atsPowerSupplyFailure(1),
- atsPowerSupplyOK(2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This variable returns the present state of the ATS 24V power supply for Source B.
- atsPowerSupplyFailure(1) indicates the 24V power supply has failed
- and the ATS is unable to switch over to the alternate power source if
- the current source fails.
- atsPowerSupplyOK(2) indicates that the ATS 24V power supply
- is operating within tolerance."
- ::= { atsStatusDeviceStatus 7 }
- atsStatusPlus12VPowerSupply OBJECT-TYPE
- SYNTAX INTEGER {
- atsPowerSupplyFailure(1),
- atsPowerSupplyOK(2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This variable returns the present state of the ATS 12V power supply.
- atsPowerSupplyFailure(1) indicates the 12V power supply has failed
- and the ATS is unable to monitor the current sensors.
- atsPowerSupplyOK(2) indicates that the ATS 12V power supply
- is operating within tolerance."
- ::= { atsStatusDeviceStatus 8 }
- atsStatusMinus12VPowerSupply OBJECT-TYPE
- SYNTAX INTEGER {
- atsPowerSupplyFailure(1),
- atsPowerSupplyOK(2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This variable returns the present state of the ATS -12V power supply.
- atsPowerSupplyFailure(1) indicates the -12V power supply has failed
- and the ATS is unable to monitor the current sensors.
- atsPowerSupplyOK(2) indicates that the ATS -12V power supply
- is operating within tolerance."
- ::= { atsStatusDeviceStatus 9 }
- atsStatusSwitchStatus OBJECT-TYPE
- SYNTAX INTEGER {
- fail(1),
- ok(2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This variable returns the status of the ATS."
- ::= { atsStatusDeviceStatus 10 }
- atsStatusFrontPanel OBJECT-TYPE
- SYNTAX INTEGER {
- locked(1),
- unlocked(2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This variable returns the present state of the ATS front panel.
- locked(1): Front panel button cannot be used to change the sources.
- unlocked(2): Front panel button can be used to change the sources. "
- ::= { atsStatusDeviceStatus 11 }
- atsStatusSourceAStatus OBJECT-TYPE
- SYNTAX INTEGER {
- fail(1),
- ok(2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This variable returns the status of the Source A."
- ::= { atsStatusDeviceStatus 12 }
- atsStatusSourceBStatus OBJECT-TYPE
- SYNTAX INTEGER {
- fail(1),
- ok(2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This variable returns the status of the Source B."
- ::= { atsStatusDeviceStatus 13 }
- atsStatusPhaseSyncStatus OBJECT-TYPE
- SYNTAX INTEGER {
- inSync(1),
- outOfSync(2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This variable returns the status of the phase synch."
- ::= { atsStatusDeviceStatus 14 }
- atsStatusVoltageOutStatus OBJECT-TYPE
- SYNTAX INTEGER {
- fail(1),
- ok(2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This variable returns the output voltage status."
- ::= { atsStatusDeviceStatus 15 }
- atsStatusHardwareStatus OBJECT-TYPE
- SYNTAX INTEGER {
- fail(1),
- ok(2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This variable returns the status of display board hardware."
- ::= { atsStatusDeviceStatus 16 }
- atsStatusResetMaxMinValues OBJECT-TYPE
- SYNTAX INTEGER {
- none(1),
- reset(2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Resets the maximum and minimum ATS values:
- atsInputMaxVoltage, atsInputMinVoltage,
- atsInputMaxCurrent, atsInputMinCurrent,
- atsInputMaxPower, atsInputMinPower,
- atsOutputMaxCurrent, atsOutputMinCurrent,
- atsOutputMaxLoad, atsOutputMinLoad,
- atsOutputMaxPercentLoad, atsOutputMinPercentLoad,
- atsOutputMaxPower, atsOutputMinPower,
- atsOutputMaxPercentPower, atsOutputMinPercentPower.
- These variables represent the maximum and minimum ATS values
- since the last time they were read or reset by this OID.
- Values unsupported by this ATS will return (-1)."
- ::= { atsStatusResetValues 1 }
- --
- -- Input Group
- --
- -- Number of Inputs
- atsNumInputs OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of input feeds to this device.
- This variable indicates the number of rows in the
- input table."
- ::= { atsStatusInput 1 }
- -- Input Table
- atsInputTable OBJECT-TYPE
- SYNTAX SEQUENCE OF AtsInputEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "A list of input table entries. The number of entries
- is given by the value of atsNumInputs."
- ::= { atsStatusInput 2 }
- atsInputEntry OBJECT-TYPE
- SYNTAX AtsInputEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "An entry containing information applicable to a
- particular input."
- INDEX { atsInputTableIndex }
- ::= { atsInputTable 1 }
- AtsInputEntry ::= SEQUENCE {
- atsInputTableIndex INTEGER,
- atsNumInputPhases INTEGER,
- atsInputVoltageOrientation INTEGER,
- atsInputFrequency INTEGER,
- atsInputType INTEGER,
- atsInputName DisplayString
- }
- atsInputTableIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The input identifier."
- ::= { atsInputEntry 1 }
- atsNumInputPhases OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of input phases utilized in this
- device. The sum of all the atsNumInputPhases
- variable indicates the number of rows in the
- input phase table."
- ::= { atsInputEntry 2 }
- atsInputVoltageOrientation OBJECT-TYPE
- SYNTAX INTEGER {
- unknown(1),
- singlePhase(2),
- splitPhase(3),
- threePhasePhaseToNeutral(4),
- threePhasePhaseToPhase(5)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The input voltage orientation:
- 1: unknown for this Source
- 2: singlePhase - phase 1 voltage is between Phase 1
- and Neutral.
- 3: splitPhase - phase 1 voltage is between Phase 1 and
- Neutral; phase 2 voltage is between Phase 2 and Neutral;
- phase 3 voltage is between Phase 1 and Phase 2.
- 4: threePhasePhaseToNeutral - phase 1 voltage is between
- Phase 1 and Neutral; phase 2 voltage is between Phase 2
- and Neutral; phase 3 voltage is between Phase 3 and
- Neutral.
- 5: threePhasePhaseToPhase - phase 1 voltage is between
- Phase 1 and Phase 2; phase 2 voltage is between Phase 2
- and Phase 3; phase 3 voltage is between Phase 3 and
- Phase 1."
- ::= { atsInputEntry 3 }
- atsInputFrequency OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The input frequency in Hertz, or -1 if it's unsupported
- by this Source."
- ::= { atsInputEntry 4 }
- atsInputType OBJECT-TYPE
- SYNTAX INTEGER {
- unknown(1),
- main(2),
- bypass(3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The input type."
- ::= { atsInputEntry 5 }
- atsInputName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "A name given to a particular input."
- ::= { atsInputEntry 6 }
- -- Input Phase Table
- atsInputPhaseTable OBJECT-TYPE
- SYNTAX SEQUENCE OF AtsInputPhaseEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "A list of input table entries. The number of entries
- is given by the sum of the atsNumInputPhases."
- ::= { atsStatusInput 3 }
- atsInputPhaseEntry OBJECT-TYPE
- SYNTAX AtsInputPhaseEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "An entry containing information applicable to a
- particular input phase."
- INDEX { atsInputPhaseTableIndex, atsInputPhaseIndex }
- ::= { atsInputPhaseTable 1 }
- AtsInputPhaseEntry ::= SEQUENCE {
- atsInputPhaseTableIndex INTEGER,
- atsInputPhaseIndex INTEGER,
- atsInputVoltage INTEGER,
- atsInputMaxVoltage INTEGER,
- atsInputMinVoltage INTEGER,
- atsInputCurrent INTEGER,
- atsInputMaxCurrent INTEGER,
- atsInputMinCurrent INTEGER,
- atsInputPower INTEGER,
- atsInputMaxPower INTEGER,
- atsInputMinPower INTEGER
- }
- atsInputPhaseTableIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The input identifier."
- ::= { atsInputPhaseEntry 1 }
- atsInputPhaseIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The input phase identifier."
- ::= { atsInputPhaseEntry 2 }
- atsInputVoltage OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The input voltage in VAC, or -1 if it's unsupported
- by this Source."
- ::= { atsInputPhaseEntry 3 }
- atsInputMaxVoltage OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The maximum input voltage in VAC measured
- since the last time this variable was read
- or reset (atsStatusResetMaxMinValues).
- Returns (-1) if unsupported."
- ::= { atsInputPhaseEntry 4 }
- atsInputMinVoltage OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The minimum input voltage in VAC measured
- since the last time this variable was read
- or reset (atsStatusResetMaxMinValues).
- Returns (-1) if unsupported."
- ::= { atsInputPhaseEntry 5 }
- atsInputCurrent OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The input current in amperes, or -1 if it's
- unsupported by this Source."
- ::= { atsInputPhaseEntry 6 }
- atsInputMaxCurrent OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The maximum input current in amperes measured
- since the last time this variable was read
- or reset (atsStatusResetMaxMinValues).
- Returns (-1) if unsupported."
- ::= { atsInputPhaseEntry 7 }
- atsInputMinCurrent OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The minimum input current in amperes measured
- since the last time this variable was read
- or reset (atsStatusResetMaxMinValues).
- Returns (-1) if unsupported."
- ::= { atsInputPhaseEntry 8 }
- atsInputPower OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The input power in Watts, or -1 if it's unsupported
- by this Source."
- ::= { atsInputPhaseEntry 9 }
- atsInputMaxPower OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The maximum input power in Watts measured
- since the last time this variable was read
- or reset (atsStatusResetMaxMinValues).
- Returns (-1) if unsupported."
- ::= { atsInputPhaseEntry 10 }
- atsInputMinPower OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The minimum input power in Watts measured
- since the last time this variable was read
- or reset (atsStatusResetMaxMinValues).
- Returns (-1) if unsupported."
- ::= { atsInputPhaseEntry 11 }
- --
- -- The Output group.
- --
- -- Number of Outputs
- atsNumOutputs OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of output feeds to this device.
- This variable indicates the number of rows in the
- output table."
- ::= { atsStatusOutput 1 }
- -- Output Table
- atsOutputTable OBJECT-TYPE
- SYNTAX SEQUENCE OF AtsOutputEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "A list of output table entries. The number of entries
- is given by the value of atsOutputNumPhases."
- ::= { atsStatusOutput 2 }
- atsOutputEntry OBJECT-TYPE
- SYNTAX AtsOutputEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "An entry containing information applicable to a
- particular output."
- INDEX { atsOutputTableIndex }
- ::= { atsOutputTable 1 }
- AtsOutputEntry ::= SEQUENCE {
- atsOutputTableIndex INTEGER,
- atsNumOutputPhases INTEGER,
- atsOutputVoltageOrientation INTEGER,
- atsOutputFrequency INTEGER
- }
- atsOutputTableIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The output identifier."
- ::= { atsOutputEntry 1 }
- atsNumOutputPhases OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of output phases utilized in this
- device. The sum of all the atsNumOutputPhases
- variable indicates the number of rows in the
- output phase table."
- ::= { atsOutputEntry 2 }
- atsOutputVoltageOrientation OBJECT-TYPE
- SYNTAX INTEGER {
- unknown(1),
- singlePhase(2),
- splitPhase(3),
- threePhasePhaseToNeutral(4),
- threePhasePhaseToPhase(5)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The output voltage orientation:
- 1: unknown for this ATS
- 2: singlePhase - phase 1 voltage is between Phase 1
- and Neutral.
- 3: splitPhase - phase 1 voltage is between Phase 1 and
- Neutral; phase 2 voltage is between Phase 2 and Neutral;
- phase 3 voltage is between Phase 1 and Phase 2.
- 4: threePhasePhaseToNeutral - phase 1 voltage is between
- Phase 1 and Neutral; phase 2 voltage is between Phase 2
- and Neutral; phase 3 voltage is between Phase 3 and
- Neutral.
- 5: threePhasePhaseToPhase - phase 1 voltage is between
- Phase 1 and Phase 2; phase 2 voltage is between Phase 2
- and Phase 3; phase 3 voltage is between Phase 3 and
- Phase 1."
- ::= { atsOutputEntry 3 }
- atsOutputFrequency OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The output frequency in Hertz, or -1 if it's
- unsupported by this ATS."
- ::= { atsOutputEntry 4 }
- -- Output Phase Table
- atsOutputPhaseTable OBJECT-TYPE
- SYNTAX SEQUENCE OF AtsOutputPhaseEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "A list of output table entries. The number of
- entries is given by the sum of the atsNumOutputPhases."
- ::= { atsStatusOutput 3 }
- atsOutputPhaseEntry OBJECT-TYPE
- SYNTAX AtsOutputPhaseEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "An entry containing information applicable to a
- particular output phase."
- INDEX { atsOutputPhaseTableIndex, atsOutputPhaseIndex }
- ::= { atsOutputPhaseTable 1 }
- AtsOutputPhaseEntry ::= SEQUENCE {
- atsOutputPhaseTableIndex INTEGER,
- atsOutputPhaseIndex INTEGER,
- atsOutputVoltage INTEGER,
- atsOutputCurrent INTEGER,
- atsOutputMaxCurrent INTEGER,
- atsOutputMinCurrent INTEGER,
- atsOutputLoad INTEGER,
- atsOutputMaxLoad INTEGER,
- atsOutputMinLoad INTEGER,
- atsOutputPercentLoad INTEGER,
- atsOutputMaxPercentLoad INTEGER,
- atsOutputMinPercentLoad INTEGER,
- atsOutputPower INTEGER,
- atsOutputMaxPower INTEGER,
- atsOutputMinPower INTEGER,
- atsOutputPercentPower INTEGER,
- atsOutputMaxPercentPower INTEGER,
- atsOutputMinPercentPower INTEGER,
- atsOutputPhaseState INTEGER
- }
- atsOutputPhaseTableIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The output identifier."
- ::= { atsOutputPhaseEntry 1 }
- atsOutputPhaseIndex OBJECT-TYPE
- SYNTAX INTEGER{
- phase1(1),
- phase2(2),
- phase3(3),
- neutral(4)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Description of each output phase utilized in
- this device and one for neutral. "
- ::= { atsOutputPhaseEntry 2 }
- atsOutputVoltage OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The output voltage in VAC, or -1 if it's unsupported
- by this ATS."
- ::= { atsOutputPhaseEntry 3 }
- atsOutputCurrent OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The output current in 0.1 amperes drawn
- by the load on the ATS, or -1 if it's unsupported
- by this ATS."
- ::= { atsOutputPhaseEntry 4 }
- atsOutputMaxCurrent OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The maximum output current in 0.1 amperes measured
- since the last time this variable was read
- or reset (atsStatusResetMaxMinValues).
- Returns (-1) if unsupported."
- ::= { atsOutputPhaseEntry 5 }
- atsOutputMinCurrent OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The minimum output current in 0.1 amperes measured
- since the last time this variable was read
- or reset (atsStatusResetMaxMinValues).
- Returns (-1) if unsupported."
- ::= { atsOutputPhaseEntry 6 }
- atsOutputLoad OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The output load in VA, or -1 if it's unsupported
- by this ATS."
- ::= { atsOutputPhaseEntry 7 }
- atsOutputMaxLoad OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The maximum output load in VA measured
- since the last time this variable was read
- or reset (atsStatusResetMaxMinValues).
- Returns (-1) if unsupported."
- ::= { atsOutputPhaseEntry 8 }
- atsOutputMinLoad OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The minimum output load in VA measured
- since the last time this variable was read
- or reset (atsStatusResetMaxMinValues).
- Returns (-1) if unsupported."
- ::= { atsOutputPhaseEntry 9 }
- atsOutputPercentLoad OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The percentage of the ATS load capacity in VA at
- redundancy @ (n + x) presently being used on this
- output phase, or -1 if it's unsupported by this ATS."
- ::= { atsOutputPhaseEntry 10 }
- atsOutputMaxPercentLoad OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The maximum percentage of the ATS load capacity in
- VA measured at redundancy @ (n + x) presently
- being used on this output phase since the last time
- this variable was read or reset (atsStatusResetMaxMinValues).
- Returns (-1) if unsupported."
- ::= { atsOutputPhaseEntry 11 }
- atsOutputMinPercentLoad OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The minimum percentage of the ATS load capacity in
- VA measured at redundancy @ (n + x) presently
- being used on this output phase since the last time
- this variable was read or reset (atsStatusResetMaxMinValues).
- Returns (-1) if unsupported."
- ::= { atsOutputPhaseEntry 12 }
- atsOutputPower OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The output power in Watts, or -1 if it's
- unsupported by this ATS."
- ::= { atsOutputPhaseEntry 13 }
- atsOutputMaxPower OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The maximum output power in Watts measured
- since the last time this variable was read
- or reset (atsStatusResetMaxMinValues).
- Returns (-1) if unsupported."
- ::= { atsOutputPhaseEntry 14 }
- atsOutputMinPower OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The minimum output power in Watts measured
- since the last time this variable was read
- or reset (atsStatusResetMaxMinValues).
- Returns (-1) if unsupported."
- ::= { atsOutputPhaseEntry 15 }
- atsOutputPercentPower OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The percentage of the ATSpower capacity in Watts at
- redundancy @ (n + x) presently being used on this
- output phase, or -1 if it's unsupported by this ATS."
- ::= { atsOutputPhaseEntry 16 }
- atsOutputMaxPercentPower OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The maximum percentage of the ATSpower capacity
- in Watts measured at redundancy @ (n + x) presently
- being used on this output phase since the last time
- this variable was read or reset (atsStatusResetMaxMinValues).
- Returns (-1) if unsupported."
- ::= { atsOutputPhaseEntry 17 }
- atsOutputMinPercentPower OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The minimum percentage of the ATSpower capacity
- in Watts measured at redundancy @ (n + x) presently
- being used on this output phase since the last time
- this variable was read or reset (atsStatusResetMaxMinValues).
- Returns (-1) if unsupported."
- ::= { atsOutputPhaseEntry 18 }
- atsOutputPhaseState OBJECT-TYPE
- SYNTAX INTEGER {
- normal (1),
- lowload (2),
- nearoverload (3),
- overload (4)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return the phase load state.
-
- normal(1) indicates that the bank is operating properly
- within the atsConfigPhaseLowLoadThreshold and
- atsConfigPhaseNearOverLoadThreshold OID values.
-
- lowload(2) indicates that the bank load has dropped below
- the atsConfigPhaseLowLoadThreshold OID value. An SNMP trap
- will occur when this state is entered or cleared.
-
- nearoverload(3) indicates that the bank load is greater than
- or equal to the atsConfigPhaseNearOverLoadThreshold OID value.
- An SNMP trap will occur when this state is entered or cleared.
-
- overload(4) indicates that the bank load is greater than or
- equal to the atsConfigPhaseOverLoadThreshold OID value.
- An SNMP trap will occur when this state is entered or cleared."
- ::= { atsOutputPhaseEntry 19 }
-
-
- atsOutputBankTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The size of the bank table."
- ::= { atsStatusOutput 4 }
-
-
- atsOutputBankTable OBJECT-TYPE
- SYNTAX SEQUENCE OF ATSOutputBankEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting table entries."
- ::= { atsStatusOutput 5 }
- atsOutputBankEntry OBJECT-TYPE
- SYNTAX ATSOutputBankEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "This gives access to bank table entries"
- INDEX { atsOutputBankTableIndex }
- ::= { atsOutputBankTable 1 }
- ATSOutputBankEntry ::=
- SEQUENCE {
- atsOutputBankTableIndex INTEGER,
- atsOutputPhase INTEGER,
- atsOutputBank INTEGER,
- atsOutputBankCurrent Gauge,
- atsOutputBankState INTEGER,
- atsOutputBankOutputVoltage INTEGER,
- atsOutputBankMaxCurrent INTEGER,
- atsOutputBankMinCurrent INTEGER,
- atsOutputBankLoad INTEGER,
- atsOutputBankMaxLoad INTEGER,
- atsOutputBankMinLoad INTEGER,
- atsOutputBankPercentLoad INTEGER,
- atsOutputBankMaxPercentLoad INTEGER,
- atsOutputBankMinPercentLoad INTEGER,
- atsOutputBankPower INTEGER,
- atsOutputBankMaxPower INTEGER,
- atsOutputBankMinPower INTEGER,
- atsOutputBankPercentPower INTEGER,
- atsOutputBankMaxPercentPower INTEGER,
- atsOutputBankMinPercentPower INTEGER
- }
- atsOutputBankTableIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the bank table entry."
- ::= { atsOutputBankEntry 1 }
- atsOutputPhase OBJECT-TYPE
- SYNTAX INTEGER {
- phase1 (1),
- phase2 (2),
- phase3 (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The phase number of an ATS"
- ::= { atsOutputBankEntry 2 }
- atsOutputBank OBJECT-TYPE
- SYNTAX INTEGER {
- total (1),
- bank1 (2),
- bank2 (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The bank number of an ATS"
- ::= { atsOutputBankEntry 3 }
-
- atsOutputBankCurrent OBJECT-TYPE
- SYNTAX Gauge
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return the bank current measured
- in tenths of Amps."
- ::= { atsOutputBankEntry 4 }
-
- atsOutputBankState OBJECT-TYPE
- SYNTAX INTEGER {
- normal (1),
- lowload (2),
- nearoverload (3),
- overload (4)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return the bank load state.
-
- normal(1) indicates that the bank is
- operating properly within the atsConfigBankLowLoadThreshold
- and atsConfigBankNearOverLoadThreshold OID values.
-
- lowload(2) indicates that the bank load has dropped below the
- atsConfigBankLowLoadThreshold OID value. An SNMP trap will
- occur when this state is entered or cleared.
-
- nearoverload(3) indicates that the bank load is greater than
- or equal to the atsConfigBankNearOverLoadThreshold OID value.
- An SNMP trap will occur when this state is entered or cleared.
-
- overload(4) indicates that the bank load is greater than or
- equal to the atsConfigBankOverLoadThreshold OID value.
- An SNMP trap will occur when this state is entered or cleared."
- ::= { atsOutputBankEntry 5 }
- atsOutputBankOutputVoltage OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The output voltage in VAC, or -1 if it's unsupported
- by this ATS."
- ::= { atsOutputBankEntry 6 }
- atsOutputBankMaxCurrent OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The maximum output current, on the bank represented by
- OID atsOutputBank, in 0.1 amperes measured since the
- last time this variable was read
- or reset (atsStatusResetMaxMinValues).
- Returns (-1) if unsupported."
- ::= { atsOutputBankEntry 7 }
- atsOutputBankMinCurrent OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The minimum output current, on the bank represented by
- OID atsOutputBank, in 0.1 amperes measured since the
- last time this variable was read
- or reset (atsStatusResetMaxMinValues).
- Returns (-1) if unsupported."
- ::= { atsOutputBankEntry 8 }
- atsOutputBankLoad OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The output load, on the bank represented by
- OID atsOutputBank, in VA, or -1 if it's
- unsupported by this ATS."
- ::= { atsOutputBankEntry 9 }
- atsOutputBankMaxLoad OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The maximum output load, on the bank represented by
- OID atsOutputBank, in VA measured since the last
- time this variable was read
- or reset (atsStatusResetMaxMinValues).
- Returns (-1) if unsupported."
- ::= { atsOutputBankEntry 10 }
- atsOutputBankMinLoad OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The minimum output load, on the bank represented by
- OID atsOutputBank, in VA measured since the last
- time this variable was read
- or reset (atsStatusResetMaxMinValues).
- Returns (-1) if unsupported."
- ::= { atsOutputBankEntry 11 }
- atsOutputBankPercentLoad OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The percentage of the ATS load capacity in VA at
- redundancy @ (n + x) presently being used on this
- bank, represented by OID atsOutputBank.
- Returns (-1) if unsupported."
- ::= { atsOutputBankEntry 12 }
- atsOutputBankMaxPercentLoad OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The maximum percentage of the ATS load capacity in
- VA measured at redundancy @ (n + x) presently
- being used on this bank, represented by OID atsOutputBank,
- since the last time this variable was read or
- reset (atsStatusResetMaxMinValues).
- Returns (-1) if unsupported."
- ::= { atsOutputBankEntry 13 }
- atsOutputBankMinPercentLoad OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The minimum percentage of the ATS load capacity in
- VA measured at redundancy @ (n + x) presently
- being used on this bank, represented by OID
- atsOutputBank, since the last time this variable was
- read or reset (atsStatusResetMaxMinValues).
- Returns (-1) if unsupported."
- ::= { atsOutputBankEntry 14 }
- atsOutputBankPower OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The output power in Watts on the bank represented by
- OID atsOutputBank or -1 if it's unsupported by this ATS."
- ::= { atsOutputBankEntry 15 }
- atsOutputBankMaxPower OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The maximum output power in Watts measured on the bank
- represented by OID atsOutputBank since the last
- time this variable was read
- or reset (atsStatusResetMaxMinValues).
- Returns (-1) if unsupported."
- ::= { atsOutputBankEntry 16 }
- atsOutputBankMinPower OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The minimum output power in Watts measured on the bank
- represented by OID atsOutputBank since the last time
- this variable was read
- or reset (atsStatusResetMaxMinValues).
- Returns (-1) if unsupported."
- ::= { atsOutputBankEntry 17 }
- atsOutputBankPercentPower OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The percentage of the ATSpower capacity in Watts at
- redundancy @ (n + x) presently being used on this
- bank, represented by OID atsOutputBank, or
- -1 if it's unsupported by this ATS."
- ::= { atsOutputBankEntry 18 }
- atsOutputBankMaxPercentPower OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The maximum percentage of the ATSpower capacity
- in Watts measured at redundancy @ (n + x) presently
- being used on this bank, represented by OID
- atsOutputBank, since the last time this variable
- was read or reset (atsStatusResetMaxMinValues).
- Returns (-1) if unsupported."
- ::= { atsOutputBankEntry 19 }
- atsOutputBankMinPercentPower OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The minimum percentage of the ATSpower capacity
- in Watts measured at redundancy @ (n + x) presently
- being used on this bank, represented by OID atsOutputBank
- since the last time this variable was read or
- reset (atsStatusResetMaxMinValues).
- Returns (-1) if unsupported."
- ::= { atsOutputBankEntry 20 }
- -- the dcmim2IdentSystem group
-
- dcmim2IdentSysFWVersion OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Integer representation of the power plant Master Controller firmware revision."
- ::= { dcmim2IdentSystem 1 }
- -- the dcmim2ControlSystem group
- dcmim2ControlRunFunctBatteryTest OBJECT-TYPE
- SYNTAX INTEGER {
- battTestOff (1),
- battTestOn (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return the battery functional test state. If
- the test is off, the battTestOff (1) value will be returned.
- If the test is on, the battTestOn (2) value will be
- returned.
-
- Setting this OID to battTestOff (1) will turn the battery functional test off.
- Setting this OID to battTestOn (2) will turn the battery functional test on."
- ::= { dcmim2ControlSystem 1 }
- dcmim2ControlRunCapacityBatteryTest OBJECT-TYPE
- SYNTAX INTEGER {
- battTestOff (1),
- battTestOn (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return the battery capacity test state. If
- the test is off, the battTestOff (1) value will be returned.
- If the test is on, the battTestOn (2) value will be
- returned.
-
- Setting this OID to battTestOff (1) will turn the battery capacity test off.
- Setting this OID to battTestOn (2) will turn the battery capacity test on."
- ::= { dcmim2ControlSystem 2 }
- -- the dcmim2ConfigSystem group
- dcmim2ConfigSysHighTempTrip OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Trip level (threshold) at which System High Temp alarm condition is created.
- Range 28 to 100 (degC).
- Values are represented in thousandths of a degree.
- Units are displayed in the scale shown in
- the 'dcmim2StatusSysTempUnits' OID (Celsius or Fahrenheit)."
-
-
- ::= { dcmim2ConfigSystem 1 }
- dcmim2ConfigSysHighTempReset OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Level at which System High Temp alarm condition is reset (cleared).
- Range 25 to (upper temp - 3) (degC).
-
- Values are represented in thousandths of a degree.
- Units are displayed in the scale shown in
- the 'dcmim2StatusSysTempUnits' OID (Celsius or Fahrenheit)."
-
- ::= { dcmim2ConfigSystem 2 }
-
- dcmim2ConfigSysLowTempTrip OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Trip level (threshold) at which System Low Temp alarm condition is created.
- Range -100 to 10 (degC).
- Values are represented in thousandths of a degree.
- Units are displayed in the scale shown in
- the 'dcmim2StatusSysTempUnits' OID (Celsius or Fahrenheit)."
-
- ::= { dcmim2ConfigSystem 3 }
- dcmim2ConfigSysLowTempReset OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Level at which System Low Temp alarm condition is reset (cleared).
- Range (lower temp + 3) to 13 (degC).
- Values are represented in thousandths of a degree.
- Units are displayed in the scale shown in
- the 'dcmim2StatusSysTempUnits' OID (Celsius or Fahrenheit)."
-
- ::= { dcmim2ConfigSystem 4 }
- -- the dcmim2ConfigBattery group
- dcmim2ConfigBattFloatVolt OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Battery Float Voltage defined at 25 degrees Celsius.
-
- Values are represented in thousandths of Volts (mV)."
-
- ::= { dcmim2ConfigBattery 1 }
- dcmim2ConfigBattMaxRecharge OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Battery Maximum Recharge Rate. This is the maximum current used
- during battery charging.
-
- Values are represented in thousandths of Amps (mA)."
-
- ::= { dcmim2ConfigBattery 2 }
- dcmim2ConfigBattMfgCapacity OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Battery capacity (Amp-Hour Size) as specified by the battery manufacturer.
-
- Values are represented in thousandths of Amp hours (mAHr)."
-
- ::= { dcmim2ConfigBattery 3 }
-
- dcmim2ConfigBattType OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Type of battery in the powerplant
-
- Valid values range from 0 to 254."
-
- ::= { dcmim2ConfigBattery 4 }
-
- dcmim2ConfigBattFunctTestDuration OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Duration of the battery functional test.
-
- Values are represented in thousandths of seconds (mSecs)."
-
- ::= { dcmim2ConfigBattery 5 }
-
- dcmim2ConfigBattFunctTestThresh OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Threshold the battery voltage of the system must remain above
- in order to pass the battery functional test.
-
- Values are represented in thousandths of Volts (mV)."
-
- ::= { dcmim2ConfigBattery 6 }
-
- dcmim2ConfigBattCapacityTestPercent OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Threshold for good battery capacity test results.
-
- Values range from 0 to 100 percent."
-
- ::= { dcmim2ConfigBattery 7 }
-
- dcmim2ConfigBattCapacityTestEndThresh OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Safeguard voltage at which battery capacity test will end
- if there is a battery problem.
-
- Values are represented in thousandths of Volts (mV)."
-
- ::= { dcmim2ConfigBattery 8 }
-
- dcmim2ConfigBattCapacityTestCurrent OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Constant current value used during battery capacity testing.
-
- Values are represented in thousandths of Amps (mA)."
-
- ::= { dcmim2ConfigBattery 9 }
- -- the dcmim2ConfigLVD group
- dcmim2ConfigLVDTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of DC powerplant LVDs controllable
- by this IP address."
- ::= { dcmim2ConfigLVD 1 }
- dcmim2ConfigLVDTable OBJECT-TYPE
- SYNTAX SEQUENCE OF Dcmim2ConfigLVDEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for accessing settings of the LVDs. The number of
- entries is contained in the dcmim2ConfigLVDTableSize OID."
- ::= { dcmim2ConfigLVD 2 }
- dcmim2ConfigLVDEntry OBJECT-TYPE
- SYNTAX Dcmim2ConfigLVDEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The LVD to configure."
- INDEX { dcmim2ConfigLVDIndex }
- ::= { dcmim2ConfigLVDTable 1 }
-
- Dcmim2ConfigLVDEntry ::=
- SEQUENCE {
- dcmim2ConfigLVDIndex INTEGER,
- dcmim2ConfigLVDTrip INTEGER,
- dcmim2ConfigLVDReset INTEGER,
- dcmim2ConfigLVDState INTEGER
- }
-
- dcmim2ConfigLVDIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the DC powerplant LVD."
- ::= { dcmim2ConfigLVDEntry 1 }
- dcmim2ConfigLVDTrip OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "LVD Trip threshold. System bus voltage at which LVD will trip (open)
- during a battery backup operation.
-
- Values are represented in thousandths of Volts (mV)."
- ::= { dcmim2ConfigLVDEntry 2 }
- dcmim2ConfigLVDReset OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "LVD Reset threshold. System bus voltage at which LVD will reset (close)
- after AC power has been restored.
-
- Values are represented in thousandths of Volts (mV)."
- ::= { dcmim2ConfigLVDEntry 3 }
-
- dcmim2ConfigLVDState OBJECT-TYPE
- SYNTAX INTEGER {
- statusClosed (1),
- statusOpened (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return statusClosed (1) if the LVD is closed.
- statusOpened (2) will be returned if the LVD is opened."
- ::= { dcmim2ConfigLVDEntry 4 }
- -- the dcmim2StatusSystem group
- dcmim2StatusSysRectCurrent OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "System (Total Rectifier) current in thousandths of Amps (mA)."
- ::= { dcmim2StatusSystem 1 }
- dcmim2StatusSysLoadCurrent OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Load current in thousandths of Amps (mA)."
- ::= { dcmim2StatusSystem 2 }
- dcmim2StatusSysBusVoltage OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "System bus voltage in thousandths of Volts (mV)."
- ::= { dcmim2StatusSystem 3 }
- dcmim2StatusSysAmbientTemp OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "System temperature based on sensor on Master Controller PCB.
-
- Values are represented in thousandths of a degree.
- Units are displayed in the scale shown in
- the 'dcmim2StatusSysTempUnits' OID (Celsius or Fahrenheit)."
- ::= { dcmim2StatusSystem 4 }
- dcmim2StatusSysUpTime OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Length of time since the DC Powerplant controller has been powered up."
- ::= { dcmim2StatusSystem 5 }
- dcmim2StatusSysTempUnits OBJECT-TYPE
- SYNTAX INTEGER {
- celsius(1),
- fahrenheit(2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The temperature scale used to display the temperature
- in the DC system, Celsius(1) or Fahrenheit(2).
- This setting is based on the system preferences
- configuration in the agent."
- ::= { dcmim2StatusSystem 6 }
- -- the dcmim2StatusRectifier group
- dcmim2StatusRectTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of DC powerplant rectifiers viewable
- by this IP address."
- ::= { dcmim2StatusRectifier 1 }
- dcmim2StatusRectTable OBJECT-TYPE
- SYNTAX SEQUENCE OF Dcmim2StatusRectEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for accessing settings of the rectifiers. The number of
- entries is contained in the dcmim2StatusRectTableSize OID."
- ::= { dcmim2StatusRectifier 2 }
- dcmim2StatusRectEntry OBJECT-TYPE
- SYNTAX Dcmim2StatusRectEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The rectifier to gather status from."
- INDEX { dcmim2StatusRectIndex }
- ::= { dcmim2StatusRectTable 1 }
-
- Dcmim2StatusRectEntry ::=
- SEQUENCE {
- dcmim2StatusRectIndex INTEGER,
- dcmim2StatusRectDevType INTEGER,
- dcmim2StatusRectID INTEGER,
- dcmim2StatusRectPhyAddr INTEGER,
- dcmim2StatusRectFail INTEGER,
- dcmim2StatusRectCurrent INTEGER
- }
- dcmim2StatusRectIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the DC powerplant rectifier."
- ::= { dcmim2StatusRectEntry 1 }
- dcmim2StatusRectDevType OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID shows the rectifier device type."
- ::= { dcmim2StatusRectEntry 2 }
- dcmim2StatusRectID OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID shows the rectifier ID. This enumerates the number of the rectifier within
- a group of rectifiers."
- ::= { dcmim2StatusRectEntry 3 }
- dcmim2StatusRectPhyAddr OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID shows the rectifier physical address (the address on the bus)."
- ::= { dcmim2StatusRectEntry 4 }
- dcmim2StatusRectFail OBJECT-TYPE
- SYNTAX INTEGER {
- statusTrue (1),
- statusFalse (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return statusTrue (1) if the rectifier has failed.
- statusFalse (2) will be returned if the rectifier has not failed."
- ::= { dcmim2StatusRectEntry 5 }
- dcmim2StatusRectCurrent OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID shows the individual rectifier current in thousandths of Amps (mA)."
- ::= { dcmim2StatusRectEntry 6 }
- -- the dcmim2StatusBattery group
- dcmim2StatusBattFloatVolt OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Battery Float Voltage represented in thousandths of Volts (mV)."
- ::= { dcmim2StatusBattery 1 }
- dcmim2StatusBattCurrent OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Battery Current: This OID shows the battery current in thousandths of Amps (mA)."
- ::= { dcmim2StatusBattery 2 }
- dcmim2StatusBattTemp OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Battery Temperature:
-
- Values are represented in thousandths of a degree.
- Units are displayed in the scale shown in
- the 'dcmim2StatusSysTempUnits' OID (Celsius or Fahrenheit)."
- ::= { dcmim2StatusBattery 3 }
- dcmim2StatusBattMfgCapacity OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Battery capacity (Amp-Hour Size) as specified by the battery manufacturer.
- Values are represented in thousandths of Amp hours (mAHr)."
- ::= { dcmim2StatusBattery 4 }
- dcmim2StatusBattTestCapacity OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Battery capacity (Amp-Hour Size) as determined by the battery capacity test.
- Values are represented in thousandths of Amp hours (mAHr)."
- ::= { dcmim2StatusBattery 5 }
- dcmim2StatusBattFunctTestResult OBJECT-TYPE
- SYNTAX INTEGER{
- functTestNotPerformed (1),
- functTestInProcess (2),
- functTestInterrupted (3),
- functTestPass (4),
- functTestFail (5)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Results of the last battery functional test that was run."
- ::= { dcmim2StatusBattery 6 }
- dcmim2StatusBattCapacityTestResult OBJECT-TYPE
- SYNTAX INTEGER{
- capacityTestNotPerformed (1),
- capacityTestInProcess (2),
- capacityTestInterrupted (3),
- capacityTestPass (4),
- capacityTestFail (5)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Results of the last battery capacity test that was run."
- ::= { dcmim2StatusBattery 7 }
- -- the dcmim2StatusLVD group
- dcmim2StatusLVDTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of DC powerplant LVDs accessible
- by this IP address."
- ::= { dcmim2StatusLVD 1 }
- dcmim2StatusLVDTable OBJECT-TYPE
- SYNTAX SEQUENCE OF Dcmim2StatusLVDEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for accessing the LVDs. The number of
- entries is contained in the dcmim2StatusLVDTableSize OID."
- ::= { dcmim2StatusLVD 2 }
- dcmim2StatusLVDEntry OBJECT-TYPE
- SYNTAX Dcmim2StatusLVDEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The LVD to access."
- INDEX { dcmim2StatusLVDIndex }
- ::= { dcmim2StatusLVDTable 1 }
-
- Dcmim2StatusLVDEntry ::=
- SEQUENCE {
- dcmim2StatusLVDIndex INTEGER,
- dcmim2StatusLVDState INTEGER
- }
-
- dcmim2StatusLVDIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the DC powerplant LVD."
- ::= { dcmim2StatusLVDEntry 1 }
-
- dcmim2StatusLVDState OBJECT-TYPE
- SYNTAX INTEGER {
- statusClosed (1),
- statusOpened (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this OID will return statusClosed (1) if the LVD is closed.
- statusOpened (2) will be returned if the LVD is opened."
- ::= { dcmim2StatusLVDEntry 2 }
- -- the dcmim2StatusAlarms group
- dcmim2StatusAlarmsTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of DC powerplant alarms viewable
- by this IP address."
- ::= { dcmim2StatusAlarms 1 }
- dcmim2StatusAlarmsTable OBJECT-TYPE
- SYNTAX SEQUENCE OF Dcmim2StatusAlarmsEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for accessing system alarms. The number of
- entries is contained in the dcmim2StatusAlarmsTableSize OID."
- ::= { dcmim2StatusAlarms 2 }
- dcmim2StatusAlarmsEntry OBJECT-TYPE
- SYNTAX Dcmim2StatusAlarmsEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The alarm to display."
- INDEX { dcmim2StatusAlarmsIndex }
- ::= { dcmim2StatusAlarmsTable 1 }
-
- Dcmim2StatusAlarmsEntry ::=
- SEQUENCE {
- dcmim2StatusAlarmsIndex INTEGER,
- dcmim2StatusAlarmsText DisplayString
- }
- dcmim2StatusAlarmsIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index of the system alarm."
- ::= { dcmim2StatusAlarmsEntry 1 }
-
- dcmim2StatusAlarmsText OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The 16 character text describing the active alarm condition."
- ::= { dcmim2StatusAlarmsEntry 2 }
- -- External Environmental Monitor
- emIdentFirmwareRevision OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The firmware revision of the Environmental Monitor."
- ::= { emIdent 1 }
- emConfigProbesNumProbes OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of temperature and humidity probes available."
- ::= { emConfig 1 }
- emConfigProbesTable OBJECT-TYPE
- SYNTAX SEQUENCE OF EmConfigProbesEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "A list of probes supported by the Environmental Monitor
- and their configurations."
- ::= { emConfig 2 }
- emConfigProbesEntry OBJECT-TYPE
- SYNTAX EmConfigProbesEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The Environmental Monitor probe configurations."
- INDEX { emConfigProbeNumber }
- ::= { emConfigProbesTable 1 }
- EmConfigProbesEntry ::=
- SEQUENCE {
- emConfigProbeNumber
- INTEGER,
- emConfigProbeName
- DisplayString,
- emConfigProbeHighTempThreshold
- INTEGER,
- emConfigProbeLowTempThreshold
- INTEGER,
- emConfigProbeTempUnits
- INTEGER,
- emConfigProbeHighHumidThreshold
- INTEGER,
- emConfigProbeLowHumidThreshold
- INTEGER,
- emConfigProbeHighTempEnable
- INTEGER,
- emConfigProbeLowTempEnable
- INTEGER,
- emConfigProbeHighHumidEnable
- INTEGER,
- emConfigProbeLowHumidEnable
- INTEGER,
- emConfigProbeMaxTempThreshold
- INTEGER,
- emConfigProbeMinTempThreshold
- INTEGER,
- emConfigProbeMaxHumidThreshold
- INTEGER,
- emConfigProbeMinHumidThreshold
- INTEGER,
- emConfigProbeMaxTempEnable
- INTEGER,
- emConfigProbeMinTempEnable
- INTEGER,
- emConfigProbeMaxHumidEnable
- INTEGER,
- emConfigProbeMinHumidEnable
- INTEGER,
- emConfigProbeTempHysteresis
- INTEGER,
- emConfigProbeHumidHysteresis
- INTEGER,
- emConfigProbeLocation
- DisplayString
- }
- emConfigProbeNumber OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index into an Environmental Monitor probe entry."
- ::= { emConfigProbesEntry 1 }
- emConfigProbeName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "A descriptive name of the probe set by the user,
- possibly denoting its location or purpose."
- ::= { emConfigProbesEntry 2 }
- emConfigProbeHighTempThreshold OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The high temperature alarm threshold for the probe.
- Units are displayed in the scale selected in
- the 'emConfigProbeTempUnits' OID (Celsius or Fahrenheit)."
- ::= { emConfigProbesEntry 3 }
- emConfigProbeLowTempThreshold OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The low temperature alarm threshold for the probe.
- Units are displayed in the scale selected in
- the 'emConfigProbeTempUnits' OID (Celsius or Fahrenheit)."
- ::= { emConfigProbesEntry 4 }
- emConfigProbeTempUnits OBJECT-TYPE
- SYNTAX INTEGER {
- celsius(1),
- fahrenheit(2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The temperature scale used to display the temperature
- thresholds of the probe, Celsius(1) or Fahrenheit(2).
- This setting is based on the system preferences
- configuration in the agent."
- ::= { emConfigProbesEntry 5 }
- emConfigProbeHighHumidThreshold OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The high humidity alarm threshold for the probe in
- percent relative humidity."
- ::= { emConfigProbesEntry 6 }
- emConfigProbeLowHumidThreshold OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The low humidity alarm threshold for the probe in
- percent relative humidity."
- ::= { emConfigProbesEntry 7 }
- emConfigProbeHighTempEnable OBJECT-TYPE
- SYNTAX INTEGER {
- disabled(1),
- enabled(2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The high temperature alarm enable/disable for the
- probe. No alarm will be generated if this value
- is set to disabled(1). The alarm will be
- generated if this value is set to enabled(2) and
- the threshold has been violated."
- ::= { emConfigProbesEntry 8 }
- emConfigProbeLowTempEnable OBJECT-TYPE
- SYNTAX INTEGER {
- disabled(1),
- enabled(2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The low temperature alarm enable/disable for the
- probe. No alarm will be generated if this value
- is set to disabled(1). The alarm will be
- generated if this value is set to enabled(2) and
- the threshold has been violated."
- ::= { emConfigProbesEntry 9 }
- emConfigProbeHighHumidEnable OBJECT-TYPE
- SYNTAX INTEGER {
- disabled(1),
- enabled(2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The high humidity alarm enable/disable for the
- probe. No alarm will be generated if this value
- is set to disabled(1). The alarm will be
- generated if this value is set to enabled(2) and
- the threshold has been violated."
- ::= { emConfigProbesEntry 10 }
- emConfigProbeLowHumidEnable OBJECT-TYPE
- SYNTAX INTEGER {
- disabled(1),
- enabled(2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The low humidity alarm enable/disable for the
- probe. No alarm will be generated if this value
- is set to disabled(1). The alarm will be
- generated if this value is set to enabled(2) and
- the threshold has been violated."
- ::= { emConfigProbesEntry 11 }
- emConfigProbeMaxTempThreshold OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The maximum temperature alarm threshold for the probe.
- Units are displayed in the scale selected in
- the 'emConfigProbeTempUnits' OID (Celsius or Fahrenheit)."
- ::= { emConfigProbesEntry 12 }
- emConfigProbeMinTempThreshold OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The minimum temperature alarm threshold for the probe.
- Units are displayed in the scale selected in
- the 'emConfigProbeTempUnits' OID (Celsius or Fahrenheit)."
- ::= { emConfigProbesEntry 13 }
- emConfigProbeMaxHumidThreshold OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The maximun humidity alarm threshold for the probe in
- percent relative humidity."
- ::= { emConfigProbesEntry 14 }
- emConfigProbeMinHumidThreshold OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The minimum humidity alarm threshold for the probe in
- percent relative humidity."
- ::= { emConfigProbesEntry 15 }
- emConfigProbeMaxTempEnable OBJECT-TYPE
- SYNTAX INTEGER {
- disabled(1),
- enabled(2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The maximum temperature alarm enable/disable for the
- probe. No alarm will be generated if this value
- is set to disabled(1). The alarm will be
- generated if this value is set to enabled(2) and
- the threshold has been violated."
- ::= { emConfigProbesEntry 16 }
- emConfigProbeMinTempEnable OBJECT-TYPE
- SYNTAX INTEGER {
- disabled(1),
- enabled(2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The minimum temperature alarm enable/disable for the
- probe. No alarm will be generated if this value
- is set to disabled(1). The alarm will be
- generated if this value is set to enabled(2) and
- the threshold has been violated."
- ::= { emConfigProbesEntry 17 }
- emConfigProbeMaxHumidEnable OBJECT-TYPE
- SYNTAX INTEGER {
- disabled(1),
- enabled(2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The maximum humidity alarm enable/disable for the
- probe. No alarm will be generated if this value
- is set to disabled(1). The alarm will be
- generated if this value is set to enabled(2) and
- the threshold has been violated."
- ::= { emConfigProbesEntry 18 }
- emConfigProbeMinHumidEnable OBJECT-TYPE
- SYNTAX INTEGER {
- disabled(1),
- enabled(2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The minimum humidity alarm enable/disable for the
- probe. No alarm will be generated if this value
- is set to disabled(1). The alarm will be
- generated if this value is set to enabled(2) and
- the threshold has been violated."
- ::= { emConfigProbesEntry 19 }
- emConfigProbeTempHysteresis OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The number of degrees beyond the temperature thresholds
- at which an active temperature alarm will be cleared.
- This configuration setting applies to all temperature
- thresholds.
- Units are displayed in the scale selected in
- the 'emConfigProbeTempUnits' OID (Celsius or Fahrenheit)."
- ::= { emConfigProbesEntry 20 }
- emConfigProbeHumidHysteresis OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The number of percent RH points beyond the humidity
- thresholds at which an active humidity alarm will be
- cleared. This configuration setting applies to all
- humidity thresholds.
- Units are displayed in the scale selected in
- the 'emConfigProbeTempUnits' OID (Celsius or Fahrenheit)."
- ::= { emConfigProbesEntry 21 }
- emConfigProbeLocation OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "A string describing the location of the probe."
- ::= { emConfigProbesEntry 22 }
- emConfigContactsNumContacts OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of contacts supported by the Environmental
- Monitor."
- ::= { emConfig 3 }
- emConfigContactsTable OBJECT-TYPE
- SYNTAX SEQUENCE OF EmConfigContactsEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "A list of contacts supported by the Environmental Monitor
- and their configurations."
- ::= { emConfig 4 }
- emConfigContactsEntry OBJECT-TYPE
- SYNTAX EmConfigContactsEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The Environmental Monitor contact configurations."
- INDEX { emConfigContactNumber }
- ::= { emConfigContactsTable 1 }
- EmConfigContactsEntry ::=
- SEQUENCE {
- emConfigContactNumber
- INTEGER,
- emConfigContactName
- DisplayString,
- emConfigContactEnable
- INTEGER,
- emConfigContactSeverity
- INTEGER,
- emConfigContactNormalState
- INTEGER,
- emConfigContactLocation
- DisplayString
- }
- emConfigContactNumber OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index of an Environmental Monitor contact."
- ::= { emConfigContactsEntry 1 }
- emConfigContactName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "A descriptive name for an Environmental Monitor
- contact set by the user, possibly denoting its
- location or purpose."
- ::= { emConfigContactsEntry 2 }
- emConfigContactEnable OBJECT-TYPE
- SYNTAX INTEGER {
- disabled(1),
- enabled(2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "An Environmental Monitor contact alarm enable/disable.
- No alarm will be generated if the contact is disabled(1).
- An alarm will be generated if the contact is enabled(2)
- and the contact has been faulted."
- ::= { emConfigContactsEntry 3 }
- emConfigContactSeverity OBJECT-TYPE
- SYNTAX INTEGER {
- critical(1),
- warning(2),
- informational(3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The severity of the alarm that will be triggered when
- the input contact is activated. The alarms can be
- critical(1), warning(2) or informational(3)."
- ::= { emConfigContactsEntry 4 }
- emConfigContactNormalState OBJECT-TYPE
- SYNTAX INTEGER {
- open(1),
- closed(2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The contact state that will be considered normal, i.e.
- will not trigger an alarm. The states are open(1) or
- closed(2)."
- ::= { emConfigContactsEntry 5 }
- emConfigContactLocation OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "A descriptive label for the contact denoting its
- location or purpose."
- ::= { emConfigContactsEntry 6 }
- emStatusCommStatus OBJECT-TYPE
- SYNTAX INTEGER {
- noComm(1),
- comm(2),
- commLost(3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The communication status between the agent
- and the Environmental Monitor.
-
- noComm(1), Communication has never been established.
- comm(2), Communication has been established.
- commLost(3), Communication was established, but was lost."
- ::= { emStatus 1 }
- emStatusProbesNumProbes OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of available probes on the Environmental
- Monitor."
- ::= { emStatus 2 }
- emStatusProbesTable OBJECT-TYPE
- SYNTAX SEQUENCE OF EmStatusProbesEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "A list of probes supported by the Environmental Monitor
- and their status."
- ::= { emStatus 3 }
- emStatusProbesEntry OBJECT-TYPE
- SYNTAX EmStatusProbesEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The status of the probe."
- INDEX { emStatusProbeNumber }
- ::= { emStatusProbesTable 1 }
- EmStatusProbesEntry ::=
- SEQUENCE {
- emStatusProbeNumber
- INTEGER,
- emStatusProbeName
- DisplayString,
- emStatusProbeStatus
- INTEGER,
- emStatusProbeCurrentTemp
- INTEGER,
- emStatusProbeTempUnits
- INTEGER,
- emStatusProbeCurrentHumid
- INTEGER,
- emStatusProbeHighTempViolation
- INTEGER,
- emStatusProbeLowTempViolation
- INTEGER,
- emStatusProbeHighHumidViolation
- INTEGER,
- emStatusProbeLowHumidViolation
- INTEGER,
- emStatusProbeMaxTempViolation
- INTEGER,
- emStatusProbeMinTempViolation
- INTEGER,
- emStatusProbeMaxHumidViolation
- INTEGER,
- emStatusProbeMinHumidViolation
- INTEGER
- }
- emStatusProbeNumber OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index of the probe."
- ::= { emStatusProbesEntry 1 }
- emStatusProbeName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A descriptive name for the probe set by the user,
- possibly denoting its location or purpose."
- ::= { emStatusProbesEntry 2 }
- emStatusProbeStatus OBJECT-TYPE
- SYNTAX INTEGER {
- disconnected(1),
- connected(2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The connected status of the probe, either
- disconnected(1) or connected(2)."
- ::= { emStatusProbesEntry 3 }
- emStatusProbeCurrentTemp OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The current temperature reading from the probe displayed
- in the units shown in the 'emStatusProbeTempUnits' OID
- (Celsius or Fahrenheit)."
- ::= { emStatusProbesEntry 4 }
- emStatusProbeTempUnits OBJECT-TYPE
- SYNTAX INTEGER {
- celsius(1),
- fahrenheit(2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The temperature scale used to display the temperature
- thresholds of the probe, Celsius(1) or Fahrenheit(2).
- This setting is based on the system preferences
- configuration in the agent."
- ::= { emStatusProbesEntry 5 }
- emStatusProbeCurrentHumid OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The current humidity reading from the probe in
- percent relative humidity."
- ::= { emStatusProbesEntry 6 }
- emStatusProbeHighTempViolation OBJECT-TYPE
- SYNTAX INTEGER {
- noViolation(1),
- highTempViolation(2),
- disabled(3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The high temperature violation status of the probe
- temperature reading. This OID will show a highTempViolation(2)
- if the current temperature reading shown in the
- 'emStatusProbeCurrentTemp' OID is greater than or equal to
- the high temperature threshold value, the
- 'emConfigProbeHighTempThreshold' OID, and the value of the
- 'emConfigProbeHighTempEnable' OID is enabled. Otherwise it will show
- noViolation(1). If the 'emConfigProbeHighTempEnable' OID is disabled,
- this OID will show disabled(3)."
- ::= { emStatusProbesEntry 7 }
- emStatusProbeLowTempViolation OBJECT-TYPE
- SYNTAX INTEGER {
- noViolation(1),
- lowTempViolation(2),
- disabled(3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The high temperature violation status of the probe
- temperature reading. This OID will show a lowTempViolation(2)
- if the current temperature reading shown in the
- 'emStatusProbeCurrentTemp' OID is less than or equal to
- the low temperature threshold value, the
- 'emConfigProbeLowTempThreshold' OID, and the value of the
- 'emConfigProbeLowTempEnable' OID is enabled. Otherwise it will show
- noViolation(1). If the 'emConfigProbeLowTempEnable' OID is disabled,
- this OID will show disabled(3)."
- ::= { emStatusProbesEntry 8 }
- emStatusProbeHighHumidViolation OBJECT-TYPE
- SYNTAX INTEGER {
- noViolation(1),
- highHumidViolation(2),
- disabled(3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The high humidity violation status of the probe humidity
- reading. This OID will show a highTempViolation(2)
- if the current humidity reading shown in the
- 'emStatusProbeCurrentHumid' OID is greater than or equal to
- the high humidity threshold value, the
- 'emConfigProbeHighHumidThreshold' OID, and the value of the
- 'emConfigProbeHighHumidEnable' OID is enabled. Otherwise it will
- show noViolation(1). If the 'emConfigProbeHighHumidEnable' OID is
- disabled, this OID will show disabled(3)"
- ::= { emStatusProbesEntry 9 }
- emStatusProbeLowHumidViolation OBJECT-TYPE
- SYNTAX INTEGER {
- noViolation(1),
- lowHumidViolation(2),
- disabled(3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The low humidity violation status of the probe humidity
- reading. This OID will show a lowTempViolation(2)
- if the current humidity reading shown in the
- 'emStatusProbeCurrentHumid' OID is less than or equal to
- the low humidity threshold value, the
- 'emConfigProbeLowHumidThreshold' OID, and the value of the
- 'emConfigProbeLowHumidEnable' OID is enabled. Otherwise it will
- show noViolation(1). If the 'emConfigProbeLowHumidEnable' OID is
- disabled, this OID will show disabled(3)."
- ::= { emStatusProbesEntry 10 }
- emStatusProbeMaxTempViolation OBJECT-TYPE
- SYNTAX INTEGER {
- noViolation(1),
- maxTempViolation(2),
- disabled(3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The max temperature violation status of the probe
- temperature reading. This OID will show a maxTempViolation(2)
- if the current temperature reading shown in the
- 'emStatusProbeCurrentTemp' OID is greater than or equal to
- the maximun temperature threshold value, the
- 'emConfigProbeMaxTempThreshold' OID, and the value of the
- 'emConfigProbeMaxTempEnable' OID is enabled. Otherwise it will show
- noViolation(1). If the 'emConfigProbeMaxTempEnable' OID is disabled,
- this OID will show disabled(3)."
- ::= { emStatusProbesEntry 11 }
- emStatusProbeMinTempViolation OBJECT-TYPE
- SYNTAX INTEGER {
- noViolation(1),
- minTempViolation(2),
- disabled(3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The minimum temperature violation status of the probe
- temperature reading. This OID will show a minTempViolation(2)
- if the current temperature reading shown in the
- 'emStatusProbeCurrentTemp' OID is less than or equal to
- the minimum temperature threshold value, the
- 'emConfigProbeMinTempThreshold' OID, and the value of the
- 'emConfigProbeMinTempEnable' OID is enabled. Otherwise it will show
- noViolation(1). If the 'emConfigProbeMinTempEnable' OID is disabled,
- this OID will show disabled(3)."
- ::= { emStatusProbesEntry 12 }
- emStatusProbeMaxHumidViolation OBJECT-TYPE
- SYNTAX INTEGER {
- noViolation(1),
- maxHumidViolation(2),
- disabled(3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The maximum humidity violation status of the probe humidity
- reading. This OID will show a maxTempViolation(2)
- if the current humidity reading shown in the
- 'emStatusProbeCurrentHumid' OID is greater than or equal to
- the maximum humidity threshold value, the
- 'emConfigProbeMaxHumidThreshold' OID, and the value of the
- 'emConfigProbeMaxHumidEnable' OID is enabled. Otherwise it will
- show noViolation(1). If the 'emConfigProbeMaxHumidEnable' OID is
- disabled, this OID will show disabled(3)"
- ::= { emStatusProbesEntry 13 }
- emStatusProbeMinHumidViolation OBJECT-TYPE
- SYNTAX INTEGER {
- noViolation(1),
- minHumidViolation(2),
- disabled(3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The minimum humidity violation status of the probe humidity
- reading. This OID will show a minTempViolation(2)
- if the current humidity reading shown in the
- 'emStatusProbeCurrentHumid' OID is less than or equal to
- the minimum humidity threshold value, the
- 'emConfigProbeMinHumidThreshold' OID, and the value of the
- 'emConfigProbeMinHumidEnable' OID is enabled. Otherwise it will
- show noViolation(1). If the 'emConfigProbeMinHumidEnable' OID is
- disabled, this OID will show disabled(3)."
- ::= { emStatusProbesEntry 14 }
- emStatusContactsNumContacts OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of contacts supported by the
- Environmental Monitor."
- ::= { emStatus 4 }
- emStatusContactsTable OBJECT-TYPE
- SYNTAX SEQUENCE OF EmStatusContactsEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "A list of contacts supported by the Environmental Monitor
- and their status."
- ::= { emStatus 5 }
- emStatusContactsEntry OBJECT-TYPE
- SYNTAX EmStatusContactsEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The status of the contact."
- INDEX { emStatusContactNumber }
- ::= { emStatusContactsTable 1 }
- EmStatusContactsEntry ::=
- SEQUENCE {
- emStatusContactNumber
- INTEGER,
- emStatusContactName
- DisplayString,
- emStatusContactStatus
- INTEGER
- }
- emStatusContactNumber OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index of the Environmental Monitor contact."
- ::= { emStatusContactsEntry 1 }
- emStatusContactName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A descriptive name for the Environmental Monitor contact
- set by the user, possibly denoting its location or purpose."
- ::= { emStatusContactsEntry 2 }
- emStatusContactStatus OBJECT-TYPE
- SYNTAX INTEGER {
- noFault(1),
- fault(2),
- disabled(3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The status of the Environmental Monitor contact. The status
- will show noFault(1) if the contact is in the normal state
- and the 'emConfigContactEnable' OID is enabled. The status will
- show a fault(2) if the contact is faulted and the
- 'emContactEnable' OID is enabled. If the 'emConfigContactEnable'
- OID is disabled, the status will show disabled(3)."
- ::= { emStatusContactsEntry 3 }
- -- Modular Environmental Manager (MEM)
- -- MEM Modules Status table
- memModulesStatusTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the memModulesStatusTable."
- ::= { memModules 1 }
-
- memModulesStatusTable OBJECT-TYPE
- SYNTAX SEQUENCE OF MemModulesStatusEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting status information from the modules
- attached to the system."
- ::= { memModules 2 }
-
- memModulesStatusEntry OBJECT-TYPE
- SYNTAX MemModulesStatusEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The unit to get data from."
- INDEX { memModulesStatusModuleNumber }
- ::= { memModulesStatusTable 1 }
-
- MemModulesStatusEntry ::=
- SEQUENCE {
- memModulesStatusModuleNumber INTEGER,
- memModulesStatusModuleName DisplayString,
- memModulesStatusModuleLocation DisplayString,
- memModulesStatusModelNumber DisplayString,
- memModulesStatusSerialNumber DisplayString,
- memModulesStatusFirmwareRev DisplayString,
- memModulesStatusHardwareRev DisplayString
- }
- memModulesStatusModuleNumber OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The module number."
- ::= { memModulesStatusEntry 1 }
- memModulesStatusModuleName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The module name."
- ::= { memModulesStatusEntry 2 }
- memModulesStatusModuleLocation OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The location of the module."
- ::= { memModulesStatusEntry 3 }
- memModulesStatusModelNumber OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The model number of the module."
- ::= { memModulesStatusEntry 4 }
- memModulesStatusSerialNumber OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The serial number of the module."
- ::= { memModulesStatusEntry 5 }
- memModulesStatusFirmwareRev OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The firmware revision of the module."
- ::= { memModulesStatusEntry 6 }
- memModulesStatusHardwareRev OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The hardware revision."
- ::= { memModulesStatusEntry 7 }
- -- MEM Modules Config table
- memModulesConfigTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the memModulesConfigTable."
- ::= { memModules 3 }
-
- memModulesConfigTable OBJECT-TYPE
- SYNTAX SEQUENCE OF MemModulesConfigEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting status information from the modules
- attached to the system."
- ::= { memModules 4 }
-
- memModulesConfigEntry OBJECT-TYPE
- SYNTAX MemModulesConfigEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The unit to get data from."
- INDEX { memModulesConfigModuleNumber }
- ::= { memModulesConfigTable 1 }
-
- MemModulesConfigEntry ::=
- SEQUENCE {
- memModulesConfigModuleNumber INTEGER,
- memModulesConfigModuleName DisplayString,
- memModulesConfigModuleLocation DisplayString
- }
- memModulesConfigModuleNumber OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The module number."
- ::= { memModulesConfigEntry 1 }
- memModulesConfigModuleName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The module name."
- ::= { memModulesConfigEntry 2 }
- memModulesConfigModuleLocation OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The location of the module."
- ::= { memModulesConfigEntry 3 }
- -- MEM Sensor Status Table
- memSensorsStatusSysTempUnits OBJECT-TYPE
- SYNTAX INTEGER {
- celsius(1),
- fahrenheit(2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The temperature scale used to display the temperature
- in the system, Celsius(1) or Fahrenheit(2).
- This setting is based on the system preferences
- configuration in the agent."
- ::= { memSensors 1 }
- memSensorsStatusTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the memSensorsStatusTable."
- ::= { memSensors 2 }
-
- memSensorsStatusTable OBJECT-TYPE
- SYNTAX SEQUENCE OF MemSensorsStatusEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting sensor status information."
- ::= { memSensors 3 }
-
- memSensorsStatusEntry OBJECT-TYPE
- SYNTAX MemSensorsStatusEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The unit to get data from."
- INDEX { memSensorsStatusModuleNumber, memSensorsStatusSensorNumber }
- ::= { memSensorsStatusTable 1 }
-
- MemSensorsStatusEntry ::=
- SEQUENCE {
- memSensorsStatusModuleNumber INTEGER,
- memSensorsStatusSensorNumber INTEGER,
- memSensorsStatusSensorName DisplayString,
- memSensorsStatusSensorLocation DisplayString,
- memSensorsTemperature INTEGER,
- memSensorsHumidity INTEGER,
- memSensorsCommStatus INTEGER,
- memSensorsAlarmStatus INTEGER
- }
- memSensorsStatusModuleNumber OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of the module that the sensor is attached to."
- ::= { memSensorsStatusEntry 1 }
- memSensorsStatusSensorNumber OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of this sensor on the module."
- ::= { memSensorsStatusEntry 2 }
- memSensorsStatusSensorName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The sensor name."
- ::= { memSensorsStatusEntry 3 }
- memSensorsStatusSensorLocation OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The location of the sensor."
- ::= { memSensorsStatusEntry 4 }
- memSensorsTemperature OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The sensor's current temperature reading.
- Units are displayed in the scale shown in
- the memSensorsStatusSysTempUnits OID (Celsius or Fahrenheit)."
- ::= { memSensorsStatusEntry 5 }
- memSensorsHumidity OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The current humidity reading from the sensor."
- ::= { memSensorsStatusEntry 6 }
- memSensorsCommStatus OBJECT-TYPE
- SYNTAX INTEGER {
- notInstalled(1),
- commsOK(2),
- commsLost(3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The communications status of the sensor."
- ::= { memSensorsStatusEntry 7 }
- memSensorsAlarmStatus OBJECT-TYPE
- SYNTAX INTEGER {
- memNormal(1),
- memWarning(2),
- memCritical(3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The alarm status of the sensor."
- ::= { memSensorsStatusEntry 8 }
- -- MEM Sensor Config Table
- memSensorsConfigTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the memSensorsConfigTable."
- ::= { memSensors 4 }
-
- memSensorsConfigTable OBJECT-TYPE
- SYNTAX SEQUENCE OF MemSensorsConfigEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting configuration information from
- sensors attached to the system."
- ::= { memSensors 5 }
-
- memSensorsConfigEntry OBJECT-TYPE
- SYNTAX MemSensorsConfigEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The unit to get data from."
- INDEX { memSensorsConfigModuleNumber, memSensorsConfigSensorNumber }
- ::= { memSensorsConfigTable 1 }
-
- MemSensorsConfigEntry ::=
- SEQUENCE {
- memSensorsConfigModuleNumber INTEGER,
- memSensorsConfigSensorNumber INTEGER,
- memSensorsName DisplayString,
- memSensorsLocation DisplayString,
- memSensorsAlarmGeneration INTEGER,
- memSensorsTempMaxThresh INTEGER,
- memSensorsTempHighThresh INTEGER,
- memSensorsTempLowThresh INTEGER,
- memSensorsTempMinThresh INTEGER,
- memSensorsTempThreshHysteresis INTEGER,
- memSensorsTempShortDecRateThreshValue INTEGER,
- memSensorsTempShortDecRateThreshTime INTEGER,
- memSensorsTempShortIncRateThreshValue INTEGER,
- memSensorsTempShortIncRateThreshTime INTEGER,
- memSensorsTempLongDecRateThreshValue INTEGER,
- memSensorsTempLongDecRateThreshTime INTEGER,
- memSensorsTempLongIncRateThreshValue INTEGER,
- memSensorsTempLongIncRateThreshTime INTEGER,
- memSensorsHumidityMaxThresh INTEGER,
- memSensorsHumidityHighThresh INTEGER,
- memSensorsHumidityLowThresh INTEGER,
- memSensorsHumidityMinThresh INTEGER,
- memSensorsHumidityThreshHysteresis INTEGER
- }
- memSensorsConfigModuleNumber OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of the module that the sensor is attached to."
- ::= { memSensorsConfigEntry 1 }
- memSensorsConfigSensorNumber OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of this sensor on the module."
- ::= { memSensorsConfigEntry 2 }
- memSensorsName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "A descriptive name for the sensor."
- ::= { memSensorsConfigEntry 3 }
-
- memSensorsLocation OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The location of the sensor."
- ::= { memSensorsConfigEntry 4 }
- memSensorsAlarmGeneration OBJECT-TYPE
- SYNTAX INTEGER {
- disabled (1),
- enabled (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enable or disable alarm generation on this sensor."
- ::= { memSensorsConfigEntry 5 }
- memSensorsTempMaxThresh OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The temperature at which the MEM will generate a maximum
- temperature threshold violation alarm on this sensor.
- The temperature scale is based on the memSensorsStatusSysTempUnits OID."
- ::= { memSensorsConfigEntry 6 }
-
- memSensorsTempHighThresh OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The temperature at which the MEM will generate a high
- temperature threshold violation alarm on this sensor.
- The temperature scale is based on the memSensorsStatusSysTempUnits OID."
- ::= { memSensorsConfigEntry 7 }
-
- memSensorsTempLowThresh OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The temperature at which the MEM will generate a low
- temperature threshold violation alarm on this sensor.
- The temperature scale is based on the memSensorsStatusSysTempUnits OID."
- ::= { memSensorsConfigEntry 8 }
-
- memSensorsTempMinThresh OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The temperature at which the MEM will generate a minimum
- temperature threshold violation alarm on this sensor.
- The temperature scale is based on the memSensorsStatusSysTempUnits OID."
- ::= { memSensorsConfigEntry 9 }
-
- memSensorsTempThreshHysteresis OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The change in temperature required to cause a
- temperature alarm to change from an active to an inactive state.
- The temperature scale is based on the memSensorsStatusSysTempUnits OID."
-
- ::= { memSensorsConfigEntry 10 }
- memSensorsTempShortDecRateThreshValue OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The value of the temperature short-term decreasing rate
- time that will cause an alarm to be generated.
- The temperature scale is based on the memSensorsStatusSysTempUnits OID."
- ::= { memSensorsConfigEntry 11 }
- memSensorsTempShortDecRateThreshTime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The time over which the temperature may not decrease
- beyond the value specified by the temperature short-term
- decreasing rate threshold value."
- ::= { memSensorsConfigEntry 12 }
-
- memSensorsTempShortIncRateThreshValue OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The value of the temperature short-term increasing rate
- time that will cause an alarm to be generated.
- The temperature scale is based on the memSensorsStatusSysTempUnits OID."
- ::= { memSensorsConfigEntry 13 }
- memSensorsTempShortIncRateThreshTime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The time over which the temperature may not increase
- beyond the value specified by the temperature short-term
- increasing rate threshold value."
- ::= { memSensorsConfigEntry 14 }
-
- memSensorsTempLongDecRateThreshValue OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The value of the temperature long-term decreasing rate
- time that will cause an alarm to be generated.
- The temperature scale is based on the memSensorsStatusSysTempUnits OID."
- ::= { memSensorsConfigEntry 15 }
- memSensorsTempLongDecRateThreshTime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The time over which the temperature may not decrease
- beyond the value specified by the temperature long-term
- decreasing rate threshold value."
- ::= { memSensorsConfigEntry 16 }
-
- memSensorsTempLongIncRateThreshValue OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The value of the temperature long-term increasing rate
- time that will cause an alarm to be generated.
- The temperature scale is based on the memSensorsStatusSysTempUnits OID."
- ::= { memSensorsConfigEntry 17 }
- memSensorsTempLongIncRateThreshTime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The time over which the temperature may not increase
- beyond the value specified by the temperature long-term
- increasing rate threshold value."
- ::= { memSensorsConfigEntry 18 }
-
- memSensorsHumidityMaxThresh OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The humidity at which the maximum humidity threshold alarm
- will be generated."
- ::= { memSensorsConfigEntry 19 }
-
- memSensorsHumidityHighThresh OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The humidity at which the high humidity threshold alarm
- will be generated."
- ::= { memSensorsConfigEntry 20 }
-
- memSensorsHumidityLowThresh OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The humidity at which the low humidity threshold alarm
- will be generated."
- ::= { memSensorsConfigEntry 21 }
-
- memSensorsHumidityMinThresh OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The humidity at which the minimum humidity threshold alarm
- will be generated."
- ::= { memSensorsConfigEntry 22 }
-
- memSensorsHumidityThreshHysteresis OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The change in humidity required to cause an active humidity
- alarm to change to the inactive state."
- ::= { memSensorsConfigEntry 23 }
- -- MEM Input Status Table
- memInputsStatusTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the memInputsStatusTable."
- ::= { memInputs 1 }
-
- memInputsStatusTable OBJECT-TYPE
- SYNTAX SEQUENCE OF MemInputsStatusEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting input status information."
- ::= { memInputs 2 }
-
- memInputsStatusEntry OBJECT-TYPE
- SYNTAX MemInputsStatusEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The unit to get data from."
- INDEX { memInputsStatusModuleNumber, memInputsStatusInputNumber }
- ::= { memInputsStatusTable 1 }
-
- MemInputsStatusEntry ::=
- SEQUENCE {
- memInputsStatusModuleNumber INTEGER,
- memInputsStatusInputNumber INTEGER,
- memInputsStatusInputName DisplayString,
- memInputsStatusInputLocation DisplayString,
- memInputsStatusCurrentState INTEGER,
- memInputsStatusCurrentAnalogValue DisplayString,
- memInputsStatusAlarmStatus INTEGER,
- memInputsCommStatus INTEGER
- }
- memInputsStatusModuleNumber OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of the module that the input is attached to."
- ::= { memInputsStatusEntry 1 }
- memInputsStatusInputNumber OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of this input on the module."
- ::= { memInputsStatusEntry 2 }
- memInputsStatusInputName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The input name."
- ::= { memInputsStatusEntry 3 }
- memInputsStatusInputLocation OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The location of the input."
- ::= { memInputsStatusEntry 4 }
- memInputsStatusCurrentState OBJECT-TYPE
- SYNTAX INTEGER {
- inputClosedHighMEM (1),
- inputOpenLowMEM (2),
- inputDisabled (3),
- inputStateNotApplicable (4)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The current state of the input. This OID will return
- inputStateNotAplicable(4) for analog input types. "
- ::= { memInputsStatusEntry 5 }
- memInputsStatusCurrentAnalogValue OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The current analog value of the input in the units defined
- by the user."
- ::= { memInputsStatusEntry 6 }
- memInputsStatusAlarmStatus OBJECT-TYPE
- SYNTAX INTEGER {
- memNormal(1),
- memWarning(2),
- memCritical(3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The alarm status of the input."
- ::= { memInputsStatusEntry 7 }
- memInputsCommStatus OBJECT-TYPE
- SYNTAX INTEGER {
- notInstalled(1),
- commsOK(2),
- commsLost(3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The communications status of the input. This OID is only supported by NBRK0200."
- ::= { memInputsStatusEntry 8 }
- -- MEM Input Config Table
- memInputsConfigTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the memInputsConfigTable."
- ::= { memInputs 3 }
-
- memInputsConfigTable OBJECT-TYPE
- SYNTAX SEQUENCE OF MemInputsConfigEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting input configuration information."
- ::= { memInputs 4 }
-
- memInputsConfigEntry OBJECT-TYPE
- SYNTAX MemInputsConfigEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The unit to get data from."
- INDEX { memInputsConfigModuleNumber, memInputsConfigInputNumber }
- ::= { memInputsConfigTable 1 }
-
- MemInputsConfigEntry ::=
- SEQUENCE {
- memInputsConfigModuleNumber INTEGER,
- memInputsConfigInputNumber INTEGER,
- memInputName DisplayString,
- memInputLocation DisplayString,
- memInputType INTEGER,
- memInputAlarmGeneration INTEGER,
- memInputNormalState INTEGER,
- memInputAbnormalSeverity INTEGER,
- memInputNumberCalibrationPoints INTEGER,
- memInputAnalogCalibrationPoint1 DisplayString,
- memInputAnalogCalibrationPoint2 DisplayString,
- memInputAnalogCalibrationPoint3 DisplayString,
- memInputAnalogCalibrationPoint4 DisplayString,
- memInputAnalogCalibrationPoint5 DisplayString,
- memInputAnalogCalibrationPoint1Value DisplayString,
- memInputAnalogCalibrationPoint2Value DisplayString,
- memInputAnalogCalibrationPoint3Value DisplayString,
- memInputAnalogCalibrationPoint4Value DisplayString,
- memInputAnalogCalibrationPoint5Value DisplayString,
- memInputAnalogMeasurementUnits DisplayString,
- memInputAnalogMaxThresh DisplayString,
- memInputAnalogHighThresh DisplayString,
- memInputAnalogLowThresh DisplayString,
- memInputAnalogMinThresh DisplayString,
- memInputAnalogThreshHysteresis DisplayString
- }
- memInputsConfigModuleNumber OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of the module that the input is attached to."
- ::= { memInputsConfigEntry 1 }
- memInputsConfigInputNumber OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of this input on the module."
- ::= { memInputsConfigEntry 2 }
- memInputName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The name of the input."
- ::= { memInputsConfigEntry 3 }
- memInputLocation OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The location of the input."
- ::= { memInputsConfigEntry 4 }
- memInputType OBJECT-TYPE
- SYNTAX INTEGER {
- noConnection (1),
- dryContact (2),
- digital (3),
- analogmAmps (4),
- analogVolts (5)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The type of input this contact will take."
- ::= { memInputsConfigEntry 5 }
- memInputAlarmGeneration OBJECT-TYPE
- SYNTAX INTEGER {
- disabled (1),
- enabled (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enable or disable alarm generation on this input."
- ::= { memInputsConfigEntry 6 }
- memInputNormalState OBJECT-TYPE
- SYNTAX INTEGER {
- inputClosedHighMEM (1),
- inputOpenLowMEM (2),
- inputDisabled (3),
- inputStateNotApplicable (4)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Defines the normal (no alarm) state of the input."
- ::= { memInputsConfigEntry 7 }
- memInputAbnormalSeverity OBJECT-TYPE
- SYNTAX INTEGER {
- inputSeverityinformational (1),
- inputSeveritywarning (2),
- inputSeveritysevere (3),
- inputSeverityNotApplicable (4)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Defines the severity of the event that is associated
- with the abnormal state of the input. This OID will return
- inputSeverityNotApplicable(4) for analog input types. "
- ::= { memInputsConfigEntry 8 }
- memInputNumberCalibrationPoints OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The number of calibration points that are required for
- this input."
- ::= { memInputsConfigEntry 9 }
-
- memInputAnalogCalibrationPoint1 OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The electrical value that the input sensor will measure at the
- first calibration point.
- This OID is relevant only for inputs configured as analog type (ma or V)."
- ::= { memInputsConfigEntry 10 }
-
- memInputAnalogCalibrationPoint2 OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The electrical value that the input sensor will measure at the
- second calibration point.
- This OID is relevant only for inputs configured as analog type (ma or V)."
- ::= { memInputsConfigEntry 11 }
-
- memInputAnalogCalibrationPoint3 OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The electrical value that the input sensor will measure at the
- third calibration point.
- This OID is relevant only for inputs configured as analog type (ma or V)."
- ::= { memInputsConfigEntry 12 }
-
- memInputAnalogCalibrationPoint4 OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The electrical value that the input sensor will measure at the
- fourth calibration point.
- This OID is relevant only for inputs configured as analog type (ma or V)."
- ::= { memInputsConfigEntry 13 }
-
- memInputAnalogCalibrationPoint5 OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The electrical value that the input sensor will measure at the
- fifth calibration point.
- This OID is relevant only for inputs configured as analog type (ma or V)."
- ::= { memInputsConfigEntry 14 }
-
- memInputAnalogCalibrationPoint1Value OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The value of the input, in units of measure defined by
- the user, that corresponds to the current setting at the
- first calibration point."
- ::= { memInputsConfigEntry 15 }
- memInputAnalogCalibrationPoint2Value OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The value of the input, in units of measure defined by
- the user, that corresponds to the current setting at the
- second calibration point."
- ::= { memInputsConfigEntry 16 }
- memInputAnalogCalibrationPoint3Value OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The value of the input, in units of measure defined by
- the user, that corresponds to the current setting at the
- third calibration point."
- ::= { memInputsConfigEntry 17 }
- memInputAnalogCalibrationPoint4Value OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The value of the input, in units of measure defined by
- the user, that corresponds to the current setting at the
- fourth calibration point."
- ::= { memInputsConfigEntry 18 }
- memInputAnalogCalibrationPoint5Value OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The value of the input, in units of measure defined by
- the user, that corresponds to the current setting at the
- fifth calibration point."
- ::= { memInputsConfigEntry 19 }
- memInputAnalogMeasurementUnits OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The units of measure to be used for this input."
- ::= { memInputsConfigEntry 20 }
-
- memInputAnalogMaxThresh OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The input value at which a maximum threshold violation
- alarm will be generated on this input."
- ::= { memInputsConfigEntry 21 }
-
- memInputAnalogHighThresh OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The input value at which a high threshold violation
- alarm will be generated on this input."
- ::= { memInputsConfigEntry 22 }
-
- memInputAnalogLowThresh OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The input value at which a low threshold violation
- alarm will be generated on this input."
- ::= { memInputsConfigEntry 23 }
-
- memInputAnalogMinThresh OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The input value at which a minimum threshold violation
- alarm will be generated on this input."
- ::= { memInputsConfigEntry 24 }
-
-
- memInputAnalogThreshHysteresis OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The change in value required to cause an alarm on this input
- to change from active to inactive."
- ::= { memInputsConfigEntry 25 }
-
- -- MEM Output Status Table
- memOutputStatusTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the memOutputStatusTable."
- ::= { memOutputs 1 }
-
- memOutputStatusTable OBJECT-TYPE
- SYNTAX SEQUENCE OF MemOutputStatusEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting output status information."
- ::= { memOutputs 2 }
-
- memOutputStatusEntry OBJECT-TYPE
- SYNTAX MemOutputStatusEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The unit to get data from."
- INDEX { memOutputStatusModuleNumber, memOutputStatusOutputNumber }
- ::= { memOutputStatusTable 1 }
-
- MemOutputStatusEntry ::=
- SEQUENCE {
- memOutputStatusModuleNumber INTEGER,
- memOutputStatusOutputNumber INTEGER,
- memOutputStatusOutputName DisplayString,
- memOutputStatusOutputLocation DisplayString,
- memOutputStatusCurrentState INTEGER
- }
- memOutputStatusModuleNumber OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of the module that the output is attached to."
- ::= { memOutputStatusEntry 1 }
- memOutputStatusOutputNumber OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of this output on the module."
- ::= { memOutputStatusEntry 2 }
- memOutputStatusOutputName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The output name."
- ::= { memOutputStatusEntry 3 }
- memOutputStatusOutputLocation OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The location of the output."
- ::= { memOutputStatusEntry 4 }
- memOutputStatusCurrentState OBJECT-TYPE
- SYNTAX INTEGER {
- memOutputClosed (1),
- memOutputOpen (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The state of the output."
- ::= { memOutputStatusEntry 5 }
- -- MEM Output Config Table
- memOutputConfigTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the memOutputConfigTable."
- ::= { memOutputs 3 }
-
- memOutputConfigTable OBJECT-TYPE
- SYNTAX SEQUENCE OF MemOutputConfigEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting output configuration information."
- ::= { memOutputs 4 }
-
- memOutputConfigEntry OBJECT-TYPE
- SYNTAX MemOutputConfigEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The unit to get data from."
- INDEX { memOutputConfigModuleNumber, memOutputConfigOutputNumber }
- ::= { memOutputConfigTable 1 }
-
- MemOutputConfigEntry ::=
- SEQUENCE {
- memOutputConfigModuleNumber INTEGER,
- memOutputConfigOutputNumber INTEGER,
- memOutputName DisplayString,
- memOutputLocation DisplayString,
- memOutputNormalState INTEGER,
- memOutputAction INTEGER
- }
- memOutputConfigModuleNumber OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of the module that the output is attached to."
- ::= { memOutputConfigEntry 1 }
- memOutputConfigOutputNumber OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of this output on the module."
- ::= { memOutputConfigEntry 2 }
- memOutputName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The name of the output."
- ::= { memOutputConfigEntry 3 }
- memOutputLocation OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The location of the output."
- ::= { memOutputConfigEntry 4 }
- memOutputNormalState OBJECT-TYPE
- SYNTAX INTEGER {
- memOutputClosed (1),
- memOutputOpen (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The state of the output that will not generate an alarm."
- ::= { memOutputConfigEntry 5 }
- memOutputAction OBJECT-TYPE
- SYNTAX INTEGER {
- memActionClose (1),
- memActionOpen (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Manual control actions for the output. SNMP get command will return the state
- of the output, SNMP set of this OID controls the output."
- ::= { memOutputConfigEntry 6 }
- -- MEM Outlet Status Table
- memOutletStatusTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the memOutletStatusTable."
- ::= { memOutlets 1 }
-
- memOutletStatusTable OBJECT-TYPE
- SYNTAX SEQUENCE OF MemOutletStatusEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting outlet status information."
- ::= { memOutlets 2 }
-
- memOutletStatusEntry OBJECT-TYPE
- SYNTAX MemOutletStatusEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The unit to get data from."
- INDEX { memOutletStatusModuleNumber, memOutletStatusOutletNumber }
- ::= { memOutletStatusTable 1 }
-
- MemOutletStatusEntry ::=
- SEQUENCE {
- memOutletStatusModuleNumber INTEGER,
- memOutletStatusOutletNumber INTEGER,
- memOutletStatusOutletName DisplayString,
- memOutletStatusOutletLocation DisplayString,
- memOutletStatusCurrentState INTEGER
- }
- memOutletStatusModuleNumber OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of the module that the outlet is attached to."
- ::= { memOutletStatusEntry 1 }
- memOutletStatusOutletNumber OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of this outlet on the module."
- ::= { memOutletStatusEntry 2 }
- memOutletStatusOutletName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The outlet name."
- ::= { memOutletStatusEntry 3 }
- memOutletStatusOutletLocation OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The location of the outlet."
- ::= { memOutletStatusEntry 4 }
- memOutletStatusCurrentState OBJECT-TYPE
- SYNTAX INTEGER {
- off (1),
- on (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The state of the outlet."
- ::= { memOutletStatusEntry 5 }
- -- MEM Outlet Config Table
- memOutletConfigTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the memOutletConfigTable."
- ::= { memOutlets 3 }
-
- memOutletConfigTable OBJECT-TYPE
- SYNTAX SEQUENCE OF MemOutletConfigEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting outlet configuration information."
- ::= { memOutlets 4 }
-
- memOutletConfigEntry OBJECT-TYPE
- SYNTAX MemOutletConfigEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The unit to get data from."
- INDEX { memOutletConfigModuleNumber, memOutletConfigOutletNumber }
- ::= { memOutletConfigTable 1 }
-
- MemOutletConfigEntry ::=
- SEQUENCE {
- memOutletConfigModuleNumber INTEGER,
- memOutletConfigOutletNumber INTEGER,
- memOutletName DisplayString,
- memOutletLocation DisplayString,
- memOutletNormalState INTEGER,
- memOutletAction INTEGER
- }
- memOutletConfigModuleNumber OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of the module that the Outlet is attached to."
- ::= { memOutletConfigEntry 1 }
- memOutletConfigOutletNumber OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of this Outlet on the module."
- ::= { memOutletConfigEntry 2 }
- memOutletName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The name of the Outlet."
- ::= { memOutletConfigEntry 3 }
- memOutletLocation OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The location of the Outlet."
- ::= { memOutletConfigEntry 4 }
- memOutletNormalState OBJECT-TYPE
- SYNTAX INTEGER {
- off (1),
- on (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The state of the Outlet that will not generate an alarm."
- ::= { memOutletConfigEntry 5 }
- memOutletAction OBJECT-TYPE
- SYNTAX INTEGER {
- turnOff (1),
- turnOn (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Manual control actions for the Outlet. Get displays state
- of outlet, set controls outlet."
- ::= { memOutletConfigEntry 6 }
- -- MEM Beacon Status Table
- memBeaconStatusTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the memBeaconStatusTable."
- ::= { memBeacons 1 }
-
- memBeaconStatusTable OBJECT-TYPE
- SYNTAX SEQUENCE OF MemBeaconStatusEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting beacon status information."
- ::= { memBeacons 2 }
-
- memBeaconStatusEntry OBJECT-TYPE
- SYNTAX MemBeaconStatusEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The unit to get data from."
- INDEX { memBeaconStatusModuleNumber, memBeaconStatusBeaconNumber }
- ::= { memBeaconStatusTable 1 }
-
- MemBeaconStatusEntry ::=
- SEQUENCE {
- memBeaconStatusModuleNumber INTEGER,
- memBeaconStatusBeaconNumber INTEGER,
- memBeaconStatusBeaconName DisplayString,
- memBeaconStatusBeaconLocation DisplayString,
- memBeaconStatusCurrentState INTEGER
- }
- memBeaconStatusModuleNumber OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of the module that the beacon is attached to."
- ::= { memBeaconStatusEntry 1 }
- memBeaconStatusBeaconNumber OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of this beacon on the module."
- ::= { memBeaconStatusEntry 2 }
- memBeaconStatusBeaconName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The beacon name."
- ::= { memBeaconStatusEntry 3 }
- memBeaconStatusBeaconLocation OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The location of the beacon."
- ::= { memBeaconStatusEntry 4 }
- memBeaconStatusCurrentState OBJECT-TYPE
- SYNTAX INTEGER {
- off (1),
- on (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The state of the beacon."
- ::= { memBeaconStatusEntry 5 }
- -- MEM Beacon Config Table
- memBeaconConfigTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the memBeaconConfigTable."
- ::= { memBeacons 3 }
-
- memBeaconConfigTable OBJECT-TYPE
- SYNTAX SEQUENCE OF MemBeaconConfigEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting beacon configuration information."
- ::= { memBeacons 4 }
-
- memBeaconConfigEntry OBJECT-TYPE
- SYNTAX MemBeaconConfigEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The unit to get data from."
- INDEX { memBeaconConfigModuleNumber, memBeaconConfigBeaconNumber }
- ::= { memBeaconConfigTable 1 }
-
- MemBeaconConfigEntry ::=
- SEQUENCE {
- memBeaconConfigModuleNumber INTEGER,
- memBeaconConfigBeaconNumber INTEGER,
- memBeaconConfigName DisplayString,
- memBeaconConfigLocation DisplayString,
- memBeaconAction INTEGER
- }
- memBeaconConfigModuleNumber OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of the module that the beacon is attached to."
- ::= { memBeaconConfigEntry 1 }
- memBeaconConfigBeaconNumber OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of this beacon on the module."
- ::= { memBeaconConfigEntry 2 }
- memBeaconConfigName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The name of the beacon."
- ::= { memBeaconConfigEntry 3 }
- memBeaconConfigLocation OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The location of the beacon."
- ::= { memBeaconConfigEntry 4 }
- memBeaconAction OBJECT-TYPE
- SYNTAX INTEGER {
- turnOff (1),
- turnOn (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Control action (on/off) for the beacon. Setting this OID will turn the
- beacon on/off. Getting this OID will respond with the current state."
- ::= { memBeaconConfigEntry 5 }
- -- Integrated Environmental Monitor (IEM)
- iemIdentHardwareRevision OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The hardware revision of the Integrated Environmental
- Monitor."
- ::= { iemIdent 1 }
- iemConfigProbesNumProbes OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of temperature and humidity probes available."
- ::= { iemConfig 1 }
- iemConfigProbesTable OBJECT-TYPE
- SYNTAX SEQUENCE OF IemConfigProbesEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "A list of probes supported by the Environmental Monitor
- and their configurations."
- ::= { iemConfig 2 }
- iemConfigProbesEntry OBJECT-TYPE
- SYNTAX IemConfigProbesEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The Environmental Monitor probe configurations."
- INDEX { iemConfigProbeNumber }
- ::= { iemConfigProbesTable 1 }
- IemConfigProbesEntry ::=
- SEQUENCE {
- iemConfigProbeNumber
- INTEGER,
- iemConfigProbeName
- DisplayString,
- iemConfigProbeHighTempThreshold
- INTEGER,
- iemConfigProbeLowTempThreshold
- INTEGER,
- iemConfigProbeTempUnits
- INTEGER,
- iemConfigProbeHighHumidThreshold
- INTEGER,
- iemConfigProbeLowHumidThreshold
- INTEGER,
- iemConfigProbeHighTempEnable
- INTEGER,
- iemConfigProbeLowTempEnable
- INTEGER,
- iemConfigProbeHighHumidEnable
- INTEGER,
- iemConfigProbeLowHumidEnable
- INTEGER,
- iemConfigProbeMaxTempThreshold
- INTEGER,
- iemConfigProbeMinTempThreshold
- INTEGER,
- iemConfigProbeMaxHumidThreshold
- INTEGER,
- iemConfigProbeMinHumidThreshold
- INTEGER,
- iemConfigProbeMaxTempEnable
- INTEGER,
- iemConfigProbeMinTempEnable
- INTEGER,
- iemConfigProbeMaxHumidEnable
- INTEGER,
- iemConfigProbeMinHumidEnable
- INTEGER,
- iemConfigProbeTempHysteresis
- INTEGER,
- iemConfigProbeHumidHysteresis
- INTEGER,
- iemConfigProbeLocation
- DisplayString
- }
- iemConfigProbeNumber OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to a Environmental Monitor probe entry."
- ::= { iemConfigProbesEntry 1 }
- iemConfigProbeName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "A descriptive name for the probe set by the user,
- possibly denoting its location or purpose."
- ::= { iemConfigProbesEntry 2 }
- iemConfigProbeHighTempThreshold OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The high temperature alarm threshold for the probe.
- Units are displayed in the scale selected in the
- 'iemConfigProbeTempUnits' OID (Celsius or Fahrenheit)."
- ::= { iemConfigProbesEntry 3 }
- iemConfigProbeLowTempThreshold OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The low temperature alarm threshold for the probe.
- Units are displayed in the scale selected in the
- 'iemConfigProbeTempUnits' OID (Celsius or Fahrenheit)."
- ::= { iemConfigProbesEntry 4 }
- iemConfigProbeTempUnits OBJECT-TYPE
- SYNTAX INTEGER {
- celsius(1),
- fahrenheit(2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The temperature scale used to display the temperature
- thresholds of the probe, Celsius(1) or Fahrenheit(2).
- This setting is based on the system preferences
- configuration in the agent."
- ::= { iemConfigProbesEntry 5 }
- iemConfigProbeHighHumidThreshold OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The high humidity alarm threshold for the probe in
- percent relative humidity."
- ::= { iemConfigProbesEntry 6 }
- iemConfigProbeLowHumidThreshold OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The low humidity alarm threshold for the probe in
- percent relative humidity."
- ::= { iemConfigProbesEntry 7 }
- iemConfigProbeHighTempEnable OBJECT-TYPE
- SYNTAX INTEGER {
- disabled(1),
- enabled(2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The high temperature alarm enable/disable for the
- probe. No alarm will be generated if this value
- is set to disabled(1). The alarm will be
- generated if this value is set to enabled(2) and
- the threshold has been violated."
- ::= { iemConfigProbesEntry 8 }
- iemConfigProbeLowTempEnable OBJECT-TYPE
- SYNTAX INTEGER {
- disabled(1),
- enabled(2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The low temperature alarm enable/disable for the
- probe. No alarm will be generated if this value
- is set to disabled(1). The alarm will be
- generated if this value is set to enabled(2) and
- the threshold has been violated."
- ::= { iemConfigProbesEntry 9 }
- iemConfigProbeHighHumidEnable OBJECT-TYPE
- SYNTAX INTEGER {
- disabled(1),
- enabled(2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The high humidity alarm enable/disable for the
- probe. No alarm will be generated if this value
- is set to disabled(1). The alarm will be
- generated if this value is set to enabled(2) and
- the threshold has been violated."
- ::= { iemConfigProbesEntry 10 }
- iemConfigProbeLowHumidEnable OBJECT-TYPE
- SYNTAX INTEGER {
- disabled(1),
- enabled(2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The low humidity alarm enable/disable for the
- probe. No alarm will be generated if this value
- is set to disabled(1). The alarm will be
- generated if this value is set to enabled(2) and
- the threshold has been violated."
- ::= { iemConfigProbesEntry 11 }
- iemConfigProbeMaxTempThreshold OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The maximun temperature alarm threshold for the probe.
- Units are displayed in the scale selected in the
- 'iemConfigProbeTempUnits' OID (Celsius or Fahrenheit)."
- ::= { iemConfigProbesEntry 12 }
- iemConfigProbeMinTempThreshold OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The minimun temperature alarm threshold for the probe.
- Units are displayed in the scale selected in the
- 'iemConfigProbeTempUnits' OID (Celsius or Fahrenheit)."
- ::= { iemConfigProbesEntry 13 }
- iemConfigProbeMaxHumidThreshold OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The maximum humidity alarm threshold for the probe in
- percent relative humidity."
- ::= { iemConfigProbesEntry 14 }
- iemConfigProbeMinHumidThreshold OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The minimum humidity alarm threshold for the probe in
- percent relative humidity."
- ::= { iemConfigProbesEntry 15 }
- iemConfigProbeMaxTempEnable OBJECT-TYPE
- SYNTAX INTEGER {
- disabled(1),
- enabled(2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The maximum temperature alarm enable/disable for the
- probe. No alarm will be generated if this value
- is set to disabled(1). The alarm will be
- generated if this value is set to enabled(2) and
- the threshold has been violated."
- ::= { iemConfigProbesEntry 16 }
- iemConfigProbeMinTempEnable OBJECT-TYPE
- SYNTAX INTEGER {
- disabled(1),
- enabled(2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The low temperature alarm enable/disable for the
- probe. No alarm will be generated if this value
- is set to disabled(1). The alarm will be
- generated if this value is set to enabled(2) and
- the threshold has been violated."
- ::= { iemConfigProbesEntry 17 }
- iemConfigProbeMaxHumidEnable OBJECT-TYPE
- SYNTAX INTEGER {
- disabled(1),
- enabled(2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The maximum humidity alarm enable/disable for the
- probe. No alarm will be generated if this value
- is set to disabled(1). The alarm will be
- generated if this value is set to enabled(2) and
- the threshold has been violated."
- ::= { iemConfigProbesEntry 18 }
- iemConfigProbeMinHumidEnable OBJECT-TYPE
- SYNTAX INTEGER {
- disabled(1),
- enabled(2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The minimum humidity alarm enable/disable for the
- probe. No alarm will be generated if this value
- is set to disabled(1). The alarm will be
- generated if this value is set to enabled(2) and
- the threshold has been violated."
- ::= { iemConfigProbesEntry 19 }
- iemConfigProbeTempHysteresis OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The number of degrees beyond the temperature thresholds
- at which an active temperature alarm will be cleared.
- This configuration setting applies to all temperature
- thresholds.
- Units are displayed in the scale selected in
- the 'emConfigProbeTempUnits' OID (Celsius or Fahrenheit)."
- ::= { iemConfigProbesEntry 20 }
- iemConfigProbeHumidHysteresis OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The number of percent RH points beyond the humidity
- thresholds at which an active humidity alarm will be
- cleared. This configuration setting applies to all
- humidity thresholds.
- Units are displayed in the scale selected in
- the 'emConfigProbeTempUnits' OID (Celsius or Fahrenheit)."
- ::= { iemConfigProbesEntry 21 }
- iemConfigProbeLocation OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "A string describing the location of the probe."
- ::= { iemConfigProbesEntry 22 }
- iemConfigContactsNumContacts OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of contacts available on the Environmental
- Monitor."
- ::= { iemConfig 3 }
- iemConfigContactsTable OBJECT-TYPE
- SYNTAX SEQUENCE OF IemConfigContactsEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "A list of contacts supported by the Environmental Monitor
- and their configurations."
- ::= { iemConfig 4 }
- iemConfigContactsEntry OBJECT-TYPE
- SYNTAX IemConfigContactsEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The Environmental Monitor contact configurations."
- INDEX { iemConfigContactNumber }
- ::= { iemConfigContactsTable 1 }
- IemConfigContactsEntry ::=
- SEQUENCE {
- iemConfigContactNumber
- INTEGER,
- iemConfigContactName
- DisplayString,
- iemConfigContactEnable
- INTEGER,
- iemConfigContactSeverity
- INTEGER,
- iemConfigContactNormalState
- INTEGER,
- iemConfigContactLocation
- DisplayString
- }
- iemConfigContactNumber OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index of an Environmental Monitor contact."
- ::= { iemConfigContactsEntry 1 }
- iemConfigContactName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "A descriptive name for the Environmental Monitor contact
- set by the user, possibly denoting its location or purpose."
- ::= { iemConfigContactsEntry 2 }
- iemConfigContactEnable OBJECT-TYPE
- SYNTAX INTEGER {
- disabled(1),
- enabled(2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "An Environmental Monitor contact alarm enable/disable."
- ::= { iemConfigContactsEntry 3 }
- iemConfigContactSeverity OBJECT-TYPE
- SYNTAX INTEGER {
- critical(1),
- warning(2),
- informational(3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The severtity of the alarm that will be triggered when
- the input contact is activated. The alarms can be
- critical(1), warning(2) or informational(3).
- NOTE: informational(3) is deprecated (and no longer valid) for this OID."
- ::= { iemConfigContactsEntry 4 }
- iemConfigContactNormalState OBJECT-TYPE
- SYNTAX INTEGER {
- open(1),
- closed(2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The contact state that will be considered normal, i.e.
- will not trigger an alarm. The states are open(1) or
- closed(2)."
- ::= { iemConfigContactsEntry 5 }
- iemConfigContactLocation OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "A descriptive label for the contact denoting its
- location or purpose."
- ::= { iemConfigContactsEntry 6 }
- iemConfigConfigRelaysNumRelays OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of output relays supported by the Environmental
- Monitor."
- ::= { iemConfig 5 }
- iemConfigRelaysTable OBJECT-TYPE
- SYNTAX SEQUENCE OF IemConfigRelaysEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "A list of output relays supported by the Environmental Monitor
- and their configurations."
- ::= { iemConfig 6 }
- iemConfigRelaysEntry OBJECT-TYPE
- SYNTAX IemConfigRelaysEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The Environmental Monitor output relay configurations."
- INDEX { iemConfigRelayNumber }
- ::= { iemConfigRelaysTable 1 }
- IemConfigRelaysEntry ::=
- SEQUENCE {
- iemConfigRelayNumber
- INTEGER,
- iemConfigRelayName
- DisplayString,
- iemConfigRelayNormalState
- INTEGER,
- iemConfigRelayFaultCondition
- INTEGER
- }
- iemConfigRelayNumber OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index of an Environmental Monitor output relay."
- ::= { iemConfigRelaysEntry 1 }
- iemConfigRelayName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "A descriptive name of an Environmental Monitor output relay,
- set by the user, describing its location or purpose."
- ::= { iemConfigRelaysEntry 2 }
- iemConfigRelayNormalState OBJECT-TYPE
- SYNTAX INTEGER {
- open(1),
- closed(2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The normal state (non-fault state) of an Environmental
- Monitor output relay, either open(1) or closed(2)."
- ::= { iemConfigRelaysEntry 3 }
- iemConfigRelayFaultCondition OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The fault condition used to activate the output relay."
- ::= { iemConfigRelaysEntry 4 }
- iemStatusProbesNumProbes OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of available probes on the Environmental
- Monitor."
- ::= { iemStatus 1 }
- iemStatusProbesTable OBJECT-TYPE
- SYNTAX SEQUENCE OF IemStatusProbesEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "A list of probes supported by the Environmental Monitor
- and their status."
- ::= { iemStatus 2 }
- iemStatusProbesEntry OBJECT-TYPE
- SYNTAX IemStatusProbesEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The status of the probe."
- INDEX { iemStatusProbeNumber }
- ::= { iemStatusProbesTable 1 }
- IemStatusProbesEntry ::=
- SEQUENCE {
- iemStatusProbeNumber
- INTEGER,
- iemStatusProbeName
- DisplayString,
- iemStatusProbeStatus
- INTEGER,
- iemStatusProbeCurrentTemp
- INTEGER,
- iemStatusProbeTempUnits
- INTEGER,
- iemStatusProbeCurrentHumid
- INTEGER,
- iemStatusProbeHighTempViolation
- INTEGER,
- iemStatusProbeLowTempViolation
- INTEGER,
- iemStatusProbeHighHumidViolation
- INTEGER,
- iemStatusProbeLowHumidViolation
- INTEGER,
- iemStatusProbeMaxTempViolation
- INTEGER,
- iemStatusProbeMinTempViolation
- INTEGER,
- iemStatusProbeMaxHumidViolation
- INTEGER,
- iemStatusProbeMinHumidViolation
- INTEGER,
- iemStatusProbeLocation
- DisplayString
- }
- iemStatusProbeNumber OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index of the probe."
- ::= { iemStatusProbesEntry 1 }
- iemStatusProbeName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A descriptive name for the probe set by the user."
- ::= { iemStatusProbesEntry 2 }
- iemStatusProbeStatus OBJECT-TYPE
- SYNTAX INTEGER {
- disconnected(1),
- connected(2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The connected status of the probe, either
- disconnected(1) or connected(2)."
- ::= { iemStatusProbesEntry 3 }
- iemStatusProbeCurrentTemp OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The current temperature reading from the probe displayed
- in the units shown in the 'iemStatusProbeTempUnits' OID
- (Celsius or Fahrenheit)."
- ::= { iemStatusProbesEntry 4 }
- iemStatusProbeTempUnits OBJECT-TYPE
- SYNTAX INTEGER {
- celsius(1),
- fahrenheit(2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The temperature scale used to display the temperature
- thresholds of the probe, Celsius(1) or Fahrenheit(2).
- This setting is based on the system preferences
- configuration in the agent."
- ::= { iemStatusProbesEntry 5 }
- iemStatusProbeCurrentHumid OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The current humidity reading from the probe in percent
- relative humidity."
- ::= { iemStatusProbesEntry 6 }
- iemStatusProbeHighTempViolation OBJECT-TYPE
- SYNTAX INTEGER {
- noViolation(1),
- highTempViolation(2),
- disabled(3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The high temperature violation status of the probe
- temperature reading. This OID will show a highTempViolation(2)
- if the current temperature reading shown in the
- 'iemStatusProbeCurrentTemp' OID is greater than or equal to
- the high temperature threshold value, the
- 'iemConfigProbeHighTempThreshold' OID, and the value of the
- 'iemConfigProbeHighTempEnable' OID is enabled. Otherwise it will show
- noViolation(1). If the 'iemConfigProbeHighTempEnable' OID is disabled,
- this OID will show disabled(3)."
- ::= { iemStatusProbesEntry 7 }
- iemStatusProbeLowTempViolation OBJECT-TYPE
- SYNTAX INTEGER {
- noViolation(1),
- lowTempViolation(2),
- disabled(3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The high temperature violation status of the probe
- temperature reading. This OID will show a lowTempViolation(2)
- if the current temperature reading shown in the
- 'iemStatusProbeCurrentTemp' OID is less than or equal to
- the low temperature threshold value, the
- 'iemConfigProbeLowTempThreshold' OID, and the value of the
- 'iemPConfigrobeLowTempEnable' OID is enabled. Otherwise it will show
- noViolation(1). If the 'iemConfigProbeLowTempEnable' OID is disabled,
- this OID will show disabled(3)."
- ::= { iemStatusProbesEntry 8 }
- iemStatusProbeHighHumidViolation OBJECT-TYPE
- SYNTAX INTEGER {
- noViolation(1),
- highHumidViolation(2),
- disabled(3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The high humidity violation status of the probe humidity
- reading. This OID will show a highTempViolation(2)
- if the current humidity reading shown in the
- 'iemStatusProbeCurrentHumid' OID is greater than or equal to
- the high humidity threshold value, the
- 'iemConfigProbeHighHumidThreshold' OID, and the value of the
- 'iemConfigProbeHighHumidEnable' OID is enabled. Otherwise it will
- show noViolation(1). If the 'iemConfigProbeHighHumidEnable' OID is
- disabled, this OID will show disabled(3)."
- ::= { iemStatusProbesEntry 9 }
- iemStatusProbeLowHumidViolation OBJECT-TYPE
- SYNTAX INTEGER {
- noViolation(1),
- lowHumidViolation(2),
- disabled(3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The low humidity violation status of the probe humidity
- reading. This OID will show a lowTempViolation(2)
- if the current humidity reading shown in the
- 'iemStatusProbeCurrentHumid' OID is less than or equal to
- the low humidity threshold value, the
- 'iemConfigProbeLowHumidThreshold' OID, and the value of the
- 'iemConfigProbeLowHumidEnable' OID is enabled. Otherwise it will
- show noViolation(1). If the 'iemConfigProbeLowHumidEnable' OID is
- disabled, this OID will show disabled(3)."
- ::= { iemStatusProbesEntry 10 }
- iemStatusProbeMaxTempViolation OBJECT-TYPE
- SYNTAX INTEGER {
- noViolation(1),
- maxTempViolation(2),
- disabled(3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The max temperature violation status of the probe
- temperature reading. This OID will show a maxTempViolation(2)
- if the current temperature reading shown in the
- 'iemStatusProbeCurrentTemp' OID is greater than or equal to
- the maximun temperature threshold value, the
- 'iemConfigProbeMaxTempThreshold' OID, and the value of the
- 'iemConfigProbeMaxTempEnable' OID is enabled. Otherwise it will show
- noViolation(1). If the 'iemConfigProbeMaxTempEnable' OID is disabled,
- this OID will show disabled(3)."
- ::= { iemStatusProbesEntry 11 }
- iemStatusProbeMinTempViolation OBJECT-TYPE
- SYNTAX INTEGER {
- noViolation(1),
- minTempViolation(2),
- disabled(3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The minimum temperature violation status of the probe
- temperature reading. This OID will show a minTempViolation(2)
- if the current temperature reading shown in the
- 'iemStatusProbeCurrentTemp' OID is less than or equal to
- the minimum temperature threshold value, the
- 'iemConfigProbeMinTempThreshold' OID, and the value of the
- 'iemConfigProbeMinTempEnable' OID is enabled. Otherwise it will show
- noViolation(1). If the 'iemConfigProbeMinTempEnable' OID is disabled,
- this OID will show disabled(3)."
- ::= { iemStatusProbesEntry 12 }
- iemStatusProbeMaxHumidViolation OBJECT-TYPE
- SYNTAX INTEGER {
- noViolation(1),
- maxHumidViolation(2),
- disabled(3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The maximum humidity violation status of the probe humidity
- reading. This OID will show a maxTempViolation(2)
- if the current humidity reading shown in the
- 'iemStatusProbeCurrentHumid' OID is greater than or equal to
- the maximum humidity threshold value, the
- 'iemConfigProbeMaxHumidThreshold' OID, and the value of the
- 'iemConfigProbeMaxHumidEnable' OID is enabled. Otherwise it will
- show noViolation(1). If the 'iemConfigProbeMaxHumidEnable' OID is
- disabled, this OID will show disabled(3)"
- ::= { iemStatusProbesEntry 13 }
- iemStatusProbeMinHumidViolation OBJECT-TYPE
- SYNTAX INTEGER {
- noViolation(1),
- minHumidViolation(2),
- disabled(3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The minimum humidity violation status of the probe humidity
- reading. This OID will show a minTempViolation(2)
- if the current humidity reading shown in the
- 'iemStatusProbeCurrentHumid' OID is less than or equal to
- the minimum humidity threshold value, the
- 'iemConfigProbeMinHumidThreshold' OID, and the value of the
- 'iemConfigProbeMinHumidEnable' OID is enabled. Otherwise it will
- show noViolation(1). If the 'iemConfigProbeMinHumidEnable' OID is
- disabled, this OID will show disabled(3)."
- ::= { iemStatusProbesEntry 14 }
- iemStatusProbeLocation OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A descriptive location for the probe set by the user."
- ::= { iemStatusProbesEntry 15 }
- iemStatusContactsNumContacts OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of contacts supported on the
- Environmental Monitor."
- ::= { iemStatus 3 }
- iemStatusContactsTable OBJECT-TYPE
- SYNTAX SEQUENCE OF IemStatusContactsEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "A list of contacts supported by the Environmental Monitor
- and their status."
- ::= { iemStatus 4 }
- iemStatusContactsEntry OBJECT-TYPE
- SYNTAX IemStatusContactsEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The status of the contact."
- INDEX { iemStatusContactNumber }
- ::= { iemStatusContactsTable 1 }
- IemStatusContactsEntry ::=
- SEQUENCE {
- iemStatusContactNumber
- INTEGER,
- iemStatusContactName
- DisplayString,
- iemStatusContactStatus
- INTEGER
- }
- iemStatusContactNumber OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index of the Environmental Monitor contact."
- ::= { iemStatusContactsEntry 1 }
- iemStatusContactName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A descriptive name for the Environmental Monitor contact
- set by the user, denoting its location or purpose."
- ::= { iemStatusContactsEntry 2 }
- iemStatusContactStatus OBJECT-TYPE
- SYNTAX INTEGER {
- noFault(1),
- fault(2),
- disabled(3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The status of the Environmental Monitor contact. The status
- will show noFault(1) if the contact is in the normal state
- and the 'iemConfigContactEnable' OID is enabled. The status will
- show a fault(2) if the contact is faulted and the
- 'iemConfigContactEnable' OID is enabled. If the
- 'iemConfigContactEnable' OID is disabled, the status will show
- disabled(3)."
- ::= { iemStatusContactsEntry 3 }
- iemStatusRelaysNumRelays OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of output relays supported on the
- Environmental Monitor."
- ::= { iemStatus 6 }
- iemStatusRelaysTable OBJECT-TYPE
- SYNTAX SEQUENCE OF IemStatusRelaysEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "A list of output relays supported by the
- Environmental Monitor and their status."
- ::= { iemStatus 7 }
- iemStatusRelaysEntry OBJECT-TYPE
- SYNTAX IemStatusRelaysEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The status of the relay."
- INDEX { iemStatusRelayNumber }
- ::= { iemStatusRelaysTable 1 }
- IemStatusRelaysEntry ::=
- SEQUENCE {
- iemStatusRelayNumber
- INTEGER,
- iemStatusRelayName
- DisplayString,
- iemStatusRelayStatus
- INTEGER
- }
- iemStatusRelayNumber OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index of the output relay."
- ::= { iemStatusRelaysEntry 1 }
- iemStatusRelayName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A descriptive name for the output relay set by the
- user, denoting its location or purpose."
- ::= { iemStatusRelaysEntry 2 }
- iemStatusRelayStatus OBJECT-TYPE
- SYNTAX INTEGER {
- faultState(1),
- normalState(2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The status of the output relay, either faultState(1) or
- normalState(2)."
- ::= { iemStatusRelaysEntry 3 }
- -- Environmental Management System (EMS)
- -- EMS IDENT
- emsIdentEMSName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the
- device. "
- ::= { emsIdent 1 }
- emsIdentProductNumber OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the model number of
- the device. This value is set at the factory."
- ::= { emsIdent 2 }
- emsIdentFirmwareRev OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The firmware revision of the device."
- ::= { emsIdent 3 }
- emsIdentHardwareRev OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The hardware revision of the device.
- This value is set at the factory."
- ::= { emsIdent 4 }
- emsIdentDateOfManufacture OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The date when the device was manufactured in mm/dd/yyyy format.
- This value is set at the factory. "
- ::= { emsIdent 5 }
-
- emsIdentSerialNumber OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the serial number of
- the device. This value is set at the factory."
- ::= { emsIdent 6 }
- -- EMS CONTROL
- -- EMS OUTPUT RELAY CONTROL STATUS TABLE
- emsOutputRelayControlTable OBJECT-TYPE
- SYNTAX SEQUENCE OF EmsOutputRelayControlEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for control of individual output relays. The number of
- entries is contained in the emsStatusOutputRelayCount OID."
- ::= { emsOutputRelayControl 1 }
- emsOutputRelayControlEntry OBJECT-TYPE
- SYNTAX EmsOutputRelayControlEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The output relays to control."
- INDEX { emsOutputRelayControlOutputRelayIndex }
- ::= { emsOutputRelayControlTable 1 }
- EmsOutputRelayControlEntry ::=
- SEQUENCE {
- emsOutputRelayControlOutputRelayIndex INTEGER,
- emsOutputRelayControlOutputRelayName DisplayString,
- emsOutputRelayControlOutputRelayCommand INTEGER
- }
- emsOutputRelayControlOutputRelayIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the output relay entry."
- ::= { emsOutputRelayControlEntry 1 }
-
- emsOutputRelayControlOutputRelayName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The name of the output relay.
- This OID is provided for informational purposes only."
- ::= { emsOutputRelayControlEntry 2 }
- emsOutputRelayControlOutputRelayCommand OBJECT-TYPE
- SYNTAX INTEGER {
- immediateCloseEMS (1),
- immediateOpenEMS (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Getting this variable will return the output relay state. If
- the output relay is closed, the immediateCloseEMS (1) value will be returned.
- If the output relay is open, the immediateOpenEMS (2) value will be
- returned.
-
- Setting this variable to immediateCloseEMS (1) will immediately close the relay.
-
- Setting this variable to immediateOpenEMS (2) will immediately open the relay."
- ::= { emsOutputRelayControlEntry 3 }
- -- EMS OUTLET CONTROL TABLE
-
- emsOutletControlTable OBJECT-TYPE
- SYNTAX SEQUENCE OF EmsOutletControlEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for control of individual outlet switches. The number of
- entries is contained in the emsStatusOutletCount OID."
- ::= { emsOutletControl 1 }
- emsOutletControlEntry OBJECT-TYPE
- SYNTAX EmsOutletControlEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The outlets to control."
- INDEX { emsOutletControlOutletIndex }
- ::= { emsOutletControlTable 1 }
- EmsOutletControlEntry ::=
- SEQUENCE {
- emsOutletControlOutletIndex INTEGER,
- emsOutletControlOutletName DisplayString,
- emsOutletControlOutletCommand INTEGER
- }
- emsOutletControlOutletIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the outlet entry."
- ::= { emsOutletControlEntry 1 }
-
- emsOutletControlOutletName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The name of the outlet.
- This OID is provided for informational purposes only."
- ::= { emsOutletControlEntry 2 }
- emsOutletControlOutletCommand OBJECT-TYPE
- SYNTAX INTEGER {
- immediateOnEMS (1),
- immediateOffEMS (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Getting this variable will return the outlet state. If
- the outlet is on, the immediateOnEMS (1) value will be returned.
- If the outlet is off, the immediateOffEMS (2) value will be
- returned.
-
- Setting this variable to immediateOnEMS (1) will immediately turn the outlet on.
-
- Setting this variable to immediateOffEMS (2) will immediately turn the outlet off."
- ::= { emsOutletControlEntry 3 }
- -- EMS SENSOR CONTROL TABLE
- emsSensorControlTable OBJECT-TYPE
- SYNTAX SEQUENCE OF EMSSensorControlEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for control/reset of individual sensors. The number of
- entries is contained in the emsStatusSensorCount OID."
- ::= { emsSensorControl 1 }
- emsSensorControlEntry OBJECT-TYPE
- SYNTAX EMSSensorControlEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The sensors to control/reset."
- INDEX { emsSensorControlSensorIndex }
- ::= { emsSensorControlTable 1 }
- EMSSensorControlEntry ::=
- SEQUENCE {
- emsSensorControlSensorIndex INTEGER,
- emsSensorControlSensorSystemName DisplayString,
- emsSensorControlSensorUserName DisplayString,
- emsSensorControlSensorCommand INTEGER
- }
- emsSensorControlSensorIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the sensor entry."
- ::= { emsSensorControlEntry 1 }
-
- emsSensorControlSensorSystemName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The system name of the sensor. This describes the hardware system
- intent of this sensor."
- ::= { emsSensorControlEntry 2 }
- emsSensorControlSensorUserName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The name of the sensor as given by the system user."
- ::= { emsSensorControlEntry 3 }
-
- emsSensorControlSensorCommand OBJECT-TYPE
- SYNTAX INTEGER {
- noCommandEMS (1),
- resetCommandEMS (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Getting this variable will return noCommandEMS(1).
-
- Setting this variable to resetCommandEMS(2) will issue a reset command to the
- sensor. Some sensors cannot be manually reset and will not be affected
- by this command."
- ::= { emsSensorControlEntry 4 }
- -- EMS ALARM DEVICE CONTROL TABLE
-
- emsAlarmDeviceControlTable OBJECT-TYPE
- SYNTAX SEQUENCE OF EmsAlarmDeviceControlEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for control of individual alarm devices.
- Note: Some alarm devices are not controllable. The number of
- entries is contained in the emsStatusAlarmDeviceCount OID."
- ::= { emsAlarmDeviceControl 1 }
- emsAlarmDeviceControlEntry OBJECT-TYPE
- SYNTAX EmsAlarmDeviceControlEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The alarm devices to control."
- INDEX { emsAlarmDeviceControlDeviceIndex }
- ::= { emsAlarmDeviceControlTable 1 }
- EmsAlarmDeviceControlEntry ::=
- SEQUENCE {
- emsAlarmDeviceControlDeviceIndex INTEGER,
- emsAlarmDeviceControlDeviceName DisplayString,
- emsAlarmDeviceControlDeviceCommand INTEGER
- }
- emsAlarmDeviceControlDeviceIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the alarm device entry."
- ::= { emsAlarmDeviceControlEntry 1 }
-
- emsAlarmDeviceControlDeviceName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The name of the alarm device.
- This OID is provided for informational purposes only."
- ::= { emsAlarmDeviceControlEntry 2 }
- emsAlarmDeviceControlDeviceCommand OBJECT-TYPE
- SYNTAX INTEGER {
- alarmDeviceOnEMS (1),
- alarmDeviceOffEMS (2),
- alarmDeviceNotInstalledEMS (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Getting this variable will return the device state. If
- the device is active, the alarmDeviceOnEMS (1) value will be returned.
- If the device is inactive, the alarmDeviceOffEMS (2) value will be
- returned. If the device is not installed, the
- alarmDeviceNotInstalledEMS (3) value will be returned.
-
- Actions resulting from setting this variable are device-dependent.
- Setting this variable to alarmDeviceOnEMS (1) will turn that device (ex. Beacon) on.
- Setting this variable to alarmDeviceOffEMS (2) will turn that device off."
- ::= { emsAlarmDeviceControlEntry 3 }
- -- EMS CONFIG
- emsConfigName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The name of the device."
- ::= { emsConfig 1 }
- emsConfigCheckLogLight OBJECT-TYPE
- SYNTAX INTEGER {
- lightDisabled (1),
- lightOnInformational (2),
- lightOnWarning (3),
- lightOnSevere (4)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The setting of this OID determines the level of event that will
- trigger the check-log light on the EMS. This is not available on the EMU2.
- lightDisabled (1) disables the check-log light.
- lightOnInformational (2) lights check-log for any event of
- informational severity or above.
- lightOnWarning (3) lights check-log for any event of
- warning severity or above.
- lightOnSevere (4) lights check-log for any event of severe severity."
- ::= { emsConfig 2 }
-
- -- EMS PROBE CONFIG TABLE
- emsProbeConfigTable OBJECT-TYPE
- SYNTAX SEQUENCE OF EMSProbeConfigEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for configuration of individual probes. The number of
- entries is contained in the emsStatusProbeCount OID."
- ::= { emsProbeConfig 1 }
- emsProbeConfigEntry OBJECT-TYPE
- SYNTAX EMSProbeConfigEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The probes to configure."
- INDEX { emsProbeConfigProbeIndex }
- ::= { emsProbeConfigTable 1 }
- EMSProbeConfigEntry ::=
- SEQUENCE {
- emsProbeConfigProbeIndex INTEGER,
- emsProbeConfigProbeName DisplayString,
- emsProbeConfigProbeHighTempThresh INTEGER,
- emsProbeConfigProbeLowTempThresh INTEGER,
- emsProbeConfigProbeHighHumidityThresh INTEGER,
- emsProbeConfigProbeLowHumidityThresh INTEGER,
- emsProbeConfigProbeMaxTempThresh INTEGER,
- emsProbeConfigProbeMinTempThresh INTEGER,
- emsProbeConfigProbeDeltaTemp INTEGER,
- emsProbeConfigProbeMaxHumidityThresh INTEGER,
- emsProbeConfigProbeMinHumidityThresh INTEGER,
- emsProbeConfigProbeDeltaHumidity INTEGER,
- emsProbeConfigProbeSTIncTempVariance INTEGER,
- emsProbeConfigProbeSTIncTempTime INTEGER,
- emsProbeConfigProbeSTDecTempVariance INTEGER,
- emsProbeConfigProbeSTDecTempTime INTEGER,
- emsProbeConfigProbeLTIncTempVariance INTEGER,
- emsProbeConfigProbeLTIncTempTime INTEGER,
- emsProbeConfigProbeLTDecTempVariance INTEGER,
- emsProbeConfigProbeLTDecTempTime INTEGER
- }
- emsProbeConfigProbeIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the probe entry."
- ::= { emsProbeConfigEntry 1 }
-
- emsProbeConfigProbeName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The name of the probe."
- ::= { emsProbeConfigEntry 2 }
- emsProbeConfigProbeHighTempThresh OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Probe high temperature threshold.
- Values are represented in whole number degrees.
- Units are displayed in the scale shown in
- the emsStatusSysTempUnits OID (Celsius or Fahrenheit)."
- ::= { emsProbeConfigEntry 3 }
-
- emsProbeConfigProbeLowTempThresh OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Probe low temperature threshold.
- Values are represented in whole number degrees.
- Units are displayed in the scale shown in
- the emsStatusSysTempUnits OID (Celsius or Fahrenheit)."
- ::= { emsProbeConfigEntry 4 }
-
- emsProbeConfigProbeHighHumidityThresh OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Probe high humidity threshold.
- Values are represented in whole number percentage."
- ::= { emsProbeConfigEntry 5 }
-
- emsProbeConfigProbeLowHumidityThresh OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Probe low humidity threshold.
- Values are represented in whole number percentage."
- ::= { emsProbeConfigEntry 6 }
- emsProbeConfigProbeMaxTempThresh OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Probe maximum temperature threshold.
- Values are represented in whole number degrees.
- Units are displayed in the scale shown in
- the emsStatusSysTempUnits OID (Celsius or Fahrenheit)."
- ::= { emsProbeConfigEntry 7 }
-
- emsProbeConfigProbeMinTempThresh OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Probe minimum temperature threshold.
- Values are represented in whole number degrees.
- Units are displayed in the scale shown in
- the emsStatusSysTempUnits OID (Celsius or Fahrenheit)."
- ::= { emsProbeConfigEntry 8 }
-
- emsProbeConfigProbeDeltaTemp OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Probe delta temperature.
- Values are represented in whole number degrees.
- Units are displayed in the scale shown in
- the emsStatusSysTempUnits OID (Celsius or Fahrenheit)."
- ::= { emsProbeConfigEntry 9 }
-
- emsProbeConfigProbeMaxHumidityThresh OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Probe maximum humidity threshold.
- Values are represented in whole number percentage."
- ::= { emsProbeConfigEntry 10 }
-
- emsProbeConfigProbeMinHumidityThresh OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Probe minimum humidity threshold.
- Values are represented in whole number percentage."
- ::= { emsProbeConfigEntry 11 }
-
- emsProbeConfigProbeDeltaHumidity OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Probe delta humidity.
- Values are represented in whole number percentage."
- ::= { emsProbeConfigEntry 12 }
-
- emsProbeConfigProbeSTIncTempVariance OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Probe short-term increasing temperature variance used for rate of change alarms.
- Values are represented in whole number degrees.
- Units are displayed in the scale shown in
- the emsStatusSysTempUnits OID (Celsius or Fahrenheit)."
- ::= { emsProbeConfigEntry 13 }
-
- emsProbeConfigProbeSTIncTempTime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Probe short-term increasing temperature time used for rate of change alarms.
- Values are represented in whole number minutes."
- ::= { emsProbeConfigEntry 14 }
-
- emsProbeConfigProbeSTDecTempVariance OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Probe short-term decreasing temperature variance used for rate of change alarms.
- Values are represented in whole number degrees.
- Units are displayed in the scale shown in
- the emsStatusSysTempUnits OID (Celsius or Fahrenheit)."
- ::= { emsProbeConfigEntry 15 }
-
- emsProbeConfigProbeSTDecTempTime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Probe short-term decreasing temperature time used for rate of change alarms.
- Values are represented in whole number minutes."
- ::= { emsProbeConfigEntry 16 }
-
- emsProbeConfigProbeLTIncTempVariance OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Probe long-term increasing temperature variance used for rate of change alarms.
- Values are represented in whole number degrees.
- Units are displayed in the scale shown in
- the emsStatusSysTempUnits OID (Celsius or Fahrenheit)."
- ::= { emsProbeConfigEntry 17 }
-
- emsProbeConfigProbeLTIncTempTime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Probe long-term increasing temperature time used for rate of change alarms.
- Values are represented in whole number hours."
- ::= { emsProbeConfigEntry 18 }
-
- emsProbeConfigProbeLTDecTempVariance OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Probe long-term decreasing temperature variance used for rate of change alarms.
- Values are represented in whole number degrees.
- Units are displayed in the scale shown in
- the emsStatusSysTempUnits OID (Celsius or Fahrenheit)."
- ::= { emsProbeConfigEntry 19 }
-
- emsProbeConfigProbeLTDecTempTime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Probe long-term decreasing temperature time used for rate of change alarms.
- Values are represented in whole number hours."
- ::= { emsProbeConfigEntry 20 }
-
- -- EMS INPUT CONTACT CONFIG STATUS TABLE
- emsInputContactConfigTable OBJECT-TYPE
- SYNTAX SEQUENCE OF EMSInputContactConfigEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for configuration of individual input contacts. The number of
- entries is contained in the emsStatusInputContactCount OID."
- ::= { emsInputContactConfig 1 }
- emsInputContactConfigEntry OBJECT-TYPE
- SYNTAX EMSInputContactConfigEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The input contacts to configure."
- INDEX { emsInputContactConfigInputContactIndex }
- ::= { emsInputContactConfigTable 1 }
- EMSInputContactConfigEntry ::=
- SEQUENCE {
- emsInputContactConfigInputContactIndex INTEGER,
- emsInputContactConfigInputContactName DisplayString,
- emsInputContactConfigInputContactNormalState INTEGER
- }
- emsInputContactConfigInputContactIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the input contact entry."
- ::= { emsInputContactConfigEntry 1 }
-
- emsInputContactConfigInputContactName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The name of the input contact."
- ::= { emsInputContactConfigEntry 2 }
- emsInputContactConfigInputContactNormalState OBJECT-TYPE
- SYNTAX INTEGER {
- normallyClosedEMS (1),
- normallyOpenEMS (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Getting this variable will return the normal state of the input contact. If
- the normal state is closed, the normallyClosedEMS (1) value will be returned.
- If the normal state is closed, the normallyOpenEMS (2) value will be
- returned.
-
- Setting this variable will change the normal state of the input contact"
- ::= { emsInputContactConfigEntry 3 }
-
- -- EMS OUTPUT RELAY CONFIG STATUS TABLE
- emsOutputRelayConfigTable OBJECT-TYPE
- SYNTAX SEQUENCE OF EMSOutputRelayConfigEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for configuration of individual output relays. The number of
- entries is contained in the emsStatusOutputRelayCount OID."
- ::= { emsOutputRelayConfig 1 }
- emsOutputRelayConfigEntry OBJECT-TYPE
- SYNTAX EMSOutputRelayConfigEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The output relays to configure."
- INDEX { emsOutputRelayConfigOutputRelayIndex }
- ::= { emsOutputRelayConfigTable 1 }
- EMSOutputRelayConfigEntry ::=
- SEQUENCE {
- emsOutputRelayConfigOutputRelayIndex INTEGER,
- emsOutputRelayConfigOutputRelayName DisplayString,
- emsOutputRelayConfigOutputRelayNormalState INTEGER
- }
- emsOutputRelayConfigOutputRelayIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the output relay entry."
- ::= { emsOutputRelayConfigEntry 1 }
-
- emsOutputRelayConfigOutputRelayName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The name of the output relay."
- ::= { emsOutputRelayConfigEntry 2 }
- emsOutputRelayConfigOutputRelayNormalState OBJECT-TYPE
- SYNTAX INTEGER {
- normallyClosedEMS (1),
- normallyOpenEMS (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Getting this variable will return the normal state of the output relay. If
- the normal state is closed, the normallyClosedEMS (1) value will be returned.
- If the normal state is closed, the normallyOpenEMS (2) value will be
- returned.
-
- Setting this variable will change the normal state of the output relay"
- ::= { emsOutputRelayConfigEntry 3 }
-
- -- EMS OUTLET CONFIG TABLE
-
- emsOutletConfigTable OBJECT-TYPE
- SYNTAX SEQUENCE OF EMSOutletConfigEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for configuration of individual outlets. The number of
- entries is contained in the emsStatusOutletCount OID."
- ::= { emsOutletConfig 1 }
- emsOutletConfigEntry OBJECT-TYPE
- SYNTAX EMSOutletConfigEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The outlets to configure."
- INDEX { emsOutletConfigOutletIndex }
- ::= { emsOutletConfigTable 1 }
- EMSOutletConfigEntry ::=
- SEQUENCE {
- emsOutletConfigOutletIndex INTEGER,
- emsOutletConfigOutletName DisplayString,
- emsOutletConfigOutletNormalState INTEGER
- }
- emsOutletConfigOutletIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the outlet entry."
- ::= { emsOutletConfigEntry 1 }
-
- emsOutletConfigOutletName OBJECT-TYPE
- SYNTAX DisplayString ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The name of the outlet."
- ::= { emsOutletConfigEntry 2 }
- emsOutletConfigOutletNormalState OBJECT-TYPE
- SYNTAX INTEGER {
- normallyOnEMS (1),
- normallyOffEMS (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Getting this variable will return the normal state of the outlet. If
- the normal state is on, the normallyOnEMS (1) value will be returned.
- If the normal state is off, the normallyOffEMS (2) value will be
- returned.
-
- Setting this variable will change the normal state of the outlet"
- ::= { emsOutletConfigEntry 3 }
-
- -- EMS SENSOR CONFIG TABLE
- emsSensorConfigTable OBJECT-TYPE
- SYNTAX SEQUENCE OF EMSSensorConfigEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for configuration of individual sensors. The number of
- entries is contained in the emsStatusSensorCount OID."
- ::= { emsSensorConfig 1 }
- emsSensorConfigEntry OBJECT-TYPE
- SYNTAX EMSSensorConfigEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The sensors to configure."
- INDEX { emsSensorConfigSensorIndex }
- ::= { emsSensorConfigTable 1 }
- EMSSensorConfigEntry ::=
- SEQUENCE {
- emsSensorConfigSensorIndex INTEGER,
- emsSensorConfigSensorSystemName DisplayString,
- emsSensorConfigSensorUserName DisplayString,
- emsSensorConfigSensorNormalState INTEGER,
- emsSensorConfigSensorAlarmDelay INTEGER
- }
- emsSensorConfigSensorIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the sensor entry."
- ::= { emsSensorConfigEntry 1 }
-
- emsSensorConfigSensorSystemName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The system name of the sensor. This describes the hardware system
- intent of this sensor."
- ::= { emsSensorConfigEntry 2 }
- emsSensorConfigSensorUserName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The name of the sensor as given by the system user."
- ::= { emsSensorConfigEntry 3 }
-
- emsSensorConfigSensorNormalState OBJECT-TYPE
- SYNTAX INTEGER {
- normallyClosedEMS (1),
- normallyOpenEMS (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Getting this variable will return the normal state of the sensor. If
- the normal state is closed, the normallyClosedEMS (1) value will be returned.
- If the normal state is closed, the normallyOpenEMS (2) value will be
- returned.
-
- Setting this variable will change the normal state of the sensor. Note:
- Only the AUX sensor in the EMS has a configurable Normal State"
- ::= { emsSensorConfigEntry 4 }
- emsSensorConfigSensorAlarmDelay OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The delay (in seconds) after a sensor detects an alarm condition before the
- condition is reported."
- ::= { emsSensorConfigEntry 5 }
- -- EMS STATUS
- --- EMS MASTER status
- emsStatusEMSName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the
- device. "
- ::= { emsStatus 1 }
- emsStatusCommStatus OBJECT-TYPE
- SYNTAX INTEGER {
- noComm(1),
- comm(2),
- commLost(3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The communication status between the agent
- and the device.
-
- noComm(1), Communication has never been established.
- comm(2), Communication has been established.
- commLost(3), Communication was established, but was lost."
- ::= { emsStatus 2 }
- emsStatusProbeCount OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The total number of T/H probes (both local and remote) that
- is supported by this device."
- ::= { emsStatus 3 }
- emsStatusInputContactCount OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The total number of Input Contacts that
- is supported by this device."
- ::= { emsStatus 4 }
- emsStatusOutputRelayCount OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The total number of Output Relays that
- is supported by this device."
- ::= { emsStatus 5 }
- emsStatusOutletCount OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The total number of AC Outlets that
- is supported by this device."
- ::= { emsStatus 6 }
- emsStatusSensorCount OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The total number of Sensors that
- is supported by this device."
- ::= { emsStatus 7 }
-
- emsStatusAlinkAruDeviceCount OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The total number of remote Aru's supported by this device."
- ::= { emsStatus 8 }
- emsStatusAlinkProbeDeviceCount OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The total number of remote T/H probes supported by this device."
- ::= { emsStatus 9 }
- emsStatusAlarmDeviceCount OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of alarm devices supported by this device."
- ::= { emsStatus 10 }
- emsStatusSysTempUnits OBJECT-TYPE
- SYNTAX INTEGER {
- celsius(1),
- fahrenheit(2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The temperature scale used to display the temperature
- in the system, Celsius(1) or Fahrenheit(2).
- This setting is based on the system preferences
- configuration in the agent."
- ::= { emsStatus 11 }
- emsStatusCheckLogLight OBJECT-TYPE
- SYNTAX INTEGER {
- lightOff (1),
- lightOn (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The status of the check-log light on the device.
- For the EMU2, this will always indicate lightOff(1).
- lightOff (1) indicates the light is off (no new log entries).
- lightOn (2) indicates the light is on (new log entries present)."
- ::= { emsStatus 12 }
- emsStatusHardwareStatus OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The status of the EMS hardware. This integer should be interpreted
- as a bit map, with each bit representing the presence or absence of
- a specific hardware error condition.
-
- 0 indicates there are no error conditions detected in the EMS hardware.
- 1 indicates a Current Limit error condition related to the Alink port.
- 2 indicates incorrect hardware is plugged into an EMS port.
- 3 indicates that both of these error conditions are present."
- ::= { emsStatus 13 }
- -- EMS PROBE STATUS TABLE
- emsProbeStatusTable OBJECT-TYPE
- SYNTAX SEQUENCE OF EMSProbeStatusEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for access of individual probes. The number of
- entries is contained in the emsStatusProbeCount OID."
- ::= { emsProbeStatus 1 }
- emsProbeStatusEntry OBJECT-TYPE
- SYNTAX EMSProbeStatusEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The probes to access."
- INDEX { emsProbeStatusProbeIndex }
- ::= { emsProbeStatusTable 1 }
- EMSProbeStatusEntry ::=
- SEQUENCE {
- emsProbeStatusProbeIndex INTEGER,
- emsProbeStatusProbeName DisplayString,
- emsProbeStatusProbeTemperature INTEGER,
- emsProbeStatusProbeHighTempThresh INTEGER,
- emsProbeStatusProbeLowTempThresh INTEGER,
- emsProbeStatusProbeHumidity INTEGER,
- emsProbeStatusProbeHighHumidityThresh INTEGER,
- emsProbeStatusProbeLowHumidityThresh INTEGER,
- emsProbeStatusProbeSerialNumber DisplayString,
- emsProbeStatusProbeCommStatus INTEGER,
- emsProbeStatusProbeAlarmStatus INTEGER,
- emsProbeStatusProbeMaxTempThresh INTEGER,
- emsProbeStatusProbeMinTempThresh INTEGER,
- emsProbeStatusProbeMaxHumidityThresh INTEGER,
- emsProbeStatusProbeMinHumidityThresh INTEGER
- }
- emsProbeStatusProbeIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the probe entry."
- ::= { emsProbeStatusEntry 1 }
-
- emsProbeStatusProbeName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The name of the probe."
- ::= { emsProbeStatusEntry 2 }
- emsProbeStatusProbeTemperature OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Probe temperature reading.
- Values are represented in whole number degrees.
- Units are displayed in the scale shown in
- the emsStatusSysTempUnits OID (Celsius or Fahrenheit)."
- ::= { emsProbeStatusEntry 3 }
- emsProbeStatusProbeHighTempThresh OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Probe high temperature threshold.
- Values are represented in whole number degrees.
- Units are displayed in the scale shown in
- the emsStatusSysTempUnits OID (Celsius or Fahrenheit)."
- ::= { emsProbeStatusEntry 4 }
-
- emsProbeStatusProbeLowTempThresh OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Probe low temperature threshold.
- Values are represented in whole number degrees.
- Units are displayed in the scale shown in
- the emsStatusSysTempUnits OID (Celsius or Fahrenheit)."
- ::= { emsProbeStatusEntry 5 }
-
- emsProbeStatusProbeHumidity OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Probe humidity reading.
- Values are represented in whole number percentage."
- ::= { emsProbeStatusEntry 6 }
- emsProbeStatusProbeHighHumidityThresh OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Probe high humidity threshold.
- Values are represented in whole number percentage."
- ::= { emsProbeStatusEntry 7 }
-
- emsProbeStatusProbeLowHumidityThresh OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Probe low humidity threshold.
- Values are represented in whole number percentage."
- ::= { emsProbeStatusEntry 8 }
- emsProbeStatusProbeSerialNumber OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A label indicating the type (Local[L] or Remote[R]) and Number
- of the probe. For example, the first local probe would be L1 and
- the third remote probe would be R3."
- ::= { emsProbeStatusEntry 9 }
- emsProbeStatusProbeCommStatus OBJECT-TYPE
- SYNTAX INTEGER {
- commsNeverDiscovered(1),
- commsEstablished(2),
- commsLost(3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- " The state of communications to the probe.
- commNeverDiscovered(1) indicates there has never been communications with this device.
- commsEstablished(2) indicates communication is normal and active with this device.
- commsLost(3) indicates communication had been established, but is no longer."
- ::= { emsProbeStatusEntry 10 }
- emsProbeStatusProbeAlarmStatus OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The alarm status of the probe. This integer should be interpreted
- as a bit map, with each bit representing the presence or absence of
- the specific alarm conditions listed below. The bit will be '1' if
- the condition is present, and '0' if the condition is not present.
-
- Bit Hex. Value Description
- 1 0x0001 Maximum temperature exceeded.
- 2 0x0002 High temperature exceeded.
- 3 0x0004 Low temperature exceeded.
- 4 0x0008 Minimum temperature exceeded.
- 5 0x0010 Short-term increasing temperature rate exceeded.
- 6 0x0020 Short-term decreasing temperature rate exceeded.
- 7 0x0040 Long-term increasing temperature rate exceeded.
- 8 0x0080 Long-term decreasing temperature rate exceeded.
- 9 0x0100 Maximum humidity exceeded.
- 10 0x0200 High humidity exceeded.
- 11 0x0400 Low humidity exceeded.
- 12 0x0800 Minimum humidity exceeded."
- ::= { emsProbeStatusEntry 11 }
- emsProbeStatusProbeMaxTempThresh OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Probe maximum temperature threshold.
- Values are represented in whole number degrees.
- Units are displayed in the scale shown in
- the emsStatusSysTempUnits OID (Celsius or Fahrenheit)."
- ::= { emsProbeStatusEntry 12 }
-
- emsProbeStatusProbeMinTempThresh OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Probe minimum temperature threshold.
- Values are represented in whole number degrees.
- Units are displayed in the scale shown in
- the emsStatusSysTempUnits OID (Celsius or Fahrenheit)."
- ::= { emsProbeStatusEntry 13 }
-
- emsProbeStatusProbeMaxHumidityThresh OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Probe maximum humidity threshold.
- Values are represented in whole number percentage."
- ::= { emsProbeStatusEntry 14 }
-
- emsProbeStatusProbeMinHumidityThresh OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Probe minimum humidity threshold.
- Values are represented in whole number percentage."
- ::= { emsProbeStatusEntry 15 }
-
- -- EMS INPUT CONTACT STATUS TABLE
- emsInputContactStatusTable OBJECT-TYPE
- SYNTAX SEQUENCE OF EMSInputContactStatusEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for access of individual input contacts. The number of
- entries is contained in the emsStatusInputContactCount OID."
- ::= { emsInputContactStatus 1 }
- emsInputContactStatusEntry OBJECT-TYPE
- SYNTAX EMSInputContactStatusEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The input contacts to access."
- INDEX { emsInputContactStatusInputContactIndex }
- ::= { emsInputContactStatusTable 1 }
- EMSInputContactStatusEntry ::=
- SEQUENCE {
- emsInputContactStatusInputContactIndex INTEGER,
- emsInputContactStatusInputContactName DisplayString,
- emsInputContactStatusInputContactState INTEGER,
- emsInputContactStatusInputContactNormalState INTEGER
- }
- emsInputContactStatusInputContactIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the input contact entry."
- ::= { emsInputContactStatusEntry 1 }
-
- emsInputContactStatusInputContactName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The name of the input contact."
- ::= { emsInputContactStatusEntry 2 }
-
- emsInputContactStatusInputContactState OBJECT-TYPE
- SYNTAX INTEGER {
- contactClosedEMS (1),
- contactOpenEMS (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this variable will return the state of the input contact. If
- the input contact is closed, the contactClosedEMS (1) value will be returned.
- If the input contact state is open, the contactOpenEMS (2) value will be
- returned. "
-
- ::= { emsInputContactStatusEntry 3 }
- emsInputContactStatusInputContactNormalState OBJECT-TYPE
- SYNTAX INTEGER {
- normallyClosedEMS (1),
- normallyOpenEMS (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this variable will return the normal state of the input contact. If
- the normal state is closed, the normallyClosedEMS (1) value will be returned.
- If the normal state is open, the normallyOpenEMS (2) value will be
- returned. "
-
- ::= { emsInputContactStatusEntry 4 }
- -- EMS OUTPUT RELAY STATUS TABLE
- emsOutputRelayStatusTable OBJECT-TYPE
- SYNTAX SEQUENCE OF EMSOutputRelayStatusEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for access of individual output relays. The number of
- entries is contained in the emsStatusOutputRelayCount OID."
- ::= { emsOutputRelayStatus 1 }
- emsOutputRelayStatusEntry OBJECT-TYPE
- SYNTAX EMSOutputRelayStatusEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The output relays to access."
- INDEX { emsOutputRelayStatusOutputRelayIndex }
- ::= { emsOutputRelayStatusTable 1 }
- EMSOutputRelayStatusEntry ::=
- SEQUENCE {
- emsOutputRelayStatusOutputRelayIndex INTEGER,
- emsOutputRelayStatusOutputRelayName DisplayString,
- emsOutputRelayStatusOutputRelayState INTEGER,
- emsOutputRelayStatusOutputRelayNormalState INTEGER
- }
- emsOutputRelayStatusOutputRelayIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the output relay entry."
- ::= { emsOutputRelayStatusEntry 1 }
-
- emsOutputRelayStatusOutputRelayName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The name of the output relay."
- ::= { emsOutputRelayStatusEntry 2 }
- emsOutputRelayStatusOutputRelayState OBJECT-TYPE
- SYNTAX INTEGER {
- relayClosedEMS (1),
- relayOpenEMS (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this variable will return the state of the output relay. If
- the output relay is closed, the relayClosedEMS (1) value will be returned.
- If the output relay is open, the relayOpenEMS (2) value will be
- returned. "
-
- ::= { emsOutputRelayStatusEntry 3 }
- emsOutputRelayStatusOutputRelayNormalState OBJECT-TYPE
- SYNTAX INTEGER {
- normallyClosedEMS (1),
- normallyOpenEMS (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this variable will return the normal state of the output relay. If
- the normal state is closed, the normallyClosedEMS (1) value will be returned.
- If the normal state is open, the normallyOpenEMS (2) value will be
- returned. "
-
- ::= { emsOutputRelayStatusEntry 4 }
-
- -- EMS OUTLET STATUS TABLE
-
- emsOutletStatusTable OBJECT-TYPE
- SYNTAX SEQUENCE OF EMSOutletStatusEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for access of individual outlets. The number of
- entries is contained in the emsStatusOutletCount OID."
- ::= { emsOutletStatus 1 }
- emsOutletStatusEntry OBJECT-TYPE
- SYNTAX EMSOutletStatusEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The outlets to access."
- INDEX { emsOutletStatusOutletIndex }
- ::= { emsOutletStatusTable 1 }
- EMSOutletStatusEntry ::=
- SEQUENCE {
- emsOutletStatusOutletIndex INTEGER,
- emsOutletStatusOutletName DisplayString,
- emsOutletStatusOutletState INTEGER,
- emsOutletStatusOutletNormalState INTEGER
- }
- emsOutletStatusOutletIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the outlet entry."
- ::= { emsOutletStatusEntry 1 }
-
- emsOutletStatusOutletName OBJECT-TYPE
- SYNTAX DisplayString ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The name of the outlet."
- ::= { emsOutletStatusEntry 2 }
- emsOutletStatusOutletState OBJECT-TYPE
- SYNTAX INTEGER {
- outletOnEMS (1),
- outletOffEMS (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this variable will return the state of the outlet. If
- the outlet is on, the outletOnEMS (1) value will be returned.
- If the outlet is off, the outletOffEMS (2) value will be
- returned. "
-
- ::= { emsOutletStatusEntry 3 }
- emsOutletStatusOutletNormalState OBJECT-TYPE
- SYNTAX INTEGER {
- normallyOnEMS (1),
- normallyOffEMS (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this variable will return the normal state of the outlet. If
- the normal state is on, the normallyOnEMS (1) value will be returned.
- If the normal state is off, the normallyOffEMS (2) value will be
- returned. "
-
- ::= { emsOutletStatusEntry 4 }
- -- EMS ALARM DEVICE STATUS TABLE
-
- emsAlarmDeviceStatusTable OBJECT-TYPE
- SYNTAX SEQUENCE OF EMSAlarmDeviceStatusEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for access of individual alarm devices. The number of
- entries is contained in the emsStatusAlarmDeviceCount OID."
- ::= { emsAlarmDeviceStatus 1 }
- emsAlarmDeviceStatusEntry OBJECT-TYPE
- SYNTAX EMSAlarmDeviceStatusEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The alarm devices to access."
- INDEX { emsAlarmDeviceStatusDeviceIndex }
- ::= { emsAlarmDeviceStatusTable 1 }
- EMSAlarmDeviceStatusEntry ::=
- SEQUENCE {
- emsAlarmDeviceStatusDeviceIndex INTEGER,
- emsAlarmDeviceStatusDeviceName DisplayString,
- emsAlarmDeviceStatusDeviceState INTEGER
- }
- emsAlarmDeviceStatusDeviceIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the alarm device entry."
- ::= { emsAlarmDeviceStatusEntry 1 }
-
- emsAlarmDeviceStatusDeviceName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The name of the alarm device.
- This OID is provided for informational purposes only."
- ::= { emsAlarmDeviceStatusEntry 2 }
- emsAlarmDeviceStatusDeviceState OBJECT-TYPE
- SYNTAX INTEGER {
- alarmDeviceOnEMS (1),
- alarmDeviceOffEMS (2),
- alarmDeviceNotInstalledEMS (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this variable will return the device state. If
- the device is active, the alarmDeviceOnEMS (1) value will be returned.
- If the device is inactive, the alarmDeviceOffEMS (2) value will be
- returned. If the device is not installed, the
- alarmDeviceNotInstalledEMS (3) value will be returned."
- ::= { emsAlarmDeviceStatusEntry 3 }
-
- -- EMS SENSOR STATUS TABLE
- emsSensorStatusTable OBJECT-TYPE
- SYNTAX SEQUENCE OF EMSSensorStatusEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for access of individual sensors. The number of
- entries is contained in the emsStatusSensorCount OID."
- ::= { emsSensorStatus 1 }
- emsSensorStatusEntry OBJECT-TYPE
- SYNTAX EMSSensorStatusEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The sensors to access."
- INDEX { emsSensorStatusSensorIndex }
- ::= { emsSensorStatusTable 1 }
- EMSSensorStatusEntry ::=
- SEQUENCE {
- emsSensorStatusSensorIndex INTEGER,
- emsSensorStatusSensorSystemName DisplayString,
- emsSensorStatusSensorName DisplayString,
- emsSensorStatusSensorState INTEGER,
- emsSensorStatusSensorNormalState INTEGER,
- emsSensorStatusSensorAlarmDelay INTEGER
- }
- emsSensorStatusSensorIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the sensor entry."
- ::= { emsSensorStatusEntry 1 }
-
- emsSensorStatusSensorSystemName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The system name of the sensor. This describes the hardware system
- intent of this sensor."
- ::= { emsSensorStatusEntry 2 }
-
- emsSensorStatusSensorName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The name of the sensor as given by the system user."
- ::= { emsSensorStatusEntry 3 }
- emsSensorStatusSensorState OBJECT-TYPE
- SYNTAX INTEGER {
- sensorFaultedEMS (1),
- sensorOKEMS (2),
- sensorNotInstalledEMS (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this variable will return the sensor state. If the sensor is faulted,
- the sensorFaultedEMS (1) value will be returned.
- If the sensor is not faulted, the sensorOKEMS (2) value will be
- returned. If the sensor is not installed, the sensorNotInstalledEMS (3)
- value will be returned."
- ::= { emsSensorStatusEntry 4 }
-
- emsSensorStatusSensorNormalState OBJECT-TYPE
- SYNTAX INTEGER {
- normallyClosedEMS (1),
- normallyOpenEMS (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Getting this variable will return the normal state of the sensor. If
- the normal state is closed, the normallyClosedEMS (1) value will be returned.
- If the normal state is closed, the normallyOpenEMS (2) value will be
- returned."
- ::= { emsSensorStatusEntry 5 }
- emsSensorStatusSensorAlarmDelay OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The delay (in seconds) after a sensor detects an alarm condition before the
- condition is reported."
- ::= { emsSensorStatusEntry 6 }
-
- -- airFM AIR CONDITIONER IDENT
- airFMIdentName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the device."
- ::= { airFMIdent 1 }
-
- airFMIdentTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the airFMIdentTable. "
- ::= { airFMIdent 2 }
- airFMIdentTable OBJECT-TYPE
- SYNTAX SEQUENCE OF AirFMIdentEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting identification information
- from each module in the system. "
- ::= { airFMIdent 3 }
- airFMIdentEntry OBJECT-TYPE
- SYNTAX AirFMIdentEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The module to get information from."
- INDEX { airFMIdentModuleIndex }
- ::= { airFMIdentTable 1 }
- AirFMIdentEntry ::=
- SEQUENCE {
- airFMIdentModuleIndex INTEGER,
- airFMIdentModuleModelNumber DisplayString,
- airFMIdentModuleDateOfMfg DisplayString,
- airFMIdentModuleSerialNumber DisplayString,
- airFMIdentModuleFirmwareRev DisplayString,
- airFMIdentModuleHardwareRev DisplayString
- }
-
- airFMIdentModuleIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index of the module information."
- ::= { airFMIdentEntry 1 }
- airFMIdentModuleModelNumber OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the
- model number. "
- ::= { airFMIdentEntry 2 }
-
- airFMIdentModuleDateOfMfg OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the
- manufacture date. "
- ::= { airFMIdentEntry 3 }
-
- airFMIdentModuleSerialNumber OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the
- unit serial number. "
- ::= { airFMIdentEntry 4 }
-
- airFMIdentModuleFirmwareRev OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the
- firmware revision. "
- ::= { airFMIdentEntry 5 }
-
- airFMIdentModuleHardwareRev OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the
- hardware revision. "
- ::= { airFMIdentEntry 6 }
- airFMIdentLocation OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the
- location of the device. "
- ::= { airFMIdent 4 }
-
- airFMIdentContact OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the
- person to contact regarding the device. "
- ::= { airFMIdent 5 }
-
-
- -- airFM AIR CONDITIONER STATUS
- airFMStatusSystemOn OBJECT-TYPE
- SYNTAX INTEGER {
- statusOn (1),
- statusOff (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The operating state of the system.
- This OID has been deprecated in favor of
- airFMGroupSysStatus."
- ::= { airFMStatus 1 }
-
- airFMStatusSystemAverageRetTempC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The system average return air
- temperature in tenths of degrees Celsius.
- This OID has been deprecated in favor of
- airFMSysAvgReturnTempC."
- ::= { airFMStatus 2 }
-
- airFMStatusSystemAverageRetTempF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The system average return air
- temperature in tenths of degrees Fahrenheit.
- This OID has been deprecated in favor of
- airFMSysAvgReturnTempF."
- ::= { airFMStatus 3 }
-
- airFMStatusSystemAverageRetHum OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The system average return air
- humidity in tenths of percent RH.
- This OID has been deprecated in favor of
- airFMSysAvgReturnHum."
- ::= { airFMStatus 4 }
-
- airFMStatusSystemActionTempC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The system action air
- temperature in tenths of degrees Celsius.
- This OID has been deprecated in favor of
- airFMSysCtrlTempC."
- ::= { airFMStatus 5 }
-
- airFMStatusSystemActionTempF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The system action air
- temperature in tenths of degrees Fahrenheit.
- This OID has been deprecated in favor of
- airFMSysCtrlTempF."
- ::= { airFMStatus 6 }
-
- airFMStatusSystemActionHum OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The system action air humidity in tenths of percent RH.
- This OID has been deprecated in favor of
- airFMSysCtrlHum."
- ::= { airFMStatus 7 }
-
- airFMStatusSystemRemoteHighTempC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The system remote high air
- temperature in tenths of degrees Celsius.
- This OID has been deprecated in favor of
- airFMSysMaxRemoteTempC."
- ::= { airFMStatus 8 }
-
- airFMStatusSystemRemoteHighTempF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The system remote high air
- temperature in tenths of degrees Fahrenheit.
- This OID has been deprecated in favor of
- airFMSysMaxRemoteTempF."
- ::= { airFMStatus 9 }
-
- airFMStatusSystemRemoteAvgTempC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The system remote average air
- temperature in tenths of degrees Celsius.
- This OID has been deprecated in favor of
- airFMSysAvgRemoteTempC."
- ::= { airFMStatus 10 }
-
- airFMStatusSystemRemoteAvgTempF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The system remote average air
- temperature in tenths of degrees Fahrenheit.
- This OID has been deprecated in favor of
- airFMSysAvgRemoteTempF."
- ::= { airFMStatus 11 }
-
- airFMStatusSystemRemoteAvgHum OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The system remote average air
- humidity in tenths of percent RH.
- This OID has been deprecated in favor of
- airFMSysAvgRemoteHum."
- ::= { airFMStatus 12 }
-
- airFMStatusSystemRemoteLowTempC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The system remote low air
- temperature in tenths of degrees Celsius.
- This OID has been deprecated in favor of
- airFMSysMinRemoteTempC."
- ::= { airFMStatus 13 }
-
- airFMStatusSystemRemoteLowTempF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The system remote low air
- temperature in tenths of degrees Fahrenheit.
- This OID has been deprecated in favor of
- airFMSysMinRemoteTempF."
- ::= { airFMStatus 14 }
-
- airFMStatusSystemCoolingEnabled OBJECT-TYPE
- SYNTAX INTEGER {
- enabledYes (1),
- enabledNo (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The state of the system cooling
- function enable.
- This OID has been deprecated in favor of
- airFMSysCoolState."
- ::= { airFMStatus 15 }
-
- airFMStatusSystemReheatingEnabled OBJECT-TYPE
- SYNTAX INTEGER {
- enabledYes (1),
- enabledNo (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The state of the system reheating
- function enable.
- This OID has been deprecated in favor of
- airFMSysReheatState."
- ::= { airFMStatus 16 }
-
- airFMStatusSystemHumidifyEnabled OBJECT-TYPE
- SYNTAX INTEGER {
- enabledYes (1),
- enabledNo (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The state of the system humidify
- function enable.
- This OID has been deprecated in favor of
- airFMSysHumState."
- ::= { airFMStatus 17 }
-
- airFMStatusSystemDehumidifyEnabled OBJECT-TYPE
- SYNTAX INTEGER {
- enabledYes (1),
- enabledNo (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The state of the system dehumidify
- function enable.
- This OID has been deprecated in favor of
- airFMSysDehumState."
- ::= { airFMStatus 18 }
-
- airFMStatusModuleTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the airFMStatusModuleTable."
- ::= { airFMStatus 19 }
- airFMStatusModuleTable OBJECT-TYPE
- SYNTAX SEQUENCE OF AirFMStatusModuleEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting information from each module
- in the system."
- ::= { airFMStatus 20 }
- airFMStatusModuleEntry OBJECT-TYPE
- SYNTAX AirFMStatusModuleEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The module to get status from."
- INDEX { airFMStatusModuleIndex }
- ::= { airFMStatusModuleTable 1 }
- AirFMStatusModuleEntry ::=
- SEQUENCE {
- airFMStatusModuleIndex INTEGER,
- airFMStatusModuleOutputCapacity INTEGER,
- airFMStatusModuleSupplyTempC INTEGER,
- airFMStatusModuleSupplyTempF INTEGER,
- airFMStatusModuleSupplyHum INTEGER,
- airFMStatusModuleReturnTempC INTEGER,
- airFMStatusModuleReturnTempF INTEGER,
- airFMStatusModuleReturnHum INTEGER
- }
-
- airFMStatusModuleIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index of the module information."
- ::= { airFMStatusModuleEntry 1 }
- airFMStatusModuleOutputCapacity OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The module output capacity in kilowatts.
- This OID has been deprecated in favor of
- airFMModOutputCapacity."
- ::= { airFMStatusModuleEntry 2 }
-
- airFMStatusModuleSupplyTempC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The module supply air temperature in
- tenths of degrees Celsius.
- This OID has been deprecated in favor of
- airFMModSupplyTempC."
- ::= { airFMStatusModuleEntry 3 }
-
- airFMStatusModuleSupplyTempF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The module supply air temperature in
- tenths of degrees Fahrenheit.
- This OID has been deprecated in favor of
- airFMModSupplyTempF."
- ::= { airFMStatusModuleEntry 4 }
-
- airFMStatusModuleSupplyHum OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The module supply air humidity in tenths of percent RH.
- This OID has been deprecated in favor of
- airFMModSupplyHum."
- ::= { airFMStatusModuleEntry 5 }
-
- airFMStatusModuleReturnTempC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The module return air temperature in
- tenths of degrees Celsius.
- This OID has been deprecated in favor of
- airFMModReturnTempC."
- ::= { airFMStatusModuleEntry 6 }
-
- airFMStatusModuleReturnTempF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The module return air temperature in
- tenths of degrees Fahrenheit.
- This OID has been deprecated in favor of
- airFMModReturnTempF."
- ::= { airFMStatusModuleEntry 7 }
-
- airFMStatusModuleReturnHum OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The module return air humidity in tenths of percent RH.
- This OID has been deprecated in favor of
- airFMModReturnHum."
- ::= { airFMStatusModuleEntry 8 }
-
- -- airFM AIR CONDITIONER GROUP DATA
- airFMGroupSysStatus OBJECT-TYPE
- SYNTAX INTEGER {
- statusOnLine (1),
- statusIdle (2),
- statusLoadShare (3),
- statusOffLine (4),
- statusFailed (5),
- statusDisabled (6),
- statusUndefined (7)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The status of this system within the group."
- ::= { airFMGroup 1 }
-
- airFMGroupSysRuntime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of hours the system has been running."
- ::= { airFMGroup 2 }
- airFMGroupSysRole OBJECT-TYPE
- SYNTAX INTEGER {
- rolePrimary (1),
- roleBackup (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The role of this system within the group."
- ::= { airFMGroup 3 }
- -- airFM Group System Roles
- airFMGroupSysRolesTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the airFMGroupSysRolesTable. "
- ::= { airFMGroupSysRoles 1 }
- airFMGroupSysRolesTable OBJECT-TYPE
- SYNTAX SEQUENCE OF AirFMGroupSysRolesEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting information from each system
- in the group. "
- ::= { airFMGroupSysRoles 2 }
- airFMGroupSysRolesEntry OBJECT-TYPE
- SYNTAX AirFMGroupSysRolesEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The system to get status from."
- INDEX { airFMGroupSysIndex }
- ::= { airFMGroupSysRolesTable 1 }
- AirFMGroupSysRolesEntry ::=
- SEQUENCE {
- airFMGroupSysIndex INTEGER,
- airFMGroupSysRoleStatus INTEGER,
- airFMGroupSysPresentRole INTEGER,
- airFMGroupSysManualRoleSetting INTEGER,
- airFMGroupSysRunHours INTEGER,
- airFMGroupSysComm INTEGER,
- airFMGroupSysIPAddress IpAddress
- }
-
- airFMGroupSysIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index of the system information."
- ::= { airFMGroupSysRolesEntry 1 }
- airFMGroupSysRoleStatus OBJECT-TYPE
- SYNTAX INTEGER {
- reserved1 (1),
- reserved2 (2),
- onLine (3),
- idle (4),
- loadShare (5),
- failed (6),
- offLine (7)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The present mode of the System."
- ::= { airFMGroupSysRolesEntry 2 }
- airFMGroupSysPresentRole OBJECT-TYPE
- SYNTAX INTEGER {
- primary (1),
- backup (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The present role of the System in a Group."
- ::= { airFMGroupSysRolesEntry 3 }
- airFMGroupSysManualRoleSetting OBJECT-TYPE
- SYNTAX INTEGER {
- primary (1),
- backup (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The manual role setting of the System in a Group.
- Only applies if Role Assignment Method is set
- to static (Manually Assigned Roles)."
- ::= { airFMGroupSysRolesEntry 4 }
- airFMGroupSysRunHours OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The total number of hours the System has been
- contributing to environmental control."
- ::= { airFMGroupSysRolesEntry 5 }
- airFMGroupSysComm OBJECT-TYPE
- SYNTAX INTEGER {
- commLost (1),
- commEstablished (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Indicates whether a system is communicating with the
- other Systems in the Group."
- ::= { airFMGroupSysRolesEntry 6 }
- airFMGroupSysIPAddress OBJECT-TYPE
- SYNTAX IpAddress
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The IP Address of the System."
- ::= { airFMGroupSysRolesEntry 7 }
- airFMGroupSysRoleAssignment OBJECT-TYPE
- SYNTAX INTEGER {
- staticManual (1),
- dynamicAutomatic (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The method used to assign roles (i.e. Primary, Backup)
- to the Systems in a Group.
- staticManual: Manually assign Primary or Backup to
- regulate run hours across the Group.
- dynamicAutomatic: User indicates the number of Systems
- that will be assigned a primary role in this Group."
- ::= { airFMGroupSysRoles 3 }
- airFMGroupAutoRoleNumPrimary OBJECT-TYPE
- SYNTAX INTEGER {
- one (1),
- two (2),
- three (3),
- four (4)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The number of Systems assigned the 'primary' role in
- this Group. Only applies if Role Assignment Method
- is set to dynamic (Automatic Run Hour Balancing)."
- ::= { airFMGroupSysRoles 4 }
- -- airFM Group Config
- airFMGroupCfgName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the group name."
- ::= { airFMGroupCfg 1 }
- airFMGroupCfgNumSystems OBJECT-TYPE
- SYNTAX INTEGER {
- one (1),
- two (2),
- three (3),
- four (4)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The number of Systems in this Group."
- ::= { airFMGroupCfg 2 }
- airFMGroupCfgIdleBlower OBJECT-TYPE
- SYNTAX INTEGER {
- off (1),
- minimumSpeed (2),
- normalSpeed (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Blower behavior for backup Systems and Systems that
- have entered a failure mode."
- ::= { airFMGroupCfg 3 }
- airFMGroupCfgShutdownSmoke OBJECT-TYPE
- SYNTAX INTEGER {
- disable (1),
- enable (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "If enabled, all Systems in the Group will shut down
- if smoke is detected."
- ::= { airFMGroupCfg 4 }
- airFMGroupCfgShutdownFire OBJECT-TYPE
- SYNTAX INTEGER {
- disable (1),
- enable (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "If enabled, all Systems in the Group will shut down
- if fire is detected."
- ::= { airFMGroupCfg 5 }
- airFMGroupCfgFailoverCommLoss OBJECT-TYPE
- SYNTAX INTEGER {
- disable (1),
- enable (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Failover on Comm Loss enables an available backup
- System to run in place of a System that has lost
- communication with the Group."
- ::= { airFMGroupCfg 6 }
- airFMGroupCfgDmdFightStatus OBJECT-TYPE
- SYNTAX INTEGER {
- off (1),
- on (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Demand Fighting and Setpoint Sharing are
- automatically enabled when a System is responding to
- a Load Sharing Request."
- ::= { airFMGroupCfg 7 }
- airFMGroupCfgDmdFightSetting OBJECT-TYPE
- SYNTAX INTEGER {
- disable (1),
- enable (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Demand Fighting prevents a System from engaging
- reheat in a Group where any System is cooling."
- ::= { airFMGroupCfg 8 }
- airFMGroupCfgSetpointShareStatus OBJECT-TYPE
- SYNTAX INTEGER {
- off (1),
- on (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Demand Fighting and Setpoint Sharing are
- automatically enabled when a System is responding to
- Load Sharing Request."
- ::= { airFMGroupCfg 9 }
- airFMGroupCfgSetpointShareSetting OBJECT-TYPE
- SYNTAX INTEGER {
- disable (1),
- enable (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "All Systems in the Group use the same setpoints."
- ::= { airFMGroupCfg 10 }
- airFMGroupCfgResetFieldServiceDefaults OBJECT-TYPE
- SYNTAX INTEGER {
- noOperation (1),
- reset (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Setting this OID to reset(2) will reset all Group
- parameters, which can only be edited by a field
- service engineer, to their factory default values.
- Getting this OID will do nothing and return the
- noOperation(1) value."
- ::= { airFMGroupCfg 11 }
- -- airFM Group Load Sharing
- airFMGroupLoadShareCoolRequests OBJECT-TYPE
- SYNTAX INTEGER {
- disable (1),
- enable (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Systems that are cooling may request assistance from
- other Systems in the Group."
- ::= { airFMGroupLoadShare 1 }
- airFMGroupLoadShareCoolThreshC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Temperature threshold at which a System will generate
- a load sharing request for cooling. Measured in
- tenths of degrees Celsius."
- ::= { airFMGroupLoadShare 2 }
- airFMGroupLoadShareCoolThreshF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Temperature threshold at which a System will generate
- a load sharing request for cooling. Measured in
- tenths of degrees Fahrenheit."
- ::= { airFMGroupLoadShare 3 }
- airFMGroupLoadShareReheatRequests OBJECT-TYPE
- SYNTAX INTEGER {
- disable (1),
- enable (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Systems that are reheating may request assistance
- from other Systems in the Group."
- ::= { airFMGroupLoadShare 4 }
- airFMGroupLoadShareReheatThreshC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Temperature threshold at which a System will generate
- a load sharing request for reheating. Measured in
- tenths of degrees Celsius."
- ::= { airFMGroupLoadShare 5 }
- airFMGroupLoadShareReheatThreshF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Temperature threshold at which a System will generate
- a load sharing request for reheating. Measured in
- tenths of degrees Fahrenheit."
- ::= { airFMGroupLoadShare 6 }
- airFMGroupLoadShareHumRequests OBJECT-TYPE
- SYNTAX INTEGER {
- disable (1),
- enable (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Systems that are humidifying may request humidification
- assistance from other Systems in the Group."
- ::= { airFMGroupLoadShare 7 }
- airFMGroupLoadShareHumThresh OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Humidity threshold at which a System will generate a
- load sharing request for humidification. Measured in
- tenths of percent relative humidity."
- ::= { airFMGroupLoadShare 8 }
- airFMGroupLoadShareDehumRequests OBJECT-TYPE
- SYNTAX INTEGER {
- disable (1),
- enable (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Systems that are dehumidifying may request assistance
- from other Systems in the Group."
- ::= { airFMGroupLoadShare 9 }
- airFMGroupLoadShareDehumThresh OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Humidity threshold at which a System will generate a
- load sharing request for dehumidification. Measured in
- tenths of percent relative humidity."
- ::= { airFMGroupLoadShare 10 }
- -- airFM Group System Failover Events
- airFMGroupFailoverSysAnyMinorAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disable (2),
- enable (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enabling this OID will cause the system to enter
- a failure state if any minor system alarm is active.
- Once in the failure state, environmental control
- ceases for the system, and the blowers enter the
- Idle Blower Operation mode.
- A value of notApplicable indicates that this alarm
- does not apply to this device due to its configuration."
- ::= { airFMGroupFailoverSys 1 }
- airFMGroupFailoverSysAnyMajorAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disable (2),
- enable (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enabling this OID will cause the system to enter
- a failure state if any major system alarm is active.
- Once in the failure state, environmental control
- ceases for the system, and the blowers enter the
- Idle Blower Operation mode.
- A value of notApplicable indicates that this alarm
- does not apply to this device due to its configuration."
- ::= { airFMGroupFailoverSys 2 }
- airFMGroupFailoverSysHighEnvTemp OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disable (2),
- enable (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enabling this OID will cause the system to enter
- a failure state if the high environmental temperature
- alarm is active.
- Once in the failure state, environmental control
- ceases for the system, and the blowers enter the
- Idle Blower Operation mode.
- A value of notApplicable indicates that this alarm
- does not apply to this device due to its configuration."
- ::= { airFMGroupFailoverSys 3 }
- airFMGroupFailoverSysLowEnvTemp OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disable (2),
- enable (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enabling this OID will cause the system to enter
- a failure state if the low environmental temperature
- alarm is active.
- Once in the failure state, environmental control
- ceases for the system, and the blowers enter the
- Idle Blower Operation mode.
- A value of notApplicable indicates that this alarm
- does not apply to this device due to its configuration."
- ::= { airFMGroupFailoverSys 4 }
- airFMGroupFailoverSysHighEnvHum OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disable (2),
- enable (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enabling this OID will cause the system to enter
- a failure state if the high environmental humidity
- alarm is active.
- Once in the failure state, environmental control
- ceases for the system, and the blowers enter the
- Idle Blower Operation mode.
- A value of notApplicable indicates that this alarm
- does not apply to this device due to its configuration."
- ::= { airFMGroupFailoverSys 5 }
- airFMGroupFailoverSysLowEnvHum OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disable (2),
- enable (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enabling this OID will cause the system to enter
- a failure state if the low environmental humidity
- alarm is active.
- Once in the failure state, environmental control
- ceases for the system, and the blowers enter the
- Idle Blower Operation mode.
- A value of notApplicable indicates that this alarm
- does not apply to this device due to its configuration."
- ::= { airFMGroupFailoverSys 6 }
- airFMGroupFailoverSysFireAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disable (2),
- enable (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enabling this OID will cause the system to enter
- a failure state if the fire alarm is active.
- Once in the failure state, environmental control
- ceases for the system, and the blowers enter the
- Idle Blower Operation mode.
- A value of notApplicable indicates that this alarm
- does not apply to this device due to its configuration."
- ::= { airFMGroupFailoverSys 7 }
- airFMGroupFailoverSysSmokeAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disable (2),
- enable (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enabling this OID will cause the system to enter
- a failure state if the smoke alarm is active.
- Once in the failure state, environmental control
- ceases for the system, and the blowers enter the
- Idle Blower Operation mode.
- A value of notApplicable indicates that this alarm
- does not apply to this device due to its configuration."
- ::= { airFMGroupFailoverSys 8 }
- airFMGroupFailoverSysCommLost OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disable (2),
- enable (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enabling this OID will cause the system to enter
- a failure state if the system has lost comm.
- Once in the failure state, environmental control
- ceases for the system, and the blowers enter the
- Idle Blower Operation mode.
- A value of notApplicable indicates that this alarm
- does not apply to this device due to its configuration."
- ::= { airFMGroupFailoverSys 9 }
- airFMGroupFailoverSysSupplySensorFail OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disable (2),
- enable (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enabling this OID will cause the system to enter
- a failure state if the supply sensor has failed.
- Once in the failure state, environmental control
- ceases for the system, and the blowers enter the
- Idle Blower Operation mode.
- A value of notApplicable indicates that this alarm
- does not apply to this device due to its configuration."
- ::= { airFMGroupFailoverSys 10 }
- airFMGroupFailoverSysReturnSensorFail OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disable (2),
- enable (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enabling this OID will cause the system to enter
- a failure state if the return sensor has failed.
- Once in the failure state, environmental control
- ceases for the system, and the blowers enter the
- Idle Blower Operation mode.
- A value of notApplicable indicates that this alarm
- does not apply to this device due to its configuration."
- ::= { airFMGroupFailoverSys 11 }
- airFMGroupFailoverSysPrimarySensorFail OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disable (2),
- enable (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enabling this OID will cause the system to enter
- a failure state if the primary sensor has failed.
- Once in the failure state, environmental control
- ceases for the system, and the blowers enter the
- Idle Blower Operation mode.
- A value of notApplicable indicates that this alarm
- does not apply to this device due to its configuration."
- ::= { airFMGroupFailoverSys 12 }
- airFMGroupFailoverSysSecondarySensorFail OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disable (2),
- enable (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enabling this OID will cause the system to enter
- a failure state if the secondary sensor has failed.
- Once in the failure state, environmental control
- ceases for the system, and the blowers enter the
- Idle Blower Operation mode.
- A value of notApplicable indicates that this alarm
- does not apply to this device due to its configuration."
- ::= { airFMGroupFailoverSys 13 }
- airFMGroupFailoverSysNoSensorsAvailable OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disable (2),
- enable (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enabling this OID will cause the system to enter
- a failure state if no sensors are available.
- Once in the failure state, environmental control
- ceases for the system, and the blowers enter the
- Idle Blower Operation mode.
- A value of notApplicable indicates that this alarm
- does not apply to this device due to its configuration."
- ::= { airFMGroupFailoverSys 14 }
- -- airFM Group Module Failover Events
- airFMGroupFailoverModMaintRequired OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disable (2),
- enable (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enabling this OID will cause the system to enter
- a failure state if maintenance is required on a
- module.
- Once in the failure state, environmental control
- ceases for the system, and the blowers enter the
- Idle Blower Operation mode.
- A value of notApplicable indicates that this alarm
- does not apply to this device due to its configuration."
- ::= { airFMGroupFailoverMod 1 }
- airFMGroupFailoverModCoolFail OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disable (2),
- enable (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enabling this OID will cause the system to enter
- a failure state if cooling has failed on a module.
- Once in the failure state, environmental control
- ceases for the system, and the blowers enter the
- Idle Blower Operation mode.
- A value of notApplicable indicates that this alarm
- does not apply to this device due to its configuration."
- ::= { airFMGroupFailoverMod 2 }
- airFMGroupFailoverModHumFail OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disable (2),
- enable (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enabling this OID will cause the system to enter
- a failure state if the humidifier has failed on a
- module.
- Once in the failure state, environmental control
- ceases for the system, and the blowers enter the
- Idle Blower Operation mode.
- A value of notApplicable indicates that this alarm
- does not apply to this device due to its configuration."
- ::= { airFMGroupFailoverMod 3 }
- airFMGroupFailoverModBlwrCntrl1Fail OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disable (2),
- enable (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enabling this OID will cause the system to enter
- a failure state if blower controller 1 has failed on
- a module.
- Once in the failure state, environmental control
- ceases for the system, and the blowers enter the
- Idle Blower Operation mode.
- A value of notApplicable indicates that this alarm
- does not apply to this device due to its configuration."
- ::= { airFMGroupFailoverMod 4 }
- airFMGroupFailoverModBlwrCntrl2Fail OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disable (2),
- enable (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enabling this OID will cause the system to enter
- a failure state if blower controller 2 has failed on
- a module.
- Once in the failure state, environmental control
- ceases for the system, and the blowers enter the
- Idle Blower Operation mode.
- A value of notApplicable indicates that this alarm
- does not apply to this device due to its configuration."
- ::= { airFMGroupFailoverMod 5 }
- airFMGroupFailoverModHighFilterDP OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disable (2),
- enable (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enabling this OID will cause the system to enter
- a failure state if a high filter differential
- pressure is present on a module.
- Once in the failure state, environmental control
- ceases for the system, and the blowers enter the
- Idle Blower Operation mode.
- A value of notApplicable indicates that this alarm
- does not apply to this device due to its configuration."
- ::= { airFMGroupFailoverMod 6 }
- airFMGroupFailoverModHighSupplyTemp OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disable (2),
- enable (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enabling this OID will cause the system to enter
- a failure state if a high supply temperature is
- active on a module.
- Once in the failure state, environmental control
- ceases for the system, and the blowers enter the
- Idle Blower Operation mode.
- A value of notApplicable indicates that this alarm
- does not apply to this device due to its configuration."
- ::= { airFMGroupFailoverMod 7 }
- airFMGroupFailoverModLowSupplyTemp OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disable (2),
- enable (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enabling this OID will cause the system to enter
- a failure state if a low supply temperature is active
- on a module.
- Once in the failure state, environmental control
- ceases for the system, and the blowers enter the
- Idle Blower Operation mode.
- A value of notApplicable indicates that this alarm
- does not apply to this device due to its configuration."
- ::= { airFMGroupFailoverMod 8 }
- airFMGroupFailoverModLossOrLowAirFlow OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disable (2),
- enable (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enabling this OID will cause the system to enter
- a failure state if there is a loss of air flow or low
- air flow on a module.
- Once in the failure state, environmental control
- ceases for the system, and the blowers enter the
- Idle Blower Operation mode.
- A value of notApplicable indicates that this alarm
- does not apply to this device due to its configuration."
- ::= { airFMGroupFailoverMod 9 }
- airFMGroupFailoverModHumReplaceCylinder OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disable (2),
- enable (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enabling this OID will cause the system to enter
- a failure state if a humidifier needs its cylinder
- replaced on a module.
- Once in the failure state, environmental control
- ceases for the system, and the blowers enter the
- Idle Blower Operation mode.
- A value of notApplicable indicates that this alarm
- does not apply to this device due to its configuration."
- ::= { airFMGroupFailoverMod 10 }
- airFMGroupFailoverModAirBlockInterlockOpen OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disable (2),
- enable (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enabling this OID will cause the system to enter
- a failure state if the air block interlock is open
- on a module.
- Once in the failure state, environmental control
- ceases for the system, and the blowers enter the
- Idle Blower Operation mode.
- A value of notApplicable indicates that this alarm
- does not apply to this device due to its configuration."
- ::= { airFMGroupFailoverMod 11 }
- airFMGroupFailoverModWaterDetected OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disable (2),
- enable (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enabling this OID will cause the system to enter
- a failure state if water is detected by a module.
- Once in the failure state, environmental control
- ceases for the system, and the blowers enter the
- Idle Blower Operation mode.
- A value of notApplicable indicates that this alarm
- does not apply to this device due to its configuration."
- ::= { airFMGroupFailoverMod 12 }
- airFMGroupFailoverModCondensatePumpFail OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disable (2),
- enable (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enabling this OID will cause the system to enter
- a failure state if the condensate pump has failed in
- a module.
- Once in the failure state, environmental control
- ceases for the system, and the blowers enter the
- Idle Blower Operation mode.
- A value of notApplicable indicates that this alarm
- does not apply to this device due to its configuration."
- ::= { airFMGroupFailoverMod 13 }
- -- airFM System Status
- airFMSysNumber OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- one (2),
- two (3),
- three (4),
- four (5)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of the system within the group.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysStatus 1 }
- airFMSysPresentStatus OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- reserved1 (2),
- reserved2 (3),
- onLine (4),
- idle (5),
- loadShare (6),
- failed (7),
- offLine (8)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The present mode of the System.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysStatus 2 }
- airFMSysPresentRole OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- primary (2),
- backup (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The present role of the System in the Group.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysStatus 3 }
- airFMSysRunHours OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The total number of hours the System has been
- contributing to environmental control.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysStatus 4 }
- airFMSysCoilFluidTempC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The temperature of the coolant at the fluid coil
- inlet. Measured in degrees Celsius.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysStatus 5 }
- airFMSysCoilFluidTempF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The temperature of the coolant at the fluid coil
- inlet. Measured in degrees Fahrenheit.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysStatus 6 }
- airFMSysHotWaterTempC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The hot water temperature. Measured in degrees
- Celsius.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysStatus 7 }
- airFMSysHotWaterTempF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The hot water temperature. Measured in degrees
- Fahrenheit.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysStatus 8 }
- airFMSysAvgReturnTempC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The average return temperature calculated from all
- present modules. Measured in tenths of degrees
- Celsius.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysStatus 9 }
- airFMSysAvgReturnTempF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The average return temperature calculated from all
- present modules. Measured in tenths of degrees
- Fahrenheit.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysStatus 10 }
- airFMSysAvgReturnHum OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The average return humidity calculated from all
- present modules. Measured in tenths of percent RH.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysStatus 11 }
- airFMSysAvgRemoteTempC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The average temperature calculated from all
- operational remote sensors. Measured in tenths of
- degrees Celsius.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysStatus 12 }
- airFMSysAvgRemoteTempF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The average temperature calculated from all
- operational remote sensors. Measured in tenths of
- degrees Fahrenheit.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysStatus 13 }
- airFMSysAvgRemoteHum OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The average return humidity calculated from all
- present modules. Measured in tenths of percent RH.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysStatus 14 }
- airFMSysMaxRemoteTempC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The maximum temperature reading from all operational
- remote sensors. Measured in tenths of degrees
- Celsius.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysStatus 15 }
- airFMSysMaxRemoteTempF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The maximum temperature reading from all operational
- remote sensors. Measured in tenths of degrees
- Fahrenheit.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysStatus 16 }
- airFMSysMinRemoteTempC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The minimum temperature reading from all operational
- remote sensors. Measured in tenths of degrees
- Celsius.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysStatus 17 }
- airFMSysMinRemoteTempF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The minimum temperature reading from all operational
- remote sensors. Measured in tenths of degrees
- Fahrenheit.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysStatus 18 }
- airFMSysTempCtrlMethod OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- avgReturn (2),
- avgRemote (3),
- maxRemote (4)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The method of environment temperature control
- selected to regulate the temperature.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysStatus 19 }
- airFMSysActualTempCtrlMethod OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- avgReturn (2),
- avgRemote (3),
- maxRemote (4)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The actual method of environment temperature control
- being used to regulate the temperature.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysStatus 20 }
- airFMSysHumCtrlMethod OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- avgReturnRH (2),
- avgReturnDewPt (3),
- avgRemoteRH (4),
- avgRemoteDewPt (5)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The method of environment humidity control selected
- to regulate the humidity.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysStatus 21 }
- airFMSysActualHumCtrlMethod OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- avgReturnRH (2),
- avgReturnDewPt (3),
- avgRemoteRH (4),
- avgRemoteDewPt (5)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The actual method of environment humidity control
- being used to regulate the humidity.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysStatus 22 }
- airFMSysCtrlTempC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The system environmental control air temperature from
- the sensor denoted by airFMSysActualTempCtrl.
- Measured in tenths of degrees Celsius.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysStatus 23 }
-
- airFMSysCtrlTempF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The system environmental control air temperature from
- the sensor denoted by airFMSysActualTempCtrl.
- Measured in tenths of degrees Fahrenheit.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysStatus 24 }
-
- airFMSysCtrlHum OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The system environmental control air humidity from
- the sensor denoted by airFMSysActualHumCtrl.
- Measured in percent relative humidity.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysStatus 25 }
- -- airFM System Demands and Actuals
- airFMSysDXCoolingDmd OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The direct expansion cooling output demanded by the
- System. Measured in percent.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysDemands 1 }
- airFMSysDXDehumDmd OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The direct expansion dehumidification output demanded
- by the System. Measured in percent.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysDemands 2 }
- airFMSysDXActualCoolDehum OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The direct expansion cooling or dehumidification
- output measured by the System. Measured in percent.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysDemands 3 }
- airFMSysCoilFluidCoolDmd OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The fluid coil cooling output demanded by the System.
- Measured in percent.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysDemands 4 }
- airFMSysCoilFluidDehumDmd OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The fluid coil dehumidification output demanded by
- the System. Measured in percent.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysDemands 5 }
- airFMSysCoilFluidActualCoolDehum OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The fluid coil cooling or dehumidification output
- measured by the System. Measured in percent.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysDemands 6 }
- airFMSysElectricReheatDmd OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The electric reheating output demanded by the System.
- Measured in percent.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysDemands 7 }
- airFMSysActualElectricReheat OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The electric reheating output of the System.
- Measured in percent.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysDemands 8 }
- airFMSysSteamHotGasReheatDmd OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- off (2),
- on (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The steam, hot water, or hot gas reheating output
- demanded by the System.
- A value of notApplicable indicates that this OID
- does not apply to this device due to its configuration."
- ::= { airFMSysDemands 9 }
- airFMSysActualSteamHotGasReheat OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- off (2),
- on (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The steam, hot water, or hot gas reheating output of
- the System.
- A value of notApplicable indicates that this OID
- does not apply to this device due to its configuration."
- ::= { airFMSysDemands 10 }
- airFMSysSteamElectrodeHumDmd OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The steam electrode humidification output demanded by
- the System. Measured in percent.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysDemands 11 }
- airFMSysActualSteamElectrodeHum OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The average steam electrode humidification output
- measured for the Modules in the System. Measured in
- percent.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysDemands 12 }
- airFMSysSteamHumDmd OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- off (2),
- on (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The steam humidification output demanded by the System.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysDemands 13 }
- airFMSysActualSteamHum OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- off (2),
- on (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The steam humidification output for the System.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysDemands 14 }
- -- airFM System Physical Setup
- airFMSysNumModules OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- one (2),
- two (3),
- three (4)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of Modules in this System.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysSetup 1 }
- airFMSysNumPCIOMs OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- one (2),
- two (3),
- three (4),
- four (5)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of Programmable Customer Input/Output
- Modules (PCIOMs) installed in the Main Module of this
- System. Each PCIOM adds four input contacts and four
- output relays to the System.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysSetup 2 }
- airFMSysMainsVlt OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The mains voltage for the Modules in this System.
- A value of N/A indicates that this OID does not apply
- to this device due to its configuration."
- ::= { airFMSysSetup 3 }
- airFMSysUPSVlt OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The UPS voltage for the Modules in this System.
- A value of N/A indicates that this OID does not apply
- to this device due to its configuration."
- ::= { airFMSysSetup 4 }
- airFMSysCoilCfg OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- dx (2),
- econ (3),
- multicool (4),
- chilledWater (5)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The type of cooling coils installed in the Modules in
- this System: DX coil, DX and MultiCool (chilled water)
- coils, DX and Economizer coils, or only a Chilled
- Liquid coil.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysSetup 5 }
- airFMSysRefrigType OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- r22 (2),
- r407C (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The type of refrigerant used by each compressor in
- the system.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysSetup 6 }
- airFMSysHeatRejection OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- airCooled (2),
- waterCooled (3),
- glycolCooled (4)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The method the Modules in this System use to transfer
- heat away from the refrigerant.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysSetup 7 }
- airFMSysDischAirPtrn OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- upFlow (2),
- downFlow (3),
- horizFlow (4)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The discharge air pattern for the Modules in this
- System.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysSetup 8 }
- airFMSysAirFltr OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- standard (2),
- highEfficiency (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The type of air filters (standard or high efficiency)
- installed in the Modules of this System.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysSetup 9 }
- airFMSysFlowSwitch OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- none (2),
- dxEcon (3),
- multiCoolChillWater (4)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The location of the optional flow switch.
- None: No flow switch is installed in this System.
- DX: Coolant input to the heat exchanger (condenser).
- MultiCool: Chilled water input to the MultiCool coil.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysSetup 10 }
- airFMSysCoilFluidVlvAct OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- none (2),
- springAnalog (3),
- floatingControl (4)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The type of valve actuator installed on the coil
- fluid valve. The coil fluid valve controls the flow
- of coolant into a fluid cooling coil, such as a
- MultiCool or Economizer coil.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysSetup 11 }
- airFMSysCoilFluidVlvType OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- twoWay (2),
- threeWay (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The type of coil fluid valve installed for the
- Modules in this System.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysSetup 12 }
- airFMSysCndsrFluidVlvAct OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- none (2),
- floatingControl (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The type of valve actuator installed on the Condenser
- fluid valve. The Condenser fluid valve controls the
- flow of coolant into the heat exchanger (condenser)
- to regulate head pressure.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysSetup 13 }
- airFMSysCndsrFluidVlvType OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- twoWay (2),
- threeWay (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The type of Condenser fluid valve installed for the
- Modules in this System.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysSetup 14 }
- airFMSysHotWaterVlvAct OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- none (2),
- springAnalog (3),
- floatingControl (4)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The type of valve actuator installed on the hot water
- valve.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysSetup 15 }
- airFMSysNumRemoteSensors OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of remote sensors detected by the system."
- ::= { airFMSysSetup 16 }
- -- airFM System Configuration
- airFMSysPrimaryControlSensor OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- return (2),
- remote (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Selects whether return or remote sensors will control
- the system.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysConfig 1 }
- airFMSysRemoteSensorData OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- average (2),
- maximum (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Selects whether average temperature or max temperature
- will be used when remote sensors are selected for
- control of the system.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysConfig 2 }
- airFMSysFastStartup OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Minimizes the time for the cooling process to begin
- after other delay constraints have been met.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysConfig 3 }
- airFMSysStartupDelay OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Set the delay that begins when power is applied and
- ends when the System starts. This allows you to
- create a staged restart among your Systems after a
- power loss. Measured in seconds.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysConfig 4 }
- airFMSysModeDelay OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Set the delay between starting the blowers and
- engaging the modes. It allows the sensors to read
- room conditions accurately and allows the controller
- to check for major alarms before engaging a mode.
- Measured in seconds.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysConfig 5 }
- airFMSysCommLossShutdownDelay OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Set the delay between an Expansion Module losing
- communication with the Main Module and the Expansion
- Module shutting down. A value of -1 will keep
- the Expansion Module running after a communication
- loss. Measured in hours.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysConfig 6 }
- airFMSysResetSysFailure OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- noOperation (2),
- reset (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Setting this OID to reset(2) will allows the system
- to return from any failure condition, if the
- failure(s) have cleared.
- Getting this OID will do nothing and return the noOperation(1) value.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysConfig 7 }
- airFMSysResetUserDflts OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- noOperation (2),
- reset (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Setting this OID to reset(2) will reset all system
- parameters that can be edited by the user to their
- factory default values.
- Getting this OID will do nothing and return the noOperation(1) value.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysConfig 8 }
- airFMSysResetFldSrvcDflts OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- noOperation (2),
- reset (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Setting this OID to reset(2) will reset all system
- parameters that can only be edited by the field
- service engineer to their factory default values.
- Getting this OID will do nothing and return the noOperation(1) value.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysConfig 9 }
- airFMSysResetRunHours OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- noOperation (2),
- reset (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Setting this OID to reset(2) will reset the system Run Hours.
- Getting this OID will do nothing and return the noOperation(1) value.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysConfig 10 }
- -- airFM System Cooling
- airFMSysCompMinOnTime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Set the minimum time the compressor continues to
- operate after it is started. The delay protects the
- compressor from damage. Caution: Reducing this delay
- shortens compressor life. Measured in seconds.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysCooling 1 }
- airFMSysCompMinOffTime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Set the minimum time the compressor will remain off
- after it ceases operation. The delay protects the
- compressor from damage. Caution: Reducing this delay
- shortens compressor life. Measured in seconds.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysCooling 2 }
- airFMSysCompRotPeriod OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Set how often to perform compressor runtime
- balancing. Measured in hours.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysCooling 3 }
- airFMSysEconIsolVlvOpenDelay OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Set the delay between opening the Economizer Isolator
- output relay and engaging the compressors. Measured
- in seconds.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysCooling 4 }
- airFMSysEconIsolVlvCloseDelay OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Set the delay between disengaging the compressor and
- closing the Economizer Isolator output relay.
- Measured in seconds.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysCooling 5 }
- airFMSysCndsrFluidVlvCloseDelay OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Set the time the condenser valve remains open after
- the compressors disengage. Measured in seconds.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysCooling 6 }
- airFMSysInterstageDelay OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The DX interstage delay allows the first compressor's
- cooling to take effect before engaging the second
- compressor. This prevents the second compressor from
- cycling on and off excessively. Measured in seconds.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysCooling 7 }
- airFMSysCoolState OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Set the mode to enabled or disabled. Disabled modes
- will not operate, and you cannot make changes to
- their settings while they are disabled.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysCooling 8 }
- airFMSysCoolEssFunction OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- yes (2),
- no (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Set the priority of the mode for alarms and events
- with the nonessential stop behavior. Nonessential
- modes are disabled during nonessential stop alarms
- and events.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysCooling 9 }
- airFMSysCoolSetpointC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The target value for the selected control sensor air
- for this mode. It must be at least 1.0 C above the
- reheat setpoint if a heater is installed. Measured
- in tenths of degrees Celsius.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysCooling 10 }
- airFMSysCoolSetpointF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The target value for the selected control sensor air
- for this mode. It must be at least 1.0 C above the
- reheat setpoint if a heater is installed. Measured
- in tenths of degrees Fahrenheit.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysCooling 11 }
- airFMSysCoolDeadbandC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The temperature range that controls output when the
- selected control sensor temperature is above the
- setpoint. At the top of this range, the cool mode
- outputs at 100%. The deadband does not apply to PID-
- controlled modes. Measured in tenths of degrees
- Celsius.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysCooling 12 }
- airFMSysCoolDeadbandF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The temperature range that controls output when the
- selected control sensor temperature is above the
- setpoint. At the top of this range, the cool mode
- outputs at 100%. The deadband does not apply to PID-
- controlled modes. Measured in tenths of degrees
- Fahrenheit.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysCooling 13 }
- airFMSysCoolEconIsolFunction OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Set the Economizer Automatic Coolant Isolation valve
- to enabled or disabled. This valve anticipates a
- cooling demand and opens the coil fluid valve.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysCooling 14 }
- airFMSysSuctPresCompensation OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Set the Suction Pressure Compensation to enabled or
- disabled. This function attempts to keep the suction
- pressure from exceeding 95 psi.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysCooling 15 }
- airFMSysCoilFluidActivThreshC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The minimum coolant temperature required to use the
- optional MultiCool or Economizer coil. Measured in
- tenths of degrees Celsius.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysCooling 16 }
- airFMSysCoilFluidActivThreshF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The minimum coolant temperature required to use the
- optional MultiCool or Economizer coil. Measured in
- tenths of degrees Fahrenheit.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysCooling 17 }
- airFMSysCoilFluidActivDeadbandC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The controller will disengage the MultiCool or
- Economizer coil when the coolant temperature reaches
- the coil fluid temperature activation threshold plus
- the deadband. Measured in tenths of degrees Celsius.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysCooling 18 }
- airFMSysCoilFluidActivDeadbandF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The controller will disengage the MultiCool or
- Economizer coil when the coolant temperature reaches
- the coil fluid temperature activation threshold plus
- the deadband. Measured in tenths of degrees
- Fahrenheit.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysCooling 19 }
- airFMSysCoolPIDMethod OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- p (2),
- pi (3),
- pid (4)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Set the multipliers that the PID algorithm will use
- to calculate the cool output. Proportional,
- Proportional + Integral, or Proportional + Integral
- + Derivative.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysCooling 20 }
- airFMSysCoolPIDGainP OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Set the proportional multiplier to correct for
- differences between the selected control sensor
- actual temperature and the setpoint. Measured in
- %/C.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysCooling 21 }
- airFMSysCoolPIDResetRateI OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Set the integral multiplier to correct for the
- proportional offset. Measured in %/(C * min).
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysCooling 22 }
- airFMSysCoolPIDDerivativeD OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Set the derivative multiplier to counteract overshoot
- and droop during changes in the room load. Measured
- in %/(C / min).
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysCooling 23 }
- -- airFM System Humidify Function
- airFMSysHumState OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Set the mode to enabled or disabled. Disabled modes
- will not operate, and you cannot make changes to their
- settings while they are disabled.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysHumidify 1 }
- airFMSysHumEssFunction OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- yes (2),
- no (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Set the priority of the mode for alarms and events
- with the nonessential stop behavior. Nonessential
- modes are disabled during nonessential stop alarms
- and events.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysHumidify 2 }
- airFMSysHumSetpoint OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The target value for the selected control sensor air
- for this mode. It must be at least 1.0 % RH below
- the dehumidification setpoint. Measured in tenths of
- percent relative humidity.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysHumidify 3 }
- airFMSysHumDeadband OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The humidity range that controls output when the
- selected control sensor humidity is below the
- setpoint. At the top of this range, the
- humidification mode outputs at 100%. The deadband
- does not apply to PID-controlled modes. Measured in
- tenths of percent relative humidity.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysHumidify 4 }
- airFMSysHumCtrlSetting OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- relativeHum (2),
- dewPoint (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Set the method to control the humidity in the room.
- The two methods are Relative Humidity (RH) or Dew
- Point of the selected control sensor air. The dew
- point method helps correct for hot spots near the
- selected control sensors.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysHumidify 5 }
- airFMSysActualHumCtrl OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- relativeHum (2),
- dewPoint (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The humidity control method the system is using.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysHumidify 6 }
- airFMSysHumSensBand OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The percentage of relative humidity below the
- setpoint at which the humidifier will output at 100%
- of capacity. Measured in percent relative humidity.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysHumidify 7 }
- -- airFM System Dehumidify Function
- airFMSysDehumState OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Set the mode to enabled or disabled. Disabled modes
- will not operate, and you cannot make changes to their
- settings while they are disabled.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysDehumidify 1 }
- airFMSysDehumEssFunction OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- yes (2),
- no (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Set the priority of the mode for alarms and events
- with the nonessential stop behavior. Nonessential
- modes are disabled during nonessential stop alarms
- and events.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysDehumidify 2 }
- airFMSysDehumSetpoint OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The target value for the selected control sensor air
- for this mode. It must be at least 1.0 % RH above
- the humidification setpoint if a humidifier is
- installed. Measured in tenths of percent relative
- humidity.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysDehumidify 3 }
- airFMSysDehumDeadband OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The humidity range above the setpoint at which the
- dehumidification mode will output at 100%. The
- deadband does not apply to PID controlled modes.
- Measured in tenths of percent relative humidity.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysDehumidify 4 }
- airFMSysDehumCapacity OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- half (2),
- full (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Set the dehumidification mode to use either half of
- the cooling coil or the full coil when dehumidifying
- the room.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysDehumidify 5 }
- airFMSysDehumPIDMethod OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- p (2),
- pi (3),
- pid (4)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Set the multipliers that the PID algorithm will use
- to calculate the output. Proportional,
- Proportional + Integral, or Proportional + Integral
- + Derivative.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysDehumidify 6 }
- airFMSysDehumPIDGainP OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Set the proportional multiplier to correct for
- differences between the selected control sensor
- actual humidity and the setpoint. Measured in %/%RH.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysDehumidify 7 }
- airFMSysDehumPIDResetRateI OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Set the integral multiplier to correct for the
- proportional offset. Measured in %/(%RH * min).
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysDehumidify 8 }
- airFMSysDehumPIDDerivativeD OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Set the derivative multiplier to counteract overshoot
- and droop during changes in the room humidity.
- Measure in %/(%RH / min).
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysDehumidify 9 }
- -- airFM System Reheat Function
- airFMSysReheatState OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Set the mode to enabled or disabled. Disabled modes
- will not operate, and you cannot make changes to their
- settings while they are disabled.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysReheat 1 }
- airFMSysReheatEssFunction OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- yes (2),
- no (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Set the priority of the mode for alarms and events
- with the nonessential stop behavior. Nonessential
- modes are disabled during nonessential stop alarms
- and events.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysReheat 2 }
- airFMSysReheatSetpointC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The target value for the selected control sensor air
- for this mode. It must be at least 1.0 C below the
- cooling setpoint. Measured in tenths of degrees
- Celsius.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysReheat 3 }
- airFMSysReheatSetpointF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The target value for the selected control sensor air
- for this mode. It must be at least 1.0 C below the
- cooling setpoint. Measured in tenths of degrees
- Fahrenheit.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysReheat 4 }
- airFMSysReheatDeadbandC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The temperature range that controls output when the
- selected control sensor temperature is below the
- setpoint. At the bottom of this range, the reheat
- mode outputs at 100%. The deadband does not apply to
- PID-controlled modes. Measured in tenths of degrees
- Celsius.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysReheat 5 }
- airFMSysReheatDeadbandF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The temperature range that controls output when the
- selected control sensor temperature is below the
- setpoint. At the bottom of this range, the reheat
- mode outputs at 100%. The deadband does not apply to
- PID-controlled modes. Measured in tenths of degrees
- Fahrenheit.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysReheat 6 }
- airFMSysReheatPIDMethod OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- p (2),
- pi (3),
- pid (4)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Set the multipliers that the PID algorithm will use
- to calculate the output. Proportional,
- Proportional + Integral, or Proportional + Integral
- + Derivative.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysReheat 7 }
- airFMSysReheatPIDGainP OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Set the proportional multiplier to correct for
- differences between the selected control sensor
- actual temperature and the setpoint. Measured in
- %/C.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysReheat 8 }
- airFMSysReheatPIDResetRateI OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Set the integral multiplier to correct for the
- proportional offset. Measured in %/(C * min).
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysReheat 9 }
- airFMSysReheatPIDDerivativeD OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Set the derivative multiplier to counteract overshoot
- and droop during changes in the room load. Measured
- in %/(C / min).
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysReheat 10 }
- -- airFM System Thresholds
- airFMSysHighSplyTempC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The high temperature threshold for air blown into the
- room (supply). If the supply temperature exceeds the
- threshold, an alarm will occur. Measured in tenths
- of degrees Celsius.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysThresholds 1 }
- airFMSysHighSplyTempF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The high temperature threshold for air blown into the
- room (supply). If the supply temperature exceeds the
- threshold, an alarm will occur. Measured in tenths
- of degrees Fahrenheit.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysThresholds 2 }
- airFMSysLowSplyTempC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The low temperature threshold for air blown into the
- room (supply). If the supply temperature drops below
- the threshold, an alarm will occur. Measured in
- tenths of degrees Celsius.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysThresholds 3 }
- airFMSysLowSplyTempF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The low temperature threshold for air blown into the
- room (supply). If the supply temperature drops below
- the threshold, an alarm will occur. Measured in
- tenths of degrees Fahrenheit.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysThresholds 4 }
- airFMSysHighCoilFluidTempC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The high temperature threshold for coolant at the
- inlet to the fluid coil. If the fluid coil coolant
- temperature exceeds the threshold, an alarm will
- occur. Measured in tenths of degrees Celsius.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysThresholds 5 }
- airFMSysHighCoilFluidTempF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The high temperature threshold for coolant at the
- inlet to the fluid coil. If the fluid coil coolant
- temperature exceeds the threshold, an alarm will
- occur. Measured in tenths of degrees Fahrenheit.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysThresholds 6 }
- airFMSysLowCoilFluidTempC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The low temperature threshold for coolant at the
- inlet to the fluid coil. If the fluid coil coolant
- temperature drops below the threshold, an alarm will
- occur. Measured in tenths of degrees Celsius.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysThresholds 7 }
- airFMSysLowCoilFluidTempF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The low temperature threshold for coolant at the
- inlet to the fluid coil. If the fluid coil coolant
- temperature drops below the threshold, an alarm will
- occur. Measured in tenths of degrees Fahrenheit.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysThresholds 8 }
- airFMSysHighCtrlTempC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The high temperature threshold for air monitored by
- the System. If the temperature exceeds the threshold,
- an alarm will occur. Measured in tenths of degrees
- Celsius.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysThresholds 9 }
- airFMSysHighCtrlTempF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The high temperature threshold for air monitored by
- the System. If the temperature exceeds the threshold,
- an alarm will occur. Measured in tenths of degrees
- Fahrenheit.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysThresholds 10 }
- airFMSysLowCtrlTempC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The low temperature threshold for air monitored by
- the System. If the temperature drops below the
- threshold, an alarm will occur. Measured in tenths
- of degrees Celsius.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysThresholds 11 }
- airFMSysLowCtrlTempF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The low temperature threshold for air monitored by
- the System. If the temperature drops below the
- threshold, an alarm will occur. Measured in tenths
- of degrees Fahrenheit.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysThresholds 12 }
- airFMSysHighCtrlHum OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The high humidity threshold for air monitored by the
- System. If the humidity exceeds the threshold, an
- alarm will occur. Measured in tenths of percent
- relative humidity.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysThresholds 13 }
- airFMSysLowCtrlHum OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The low humidity threshold for air monitored by the
- System. If the humidity drops below the threshold,
- an alarm will occur. Measured in tenths of percent
- relative humidity.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysThresholds 14 }
- airFMSysTempAlarmDelay OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The amount of time the blower must be on before a
- temperature alarm can be issued. Measured in
- seconds.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysThresholds 15 }
- airFMSysHumAlarmDelay OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The amount of time the blower must be on before a
- humidity alarm can be issued. Measured in seconds.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysThresholds 16 }
- -- airFM System Input Contacts
- airFMSysInputTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the airFMSysInputTable. "
- ::= { airFMSysInputs 1 }
- airFMSysInputTable OBJECT-TYPE
- SYNTAX SEQUENCE OF AirFMSysInputEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting information from each input
- contact."
- ::= { airFMSysInputs 2 }
- airFMSysInputEntry OBJECT-TYPE
- SYNTAX AirFMSysInputEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The input contact to obtain status from."
- INDEX { airFMSysInputIndex }
- ::= { airFMSysInputTable 1 }
- AirFMSysInputEntry ::=
- SEQUENCE {
- airFMSysInputIndex INTEGER,
- airFMSysInputName DisplayString,
- airFMSysInputStatus INTEGER,
- airFMSysInputNormalState INTEGER,
- airFMSysInputDelay INTEGER,
- airFMSysInputAlarmAction INTEGER
- }
-
- airFMSysInputIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number designator of the Input Contact."
- ::= { airFMSysInputEntry 1 }
- airFMSysInputName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The configurable name for the Input Contact. Maximum
- text input is 13 characters."
- ::= { airFMSysInputEntry 2 }
- airFMSysInputStatus OBJECT-TYPE
- SYNTAX INTEGER {
- open (1),
- closed (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The state of this contact: Open or Closed. A
- violation will occur when this relay is not in its
- normal state."
- ::= { airFMSysInputEntry 3 }
- airFMSysInputNormalState OBJECT-TYPE
- SYNTAX INTEGER {
- open (1),
- closed (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Set the normal state of this contact (the state when
- no alarm/event exists)."
- ::= { airFMSysInputEntry 4 }
- airFMSysInputDelay OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Set the delay between this contact exiting its normal
- state and an alarm being triggered. Measured in
- seconds."
- ::= { airFMSysInputEntry 5 }
- airFMSysInputAlarmAction OBJECT-TYPE
- SYNTAX INTEGER {
- statusOnly (1),
- minor (2),
- major (3),
- remoteRunStop (4),
- nonessStop (5),
- immShutdown (6)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Sets the behavior for this contact when it exits its
- normal state."
- ::= { airFMSysInputEntry 6 }
- -- airFM System Output Relays
- airFMSysOutputTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the airFMSysOutputTable. "
- ::= { airFMSysOutputs 1 }
- airFMSysOutputTable OBJECT-TYPE
- SYNTAX SEQUENCE OF AirFMSysOutputEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting information from each output relay. "
- ::= { airFMSysOutputs 2 }
- airFMSysOutputEntry OBJECT-TYPE
- SYNTAX AirFMSysOutputEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The output relay to obtain status from."
- INDEX { airFMSysOutputIndex }
- ::= { airFMSysOutputTable 1 }
- AirFMSysOutputEntry ::=
- SEQUENCE {
- airFMSysOutputIndex INTEGER,
- airFMSysOutputStatus INTEGER,
- airFMSysOutputNormalState INTEGER
- }
-
- airFMSysOutputIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number designator of the output relay."
- ::= { airFMSysOutputEntry 1 }
- airFMSysOutputStatus OBJECT-TYPE
- SYNTAX INTEGER {
- open (1),
- closed (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The state of this relay: Open or Closed. A violation
- will occur when this relay is not in its normal state."
- ::= { airFMSysOutputEntry 2 }
- airFMSysOutputNormalState OBJECT-TYPE
- SYNTAX INTEGER {
- open (1),
- closed (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Set the normal state of this relay (the state when no
- alarm/event exists)."
- ::= { airFMSysOutputEntry 3 }
- -- airFM System Output Alarm Mapping
- airFMSysAlarmMapSysTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the airFMSysAlarmMapSysTable. "
- ::= { airFMSysAlarmMapSys 1 }
- airFMSysAlarmMapSysTable OBJECT-TYPE
- SYNTAX SEQUENCE OF AirFMSysAlarmMapSysEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting alarm map information."
- ::= { airFMSysAlarmMapSys 2 }
- airFMSysAlarmMapSysEntry OBJECT-TYPE
- SYNTAX AirFMSysAlarmMapSysEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The system alarm map type to reference."
- INDEX { airFMSysAlarmMapSysOutputIndex }
- ::= { airFMSysAlarmMapSysTable 1 }
- AirFMSysAlarmMapSysEntry ::=
- SEQUENCE {
- airFMSysAlarmMapSysOutputIndex INTEGER,
- airFMSysAlarmMapSysAnyAlarm INTEGER,
- airFMSysAlarmMapSystemOn INTEGER,
- airFMSysAlarmMapSystemOffline INTEGER,
- airFMSysAlarmMapSysHighEnvTemp INTEGER,
- airFMSysAlarmMapSysLowEnvTemp INTEGER,
- airFMSysAlarmMapSysHighEnvHum INTEGER,
- airFMSysAlarmMapSysLowEnvHum INTEGER,
- airFMSysAlarmMapSysFireDet INTEGER,
- airFMSysAlarmMapSysSmokeDet INTEGER,
- airFMSysAlarmMapSysEconIsol INTEGER,
- airFMSysAlarmMapSysSupplySensFail INTEGER,
- airFMSysAlarmMapSysReturnSensFail INTEGER,
- airFMSysAlarmMapSysRemSensRemoved INTEGER,
- airFMSysAlarmMapSysPrimSensFail INTEGER,
- airFMSysAlarmMapSysSecSensFail INTEGER,
- airFMSysAlarmMapSysSecSensActive INTEGER
- }
-
- airFMSysAlarmMapSysOutputIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index of the output relay."
- ::= { airFMSysAlarmMapSysEntry 1 }
- airFMSysAlarmMapSysAnyAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "System alarm map setting for Any Alarm.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapSysEntry 2 }
- airFMSysAlarmMapSystemOn OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "System alarm map setting for System On.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapSysEntry 3 }
- airFMSysAlarmMapSystemOffline OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "System alarm map setting for System Offline.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapSysEntry 4 }
- airFMSysAlarmMapSysHighEnvTemp OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "System alarm map setting for High Environmental
- Temperature.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapSysEntry 5 }
- airFMSysAlarmMapSysLowEnvTemp OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "System alarm map setting for Low Environmental
- Temperature.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapSysEntry 6 }
- airFMSysAlarmMapSysHighEnvHum OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "System alarm map setting for High Environmental
- Humidity.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapSysEntry 7 }
- airFMSysAlarmMapSysLowEnvHum OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "System alarm map setting for Low Environmental
- Humidity.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapSysEntry 8 }
- airFMSysAlarmMapSysFireDet OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "System alarm map setting for Fire Detected.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapSysEntry 9 }
- airFMSysAlarmMapSysSmokeDet OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "System alarm map setting for Smoke Detected.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapSysEntry 10 }
- airFMSysAlarmMapSysEconIsol OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "System alarm map setting for Econ Isolator.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapSysEntry 11 }
- airFMSysAlarmMapSysSupplySensFail OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "System alarm map setting for Supply Sensor Failure.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapSysEntry 12 }
- airFMSysAlarmMapSysReturnSensFail OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "System alarm map setting for Return Sensor Failure.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapSysEntry 13 }
- airFMSysAlarmMapSysRemSensRemoved OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "System alarm map setting for Remote Sensor Removed.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapSysEntry 14 }
- airFMSysAlarmMapSysPrimSensFail OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "System alarm map setting for Primary Sensor Failure.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapSysEntry 15 }
- airFMSysAlarmMapSysSecSensFail OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "System alarm map setting for Secondary Sensor Failure.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapSysEntry 16 }
- airFMSysAlarmMapSysSecSensActive OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "System alarm map setting for Secondary Sensor Active.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapSysEntry 17 }
- -- airFM Main Module Output Alarm Mapping
- airFMSysAlarmMapMainModTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the airFMSysAlarmMapMainModTable. "
- ::= { airFMSysAlarmMapMainMod 1 }
- airFMSysAlarmMapMainModTable OBJECT-TYPE
- SYNTAX SEQUENCE OF AirFMSysAlarmMapMainModEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting alarm map information."
- ::= { airFMSysAlarmMapMainMod 2 }
- airFMSysAlarmMapMainModEntry OBJECT-TYPE
- SYNTAX AirFMSysAlarmMapMainModEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The main module alarm map type to reference."
- INDEX { airFMSysAlarmMapMainModOutputIndex }
- ::= { airFMSysAlarmMapMainModTable 1 }
- AirFMSysAlarmMapMainModEntry ::=
- SEQUENCE {
- airFMSysAlarmMapMainModOutputIndex INTEGER,
- airFMSysAlarmMapMainModAnyAlarm INTEGER,
- airFMSysAlarmMapMainModMaintReq INTEGER,
- airFMSysAlarmMapMainModCoolFail INTEGER,
- airFMSysAlarmMapMainModHighSupplyTemp INTEGER,
- airFMSysAlarmMapMainModLowSupplyTemp INTEGER,
- airFMSysAlarmMapMainModHumFail INTEGER,
- airFMSysAlarmMapMainModHumReplCyl INTEGER,
- airFMSysAlarmMapMainModCondPumpFail INTEGER,
- airFMSysAlarmMapMainModBlwrCntl1Fail INTEGER,
- airFMSysAlarmMapMainModBlwrCntl2Fail INTEGER,
- airFMSysAlarmMapMainModHighFltrDP INTEGER,
- airFMSysAlarmMapMainModLowAirFlow INTEGER,
- airFMSysAlarmMapMainModAirBlckIntOpen INTEGER,
- airFMSysAlarmMapMainModWaterDetected INTEGER
- }
-
- airFMSysAlarmMapMainModOutputIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index of the output relay."
- ::= { airFMSysAlarmMapMainModEntry 1 }
- airFMSysAlarmMapMainModAnyAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Main Module alarm map setting for Any Alarm.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapMainModEntry 2 }
- airFMSysAlarmMapMainModMaintReq OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Main Module alarm map setting for Module Maintenance
- Required.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapMainModEntry 3 }
- airFMSysAlarmMapMainModCoolFail OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Main Module alarm map setting for Module Cooling
- Failure.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapMainModEntry 4 }
- airFMSysAlarmMapMainModHighSupplyTemp OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Main Module alarm map setting for High Supply
- Temperature.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapMainModEntry 5 }
- airFMSysAlarmMapMainModLowSupplyTemp OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Main Module alarm map setting for Low Supply
- Temperature.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapMainModEntry 6 }
- airFMSysAlarmMapMainModHumFail OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Main Module alarm map setting for Humidifier Failure.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapMainModEntry 7 }
- airFMSysAlarmMapMainModHumReplCyl OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Main Module alarm map setting for Humidifier Replace
- Cylinder.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapMainModEntry 8 }
- airFMSysAlarmMapMainModCondPumpFail OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Main Module alarm map setting for Condensate Pump
- Failure.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapMainModEntry 9 }
- airFMSysAlarmMapMainModBlwrCntl1Fail OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Main Module alarm map setting for Blower Controller 1
- Failure.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapMainModEntry 10 }
- airFMSysAlarmMapMainModBlwrCntl2Fail OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Main Module alarm map setting for Blower Controller 2
- Failure.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapMainModEntry 11 }
- airFMSysAlarmMapMainModHighFltrDP OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Main Module alarm map setting for High Filter
- Differential Pressure.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapMainModEntry 12 }
- airFMSysAlarmMapMainModLowAirFlow OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Main Module alarm map setting for Low Air Flow.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapMainModEntry 13 }
- airFMSysAlarmMapMainModAirBlckIntOpen OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Main Module alarm map setting for Air Block Interlock
- Open.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapMainModEntry 14 }
- airFMSysAlarmMapMainModWaterDetected OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Main Module alarm map setting for Water Detected.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapMainModEntry 15 }
- -- airFM Exp Module 1 Output Alarm Mapping
- airFMSysAlarmMapExpMod1TableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the airFMSysAlarmMapExpMod1Table. "
- ::= { airFMSysAlarmMapExpMod1 1 }
- airFMSysAlarmMapExpMod1Table OBJECT-TYPE
- SYNTAX SEQUENCE OF AirFMSysAlarmMapExpMod1Entry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting alarm map information."
- ::= { airFMSysAlarmMapExpMod1 2 }
- airFMSysAlarmMapExpMod1Entry OBJECT-TYPE
- SYNTAX AirFMSysAlarmMapExpMod1Entry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The expansion module 1 alarm map type to reference."
- INDEX { airFMSysAlarmMapExpMod1OutputIndex }
- ::= { airFMSysAlarmMapExpMod1Table 1 }
- AirFMSysAlarmMapExpMod1Entry ::=
- SEQUENCE {
- airFMSysAlarmMapExpMod1OutputIndex INTEGER,
- airFMSysAlarmMapExpMod1AnyAlarm INTEGER,
- airFMSysAlarmMapExpMod1MaintReq INTEGER,
- airFMSysAlarmMapExpMod1CoolFail INTEGER,
- airFMSysAlarmMapExpMod1HighSupplyTemp INTEGER,
- airFMSysAlarmMapExpMod1LowSupplyTemp INTEGER,
- airFMSysAlarmMapExpMod1HumFail INTEGER,
- airFMSysAlarmMapExpMod1HumReplCyl INTEGER,
- airFMSysAlarmMapExpMod1CondPumpFail INTEGER,
- airFMSysAlarmMapExpMod1BlwrCntl1Fail INTEGER,
- airFMSysAlarmMapExpMod1BlwrCntl2Fail INTEGER,
- airFMSysAlarmMapExpMod1HighFltrDP INTEGER,
- airFMSysAlarmMapExpMod1LowAirFlow INTEGER,
- airFMSysAlarmMapExpMod1AirBlckIntOpen INTEGER,
- airFMSysAlarmMapExpMod1WaterDetected INTEGER
- }
-
- airFMSysAlarmMapExpMod1OutputIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index of the output relay."
- ::= { airFMSysAlarmMapExpMod1Entry 1 }
- airFMSysAlarmMapExpMod1AnyAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Exp Module 1 alarm map setting for Any Alarm.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapExpMod1Entry 2 }
- airFMSysAlarmMapExpMod1MaintReq OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Exp Module 1 alarm map setting for Module Maintenance
- Required.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapExpMod1Entry 3 }
- airFMSysAlarmMapExpMod1CoolFail OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Exp Module 1 alarm map setting for Module Cooling
- Failure.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapExpMod1Entry 4 }
- airFMSysAlarmMapExpMod1HighSupplyTemp OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Exp Module 1 alarm map setting for High Supply
- Temperature.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapExpMod1Entry 5 }
- airFMSysAlarmMapExpMod1LowSupplyTemp OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Exp Module 1 alarm map setting for Low Supply
- Temperature.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapExpMod1Entry 6 }
- airFMSysAlarmMapExpMod1HumFail OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Exp Module 1 alarm map setting for Humidifier Failure.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapExpMod1Entry 7 }
- airFMSysAlarmMapExpMod1HumReplCyl OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Exp Module 1 alarm map setting for Humidifier Replace
- Cylinder.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapExpMod1Entry 8 }
- airFMSysAlarmMapExpMod1CondPumpFail OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Exp Module 1 alarm map setting for Condensate Pump
- Failure.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapExpMod1Entry 9 }
- airFMSysAlarmMapExpMod1BlwrCntl1Fail OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Exp Module 1 alarm map setting for Blower Controller 1
- Failure.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapExpMod1Entry 10 }
- airFMSysAlarmMapExpMod1BlwrCntl2Fail OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Exp Module 1 alarm map setting for Blower Controller 2
- Failure.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapExpMod1Entry 11 }
- airFMSysAlarmMapExpMod1HighFltrDP OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Exp Module 1 alarm map setting for High Filter
- Differential Pressure.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapExpMod1Entry 12 }
- airFMSysAlarmMapExpMod1LowAirFlow OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Exp Module 1 alarm map setting for Low Air Flow.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapExpMod1Entry 13 }
- airFMSysAlarmMapExpMod1AirBlckIntOpen OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Exp Module 1 alarm map setting for Air Block Interlock
- Open.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapExpMod1Entry 14 }
- airFMSysAlarmMapExpMod1WaterDetected OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Exp Module 1 alarm map setting for Water Detected.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapExpMod1Entry 15 }
- -- airFM Expansion Module 2 Output Alarm Mapping
- airFMSysAlarmMapExpMod2TableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the
- airFMSysAlarmMapExpMod2Table."
- ::= { airFMSysAlarmMapExpMod2 1 }
- airFMSysAlarmMapExpMod2Table OBJECT-TYPE
- SYNTAX SEQUENCE OF AirFMSysAlarmMapExpMod2Entry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting alarm map information."
- ::= { airFMSysAlarmMapExpMod2 2 }
- airFMSysAlarmMapExpMod2Entry OBJECT-TYPE
- SYNTAX AirFMSysAlarmMapExpMod2Entry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The expansion module 2 alarm map type to reference."
- INDEX { airFMSysAlarmMapExpMod2OutputIndex }
- ::= { airFMSysAlarmMapExpMod2Table 1 }
- AirFMSysAlarmMapExpMod2Entry ::=
- SEQUENCE {
- airFMSysAlarmMapExpMod2OutputIndex INTEGER,
- airFMSysAlarmMapExpMod2AnyAlarm INTEGER,
- airFMSysAlarmMapExpMod2MaintReq INTEGER,
- airFMSysAlarmMapExpMod2CoolFail INTEGER,
- airFMSysAlarmMapExpMod2HighSupplyTemp INTEGER,
- airFMSysAlarmMapExpMod2LowSupplyTemp INTEGER,
- airFMSysAlarmMapExpMod2HumFail INTEGER,
- airFMSysAlarmMapExpMod2HumReplCyl INTEGER,
- airFMSysAlarmMapExpMod2CondPumpFail INTEGER,
- airFMSysAlarmMapExpMod2BlwrCntl1Fail INTEGER,
- airFMSysAlarmMapExpMod2BlwrCntl2Fail INTEGER,
- airFMSysAlarmMapExpMod2HighFltrDP INTEGER,
- airFMSysAlarmMapExpMod2LowAirFlow INTEGER,
- airFMSysAlarmMapExpMod2AirBlckIntOpen INTEGER,
- airFMSysAlarmMapExpMod2WaterDetected INTEGER
- }
-
- airFMSysAlarmMapExpMod2OutputIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index of the output relay."
- ::= { airFMSysAlarmMapExpMod2Entry 1 }
- airFMSysAlarmMapExpMod2AnyAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Exp Module 2 alarm map setting for Any Alarm.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapExpMod2Entry 2 }
- airFMSysAlarmMapExpMod2MaintReq OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Exp Module 2 alarm map setting for Module Maintenance
- Required.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapExpMod2Entry 3 }
- airFMSysAlarmMapExpMod2CoolFail OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Exp Module 2 alarm map setting for Module Cooling
- Failure.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapExpMod2Entry 4 }
- airFMSysAlarmMapExpMod2HighSupplyTemp OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Exp Module 2 alarm map setting for High Supply
- Temperature.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapExpMod2Entry 5 }
- airFMSysAlarmMapExpMod2LowSupplyTemp OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Exp Module 2 alarm map setting for Low Supply
- Temperature.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapExpMod2Entry 6 }
- airFMSysAlarmMapExpMod2HumFail OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Exp Module 2 alarm map setting for Humidifier Failure.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapExpMod2Entry 7 }
- airFMSysAlarmMapExpMod2HumReplCyl OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Exp Module 2 alarm map setting for Humidifier Replace
- Cylinder.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapExpMod2Entry 8 }
- airFMSysAlarmMapExpMod2CondPumpFail OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Exp Module 2 alarm map setting for Condensate Pump
- Failure.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapExpMod2Entry 9 }
- airFMSysAlarmMapExpMod2BlwrCntl1Fail OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Exp Module 2 alarm map setting for Blower Controller 1
- Failure.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapExpMod2Entry 10 }
- airFMSysAlarmMapExpMod2BlwrCntl2Fail OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Exp Module 2 alarm map setting for Blower Controller 2
- Failure.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapExpMod2Entry 11 }
- airFMSysAlarmMapExpMod2HighFltrDP OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Exp Module 2 alarm map setting for High Filter
- Differential Pressure.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapExpMod2Entry 12 }
- airFMSysAlarmMapExpMod2LowAirFlow OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Exp Module 2 alarm map setting for Low Air Flow.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapExpMod2Entry 13 }
- airFMSysAlarmMapExpMod2AirBlckIntOpen OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Exp Module 2 alarm map setting for Air Block Interlock
- Open.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapExpMod2Entry 14 }
- airFMSysAlarmMapExpMod2WaterDetected OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Exp Module 2 alarm map setting for Water Detected.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapExpMod2Entry 15 }
- -- airFM Input Alarm Mapping
- airFMSysAlarmMapInputTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the airFMSysAlarmMapInputTable. "
- ::= { airFMSysAlarmMapInput 1 }
- airFMSysAlarmMapInputTable OBJECT-TYPE
- SYNTAX SEQUENCE OF AirFMSysAlarmMapInputEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting alarm map information."
- ::= { airFMSysAlarmMapInput 2 }
- airFMSysAlarmMapInputEntry OBJECT-TYPE
- SYNTAX AirFMSysAlarmMapInputEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The input contact alarm map type to reference."
- INDEX { airFMSysAlarmMapInputOutputIndex }
- ::= { airFMSysAlarmMapInputTable 1 }
- AirFMSysAlarmMapInputEntry ::=
- SEQUENCE {
- airFMSysAlarmMapInputOutputIndex INTEGER,
- airFMSysAlarmMapInput1 INTEGER,
- airFMSysAlarmMapInput2 INTEGER,
- airFMSysAlarmMapInput3 INTEGER,
- airFMSysAlarmMapInput4 INTEGER,
- airFMSysAlarmMapInput5 INTEGER,
- airFMSysAlarmMapInput6 INTEGER,
- airFMSysAlarmMapInput7 INTEGER,
- airFMSysAlarmMapInput8 INTEGER,
- airFMSysAlarmMapInput9 INTEGER,
- airFMSysAlarmMapInput10 INTEGER,
- airFMSysAlarmMapInput11 INTEGER,
- airFMSysAlarmMapInput12 INTEGER,
- airFMSysAlarmMapInput13 INTEGER,
- airFMSysAlarmMapInput14 INTEGER,
- airFMSysAlarmMapInput15 INTEGER,
- airFMSysAlarmMapInput16 INTEGER
- }
-
- airFMSysAlarmMapInputOutputIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index of the output relay."
- ::= { airFMSysAlarmMapInputEntry 1 }
- airFMSysAlarmMapInput1 OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Input contact 1 alarm map setting.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapInputEntry 2 }
- airFMSysAlarmMapInput2 OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Input contact 2 alarm map setting.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapInputEntry 3 }
- airFMSysAlarmMapInput3 OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Input contact 3 alarm map setting.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapInputEntry 4 }
- airFMSysAlarmMapInput4 OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Input contact 4 alarm map setting.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapInputEntry 5 }
- airFMSysAlarmMapInput5 OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Input contact 5 alarm map setting.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapInputEntry 6 }
- airFMSysAlarmMapInput6 OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Input contact 6 alarm map setting.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapInputEntry 7 }
- airFMSysAlarmMapInput7 OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Input contact 7 alarm map setting.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapInputEntry 8 }
- airFMSysAlarmMapInput8 OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Input contact 8 alarm map setting.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapInputEntry 9 }
- airFMSysAlarmMapInput9 OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Input contact 9 alarm map setting.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapInputEntry 10 }
- airFMSysAlarmMapInput10 OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Input contact 10 alarm map setting.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapInputEntry 11 }
- airFMSysAlarmMapInput11 OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Input contact 11 alarm map setting.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapInputEntry 12 }
- airFMSysAlarmMapInput12 OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Input contact 12 alarm map setting.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapInputEntry 13 }
- airFMSysAlarmMapInput13 OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Input contact 13 alarm map setting.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapInputEntry 14 }
- airFMSysAlarmMapInput14 OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Input contact 14 alarm map setting.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapInputEntry 15 }
- airFMSysAlarmMapInput15 OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Input contact 15 alarm map setting.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapInputEntry 16 }
- airFMSysAlarmMapInput16 OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Input contact 16 alarm map setting.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapInputEntry 17 }
- -- airFM Output Alarm Mapping
- airFMSysAlarmMapOutputTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the
- airFMSysAlarmMapOutputTable. "
- ::= { airFMSysAlarmMapOutput 1 }
- airFMSysAlarmMapOutputTable OBJECT-TYPE
- SYNTAX SEQUENCE OF AirFMSysAlarmMapOutputEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting alarm map information."
- ::= { airFMSysAlarmMapOutput 2 }
- airFMSysAlarmMapOutputEntry OBJECT-TYPE
- SYNTAX AirFMSysAlarmMapOutputEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The input contact alarm map type to reference."
- INDEX { airFMSysAlarmMapOutputIndex }
- ::= { airFMSysAlarmMapOutputTable 1 }
- AirFMSysAlarmMapOutputEntry ::=
- SEQUENCE {
- airFMSysAlarmMapOutputIndex INTEGER,
- airFMSysAlarmMapOutput1 INTEGER,
- airFMSysAlarmMapOutput2 INTEGER,
- airFMSysAlarmMapOutput3 INTEGER,
- airFMSysAlarmMapOutput4 INTEGER,
- airFMSysAlarmMapOutput5 INTEGER,
- airFMSysAlarmMapOutput6 INTEGER,
- airFMSysAlarmMapOutput7 INTEGER,
- airFMSysAlarmMapOutput8 INTEGER,
- airFMSysAlarmMapOutput9 INTEGER,
- airFMSysAlarmMapOutput10 INTEGER,
- airFMSysAlarmMapOutput11 INTEGER,
- airFMSysAlarmMapOutput12 INTEGER,
- airFMSysAlarmMapOutput13 INTEGER,
- airFMSysAlarmMapOutput14 INTEGER,
- airFMSysAlarmMapOutput15 INTEGER,
- airFMSysAlarmMapOutput16 INTEGER
- }
-
- airFMSysAlarmMapOutputIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index of the output relay."
- ::= { airFMSysAlarmMapOutputEntry 1 }
- airFMSysAlarmMapOutput1 OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Output relay 1 alarm map setting.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapOutputEntry 2 }
- airFMSysAlarmMapOutput2 OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Output relay 2 alarm map setting.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapOutputEntry 3 }
- airFMSysAlarmMapOutput3 OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Output relay 3 alarm map setting.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapOutputEntry 4 }
- airFMSysAlarmMapOutput4 OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Output relay 4 alarm map setting.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapOutputEntry 5 }
- airFMSysAlarmMapOutput5 OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Output relay 5 alarm map setting.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapOutputEntry 6 }
- airFMSysAlarmMapOutput6 OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Output relay 6 alarm map setting.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapOutputEntry 7 }
- airFMSysAlarmMapOutput7 OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Output relay 7 alarm map setting.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapOutputEntry 8 }
- airFMSysAlarmMapOutput8 OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Output relay 8 alarm map setting.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapOutputEntry 9 }
- airFMSysAlarmMapOutput9 OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Output relay 9 alarm map setting.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapOutputEntry 10 }
- airFMSysAlarmMapOutput10 OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Output relay 10 alarm map setting.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapOutputEntry 11 }
- airFMSysAlarmMapOutput11 OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Output relay 11 alarm map setting.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapOutputEntry 12 }
- airFMSysAlarmMapOutput12 OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Output relay 12 alarm map setting.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapOutputEntry 13 }
- airFMSysAlarmMapOutput13 OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Output relay 13 alarm map setting.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapOutputEntry 14 }
- airFMSysAlarmMapOutput14 OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Output relay 14 alarm map setting.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapOutputEntry 15 }
- airFMSysAlarmMapOutput15 OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Output relay 15 alarm map setting.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapOutputEntry 16 }
- airFMSysAlarmMapOutput16 OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- disabled (2),
- enabled (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Output relay 16 alarm map setting.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMSysAlarmMapOutputEntry 17 }
- -- airFM Module Identification Table
- airFMModIdentTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the airFMModIdentTable. "
- ::= { airFMModIdent 1 }
- airFMModIdentTable OBJECT-TYPE
- SYNTAX SEQUENCE OF AirFMModIdentEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting information from each module in
- the system. "
- ::= { airFMModIdent 2 }
- airFMModIdentEntry OBJECT-TYPE
- SYNTAX AirFMModIdentEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The module to get information from."
- INDEX { airFMModIdentModuleIndex }
- ::= { airFMModIdentTable 1 }
- AirFMModIdentEntry ::=
- SEQUENCE {
- airFMModIdentModuleIndex INTEGER,
- airFMModModelNumber DisplayString,
- airFMModSerialNumber DisplayString,
- airFMModManufactureDate DisplayString,
- airFMModFirmwareRev DisplayString,
- airFMModHardwareRev DisplayString
- }
-
- airFMModIdentModuleIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index of the module."
- ::= { airFMModIdentEntry 1 }
- airFMModModelNumber OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Model number of the Module."
- ::= { airFMModIdentEntry 2 }
- airFMModSerialNumber OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unique identification number for this Module."
- ::= { airFMModIdentEntry 3 }
- airFMModManufactureDate OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Date the Module was manufactured."
- ::= { airFMModIdentEntry 4 }
- airFMModFirmwareRev OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Revision number of the firmware installed on this
- Module."
- ::= { airFMModIdentEntry 5 }
- airFMModHardwareRev OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Revision number of the hardware installed on this
- Module."
- ::= { airFMModIdentEntry 6 }
- -- airFM Module Status Table
- airFMModStatusTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the airFMModStatusTable. "
- ::= { airFMModStatus 1 }
- airFMModStatusTable OBJECT-TYPE
- SYNTAX SEQUENCE OF AirFMModStatusEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting information from each module in
- the system. "
- ::= { airFMModStatus 2 }
- airFMModStatusEntry OBJECT-TYPE
- SYNTAX AirFMModStatusEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The module to get information from."
- INDEX { airFMModStatusModuleIndex }
- ::= { airFMModStatusTable 1 }
- AirFMModStatusEntry ::=
- SEQUENCE {
- airFMModStatusModuleIndex INTEGER,
- airFMModSupplyTempC INTEGER,
- airFMModSupplyTempF INTEGER,
- airFMModSupplyHum INTEGER,
- airFMModReturnTempC INTEGER,
- airFMModReturnTempF INTEGER,
- airFMModReturnHum INTEGER,
- airFMModFilterDiffPresPa INTEGER,
- airFMModFilterDiffPresInWC INTEGER,
- airFMModCoilDiffPresPa INTEGER,
- airFMModCoilDiffPresInWC INTEGER
- }
-
- airFMModStatusModuleIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index of the module."
- ::= { airFMModStatusEntry 1 }
- airFMModSupplyTempC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The temperature measured at the supply sensor.
- Measured in tenths of degrees Celsius.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModStatusEntry 2 }
- airFMModSupplyTempF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The temperature measured at the supply sensor.
- Measured in tenths of degrees Fahrenheit.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModStatusEntry 3 }
- airFMModSupplyHum OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The humidity measured at the supply sensor.
- Measured in tenths of percent relative humidity.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModStatusEntry 4 }
- airFMModReturnTempC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The temperature measured at the return sensor.
- Measured in tenths of degrees Celsius.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModStatusEntry 5 }
- airFMModReturnTempF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The temperature measured at the return sensor.
- Measured in tenths of degrees Fahrenheit.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModStatusEntry 6 }
- airFMModReturnHum OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The humidity measured at the return sensor.
- Measured in tenths of percent relative humidity.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModStatusEntry 7 }
- airFMModFilterDiffPresPa OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The difference in pressure on either side of the air
- filters. A high differential pressure indicates a
- clogged filter. Measured in Pascals.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModStatusEntry 8 }
- airFMModFilterDiffPresInWC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The difference in pressure on either side of the air
- filters. A high differential pressure indicates a
- clogged filter. Measured in hundredths of inches
- water column.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModStatusEntry 9 }
- airFMModCoilDiffPresPa OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The difference in pressure on either side of the
- cooling/dehumidification coils. Measured in Pascals.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModStatusEntry 10 }
- airFMModCoilDiffPresInWC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The difference in pressure on either side of the
- cooling/dehumidification coils. Measured in
- hundredths of inches water column.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModStatusEntry 11 }
- -- airFM Module Properties Table
- airFMModPropTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the airFMModPropTable. "
- ::= { airFMModProperties 1 }
- airFMModPropTable OBJECT-TYPE
- SYNTAX SEQUENCE OF AirFMModPropEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting information from each module in
- the system. "
- ::= { airFMModProperties 2 }
- airFMModPropEntry OBJECT-TYPE
- SYNTAX AirFMModPropEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The module to get information from."
- INDEX { airFMModPropModuleIndex }
- ::= { airFMModPropTable 1 }
- AirFMModPropEntry ::=
- SEQUENCE {
- airFMModPropModuleIndex INTEGER,
- airFMModOutputCapacity INTEGER,
- airFMModCapacityCtrl INTEGER,
- airFMModHeaterType INTEGER,
- airFMModElectricHeaterType INTEGER,
- airFMModHumidifierType INTEGER,
- airFMModBlwrFreqSetting INTEGER,
- airFMModNomCoilDiffPresPa INTEGER,
- airFMModNomCoilDiffPresInWC INTEGER,
- airFMModCondPump INTEGER,
- airFMModFireDetector INTEGER,
- airFMModSmokeDetector INTEGER,
- airFMModWaterDetector INTEGER
- }
-
- airFMModPropModuleIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index of the module."
- ::= { airFMModPropEntry 1 }
- airFMModOutputCapacity OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- kw45 (2),
- kw35 (3),
- kw40 (4),
- kw50 (5),
- kw80 (6)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The cooling capacity (in Kilowatts) of the displayed
- Module.
- A value of notApplicable indicates that this OID
- does not apply to this device due to its configuration."
- ::= { airFMModPropEntry 2 }
- airFMModCapacityCtrl OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- tandem (2),
- hotGasBypass (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The method used to load and unload the compressors.
- Tandem compressor Modules use two stages (one
- compressor each). Single compressor Modules use hot
- gas bypass.
- A value of notApplicable indicates that this OID
- does not apply to this device due to its configuration."
- ::= { airFMModPropEntry 3 }
- airFMModHeaterType OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- none (2),
- electricSCR (3),
- steam (4),
- hotWaterOnOff (5),
- hotGasReheat (6),
- hotGasAndElectric (7),
- hotWaterProp (8)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The type of reheating device installed in this Module.
- A value of notApplicable indicates that this OID
- does not apply to this device due to its configuration."
- ::= { airFMModPropEntry 4 }
- airFMModElectricHeaterType OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- kw10 (2),
- kw15 (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The type/capacity of the electric heater, if installed.
- A value of notApplicable indicates that this OID
- does not apply to this device due to its configuration."
- ::= { airFMModPropEntry 5 }
- airFMModHumidifierType OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- none (2),
- steamElectrode (3),
- liveSteam (4)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The type of equipment installed in the Module to run
- the humidification mode.
- A value of notApplicable indicates that this OID
- does not apply to this device due to its configuration."
- ::= { airFMModPropEntry 6 }
- airFMModBlwrFreqSetting OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Frequency of the blower in tenths of hertz.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModPropEntry 7 }
- airFMModNomCoilDiffPresPa OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The difference in pressure on either side of the
- cooling/dehumidification coils. Measured in Pascals.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModPropEntry 8 }
- airFMModNomCoilDiffPresInWC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The difference in pressure on either side of the
- cooling/dehumidification coils. Measured in
- hundredths of inches water column.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModPropEntry 9 }
- airFMModCondPump OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- notPresent (2),
- present (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Indicates the presence of a condensate pump in the
- Modules of this System.
- A value of notApplicable indicates that this OID
- does not apply to this device due to its configuration."
- ::= { airFMModPropEntry 10 }
- airFMModFireDetector OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- notPresent (2),
- present (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Indicates the presence of a fire detector for each
- of the Modules in this System.
- A value of notApplicable indicates that this OID
- does not apply to this device due to its configuration."
- ::= { airFMModPropEntry 11 }
- airFMModSmokeDetector OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- notPresent (2),
- present (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Indicates the presence of a smoke detector for each
- of the Modules in this System.
- A value of notApplicable indicates that this OID
- does not apply to this device due to its configuration."
- ::= { airFMModPropEntry 12 }
- airFMModWaterDetector OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- notPresent (2),
- present (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Indicates the presence of a water leak detector for
- each of the Modules in this System.
- A value of notApplicable indicates that this OID
- does not apply to this device due to its configuration."
- ::= { airFMModPropEntry 13 }
- -- airFM Module Cooling Table
- airFMModCoolTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the airFMModCoolTable. "
- ::= { airFMModCooling 1 }
- airFMModCoolTable OBJECT-TYPE
- SYNTAX SEQUENCE OF AirFMModCoolEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting information from each module in
- the system. "
- ::= { airFMModCooling 2 }
- airFMModCoolEntry OBJECT-TYPE
- SYNTAX AirFMModCoolEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The module to get information from."
- INDEX { airFMModCoolModuleIndex }
- ::= { airFMModCoolTable 1 }
- AirFMModCoolEntry ::=
- SEQUENCE {
- airFMModCoolModuleIndex INTEGER,
- airFMModComp1 INTEGER,
- airFMModComp2 INTEGER,
- airFMModSuctPresKPa INTEGER,
- airFMModSuctPresPSI INTEGER,
- airFMModDischPresKPa INTEGER,
- airFMModDischPresPSI INTEGER,
- airFMModCondFluidVlvPos INTEGER,
- airFMModCoilFluidVlvPos INTEGER
- }
-
- airFMModCoolModuleIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index of the module."
- ::= { airFMModCoolEntry 1 }
- airFMModComp1 OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- on (2),
- off (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The status of compressor 1 of the tandem compressor
- unit (on or off).
- A value of notApplicable indicates that this OID
- does not apply to this device due to its configuration."
- ::= { airFMModCoolEntry 2 }
- airFMModComp2 OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- on (2),
- off (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The status of compressor 2 of the tandem compressor
- unit (on or off).
- A value of notApplicable indicates that this OID
- does not apply to this device due to its configuration."
- ::= { airFMModCoolEntry 3 }
- airFMModSuctPresKPa OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The refrigerant pressure measured at the suction
- inlet of the compressor. Measured in kiloPascals.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModCoolEntry 4 }
- airFMModSuctPresPSI OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The refrigerant pressure measured at the suction
- inlet of the compressor. Measured in pounds per
- square inch.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModCoolEntry 5 }
- airFMModDischPresKPa OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The refrigerant pressure measured at the discharge
- outlet of the compressor. Measured in kiloPascals.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModCoolEntry 6 }
- airFMModDischPresPSI OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The refrigerant pressure measured at the discharge
- outlet of the compressor. Measured in pounds per
- square inch.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModCoolEntry 7 }
- airFMModCondFluidVlvPos OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The position of the condenser fluid valve. The valve
- regulates the flow of liquid coolant into the heat
- exchanger (condenser). 100% indicates the valve is
- completely open, and 0% indicates that the valve is
- closed. Measured in percent.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModCoolEntry 8 }
- airFMModCoilFluidVlvPos OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The position of the coil fluid valve. The valve
- regulates the flow of liquid coolant in the fluid
- cooling coil (MultiCool, Economizer, or Chilled
- Water). 100% indicates the valve is completely open,
- and 0% indicates that the valve is closed. Measured
- in percent.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModCoolEntry 9 }
- -- airFM Module Humidity Control Table
- airFMModHumTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the airFMModHumTable. "
- ::= { airFMModHumidity 1 }
- airFMModHumTable OBJECT-TYPE
- SYNTAX SEQUENCE OF AirFMModHumEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting information from each module in
- the system. "
- ::= { airFMModHumidity 2 }
- airFMModHumEntry OBJECT-TYPE
- SYNTAX AirFMModHumEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The module to get information from."
- INDEX { airFMModHumModuleIndex }
- ::= { airFMModHumTable 1 }
- AirFMModHumEntry ::=
- SEQUENCE {
- airFMModHumModuleIndex INTEGER,
- airFMModHumidifier INTEGER,
- airFMModElectrodeCurrent INTEGER,
- airFMModHumActualOutput INTEGER,
- airFMModWaterConductivity INTEGER,
- airFMModHotWaterVlvPos INTEGER,
- airFMModStmElectHumMode INTEGER
- }
-
- airFMModHumModuleIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index of the module."
- ::= { airFMModHumEntry 1 }
- airFMModHumidifier OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- none (2),
- steamElectrode (3),
- liveSteam (4)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The type of equipment installed in the Module to run
- the humidification mode.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModHumEntry 2 }
- airFMModElectrodeCurrent OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The current drawn by the electrodes of the steam
- cylinder humidifier. Measured in tenths of amps.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModHumEntry 3 }
- airFMModHumActualOutput OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The humidification output of an individual Module.
- Measured in percent.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModHumEntry 4 }
- airFMModWaterConductivity OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The conductivity of the water in the humidifier
- cylinder. Measured in microSiemens per centimeter.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModHumEntry 5 }
- airFMModHotWaterVlvPos OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The position of the hot water valve. 100% indicates
- the valve is completely open, and 0% indicates that
- the valve is closed. Measured in percent.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModHumEntry 6 }
- airFMModStmElectHumMode OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- off (2),
- auto (3),
- drain (4)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Set the humidifier function mode.
- Off: Remove power from electrodes.
- Auto: Humidifier controlled by Module controller.
- Drain: Remove power from electrodes and drain the cylinder.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModHumEntry 7 }
- -- airFM Module Blower 1 Table
- airFMModBlwr1TableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the airFMModBlwr1Table. "
- ::= { airFMModBlower1 1 }
- airFMModBlwr1Table OBJECT-TYPE
- SYNTAX SEQUENCE OF AirFMModBlwr1Entry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting information from each module in
- the system. "
- ::= { airFMModBlower1 2 }
- airFMModBlwr1Entry OBJECT-TYPE
- SYNTAX AirFMModBlwr1Entry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The module to get information from."
- INDEX { airFMModBlwr1ModuleIndex }
- ::= { airFMModBlwr1Table 1 }
- AirFMModBlwr1Entry ::=
- SEQUENCE {
- airFMModBlwr1ModuleIndex INTEGER,
- airFMModBlwr1CtrlType INTEGER,
- airFMModBlwr1CmdFreq INTEGER,
- airFMModBlwr1ActFreq INTEGER,
- airFMModBlwr1Poles INTEGER,
- airFMModBlwr1RatedHorsePower INTEGER,
- airFMModBlwr1RatedCurrent INTEGER,
- airFMModBlwr1ActTorq INTEGER,
- airFMModBlwr1Current INTEGER,
- airFMModBlwr1Vlt INTEGER,
- airFMModBlwr1DCLinkVlt INTEGER,
- airFMModBlwr1AccTime INTEGER,
- airFMModBlwr1DecTime INTEGER,
- airFMModBlwr1CapLife INTEGER,
- airFMModBlwr1CtrlCoolFanLife INTEGER,
- airFMModBlwr1ElOvMode INTEGER,
- airFMModBlwr1ElOvSetting INTEGER,
- airFMModBlwr1ElOvTimeConst INTEGER,
- airFMModBlwr1FanPower INTEGER,
- airFMModBlwr1HeatsinkTempC INTEGER,
- airFMModBlwr1HeatsinkTempF INTEGER,
- airFMModBlwr1ChokeTempC INTEGER,
- airFMModBlwr1ChokeTempF INTEGER,
- airFMModBlwr1InverterTempC INTEGER,
- airFMModBlwr1InverterTempF INTEGER
- }
-
- airFMModBlwr1ModuleIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index of the module."
- ::= { airFMModBlwr1Entry 1 }
- airFMModBlwr1CtrlType OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- fujiVFD (2),
- ecController (3),
- danfossVFD (4)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The type of blower controller.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModBlwr1Entry 2 }
- airFMModBlwr1CmdFreq OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The requested operating frequency for the blower.
- Measured in tenths of hertz.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModBlwr1Entry 3 }
- airFMModBlwr1ActFreq OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The frequency at which the blower controller is
- operating. Measured in tenths of hertz.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModBlwr1Entry 4 }
- airFMModBlwr1Poles OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of poles of the blower motor that the
- blower controller is controlling.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModBlwr1Entry 5 }
- airFMModBlwr1RatedHorsePower OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The power rating of the blower motor. Measured in
- hundredths of horsepower.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModBlwr1Entry 6 }
- airFMModBlwr1RatedCurrent OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The current rating of the blower motor. Measured in
- hundredths of amps.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModBlwr1Entry 7 }
- airFMModBlwr1ActTorq OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The actual torque of the blower motor. Measured in
- hundredths of percent.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModBlwr1Entry 8 }
- airFMModBlwr1Current OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The percent of rated current drawn by the blower
- motor. Measured in hundredths of percent.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModBlwr1Entry 9 }
- airFMModBlwr1Vlt OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The voltage supplied to the blower motor. Measured
- in tenths of volts RMS.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModBlwr1Entry 10 }
- airFMModBlwr1DCLinkVlt OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The voltage of the blower controller's DC bus.
- Measured in volts DC.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModBlwr1Entry 11 }
- airFMModBlwr1AccTime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The time to accelerate the blower to the specified
- frequency. Measured in tenths of seconds.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModBlwr1Entry 12 }
- airFMModBlwr1DecTime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The time to decelerate the blower frequency to zero.
- Measured in tenths of seconds.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModBlwr1Entry 13 }
- airFMModBlwr1CapLife OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The remaining life of the main circuit capacitor.
- Measured in tenths of percent.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModBlwr1Entry 14 }
- airFMModBlwr1CtrlCoolFanLife OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The total operation time of the blower controller
- cooling fan. Measured in hours.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModBlwr1Entry 15 }
- airFMModBlwr1ElOvMode OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- inactive (2),
- active (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Enables or disables the electronic overload relay.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModBlwr1Entry 16 }
- airFMModBlwr1ElOvSetting OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The electronic overload relay is activated when the
- current exceeds this threshold. Measured in
- hundredths of amps.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModBlwr1Entry 17 }
- airFMModBlwr1ElOvTimeConst OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The delay between the current exceeding the overload
- threshold and the activation of the electronic
- overload relay. Measured in tenths of minutes.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModBlwr1Entry 18 }
- airFMModBlwr1FanPower OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The actual power of the blower motor. Measured in
- tenths of percent.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModBlwr1Entry 19 }
- airFMModBlwr1HeatsinkTempC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The temperature of the heatsink on the blower
- controller. Measured in degrees Celsius.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModBlwr1Entry 20 }
- airFMModBlwr1HeatsinkTempF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The temperature of the heatsink on the blower
- controller. Measured in degrees Fahrenheit.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModBlwr1Entry 21 }
- airFMModBlwr1ChokeTempC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The temperature of the choke on the blower
- controller. Measured in degrees Celsius.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModBlwr1Entry 22 }
- airFMModBlwr1ChokeTempF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The temperature of the choke on the blower
- controller. Measured in degrees Fahrenheit.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModBlwr1Entry 23 }
- airFMModBlwr1InverterTempC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The temperature of the inverter on the blower
- controller. Measured in degrees Celsius.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModBlwr1Entry 24 }
- airFMModBlwr1InverterTempF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The temperature of the inverter on the blower
- controller. Measured in degrees Fahrenheit.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModBlwr1Entry 25 }
- -- airFM Module Blower 2 Table
- airFMModBlwr2TableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the airFMModBlwr2Table. "
- ::= { airFMModBlower2 1 }
- airFMModBlwr2Table OBJECT-TYPE
- SYNTAX SEQUENCE OF AirFMModBlwr2Entry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting information from each module in
- the system. "
- ::= { airFMModBlower2 2 }
- airFMModBlwr2Entry OBJECT-TYPE
- SYNTAX AirFMModBlwr2Entry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The module to get information from."
- INDEX { airFMModBlwr2ModuleIndex }
- ::= { airFMModBlwr2Table 1 }
- AirFMModBlwr2Entry ::=
- SEQUENCE {
- airFMModBlwr2ModuleIndex INTEGER,
- airFMModBlwr2CtrlType INTEGER,
- airFMModBlwr2CmdFreq INTEGER,
- airFMModBlwr2ActFreq INTEGER,
- airFMModBlwr2Poles INTEGER,
- airFMModBlwr2RatedHorsePower INTEGER,
- airFMModBlwr2RatedCurrent INTEGER,
- airFMModBlwr2ActTorq INTEGER,
- airFMModBlwr2Current INTEGER,
- airFMModBlwr2Vlt INTEGER,
- airFMModBlwr2DCLinkVlt INTEGER,
- airFMModBlwr2AccTime INTEGER,
- airFMModBlwr2DecTime INTEGER,
- airFMModBlwr2CapLife INTEGER,
- airFMModBlwr2CtrlCoolFanLife INTEGER,
- airFMModBlwr2ElOvMode INTEGER,
- airFMModBlwr2ElOvSetting INTEGER,
- airFMModBlwr2ElOvTimeConst INTEGER,
- airFMModBlwr2FanPower INTEGER,
- airFMModBlwr2HeatsinkTempC INTEGER,
- airFMModBlwr2HeatsinkTempF INTEGER,
- airFMModBlwr2ChokeTempC INTEGER,
- airFMModBlwr2ChokeTempF INTEGER,
- airFMModBlwr2InverterTempC INTEGER,
- airFMModBlwr2InverterTempF INTEGER
- }
-
- airFMModBlwr2ModuleIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index of the module."
- ::= { airFMModBlwr2Entry 1 }
- airFMModBlwr2CtrlType OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- fujiVFD (2),
- ecController (3),
- danfossVFD (4)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The type of blower controller.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModBlwr2Entry 2 }
- airFMModBlwr2CmdFreq OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The requested operating frequency for the blower.
- Measured in tenths of hertz.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModBlwr2Entry 3 }
- airFMModBlwr2ActFreq OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The frequency at which the blower controller is
- operating. Measured in tenths of hertz.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModBlwr2Entry 4 }
- airFMModBlwr2Poles OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of poles of the blower motor that the
- blower controller is controlling.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModBlwr2Entry 5 }
- airFMModBlwr2RatedHorsePower OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The power rating of the blower motor. Measured in
- hundredths of horsepower.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModBlwr2Entry 6 }
- airFMModBlwr2RatedCurrent OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The current rating of the blower motor. Measured in
- hundredths of amps.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModBlwr2Entry 7 }
- airFMModBlwr2ActTorq OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The actual torque of the blower motor. Measured in
- hundredths of percent.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModBlwr2Entry 8 }
- airFMModBlwr2Current OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The percent of rated current drawn by the blower
- motor. Measured in hundredths of percent.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModBlwr2Entry 9 }
- airFMModBlwr2Vlt OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The voltage supplied to the blower motor. Measured
- in tenths of volts RMS.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModBlwr2Entry 10 }
- airFMModBlwr2DCLinkVlt OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The voltage of the blower controller's DC bus.
- Measured in volts DC.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModBlwr2Entry 11 }
- airFMModBlwr2AccTime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The time to accelerate the blower to the specified
- frequency. Measured in tenths of seconds.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModBlwr2Entry 12 }
- airFMModBlwr2DecTime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The time to decelerate the blower frequency to zero.
- Measured in tenths of seconds.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModBlwr2Entry 13 }
- airFMModBlwr2CapLife OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The remaining life of the main circuit capacitor.
- Measured in tenths of percent.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModBlwr2Entry 14 }
- airFMModBlwr2CtrlCoolFanLife OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The total operation time of the blower controller
- cooling fan. Measured in hours.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModBlwr2Entry 15 }
- airFMModBlwr2ElOvMode OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- inactive (2),
- active (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Enables or disables the electronic overload relay.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModBlwr2Entry 16 }
- airFMModBlwr2ElOvSetting OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The electronic overload relay is activated when the
- current exceeds this threshold. Measured in
- hundredths of amps.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModBlwr2Entry 17 }
- airFMModBlwr2ElOvTimeConst OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The delay between the current exceeding the overload
- threshold and the activation of the electronic
- overload relay. Measured in tenths of minutes.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModBlwr2Entry 18 }
- airFMModBlwr2FanPower OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The actual power of the blower motor. Measured in
- tenths of percent.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModBlwr2Entry 19 }
- airFMModBlwr2HeatsinkTempC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The temperature of the heatsink on the blower
- controller. Measured in degrees Celsius.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModBlwr2Entry 20 }
- airFMModBlwr2HeatsinkTempF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The temperature of the heatsink on the blower
- controller. Measured in degrees Fahrenheit.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModBlwr2Entry 21 }
- airFMModBlwr2ChokeTempC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The temperature of the choke on the blower
- controller. Measured in degrees Celsius.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModBlwr2Entry 22 }
- airFMModBlwr2ChokeTempF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The temperature of the choke on the blower
- controller. Measured in degrees Fahrenheit.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModBlwr2Entry 23 }
- airFMModBlwr2InverterTempC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The temperature of the inverter on the blower
- controller. Measured in degrees Celsius.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModBlwr2Entry 24 }
- airFMModBlwr2InverterTempF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The temperature of the inverter on the blower
- controller. Measured in degrees Fahrenheit.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModBlwr2Entry 25 }
- -- airFM Module Run Hours Table
- airFMModRHTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the airFMModRHTable. "
- ::= { airFMModRunHours 1 }
- airFMModRHTable OBJECT-TYPE
- SYNTAX SEQUENCE OF AirFMModRHEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting information from each module in
- the system. "
- ::= { airFMModRunHours 2 }
- airFMModRHEntry OBJECT-TYPE
- SYNTAX AirFMModRHEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The module to get information from."
- INDEX { airFMModRHModuleIndex }
- ::= { airFMModRHTable 1 }
- AirFMModRHEntry ::=
- SEQUENCE {
- airFMModRHModuleIndex INTEGER,
- airFMModRHComp1 INTEGER,
- airFMModRHComp2 INTEGER,
- airFMModRHHeater INTEGER,
- airFMModRHHum INTEGER,
- airFMModRHBlwr1 INTEGER,
- airFMModRHBlwr2 INTEGER,
- airFMModRHBlwrCtrl1 INTEGER,
- airFMModRHBlwrCtrl2 INTEGER,
- airFMModRHComp1Reset INTEGER,
- airFMModRHComp2Reset INTEGER,
- airFMModRHHeaterReset INTEGER,
- airFMModRHHumReset INTEGER,
- airFMModRHBlwr1Reset INTEGER,
- airFMModRHBlwr2Reset INTEGER
- }
-
- airFMModRHModuleIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index of the module."
- ::= { airFMModRHEntry 1 }
- airFMModRHComp1 OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Compressor 1 run hours.
- A value of -2147483648 indicates that this OID
- does not apply to this device due to its configuration."
- ::= { airFMModRHEntry 2 }
- airFMModRHComp2 OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Compressor 2 run hours.
- A value of -2147483648 indicates that this OID
- does not apply to this device due to its configuration."
- ::= { airFMModRHEntry 3 }
- airFMModRHHeater OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Heater run hours.
- A value of -2147483648 indicates that this OID
- does not apply to this device due to its configuration."
- ::= { airFMModRHEntry 4 }
- airFMModRHHum OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Humidifier run hours
- A value of -2147483648 indicates that this OID
- does not apply to this device due to its configuration."
- ::= { airFMModRHEntry 5 }
- airFMModRHBlwr1 OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Blower 1 run hours.
- A value of -2147483648 indicates that this OID
- does not apply to this device due to its configuration."
- ::= { airFMModRHEntry 6 }
- airFMModRHBlwr2 OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Blower 2 run hours.
- A value of -2147483648 indicates that this OID
- does not apply to this device due to its configuration."
- ::= { airFMModRHEntry 7 }
- airFMModRHBlwrCtrl1 OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Blower Controller 1 run hours.
- A value of -2147483648 indicates that this OID
- does not apply to this device due to its configuration."
- ::= { airFMModRHEntry 8 }
- airFMModRHBlwrCtrl2 OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Blower Controller 2 run hours.
- A value of -2147483648 indicates that this OID
- does not apply to this device due to its configuration."
- ::= { airFMModRHEntry 9 }
- airFMModRHComp1Reset OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- noOperation (2),
- reset (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Reset the compressor 1 run hours.
- Getting this OID will do nothing and return the
- noOperation value.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModRHEntry 10 }
- airFMModRHComp2Reset OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- noOperation (2),
- reset (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Reset the compressor 2 run hours.
- Getting this OID will do nothing and return the
- noOperation value.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModRHEntry 11 }
- airFMModRHHeaterReset OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- noOperation (2),
- reset (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Reset the heater run hours.
- Getting this OID will do nothing and return the
- noOperation value.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModRHEntry 12 }
- airFMModRHHumReset OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- noOperation (2),
- reset (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Reset the humidifier run hours.
- Getting this OID will do nothing and return the
- noOperation value.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModRHEntry 13 }
- airFMModRHBlwr1Reset OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- noOperation (2),
- reset (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Reset the blower 1 run hours.
- Getting this OID will do nothing and return the
- noOperation value.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModRHEntry 14 }
- airFMModRHBlwr2Reset OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- noOperation (2),
- reset (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Reset the blower 2 run hours.
- Getting this OID will do nothing and return the
- noOperation value.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModRHEntry 15 }
- -- airFM Module Service Intervals
- airFMModServIntComp1 OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The interval at which to generate a maintenance alarm
- for compressor 1. Values stored in increments of 100
- hours.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModServIntervals 1 }
- airFMModServIntComp2 OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The interval at which to generate a maintenance alarm
- for compressor 2. Values stored in increments of 100
- hours.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModServIntervals 2 }
- airFMModServIntHeater OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The interval at which to generate a maintenance alarm
- for the reheat components. Values stored in
- increments of 100 hours.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModServIntervals 3 }
- airFMModServIntHum OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The interval at which to generate a maintenance alarm
- for the humidifier. Values stored in increments of
- 100 hours.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModServIntervals 4 }
- airFMModServIntBlwr1 OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The interval at which to generate a maintenance alarm
- for blower 1. Values stored in increments of 100
- hours.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModServIntervals 5 }
- airFMModServIntBlwr2 OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The interval at which to generate a maintenance alarm
- for blower 2. Values stored in increments of 100
- hours.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModServIntervals 6 }
- airFMModServIntBlwrCtrl1 OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The interval at which to generate a maintenance alarm
- for blower controller 1. Values stored in increments
- of 100 hours.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModServIntervals 7 }
- airFMModServIntBlwrCtrl2 OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The interval at which to generate a maintenance alarm
- for blower controller 2. Values stored in increments
- of 100 hours.
- A value of -2147483648 indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModServIntervals 8 }
- -- airFM Module Service Intervals Reset Table
- airFMModServIntResetTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the airFMModServIntTable. "
- ::= { airFMModServIntResets 1 }
- airFMModServIntResetTable OBJECT-TYPE
- SYNTAX SEQUENCE OF AirFMModServIntResetEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting information from each module in
- the system. "
- ::= { airFMModServIntResets 2 }
- airFMModServIntResetEntry OBJECT-TYPE
- SYNTAX AirFMModServIntResetEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The module to get information from."
- INDEX { airFMModServIntResetModuleIndex }
- ::= { airFMModServIntResetTable 1 }
- AirFMModServIntResetEntry ::=
- SEQUENCE {
- airFMModServIntResetModuleIndex INTEGER,
- airFMModServIntComp1Reset INTEGER,
- airFMModServIntComp2Reset INTEGER,
- airFMModServIntHeaterReset INTEGER,
- airFMModServIntHumReset INTEGER,
- airFMModServIntBlwr1Reset INTEGER,
- airFMModServIntBlwr2Reset INTEGER,
- airFMModServIntBlwrCtrl1Reset INTEGER,
- airFMModServIntBlwrCtrl2Reset INTEGER
- }
-
- airFMModServIntResetModuleIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index of the module."
- ::= { airFMModServIntResetEntry 1 }
- airFMModServIntComp1Reset OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- noOperation (2),
- reset (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Reset the compressor 1 service interval maintenance
- alarm.
- Getting this OID will do nothing and return the
- noOperation value.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModServIntResetEntry 2 }
- airFMModServIntComp2Reset OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- noOperation (2),
- reset (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Reset the compressor 2 service interval maintenance
- alarm.
- Getting this OID will do nothing and return the
- noOperation value.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModServIntResetEntry 3 }
- airFMModServIntHeaterReset OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- noOperation (2),
- reset (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Reset the heater service interval maintenance alarm.
- Getting this OID will do nothing and return the
- noOperation value.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModServIntResetEntry 4 }
- airFMModServIntHumReset OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- noOperation (2),
- reset (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Reset the humidifier service interval maintenance
- alarm.
- Getting this OID will do nothing and return the
- noOperation value.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModServIntResetEntry 5 }
- airFMModServIntBlwr1Reset OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- noOperation (2),
- reset (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Reset the blower 1 service interval maintenance
- alarm.
- Getting this OID will do nothing and return the
- noOperation value.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModServIntResetEntry 6 }
- airFMModServIntBlwr2Reset OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- noOperation (2),
- reset (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Reset the blower 2 service interval maintenance
- alarm.
- Getting this OID will do nothing and return the
- noOperation value.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModServIntResetEntry 7 }
- airFMModServIntBlwrCtrl1Reset OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- noOperation (2),
- reset (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Reset the blower controller 1 service interval
- maintenance alarm.
- Getting this OID will do nothing and return the
- noOperation value.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModServIntResetEntry 8 }
- airFMModServIntBlwrCtrl2Reset OBJECT-TYPE
- SYNTAX INTEGER {
- notApplicable (1),
- noOperation (2),
- reset (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Reset the blower controller 2 service interval
- maintenance alarm.
- Getting this OID will do nothing and return the
- noOperation value.
- A value of notApplicable indicates that this OID does
- not apply to this device due to its configuration."
- ::= { airFMModServIntResetEntry 9 }
- -- airFM Alarms Table
- airFMAlarmClearActiveGroupAlarms OBJECT-TYPE
- SYNTAX INTEGER {
- noOperation (1),
- clearAlarms (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Clear active group alarms. If alarm conditions are
- still present, new alarms will be generated for those
- conditions.
- Getting this OID will do nothing and return the
- noOperation value."
- ::= { airFMAlarms 1 }
- airFMAlarmClearActiveSysModAlarms OBJECT-TYPE
- SYNTAX INTEGER {
- noOperation (1),
- clearAlarms (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Clear active system and module alarms. If alarm
- conditions are still present, new alarms will be
- generated for those conditions.
- Getting this OID will do nothing and return the
- noOperation value."
- ::= { airFMAlarms 2 }
- airFMAlarmConditionsTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of active alarm conditions in the
- airFMAlarmConditionTable."
- ::= { airFMAlarms 3 }
- airFMAlarmConditionsTable OBJECT-TYPE
- SYNTAX SEQUENCE OF AirFMAlarmConditionsEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Table of active alarm conditions for the device."
- ::= { airFMAlarms 4 }
- airFMAlarmConditionsEntry OBJECT-TYPE
- SYNTAX AirFMAlarmConditionsEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION "Alarm condition specification"
- INDEX { airFMAlarmConditionsIndex }
- ::= { airFMAlarmConditionsTable 1 }
- AirFMAlarmConditionsEntry ::= SEQUENCE {
- airFMAlarmConditionsIndex INTEGER,
- airFMAlarmSeverity INTEGER,
- airFMAlarmType INTEGER,
- airFMEventCode INTEGER,
- airFMAlarmDate DisplayString,
- airFMAlarmTime DisplayString,
- airFMAlarmDescription DisplayString
- }
- airFMAlarmConditionsIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION "Alarm condition index."
- ::= { airFMAlarmConditionsEntry 1 }
- airFMAlarmSeverity OBJECT-TYPE
- SYNTAX INTEGER {
- informational (1),
- warningMinor (2),
- criticalMajor (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION "Severity of the alarm."
- ::= { airFMAlarmConditionsEntry 2 }
- airFMAlarmType OBJECT-TYPE
- SYNTAX INTEGER {
- group (1),
- system (2),
- mainMod (3),
- expMod1 (4),
- expMod2 (5)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION "Type of alarm."
- ::= { airFMAlarmConditionsEntry 3 }
- airFMEventCode OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION "APC event code for the alarm."
- ::= { airFMAlarmConditionsEntry 4 }
- airFMAlarmDate OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION "Date the alarm was recorded."
- ::= { airFMAlarmConditionsEntry 5 }
-
- airFMAlarmTime OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION "Time the alarm was recorded."
- ::= { airFMAlarmConditionsEntry 6 }
-
- airFMAlarmDescription OBJECT-TYPE
- SYNTAX DisplayString (SIZE (0..64))
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION "Description of the alarm."
- ::= { airFMAlarmConditionsEntry 7 }
-
- -- airPA Portable Air Conditioner Ident
- airPAIdentName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the device name."
- ::= { airPAIdent 1 }
-
- airPAModelNumber OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the device model number."
- ::= { airPAIdent 2 }
-
- airPADateOfManufacture OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying when the device was produced."
- ::= { airPAIdent 3 }
-
- airPASerialNumber OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the device serial number."
- ::= { airPAIdent 4 }
- airPAFirmwareRevision OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the device firmware revision."
- ::= { airPAIdent 5 }
- airPAHardwareRevision OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the device hardware revision."
- ::= { airPAIdent 6 }
- -- airPA Portable Air Conditioner Status
- airPASystemPower OBJECT-TYPE
- SYNTAX INTEGER {
- powerON (1),
- powerOFF (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The status of the unit's system power setting.
-
- ON(1) The system power is turned on.
- OFF(2) The system power is turned off. "
- ::= { airPAStatus 1 }
- airPAOperatingMode OBJECT-TYPE
- SYNTAX INTEGER {
- modeOFF (1),
- modeVENTING (2),
- modeCOOLING (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The current operating mode of the unit.
- OFF(1) The system is off.
- VENTING(2) The system's venting function is active.
- COOLING(3) The system's cooling function is active. "
- ::= { airPAStatus 2 }
- airPASetpointTempF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The temperature setpoint in Fahrenheit to which the unit is controlling. "
- ::= { airPAStatus 3 }
- airPASetpointTempC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The temperature setpoint in Celsius to which the unity is controlling. "
- ::= { airPAStatus 4 }
- airPABlowerSpeed OBJECT-TYPE
- SYNTAX INTEGER {
- speedLOW (1),
- speedHIGH (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit's blower speed setting.
- LOW(1) The blower speed is low.
- HIGH(2) The blower speed is high. "
- ::= { airPAStatus 5 }
- airPACompressor OBJECT-TYPE
- SYNTAX INTEGER {
- statusON (1),
- statusOFF (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit's compressor status.
- ON(1) The compressor is turned on.
- OFF(2) The compressor is turned off. "
- ::= { airPAStatus 6 }
- airPACondenserFan OBJECT-TYPE
- SYNTAX INTEGER {
- statusON (1),
- statusOFF (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit's condenser fan status.
- ON(1) The condenser fan is turned on.
- OFF(2) The condenser fan is turned off. "
- ::= { airPAStatus 7 }
- airPACondensatePump OBJECT-TYPE
- SYNTAX INTEGER {
- statusON (1),
- statusOFF (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit's condensate pump status.
-
- ON(1) The condensate pump is turned on.
- OFF(2) The condensate pump is turned off. "
- ::= { airPAStatus 8 }
- airPASupplyTempF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The supply temperature in degrees Fahrenheit. "
- ::= { airPAStatus 9 }
- airPASupplyTempC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The supply temperature in degrees Celsius. "
- ::= { airPAStatus 10 }
- airPAReturnTempF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The return temperature in degrees Fahrenheit. "
- ::= { airPAStatus 11 }
- airPAReturnTempC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The return temperature in degrees Celsius. "
- ::= { airPAStatus 12 }
- airPARemoteTempF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The remote temperature in degrees Fahrenheit. "
- ::= { airPAStatus 13 }
- airPARemoteTempC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The remote temperature in degrees Celsius. "
- ::= { airPAStatus 14 }
- airPARemoteHumidity OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The remote humidity. "
- ::= { airPAStatus 15 }
- -- air InRow Air Conditioners
- -- airIR AIR CONDITIONER Alarm Status - shared across all IR products
- airIRAlarmConditionsTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of active alarm conditions in the airIRAlarmConditionTable."
- ::= { airIRAlarms 1 }
- airIRAlarmConditionsTable OBJECT-TYPE
- SYNTAX SEQUENCE OF AirIRAlarmConditionsEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Table of active alarm conditions for the device."
- ::= { airIRAlarms 2 }
- airIRAlarmConditionsEntry OBJECT-TYPE
- SYNTAX AirIRAlarmConditionsEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION "Alarm condition specification"
- INDEX { airIRAlarmConditionsIndex }
- ::= { airIRAlarmConditionsTable 1 }
- AirIRAlarmConditionsEntry ::= SEQUENCE {
- airIRAlarmConditionsIndex INTEGER,
- airIREventCode INTEGER,
- airIRAlarmDescription DisplayString
- }
- airIRAlarmConditionsIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION "Alarm condition index."
- ::= { airIRAlarmConditionsEntry 1 }
- airIREventCode OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION "Code for the alarm."
- ::= { airIRAlarmConditionsEntry 2 }
- airIRAlarmDescription OBJECT-TYPE
- SYNTAX DisplayString (SIZE (0..64))
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION "Description of the alarm."
- ::= { airIRAlarmConditionsEntry 3 }
-
- -- airIRRC AIR CONDITIONER Group Status
- airIRRCGroupStatusCoolOutput OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Group coolant output in tenths of kW."
- ::= { airIRRCGroupStatus 1 }
-
- airIRRCGroupStatusCoolDemand OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Group coolant demand in tenths of kW."
- ::= { airIRRCGroupStatus 2 }
-
- airIRRCGroupStatusAirFlowUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Group air flow in cubic feet per minute."
- ::= { airIRRCGroupStatus 3 }
-
- airIRRCGroupStatusAirFlowMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Group air flow in liters per second."
- ::= { airIRRCGroupStatus 4 }
-
- airIRRCGroupStatusMaxRackInletTempUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Group maximum rack inlet temperature in tenths of
- degrees Fahrenheit."
- ::= { airIRRCGroupStatus 5 }
-
- airIRRCGroupStatusMaxRackInletTempMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Group maximum rack inlet temperature in tenths of
- degrees Celsius."
- ::= { airIRRCGroupStatus 6 }
-
- airIRRCGroupStatusMinRackInletTempUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Group minimum rack inlet temperature in tenths of
- degrees Fahrenheit."
- ::= { airIRRCGroupStatus 7 }
-
- airIRRCGroupStatusMinRackInletTempMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Group minimum rack inlet temperature in tenths of
- degrees Celsius."
- ::= { airIRRCGroupStatus 8 }
-
- -- airIRRC AIR CONDITIONER Group Setpoints
- airIRRCGroupSetpointsCoolUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Group cooling setpoint in tenths of
- degrees Fahrenheit."
- ::= { airIRRCGroupSetpoints 1 }
- airIRRCGroupSetpointsCoolMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Group cooling setpoint in tenths of
- degrees Celsius."
- ::= { airIRRCGroupSetpoints 2 }
- airIRRCGroupSetpointsSupplyAirUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Group supply air setpoint in tenths of
- degrees Fahrenheit."
- ::= { airIRRCGroupSetpoints 3 }
- airIRRCGroupSetpointsSupplyAirMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Group supply air setpoint in tenths of
- degrees Celsius."
- ::= { airIRRCGroupSetpoints 4 }
- airIRRCGroupSetpointsFanSpeedPreference OBJECT-TYPE
- SYNTAX INTEGER {
- low (1),
- med-low (2),
- med (3),
- med-high (4),
- high (5)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The preferred fan speed setting."
- ::= { airIRRCGroupSetpoints 5 }
- -- airIRRC AIR CONDITIONER Group Config
- airIRRCGroupConfigNumberofCoolingUnits OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The number of cooling units present in the group."
- ::= { airIRRCGroupConfig 1 }
- airIRRCGroupConfigConfigurationType OBJECT-TYPE
- SYNTAX INTEGER {
- racs (1),
- hacs (2),
- in-row (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The group configuration type."
- ::= { airIRRCGroupConfig 2 }
- airIRRCGroupConfigPctGlycol OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The glycol mixture in percent."
- ::= { airIRRCGroupConfig 3 }
- airIRRCGroupConfigCoolGainP OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The gain component of the PID in hundredths."
- ::= { airIRRCGroupConfig 4 }
- airIRRCGroupConfigCoolResetRateI OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The integral component of the PID in hundredths."
- ::= { airIRRCGroupConfig 5 }
- airIRRCGroupConfigCoolDerivativeD OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The derivative component of the PID in hundredths."
- ::= { airIRRCGroupConfig 6 }
- airIRRCGroupConfigMaxFanSpeed OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The maximum desired fan speed setting in percent."
- ::= { airIRRCGroupConfig 7 }
- -- airIRRC AIR CONDITIONER UNIT Status
- airIRRCUnitStatusOperateMode OBJECT-TYPE
- SYNTAX INTEGER {
- standby (1),
- on (2),
- idle (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The cooling unit operating mode."
- ::= { airIRRCUnitStatus 1 }
- airIRRCUnitStatusCoolOutput OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit cooling output in tenths of kW."
- ::= { airIRRCUnitStatus 2 }
- airIRRCUnitStatusCoolDemand OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit cooling demand in tenths of kW."
- ::= { airIRRCUnitStatus 3 }
- airIRRCUnitStatusAirFlowUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit air flow in cubic feet per minute."
- ::= { airIRRCUnitStatus 4 }
- airIRRCUnitStatusAirFlowMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit air flow in hundredths of
- liters per second."
- ::= { airIRRCUnitStatus 5 }
- airIRRCUnitStatusRackInletTempUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit rack inlet temperature in tenths of
- degrees Fahrenheit."
- ::= { airIRRCUnitStatus 6 }
- airIRRCUnitStatusRackInletTempMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit rack inlet temperature in tenths of
- degrees Celsius."
- ::= { airIRRCUnitStatus 7 }
- airIRRCUnitStatusSupplyAirTempUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit supply air temperature in tenths of
- degrees Fahrenheit."
- ::= { airIRRCUnitStatus 8 }
- airIRRCUnitStatusSupplyAirTempMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit supply air temperature in tenths of
- degrees Celsius."
- ::= { airIRRCUnitStatus 9 }
- airIRRCUnitStatusReturnAirTempUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit return air temperature in tenths of
- degrees Fahrenheit."
- ::= { airIRRCUnitStatus 10 }
- airIRRCUnitStatusReturnAirTempMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit return air temperature in tenths of
- degrees Celsius."
- ::= { airIRRCUnitStatus 11 }
- airIRRCUnitStatusContainmtDPUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit containment differential pressure in
- hundredths of inches of water."
- ::= { airIRRCUnitStatus 12 }
- airIRRCUnitStatusContainmtDPMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit containment differential pressure in Pa."
- ::= { airIRRCUnitStatus 13 }
- airIRRCUnitStatusFilterDPUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit air filter differential pressure in
- hundredths of inches of water."
- ::= { airIRRCUnitStatus 14 }
- airIRRCUnitStatusFilterDPMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit air filter differential pressure in Pa."
- ::= { airIRRCUnitStatus 15 }
- airIRRCUnitStatusFanSpeed OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit average fan speed in tenths of percent."
- ::= { airIRRCUnitStatus 16 }
- airIRRCUnitStatusInputState OBJECT-TYPE
- SYNTAX INTEGER {
- open (1),
- closed (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The state of the input contact."
- ::= { airIRRCUnitStatus 17 }
- airIRRCUnitStatusOutputState OBJECT-TYPE
- SYNTAX INTEGER {
- open (1),
- closed (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The state of the output relay."
- ::= { airIRRCUnitStatus 18 }
- airIRRCUnitStatusActivePowerSource OBJECT-TYPE
- SYNTAX INTEGER {
- sourceA (1),
- sourceB (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The power source that is powering the unit."
- ::= { airIRRCUnitStatus 19 }
- airIRRCUnitStatusFluidValvePosition OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The fluid valve position in percent open."
- ::= { airIRRCUnitStatus 20 }
- airIRRCUnitStatusFluidFlowUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The fluid flow in tenths of gallons per minute."
- ::= { airIRRCUnitStatus 21 }
- airIRRCUnitStatusFluidFlowMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The fluid flow in hundredths of liters per second."
- ::= { airIRRCUnitStatus 22 }
- airIRRCUnitStatusEnteringFluidTemperatureUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The temperature of the entering fluid in
- tenths of degrees Fahrenheit."
- ::= { airIRRCUnitStatus 23 }
- airIRRCUnitStatusEnteringFluidTemperatureMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The temperature of the entering fluid in
- tenths of degrees Celsius."
- ::= { airIRRCUnitStatus 24 }
- airIRRCUnitStatusLeavingFluidTemperatureUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The temperature of the Leaving fluid in
- tenths of degrees Fahrenheit."
- ::= { airIRRCUnitStatus 25 }
- airIRRCUnitStatusLeavingFluidTemperatureMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The temperature of the Leaving fluid in
- tenths of degrees Celsius."
- ::= { airIRRCUnitStatus 26 }
- -- airIRRC AIR CONDITIONER UNIT Ident
- airIRRCUnitIdentID OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The unit identification number."
- ::= { airIRRCUnitIdent 1 }
- airIRRCUnitIdentName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the
- unit name."
- ::= { airIRRCUnitIdent 2 }
- airIRRCUnitIdentLocation OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the
- unit location."
- ::= { airIRRCUnitIdent 3 }
- airIRRCUnitIdentModelNumber OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the
- unit model number."
- ::= { airIRRCUnitIdent 4 }
- airIRRCUnitIdentSerialNumber OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the
- unit serial number."
- ::= { airIRRCUnitIdent 5 }
- airIRRCUnitIdentFirmwareRevision OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the
- unit firmware version."
- ::= { airIRRCUnitIdent 6 }
- airIRRCUnitIdentHardwareRevision OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the
- unit controller hardware revision."
- ::= { airIRRCUnitIdent 7 }
- airIRRCUnitIdentManufactureDate OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the
- unit manufacture date."
- ::= { airIRRCUnitIdent 8 }
- -- airIRRC AIR CONDITIONER UNIT Runhours
- airIRRCUnitRunHoursAirFilter OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit air filter run hours."
- ::= { airIRRCUnitRunHours 1 }
- airIRRCUnitRunHoursFan1 OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit fan 1 run hours."
- ::= { airIRRCUnitRunHours 2 }
- airIRRCUnitRunHoursFan2 OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit fan 2 run hours."
- ::= { airIRRCUnitRunHours 3 }
- airIRRCUnitRunHoursFan3 OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit fan 3 run hours."
- ::= { airIRRCUnitRunHours 4 }
- airIRRCUnitRunHoursFan4 OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit fan 4 run hours."
- ::= { airIRRCUnitRunHours 5 }
- airIRRCUnitRunHoursFan5 OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit fan 5 run hours."
- ::= { airIRRCUnitRunHours 6 }
- airIRRCUnitRunHoursFan6 OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit fan 6 run hours."
- ::= { airIRRCUnitRunHours 7 }
- airIRRCUnitRunHoursFan7 OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit fan 7 run hours."
- ::= { airIRRCUnitRunHours 8}
- airIRRCUnitRunHoursFan8 OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit fan 8 run hours."
- ::= { airIRRCUnitRunHours 9 }
- airIRRCUnitRunHoursFanPowerSupplyLeft OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit fan left power supply run hours."
- ::= { airIRRCUnitRunHours 10 }
- airIRRCUnitRunHoursFanPowerSupplyRight OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit fan right power supply run hours."
- ::= { airIRRCUnitRunHours 11 }
- airIRRCUnitRunHoursCondensatePump OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit condensate pump run hours."
- ::= { airIRRCUnitRunHours 12 }
- -- airIRRC AIR CONDITIONER UNIT Service Intervals
- airIRRCUnitServiceIntervalsAirFilter OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Air filter service interval in weeks."
- ::= { airIRRCUnitServiceIntervals 1 }
- airIRRCUnitServiceIntervalsAirFilterAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- enable (1),
- disable (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The air filter service interval alarm enable/disable."
- ::= { airIRRCUnitServiceIntervals 2 }
- -- airIRRC AIR CONDITIONER UNIT Thresholds
- airIRRCUnitThresholdsRackInletHighTempUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Unit rack inlet air high temperature threshold in
- tenths of degrees Fahrenheit."
- ::= { airIRRCUnitThresholds 1 }
- airIRRCUnitThresholdsRackInletHighTempMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Unit rack inlet air high temperature threshold in
- tenths of degrees Celsius."
- ::= { airIRRCUnitThresholds 2 }
- airIRRCUnitThresholdsSupplyAirHighTempUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Unit supply air high temperature threshold in
- tenths of degrees Fahrenheit."
- ::= { airIRRCUnitThresholds 3 }
- airIRRCUnitThresholdsSupplyAirHighTempMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Unit supply air high temperature threshold in
- tenths of degrees Celsius."
- ::= { airIRRCUnitThresholds 4 }
- airIRRCUnitThresholdsReturnAirHighTempUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Unit return air high temperature threshold in
- tenths of degrees Fahrenheit."
- ::= { airIRRCUnitThresholds 5 }
- airIRRCUnitThresholdsReturnAirHighTempMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Unit return air high temperature threshold in
- tenths of degrees Celsius."
- ::= { airIRRCUnitThresholds 6 }
- airIRRCUnitThresholdsEnteringFluidHighTempUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Unit entering fluid high temperature threshold in
- tenths of degrees Fahrenheit."
- ::= { airIRRCUnitThresholds 7 }
- airIRRCUnitThresholdsEnteringFluidHighTempMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Unit incoming fluid high temperature threshold in
- tenths of degrees Celsius."
- ::= { airIRRCUnitThresholds 8 }
- -- airIRRC AIR CONDITIONER UNIT Config
- airIRRCUnitConfigCoolCapacity OBJECT-TYPE
- SYNTAX INTEGER {
- automatic (1),
- maximum (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The cooling capacity options setting."
- ::= { airIRRCUnitConfig 1 }
- airIRRCUnitConfigStartupDelay OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The startup delay in seconds."
- ::= { airIRRCUnitConfig 2 }
- airIRRCUnitConfigIdleOnLeakDetect OBJECT-TYPE
- SYNTAX INTEGER {
- yes (1),
- no (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The idle on leak options setting."
- ::= { airIRRCUnitConfig 3 }
- airIRRCUnitConfigPowerSource OBJECT-TYPE
- SYNTAX INTEGER {
- sourceA (1),
- sourceB (2),
- sourceAandB (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The configured power source of the unit."
- ::= { airIRRCUnitConfig 4 }
- airIRRCUnitConfigInputNormalState OBJECT-TYPE
- SYNTAX INTEGER {
- open (1),
- closed (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The normal state of the input contact."
- ::= { airIRRCUnitConfig 5 }
- airIRRCUnitConfigOutputNormalState OBJECT-TYPE
- SYNTAX INTEGER {
- open (1),
- closed (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The normal state of the output relay."
- ::= { airIRRCUnitConfig 6 }
- airIRRCUnitConfigOutputSource OBJECT-TYPE
- SYNTAX INTEGER {
- anyAlarm (1),
- criticalAlarm (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The source of output relay change."
- ::= { airIRRCUnitConfig 7 }
- -- airIRRP100 AIR CONDITIONER Group Status
- airIRRP100GroupStatusAirFlowUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Group air flow in cubic feet per minute."
- ::= { airIRRP100GroupStatus 1 }
- airIRRP100GroupStatusAirFlowMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Group air flow in liters per second."
- ::= { airIRRP100GroupStatus 2 }
- airIRRP100GroupStatusMaxRackInletTempUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Group maximum rack inlet temperature in tenths of
- degrees Fahrenheit."
- ::= { airIRRP100GroupStatus 3 }
- airIRRP100GroupStatusMaxRackInletTempMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Group maximum rack inlet temperature in tenths of
- degrees Celsius."
- ::= { airIRRP100GroupStatus 4 }
- airIRRP100GroupStatusMinRackInletTempUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Group minimum rack inlet temperature in tenths of
- degrees Fahrenheit."
- ::= { airIRRP100GroupStatus 5 }
- airIRRP100GroupStatusMinRackInletTempMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Group minimum rack inlet temperature in tenths of
- degrees Celsius."
- ::= { airIRRP100GroupStatus 6 }
- airIRRP100GroupStatusCoolDemand OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Group coolant demand in tenths of kiloWatts."
- ::= { airIRRP100GroupStatus 7 }
- airIRRP100GroupStatusCoolOutput OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Group coolant output in tenths of kiloWatts."
- ::= { airIRRP100GroupStatus 8 }
- airIRRP100GroupStatusHumidifyDemand OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The amount of humidification the group is demanding
- from the humidifiers in percent."
- ::= { airIRRP100GroupStatus 9 }
- airIRRP100GroupStatusHumidifyOutput OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The actual amount of humidification the group is
- supplying in percent."
- ::= { airIRRP100GroupStatus 10 }
- airIRRP100GroupStatusDehumidifyDemand OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The amount of dehumidification the group is demanding
- from the electric heaters in percent."
- ::= { airIRRP100GroupStatus 11 }
- airIRRP100GroupStatusDehumidifyOutput OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The actual amount of dehumidification the group is
- supplying in percent."
- ::= { airIRRP100GroupStatus 12 }
- airIRRP100GroupStatusReheatDemand OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The amount of heating the group is demanding
- from the electric heaters in percent."
- ::= { airIRRP100GroupStatus 13 }
- airIRRP100GroupStatusReheatOutput OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The actual amount of heating the group is
- supplying in percent."
- ::= { airIRRP100GroupStatus 14 }
-
- -- airIRRP100 AIR CONDITIONER Group Setpoints
- airIRRP100GroupSetpointsCoolUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Group cooling setpoint in tenths of
- degrees Fahrenheit."
- ::= { airIRRP100GroupSetpoints 1 }
- airIRRP100GroupSetpointsCoolMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Group cooling setpoint in tenths of
- degrees Celsius."
- ::= { airIRRP100GroupSetpoints 2 }
- airIRRP100GroupSetpointsSupplyAirUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Group supply air setpoint in tenths of
- degrees Fahrenheit."
- ::= { airIRRP100GroupSetpoints 3 }
- airIRRP100GroupSetpointsSupplyAirMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Group supply air setpoint in tenths of
- degrees Celsius."
- ::= { airIRRP100GroupSetpoints 4 }
- airIRRP100GroupSetpointsHumidify OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Group humidify setpoint in tenths of
- percent relative humidity."
- ::= { airIRRP100GroupSetpoints 5 }
- airIRRP100GroupSetpointsDehumidify OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Group dehumidify setpoint in tenths of
- percent relative humidity."
- ::= { airIRRP100GroupSetpoints 6 }
- airIRRP100GroupSetpointsDehumidifyDeadband OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Group dehumidify deadband in percent relative humidity."
- ::= { airIRRP100GroupSetpoints 7 }
- airIRRP100GroupSetpointsReheatUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Group supply air setpoint in tenths of
- degrees Fahrenheit."
- ::= { airIRRP100GroupSetpoints 8 }
- airIRRP100GroupSetpointsReheatMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Group supply air setpoint in tenths of
- degrees Celsius."
- ::= { airIRRP100GroupSetpoints 9 }
- airIRRP100GroupSetpointsFanSpeedPreference OBJECT-TYPE
- SYNTAX INTEGER {
- low (1),
- med-low (2),
- med (3),
- med-high (4),
- high (5)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The preferred fan speed setting."
- ::= { airIRRP100GroupSetpoints 10 }
- airIRRP100GroupSetpointsFanSpeedControl OBJECT-TYPE
- SYNTAX INTEGER {
- automatic (1),
- manual (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The fan speed control setting."
- ::= { airIRRP100GroupSetpoints 11 }
- -- airIRRP100 AIR CONDITIONER Group Config
- airIRRP100GroupConfigNumberofCoolingUnits OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The number of cooling units present in the group."
- ::= { airIRRP100GroupConfig 1 }
- airIRRP100GroupConfigConfigurationType OBJECT-TYPE
- SYNTAX INTEGER {
- racs (1),
- hacs (2),
- in-row (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The group configuration type."
- ::= { airIRRP100GroupConfig 2 }
- airIRRP100GroupConfigCoolGainP OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The gain component of the cool PID in hundredths."
- ::= { airIRRP100GroupConfig 3 }
- airIRRP100GroupConfigCoolResetRateI OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The integral component of the cool PID in hundredths."
- ::= { airIRRP100GroupConfig 4 }
- airIRRP100GroupConfigCoolDerivativeD OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The derivative component of the cool PID in hundredths."
- ::= { airIRRP100GroupConfig 5 }
- airIRRP100GroupConfigHumidifySensitivityBand OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The percent relative humidity below the setpoint that
- will cause the humidifier to run at 100% capacity."
- ::= { airIRRP100GroupConfig 6 }
- airIRRP100GroupConfigReheatGainP OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The gain component of the reheat PID in hundredths."
- ::= { airIRRP100GroupConfig 7 }
- airIRRP100GroupConfigReheatResetRateI OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The integral component of the reheat PID in hundredths."
- ::= { airIRRP100GroupConfig 8 }
- airIRRP100GroupConfigReheatDerivativeD OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The derivative component of the reheat PID in hundredths."
- ::= { airIRRP100GroupConfig 9 }
- -- airIRRP100 AIR CONDITIONER UNIT Status
- airIRRP100UnitStatusOperateMode OBJECT-TYPE
- SYNTAX INTEGER {
- standby (1),
- on (2),
- idle (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The cooling unit operating mode."
- ::= { airIRRP100UnitStatus 1 }
- airIRRP100UnitStatusRackInletTempUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit rack inlet temperature in tenths of
- degrees Fahrenheit."
- ::= { airIRRP100UnitStatus 2 }
- airIRRP100UnitStatusRackInletTempMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit rack inlet temperature in tenths of
- degrees Celsius."
- ::= { airIRRP100UnitStatus 3 }
- airIRRP100UnitStatusSupplyAirTempUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit supply air temperature in tenths of
- degrees Fahrenheit."
- ::= { airIRRP100UnitStatus 4 }
- airIRRP100UnitStatusSupplyAirTempMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit supply air temperature in tenths of
- degrees Celsius."
- ::= { airIRRP100UnitStatus 5 }
- airIRRP100UnitStatusReturnAirTempUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit return air temperature in tenths of
- degrees Fahrenheit."
- ::= { airIRRP100UnitStatus 6 }
- airIRRP100UnitStatusReturnAirTempMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit return air temperature in tenths of
- degrees Celsius."
- ::= { airIRRP100UnitStatus 7 }
- airIRRP100UnitStatusSupplyHumidity OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The relative humidity of the supply air in
- tenths of percent."
- ::= { airIRRP100UnitStatus 8 }
- airIRRP100UnitStatusReturnHumidity OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The relative humidity of the return air in
- tenths of percent."
- ::= { airIRRP100UnitStatus 9 }
- airIRRP100UnitStatusAirFlowUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit air flow in cubic feet per minute."
- ::= { airIRRP100UnitStatus 10 }
- airIRRP100UnitStatusAirFlowMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit air flow in hundredths of
- liters per second."
- ::= { airIRRP100UnitStatus 11 }
- airIRRP100UnitStatusFanSpeed OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit average fan speed in tenths of percent."
- ::= { airIRRP100UnitStatus 12 }
- airIRRP100UnitStatusCoolDemand OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit cooling demand in tenths of kiloWatts."
- ::= { airIRRP100UnitStatus 13 }
- airIRRP100UnitStatusCoolOutput OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit cooling output in tenths of kiloWatts."
- ::= { airIRRP100UnitStatus 14 }
- airIRRP100UnitStatusHumidifyDemand OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The amount of humidification the unit is demanding
- from the humidifier in percent."
- ::= { airIRRP100UnitStatus 15 }
- airIRRP100UnitStatusHumidifyOutput OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The actual humidification output of the unit
- in percent."
- ::= { airIRRP100UnitStatus 16 }
- airIRRP100UnitStatusDehumidifyDemand OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The amount of dehumidification the unit is
- demanding in percent."
- ::= { airIRRP100UnitStatus 17 }
- airIRRP100UnitStatusDehumidifyOutput OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The actual dehumidification output of the unit
- in percent."
- ::= { airIRRP100UnitStatus 18 }
- airIRRP100UnitStatusReheatDemand OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The amount of heating the unit is demanding
- from the electric heater in percent."
- ::= { airIRRP100UnitStatus 19 }
- airIRRP100UnitStatusReheatOutput OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The actual heating output of the unit
- in percent."
- ::= { airIRRP100UnitStatus 20 }
- airIRRP100UnitStatusInputState OBJECT-TYPE
- SYNTAX INTEGER {
- open (1),
- closed (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The state of the input contact."
- ::= { airIRRP100UnitStatus 21 }
- airIRRP100UnitStatusOutputState OBJECT-TYPE
- SYNTAX INTEGER {
- open (1),
- closed (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The state of the output relay."
- ::= { airIRRP100UnitStatus 22 }
- airIRRP100UnitStatusRackInletTemperature1US OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit rack inlet temperature sensor in tenths of
- degrees Fahrenheit."
- ::= { airIRRP100UnitStatus 23 }
- airIRRP100UnitStatusRackInletTemperature1Metric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit rack inlet temperature sensor in tenths of
- degrees Celsius."
- ::= { airIRRP100UnitStatus 24 }
- airIRRP100UnitStatusRackInletTemperature2US OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit rack inlet temperature sensor in tenths of
- degrees Fahrenheit."
- ::= { airIRRP100UnitStatus 25 }
- airIRRP100UnitStatusRackInletTemperature2Metric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit rack inlet temperature sensor in tenths of
- degrees Celsius."
- ::= { airIRRP100UnitStatus 26 }
- airIRRP100UnitStatusRackInletTemperature3US OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit rack inlet temperature sensor in tenths of
- degrees Fahrenheit."
- ::= { airIRRP100UnitStatus 27 }
- airIRRP100UnitStatusRackInletTemperature3Metric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit rack inlet temperature sensor in tenths of
- degrees Celsius."
- ::= { airIRRP100UnitStatus 28 }
- airIRRP100UnitStatusFilterDPUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit air filter differential pressure in
- hundredths of inches of water."
- ::= { airIRRP100UnitStatus 29 }
- airIRRP100UnitStatusFilterDPMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit air filter differential pressure in Pa."
- ::= { airIRRP100UnitStatus 30 }
- airIRRP100UnitStatusContainmtDPUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit containment differential pressure in
- hundredths of inches of water."
- ::= { airIRRP100UnitStatus 31 }
- airIRRP100UnitStatusContainmtDPMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit containment differential pressure in Pa."
- ::= { airIRRP100UnitStatus 32 }
- airIRRP100UnitStatusHumidifierCurrent OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The humidifier current of the unit
- in amperes."
- ::= { airIRRP100UnitStatus 33 }
- airIRRP100UnitStatusHumidifierWaterConductivity OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The water conductivity in the humidifier of the unit
- in microSiemens/cm."
- ::= { airIRRP100UnitStatus 34 }
- airIRRP100UnitStatusCompressorDriveSpeed OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The compressor drive speed in hundredths of Hertz."
- ::= { airIRRP100UnitStatus 35 }
- airIRRP100UnitStatusCompressorDrivePower OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The compressor drive power consumption in
- tenths of kiloWatts."
- ::= { airIRRP100UnitStatus 36 }
- airIRRP100UnitStatusCompressorDriveVoltage OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The compressor drive voltage consumption in
- tenths of volts."
- ::= { airIRRP100UnitStatus 37 }
- airIRRP100UnitStatusCompressorDriveCurrent OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The compressor drive voltage consumption in
- tenths of amperes."
- ::= { airIRRP100UnitStatus 38 }
- airIRRP100UnitStatusCompressorDriveDCLinkVoltage OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The compressor drive DC link voltage in
- tenths of volts."
- ::= { airIRRP100UnitStatus 39 }
- airIRRP100UnitStatusCompressorDriveHeatSinkTempUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The temperature of the compressor drive heatsink
- in tenths of degrees Fahrenheit."
- ::= { airIRRP100UnitStatus 40 }
- airIRRP100UnitStatusCompressorDriveHeatSinkTempMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The temperature of the compressor drive heatsink
- in tenths of degrees Celsius."
- ::= { airIRRP100UnitStatus 41 }
- airIRRP100UnitStatusCompressorDriveControlCardTempUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The temperature of the compressor drive control card
- in tenths of degrees Fahrenheit."
- ::= { airIRRP100UnitStatus 42 }
- airIRRP100UnitStatusCompressorDriveControlCardTempMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The temperature of the compressor drive control card
- in tenths of degrees Celsius."
- ::= { airIRRP100UnitStatus 43 }
- airIRRP100UnitStatusCompressorDriveWarningStatus OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The four byte warning status of the compressor drive
- in hexadecimal."
- ::= { airIRRP100UnitStatus 44 }
- airIRRP100UnitStatusCompressorDriveAlarmStatus OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The four byte alarm status of the compressor drive
- in hexadecimal."
- ::= { airIRRP100UnitStatus 45 }
- airIRRP100UnitStatusSuctionPressureUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit suction pressure in pounds per square inch (PSI)."
- ::= { airIRRP100UnitStatus 46 }
- airIRRP100UnitStatusSuctionPressureMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit suction pressure in kiloPascals (kPa)."
- ::= { airIRRP100UnitStatus 47 }
-
- airIRRP100UnitStatusDischargePressureUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit discharge pressure in pounds per square inch (PSI)."
- ::= { airIRRP100UnitStatus 48 }
- airIRRP100UnitStatusDischargePressureMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit discharge pressure in kiloPascals (kPa)."
- ::= { airIRRP100UnitStatus 49 }
- -- airIRRP100 AIR CONDITIONER UNIT Ident
- airIRRP100UnitIdentID OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The unit identification number."
- ::= { airIRRP100UnitIdent 1 }
- airIRRP100UnitIdentName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the
- unit name."
- ::= { airIRRP100UnitIdent 2 }
- airIRRP100UnitIdentLocation OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the
- unit location."
- ::= { airIRRP100UnitIdent 3 }
- airIRRP100UnitIdentModelNumber OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the
- unit model number."
- ::= { airIRRP100UnitIdent 4 }
- airIRRP100UnitIdentSerialNumber OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the
- unit serial number."
- ::= { airIRRP100UnitIdent 5 }
- airIRRP100UnitIdentFirmwareRevision OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the
- unit firmware version."
- ::= { airIRRP100UnitIdent 6 }
- airIRRP100UnitIdentHardwareRevision OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the
- unit controller hardware revision."
- ::= { airIRRP100UnitIdent 7 }
- airIRRP100UnitIdentManufactureDate OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the
- unit manufacture date."
- ::= { airIRRP100UnitIdent 8 }
- -- airIRRP100 AIR CONDITIONER UNIT Runhours
- airIRRP100UnitRunHoursAirFilter OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit air filter run hours."
- ::= { airIRRP100UnitRunHours 1 }
- airIRRP100UnitRunHoursCondensatePump OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit condensate pump run hours."
- ::= { airIRRP100UnitRunHours 2 }
- airIRRP100UnitRunHoursHumidifier OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit fan right power supply run hours."
- ::= { airIRRP100UnitRunHours 3 }
- airIRRP100UnitRunHoursFan1 OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit fan 1 run hours."
- ::= { airIRRP100UnitRunHours 4 }
- airIRRP100UnitRunHoursHeater1 OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit heater 1 run hours."
- ::= { airIRRP100UnitRunHours 5 }
- airIRRP100UnitRunHoursFan2 OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit fan 2 run hours."
- ::= { airIRRP100UnitRunHours 6 }
- airIRRP100UnitRunHoursHeater2 OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit Heater 2 run hours."
- ::= { airIRRP100UnitRunHours 7 }
- airIRRP100UnitRunHoursCompressor OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit compressor run hours."
- ::= { airIRRP100UnitRunHours 8 }
- -- airIRRP100 AIR CONDITIONER UNIT Service Intervals
- airIRRP100UnitServiceIntervalAirFilter OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Air filter service interval in weeks."
- ::= { airIRRP100UnitServiceIntervals 1 }
- airIRRP100UnitServiceIntervalAirFilterAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- enable (1),
- disable (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The air filter service interval alarm enable/disable."
- ::= { airIRRP100UnitServiceIntervals 2 }
- airIRRP100UnitServiceIntervalHumidifier OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Humidifier service interval in weeks."
- ::= { airIRRP100UnitServiceIntervals 3 }
- airIRRP100UnitServiceIntervalHumidifierAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- enable (1),
- disable (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The humidifier service interval alarm enable/disable."
- ::= { airIRRP100UnitServiceIntervals 4 }
- airIRRP100UnitServiceIntervalHeater OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Heater service interval in weeks."
- ::= { airIRRP100UnitServiceIntervals 5 }
- airIRRP100UnitServiceIntervalHeaterAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- enable (1),
- disable (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The heater service interval alarm enable/disable."
- ::= { airIRRP100UnitServiceIntervals 6 }
- airIRRP100UnitServiceIntervalCompressor OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Compressor service interval in weeks."
- ::= { airIRRP100UnitServiceIntervals 7 }
- airIRRP100UnitServiceIntervalCompressorAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- enable (1),
- disable (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The compressor service interval alarm enable/disable."
- ::= { airIRRP100UnitServiceIntervals 8 }
- airIRRP100UnitServiceIntervalCondensatePump OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Condensate pump service interval in weeks."
- ::= { airIRRP100UnitServiceIntervals 9 }
- airIRRP100UnitServiceIntervalCondensatePumpAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- enable (1),
- disable (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The condensate pump service interval alarm enable/disable."
- ::= { airIRRP100UnitServiceIntervals 10 }
- airIRRP100UnitServiceIntervalFans OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Fans service interval in weeks."
- ::= { airIRRP100UnitServiceIntervals 11 }
- airIRRP100UnitServiceIntervalFansAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- enable (1),
- disable (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The fans service interval alarm enable/disable."
- ::= { airIRRP100UnitServiceIntervals 12 }
- -- airIRRP100 AIR CONDITIONER UNIT Thresholds
- airIRRP100UnitThresholdsRackInletHighTempUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Unit rack inlet air high temperature threshold in
- tenths of degrees Fahrenheit."
- ::= { airIRRP100UnitThresholds 1 }
- airIRRP100UnitThresholdsRackInletHighTempMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Unit rack inlet air high temperature threshold in
- tenths of degrees Celsius."
- ::= { airIRRP100UnitThresholds 2 }
- airIRRP100UnitThresholdsSupplyAirHighTempUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Unit supply air high temperature threshold in
- tenths of degrees Fahrenheit."
- ::= { airIRRP100UnitThresholds 3 }
- airIRRP100UnitThresholdsSupplyAirHighTempMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Unit supply air high temperature threshold in
- tenths of degrees Celsius."
- ::= { airIRRP100UnitThresholds 4 }
- airIRRP100UnitThresholdsReturnAirHighTempUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Unit return air high temperature threshold in
- tenths of degrees Fahrenheit."
- ::= { airIRRP100UnitThresholds 5 }
- airIRRP100UnitThresholdsReturnAirHighTempMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Unit return air high temperature threshold in
- tenths of degrees Celsius."
- ::= { airIRRP100UnitThresholds 6 }
- airIRRP100UnitThresholdsSupplyHumidityHigh OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Unit supply humidity high threshold in
- tenths of percent relative humidity."
- ::= { airIRRP100UnitThresholds 7 }
- airIRRP100UnitThresholdsSupplyHumidityLow OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Unit supply humidity low threshold in
- tenths of percent relative humidity."
- ::= { airIRRP100UnitThresholds 8 }
- -- airIRRP100 AIR CONDITIONER UNIT Config
- airIRRP100UnitConfigStartupDelay OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The startup delay in seconds."
- ::= { airIRRP100UnitConfig 1 }
- airIRRP100UnitConfigCoolCapacity OBJECT-TYPE
- SYNTAX INTEGER {
- automatic (1),
- maximum (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The cooling capacity options setting."
- ::= { airIRRP100UnitConfig 2 }
- airIRRP100UnitConfigIdleOnLeakDetect OBJECT-TYPE
- SYNTAX INTEGER {
- yes (1),
- no (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The idle on leak options setting."
- ::= { airIRRP100UnitConfig 3 }
- airIRRP100UnitConfigInputNormalState OBJECT-TYPE
- SYNTAX INTEGER {
- open (1),
- closed (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The normal state of the input contact."
- ::= { airIRRP100UnitConfig 4 }
- airIRRP100UnitConfigOutputNormalState OBJECT-TYPE
- SYNTAX INTEGER {
- open (1),
- closed (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The normal state of the output relay."
- ::= { airIRRP100UnitConfig 5 }
- airIRRP100UnitConfigOutputSource OBJECT-TYPE
- SYNTAX INTEGER {
- anyAlarm (1),
- criticalAlarm (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The source of output relay change."
- ::= { airIRRP100UnitConfig 6 }
- airIRRP100UnitConfigHumidifyEnable OBJECT-TYPE
- SYNTAX INTEGER {
- enable (1),
- disable (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enable/disable humidification."
- ::= { airIRRP100UnitConfig 7 }
- airIRRP100UnitConfigHumidifierControl OBJECT-TYPE
- SYNTAX INTEGER {
- auto (1),
- drainOff (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The humidifier drain control."
- ::= { airIRRP100UnitConfig 8 }
- airIRRP100UnitConfigDehumidifyEnable OBJECT-TYPE
- SYNTAX INTEGER {
- enable (1),
- disable (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enable/disable dehumidification."
- ::= { airIRRP100UnitConfig 9 }
- airIRRP100UnitConfigReheatEnable OBJECT-TYPE
- SYNTAX INTEGER {
- enable (1),
- disable (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enable/disable reheat."
- ::= { airIRRP100UnitConfig 10 }
- airIRRP100UnitConfigHeatAssistEnable OBJECT-TYPE
- SYNTAX INTEGER {
- enable (1),
- disable (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enable/disable heat assist."
- ::= { airIRRP100UnitConfig 11 }
- -- airIRRP500 AIR CONDITIONER Group Status
- airIRRP500GroupStatusAirFlowUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Group air flow in cubic feet per minute."
- ::= { airIRRP500GroupStatus 1 }
-
- airIRRP500GroupStatusAirFlowMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Group air flow in liters per second."
- ::= { airIRRP500GroupStatus 2 }
-
- airIRRP500GroupStatusMaxRackInletTempUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Group maximum rack inlet temperature in tenths of
- degrees Fahrenheit."
- ::= { airIRRP500GroupStatus 3 }
-
- airIRRP500GroupStatusMaxRackInletTempMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Group maximum rack inlet temperature in tenths of
- degrees Celsius."
- ::= { airIRRP500GroupStatus 4 }
-
- airIRRP500GroupStatusMinRackInletTempUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Group minimum rack inlet temperature in tenths of
- degrees Fahrenheit."
- ::= { airIRRP500GroupStatus 5 }
-
- airIRRP500GroupStatusMinRackInletTempMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Group minimum rack inlet temperature in tenths of
- degrees Celsius."
- ::= { airIRRP500GroupStatus 6 }
-
- airIRRP500GroupStatusCoolDemand OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Group coolant demand in tenths of kiloWatts."
- ::= { airIRRP500GroupStatus 7 }
-
- airIRRP500GroupStatusCoolOutput OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Group coolant output in tenths of kiloWatts."
- ::= { airIRRP500GroupStatus 8 }
- airIRRP500GroupStatusHumidifyDemand OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The amount of humidification the group is demanding
- from the humidifiers in percent."
- ::= { airIRRP500GroupStatus 9 }
-
- airIRRP500GroupStatusHumidifyOutput OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The actual amount of humidification the group is
- supplying in percent."
- ::= { airIRRP500GroupStatus 10 }
-
- airIRRP500GroupStatusDehumidifyDemand OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The amount of dehumidification the group is demanding
- from the electric heaters in percent."
- ::= { airIRRP500GroupStatus 11 }
-
- airIRRP500GroupStatusDehumidifyOutput OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The actual amount of dehumidification the group is
- supplying in percent."
- ::= { airIRRP500GroupStatus 12 }
-
- airIRRP500GroupStatusReheatDemand OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The amount of heating the group is demanding
- from the electric heaters in percent."
- ::= { airIRRP500GroupStatus 13 }
-
- airIRRP500GroupStatusReheatOutput OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The actual amount of heating the group is
- supplying in percent."
- ::= { airIRRP500GroupStatus 14 }
-
- -- airIRRP500 AIR CONDITIONER Group Setpoints
- airIRRP500GroupSetpointsCoolUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Group cooling setpoint in tenths of
- degrees Fahrenheit."
- ::= { airIRRP500GroupSetpoints 1 }
- airIRRP500GroupSetpointsCoolMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Group cooling setpoint in tenths of
- degrees Celsius."
- ::= { airIRRP500GroupSetpoints 2 }
- airIRRP500GroupSetpointsSupplyAirUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Group supply air setpoint in tenths of
- degrees Fahrenheit."
- ::= { airIRRP500GroupSetpoints 3 }
- airIRRP500GroupSetpointsSupplyAirMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Group supply air setpoint in tenths of
- degrees Celsius."
- ::= { airIRRP500GroupSetpoints 4 }
- airIRRP500GroupSetpointsHumidify OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Group humidify setpoint in tenths of
- percent relative humidity."
- ::= { airIRRP500GroupSetpoints 5 }
- airIRRP500GroupSetpointsDehumidify OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Group dehumidify setpoint in tenths of
- percent relative humidity."
- ::= { airIRRP500GroupSetpoints 6 }
- airIRRP500GroupSetpointsDehumidifyDeadband OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Group dehumidify deadband in
- percent relative humidity."
- ::= { airIRRP500GroupSetpoints 7 }
- airIRRP500GroupSetpointsReheatUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Group supply air setpoint in tenths of
- degrees Fahrenheit."
- ::= { airIRRP500GroupSetpoints 8 }
- airIRRP500GroupSetpointsReheatMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Group supply air setpoint in tenths of
- degrees Celsius."
- ::= { airIRRP500GroupSetpoints 9 }
- airIRRP500GroupSetpointsFanSpeedPreference OBJECT-TYPE
- SYNTAX INTEGER {
- low (1),
- med-low (2),
- med (3),
- med-high (4),
- high (5)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The preferred fan speed setting."
- ::= { airIRRP500GroupSetpoints 10 }
- airIRRP500GroupSetpointsFanSpeedControl OBJECT-TYPE
- SYNTAX INTEGER {
- automatic (1),
- manual (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The fan speed control setting."
- ::= { airIRRP500GroupSetpoints 11 }
- -- airIRRP500 AIR CONDITIONER Group Config
- airIRRP500GroupConfigNumberofCoolingUnits OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The number of cooling units."
- ::= { airIRRP500GroupConfig 1 }
- airIRRP500GroupConfigConfigurationType OBJECT-TYPE
- SYNTAX INTEGER {
- racs (1),
- hacs (2),
- in-row (3)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The group configuration type."
- ::= { airIRRP500GroupConfig 2 }
- airIRRP500GroupConfigPercentGlycol OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The glycol mixture in percent."
- ::= { airIRRP500GroupConfig 3 }
- airIRRP500GroupConfigCoolGainP OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The gain component of the cool PID in hundredths."
- ::= { airIRRP500GroupConfig 4 }
- airIRRP500GroupConfigCoolResetRateI OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The integral component of the cool PID in hundredths."
- ::= { airIRRP500GroupConfig 5 }
- airIRRP500GroupConfigCoolDerivativeD OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The derivative component of the cool PID in hundredths."
- ::= { airIRRP500GroupConfig 6 }
- airIRRP500GroupConfigHumidifySensitivityBand OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The percent relative humidity below the setpoint that
- will cause the humidifier to run at 100% capacity."
- ::= { airIRRP500GroupConfig 7 }
- airIRRP500GroupConfigReheatGainP OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The gain component of the reheat PID in hundredths."
- ::= { airIRRP500GroupConfig 8 }
- airIRRP500GroupConfigReheatResetRateI OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The integral component of the reheat PID in hundredths."
- ::= { airIRRP500GroupConfig 9 }
- airIRRP500GroupConfigReheatDerivativeD OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The derivative component of the reheat PID in hundredths."
- ::= { airIRRP500GroupConfig 10 }
- -- airIRRP500 AIR CONDITIONER UNIT Status
- airIRRP500UnitStatusOperateMode OBJECT-TYPE
- SYNTAX INTEGER {
- standby (1),
- on (2),
- idle (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The cooling unit operating mode."
- ::= { airIRRP500UnitStatus 1 }
- airIRRP500UnitStatusMaximumRackInletTempUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The maximum unit rack inlet temperature in tenths of
- degrees Fahrenheit."
- ::= { airIRRP500UnitStatus 2 }
-
- airIRRP500UnitStatusMaximumRackInletTempMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The maximum unit rack inlet temperature in tenths of
- degrees Celsius."
- ::= { airIRRP500UnitStatus 3 }
- airIRRP500UnitStatusSupplyAirTempUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit supply air temperature in tenths of
- degrees Fahrenheit."
- ::= { airIRRP500UnitStatus 4 }
- airIRRP500UnitStatusSupplyAirTempMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit supply air temperature in tenths of
- degrees Celsius."
- ::= { airIRRP500UnitStatus 5 }
- airIRRP500UnitStatusReturnAirTempUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit return air temperature in tenths of
- degrees Fahrenheit."
- ::= { airIRRP500UnitStatus 6 }
- airIRRP500UnitStatusReturnAirTempMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit return air temperature in tenths of
- degrees Celsius."
- ::= { airIRRP500UnitStatus 7 }
- airIRRP500UnitStatusSupplyHumidity OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The relative humidity of the supply air in
- tenths of percent."
- ::= { airIRRP500UnitStatus 8 }
- airIRRP500UnitStatusReturnHumidity OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The relative humidity of the return air in
- tenths of percent."
- ::= { airIRRP500UnitStatus 9 }
- airIRRP500UnitStatusAirFlowUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit air flow in cubic feet per minute."
- ::= { airIRRP500UnitStatus 10 }
- airIRRP500UnitStatusAirFlowMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit air flow in hundredths of
- liters per second."
- ::= { airIRRP500UnitStatus 11 }
- airIRRP500UnitStatusFanSpeed OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit average fan speed in tenths of percent."
- ::= { airIRRP500UnitStatus 12 }
- airIRRP500UnitStatusCoolDemand OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit cooling demand in tenths of kiloWatts."
- ::= { airIRRP500UnitStatus 13 }
- airIRRP500UnitStatusCoolOutput OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit cooling output in tenths of kiloWatts."
- ::= { airIRRP500UnitStatus 14 }
- airIRRP500UnitStatusHumidifyDemand OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The amount of humidification the unit is demanding
- from the humidifier in percent."
- ::= { airIRRP500UnitStatus 15 }
- airIRRP500UnitStatusHumidifyOutput OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The actual humidification output of the unit
- in percent."
- ::= { airIRRP500UnitStatus 16 }
- airIRRP500UnitStatusDehumidifyDemand OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The amount of dehumidification the unit is
- demanding in percent."
- ::= { airIRRP500UnitStatus 17 }
- airIRRP500UnitStatusDehumidifyOutput OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The actual dehumidification output of the unit
- in percent."
- ::= { airIRRP500UnitStatus 18 }
- airIRRP500UnitStatusReheatDemand OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The amount of heating the unit is demanding
- from the electric heater in percent."
- ::= { airIRRP500UnitStatus 19 }
- airIRRP500UnitStatusReheatOutput OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The actual heating output of the unit
- in percent."
- ::= { airIRRP500UnitStatus 20 }
- airIRRP500UnitStatusInputState OBJECT-TYPE
- SYNTAX INTEGER {
- open (1),
- closed (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The state of the input contact."
- ::= { airIRRP500UnitStatus 21 }
- airIRRP500UnitStatusOutputState OBJECT-TYPE
- SYNTAX INTEGER {
- open (1),
- closed (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The state of the output relay."
- ::= { airIRRP500UnitStatus 22 }
- airIRRP500UnitStatusRackInletTemperature1US OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit rack inlet temperature sensor in tenths of
- degrees Fahrenheit."
- ::= { airIRRP500UnitStatus 23 }
- airIRRP500UnitStatusRackInletTemperature1Metric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit rack inlet temperature sensor in tenths of
- degrees Celsius."
- ::= { airIRRP500UnitStatus 24 }
- airIRRP500UnitStatusRackInletTemperature2US OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit rack inlet temperature sensor in tenths of
- degrees Fahrenheit."
- ::= { airIRRP500UnitStatus 25 }
- airIRRP500UnitStatusRackInletTemperature2Metric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit rack inlet temperature sensor in tenths of
- degrees Celsius."
- ::= { airIRRP500UnitStatus 26 }
- airIRRP500UnitStatusRackInletTemperature3US OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit rack inlet temperature sensor in tenths of
- degrees Fahrenheit."
- ::= { airIRRP500UnitStatus 27 }
- airIRRP500UnitStatusRackInletTemperature3Metric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit rack inlet temperature sensor in tenths of
- degrees Celsius."
- ::= { airIRRP500UnitStatus 28 }
- airIRRP500UnitStatusContainmtDPUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit containment differential pressure in
- hundredths of inches of water."
- ::= { airIRRP500UnitStatus 29 }
- airIRRP500UnitStatusContainmtDPMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit containment differential pressure in Pa."
- ::= { airIRRP500UnitStatus 30 }
- airIRRP500UnitStatusFilterDPUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit air filter differential pressure in
- hundredths of inches of water."
- ::= { airIRRP500UnitStatus 31 }
- airIRRP500UnitStatusFilterDPMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit air filter differential pressure in Pa."
- ::= { airIRRP500UnitStatus 32 }
-
- airIRRP500UnitStatusHumidifierCurrent OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The humidifier current of the unit
- in amperes."
- ::= { airIRRP500UnitStatus 33 }
- airIRRP500UnitStatusHumidifierWaterConductivity OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The water conductivity in the humidifier of the unit
- in microSiemens/cm."
- ::= { airIRRP500UnitStatus 34 }
- airIRRP500UnitStatusActivePowerSource OBJECT-TYPE
- SYNTAX INTEGER {
- sourceA (1),
- sourceB (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The power source that is powering the unit."
- ::= { airIRRP500UnitStatus 35 }
- airIRRP500UnitStatusFluidValvePosition OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The fluid valve position in percent open."
- ::= { airIRRP500UnitStatus 36 }
- airIRRP500UnitStatusFluidFlowUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The fluid flow in tenths of gallons per minute."
- ::= { airIRRP500UnitStatus 37 }
- airIRRP500UnitStatusFluidFlowMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The fluid flow in hundredths of liters per second."
- ::= { airIRRP500UnitStatus 38 }
- airIRRP500UnitStatusEnteringFluidTemperatureUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The temperature of the entering fluid in
- tenths of degrees Fahrenheit."
- ::= { airIRRP500UnitStatus 39 }
- airIRRP500UnitStatusEnteringFluidTemperatureMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The temperature of the entering fluid in
- tenths of degrees Celsius."
- ::= { airIRRP500UnitStatus 40 }
- airIRRP500UnitStatusLeavingFluidTemperatureUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The temperature of the Leaving fluid in
- tenths of degrees Fahrenheit."
- ::= { airIRRP500UnitStatus 41 }
- airIRRP500UnitStatusLeavingFluidTemperatureMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The temperature of the Leaving fluid in
- tenths of degrees Celsius."
- ::= { airIRRP500UnitStatus 42 }
- -- airIRRP500 AIR CONDITIONER UNIT Ident
- airIRRP500UnitIdentID OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The unit identification number."
- ::= { airIRRP500UnitIdent 1 }
- airIRRP500UnitIdentName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the
- unit name."
- ::= { airIRRP500UnitIdent 2 }
- airIRRP500UnitIdentLocation OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the
- unit location."
- ::= { airIRRP500UnitIdent 3 }
- airIRRP500UnitIdentModelNumber OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the
- unit model number."
- ::= { airIRRP500UnitIdent 4 }
- airIRRP500UnitIdentSerialNumber OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the
- unit serial number."
- ::= { airIRRP500UnitIdent 5 }
-
- airIRRP500UnitIdentFirmwareRevision OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the
- unit firmware version."
- ::= { airIRRP500UnitIdent 6 }
- airIRRP500UnitIdentHardwareRevision OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the
- unit controller hardware revision."
- ::= { airIRRP500UnitIdent 7 }
- airIRRP500UnitIdentManufactureDate OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the
- unit manufacture date."
- ::= { airIRRP500UnitIdent 8 }
- -- airIRRP500 AIR CONDITIONER UNIT Runhours
- airIRRP500UnitRunHoursAirFilter OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit air filter run hours in hours."
- ::= { airIRRP500UnitRunHours 1 }
- airIRRP500UnitRunHoursCondensatePump OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit condensate pump run hours in hours."
- ::= { airIRRP500UnitRunHours 2 }
- airIRRP500UnitRunHoursHumidifier OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit fan right power supply run hours in hours."
- ::= { airIRRP500UnitRunHours 3 }
- airIRRP500UnitRunHoursFan1 OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit fan 1 run hours in hours."
- ::= { airIRRP500UnitRunHours 4 }
- airIRRP500UnitRunHoursHeater1 OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit heater 1 run hours in hours."
- ::= { airIRRP500UnitRunHours 5 }
- airIRRP500UnitRunHoursFan2 OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit fan 2 run hours in hours."
- ::= { airIRRP500UnitRunHours 6 }
- airIRRP500UnitRunHoursHeater2 OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit Heater 2 run hours in hours."
- ::= { airIRRP500UnitRunHours 7 }
- airIRRP500UnitRunHoursFan3 OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit fan 3 run hours in hours."
- ::= { airIRRP500UnitRunHours 8 }
- airIRRP500UnitRunHoursHeater3 OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit heater 3 run hours in hours."
- ::= { airIRRP500UnitRunHours 9 }
- -- airIRRP500 AIR CONDITIONER UNIT Service Intervals
- airIRRP500UnitServiceIntervalAirFilter OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Air filter service interval in weeks."
- ::= { airIRRP500UnitServiceIntervals 1 }
- airIRRP500UnitServiceIntervalAirFilterAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- enable (1),
- disable (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The air filter service interval alarm enable/disable."
- ::= { airIRRP500UnitServiceIntervals 2 }
- airIRRP500UnitServiceIntervalHumidifier OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Humidifier service interval in weeks."
- ::= { airIRRP500UnitServiceIntervals 3 }
- airIRRP500UnitServiceIntervalHumidifierAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- enable (1),
- disable (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The humidifier service interval alarm enable/disable."
- ::= { airIRRP500UnitServiceIntervals 4 }
- airIRRP500UnitServiceIntervalHeater OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Heater service interval in weeks."
- ::= { airIRRP500UnitServiceIntervals 5 }
- airIRRP500UnitServiceIntervalHeaterAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- enable (1),
- disable (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The heater service interval alarm enable/disable."
- ::= { airIRRP500UnitServiceIntervals 6 }
- airIRRP500UnitServiceIntervalCondensatePump OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Condensate pump service interval in weeks."
- ::= { airIRRP500UnitServiceIntervals 7 }
- airIRRP500UnitServiceIntervalCondensatePumpAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- enable (1),
- disable (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The condensate pump service interval alarm enable/disable."
- ::= { airIRRP500UnitServiceIntervals 8 }
- airIRRP500UnitServiceIntervalFans OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Fans service interval in weeks."
- ::= { airIRRP500UnitServiceIntervals 9 }
- airIRRP500UnitServiceIntervalFansAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- enable (1),
- disable (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The fans service interval alarm enable/disable."
- ::= { airIRRP500UnitServiceIntervals 10 }
- -- airIRRP500 AIR CONDITIONER UNIT Thresholds
- airIRRP500UnitThresholdsRackInletHighTempUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Unit rack inlet air high temperature threshold in
- tenths of degrees Fahrenheit."
- ::= { airIRRP500UnitThresholds 1 }
- airIRRP500UnitThresholdsRackInletHighTempMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Unit rack inlet air high temperature threshold in
- tenths of degrees Celsius."
- ::= { airIRRP500UnitThresholds 2 }
- airIRRP500UnitThresholdsSupplyAirHighTempUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Unit supply air temperature high threshold in
- tenths of degrees Fahrenheit."
- ::= { airIRRP500UnitThresholds 3 }
- airIRRP500UnitThresholdsSupplyAirHighTempMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Unit supply air high temperature high threshold in
- tenths of degrees Celsius."
- ::= { airIRRP500UnitThresholds 4 }
- airIRRP500UnitThresholdsReturnAirHighTempUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Unit return air high temperature threshold in
- tenths of degrees Fahrenheit."
- ::= { airIRRP500UnitThresholds 5 }
- airIRRP500UnitThresholdsReturnAirHighTempMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Unit return air high temperature threshold in
- tenths of degrees Celsius."
- ::= { airIRRP500UnitThresholds 6 }
- airIRRP500UnitThresholdsSupplyHumidityHigh OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Unit supply humidity high threshold in
- tenths of percent relative humidity."
- ::= { airIRRP500UnitThresholds 7 }
- airIRRP500UnitThresholdsSupplyHumidityLow OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Unit supply humidity low threshold in
- tenths of percent relative humidity."
- ::= { airIRRP500UnitThresholds 8 }
- airIRRP500UnitThresholdsEnteringFluidHighTempUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Entering fluid high temperature threshold in
- tenths of degrees Fahrenheit."
- ::= { airIRRP500UnitThresholds 9 }
- airIRRP500UnitThresholdsEnteringFluidHighTempMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Entering fluid high temperature threshold in
- tenths of degrees Celsius."
- ::= { airIRRP500UnitThresholds 10 }
- -- airIRRP500 AIR CONDITIONER UNIT Config
- airIRRP500UnitConfigStartupDelay OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The startup delay in seconds."
- ::= { airIRRP500UnitConfig 1 }
- airIRRP500UnitConfigCoolCapacity OBJECT-TYPE
- SYNTAX INTEGER {
- automatic (1),
- maximum (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The cooling capacity options setting."
- ::= { airIRRP500UnitConfig 2 }
- airIRRP500UnitConfigIdleOnLeakDetect OBJECT-TYPE
- SYNTAX INTEGER {
- yes (1),
- no (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The idle on leak options setting."
- ::= { airIRRP500UnitConfig 3 }
- airIRRP500UnitConfigInputNormalState OBJECT-TYPE
- SYNTAX INTEGER {
- open (1),
- closed (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The normal state of the input contact."
- ::= { airIRRP500UnitConfig 4 }
- airIRRP500UnitConfigOutputNormalState OBJECT-TYPE
- SYNTAX INTEGER {
- open (1),
- closed (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The normal state of the output relay."
- ::= { airIRRP500UnitConfig 5 }
- airIRRP500UnitConfigOutputSource OBJECT-TYPE
- SYNTAX INTEGER {
- anyAlarm (1),
- criticalAlarm (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The source of output relay change."
- ::= { airIRRP500UnitConfig 6 }
- airIRRP500UnitConfigHumidifyEnable OBJECT-TYPE
- SYNTAX INTEGER {
- enable (1),
- disable (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enable/disable humidification."
- ::= { airIRRP500UnitConfig 7 }
- airIRRP500UnitConfigHumidifierControl OBJECT-TYPE
- SYNTAX INTEGER {
- auto (1),
- drainOff (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The humidifier drain control."
- ::= { airIRRP500UnitConfig 8 }
- airIRRP500UnitConfigDehumidifyEnable OBJECT-TYPE
- SYNTAX INTEGER {
- enable (1),
- disable (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enable/disable dehumidification."
- ::= { airIRRP500UnitConfig 9 }
-
- airIRRP500UnitConfigReheatEnable OBJECT-TYPE
- SYNTAX INTEGER {
- enable (1),
- disable (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enable/disable reheat."
- ::= { airIRRP500UnitConfig 10 }
- airIRRP500UnitConfigHeatAssistEnable OBJECT-TYPE
- SYNTAX INTEGER {
- enable (1),
- disable (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enable/disable heat assist."
- ::= { airIRRP500UnitConfig 11 }
- -- airIRSC AIR CONDITIONER Defines
- AirIRSCConfigType ::= INTEGER {
- racs (1),
- spot (2),
- in-row (3)
- }
- AirIRSCCapacityControlType ::= INTEGER {
- discrete (1),
- proportional (2)
- }
- AirIRSCFanSpeedPreference ::= INTEGER {
- low (1),
- med-low (2),
- med (3),
- med-high (4),
- high (5)
- }
- AirIRSCFanSpeedControl ::= INTEGER {
- automatic (1),
- manual (2)
- }
- -- airIRSC AIR CONDITIONER UNIT Status
- airIRSCUnitStatusOperateMode OBJECT-TYPE
- SYNTAX INTEGER {
- standby (1),
- on (2),
- idle (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The cooling unit operating mode."
- ::= { airIRSCUnitStatus 1 }
- airIRSCUnitStatusCoolOutput OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit cooling output in tenths of kW."
- ::= { airIRSCUnitStatus 2 }
- airIRSCUnitStatusCoolDemand OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit cooling demand in tenths of kW."
- ::= { airIRSCUnitStatus 3 }
- airIRSCUnitStatusAirFlowUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit air flow in cubic feet per minute."
- ::= { airIRSCUnitStatus 4 }
- airIRSCUnitStatusAirFlowMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit air flow in hundredths of
- liters per second."
- ::= { airIRSCUnitStatus 5 }
- airIRSCUnitStatusRackInletTempUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit rack inlet temperature in tenths of
- degrees Fahrenheit."
- ::= { airIRSCUnitStatus 6 }
- airIRSCUnitStatusRackInletTempMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit rack inlet temperature in tenths of
- degrees Celsius."
- ::= { airIRSCUnitStatus 7 }
- airIRSCUnitStatusSupplyAirTempUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit supply air temperature in tenths of
- degrees Fahrenheit."
- ::= { airIRSCUnitStatus 8 }
- airIRSCUnitStatusSupplyAirTempMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit supply air temperature in tenths of
- degrees Celsius."
- ::= { airIRSCUnitStatus 9 }
- airIRSCUnitStatusReturnAirTempUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit return air temperature in tenths of
- degrees Fahrenheit."
- ::= { airIRSCUnitStatus 10 }
- airIRSCUnitStatusReturnAirTempMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit return air temperature in tenths of
- degrees Celsius."
- ::= { airIRSCUnitStatus 11 }
- airIRSCUnitStatusSuctionTempUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit suction temperature in tenths of
- degrees Fahrenheit."
- ::= { airIRSCUnitStatus 12 }
- airIRSCUnitStatusSuctionTempMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit suction temperature in tenths of
- degrees Celsius."
- ::= { airIRSCUnitStatus 13 }
- airIRSCUnitStatusSuperheatTempUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit superheat temperature in tenths of
- degrees Fahrenheit."
- ::= { airIRSCUnitStatus 14 }
- airIRSCUnitStatusSuperheatTempMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit superheat temperature in tenths of
- degrees Celsius."
- ::= { airIRSCUnitStatus 15 }
- airIRSCUnitStatusContainmtDPUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit containment differential pressure in
- hundredths of inches of water."
- ::= { airIRSCUnitStatus 16 }
- airIRSCUnitStatusContainmtDPMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit containment differential pressure in Pa."
- ::= { airIRSCUnitStatus 17 }
- airIRSCUnitStatusFilterDPUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit air filter differential pressure in
- hundredths of inches of water."
- ::= { airIRSCUnitStatus 18 }
- airIRSCUnitStatusFilterDPMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit air filter differential pressure in Pa."
- ::= { airIRSCUnitStatus 19 }
- airIRSCUnitStatusSuctionPressureUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit suction pressure in pounds per square inch (PSI)."
- ::= { airIRSCUnitStatus 20 }
- airIRSCUnitStatusSuctionPressureMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit suction pressure in kiloPascals (kPa)."
- ::= { airIRSCUnitStatus 21 }
-
- airIRSCUnitStatusDischargePressureUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit discharge pressure in pounds per square inch (PSI)."
- ::= { airIRSCUnitStatus 22 }
- airIRSCUnitStatusDischargePressureMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit discharge pressure in kiloPascals (kPa)."
- ::= { airIRSCUnitStatus 23 }
- airIRSCUnitStatusEvaporatorFanSpeed OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit average evaporator fan speed in tenths of percent."
- ::= { airIRSCUnitStatus 24 }
- airIRSCUnitStatusCondenserFanSpeed OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit average condenser fan speed in tenths of percent."
- ::= { airIRSCUnitStatus 25 }
- airIRSCUnitStatusInputState OBJECT-TYPE
- SYNTAX INTEGER {
- open (1),
- closed (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The state of the input contact."
- ::= { airIRSCUnitStatus 26 }
- airIRSCUnitStatusOutputState OBJECT-TYPE
- SYNTAX INTEGER {
- open (1),
- closed (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The state of the output relay."
- ::= { airIRSCUnitStatus 27 }
- airIRSCUnitStatusCondOutletTempUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit condenser outlet air temperature in tenths of
- degrees Fahrenheit."
- ::= { airIRSCUnitStatus 28 }
- airIRSCUnitStatusCondOutletTempMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit condenser outlet air temperature in tenths of
- degrees Celsius."
- ::= { airIRSCUnitStatus 29 }
- airIRSCUnitStatusCondInletTempUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit condenser inlet air temperature in tenths of
- degrees Fahrenheit."
- ::= { airIRSCUnitStatus 30 }
- airIRSCUnitStatusCondInletTempMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit condenser inlet air temperature in tenths of
- degrees Celsius."
- ::= { airIRSCUnitStatus 31 }
- airIRSCUnitStatusCompressor OBJECT-TYPE
- SYNTAX INTEGER {
- off (1),
- on (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The state (off/on) of the compressor."
- ::= { airIRSCUnitStatus 32 }
- -- airIRSC AIR CONDITIONER UNIT Ident
- airIRSCUnitIdentName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the
- unit name."
- ::= { airIRSCUnitIdent 1 }
- airIRSCUnitIdentLocation OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the
- unit location."
- ::= { airIRSCUnitIdent 2 }
- airIRSCUnitIdentModelNumber OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the
- unit model number."
- ::= { airIRSCUnitIdent 3 }
- airIRSCUnitIdentSerialNumber OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the
- unit serial number."
- ::= { airIRSCUnitIdent 4 }
- airIRSCUnitIdentFirmwareRevision OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the
- unit firmware version."
- ::= { airIRSCUnitIdent 5 }
- airIRSCUnitIdentHardwareRevision OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the
- unit controller hardware revision."
- ::= { airIRSCUnitIdent 6 }
- airIRSCUnitIdentManufactureDate OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the
- unit manufacture date."
- ::= { airIRSCUnitIdent 7 }
- -- airIRSC AIR CONDITIONER UNIT Runhours
- airIRSCUnitRunHoursAirFilter OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit air filter run hours."
- ::= { airIRSCUnitRunHours 1 }
- airIRSCUnitRunHoursEvaporatorFan1 OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit evaporator fan 1 run hours."
- ::= { airIRSCUnitRunHours 2 }
- airIRSCUnitRunHoursEvaporatorFan2 OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit evaporator fan 2 run hours."
- ::= { airIRSCUnitRunHours 3 }
- airIRSCUnitRunHoursEvaporatorFan3 OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit evaporator fan 3 run hours."
- ::= { airIRSCUnitRunHours 4 }
- airIRSCUnitRunHoursCondenserFan1 OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit condenser fan 1 run hours."
- ::= { airIRSCUnitRunHours 5 }
- airIRSCUnitRunHoursCondenserFan2 OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit condenser fan 2 run hours."
- ::= { airIRSCUnitRunHours 6 }
- airIRSCUnitRunHoursCondenserFan3 OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit condenser fan 3 run hours."
- ::= { airIRSCUnitRunHours 7 }
- airIRSCUnitRunHoursFanPowerSupplyLeft OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit fan left power supply run hours."
- ::= { airIRSCUnitRunHours 8 }
- airIRSCUnitRunHoursFanPowerSupplyRight OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit fan right power supply run hours."
- ::= { airIRSCUnitRunHours 9 }
- airIRSCUnitRunHoursCondensatePump OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit condensate pump run hours."
- ::= { airIRSCUnitRunHours 10 }
- airIRSCUnitRunHoursCompressor OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit compressor run hours."
- ::= { airIRSCUnitRunHours 11 }
- -- airIRSC AIR CONDITIONER UNIT Service Intervals
- airIRSCUnitServiceIntervalsAirFilter OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Air filter service interval in weeks."
- ::= { airIRSCUnitServiceIntervals 1 }
- airIRSCUnitServiceIntervalsAirFilterAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- enable (1),
- disable (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The air filter service interval alarm enable/disable."
- ::= { airIRSCUnitServiceIntervals 2 }
- -- airIRSC AIR CONDITIONER UNIT Thresholds
- airIRSCUnitThresholdsRackInletHighTempUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Unit rack inlet air high temperature threshold in
- tenths of degrees Fahrenheit."
- ::= { airIRSCUnitThresholds 1 }
- airIRSCUnitThresholdsRackInletHighTempMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Unit rack inlet air high temperature threshold in
- tenths of degrees Celsius."
- ::= { airIRSCUnitThresholds 2 }
- airIRSCUnitThresholdsSupplyAirHighTempUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Unit supply air high temperature threshold in
- tenths of degrees Fahrenheit."
- ::= { airIRSCUnitThresholds 3 }
- airIRSCUnitThresholdsSupplyAirHighTempMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Unit supply air high temperature threshold in
- tenths of degrees Celsius."
- ::= { airIRSCUnitThresholds 4 }
- airIRSCUnitThresholdsReturnAirHighTempUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Unit return air high temperature threshold in
- tenths of degrees Fahrenheit."
- ::= { airIRSCUnitThresholds 5 }
- airIRSCUnitThresholdsReturnAirHighTempMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Unit return air high temperature threshold in
- tenths of degrees Celsius."
- ::= { airIRSCUnitThresholds 6 }
- -- airIRSC AIR CONDITIONER UNIT Setpoints
- airIRSCUnitSetptsCoolSetpointUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Unit cooling setpoint in tenths of
- degrees Fahrenheit."
- ::= { airIRSCUnitSetpoints 1 }
- airIRSCUnitSetptsCoolSetpointMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Unit cooling setpoint in tenths of
- degrees Celsius."
- ::= { airIRSCUnitSetpoints 2 }
- airIRSCUnitSetptsCoolDeadbandUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Unit cooling deadband in tenths of
- degrees Fahrenheit."
- ::= { airIRSCUnitSetpoints 3 }
- airIRSCUnitSetptsCoolDeadbandMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Unit cooling deadband in tenths of
- degrees Celsius."
- ::= { airIRSCUnitSetpoints 4 }
- airIRSCUnitSetptsFanSpeedPreference OBJECT-TYPE
- SYNTAX AirIRSCFanSpeedPreference
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The preferred fan speed setting."
- ::= { airIRSCUnitSetpoints 5 }
- airIRSCUnitSetptsSupplyAirSetpointUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Unit supply air setpoint in tenths of
- degrees Fahrenheit."
- ::= { airIRSCUnitSetpoints 6 }
- airIRSCUnitSetptsSupplyAirSetpointMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Unit supply air setpoint in tenths of
- degrees Celsius."
- ::= { airIRSCUnitSetpoints 7 }
- -- airIRSC AIR CONDITIONER UNIT Config
- airIRSCUnitConfigConfigurationType OBJECT-TYPE
- SYNTAX AirIRSCConfigType
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The unit configuration type."
- ::= { airIRSCUnitConfig 1 }
- airIRSCUnitConfigCapacityControlType OBJECT-TYPE
- SYNTAX AirIRSCCapacityControlType
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The unit capacity control."
- ::= { airIRSCUnitConfig 2 }
- airIRSCUnitConfigStartupDelay OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The startup delay in seconds."
- ::= { airIRSCUnitConfig 3 }
- airIRSCUnitConfigIdleOnLeakDetect OBJECT-TYPE
- SYNTAX INTEGER {
- yes (1),
- no (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The idle on leak options setting."
- ::= { airIRSCUnitConfig 4 }
- airIRSCUnitConfigInputNormalState OBJECT-TYPE
- SYNTAX INTEGER {
- open (1),
- closed (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The normal state of the input contact."
- ::= { airIRSCUnitConfig 5 }
- airIRSCUnitConfigOutputNormalState OBJECT-TYPE
- SYNTAX INTEGER {
- open (1),
- closed (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The normal state of the output relay."
- ::= { airIRSCUnitConfig 6 }
- airIRSCUnitConfigOutputSource OBJECT-TYPE
- SYNTAX INTEGER {
- anyAlarm (1),
- criticalAlarm (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The source of output relay change."
- ::= { airIRSCUnitConfig 7 }
- airIRSCUnitConfigAltitudeUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The altitude of the unit above sea level in feet."
- ::= { airIRSCUnitConfig 8 }
- airIRSCUnitConfigAltitudeMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The altitude of the unit above sea level in meters."
- ::= { airIRSCUnitConfig 9 }
- airIRSCUnitConfigOpControl OBJECT-TYPE
- SYNTAX INTEGER {
- standby (1),
- on (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The unit operational control."
- ::= { airIRSCUnitConfig 10 }
- -- airIRSC AIR CONDITIONER GROUP Status
- airIRSCGroupStatusCoolOutput OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The group cooling output in tenths of kW."
- ::= { airIRSCGroupStatus 1 }
- airIRSCGroupStatusCoolDemand OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The group cooling demand in tenths of kW."
- ::= { airIRSCGroupStatus 2 }
- airIRSCGroupStatusAirFlowUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The group air flow in cubic feet per minute."
- ::= { airIRSCGroupStatus 3 }
- airIRSCGroupStatusAirFlowMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The group air flow in hundredths of
- liters per second."
- ::= { airIRSCGroupStatus 4 }
- airIRSCGroupStatusMaxRackInletTempUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The group maximum rack inlet temperature in tenths of
- degrees Fahrenheit."
- ::= { airIRSCGroupStatus 5 }
- airIRSCGroupStatusMaxRackInletTempMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The group maximum rack inlet temperature in tenths of
- degrees Celsius."
- ::= { airIRSCGroupStatus 6 }
- airIRSCGroupStatusMinRackInletTempUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The group minimum rack inlet temperature in tenths of
- degrees Fahrenheit."
- ::= { airIRSCGroupStatus 7 }
- airIRSCGroupStatusMinRackInletTempMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The group minimum rack inlet temperature in tenths of
- degrees Celsius."
- ::= { airIRSCGroupStatus 8 }
- airIRSCGroupStatusMaxReturnAirTempUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The group maximum return air temperature in tenths of
- degrees Fahrenheit."
- ::= { airIRSCGroupStatus 9 }
- airIRSCGroupStatusMaxReturnAirTempMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The group maximum return air temperature in tenths of
- degrees Celsius."
- ::= { airIRSCGroupStatus 10 }
- airIRSCGroupStatusMinReturnAirTempUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The group minimum return air temperature in tenths of
- degrees Fahrenheit."
- ::= { airIRSCGroupStatus 11 }
- airIRSCGroupStatusMinReturnAirTempMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The group minimum return air temperature in tenths of
- degrees Celsius."
- ::= { airIRSCGroupStatus 12 }
- -- airIRSC AIR CONDITIONER GROUP Setpoint
- airIRSCGroupSetptsCoolSetpointUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Group cooling setpoint in tenths of
- degrees Fahrenheit."
- ::= { airIRSCGroupSetpoints 1 }
- airIRSCGroupSetptsCoolSetpointMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Group cooling setpoint in tenths of
- degrees Celsius."
- ::= { airIRSCGroupSetpoints 2 }
- airIRSCGroupSetptsCoolDeadbandUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Group cooling deadband in tenths of
- degrees Fahrenheit."
- ::= { airIRSCGroupSetpoints 3 }
- airIRSCGroupSetptsCoolDeadbandMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Group cooling deadband in tenths of
- degrees Celsius."
- ::= { airIRSCGroupSetpoints 4 }
- airIRSCGroupSetptsFanSpeedPreference OBJECT-TYPE
- SYNTAX AirIRSCFanSpeedPreference
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The group preferred fan speed setting."
- ::= { airIRSCGroupSetpoints 5 }
- airIRSCGroupSetptsSupplyAirSetpointUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Group supply air setpoint in tenths of
- degrees Fahrenheit."
- ::= { airIRSCGroupSetpoints 6 }
- airIRSCGroupSetptsSupplyAirSetpointMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Group supply air setpoint in tenths of
- degrees Celsius."
- ::= { airIRSCGroupSetpoints 7 }
- -- airIRSC AIR CONDITIONER GROUP Config
- airIRSCGroupConfigNumberofCoolingUnits OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The number of cooling units."
- ::= { airIRSCGroupConfig 1 }
- airIRSCGroupConfigConfigurationType OBJECT-TYPE
- SYNTAX AirIRSCConfigType
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The group configuration type."
- ::= { airIRSCGroupConfig 2 }
- airIRSCGroupConfigCapacityControlType OBJECT-TYPE
- SYNTAX AirIRSCCapacityControlType
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The group capacity control."
- ::= { airIRSCGroupConfig 3 }
- airIRSCGroupConfigAltitudeUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The group altitude of the units above sea level in feet."
- ::= { airIRSCGroupConfig 4 }
- airIRSCGroupConfigAltitudeMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The group altitude of the units above sea level in meters."
- ::= { airIRSCGroupConfig 5 }
- airIRSCGroupConfigFanSpeedControl OBJECT-TYPE
- SYNTAX AirIRSCFanSpeedControl
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The group fan speed control."
- ::= { airIRSCGroupConfig 6 }
- -- ******************************************************************
- -- airIRG2 Ident
- -- ******************************************************************
- airIRG2IdentName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the unit name."
- ::= { airIRG2Ident 1 }
- airIRG2IdentLocation OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the unit location."
- ::= { airIRG2Ident 2 }
- airIRG2IdentModelNumber OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the unit model number."
- ::= { airIRG2Ident 3 }
- airIRG2IdentSerialNumber OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the unit serial number."
- ::= { airIRG2Ident 4 }
- airIRG2IdentFirmwareRevision OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the unit firmware version."
- ::= { airIRG2Ident 5 }
- airIRG2IdentHardwareRevision OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the unit controller hardware revision."
- ::= { airIRG2Ident 6 }
- airIRG2IdentManufactureDate OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the unit manufacture date."
- ::= { airIRG2Ident 7 }
- airIRG2IdentUnitSysOID OBJECT-TYPE
- SYNTAX OBJECT IDENTIFIER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID contains an OID path to the device's top level unit data."
- ::= { airIRG2Ident 8 }
- airIRG2IdentGroupSysOID OBJECT-TYPE
- SYNTAX OBJECT IDENTIFIER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID contains an OID path to the device's top level group data."
- ::= { airIRG2Ident 9 }
- -- ******************************************************************
- -- airIRG2 GROUP Status
- -- ******************************************************************
- airIRG2GroupStatusCoolOutput OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The group cooling output in tenths of kilowatts (kW)."
- ::= { airIRG2GroupStatus 1 }
- airIRG2GroupStatusCoolDemand OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The group cooling demand in tenths of kilowatts (kW)."
- ::= { airIRG2GroupStatus 2 }
- airIRG2GroupStatusAirFlowUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The group air flow in cubic feet per minute."
- ::= { airIRG2GroupStatus 3 }
- airIRG2GroupStatusAirFlowMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The group air flow in hundredths of
- liters per second."
- ::= { airIRG2GroupStatus 4 }
- airIRG2GroupStatusMaxRackInletTempUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The group maximum rack inlet temperature in tenths of
- degrees Fahrenheit."
- ::= { airIRG2GroupStatus 5 }
- airIRG2GroupStatusMaxRackInletTempMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The group maximum rack inlet temperature in tenths of
- degrees Celsius."
- ::= { airIRG2GroupStatus 6 }
- airIRG2GroupStatusMinRackInletTempUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The group minimum rack inlet temperature in tenths of
- degrees Fahrenheit."
- ::= { airIRG2GroupStatus 7 }
- airIRG2GroupStatusMinRackInletTempMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The group minimum rack inlet temperature in tenths of
- degrees Celsius."
- ::= { airIRG2GroupStatus 8 }
- airIRG2GroupStatusMaxReturnAirTempUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The group maximum return air temperature in tenths of
- degrees Fahrenheit."
- ::= { airIRG2GroupStatus 9 }
- airIRG2GroupStatusMaxReturnAirTempMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The group maximum return air temperature in tenths of
- degrees Celsius."
- ::= { airIRG2GroupStatus 10 }
- airIRG2GroupStatusMinReturnAirTempUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The group minimum return air temperature in tenths of
- degrees Fahrenheit."
- ::= { airIRG2GroupStatus 11 }
- airIRG2GroupStatusMinReturnAirTempMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The group minimum return air temperature in tenths of
- degrees Celsius."
- ::= { airIRG2GroupStatus 12 }
- -- ******************************************************************
- -- airIRG2 GROUP Setpoint
- -- ******************************************************************
- airIRG2GroupSetptsCoolSetpointUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Group cooling setpoint in tenths of
- degrees Fahrenheit."
- ::= { airIRG2GroupSetpoints 1 }
- airIRG2GroupSetptsCoolSetpointMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Group cooling setpoint in tenths of
- degrees Celsius."
- ::= { airIRG2GroupSetpoints 2 }
- airIRG2GroupSetptsCoolDeadbandUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Group cooling deadband in tenths of
- degrees Fahrenheit."
- ::= { airIRG2GroupSetpoints 3 }
- airIRG2GroupSetptsCoolDeadbandMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Group cooling deadband in tenths of
- degrees Celsius."
- ::= { airIRG2GroupSetpoints 4 }
- airIRG2GroupSetptsFanSpeedPreference OBJECT-TYPE
- SYNTAX INTEGER {
- low (1),
- med-low (2),
- med (3),
- med-high (4),
- high (5)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The group preferred fan speed setting."
- ::= { airIRG2GroupSetpoints 5 }
- airIRG2GroupSetptsSupplyAirSetpointUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Group supply air setpoint in tenths of
- degrees Fahrenheit."
- ::= { airIRG2GroupSetpoints 6 }
- airIRG2GroupSetptsSupplyAirSetpointMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Group supply air setpoint in tenths of
- degrees Celsius."
- ::= { airIRG2GroupSetpoints 7 }
- -- ******************************************************************
- -- airIRG2 GROUP Config
- -- ******************************************************************
- airIRG2GroupConfigNumberofCoolingUnits OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The number of cooling units."
- ::= { airIRG2GroupConfig 1 }
- airIRG2GroupConfigConfigurationType OBJECT-TYPE
- SYNTAX INTEGER {
- racs (1),
- spot (2),
- in-row (3),
- hacs (4)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The group configuration type."
- ::= { airIRG2GroupConfig 2 }
- airIRG2GroupConfigCapacityControlType OBJECT-TYPE
- SYNTAX INTEGER {
- discrete (1),
- proportional (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The group capacity control."
- ::= { airIRG2GroupConfig 3 }
- airIRG2GroupConfigFanSpeedControl OBJECT-TYPE
- SYNTAX INTEGER {
- automatic (1),
- manual (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The group fan speed control."
- ::= { airIRG2GroupConfig 4 }
- airIRG2GroupConfigCoolGainP OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The gain component of the PID in hundredths."
- ::= { airIRG2GroupConfig 5 }
- airIRG2GroupConfigCoolResetRateI OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The integral component of the PID in hundredths."
- ::= { airIRG2GroupConfig 6 }
- airIRG2GroupConfigCoolDerivativeD OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The derivative component of the PID in hundredths."
- ::= { airIRG2GroupConfig 7 }
- airIRG2GroupConfigCoolPIDReset OBJECT-TYPE
- SYNTAX INTEGER {
- readBack (1),
- reset (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Will reset the PID coefficients back to the factory defaults."
- ::= { airIRG2GroupConfig 8 }
- airIRG2GroupConfigNumberofBackupUnits OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The number of backup units."
- ::= { airIRG2GroupConfig 9 }
- airIRG2GroupConfigRuntimeBalancingEnable OBJECT-TYPE
- SYNTAX INTEGER {
- disable (1),
- enable (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enable or disable runtime balancing feature."
- ::= { airIRG2GroupConfig 10 }
- airIRG2GroupConfigLoadAssistEnable OBJECT-TYPE
- SYNTAX INTEGER {
- disable (1),
- enable (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enable or disable load assist feature."
- ::= { airIRG2GroupConfig 11 }
- -- ***************************************
- -- airIRG2 Alarm Status
- -- ***************************************
- airIRG2AlarmsTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of active alarms in the airIRG2AlarmsTable."
- ::= { airIRG2Alarms 1 }
- AirIRG2AlarmsEntry ::= SEQUENCE {
- airIRG2AlarmsIndex INTEGER,
- airIRG2AlarmsEventCode INTEGER,
- airIRG2AlarmsDescription DisplayString
- }
- airIRG2AlarmsTable OBJECT-TYPE
- SYNTAX SEQUENCE OF AirIRG2AlarmsEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Table of active alarms for the device."
- ::= { airIRG2Alarms 2 }
- airIRG2AlarmsEntry OBJECT-TYPE
- SYNTAX AirIRG2AlarmsEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Alarms specification"
- INDEX { airIRG2AlarmsIndex }
- ::= { airIRG2AlarmsTable 1 }
- airIRG2AlarmsIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Alarm index."
- ::= { airIRG2AlarmsEntry 1 }
- airIRG2AlarmsEventCode OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Code for the alarm."
- ::= { airIRG2AlarmsEntry 2 }
- airIRG2AlarmsDescription OBJECT-TYPE
- SYNTAX DisplayString (SIZE (0..64))
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Description of the alarm."
- ::= { airIRG2AlarmsEntry 3 }
- -- ***************************************
- -- airIRG2RDType2 AIR CONDITIONER Defines
- -- ***************************************
- AirIRG2RDType2IOState ::= INTEGER {
- open (1),
- closed (2)
- }
- -- ******************************************************************
- -- airIRG2RDT2 Status
- -- ******************************************************************
- airIRG2RDT2StatusOperateMode OBJECT-TYPE
- SYNTAX INTEGER {
- standby (1),
- on (2),
- idle (3),
- reserved (4),
- service (5)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The cooling unit operating mode."
- ::= { airIRG2RDT2Status 1 }
- airIRG2RDT2StatusCoolOutput OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit cooling output in tenths of kilowatts (kW)."
- ::= { airIRG2RDT2Status 2 }
- airIRG2RDT2StatusCoolDemand OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit cooling demand in tenths of kilowatts (kW)."
- ::= { airIRG2RDT2Status 3 }
- airIRG2RDT2StatusAirFlowUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit air flow in cubic feet per minute."
- ::= { airIRG2RDT2Status 4 }
- airIRG2RDT2StatusAirFlowMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit air flow in hundredths of
- liters per second."
- ::= { airIRG2RDT2Status 5 }
- airIRG2RDT2StatusRackInletTempUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit rack inlet temperature in tenths of
- degrees Fahrenheit."
- ::= { airIRG2RDT2Status 6 }
- airIRG2RDT2StatusRackInletTempMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit rack inlet temperature in tenths of
- degrees Celsius."
- ::= { airIRG2RDT2Status 7 }
- airIRG2RDT2StatusSupplyAirTempUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit supply air temperature in tenths of
- degrees Fahrenheit."
- ::= { airIRG2RDT2Status 8 }
- airIRG2RDT2StatusSupplyAirTempMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit supply air temperature in tenths of
- degrees Celsius."
- ::= { airIRG2RDT2Status 9 }
- airIRG2RDT2StatusReturnAirTempUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit return air temperature in tenths of
- degrees Fahrenheit."
- ::= { airIRG2RDT2Status 10 }
- airIRG2RDT2StatusReturnAirTempMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit return air temperature in tenths of
- degrees Celsius."
- ::= { airIRG2RDT2Status 11 }
- airIRG2RDT2StatusSuctionTempUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit suction temperature in tenths of
- degrees Fahrenheit."
- ::= { airIRG2RDT2Status 12 }
- airIRG2RDT2StatusSuctionTempMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit suction temperature in tenths of
- degrees Celsius."
- ::= { airIRG2RDT2Status 13 }
- airIRG2RDT2StatusSuperheatTempUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit superheat temperature in tenths of
- degrees Fahrenheit."
- ::= { airIRG2RDT2Status 14 }
- airIRG2RDT2StatusSuperheatTempMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit superheat temperature in tenths of
- degrees Celsius."
- ::= { airIRG2RDT2Status 15 }
- airIRG2RDT2StatusFilterDPUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit air filter differential pressure in
- hundredths of inches of water."
- ::= { airIRG2RDT2Status 16 }
- airIRG2RDT2StatusFilterDPMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit air filter differential pressure in pascals (Pa)."
- ::= { airIRG2RDT2Status 17 }
- airIRG2RDT2StatusSuctionPressureUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit suction pressure in pounds per square inch (PSI)."
- ::= { airIRG2RDT2Status 18 }
- airIRG2RDT2StatusSuctionPressureMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit suction pressure in kiloPascals (kPa)."
- ::= { airIRG2RDT2Status 19 }
-
- airIRG2RDT2StatusDischargePressureUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit discharge pressure in pounds per square inch (PSI)."
- ::= { airIRG2RDT2Status 20 }
- airIRG2RDT2StatusDischargePressureMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit discharge pressure in kiloPascals (kPa)."
- ::= { airIRG2RDT2Status 21 }
- airIRG2RDT2StatusEvaporatorFanSpeed OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The unit average evaporator fan speed in tenths of percent."
- ::= { airIRG2RDT2Status 22 }
- airIRG2RDT2StatusInputState OBJECT-TYPE
- SYNTAX AirIRG2RDType2IOState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The state of the input contact."
- ::= { airIRG2RDT2Status 23 }
- airIRG2RDT2StatusOutputState OBJECT-TYPE
- SYNTAX AirIRG2RDType2IOState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The state of the output relay."
- ::= { airIRG2RDT2Status 24 }
- airIRG2RDT2StatusOHEInputState OBJECT-TYPE
- SYNTAX AirIRG2RDType2IOState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The state of the outside heat exchanger(OHE) input contact."
- ::= { airIRG2RDT2Status 25 }
- airIRG2RDT2StatusOHEOutputState OBJECT-TYPE
- SYNTAX AirIRG2RDType2IOState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The state of the outside heat exchanger(OHE) output relay."
- ::= { airIRG2RDT2Status 26 }
- airIRG2RDT2StatusCompressor OBJECT-TYPE
- SYNTAX INTEGER {
- off (1),
- on (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The state (off/on) of the compressor."
- ::= { airIRG2RDT2Status 27 }
- airIRG2RDT2StatusFluidValvePos OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The position of the fluid valve in percent. This OID is only valid
- when airIRG2RDT2ConfigUnitType indicates fluidCooled(1)."
- ::= { airIRG2RDT2Status 28 }
- airIRG2RDT2StatusHotGasBypassValvePos OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The position of the hot gas bypass valve in hundredths of percent."
- ::= { airIRG2RDT2Status 29 }
- -- ******************************************************************
- -- airIRG2RDT2 Runhours
- -- ******************************************************************
- airIRG2RDT2RunHoursAirFilter OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit air filter run hours."
- ::= { airIRG2RDT2RunHours 1 }
- airIRG2RDT2RunHoursCondensatePump OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit condensate pump run hours."
- ::= { airIRG2RDT2RunHours 2 }
- airIRG2RDT2RunHoursCompressor OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit compressor run hours."
- ::= { airIRG2RDT2RunHours 3 }
- -- *******************************
- -- Run Hour Fan Power supply table
- -- *******************************
- airIRG2RDT2RunHoursFanPSTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the run hour fan power supply table
- (airIRG2RDT2RunHoursFanPSTable)."
- ::= { airIRG2RDT2RunHours 4 }
- AirIRG2RDT2RunHoursFanPSEntry ::=
- SEQUENCE {
- airIRG2RDT2RunHoursFanPSIndex INTEGER,
- airIRG2RDT2RunHoursFanPSPosition INTEGER,
- airIRG2RDT2RunHoursFanPSHours INTEGER
- }
- airIRG2RDT2RunHoursFanPSTable OBJECT-TYPE
- SYNTAX SEQUENCE OF AirIRG2RDT2RunHoursFanPSEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting run hour information from each power supply."
- ::= { airIRG2RDT2RunHours 5 }
- airIRG2RDT2RunHoursFanPSEntry OBJECT-TYPE
- SYNTAX AirIRG2RDT2RunHoursFanPSEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The run hours fan power supply table entry."
- INDEX { airIRG2RDT2RunHoursFanPSIndex }
- ::= { airIRG2RDT2RunHoursFanPSTable 1 }
- airIRG2RDT2RunHoursFanPSIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Index of run hours fan power supply table."
- ::= { airIRG2RDT2RunHoursFanPSEntry 1 }
- airIRG2RDT2RunHoursFanPSHours OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Fan power supply run time in hours."
- ::= { airIRG2RDT2RunHoursFanPSEntry 2 }
- airIRG2RDT2RunHoursFanPSPosition OBJECT-TYPE
- SYNTAX INTEGER {
- upper (1),
- lower (2),
- left (3),
- right (4)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Position of fan power supply within the unit."
- ::= { airIRG2RDT2RunHoursFanPSEntry 3 }
- -- *****************************
- -- Run Hour Evaporator Fan table
- -- *****************************
- airIRG2RDT2RunHoursEvapFanTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the run hour evaporator fan table
- (airIRG2RDT2RunHoursEvapFanTable)."
- ::= { airIRG2RDT2RunHours 6 }
- AirIRG2RDT2RunHoursEvapFanEntry ::=
- SEQUENCE {
- airIRG2RDT2RunHoursEvapFanIndex INTEGER,
- airIRG2RDT2RunHoursEvapFanHours INTEGER
- }
- airIRG2RDT2RunHoursEvapFanTable OBJECT-TYPE
- SYNTAX SEQUENCE OF AirIRG2RDT2RunHoursEvapFanEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting information from each evaporator fan run
- hour in the system. "
- ::= { airIRG2RDT2RunHours 7 }
- airIRG2RDT2RunHoursEvapFanEntry OBJECT-TYPE
- SYNTAX AirIRG2RDT2RunHoursEvapFanEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting information from each evaporator fan run
- hour in the system. "
- INDEX { airIRG2RDT2RunHoursEvapFanIndex }
- ::= { airIRG2RDT2RunHoursEvapFanTable 1 }
- airIRG2RDT2RunHoursEvapFanIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Index of run hours evaporator fan table."
- ::= { airIRG2RDT2RunHoursEvapFanEntry 1 }
- airIRG2RDT2RunHoursEvapFanHours OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Evaporator fan run time in hours."
- ::= { airIRG2RDT2RunHoursEvapFanEntry 2 }
- airIRG2RDT2RunHoursUnit OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit run time in hours."
- ::= { airIRG2RDT2RunHours 8 }
-
- -- ******************************************************************
- -- airIRG2RDT2 Service Intervals
- -- ******************************************************************
- airIRG2RDT2ServiceIntervalsAirFilter OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Air filter service interval in weeks."
- ::= { airIRG2RDT2ServiceIntervals 1 }
- airIRG2RDT2ServiceIntervalsAirFilterAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- enable (1),
- disable (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The air filter service interval alarm enable/disable."
- ::= { airIRG2RDT2ServiceIntervals 2 }
- -- ******************************************************************
- -- airIRG2RDT2 Thresholds
- -- ******************************************************************
- airIRG2RDT2ThresholdsRackInletHighTempUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Unit rack inlet air high temperature threshold in
- tenths of degrees Fahrenheit."
- ::= { airIRG2RDT2Thresholds 1 }
- airIRG2RDT2ThresholdsRackInletHighTempMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Unit rack inlet air high temperature threshold in
- tenths of degrees Celsius."
- ::= { airIRG2RDT2Thresholds 2 }
- airIRG2RDT2ThresholdsSupplyAirHighTempUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Unit supply air high temperature threshold in
- tenths of degrees Fahrenheit."
- ::= { airIRG2RDT2Thresholds 3 }
- airIRG2RDT2ThresholdsSupplyAirHighTempMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Unit supply air high temperature threshold in
- tenths of degrees Celsius."
- ::= { airIRG2RDT2Thresholds 4 }
- airIRG2RDT2ThresholdsReturnAirHighTempUS OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Unit return air high temperature threshold in
- tenths of degrees Fahrenheit."
- ::= { airIRG2RDT2Thresholds 5 }
- airIRG2RDT2ThresholdsReturnAirHighTempMetric OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Unit return air high temperature threshold in
- tenths of degrees Celsius."
- ::= { airIRG2RDT2Thresholds 6 }
- -- ******************************************************************
- -- airIRG2RDT2 Setpoints
- -- ******************************************************************
- -- There are no setpoint OIDs. This is just a placeholder in case
- -- we add some unit setpoints.
- -- ******************************************************************
- -- airIRG2RDT2 Config
- -- ******************************************************************
- airIRG2RDT2ConfigUnitType OBJECT-TYPE
- SYNTAX INTEGER {
- fluidCooled (1),
- airCooled (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The type of the unit."
- ::= { airIRG2RDT2Config 1 }
- airIRG2RDT2ConfigStartupDelay OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The startup delay in seconds."
- ::= { airIRG2RDT2Config 2 }
- airIRG2RDT2ConfigIdleOnLeakDetect OBJECT-TYPE
- SYNTAX INTEGER {
- yes (1),
- no (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The idle on leak options setting."
- ::= { airIRG2RDT2Config 3 }
- airIRG2RDT2ConfigInputNormalState OBJECT-TYPE
- SYNTAX AirIRG2RDType2IOState
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The normal state of the input contact."
- ::= { airIRG2RDT2Config 4 }
- airIRG2RDT2ConfigOutputNormalState OBJECT-TYPE
- SYNTAX AirIRG2RDType2IOState
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The normal state of the output relay."
- ::= { airIRG2RDT2Config 5 }
- airIRG2RDT2ConfigOutputSource OBJECT-TYPE
- SYNTAX INTEGER {
- anyAlarm (1),
- criticalAlarm (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The source of output relay change."
- ::= { airIRG2RDT2Config 6 }
- airIRG2RDT2ConfigOHEInputNormalState OBJECT-TYPE
- SYNTAX AirIRG2RDType2IOState
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The normal state of the outside heat exchanger(OHE) input relay."
- ::= { airIRG2RDT2Config 7 }
- airIRG2RDT2ConfigUnitRoleOverride OBJECT-TYPE
- SYNTAX INTEGER {
- automatic (1),
- forcedOn (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "When this OID value is (1) automatic, the system determines
- which units are used as primary units and which units are used as backups.
- When this OID value is (2) forcedOn, the connected unit is set as a primary
- unit."
- ::= { airIRG2RDT2Config 8 }
- airIRG2RDT2ConfigUnitIdleOnCoolFail OBJECT-TYPE
- SYNTAX INTEGER {
- no (1),
- yes (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "When this OID value is (2) yes, the unit idles if it detects that it is blowing warm
- air into the cold aisle. The unit will attempt to restart at 5 minute intervals."
- ::= { airIRG2RDT2Config 9 }
- -- Beginning of AC InRoom
- -- common InRoom values
- AirIRmAlarmState ::= INTEGER { ok (1), alarm (2) }
- AirIRmControlState ::= INTEGER { off (1), on (2) }
- AirIRmStopState ::= INTEGER { maybeOn (1), unitOff (2) }
- AirIRmActivityState ::= INTEGER { inactive (1), active (2) }
- -- ***************************************
- -- InRoom Ident
- -- ***************************************
- airIRmIdentName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the unit name."
- ::= { airIRmIdent 1 }
- airIRmIdentLocation OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the unit location."
- ::= { airIRmIdent 2 }
- airIRmIdentModelNumber OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the unit model number."
- ::= { airIRmIdent 3 }
- airIRmIdentSerialNumber OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the unit serial number."
- ::= { airIRmIdent 4 }
- airIRmIdentFirmwareRevision OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the unit firmware version."
- ::= { airIRmIdent 5 }
- airIRmIdentHardwareRevision OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the unit controller hardware revision."
- ::= { airIRmIdent 6 }
- airIRmIdentManufactureDate OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the unit manufacture date."
- ::= { airIRmIdent 7 }
- airIRmIdentSysOID OBJECT-TYPE
- SYNTAX OBJECT IDENTIFIER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID contains an OID path to the device's top level data."
- ::= { airIRmIdent 8 }
- -- ***************************************
- -- InRoom Alarm Status
- -- ***************************************
- airIRmAlarmsTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of active alarms in the airIRG2AlarmsTable."
- ::= { airIRmAlarms 1 }
- AirIRmAlarmsEntry ::= SEQUENCE {
- airIRmAlarmsIndex INTEGER,
- airIRmAlarmsEventCode INTEGER,
- airIRmAlarmsDescription DisplayString
- }
- airIRmAlarmsTable OBJECT-TYPE
- SYNTAX SEQUENCE OF AirIRmAlarmsEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Table of active alarms for the device."
- ::= { airIRmAlarms 2 }
- airIRmAlarmsEntry OBJECT-TYPE
- SYNTAX AirIRmAlarmsEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Alarms specification"
- INDEX { airIRmAlarmsIndex }
- ::= { airIRmAlarmsTable 1 }
- airIRmAlarmsIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Alarm index."
- ::= { airIRmAlarmsEntry 1 }
- airIRmAlarmsEventCode OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Code for the alarm."
- ::= { airIRmAlarmsEntry 2 }
- airIRmAlarmsDescription OBJECT-TYPE
- SYNTAX DisplayString (SIZE (0..64))
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Description of the alarm."
- ::= { airIRmAlarmsEntry 3 }
- -- airIRmPmCommon1
- airIRmPmUnitType OBJECT-TYPE
- SYNTAX INTEGER {
- mc (1),
- dx (2),
- cw (3),
- ch (4),
- ecoCool (5),
- msc (6),
- ge1 (7),
- ge2 (8),
- dualFluid (9),
- cw2 (10),
- unknown (256) }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit type (1)."
- ::= { airIRmPmCommon1 1 }
- airIRmPmSwVersion OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Software version (3)."
- ::= { airIRmPmCommon1 3 }
- airIRmPmBusAddress OBJECT-TYPE
- SYNTAX INTEGER (0..65535)
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Bus addresss of unit (5)."
- ::= { airIRmPmCommon1 5 }
- airIRmPmControllerType OBJECT-TYPE
- SYNTAX INTEGER {
- unknown (1),
- c4000 (2),
- c1001 (3),
- c1002 (4),
- c5000 (5),
- c6000 (6),
- c1010 (7),
- c7000IOC (8),
- c7000AT (9),
- c7000PT (10),
- c5MSC (11),
- c7000PT2 (12) }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Controller type (7)."
- ::= { airIRmPmCommon1 7 }
- airIRmPmGeneralError OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "General Error (8)"
- ::= { airIRmPmCommon1 8 }
- airIRmPmErrorOnBus OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Error On Bus (9)"
- ::= { airIRmPmCommon1 9 }
- -- airIRmPmCommon2
- airIRmPmPCStop OBJECT-TYPE
- SYNTAX AirIRmStopState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "PC-STOP (1000)"
- ::= { airIRmPmCommon2 1 }
- airIRmPmRemoteStop OBJECT-TYPE
- SYNTAX AirIRmStopState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Remote Stop (1001)"
- ::= { airIRmPmCommon2 2 }
- airIRmPmLocalStop OBJECT-TYPE
- SYNTAX AirIRmStopState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Local Stop (1002)"
- ::= { airIRmPmCommon2 3}
- airIRmPmTimerStop OBJECT-TYPE
- SYNTAX AirIRmStopState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Timer Stop (1003)"
- ::= { airIRmPmCommon2 4}
- airIRmPmSeqStop OBJECT-TYPE
- SYNTAX AirIRmStopState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Seq. Stop (1004)"
- ::= { airIRmPmCommon2 5}
- airIRmPmRemoteUPS OBJECT-TYPE
- SYNTAX INTEGER {
- off (1),
- on (2) }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Remote UPS (1006)"
- ::= { airIRmPmCommon2 7}
- airIRmPmLocalUPS OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Local UPS (1007)"
- ::= { airIRmPmCommon2 8}
- airIRmPmCommonAlarm OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Common alarm (1010)."
- ::= { airIRmPmCommon2 11 }
- airIRmPmResetAllAlarms OBJECT-TYPE
- SYNTAX INTEGER {
- doNothing (1),
- reset (2) }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Reset all alarms control (1011)."
- ::= { airIRmPmCommon2 12 }
- airIRmPmUnitOnOff OBJECT-TYPE
- SYNTAX AirIRmControlState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit running state (1013)."
- ::= { airIRmPmCommon2 14 }
- airIRmPmMaintenance OBJECT-TYPE
- SYNTAX INTEGER {
- notNecessary (1),
- necessary (2) }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Maintenance necessary state (1014)."
- ::= { airIRmPmCommon2 15 }
- airIRmPmUnitTemperatureScale OBJECT-TYPE
- SYNTAX INTEGER {
- celsius (1),
- fahrenheit (2) }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Current Unit Temperature Scale (1022)."
- ::= { airIRmPmCommon2 23 }
- airIRmPmUnitWinterMode OBJECT-TYPE
- SYNTAX INTEGER {
- summer (1),
- winter (2) }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Winter or summer configuration mode (1023)."
- ::= { airIRmPmCommon2 24 }
- airIRmPmDayNightMode OBJECT-TYPE
- SYNTAX INTEGER {
- day (1),
- night (2) }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Day or night configuration mode (1024)."
- ::= { airIRmPmCommon2 25 }
- -- airIRmPmCommon3
- airIRmPmLastMaintenanceYear OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Last maintenance year (1160)."
- ::= { airIRmPmCommon3 1 }
- airIRmPmLastMaintenanceMonth OBJECT-TYPE
- SYNTAX INTEGER (1..12)
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Last maintenance month (1161)."
- ::= { airIRmPmCommon3 2 }
- airIRmPmLastMaintenanceDay OBJECT-TYPE
- SYNTAX INTEGER (1..31)
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Last maintenance day (1162)."
- ::= { airIRmPmCommon3 3 }
- airIRmPmUnitMaintenanceInterval OBJECT-TYPE
- SYNTAX INTEGER (1..255)
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit maintenance interval in months (1163)."
- ::= { airIRmPmCommon3 4 }
- airIRmPmRuntimeUnit OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Runtime unit in hours (1164)."
- ::= { airIRmPmCommon3 5 }
- airIRmPmStoptimeUnit OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit stoptime in hours (1165)"
- ::= { airIRmPmCommon3 6 }
- airIRmPmRuntimeCooling OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Cooling runtime in hours (1166)"
- ::= { airIRmPmCommon3 7 }
- airIRmPmRuntimeHeating OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Heating runtime in hours (1167)"
- ::= { airIRmPmCommon3 8 }
- airIRmPmRuntimeHumidification OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Humidification runtime in hours (1168)"
- ::= { airIRmPmCommon3 9 }
- airIRmPmRuntimeDehumidification OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Dehumidification runtime in hours (1169)"
- ::= { airIRmPmCommon3 10 }
- airIRmPmUnitTemperature OBJECT IDENTIFIER ::= { airIRmPmCommon3 11 }
- airIRmPmUnitTemperatureC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit temperature in tenths of degrees Celsius (1170)."
- ::= { airIRmPmUnitTemperature 1 }
- airIRmPmUnitTemperatureF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit temperature in tenths of degrees Fahrenheit (1170)."
- ::= { airIRmPmUnitTemperature 2 }
- airIRmPmUnitHumidity OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit humidity in tenths of %RH (1171)."
- ::= { airIRmPmCommon3 12 }
- airIRmPmSetpointTemperatureDay OBJECT IDENTIFIER ::= { airIRmPmCommon3 14 }
- airIRmPmSetpointTemperatureDayC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Setpoint daytime temperature in tenths
- of degrees Celsius (1173)."
- ::= { airIRmPmSetpointTemperatureDay 1 }
- airIRmPmSetpointTemperatureDayF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Setpoint daytime temperature in tenths
- of degrees Fahrenheit (1173)."
- ::= { airIRmPmSetpointTemperatureDay 2 }
- airIRmPmSetpointTemperatureNight OBJECT IDENTIFIER ::= { airIRmPmCommon3 15 }
- airIRmPmSetpointTemperatureNightC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Setpoint nighttime temperature in tenths
- of degrees Celsius (1174)."
- ::= { airIRmPmSetpointTemperatureNight 1 }
- airIRmPmSetpointTemperatureNightF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Setpoint nighttime temperature in tenths
- of degrees Fahrenheit (1174)."
- ::= { airIRmPmSetpointTemperatureNight 2 }
- airIRmPmSetpointHumidity OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Setpoint humidity in tenths of %RH (1176)."
- ::= { airIRmPmCommon3 17 }
- airIRmPmUnitControlType OBJECT-TYPE
- SYNTAX INTEGER {
- room (1),
- supply (2),
- room-SupplyLimit (3),
- supply-RoomLimit (4) }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Current unit control type (1183)."
- ::= { airIRmPmCommon3 24 }
- airIRmPmWinterModeStartTemp OBJECT IDENTIFIER ::= { airIRmPmCommon3 29 }
- airIRmPmWinterModeStartTempC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Winter mode start temperature in tenths of degrees Celsius (1188)."
- ::= { airIRmPmWinterModeStartTemp 1 }
- airIRmPmWinterModeStartTempF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Winter mode start temperature in tenths of degrees Fahrenheit (1188)."
- ::= { airIRmPmWinterModeStartTemp 2 }
- airIRmPmWinterModeHysteresis OBJECT IDENTIFIER ::= { airIRmPmCommon3 30 }
- airIRmPmWinterModeHysteresisK OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Winter mode hysteresis in tenths of Kelvins (1189)"
- ::= { airIRmPmWinterModeHysteresis 1 }
- airIRmPmWinterModeHysteresisF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Winter mode hysteresis in tenths of degrees Fahrenheit (1189)"
- ::= { airIRmPmWinterModeHysteresis 2 }
- airIRmPmWaterTemperature OBJECT IDENTIFIER ::= { airIRmPmCommon3 32 }
- airIRmPmWaterTemperatureC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Water temperature in tenths of degrees Celsius (1191)."
- ::= { airIRmPmWaterTemperature 1 }
- airIRmPmWaterTemperatureF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Water temperature in tenths of degrees Fahrenheit (1191)."
- ::= { airIRmPmWaterTemperature 2 }
- airIRmPmReturnAirTemperature OBJECT IDENTIFIER ::= { airIRmPmCommon3 33 }
- airIRmPmReturnAirTemperatureC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Return air temperature in tenths of degrees Celsius (1192)."
- ::= { airIRmPmReturnAirTemperature 1 }
- airIRmPmReturnAirTemperatureF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Return air temperature in tenths of degrees Fahrenheit (1192)."
- ::= { airIRmPmReturnAirTemperature 2 }
- airIRmPmSupplyAirTemperature OBJECT IDENTIFIER ::= { airIRmPmCommon3 34 }
- airIRmPmSupplyAirTemperatureC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Supply air temperature in tenths of degrees Celsius (1193)."
- ::= { airIRmPmSupplyAirTemperature 1 }
- airIRmPmSupplyAirTemperatureF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Supply air temperature in tenths of degrees Fahrenheit (1193)."
- ::= { airIRmPmSupplyAirTemperature 2 }
- airIRmPmReturnAirHumidity OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Return air humidity in tenths of %RH (1194)."
- ::= { airIRmPmCommon3 35 }
- airIRmPmSupplyAirHumidity OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Supply air humidity in tenths of %RH (1195)."
- ::= { airIRmPmCommon3 36 }
- airIRmPmOutsideAirTemperature OBJECT IDENTIFIER ::= { airIRmPmCommon3 37 }
- airIRmPmOutsideAirTemperatureC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Outside air temperature in tenths of degrees Celsius (1196)"
- ::= { airIRmPmOutsideAirTemperature 1 }
- airIRmPmOutsideAirTemperatureF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Outside air temperature in tenths of degrees Fahrenheit (1196)"
- ::= { airIRmPmOutsideAirTemperature 2 }
- airIRmPmOutsideAirHumidity OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Outside air humidity in tenths of percent relative humidity (1197)"
- ::= { airIRmPmCommon3 38 }
- airIRmPmCoolingPriority OBJECT-TYPE
- SYNTAX INTEGER {
- ge (1),
- cw (2),
- dx (3) }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Cooling priority (1198)."
- ::= { airIRmPmCommon3 39 }
- airIRmPmWaterTemperature2 OBJECT IDENTIFIER ::= { airIRmPmCommon3 43 }
- airIRmPmWaterTemperature2C OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Water temperature 2 in tenths of degrees Celsius (1202)."
- ::= { airIRmPmWaterTemperature2 1 }
- airIRmPmWaterTemperature2F OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Water temperature 2 in tenths of degrees Fahrenheit (1202)."
- ::= { airIRmPmWaterTemperature2 2 }
- airIRmPmRuntimeFreeCooling OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Freecooling runtime in hours (1203)"
- ::= { airIRmPmCommon3 44 }
- airIRmPmRuntimeMixedModeFreeCooling OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Mixed mode freecooling runtime in hours (1203)"
- ::= { airIRmPmCommon3 45 }
- -- airIRmPmCommon4
- airIRmPmNumberOfCompressors OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Number of compressors (1761)"
- ::= { airIRmPmCommon4 4 }
- airIRmPmNumberOfSuctionValves OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Number of suction valves (1762)"
- ::= { airIRmPmCommon4 5 }
- airIRmPmNumberOfDryCoolers OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Number of drycoolers (1763)"
- ::= { airIRmPmCommon4 6 }
- airIRmPmNumberOfPumps OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Number of pumps (1764)"
- ::= { airIRmPmCommon4 7 }
- airIRmPmNumberOfElectricHeaters OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Number of electric heaters (1765)"
- ::= { airIRmPmCommon4 8 }
- airIRmPmNumberOfHumidifiers OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Number of humidifiers (1766)"
- ::= { airIRmPmCommon4 9 }
- airIRmPmNumberOfFans OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Number of fans (1767)"
- ::= { airIRmPmCommon4 10 }
- airIRmPmNumberOfLouvers OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Number of louvers (1768)"
- ::= { airIRmPmCommon4 11 }
- airIRmPmNumberOfSensors OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Number of sensors (1769)"
- ::= { airIRmPmCommon4 12 }
- airIRmPmNumberOfExternalAlarmInputs OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Number of external alarm inputs (1770)"
- ::= { airIRmPmCommon4 13 }
- airIRmPmNumberOfGECWValves OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Number of GE/CW valves (1771)"
- ::= { airIRmPmCommon4 14 }
- airIRmPmNumberOfHotGasReheat OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Number of hot gas reheaters (1772)"
- ::= { airIRmPmCommon4 15 }
- airIRmPmNumberOfPWWReheat OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Number of PWW reheaters (1773)"
- ::= { airIRmPmCommon4 16 }
- airIRmPmNumberOfDehumidifiers OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Number of dehumidifiers (1774)"
- ::= { airIRmPmCommon4 17 }
- -- airIRmPmCommon5
- airIRmPmUnitEvaporationTemperature1 OBJECT IDENTIFIER ::= { airIRmPmCommon5 1 }
- airIRmPmUnitEvaporationTemperature1C OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit evaporation temperature 1 in tenths
- of degrees Celsius (2232)"
- ::= { airIRmPmUnitEvaporationTemperature1 1 }
- airIRmPmUnitEvaporationTemperature1F OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit evaporation temperature 1 in tenths
- of degrees Fahrenheit (2232)"
- ::= { airIRmPmUnitEvaporationTemperature1 2 }
- airIRmPmUnitEvaporationPressure1 OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit evaporation pressure 1 in tenths
- of Bars (2233)"
- ::= { airIRmPmCommon5 2 }
- airIRmPmUnitCondensationTemperature1 OBJECT IDENTIFIER ::= { airIRmPmCommon5 3 }
- airIRmPmUnitCondensationTemperature1C OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit condensation temperature 1 in tenths
- of degrees Celsius (2234)"
- ::= { airIRmPmUnitCondensationTemperature1 1 }
- airIRmPmUnitCondensationTemperature1F OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit condensation temperature 1 in tenths
- of degrees Fahrenheit (2234)"
- ::= { airIRmPmUnitCondensationTemperature1 2 }
- airIRmPmUnitCondensationPressure1 OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit condensation pressure 1 in tenths
- of Bars (2235)"
- ::= { airIRmPmCommon5 4 }
- airIRmPmMaxLimitReturnAirTemperature OBJECT IDENTIFIER ::= { airIRmPmCommon5 8 }
- airIRmPmMaxLimitReturnAirTemperatureC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Maximum limit return air temperature in tenths
- of degrees Celsius (2239)."
- ::= { airIRmPmMaxLimitReturnAirTemperature 1 }
- airIRmPmMaxLimitReturnAirTemperatureF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Maximum limit return air temperature in tenths
- of degrees Fahrenheit (2239)."
- ::= { airIRmPmMaxLimitReturnAirTemperature 2 }
- airIRmPmMinLimitReturnAirTemperature OBJECT IDENTIFIER ::= { airIRmPmCommon5 9 }
- airIRmPmMinLimitReturnAirTemperatureC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Minimum limit return air temperature in tenths
- of degrees Celsius (2240)."
- ::= { airIRmPmMinLimitReturnAirTemperature 1 }
- airIRmPmMinLimitReturnAirTemperatureF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Minimum limit return air temperature in tenths
- of degrees Fahrenheit (2240)."
- ::= { airIRmPmMinLimitReturnAirTemperature 2 }
- airIRmPmMaxLimitSupplyAirTemperature OBJECT IDENTIFIER ::= { airIRmPmCommon5 10 }
- airIRmPmMaxLimitSupplyAirTemperatureC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Maximum limit supply air temperature in tenths
- of degrees Celsius (2241)."
- ::= { airIRmPmMaxLimitSupplyAirTemperature 1 }
- airIRmPmMaxLimitSupplyAirTemperatureF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Maximum limit supply air temperature in tenths
- of degrees Fahrenheit (2241)."
- ::= { airIRmPmMaxLimitSupplyAirTemperature 2 }
- airIRmPmMinLimitSupplyAirTemperature OBJECT IDENTIFIER ::= { airIRmPmCommon5 11 }
- airIRmPmMinLimitSupplyAirTemperatureC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Minimum limit supply air temperature in tenths
- of degrees Celsius (2242)."
- ::= { airIRmPmMinLimitSupplyAirTemperature 1 }
- airIRmPmMinLimitSupplyAirTemperatureF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Minimum limit supply air temperature in tenths
- of degrees Fahrenheit (2242)."
- ::= { airIRmPmMinLimitSupplyAirTemperature 2 }
- airIRmPmMaxLimitWaterTemperature OBJECT IDENTIFIER ::= { airIRmPmCommon5 12 }
- airIRmPmMaxLimitWaterTemperatureC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Maximum limit water temperature in tenths of degrees Celsius (2243)."
- ::= { airIRmPmMaxLimitWaterTemperature 1 }
- airIRmPmMaxLimitWaterTemperatureF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Maximum limit water temperature in tenths
- of degrees Fahrenheit (2243)."
- ::= { airIRmPmMaxLimitWaterTemperature 2 }
- airIRmPmMinLimitWaterTemperature OBJECT IDENTIFIER ::= { airIRmPmCommon5 13 }
- airIRmPmMinLimitWaterTemperatureC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Minimum limit water temperature in tenths
- of degrees Celsius (2244)."
- ::= { airIRmPmMinLimitWaterTemperature 1 }
- airIRmPmMinLimitWaterTemperatureF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Minimum limit water temperature in tenths
- of degrees Fahrenheit (2244)."
- ::= { airIRmPmMinLimitWaterTemperature 2 }
- airIRmPmMaxLimitReturnAirHumidity OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Maximum limit return air humidity in tenths of %RH (2245)."
- ::= { airIRmPmCommon5 14 }
- airIRmPmMinLimitReturnAirHumidity OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Minimum limit return air humidity in tenths of %RH (2246)."
- ::= { airIRmPmCommon5 15 }
- airIRmPmMaxLimitSupplyAirHumidity OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Maximum limit supply air humidity in tenths of %RH (2247)."
- ::= { airIRmPmCommon5 16 }
- airIRmPmMinLimitSupplyAirHumidity OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Minimum limit supply air humidity in tenths of %RH (2248)."
- ::= { airIRmPmCommon5 17 }
- airIRmPmLowPressureWinterDelay OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Winter mode low pressure delay in seconds (2249)"
- ::= { airIRmPmCommon5 18 }
- airIRmPmUnitCondensationPressure2 OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit condensation pressure 2 in tenths of Bars (2250)"
- ::= { airIRmPmCommon5 19 }
- airIRmPmUnitOverloadSwitch OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit overload switch setting in tenths of Kelvins (2251)"
- ::= { airIRmPmCommon5 20 }
- airIRmPmUnitCondensationTemperature2 OBJECT IDENTIFIER ::= { airIRmPmCommon5 41 }
- airIRmPmUnitCondensationTemperature2C OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit condensation temperature 2 in tenths
- of degrees Celsius (2272)"
- ::= { airIRmPmUnitCondensationTemperature2 1 }
- airIRmPmUnitCondensationTemperature2F OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit condensation temperature 2 in tenths
- of degrees Fahrenheit (2272)"
- ::= { airIRmPmUnitCondensationTemperature2 2 }
- airIRmPmUnitEvaporationPressure2 OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit evaporation pressure 2 in tenths
- of Bars (2273)"
- ::= { airIRmPmCommon5 42 }
- airIRmPmUnitEvaporationTemperature2 OBJECT IDENTIFIER ::= { airIRmPmCommon5 43 }
- airIRmPmUnitEvaporationTemperature2C OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit evaporation temperature 2 in tenths
- of degrees Celsius (2274)"
- ::= { airIRmPmUnitEvaporationTemperature2 1 }
- airIRmPmUnitEvaporationTemperature2F OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Unit evaporation temperature 2 in tenths
- of degrees Fahrenheit (2274)"
- ::= { airIRmPmUnitEvaporationTemperature2 2 }
- -- airIRmPmCompressor1
- airIRmPmCmp1ManOperationActive OBJECT-TYPE
- SYNTAX INTEGER {
- automatic (1),
- manual (2) }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Compressor 1 manual operation active (4401)"
- ::= { airIRmPmCompressor1 2 }
- airIRmPmCmp1ManOperationState OBJECT-TYPE
- SYNTAX AirIRmControlState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Compressor 1 manual operation state (4402)"
- ::= { airIRmPmCompressor1 3 }
- airIRmPmCmp1Running OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Compressor 1 running (4403)"
- ::= { airIRmPmCompressor1 4 }
- airIRmPmCmp1StartTempSummer OBJECT IDENTIFIER ::= { airIRmPmCompressor1 17 }
- airIRmPmCmp1StartTempSummerK OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Compressor 1 summer mode start temperature
- in tenths of Kelvins (4416)"
- ::= { airIRmPmCmp1StartTempSummer 1 }
- airIRmPmCmp1StartTempSummerF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Compressor 1 summer mode start temperature
- in tenths of degrees Fahrenheit (4416)"
- ::= { airIRmPmCmp1StartTempSummer 2 }
- airIRmPmCmp1HysteresisSummer OBJECT IDENTIFIER ::= { airIRmPmCompressor1 18 }
- airIRmPmCmp1HysteresisSummerK OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Compressor 1 summer mode hysteresis setting
- in tenths of Kelvins (4417)"
- ::= { airIRmPmCmp1HysteresisSummer 1 }
- airIRmPmCmp1HysteresisSummerF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Compressor 1 summer mode hysteresis setting
- in tenths of Fahrenheit (4417)"
- ::= { airIRmPmCmp1HysteresisSummer 2 }
- airIRmPmCmp1StartTempWinter OBJECT IDENTIFIER ::= { airIRmPmCompressor1 19 }
- airIRmPmCmp1StartTempWinterK OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Compressor 1 winter mode start temperature
- in tenths of Kelvins (4418)"
- ::= { airIRmPmCmp1StartTempWinter 1 }
- airIRmPmCmp1StartTempWinterF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Compressor 1 winter mode start temperature
- in tenths of degrees Fahrenheit (4418)"
- ::= { airIRmPmCmp1StartTempWinter 2 }
- airIRmPmCmp1HysteresisWinter OBJECT IDENTIFIER ::= { airIRmPmCompressor1 20 }
- airIRmPmCmp1HysteresisWinterK OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Compressor 1 Winter mode hysteresis setting
- in tenths of Kelvins (4419)"
- ::= { airIRmPmCmp1HysteresisWinter 1 }
- airIRmPmCmp1HysteresisWinterF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Compressor 1 Winter mode hysteresis setting
- in tenths of Fahrenheit (4419)"
- ::= { airIRmPmCmp1HysteresisWinter 2 }
- airIRmPmCmp1Runtime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Compressor 1 runtime in hours (4428)"
- ::= { airIRmPmCompressor1 29 }
- -- airIRmPmCompressor2
- airIRmPmCmp2ManOperationActive OBJECT-TYPE
- SYNTAX INTEGER {
- automatic (1),
- manual (2) }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Compressor 2 manual operation active (4501)"
- ::= { airIRmPmCompressor2 2 }
- airIRmPmCmp2ManOperationState OBJECT-TYPE
- SYNTAX AirIRmControlState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Compressor 2 manual operation state (4502)"
- ::= { airIRmPmCompressor2 3 }
- airIRmPmCmp2Running OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Compressor 2 running (4503)"
- ::= { airIRmPmCompressor2 4 }
- airIRmPmCmp2StartTempSummer OBJECT IDENTIFIER ::= { airIRmPmCompressor2 17 }
- airIRmPmCmp2StartTempSummerK OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Compressor 2 summer mode start temperature
- in tenths of Kelvins (4516)"
- ::= { airIRmPmCmp2StartTempSummer 1 }
- airIRmPmCmp2StartTempSummerF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Compressor 2 summer mode start temperature
- in tenths of degrees Fahrenheit (4516)"
- ::= { airIRmPmCmp2StartTempSummer 2 }
- airIRmPmCmp2HysteresisSummer OBJECT IDENTIFIER ::= { airIRmPmCompressor2 18 }
- airIRmPmCmp2HysteresisSummerK OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Compressor 2 summer mode hysteresis setting
- in tenths of Kelvins (4517)"
- ::= { airIRmPmCmp2HysteresisSummer 1 }
- airIRmPmCmp2HysteresisSummerF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Compressor 2 summer mode hysteresis setting
- in tenths of Fahrenheit (4517)"
- ::= { airIRmPmCmp2HysteresisSummer 2 }
- airIRmPmCmp2StartTempWinter OBJECT IDENTIFIER ::= { airIRmPmCompressor2 19 }
- airIRmPmCmp2StartTempWinterK OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Compressor 2 winter mode start temperature
- in tenths of Kelvins (4518)"
- ::= { airIRmPmCmp2StartTempWinter 1 }
- airIRmPmCmp2StartTempWinterF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Compressor 2 winter mode start temperature
- in tenths of degrees Fahrenheit (4518)"
- ::= { airIRmPmCmp2StartTempWinter 2 }
- airIRmPmCmp2HysteresisWinter OBJECT IDENTIFIER ::= { airIRmPmCompressor2 20 }
- airIRmPmCmp2HysteresisWinterK OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Compressor 2 Winter mode hysteresis setting
- in tenths of Kelvins (4519)"
- ::= { airIRmPmCmp2HysteresisWinter 1 }
- airIRmPmCmp2HysteresisWinterF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Compressor 2 Winter mode hysteresis setting
- in tenths of Fahrenheit (4519)"
- ::= { airIRmPmCmp2HysteresisWinter 2 }
- airIRmPmCmp2Runtime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Compressor 2 runtime in hours (4528)"
- ::= { airIRmPmCompressor2 29 }
- -- airIRmPmSuctionValve1
- -- Empty
- -- airIRmPmSuctionValve2
- -- Empty
- -- airIRmPmEheating1
- airIRmPmEheating1ManOpEnable OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Electric heater #1 manual operation enable (4801)"
- ::= { airIRmPmEheating1 2 }
- airIRmPmEheating1Running OBJECT-TYPE
- SYNTAX AirIRmControlState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Electric heater #1 running state (4803)"
- ::= { airIRmPmEheating1 4 }
- airIRmPmEheating1ManOpRunning OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Electric heater #1 running in manual operation mode (4804)"
- ::= { airIRmPmEheating1 5 }
- airIRmPmEheating1Type OBJECT-TYPE
- SYNTAX INTEGER {
- direct (1),
- pwm (2) }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Electric heater #1 type (4808)"
- ::= { airIRmPmEheating1 9 }
- airIRmPmEheating1StartTemperature OBJECT IDENTIFIER ::= { airIRmPmEheating1 10 }
- airIRmPmEheating1StartTemperatureK OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Electric heater #1 start temperature in tenths of Kelvins (4809)"
- ::= { airIRmPmEheating1StartTemperature 1 }
- airIRmPmEheating1StartTemperatureF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Electric heater #1 start temperature in tenths of degrees Fahrenheit (4809)"
- ::= { airIRmPmEheating1StartTemperature 2 }
- airIRmPmEheating1Hysteresis OBJECT IDENTIFIER ::= { airIRmPmEheating1 11 }
- airIRmPmEheating1HysteresisK OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Electric heater #1 hysteresis in tenths of Kelvins (4810)"
- ::= { airIRmPmEheating1Hysteresis 1 }
- airIRmPmEheating1HysteresisF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Electric heater #1 hysteresis in tenths of degrees Fahrenheit (4810)"
- ::= { airIRmPmEheating1Hysteresis 2 }
- airIRmPmEheating1Runtime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Electric heater #1 runtime in hours (4816)"
- ::= { airIRmPmEheating1 17 }
- -- airIRmPmEheating2
- airIRmPmEheating2ManOpEnable OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Electric heater #2 manual operation enable (4901)"
- ::= { airIRmPmEheating2 2 }
- airIRmPmEheating2Running OBJECT-TYPE
- SYNTAX AirIRmControlState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Electric heater #2 running state (4903)"
- ::= { airIRmPmEheating2 4 }
- airIRmPmEheating2ManOpRunning OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Electric heater #2 running in manual operation mode (4904)"
- ::= { airIRmPmEheating2 5 }
- airIRmPmEheating2Type OBJECT-TYPE
- SYNTAX INTEGER {
- direct (1),
- pwm (2) }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Electric heater #2 type (4908)"
- ::= { airIRmPmEheating2 9 }
- airIRmPmEheating2StartTemperature OBJECT IDENTIFIER ::= { airIRmPmEheating2 10 }
- airIRmPmEheating2StartTemperatureK OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Electric heater #2 start temperature in tenths of Kelvins (4909)"
- ::= { airIRmPmEheating2StartTemperature 1 }
- airIRmPmEheating2StartTemperatureF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Electric heater #2 start temperature in tenths of degrees Fahrenheit (4909)"
- ::= { airIRmPmEheating2StartTemperature 2 }
- airIRmPmEheating2Hysteresis OBJECT IDENTIFIER ::= { airIRmPmEheating2 11 }
- airIRmPmEheating2HysteresisK OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Electric heater #2 hysteresis in tenths of Kelvins (4910)"
- ::= { airIRmPmEheating2Hysteresis 1 }
- airIRmPmEheating2HysteresisF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Electric heater #2 hysteresis in tenths of degrees Fahrenheit (4910)"
- ::= { airIRmPmEheating2Hysteresis 2 }
- airIRmPmEheating2Runtime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Electric heater #2 runtime in hours (4916)"
- ::= { airIRmPmEheating2 17 }
- -- airIRmPmEheating3
- airIRmPmEheating3ManOpEnable OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Electric heater #3 manual operation enable (5001)"
- ::= { airIRmPmEheating3 2 }
- airIRmPmEheating3Running OBJECT-TYPE
- SYNTAX AirIRmControlState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Electric heater #3 running state (5003)"
- ::= { airIRmPmEheating3 4 }
- airIRmPmEheating3ManOpRunning OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Electric heater #3 running in manual operation mode (5004)"
- ::= { airIRmPmEheating3 5 }
- airIRmPmEheating3Type OBJECT-TYPE
- SYNTAX INTEGER {
- direct (1),
- pwm (2) }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Electric heater #3 type (5008)"
- ::= { airIRmPmEheating3 9 }
- airIRmPmEheating3StartTemperature OBJECT IDENTIFIER ::= { airIRmPmEheating3 10 }
- airIRmPmEheating3StartTemperatureK OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Electric heater #3 start temperature in tenths of Kelvins (5009)"
- ::= { airIRmPmEheating3StartTemperature 1 }
- airIRmPmEheating3StartTemperatureF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Electric heater #3 start temperature in tenths of degrees Fahrenheit (5009)"
- ::= { airIRmPmEheating3StartTemperature 2 }
- airIRmPmEheating3Hysteresis OBJECT IDENTIFIER ::= { airIRmPmEheating3 11 }
- airIRmPmEheating3HysteresisK OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Electric heater #3 hysteresis in tenths of Kelvins (5010)"
- ::= { airIRmPmEheating3Hysteresis 1 }
- airIRmPmEheating3HysteresisF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Electric heater #3 hysteresis in tenths of degrees Fahrenheit (5010)"
- ::= { airIRmPmEheating3Hysteresis 2 }
- airIRmPmEheating3Runtime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Electric heater #3 runtime in hours (5016)"
- ::= { airIRmPmEheating3 17 }
- -- airIRmPmEheating4
- airIRmPmEheating4ManOpEnable OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Electric heater #4 manual operation enable (5101)"
- ::= { airIRmPmEheating4 2 }
- airIRmPmEheating4Running OBJECT-TYPE
- SYNTAX AirIRmControlState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Electric heater #4 running state (5103)"
- ::= { airIRmPmEheating4 4 }
- airIRmPmEheating4ManOpRunning OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Electric heater #4 running in manual operation mode (5104)"
- ::= { airIRmPmEheating4 5 }
- airIRmPmEheating4Type OBJECT-TYPE
- SYNTAX INTEGER {
- direct (1),
- pwm (2) }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Electric heater #4 type (5108)"
- ::= { airIRmPmEheating4 9 }
- airIRmPmEheating4StartTemperature OBJECT IDENTIFIER ::= { airIRmPmEheating4 10 }
- airIRmPmEheating4StartTemperatureK OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Electric heater #4 start temperature in tenths of Kelvins (5109)"
- ::= { airIRmPmEheating4StartTemperature 1 }
- airIRmPmEheating4StartTemperatureF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Electric heater #4 start temperature in tenths of degrees Fahrenheit (5109)"
- ::= { airIRmPmEheating4StartTemperature 2 }
- airIRmPmEheating4Hysteresis OBJECT IDENTIFIER ::= { airIRmPmEheating4 11 }
- airIRmPmEheating4HysteresisK OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Electric heater #4 hysteresis in tenths of Kelvins (5110)"
- ::= { airIRmPmEheating4Hysteresis 1 }
- airIRmPmEheating4HysteresisF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Electric heater #4 hysteresis in tenths of degrees Fahrenheit (5110)"
- ::= { airIRmPmEheating4Hysteresis 2 }
- airIRmPmEheating4Runtime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Electric heater #4 runtime in hours (5116)"
- ::= { airIRmPmEheating4 17 }
- -- airIRmPmGECWvalve
- airIRmPmGECWvalveManOpEnable OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "GE/CW valve manual operation enable (5201)"
- ::= { airIRmPmGECWvalve 2 }
- airIRmPmGECWvalveStartTemperature OBJECT IDENTIFIER ::= { airIRmPmGECWvalve 9 }
- airIRmPmGECWvalveStartTemperatureK OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "GE/CW valve start temperature in tenths of Kelvins (5208)"
- ::= { airIRmPmGECWvalveStartTemperature 1 }
- airIRmPmGECWvalveStartTemperatureF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "GE/CW valve start temperature in tenths of degrees Fahrenheit (5208)"
- ::= { airIRmPmGECWvalveStartTemperature 2 }
- airIRmPmGECWvalveLinearRange OBJECT IDENTIFIER ::= { airIRmPmGECWvalve 10 }
- airIRmPmGECWvalveLinearRangeK OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "GE/CW valve linear range in tenths of Kelvins (5209)"
- ::= { airIRmPmGECWvalveLinearRange 1 }
- airIRmPmGECWvalveLinearRangeF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "GE/CW valve linear range in tenths of degrees Fahrenheit (5209)"
- ::= { airIRmPmGECWvalveLinearRange 2 }
- airIRmPmGECWvalveGEOffTemp OBJECT IDENTIFIER ::= { airIRmPmGECWvalve 12 }
- airIRmPmGECWvalveGEOffTempC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "GE/CW valve GE off temperature in tenths of degrees Celsius (5211)"
- ::= { airIRmPmGECWvalveGEOffTemp 1 }
- airIRmPmGECWvalveGEOffTempF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "GE/CW valve GE off temperature in tenths of degrees Fahrenheit (5211)"
- ::= { airIRmPmGECWvalveGEOffTemp 2 }
- airIRmPmGECWvalveOpeningGrade OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "GE/CW valve opening grade in percent (5214)"
- ::= { airIRmPmGECWvalve 15 }
- airIRmPmGECWvalveManOpOpeningGrade OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "GE/CW valve manual operation opening grade in percent (5215)"
- ::= { airIRmPmGECWvalve 16 }
- -- airIRmPmGvalve
- airIRmPmGvalveManOperationEnable OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "G-valve manual operation enable (5301)"
- ::= { airIRmPmGvalve 2 }
- airIRmPmGvalvePreOpeningTime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "G-valve pre-opening time in seconds (5310)"
- ::= { airIRmPmGvalve 11 }
- airIRmPmGvalvePreOpeningGrade OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "G-valve pre-opening grade in percent (5311)"
- ::= { airIRmPmGvalve 12 }
- airIRmPmGvalveOpeningGrade OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "G-valve opening grade in percent (5312)"
- ::= { airIRmPmGvalve 13 }
- airIRmPmGvalveManOpOpeningGrade OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "G-valve manual operation opening grade in percent (5313)"
- ::= { airIRmPmGvalve 14 }
- -- airIRmPmDrycooler1
- airIRmPmDrycooler1ManOpEnable OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Drycooler 1 manual operation enable setting (5401)"
- ::= { airIRmPmDrycooler1 2 }
- airIRmPmDrycooler1Running OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Drycooler 1 running (5402)"
- ::= { airIRmPmDrycooler1 3 }
- airIRmPmDrycooler1ManOpRunning OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Drycooler 1 manual operation running (5404)"
- ::= { airIRmPmDrycooler1 5 }
- airIRmPmDrycooler1WinterStartTemp OBJECT IDENTIFIER ::= { airIRmPmDrycooler1 9 }
- airIRmPmDrycooler1WinterStartTempC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Drycooler 1 winter mode start temperature
- in tenths of degrees Celsius (5408)"
- ::= { airIRmPmDrycooler1WinterStartTemp 1 }
- airIRmPmDrycooler1WinterStartTempF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Drycooler 1 winter mode start temperature
- in tenths of degrees Fahrenheit (5408)"
- ::= { airIRmPmDrycooler1WinterStartTemp 2 }
- airIRmPmDrycooler1SummerStartTemp OBJECT IDENTIFIER ::= { airIRmPmDrycooler1 10 }
- airIRmPmDrycooler1SummerStartTempC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Drycooler 1 summer mode start temperature
- in tenths of degrees Celsius (5409)"
- ::= { airIRmPmDrycooler1SummerStartTemp 1 }
- airIRmPmDrycooler1SummerStartTempF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Drycooler 1 summer mode start temperature
- in tenths of degrees Fahrenheit (5409)"
- ::= { airIRmPmDrycooler1SummerStartTemp 2 }
- airIRmPmDrycooler1Hysteresis OBJECT IDENTIFIER ::= { airIRmPmDrycooler1 11 }
- airIRmPmDrycooler1HysteresisK OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Drycooler 1 hysteresis in tenths of Kelvins (5410)"
- ::= { airIRmPmDrycooler1Hysteresis 1 }
- airIRmPmDrycooler1HysteresisF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Drycooler 1 hysteresis in tenths of degrees Fahrenheit (5410)"
- ::= { airIRmPmDrycooler1Hysteresis 2 }
- airIRmPmDrycooler1Runtime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Drycooler 1 runtime in hours (5415)"
- ::= { airIRmPmDrycooler1 16 }
- -- airIRmPmDrycooler2
- airIRmPmDrycooler2ManOpEnable OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Drycooler 2 manual operation enable setting (5501)"
- ::= { airIRmPmDrycooler2 2 }
- airIRmPmDrycooler2Running OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Drycooler 2 running (5502)"
- ::= { airIRmPmDrycooler2 3 }
- airIRmPmDrycooler2ManOpRunning OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Drycooler 2 manual operation running (5504)"
- ::= { airIRmPmDrycooler2 5 }
- airIRmPmDrycooler2WinterStartTemp OBJECT IDENTIFIER ::= { airIRmPmDrycooler2 9 }
- airIRmPmDrycooler2WinterStartTempC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Drycooler 2 winter mode start temperature
- in tenths of degrees Celsius (5508)"
- ::= { airIRmPmDrycooler2WinterStartTemp 1 }
- airIRmPmDrycooler2WinterStartTempF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Drycooler 2 winter mode start temperature
- in tenths of degrees Fahrenheit (5508)"
- ::= { airIRmPmDrycooler2WinterStartTemp 2 }
- airIRmPmDrycooler2SummerStartTemp OBJECT IDENTIFIER ::= { airIRmPmDrycooler2 10 }
- airIRmPmDrycooler2SummerStartTempC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Drycooler 2 summer mode start temperature
- in tenths of degrees Celsius (5509)"
- ::= { airIRmPmDrycooler2SummerStartTemp 1 }
- airIRmPmDrycooler2SummerStartTempF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Drycooler 2 summer mode start temperature
- in tenths of degrees Fahrenheit (5509)"
- ::= { airIRmPmDrycooler2SummerStartTemp 2 }
- airIRmPmDrycooler2Hysteresis OBJECT IDENTIFIER ::= { airIRmPmDrycooler2 11 }
- airIRmPmDrycooler2HysteresisK OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Drycooler 2 hysteresis in tenths of Kelvins (5510)"
- ::= { airIRmPmDrycooler2Hysteresis 1 }
- airIRmPmDrycooler2HysteresisF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Drycooler 2 hysteresis in tenths of degrees Fahrenheit (5510)"
- ::= { airIRmPmDrycooler2Hysteresis 2 }
- airIRmPmDrycooler2Runtime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Drycooler 2 runtime in hours (5515)"
- ::= { airIRmPmDrycooler2 16 }
- -- airIRmPmDrycooler3
- airIRmPmDrycooler3ManOpEnable OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Drycooler 3 manual operation enable setting (5601)"
- ::= { airIRmPmDrycooler3 2 }
- airIRmPmDrycooler3Running OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Drycooler 3 running (5602)"
- ::= { airIRmPmDrycooler3 3 }
- airIRmPmDrycooler3ManOpRunning OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Drycooler 3 manual operation running (5604)"
- ::= { airIRmPmDrycooler3 5 }
- airIRmPmDrycooler3WinterStartTemp OBJECT IDENTIFIER ::= { airIRmPmDrycooler3 9 }
- airIRmPmDrycooler3WinterStartTempC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Drycooler 3 winter mode start temperature
- in tenths of degrees Celsius (5608)"
- ::= { airIRmPmDrycooler3WinterStartTemp 1 }
- airIRmPmDrycooler3WinterStartTempF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Drycooler 3 winter mode start temperature
- in tenths of degrees Fahrenheit (5608)"
- ::= { airIRmPmDrycooler3WinterStartTemp 2 }
- airIRmPmDrycooler3SummerStartTemp OBJECT IDENTIFIER ::= { airIRmPmDrycooler3 10 }
- airIRmPmDrycooler3SummerStartTempC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Drycooler 3 summer mode start temperature
- in tenths of degrees Celsius (5609)"
- ::= { airIRmPmDrycooler3SummerStartTemp 1 }
- airIRmPmDrycooler3SummerStartTempF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Drycooler 3 summer mode start temperature
- in tenths of degrees Fahrenheit (5609)"
- ::= { airIRmPmDrycooler3SummerStartTemp 2 }
- airIRmPmDrycooler3Hysteresis OBJECT IDENTIFIER ::= { airIRmPmDrycooler3 11 }
- airIRmPmDrycooler3HysteresisK OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Drycooler 3 hysteresis in tenths of Kelvins (5610)"
- ::= { airIRmPmDrycooler3Hysteresis 1 }
- airIRmPmDrycooler3HysteresisF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Drycooler 3 hysteresis in tenths of degrees Fahrenheit (5610)"
- ::= { airIRmPmDrycooler3Hysteresis 2 }
- airIRmPmDrycooler3Runtime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Drycooler 3 runtime in hours (5615)"
- ::= { airIRmPmDrycooler3 16 }
- -- airIRmPmDrycooler4
- airIRmPmDrycooler4ManOpEnable OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Drycooler 4 manual operation enable setting (5701)"
- ::= { airIRmPmDrycooler4 2 }
- airIRmPmDrycooler4Running OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Drycooler 4 running (5702)"
- ::= { airIRmPmDrycooler4 3 }
- airIRmPmDrycooler4ManOpRunning OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Drycooler 4 manual operation running (5704)"
- ::= { airIRmPmDrycooler4 5 }
- airIRmPmDrycooler4WinterStartTemp OBJECT IDENTIFIER ::= { airIRmPmDrycooler4 9 }
- airIRmPmDrycooler4WinterStartTempC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Drycooler 4 winter mode start temperature
- in tenths of degrees Celsius (5708)"
- ::= { airIRmPmDrycooler4WinterStartTemp 1 }
- airIRmPmDrycooler4WinterStartTempF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Drycooler 4 winter mode start temperature
- in tenths of degrees Fahrenheit (5708)"
- ::= { airIRmPmDrycooler4WinterStartTemp 2 }
- airIRmPmDrycooler4SummerStartTemp OBJECT IDENTIFIER ::= { airIRmPmDrycooler4 10 }
- airIRmPmDrycooler4SummerStartTempC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Drycooler 4 summer mode start temperature
- in tenths of degrees Celsius (5709)"
- ::= { airIRmPmDrycooler4SummerStartTemp 1 }
- airIRmPmDrycooler4SummerStartTempF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Drycooler 4 summer mode start temperature
- in tenths of degrees Fahrenheit (5709)"
- ::= { airIRmPmDrycooler4SummerStartTemp 2 }
- airIRmPmDrycooler4Hysteresis OBJECT IDENTIFIER ::= { airIRmPmDrycooler4 11 }
- airIRmPmDrycooler4HysteresisK OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Drycooler 4 hysteresis in tenths of Kelvins (5710)"
- ::= { airIRmPmDrycooler4Hysteresis 1 }
- airIRmPmDrycooler4HysteresisF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Drycooler 4 hysteresis in tenths of degrees Fahrenheit (5710)"
- ::= { airIRmPmDrycooler4Hysteresis 2 }
- airIRmPmDrycooler4Runtime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Drycooler 4 runtime in hours (5715)"
- ::= { airIRmPmDrycooler4 16 }
- -- airIRmPmPump1
- airIRmPmPump1ManOpEnable OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Pump 1 manual operation enable state (5801)"
- ::= { airIRmPmPump1 2 }
- airIRmPmPump1Running OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Pump 1 running (5802)"
- ::= { airIRmPmPump1 3 }
- airIRmPmPump1ManOpRunning OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Pump 1 manual operation running (5805)"
- ::= { airIRmPmPump1 6 }
- airIRmPmPump1StartTemperature OBJECT IDENTIFIER ::= { airIRmPmPump1 10 }
- airIRmPmPump1StartTemperatureK OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Pump 1 starting temperature in tenths of Kelvins (5809)"
- ::= { airIRmPmPump1StartTemperature 1 }
- airIRmPmPump1StartTemperatureF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Pump 1 starting temperature in tenths of degrees Fahrenheit (5809)"
- ::= { airIRmPmPump1StartTemperature 2 }
- airIRmPmPump1Hysteresis OBJECT IDENTIFIER ::= { airIRmPmPump1 11 }
- airIRmPmPump1HysteresisK OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Pump 1 hysteresis in tenths of Kelvins (5810)"
- ::= { airIRmPmPump1Hysteresis 1 }
- airIRmPmPump1HysteresisF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Pump 1 hysteresis in tenths of degrees Fahrenheit (5810)"
- ::= { airIRmPmPump1Hysteresis 2 }
- airIRmPmPump1LinearRange OBJECT IDENTIFIER ::= { airIRmPmPump1 12 }
- airIRmPmPump1LinearRangeK OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Pump 1 linear range in tenths of Kelvins (5811)"
- ::= { airIRmPmPump1LinearRange 1 }
- airIRmPmPump1LinearRangeF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Pump 1 linear range in tenths of degrees Fahrenheit (5811)"
- ::= { airIRmPmPump1LinearRange 2 }
- airIRmPmPump1PressureSetpoint OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Pump 1 pressure setpoint in tenths of Bars (5812)"
- ::= { airIRmPmPump1 13 }
- airIRmPmPump1Runtime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Pump 1 runtime in hours (5820)"
- ::= { airIRmPmPump1 21 }
- airIRmPmPump1Speed OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Pump 1 speed in percent (5821)"
- ::= { airIRmPmPump1 22 }
- airIRmPmPump1ControlCycle OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Pump 1 control cycle length in seconds (5827)"
- ::= { airIRmPmPump1 28 }
- airIRmPmPump1MaxAdjust OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Pump 1 maximum adjustment in percent (5828)"
- ::= { airIRmPmPump1 29 }
- airIRmPmPump1ControlFactor OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Pump 1 control factor setting (5829)"
- ::= { airIRmPmPump1 30 }
- -- airIRmPmPump2
- airIRmPmPump2ManOpEnable OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Pump 2 manual operation enable state (5901)"
- ::= { airIRmPmPump2 2 }
- airIRmPmPump2Running OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Pump 2 running (5902)"
- ::= { airIRmPmPump2 3 }
- airIRmPmPump2ManOpRunning OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Pump 2 manual operation running (5905)"
- ::= { airIRmPmPump2 6 }
- airIRmPmPump2StartTemperature OBJECT IDENTIFIER ::= { airIRmPmPump2 10 }
- airIRmPmPump2StartTemperatureK OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Pump 2 starting temperature in tenths of Kelvins (5909)"
- ::= { airIRmPmPump2StartTemperature 1 }
- airIRmPmPump2StartTemperatureF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Pump 2 starting temperature in tenths of degrees Fahrenheit (5909)"
- ::= { airIRmPmPump2StartTemperature 2 }
- airIRmPmPump2Hysteresis OBJECT IDENTIFIER ::= { airIRmPmPump2 11 }
- airIRmPmPump2HysteresisK OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Pump 2 hysteresis in tenths of Kelvins (5910)"
- ::= { airIRmPmPump2Hysteresis 1 }
- airIRmPmPump2HysteresisF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Pump 2 hysteresis in tenths of degrees Fahrenheit (5910)"
- ::= { airIRmPmPump2Hysteresis 2 }
- airIRmPmPump2LinearRange OBJECT IDENTIFIER ::= { airIRmPmPump2 12 }
- airIRmPmPump2LinearRangeK OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Pump 2 linear range in tenths of Kelvins (5911)"
- ::= { airIRmPmPump2LinearRange 1 }
- airIRmPmPump2LinearRangeF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Pump 2 linear range in tenths of degrees Fahrenheit (5911)"
- ::= { airIRmPmPump2LinearRange 2 }
- airIRmPmPump2PressureSetpoint OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Pump 2 pressure setpoint in tenths of Bars (5912)"
- ::= { airIRmPmPump2 13 }
- airIRmPmPump2Runtime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Pump 2 runtime in hours (5920)"
- ::= { airIRmPmPump2 21 }
- airIRmPmPump2Speed OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Pump 2 speed in percent (5921)"
- ::= { airIRmPmPump2 22 }
- airIRmPmPump2ControlCycle OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Pump 2 control cycle length in seconds (5927)"
- ::= { airIRmPmPump2 28 }
- airIRmPmPump2MaxAdjust OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Pump 2 maximum adjustment in percent (5928)"
- ::= { airIRmPmPump2 29 }
- airIRmPmPump2ControlFactor OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Pump 2 control factor setting (5929)"
- ::= { airIRmPmPump2 30 }
- -- airIRmPmPump3
- airIRmPmPump3ManOpEnable OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Pump 3 manual operation enable state (6001)"
- ::= { airIRmPmPump3 2 }
- airIRmPmPump3Running OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Pump 3 running (6002)"
- ::= { airIRmPmPump3 3 }
- airIRmPmPump3ManOpRunning OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Pump 3 manual operation running (6005)"
- ::= { airIRmPmPump3 6 }
- airIRmPmPump3StartTemperature OBJECT IDENTIFIER ::= { airIRmPmPump3 10 }
- airIRmPmPump3StartTemperatureK OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Pump 3 starting temperature in tenths of Kelvins (6009)"
- ::= { airIRmPmPump3StartTemperature 1 }
- airIRmPmPump3StartTemperatureF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Pump 3 starting temperature in tenths of degrees Fahrenheit (6009)"
- ::= { airIRmPmPump3StartTemperature 2 }
- airIRmPmPump3Hysteresis OBJECT IDENTIFIER ::= { airIRmPmPump3 11 }
- airIRmPmPump3HysteresisK OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Pump 3 hysteresis in tenths of Kelvins (6010)"
- ::= { airIRmPmPump3Hysteresis 1 }
- airIRmPmPump3HysteresisF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Pump 3 hysteresis in tenths of degrees Fahrenheit (6010)"
- ::= { airIRmPmPump3Hysteresis 2 }
- airIRmPmPump3LinearRange OBJECT IDENTIFIER ::= { airIRmPmPump3 12 }
- airIRmPmPump3LinearRangeK OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Pump 3 linear range in tenths of Kelvins (6011)"
- ::= { airIRmPmPump3LinearRange 1 }
- airIRmPmPump3LinearRangeF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Pump 3 linear range in tenths of degrees Fahrenheit (6011)"
- ::= { airIRmPmPump3LinearRange 2 }
- airIRmPmPump3PressureSetpoint OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Pump 3 pressure setpoint in tenths of Bars (6012)"
- ::= { airIRmPmPump3 13 }
- airIRmPmPump3Runtime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Pump 3 runtime in hours (6020)"
- ::= { airIRmPmPump3 21 }
- airIRmPmPump3Speed OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Pump 3 speed in percent (6021)"
- ::= { airIRmPmPump3 22 }
- airIRmPmPump3ControlCycle OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Pump 3 control cycle length in seconds (6027)"
- ::= { airIRmPmPump3 28 }
- airIRmPmPump3MaxAdjust OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Pump 3 maximum adjustment in percent (6028)"
- ::= { airIRmPmPump3 29 }
- airIRmPmPump3ControlFactor OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Pump 3 control factor setting (6029)"
- ::= { airIRmPmPump3 30 }
- -- airIRmPmPump4
- airIRmPmPump4ManOpEnable OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Pump 4 manual operation enable state (6101)"
- ::= { airIRmPmPump4 2 }
- airIRmPmPump4Running OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Pump 4 running (6102)"
- ::= { airIRmPmPump4 3 }
- airIRmPmPump4ManOpRunning OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Pump 4 manual operation running (6105)"
- ::= { airIRmPmPump4 6 }
- airIRmPmPump4StartTemperature OBJECT IDENTIFIER ::= { airIRmPmPump4 10 }
- airIRmPmPump4StartTemperatureK OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Pump 4 starting temperature in tenths of Kelvins (6109)"
- ::= { airIRmPmPump4StartTemperature 1 }
- airIRmPmPump4StartTemperatureF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Pump 4 starting temperature in tenths of degrees Fahrenheit (6109)"
- ::= { airIRmPmPump4StartTemperature 2 }
- airIRmPmPump4Hysteresis OBJECT IDENTIFIER ::= { airIRmPmPump4 11 }
- airIRmPmPump4HysteresisK OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Pump 4 hysteresis in tenths of Kelvins (6110)"
- ::= { airIRmPmPump4Hysteresis 1 }
- airIRmPmPump4HysteresisF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Pump 4 hysteresis in tenths of degrees Fahrenheit (6110)"
- ::= { airIRmPmPump4Hysteresis 2 }
- airIRmPmPump4LinearRange OBJECT IDENTIFIER ::= { airIRmPmPump4 12 }
- airIRmPmPump4LinearRangeK OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Pump 4 linear range in tenths of Kelvins (6111)"
- ::= { airIRmPmPump4LinearRange 1 }
- airIRmPmPump4LinearRangeF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Pump 4 linear range in tenths of degrees Fahrenheit (6111)"
- ::= { airIRmPmPump4LinearRange 2 }
- airIRmPmPump4PressureSetpoint OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Pump 4 pressure setpoint in tenths of Bars (6112)"
- ::= { airIRmPmPump4 13 }
- airIRmPmPump4Runtime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Pump 4 runtime in hours (6120)"
- ::= { airIRmPmPump4 21 }
- airIRmPmPump4Speed OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Pump 4 speed in percent (6121)"
- ::= { airIRmPmPump4 22 }
- airIRmPmPump4ControlCycle OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Pump 4 control cycle length in seconds (6127)"
- ::= { airIRmPmPump4 28 }
- airIRmPmPump4MaxAdjust OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Pump 4 maximum adjustment in percent (6128)"
- ::= { airIRmPmPump4 29 }
- airIRmPmPump4ControlFactor OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Pump 4 control factor setting (6129)"
- ::= { airIRmPmPump4 30 }
- -- airIRmPmHotgasHeating
- airIRmPmHotgasHeatRunning OBJECT-TYPE
- SYNTAX AirIRmControlState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Hotgas heat running state. (6202)"
- ::= { airIRmPmHotgasHeating 3 }
- -- airIRmPmPWWHeating
- airIRmPmPWWHeatingManOpEnable OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "PWW-heating manual operation enable (6301)"
- ::= { airIRmPmPWWHeating 2 }
- airIRmPmPWWHeatingRunning OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "PWW-heating running (6302)"
- ::= { airIRmPmPWWHeating 3 }
- airIRmPmPWWHeatingManOpRunning OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "PWW-heating manual operation running (6303)"
- ::= { airIRmPmPWWHeating 4 }
- airIRmPmPWWHeatingType OBJECT-TYPE
- SYNTAX INTEGER {
- direct (1),
- undefined (2) }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "PWW-heating type (6308)"
- ::= { airIRmPmPWWHeating 9 }
- airIRmPmPWWHeatingStartTemp OBJECT IDENTIFIER ::= { airIRmPmPWWHeating 10 }
- airIRmPmPWWHeatingStartTempK OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "PWW-heating starting temperature in Kelvins (6309)"
- ::= { airIRmPmPWWHeatingStartTemp 1 }
- airIRmPmPWWHeatingStartTempF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "PWW-heating starting temperature in degrees Fahrenheit (6309)"
- ::= { airIRmPmPWWHeatingStartTemp 2 }
- airIRmPmPWWHeatingHysteresis OBJECT IDENTIFIER ::= { airIRmPmPWWHeating 12 }
- airIRmPmPWWHeatingHysteresisK OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "PWW-heating hysteresis in Kelvins (6311)"
- ::= { airIRmPmPWWHeatingHysteresis 1 }
- airIRmPmPWWHeatingHysteresisF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "PWW-heating hysteresis in degrees Fahrenheit (6311)"
- ::= { airIRmPmPWWHeatingHysteresis 2 }
- airIRmPmPWWHeatingLinearRange OBJECT IDENTIFIER ::= { airIRmPmPWWHeating 13 }
- airIRmPmPWWHeatingLinearRangeK OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "PWW-heating linear range in Kelvins (6312)"
- ::= { airIRmPmPWWHeatingLinearRange 1 }
- airIRmPmPWWHeatingLinearRangeF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "PWW-heating linear range in degrees Fahrenheit (6312)"
- ::= { airIRmPmPWWHeatingLinearRange 2 }
- airIRmPmPWWHeatingCurrentValue OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "PWW-heating current value in percent (6315)"
- ::= { airIRmPmPWWHeating 16 }
- airIRmPmPWWHeatingManOpValue OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "PWW-heating manual operation value in percent (6316)"
- ::= { airIRmPmPWWHeating 17 }
- -- airIRmPmHumidifier1
- airIRmPmHumidifier1ManOpEnable OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Humidifier #1 manual operation enable (6401)"
- ::= { airIRmPmHumidifier1 2 }
- airIRmPmHumidifier1Running OBJECT-TYPE
- SYNTAX AirIRmControlState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Humidifier #1 running state (6402)"
- ::= { airIRmPmHumidifier1 3 }
- airIRmPmHumidifier1ManOpRunning OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Humidifier #1 manual operation running state (6404)"
- ::= { airIRmPmHumidifier1 5 }
- airIRmPmHumidifier1Type OBJECT-TYPE
- SYNTAX INTEGER {
- direct (1),
- proportional (2) }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Humidifier #1 type (6416)"
- ::= { airIRmPmHumidifier1 17 }
- airIRmPmHumidifier1StartHumidity OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Humidifier #1 start humidity in tenths
- of percent relative humidity (6417)"
- ::= { airIRmPmHumidifier1 18 }
- airIRmPmHumidifier1Hysteresis OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Humidifier #1 hysteresis in tenths
- of percent relative humidity (6419)"
- ::= { airIRmPmHumidifier1 20 }
- airIRmPmHumidifier1LinearRange OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Humidifier #1 linear range in tenths
- of percent relative humidity per Kelvin (6420)"
- ::= { airIRmPmHumidifier1 21 }
- airIRmPmHumidifier1Runtime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Humidifier #1 runtime in hours (6426)"
- ::= { airIRmPmHumidifier1 27 }
- airIRmPmHumidifier1CurrentValue OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Humidifier #1 current value in percent (6427)"
- ::= { airIRmPmHumidifier1 28 }
- airIRmPmHumidifier1ManOpValue OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Humidifier #1 manual operation value in percent (6428)"
- ::= { airIRmPmHumidifier1 29 }
- -- airIRmPmHumidifier2
- airIRmPmHumidifier2ManOpEnable OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Humidifier #2 manual operation enable (6501)"
- ::= { airIRmPmHumidifier2 2 }
-
- airIRmPmHumidifier2Running OBJECT-TYPE
- SYNTAX AirIRmControlState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Humidifier #2 running state (6502)"
- ::= { airIRmPmHumidifier2 3 }
- airIRmPmHumidifier2ManOpRunning OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Humidifier #2 manual operation running state (6504)"
- ::= { airIRmPmHumidifier2 5 }
- airIRmPmHumidifier2Type OBJECT-TYPE
- SYNTAX INTEGER {
- direct (1),
- proportional (2) }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Humidifier #2 type (6516)"
- ::= { airIRmPmHumidifier2 17 }
- airIRmPmHumidifier2StartHumidity OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Humidifier #2 start humidity in tenths
- of percent relative humidity (6517)"
- ::= { airIRmPmHumidifier2 18 }
- airIRmPmHumidifier2Hysteresis OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Humidifier #2 hysteresis in tenths
- of percent relative humidity (6519)"
- ::= { airIRmPmHumidifier2 20 }
- airIRmPmHumidifier2LinearRange OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Humidifier #2 linear range in tenths
- of percent relative humidity per Kelvin (6520)"
- ::= { airIRmPmHumidifier2 21 }
- airIRmPmHumidifier2Runtime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Humidifier #2 runtime in hours (6526)"
- ::= { airIRmPmHumidifier2 27 }
- airIRmPmHumidifier2CurrentValue OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Humidifier #2 current value in percent (6527)"
- ::= { airIRmPmHumidifier2 28 }
- airIRmPmHumidifier2ManOpValue OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Humidifier #2 manual operation value in percent (6528)"
- ::= { airIRmPmHumidifier2 29 }
- -- airIRmPmDehumidification
- airIRmPmDehumidificManOpEnable OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Dehumidifier manual operation enable setting (6801)"
- ::= { airIRmPmDehumidification 2 }
- airIRmPmDehumidificRunning OBJECT-TYPE
- SYNTAX AirIRmControlState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Dehumidifier running state (6802)"
- ::= { airIRmPmDehumidification 3 }
- airIRmPmDehumidificManOpRunning OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Dehumidifier manual operation running (6804)"
- ::= { airIRmPmDehumidification 5 }
- airIRmPmDehumidificStartHumidity OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Dehumidifier start humidity in tenths of percent relative humidity (6809)"
- ::= { airIRmPmDehumidification 10 }
- airIRmPmDehumidificHysteresis OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Dehumidifier hysteresis in tenths of percent relative humidity (6811)"
- ::= { airIRmPmDehumidification 12 }
- airIRmPmDehumidificMinWaterTemp OBJECT IDENTIFIER ::= { airIRmPmDehumidification 18 }
- airIRmPmDehumidificMinWaterTempC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Dehumidifier minimum water temperature in tenths of
- degrees Celsius (6817)"
- ::= { airIRmPmDehumidificMinWaterTemp 1 }
- airIRmPmDehumidificMinWaterTempF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Dehumidifier minimum water temperature in tenths of
- degrees Fahrenheit (6817)"
- ::= { airIRmPmDehumidificMinWaterTemp 2 }
- airIRmPmDehumidificMaxWaterTemp OBJECT IDENTIFIER ::= { airIRmPmDehumidification 19 }
- airIRmPmDehumidificMaxWaterTempC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Dehumidifier maximum water temperature in tenths of
- degrees Celsius (6818)"
- ::= { airIRmPmDehumidificMaxWaterTemp 1 }
- airIRmPmDehumidificMaxWaterTempF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Dehumidifier maximum water temperature in tenths of
- degrees Fahrenheit (6818)"
- ::= { airIRmPmDehumidificMaxWaterTemp 2 }
- airIRmPmDehumidificRuntime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Dehumidifier runtime in hours (6820)"
- ::= { airIRmPmDehumidification 21 }
- -- airIRmPmFan1
- airIRmPmFan1ManOpEnable OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Fan 1 manual operation enable (6901)"
- ::= { airIRmPmFan1 2 }
- airIRmPmFan1Running OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Fan 1 running (6902)"
- ::= { airIRmPmFan1 3 }
- airIRmPmFan1ManOpRunning OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Fan 1 manual operation running (6905)"
- ::= { airIRmPmFan1 6 }
- airIRmPmFan1Type OBJECT-TYPE
- SYNTAX INTEGER {
- direct (1),
- proportional (2) }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Fan 1 type (6908)"
- ::= { airIRmPmFan1 9 }
- airIRmPmFan1Runtime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Fan 1 runtime in hours (6931)"
- ::= { airIRmPmFan1 32 }
- airIRmPmFan1Speed OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Fan 1 speed in percent (6932)"
- ::= { airIRmPmFan1 33 }
- airIRmPmFan1ManOpSpeed OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Fan 1 manual operation speed in percent (6933)"
- ::= { airIRmPmFan1 34 }
- -- airIRmPmFan2
- airIRmPmFan2ManOpEnable OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Fan 1 manual operation enable (7001)"
- ::= { airIRmPmFan2 2 }
- airIRmPmFan2Running OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Fan 1 running (7002)"
- ::= { airIRmPmFan2 3 }
- airIRmPmFan2ManOpRunning OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Fan 1 manual operation running (7005)"
- ::= { airIRmPmFan2 6 }
- airIRmPmFan2Type OBJECT-TYPE
- SYNTAX INTEGER {
- direct (1),
- proportional (2) }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Fan 2 type (7008)"
- ::= { airIRmPmFan2 9 }
- airIRmPmFan2Runtime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Fan 1 runtime in hours (7031)"
- ::= { airIRmPmFan2 32 }
- airIRmPmFan2Speed OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Fan 1 speed in percent (7032)"
- ::= { airIRmPmFan2 33 }
- airIRmPmFan2ManOpSpeed OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Fan 1 manual operation speed in percent (7033)"
- ::= { airIRmPmFan2 34 }
- -- airIRmPmFan3
- airIRmPmFan3ManOpEnable OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Fan 1 manual operation enable (7101)"
- ::= { airIRmPmFan3 2 }
- airIRmPmFan3Running OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Fan 1 running (7102)"
- ::= { airIRmPmFan3 3 }
- airIRmPmFan3ManOpRunning OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Fan 1 manual operation running (7105)"
- ::= { airIRmPmFan3 6 }
- airIRmPmFan3Type OBJECT-TYPE
- SYNTAX INTEGER {
- direct (1),
- proportional (2) }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Fan 3 type (7108)"
- ::= { airIRmPmFan3 9 }
- airIRmPmFan3Runtime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Fan 1 runtime in hours (7131)"
- ::= { airIRmPmFan3 32 }
- airIRmPmFan3Speed OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Fan 1 speed in percent (7132)"
- ::= { airIRmPmFan3 33 }
- airIRmPmFan3ManOpSpeed OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Fan 1 manual operation speed in percent (7133)"
- ::= { airIRmPmFan3 34 }
- -- airIRmPmLouver1
- airIRmPmLouver1ManOpEnable OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Louver 1 manual operation enable (7201)"
- ::= { airIRmPmLouver1 2 }
- airIRmPmLouver1Position OBJECT-TYPE
- SYNTAX INTEGER {
- closed (1),
- open (2) }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Louver 1 position (7202)"
- ::= { airIRmPmLouver1 3 }
- airIRmPmLouver1ManOpPosition OBJECT-TYPE
- SYNTAX INTEGER {
- closed (1),
- open (2) }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Louver 1 manual operation position setting (7203)"
- ::= { airIRmPmLouver1 4 }
- -- airIRmPmLouver2
- airIRmPmLouver2ManOpEnable OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Louver 2 manual operation enable (7301)"
- ::= { airIRmPmLouver2 2 }
- airIRmPmLouver2Position OBJECT-TYPE
- SYNTAX INTEGER {
- closed (1),
- open (2) }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Louver 2 position (7302)"
- ::= { airIRmPmLouver2 3 }
- airIRmPmLouver2ManOpPosition OBJECT-TYPE
- SYNTAX INTEGER {
- closed (1),
- open (2) }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Louver 2 manual operation position setting (7303)"
- ::= { airIRmPmLouver2 4 }
- -- airIRmPmLouver3
- airIRmPmLouver3ManOpEnable OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Louver 3 manual operation enable (7401)"
- ::= { airIRmPmLouver3 2 }
- airIRmPmLouver3Position OBJECT-TYPE
- SYNTAX INTEGER {
- closed (1),
- open (2) }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Louver 3 position (7402)"
- ::= { airIRmPmLouver3 3 }
- airIRmPmLouver3ManOpPosition OBJECT-TYPE
- SYNTAX INTEGER {
- closed (1),
- open (2) }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Louver 3 manual operation position setting (7403)"
- ::= { airIRmPmLouver3 4 }
- -- airIRmPmAuxAlarm1
- -- Empty
- -- airIRmPmAuxAlarm2
- -- Empty
- -- airIRmPmAuxAlarm3
- -- Empty
- -- airIRmPmAuxAlarm4
- -- Empty
- -- airIRmPmAuxAlarm5
- -- Empty
- -- airIRmPmAlarmBits
- airIRmPmFan1Failure OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Fan #1 failure (8500)."
- ::= { airIRmPmAlarmBits 1 }
- airIRmPmFan2Failure OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Fan #2 failure (8501)."
- ::= { airIRmPmAlarmBits 2 }
- airIRmPmFan3Failure OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Fan #3 failure (8502)."
- ::= { airIRmPmAlarmBits 3 }
- airIRmPmCompressor1Failure OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Compressor #1 failure (8503)."
- ::= { airIRmPmAlarmBits 4 }
- airIRmPmCompressor2Failure OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Compressor #2 failure (8504)."
- ::= { airIRmPmAlarmBits 5 }
- airIRmPmWaterDetector OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Water detector alarm (8505)."
- ::= { airIRmPmAlarmBits 6 }
- airIRmPmPhaseFailure OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Phase failure (8506)."
- ::= { airIRmPmAlarmBits 7 }
- airIRmPmFireSmokeDetector OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Fire/smoke detector (8507)."
- ::= { airIRmPmAlarmBits 8 }
- airIRmPmReturnAirTemperatureTooHigh OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Return air temperature too high (8508)."
- ::= { airIRmPmAlarmBits 9 }
- airIRmPmReturnAirHumidityTooHigh OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Return air humidity too high (8509)."
- ::= { airIRmPmAlarmBits 10 }
- airIRmPmSupplyAirTemperatureTooHigh OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Supply air temperature too high (8510)."
- ::= { airIRmPmAlarmBits 11 }
- airIRmPmSupplyAirHumidityTooHigh OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Supply air humidity too high (8511)."
- ::= { airIRmPmAlarmBits 12 }
- airIRmPmWaterTemperatureTooHigh OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Water temperature too high (8512)."
- ::= { airIRmPmAlarmBits 13 }
- airIRmPmReturnAirTemperatureTooLow OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Return air temperature too low (8513)."
- ::= { airIRmPmAlarmBits 14 }
- airIRmPmReturnAirHumidityTooLow OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Return air humidity too low (8514)."
- ::= { airIRmPmAlarmBits 15 }
- airIRmPmSupplyAirTemperatureTooLow OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Supply air temperature too low (8515)."
- ::= { airIRmPmAlarmBits 16 }
- airIRmPmSupplyAirHumidityTooLow OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Supply air humidity too low (8516)."
- ::= { airIRmPmAlarmBits 17 }
- airIRmPmWaterTemperatureTooLow OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Water temperature too low (8517)."
- ::= { airIRmPmAlarmBits 18 }
- airIRmPmSensor1Failure OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Sensor #1 failure (8518)."
- ::= { airIRmPmAlarmBits 19 }
- airIRmPmSensor2Failure OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Sensor #2 failure (8519)."
- ::= { airIRmPmAlarmBits 20 }
- airIRmPmSensor3Failure OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Sensor #3 failure (8520)."
- ::= { airIRmPmAlarmBits 21 }
- airIRmPmSensor4Failure OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Sensor #4 failure (8521)."
- ::= { airIRmPmAlarmBits 22 }
- airIRmPmSensor5Failure OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Sensor #5 failure (8522)."
- ::= { airIRmPmAlarmBits 23 }
- airIRmPmSensor6Failure OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Sensor #6 failure (8523)."
- ::= { airIRmPmAlarmBits 24 }
- airIRmPmSensor7Failure OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Sensor #7 failure (8524)."
- ::= { airIRmPmAlarmBits 25 }
- airIRmPmSensor8Failure OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Sensor #8 failure (8525)."
- ::= { airIRmPmAlarmBits 26 }
- airIRmPmSensor9Failure OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Sensor #9 failure (8526)."
- ::= { airIRmPmAlarmBits 27 }
- airIRmPmSensor10Failure OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Sensor #10 failure (8527)."
- ::= { airIRmPmAlarmBits 28 }
- airIRmPmSensor11Failure OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Sensor #11 failure (8528)."
- ::= { airIRmPmAlarmBits 29 }
- airIRmPmSensor12Failure OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Sensor #12 failure (8529)."
- ::= { airIRmPmAlarmBits 30 }
- airIRmPmSensor13Failure OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Sensor #13 failure (8530)."
- ::= { airIRmPmAlarmBits 31 }
- airIRmPmSensor14Failure OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Sensor #14 failure (8531)."
- ::= { airIRmPmAlarmBits 32 }
- airIRmPmSensor15Failure OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Sensor #15 failure (8532)."
- ::= { airIRmPmAlarmBits 33 }
- airIRmPmSensor16Failure OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Sensor #16 failure (8533)."
- ::= { airIRmPmAlarmBits 34 }
- airIRmPmSensor17Failure OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Sensor #17 failure (8534)."
- ::= { airIRmPmAlarmBits 35 }
- airIRmPmSensor18Failure OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Sensor #18 failure (8535)."
- ::= { airIRmPmAlarmBits 36 }
- airIRmPmSensor19Failure OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Sensor #19 failure (8536)."
- ::= { airIRmPmAlarmBits 37 }
- airIRmPmSensor20Failure OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Sensor #20 failure (8537)."
- ::= { airIRmPmAlarmBits 38 }
- airIRmPmSensor21Failure OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Sensor #21 failure (8538)."
- ::= { airIRmPmAlarmBits 39 }
- airIRmPmSensor1Defect OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Sensor #1 defect (8539)."
- ::= { airIRmPmAlarmBits 40 }
- airIRmPmSensor2Defect OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Sensor #2 defect (8540)."
- ::= { airIRmPmAlarmBits 41 }
- airIRmPmSensor3Defect OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Sensor #3 defect (8541)."
- ::= { airIRmPmAlarmBits 42 }
- airIRmPmSensor4Defect OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Sensor #4 defect (8542)."
- ::= { airIRmPmAlarmBits 43 }
- airIRmPmSensor5Defect OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Sensor #5 defect (8543)."
- ::= { airIRmPmAlarmBits 44 }
- airIRmPmSensor6Defect OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Sensor #6 defect (8544)."
- ::= { airIRmPmAlarmBits 45 }
- airIRmPmSensor7Defect OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Sensor #7 defect (8545)."
- ::= { airIRmPmAlarmBits 46 }
- airIRmPmSensor8Defect OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Sensor #8 defect (8546)."
- ::= { airIRmPmAlarmBits 47 }
- airIRmPmSensor9Defect OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Sensor #9 defect (8547)."
- ::= { airIRmPmAlarmBits 48 }
- airIRmPmSensor10Defect OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Sensor #10 defect (8548)."
- ::= { airIRmPmAlarmBits 49 }
- airIRmPmSensor11Defect OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Sensor #11 defect (8549)."
- ::= { airIRmPmAlarmBits 50 }
- airIRmPmSensor12Defect OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Sensor #12 defect (8550)."
- ::= { airIRmPmAlarmBits 51 }
- airIRmPmSensor13Defect OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Sensor #13 defect (8551)."
- ::= { airIRmPmAlarmBits 52 }
- airIRmPmSensor14Defect OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Sensor #14 defect (8552)."
- ::= { airIRmPmAlarmBits 53 }
- airIRmPmSensor15Defect OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Sensor #15 defect (8553)."
- ::= { airIRmPmAlarmBits 54 }
- airIRmPmSensor16Defect OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Sensor #16 defect (8554)."
- ::= { airIRmPmAlarmBits 55 }
- airIRmPmSensor17Defect OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Sensor #17 defect (8555)."
- ::= { airIRmPmAlarmBits 56 }
- airIRmPmSensor18Defect OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Sensor #18 defect (8556)"
- ::= { airIRmPmAlarmBits 57 }
- airIRmPmSensor19Defect OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Sensor #19 defect (8557)."
- ::= { airIRmPmAlarmBits 58 }
- airIRmPmSensor20Defect OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Sensor #20 defect (8558)."
- ::= { airIRmPmAlarmBits 59 }
- airIRmPmSensor21Defect OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Sensor #21 defect (8559)."
- ::= { airIRmPmAlarmBits 60 }
- airIRmPmCompressor1Alarm OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Compressor #1 alarm (8560)."
- ::= { airIRmPmAlarmBits 61 }
- airIRmPmCompressor2Alarm OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Compressor #2 alarm (8561)."
- ::= { airIRmPmAlarmBits 62 }
- airIRmPmCompressor1LowPressure OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Compressor #1 low pressure (8562)."
- ::= { airIRmPmAlarmBits 63 }
- airIRmPmCompressor2LowPressure OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Compressor #2 low pressure (8563)."
- ::= { airIRmPmAlarmBits 64 }
- airIRmPmReheat1Failure OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Reheat #1 failure (8564)."
- ::= { airIRmPmAlarmBits 65 }
- airIRmPmReheat2Failure OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Reheat #2 failure (8565)."
- ::= { airIRmPmAlarmBits 66 }
- airIRmPmReheat3Failure OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Reheat #3 failure (8566)."
- ::= { airIRmPmAlarmBits 67 }
- airIRmPmReheat4Failure OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Reheat #4 failure (8567)."
- ::= { airIRmPmAlarmBits 68 }
- airIRmPmDrycooler1Failure OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Drycooler #1 failure (8568)."
- ::= { airIRmPmAlarmBits 69 }
- airIRmPmDrycooler2Failure OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Drycooler #2 failure (8569)."
- ::= { airIRmPmAlarmBits 70 }
- airIRmPmDrycooler3Failure OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Drycooler #3 failure (8570)."
- ::= { airIRmPmAlarmBits 71 }
- airIRmPmDrycooler4Failure OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Drycooler #4 failure (8571)."
- ::= { airIRmPmAlarmBits 72 }
- airIRmPmPump1Failure OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Pump #1 failure (8572)."
- ::= { airIRmPmAlarmBits 73 }
- airIRmPmPump2Failure OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Pump #2 failure (8573)."
- ::= { airIRmPmAlarmBits 74 }
- airIRmPmPump3Failure OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Pump #3 failure (8574)."
- ::= { airIRmPmAlarmBits 75 }
- airIRmPmPump4Failure OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Pump #4 failure (8575)."
- ::= { airIRmPmAlarmBits 76 }
- airIRmPmHumidifier1Failure OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Humidifier #1 failure (8576)."
- ::= { airIRmPmAlarmBits 77 }
- airIRmPmHumidifier2Failure OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Humidifier #2 failure (8577)."
- ::= { airIRmPmAlarmBits 78 }
- airIRmPmHumidifier3Failure OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Humidifier #3 failure (8578)."
- ::= { airIRmPmAlarmBits 79 }
- airIRmPmHumidifier1Alarm5us OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Humidifier #1 5us alarm (8579)."
- ::= { airIRmPmAlarmBits 80 }
- airIRmPmHumidifier2Alarm5us OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Humidifier #2 5us alarm (8580)."
- ::= { airIRmPmAlarmBits 81 }
- airIRmPmHumidifier3Alarm5us OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Humidifier #3 5us alarm (8581)."
- ::= { airIRmPmAlarmBits 82 }
- airIRmPmHumidifier1Alarm20us OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Humidifier #1 20us alarm (8582)."
- ::= { airIRmPmAlarmBits 83 }
- airIRmPmHumidifier2Alarm20us OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Humidifier #2 20us alarm (8583)."
- ::= { airIRmPmAlarmBits 84 }
- airIRmPmHumidifier3Alarm20us OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Humidifier #3 20us alarm (8584)."
- ::= { airIRmPmAlarmBits 85 }
- airIRmPmFan1Alarm OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Fan #1 alarm (8585)."
- ::= { airIRmPmAlarmBits 86 }
- airIRmPmFan2Alarm OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Fan #2 alarm (8586)."
- ::= { airIRmPmAlarmBits 87 }
- airIRmPmFan3Alarm OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Fan #3 alarm (8587)."
- ::= { airIRmPmAlarmBits 88 }
- airIRmPmFilter1Clogged OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Filter #1 clogged (8588)."
- ::= { airIRmPmAlarmBits 89 }
- airIRmPmFilter2Clogged OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Filter #2 clogged (8589)."
- ::= { airIRmPmAlarmBits 90 }
- airIRmPmFilter3Clogged OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Filter #3 clogged (8590)."
- ::= { airIRmPmAlarmBits 91 }
- airIRmPmAuxiliaryAlarm1 OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Auxiliary #1 alarm (8591)."
- ::= { airIRmPmAlarmBits 92 }
- airIRmPmAuxiliaryAlarm2 OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Auxiliary #2 alarm (8592)."
- ::= { airIRmPmAlarmBits 93 }
- airIRmPmAuxiliaryAlarm3 OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Auxiliary #3 alarm (8593)."
- ::= { airIRmPmAlarmBits 94 }
- airIRmPmAuxiliaryAlarm4 OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Auxiliary #4 alarm (8594)."
- ::= { airIRmPmAlarmBits 95 }
- airIRmPmAuxiliaryAlarm5 OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Auxiliary #5 alarm (8595)."
- ::= { airIRmPmAlarmBits 96 }
- airIRmPmAuxiliaryAlarm6 OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Auxiliary #6 alarm (8596)."
- ::= { airIRmPmAlarmBits 97 }
- airIRmPmAuxiliaryAlarm7 OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Auxiliary #7 alarm (8597)."
- ::= { airIRmPmAlarmBits 98 }
- airIRmPmAuxiliaryAlarm8 OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Auxiliary #8 alarm (8598)."
- ::= { airIRmPmAlarmBits 99 }
- airIRmPmAuxiliaryAlarm9 OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Auxiliary #9 alarm (8599)."
- ::= { airIRmPmAlarmBits 100 }
- airIRmPmAuxiliaryAlarm10 OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Auxiliary #10 alarm (8600)."
- ::= { airIRmPmAlarmBits 101 }
- airIRmPmHotGasHeatingAlarm OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Hot gas heating alarm (8601)."
- ::= { airIRmPmAlarmBits 102 }
- airIRmPmEEV1PressureSensorError OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "EEV1 pressure sensor error (8602)."
- ::= { airIRmPmAlarmBits 103 }
- airIRmPmEEV1TemperatureSensorError OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "EEV1 temperature sensor error (8603)."
- ::= { airIRmPmAlarmBits 104 }
- airIRmPmEEV1StepperMotorError OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "EEV1 stepper motor error (8604)."
- ::= { airIRmPmAlarmBits 105 }
- airIRmPmEEV2PressureSensorError OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "EEV2 pressure sensor error (8605)."
- ::= { airIRmPmAlarmBits 106 }
- airIRmPmEEV2TemperatureSensorError OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "EEV2 temperature sensor error (8606)."
- ::= { airIRmPmAlarmBits 107 }
- airIRmPmEEV2StepperMotorError OBJECT-TYPE
- SYNTAX AirIRmAlarmState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "EEV2 stepper motor error (8607)."
- ::= { airIRmPmAlarmBits 108 }
- -- airIRmPmMyZone
- airIRmPmMyZoneNumber OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "My zone number (11700)."
- ::= { airIRmPmMyZone 1 }
- airIRmPmMyZoneRoomTemperature OBJECT IDENTIFIER ::= { airIRmPmMyZone 2 }
- airIRmPmMyZoneRoomTemperatureC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "My zone room temperature in tenths of degrees Celsius (11701)."
- ::= { airIRmPmMyZoneRoomTemperature 1 }
- airIRmPmMyZoneRoomTemperatureF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "My zone room temperature in tenths of degrees Fahrenheit (11701)."
- ::= { airIRmPmMyZoneRoomTemperature 2 }
- airIRmPmMyZoneRoomHumidity OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "My zone room humidity in tenths of %RH (11702)."
- ::= { airIRmPmMyZone 3 }
- airIRmPmMyZoneSupplyTemperature OBJECT IDENTIFIER ::= { airIRmPmMyZone 4 }
- airIRmPmMyZoneSupplyTemperatureC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "My zone supply temperature in tenths of degrees Celsius (11703)."
- ::= { airIRmPmMyZoneSupplyTemperature 1 }
- airIRmPmMyZoneSupplyTemperatureF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "My zone supply temperature in tenths
- of degrees Fahrenheit (11703)."
- ::= { airIRmPmMyZoneSupplyTemperature 2 }
- airIRmPmMyZoneSupplyHumidity OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "My zone supply humidity in tenths of %RH (11704)."
- ::= { airIRmPmMyZone 5 }
- airIRmPmMyZoneSequencingTime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "My zone sequencing time in minutes (11705)."
- ::= { airIRmPmMyZone 6 }
- airIRmPmMyZoneNumberOfErrorUnits OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Number of error units in my zone (11706)."
- ::= { airIRmPmMyZone 7 }
- airIRmPmMyZoneEmergencyTemperature OBJECT IDENTIFIER ::= { airIRmPmMyZone 8 }
- airIRmPmMyZoneEmergencyTemperatureC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "My zone emergency temperature in tenths of degrees Celsius (11707)."
- ::= { airIRmPmMyZoneEmergencyTemperature 1 }
- airIRmPmMyZoneEmergencyTemperatureF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "My zone emergency temperature in tenths
- of degrees Fahrenheit (11707)."
- ::= { airIRmPmMyZoneEmergencyTemperature 2 }
- airIRmPmMyZoneCWEnergySaveMode OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "My zone CW energy save mode (11708)."
- ::= { airIRmPmMyZone 9 }
- -- airIRmPmGlobalZoneData
- airIRmPmGlobalZoneDataEmergencyOpMode OBJECT-TYPE
- SYNTAX AirIRmActivityState
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Emergency operation mode (11800)."
- ::= { airIRmPmGlobalZoneData 1 }
- -- End of AC InRoom
- -- RACK AIR REMOVAL UNIT IDENT
- rARUIdentTable OBJECT-TYPE
- SYNTAX SEQUENCE OF RARUIdentEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for query of the individual devices.
- The number of entries is contained in the
- rARUStatusAruDeviceCount OID."
- ::= { rARUIdent 1 }
- rARUIdentEntry OBJECT-TYPE
- SYNTAX RARUIdentEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The device to query."
- INDEX { rARUIdentAruIndex}
- ::= { rARUIdentTable 1 }
- RARUIdentEntry ::=
- SEQUENCE {
- rARUIdentAruIndex INTEGER,
- rARUIdentName DisplayString
- }
- rARUIdentAruIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the ARU entry."
- ::= { rARUIdentEntry 1 }
- rARUIdentName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the device. "
- ::= { rARUIdentEntry 2 }
- -- RACK AIR REMOVAL UNIT CONFIGURATION
- rARUConfigTable OBJECT-TYPE
- SYNTAX SEQUENCE OF RARUConfigEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for configuration of the individual ARU devices accessible from this IP address.
- The number of entries is contained in the rARUStatusAruDeviceCount OID."
- ::= { rARUConfig 1 }
- rARUConfigEntry OBJECT-TYPE
- SYNTAX RARUConfigEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The ARUs to configure."
- INDEX { rARUConfigAruIndex }
- ::= { rARUConfigTable 1 }
- RARUConfigEntry ::=
- SEQUENCE {
- rARUConfigAruIndex INTEGER,
- rARUConfigAruName DisplayString,
- rARUConfigAruRemoteSetpoint INTEGER,
- rARUConfigAruTempOvrdEnableDisable INTEGER,
- rARUConfigAruTempOvrdSetpoint INTEGER,
- rARUConfigAruMasterControl INTEGER
- }
- rARUConfigAruIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the ARU entry."
- ::= { rARUConfigEntry 1 }
-
- rARUConfigAruName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The name of the ARU."
- ::= { rARUConfigEntry 2 }
- rARUConfigAruRemoteSetpoint OBJECT-TYPE
- SYNTAX INTEGER {
- aruOff (1),
- aru85F-29C (2),
- aru90F-32C (3),
- aru95F-35C (4),
- aru100F-38C (5),
- aru7kW-1200cfm (6),
- aru5kW-800cfm (7),
- aru3kW-500cfm (8),
- aru2kW-300cfm (9),
- aru400cfm (10),
- aru600cfm (11),
- aru700cfm (12),
- aru900cfm (13),
- aru1000cfm (14),
- aru1400cfm (15),
- aru1600cfm (16),
- aru1800cfm (17),
- aru2000cfm (18)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "This OID defines the desired base airflow of the ARU, and sets the
- speed of the ARU fans when the temperature override is inactive.
- Values specified in cfm (cubic feet per minute) can be converted
- to metric values using the conversion factor:
-
- 1 cfm = 1.70 m^3/hr (cubic meters per hour).
- Values (1) through (9) are for support of legacy (1st generation) ARUs.
- Writing these values to a 2nd generation ARU will result in the following:
- A value greater than (9) will be ignored by a 1st generation ARU.
- aruOff (1) - Ignored
- aru85F-29C (2) - 1200 cfm
- aru90F-32C (3) - 800 cfm
- aru95F-35C (4) - 500 cfm
- aru100F-38C (5) - 400 cfm
- aru7kW (6) - 1200 cfm
- aru5kW (7) - 800 cfm
- aru3kW (8) - 500 cfm
- aru2kW (9) - 400 cfm
- NOTE: -1 will be returned if the ARU is not communicating."
- ::= { rARUConfigEntry 3 }
- rARUConfigAruTempOvrdEnableDisable OBJECT-TYPE
- SYNTAX INTEGER {
- disabled(1),
- enabled(2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "This OID is used to enable/disable the remote temperature override setting of the ARU.
-
- If this OID is set to 1, the remote setting for temperature override is disabled.
- If this OID is set to 2, the remote setting for temperature override is enabled."
- ::= { rARUConfigEntry 4 }
- rARUConfigAruTempOvrdSetpoint OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "This OID is the Temperature Override setpoint of the ARU.
- NOTE: -1 will be returned if the ARU is not communicating.
- Values are represented in whole number degrees using the
- units specified in the rARUStatusSysTempUnits OID (Celsius or Fahrenheit)."
- ::= { rARUConfigEntry 5 }
-
- rARUConfigAruMasterControl OBJECT-TYPE
- SYNTAX INTEGER {
- aruOn (1),
- aruOff (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "This is the master on/off control for the ARU."
- ::= { rARUConfigEntry 6 }
- -- RACK AIR REMOVAL UNIT STATUS
- rARUStatusAruDeviceCount OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The total number of ARUs accessible from this IP."
- ::= { rARUStatus 1 }
- rARUStatusSysTempUnits OBJECT-TYPE
- SYNTAX INTEGER {
- celsius(1),
- fahrenheit(2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The temperature scale used to display the temperature
- in the system, Celsius(1) or Fahrenheit(2).
- This setting is based on the system preferences
- configuration in the agent."
- ::= { rARUStatus 2 }
- rARUStatusTable OBJECT-TYPE
- SYNTAX SEQUENCE OF RARUStatusEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for query of the individual ARUs accessible from this IP address.
- The number of entries is contained in the rARUStatusAruDeviceCount OID."
- ::= { rARUStatus 3 }
- rARUStatusEntry OBJECT-TYPE
- SYNTAX RARUStatusEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The ARUs to access."
- INDEX { rARUStatusAruIndex }
- ::= { rARUStatusTable 1 }
- RARUStatusEntry ::=
- SEQUENCE {
- rARUStatusAruIndex INTEGER,
- rARUStatusAruName DisplayString,
- rARUStatusAruRemoteSetpoint INTEGER,
- rARUStatusAruManualSetpoint INTEGER,
- rARUStatusAruTemp1 INTEGER,
- rARUStatusAruTemp2 INTEGER,
- rARUStatusAruTemp3 INTEGER,
- rARUStatusAruTempOvrdEnableDisable INTEGER,
- rARUStatusAruTempOvrdSetpoint INTEGER,
- rARUStatusAruAlarmState DisplayString,
- rARUStatusAruCommStatus INTEGER,
- rARUStatusAruTempOvrdStatus INTEGER,
- rARUStatusAruMasterControl INTEGER,
- rARUStatusAruTotalAirflow INTEGER
- }
- rARUStatusAruIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the ARU entry."
- ::= { rARUStatusEntry 1 }
-
- rARUStatusAruName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The name of the ARU."
- ::= { rARUStatusEntry 2 }
- rARUStatusAruRemoteSetpoint OBJECT-TYPE
- SYNTAX INTEGER {
- aruOff (1),
- aru85F-29C (2),
- aru90F-32C (3),
- aru95F-35C (4),
- aru100F-38C (5),
- aru7kW-1200cfm (6),
- aru5kW-800cfm (7),
- aru3kW-500cfm (8),
- aru2kW-300cfm (9),
- aru400cfm (10),
- aru600cfm (11),
- aru700cfm (12),
- aru900cfm (13),
- aru1000cfm (14),
- aru1400cfm (15),
- aru1600cfm (16),
- aru1800cfm (17),
- aru2000cfm (18)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID defines the desired base airflow of the ARU, or the
- speed of the ARU fans when the temperature override is inactive.
- See also the rARUConfigAruRemoteSetpoint OID.
- NOTE: -1 will be returned if the ARU is not communicating."
- ::= { rARUStatusEntry 3 }
- rARUStatusAruManualSetpoint OBJECT-TYPE
- SYNTAX INTEGER {
- aruOff (1),
- aru85F-29C (2),
- aru90F-32C (3),
- aru95F-35C (4),
- aru100F-38C (5),
- aru7kW (6),
- aru5kW (7),
- aru3kW (8),
- aru2kW (9),
- aruRem (10)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Manual operating setpoint of the ARU, which is set on the
- panel of the ARU. If the ARU doesn't have a manual ,
- the OID will always return a value of aruRem (10).
- NOTE: -1 will be returned if the ARU is not communicating.
- Values are represented in whole number degrees or kW.
- If the manual setpoint is set to Remote, or if the ARU doesn't
- have a manual switch, this OID will return aruRem."
- ::= { rARUStatusEntry 4 }
- rARUStatusAruTemp1 OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "ARU temperature probe #1 reading.
- The summary exhaust temperature on 2nd generation ARUs.
- NOTE: -1 will be returned if the ARU is not communicating.
- Values are represented in whole number degrees.
- Units are displayed in the scale shown in
- the rARUStatusSysTempUnits OID (Celsius or Fahrenheit)."
- ::= { rARUStatusEntry 5 }
- rARUStatusAruTemp2 OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "ARU temperature probe #2 reading.
- The exhaust temperature in the upper plenum on 2nd generation ARUs.
- NOTE: -1 will be returned if the ARU is not communicating.
- Values are represented in whole number degrees.
- Units are displayed in the scale shown in
- the rARUStatusSysTempUnits OID (Celsius or Fahrenheit)."
- ::= { rARUStatusEntry 6 }
- rARUStatusAruTemp3 OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "ARU temperature probe #3 reading.
- The exhaust temperature in the lower plenum on 2nd generation ARUs.
- NOTE: -1 will be returned if the ARU is not communicating.
- Values are represented in whole number degrees.
- Units are displayed in the scale shown in
- the rARUStatusSysTempUnits OID (Celsius or Fahrenheit)."
- ::= { rARUStatusEntry 7 }
- rARUStatusAruTempOvrdEnableDisable OBJECT-TYPE
- SYNTAX INTEGER {
- disabled(1),
- enabled(2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This OID indicates whether the ARU remote temperature override is enabled or disabled.
- If this OID is a 1, the remote setting for temperature override is disabled.
- If this OID is a 2, the remote setting for temperature override is enabled."
- ::= { rARUStatusEntry 8 }
- rARUStatusAruTempOvrdSetpoint OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "ARU remote temperature override setpoint setting.
- NOTE: -1 will be returned if the ARU is not communicating.
- Values are represented in whole number degrees.
- Units are displayed in the scale shown in
- the rARUStatusSysTempUnits OID (Celsius or Fahrenheit)."
- ::= { rARUStatusEntry 9 }
- rARUStatusAruAlarmState OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "An ASCII string containing the 8 flags representing
- the current alarm state of the ARU. If the state of
- the ARU is unknown, this variable is set to 'UNKNOWN'.
- The flags are numbered 1 to 8, read from left to
- right. The flags are defined as follows:
-
- Flag 1: Fan Fail 1
- Flag 2: Fan Fail 2
- Flag 3: Fan Fail 3
- Flag 4: Smoke (if ARU is equipped with smoke detector)
-
- Flag 5: High Temp (Out of Thermal Control)
- Flag 6: Over Temp (Exhaust Temp. Exceeds Override Setpoint)
- Flag 7: Fan Fail 4 (Gen 2 ARU only)
- Flag 8: Reserved"
- ::= { rARUStatusEntry 10 }
- rARUStatusAruCommStatus OBJECT-TYPE
- SYNTAX INTEGER {
- commsNeverDiscovered(1),
- commsEstablished(2),
- commsLost(3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The state of communications to the device.
- commNeverDiscovered(1) indicates there has never been communications with this device.
- commsEstablished(2) indicates communication is normal and active with this device.
- commsLost(3) indicates communication had been established, but is no device."
- ::= { rARUStatusEntry 11 }
- rARUStatusAruTempOvrdStatus OBJECT-TYPE
- SYNTAX INTEGER {
- inactive (1),
- active (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Specifies whether the ARU is increasing airflow because
- exhaust air temperature has exceeded the setting specified in the
- rARUConfigAruTempOvrdSetpoint OID."
- ::= { rARUStatusEntry 12 }
- rARUStatusAruMasterControl OBJECT-TYPE
- SYNTAX INTEGER {
- aruOn (1),
- aruOff (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This is the master on/off control for the ARU."
- ::= { rARUStatusEntry 13 }
- rARUStatusAruTotalAirflow OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The total airflow provided by the aru. Specified in cfm (cubic feet per minute).
- Can be converted to metric values using the conversion factor:
- 1 cfm = 1.70 m^3/hr (cubic meters per hour)."
- ::= { rARUStatusEntry 14 }
- -- RACK AIR REMOVAL UNIT FAN STATUS
- rARUFanStatusTable OBJECT-TYPE
- SYNTAX SEQUENCE OF RARUFanStatusEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for query of the individual devices.
- The number of entries is contained in the
- rARUStatusAruDeviceCount OID."
- ::= { rARUFanStatus 1 }
- rARUFanStatusEntry OBJECT-TYPE
- SYNTAX RARUFanStatusEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The device to query."
- INDEX { rARUFanStatusAruIndex, rARUFanStatusFanIndex}
- ::= { rARUFanStatusTable 1 }
- RARUFanStatusEntry ::=
- SEQUENCE {
- rARUFanStatusAruIndex INTEGER,
- rARUFanStatusNominalFanSpeed INTEGER,
- rARUFanStatusSelectedFanLevel INTEGER,
- rARUFanStatusReplacementThreshold INTEGER,
- rARUFanStatusFanIndex INTEGER,
- rARUFanStatusFanOperatingStatus INTEGER,
- rARUFanStatusFanRpmSpeed INTEGER,
- rARUFanStatusFanFlowRate INTEGER,
- rARUFanStatusFanInServiceDate DisplayString,
- rARUFanStatusFanRunhourCounter INTEGER,
- rARUFanStatusFanRunhourReset INTEGER
- }
- rARUFanStatusAruIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the ARU entry."
- ::= { rARUFanStatusEntry 1 }
- rARUFanStatusNominalFanSpeed OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The nominal rotational speed (RPM) of the fans when they are
- operating at the 100% level."
- ::= { rARUFanStatusEntry 2 }
- rARUFanStatusSelectedFanLevel OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The currently selected ARU speed level,
- specified in percent of full capacity."
- ::= { rARUFanStatusEntry 3 }
- rARUFanStatusReplacementThreshold OBJECT-TYPE
- SYNTAX INTEGER {
- disabled (1),
- khr20 (2),
- khr25 (3),
- khr30 (4),
- khr35 (5),
- khr40 (6),
- khr50 (7)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Threshold above which a run hour alarm will exist, indicating
- that it might be time to proactively replace a fan."
- ::= { rARUFanStatusEntry 4 }
- rARUFanStatusFanIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to an individual fan table entry."
- ::= { rARUFanStatusEntry 5 }
-
- rARUFanStatusFanOperatingStatus OBJECT-TYPE
- SYNTAX INTEGER {
- unknown (1),
- off (2),
- onOk (3),
- onDegraded (4),
- offFailed (5)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The current operating state of the fan."
- ::= { rARUFanStatusEntry 6 }
- rARUFanStatusFanRpmSpeed OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The current rotational speed of the fan,
- specified in rotations per minute (RPM)."
- ::= { rARUFanStatusEntry 7 }
- rARUFanStatusFanFlowRate OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The flow rate provided by the fan, based on its measured rotational speed.
- Specified in cfm (cubic feet per minute). Can be converted to metric values
- using the conversion factor: 1 cfm = 1.70 m^3/hr (cubic meters per hour)."
- ::= { rARUFanStatusEntry 8 }
- rARUFanStatusFanInServiceDate OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The installation/replacement date of the fan."
- ::= { rARUFanStatusEntry 9 }
- rARUFanStatusFanRunhourCounter OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The total time for which the fan has been running.
- Specified in 10ths of hours."
- ::= { rARUFanStatusEntry 10 }
- rARUFanStatusFanRunhourReset OBJECT-TYPE
- SYNTAX INTEGER {
- yes (1),
- no (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Writing yes to this This OID will reset a fan's total run hour counter,
- which is shown in the rARUFanStatusFanRunhourCounter OID."
- ::= { rARUFanStatusEntry 11 }
- -- RACK AIR REMOVAL UNIT INPUT POWER STATUS
- rARUPowerStatusTable OBJECT-TYPE
- SYNTAX SEQUENCE OF RARUPowerStatusEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for query of the individual ARUs accessible from this IP address.
- The number of entries is contained in the rARUStatusAruDeviceCount OID."
- ::= { rARUPower 1 }
- rARUPowerStatusEntry OBJECT-TYPE
- SYNTAX RARUPowerStatusEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The device to query."
- INDEX { rARUPowerStatusAruIndex}
- ::= { rARUPowerStatusTable 1 }
- RARUPowerStatusEntry ::=
- SEQUENCE {
- rARUPowerStatusAruIndex INTEGER,
- rARUPowerStatusPrimaryAcPresent INTEGER,
- rARUPowerStatusAuxiliaryAcPresent INTEGER,
- rARUPowerStatusRedundantAcConfig INTEGER
- }
- rARUPowerStatusAruIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the ARU entry."
- ::= { rARUPowerStatusEntry 1 }
- rARUPowerStatusPrimaryAcPresent OBJECT-TYPE
- SYNTAX INTEGER {
- yes (1),
- no (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Indicates whether or not line voltage is present on AC input 1."
- ::= { rARUPowerStatusEntry 2 }
- rARUPowerStatusAuxiliaryAcPresent OBJECT-TYPE
- SYNTAX INTEGER {
- yes (1),
- no (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Indicates whether or not line voltage is present on AC input 2."
- ::= { rARUPowerStatusEntry 3 }
- rARUPowerStatusRedundantAcConfig OBJECT-TYPE
- SYNTAX INTEGER {
- singleCord (1),
- dualCord (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Indicates whether or not a dual cord is in use.
- When this setting is set to dualCord (2), aruRedundantPowerLostAlarm
- traps will be generated when either primary or auxiliary input
- voltage is not present. When this setting is set to singleCord (1),
- aruRedundantPowerLostAlarm traps will not be generated."
- ::= { rARUPowerStatusEntry 4 }
- -- RACK AIR REMOVAL UNIT SENSOR STATUS
- rARUSensorsStatusTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the rARUSensorsStatusTable."
- ::= { rARUSensors 1 }
-
- rARUSensorsStatusTable OBJECT-TYPE
- SYNTAX SEQUENCE OF RARUSensorsStatusEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting environmental sensor status information."
- ::= { rARUSensors 2 }
-
- rARUSensorsStatusEntry OBJECT-TYPE
- SYNTAX RARUSensorsStatusEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The unit to get data from."
- INDEX { rARUSensorsStatusAruIndex, rARUSensorsStatusSensorNumber }
- ::= { rARUSensorsStatusTable 1 }
-
- RARUSensorsStatusEntry ::=
- SEQUENCE {
- rARUSensorsStatusAruIndex INTEGER,
- rARUSensorsStatusSensorNumber INTEGER,
- rARUSensorsTemperature INTEGER
- }
- rARUSensorsStatusAruIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the ARU entry."
- ::= { rARUSensorsStatusEntry 1 }
- rARUSensorsStatusSensorNumber OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of the sensor on the device."
- ::= { rARUSensorsStatusEntry 2 }
- rARUSensorsTemperature OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The sensor's current temperature reading. The temperature scale
- is based on the system preferences configuration."
- ::= { rARUSensorsStatusEntry 3 }
- -- RACK AIR REMOVAL UNIT CONFIG STATUS
- rARUSensorsConfigTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the rARUSensorsConfigTable."
- ::= { rARUSensors 3 }
-
- rARUSensorsConfigTable OBJECT-TYPE
- SYNTAX SEQUENCE OF RARUSensorsConfigEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting configuration information from
- environmental sensors attached to the device."
- ::= { rARUSensors 4 }
-
- rARUSensorsConfigEntry OBJECT-TYPE
- SYNTAX RARUSensorsConfigEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The unit to get data from."
- INDEX { rARUSensorsConfigAruIndex, rARUSensorsConfigSensorNumber }
- ::= { rARUSensorsConfigTable 1 }
-
- RARUSensorsConfigEntry ::=
- SEQUENCE {
- rARUSensorsConfigAruIndex INTEGER,
- rARUSensorsConfigSensorNumber INTEGER,
- rARUSensorsName DisplayString,
- rARUSensorsLocation DisplayString,
- rARUSensorsTempMaxThresh INTEGER,
- rARUSensorsTempHighThresh INTEGER,
- rARUSensorsTempLowThresh INTEGER,
- rARUSensorsTempMinThresh INTEGER,
- rARUSensorsTempThreshHysteresis INTEGER,
- rARUSensorsTempShortDecRateThreshValue INTEGER,
- rARUSensorsTempShortDecRateThreshTime INTEGER,
- rARUSensorsTempShortIncRateThreshValue INTEGER,
- rARUSensorsTempShortIncRateThreshTime INTEGER,
- rARUSensorsTempLongDecRateThreshValue INTEGER,
- rARUSensorsTempLongDecRateThreshTime INTEGER,
- rARUSensorsTempLongIncRateThreshValue INTEGER,
- rARUSensorsTempLongIncRateThreshTime INTEGER
- }
- rARUSensorsConfigAruIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to the ARU entry."
- ::= { rARUSensorsConfigEntry 1 }
- rARUSensorsConfigSensorNumber OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of the sensor on the device."
- ::= { rARUSensorsConfigEntry 2 }
- rARUSensorsName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "A descriptive name for the sensor."
- ::= { rARUSensorsConfigEntry 3 }
-
- rARUSensorsLocation OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The location of the sensor."
- ::= { rARUSensorsConfigEntry 4 }
- rARUSensorsTempMaxThresh OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The temperature at which a maximum temperature threshold
- violation alarm will be generated for this sensor.
- The temperature scale is based on the system preferences
- configuration."
- ::= { rARUSensorsConfigEntry 5 }
-
- rARUSensorsTempHighThresh OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The temperature at which a high temperature threshold
- violation alarm will be generated for this sensor.
- The temperature scale is based on the system preferences
- configuration."
- ::= { rARUSensorsConfigEntry 6 }
-
- rARUSensorsTempLowThresh OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The temperature at which a low temperature threshold
- violation alarm will be generated for this sensor.
- The temperature scale is based on the system preferences
- configuration."
- ::= { rARUSensorsConfigEntry 7 }
-
- rARUSensorsTempMinThresh OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The temperature at which a min temperature threshold
- violation alarm will be generated for this sensor.
- The temperature scale is based on the system preferences
- configuration."
- ::= { rARUSensorsConfigEntry 8 }
-
- rARUSensorsTempThreshHysteresis OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The change in temperature required to cause a
- temperature alarm to change from an active to an
- inactive state. The temperature scale is based on
- the system preferences configuration."
- ::= { rARUSensorsConfigEntry 9 }
- rARUSensorsTempShortDecRateThreshValue OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The value of the temperature short-term decreasing rate
- time that will cause an alarm to be generated.
- The temperature scale is based on the system preferences
- configuration."
- ::= { rARUSensorsConfigEntry 10 }
- rARUSensorsTempShortDecRateThreshTime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The time over which the temperature may not decrease
- beyond the value specified by the temperature short-term
- decreasing rate threshold value."
- ::= { rARUSensorsConfigEntry 11 }
-
- rARUSensorsTempShortIncRateThreshValue OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The value of the temperature short-term increasing rate
- time that will cause an alarm to be generated.
- The temperature scale is based on the system preferences
- configuration."
- ::= { rARUSensorsConfigEntry 12 }
- rARUSensorsTempShortIncRateThreshTime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The time over which the temperature may not increase
- beyond the value specified by the temperature short-term
- increasing rate threshold value."
- ::= { rARUSensorsConfigEntry 13 }
-
- rARUSensorsTempLongDecRateThreshValue OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The value of the temperature long-term decreasing rate
- time that will cause an alarm to be generated.
- The temperature scale is based on the system preferences
- configuration."
- ::= { rARUSensorsConfigEntry 14 }
- rARUSensorsTempLongDecRateThreshTime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The time over which the temperature may not decrease
- beyond the value specified by the temperature long-term
- decreasing rate threshold value."
- ::= { rARUSensorsConfigEntry 15 }
-
- rARUSensorsTempLongIncRateThreshValue OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The value of the temperature long-term increasing rate
- time that will cause an alarm to be generated.
- The temperature scale is based on the system preferences
- configuration."
- ::= { rARUSensorsConfigEntry 16 }
- rARUSensorsTempLongIncRateThreshTime OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The time over which the temperature may not increase
- beyond the value specified by the temperature long-term
- increasing rate threshold value."
- ::= { rARUSensorsConfigEntry 17 }
- -- MODULAR DISTRIBUTION SYSTEM
- -- Modular Information
- isxModularDistInfoTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the isxModularDistInfoTable."
- ::= { isxModularDistInfo 1 }
- isxModularDistInfoTable OBJECT-TYPE
- SYNTAX SEQUENCE OF IsxModularDistInfoEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting information about the modular
- distribution metering equipment."
- ::= { isxModularDistInfo 2 }
-
- isxModularDistInfoEntry OBJECT-TYPE
- SYNTAX IsxModularDistInfoEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "An entry containing information about an individual metering segment."
- INDEX { isxModularDistInfoSegmentIndex }
- ::= { isxModularDistInfoTable 1 }
-
- IsxModularDistInfoEntry ::=
- SEQUENCE {
- isxModularDistInfoSegmentIndex INTEGER,
- isxModularDistInfoMeterModelNumber DisplayString,
- isxModularDistInfoMeterSerialNumber DisplayString,
- isxModularDistInfoMeterDateOfManufacture DisplayString,
- isxModularDistInfoMeterFirmwareRev DisplayString,
- isxModularDistInfoMeterHardwareRev DisplayString
- }
- isxModularDistInfoSegmentIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index of the metering segment."
- ::= { isxModularDistInfoEntry 1 }
- isxModularDistInfoMeterModelNumber OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The model number of the metering board for this segment."
- ::= { isxModularDistInfoEntry 2 }
- isxModularDistInfoMeterSerialNumber OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The serial number of the metering board for this segment."
- ::= { isxModularDistInfoEntry 3 }
- isxModularDistInfoMeterDateOfManufacture OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The date of manufacture for the metering board for this segment,
- in the format mm/dd/yyyy."
- ::= { isxModularDistInfoEntry 4 }
- isxModularDistInfoMeterFirmwareRev OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The firmware revision number of the metering board for this segment."
- ::= { isxModularDistInfoEntry 5 }
- isxModularDistInfoMeterHardwareRev OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The hardware revision number of the metering board for this segment."
- ::= { isxModularDistInfoEntry 6 }
- -- Distribution Modules
- isxModularDistModuleInfoTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the isxModularDistModuleInfoTable."
- ::= { isxModularDistModules 1 }
- isxModularDistModuleInfoTable OBJECT-TYPE
- SYNTAX SEQUENCE OF IsxModularDistModuleInfoEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting basic information about the distribution modules
- installed in the system."
- ::= { isxModularDistModules 2 }
- isxModularDistModuleInfoEntry OBJECT-TYPE
- SYNTAX IsxModularDistModuleInfoEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "An entry containing information about a specific distribution module."
- INDEX { isxModularDistModuleInfoModIndex }
- ::= { isxModularDistModuleInfoTable 1 }
- IsxModularDistModuleInfoEntry ::=
- SEQUENCE {
- isxModularDistModuleInfoModIndex INTEGER,
- isxModularDistModuleInfoAlarmStatus INTEGER,
- isxModularDistModuleInfoModelNumber DisplayString,
- isxModularDistModuleInfoSerialNumber DisplayString,
- isxModularDistModuleInfoDateOfManufacture DisplayString,
- isxModularDistModuleInfoNumCables INTEGER
- }
- isxModularDistModuleInfoModIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of the distribution module."
- ::= { isxModularDistModuleInfoEntry 1 }
- isxModularDistModuleInfoAlarmStatus OBJECT-TYPE
- SYNTAX INTEGER {
- normal (1),
- warning (2),
- critical (3),
- notPresent (4),
- unknown (5)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The status of this module. This reflects the indicator lamp(s) on the front of the module.
- A value of notPresent indicates that the module is not installed.
- A value of unknown indicates that there is no communication with the
- metering segment for this module."
- ::= { isxModularDistModuleInfoEntry 2 }
- isxModularDistModuleInfoModelNumber OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The model number of the distribution module."
- ::= { isxModularDistModuleInfoEntry 3 }
- isxModularDistModuleInfoSerialNumber OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The serial number of the distribution module."
- ::= { isxModularDistModuleInfoEntry 4 }
- isxModularDistModuleInfoDateOfManufacture OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The date that the distribution module was manufactured."
- ::= { isxModularDistModuleInfoEntry 5 }
- isxModularDistModuleInfoNumCables OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of cables provided by this distribution module."
- ::= { isxModularDistModuleInfoEntry 6 }
- isxModularDistModuleBreakerTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the isxModularDistModuleBreakerTable."
- ::= { isxModularDistModules 3 }
- isxModularDistModuleBreakerTable OBJECT-TYPE
- SYNTAX SEQUENCE OF IsxModularDistModuleBreakerEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting operational information about the distribution modules."
- ::= { isxModularDistModules 4 }
- isxModularDistModuleBreakerEntry OBJECT-TYPE
- SYNTAX IsxModularDistModuleBreakerEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "An entry containing information about a specific distribution modules and circuit breakers."
- INDEX { isxModularDistModuleBreakerModIndex, isxModularDistModuleBreakerPhaseIndex}
- ::= { isxModularDistModuleBreakerTable 1 }
- IsxModularDistModuleBreakerEntry ::=
- SEQUENCE {
- isxModularDistModuleBreakerModIndex INTEGER,
- isxModularDistModuleBreakerPhaseIndex INTEGER,
- isxModularDistModuleBreakerAlarmStatus INTEGER,
- isxModularDistModuleBreakerRating INTEGER,
- isxModularDistModuleBreakerPhysicalGroup INTEGER,
- isxModularDistModuleBreakerCableNum INTEGER,
- isxModularDistModuleBreakerPosition INTEGER,
- isxModularDistModuleBreakerPositionAlarms INTEGER,
- isxModularDistModuleBreakerCurrent INTEGER,
- isxModularDistModuleBreakerPercent INTEGER,
- isxModularDistModuleBreakerPower INTEGER
- }
- isxModularDistModuleBreakerModIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The distribution module number."
- ::= { isxModularDistModuleBreakerEntry 1 }
- isxModularDistModuleBreakerPhaseIndex OBJECT-TYPE
- SYNTAX INTEGER{
- phaseL1(1),
- phaseL2(2),
- phaseL3(3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index to an individual breaker in the distribution module. The index also corresponds
- to the system phase to which the breaker is attached."
- ::= { isxModularDistModuleBreakerEntry 2 }
- isxModularDistModuleBreakerAlarmStatus OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This is a bit map representing the active alarms for this breaker:
- b0 - Minimum current threshold exceeded (critical)
- b1 - Low current threshold exceeded (warning)
- b2 - High current threshold exceeded (warning)
- b3 - Maximum current threshold exceeded (critical)
- b4 - Breaker is open (critical)
- If a bit is set, the corresponding alarm is active."
- ::= { isxModularDistModuleBreakerEntry 3 }
- isxModularDistModuleBreakerRating OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The current rating of the breaker."
- ::= { isxModularDistModuleBreakerEntry 4 }
- isxModularDistModuleBreakerPhysicalGroup OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Numeric value used to indicate that a breaker is a part of a multi-pole breaker.
- Breakers within a distribution module, with equivalent physical group numbers,
- have their handles physically tied together.
- A value of zero indicates a single-handle breaker."
- ::= { isxModularDistModuleBreakerEntry 5 }
- isxModularDistModuleBreakerCableNum OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Numeric value used to indicate the distribution cable to which
- this breaker is connected. These distribution cables are described
- in the table isxModularDistModuleOutputTable,
- and indexed by the OID isxModularDistModuleOutputCordIndex."
- ::= { isxModularDistModuleBreakerEntry 6 }
- isxModularDistModuleBreakerPosition OBJECT-TYPE
- SYNTAX INTEGER {
- open (1),
- closed (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The physical status of this breaker pole, either closed or open (including tripped)."
- ::= { isxModularDistModuleBreakerEntry 7 }
- isxModularDistModuleBreakerPositionAlarms OBJECT-TYPE
- SYNTAX INTEGER {
- disabled (1),
- enabled (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enable or disable breaker position alarms for this circuit breaker."
- ::= { isxModularDistModuleBreakerEntry 8 }
- isxModularDistModuleBreakerCurrent OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The current flowing though this breaker. Measured in tenths of amps."
- ::= { isxModularDistModuleBreakerEntry 9 }
- isxModularDistModuleBreakerPercent OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The loading on this breaker as a percentage of the breaker's current rating.
- Expressed in tenths of percent."
- ::= { isxModularDistModuleBreakerEntry 10 }
- isxModularDistModuleBreakerPower OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The power being supplied through this breaker. Measured in tenths of kW."
- ::= { isxModularDistModuleBreakerEntry 11 }
- isxModularDistModuleOutputsTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the isxModularDistModuleOutputTable."
- ::= { isxModularDistModules 5 }
- isxModularDistModuleOutputTable OBJECT-TYPE
- SYNTAX SEQUENCE OF IsxModularDistModuleOutputEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting and setting information related to the
- load equipment being fed by the distribution modules in the ISX
- Modular Distribution System."
- ::= { isxModularDistModules 6 }
-
- isxModularDistModuleOutputEntry OBJECT-TYPE
- SYNTAX IsxModularDistModuleOutputEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "An entry containing information about a specific distribution module
- and its output distribution cables."
- INDEX { isxModularDistModuleOutputModIndex, isxModularDistModuleOutputCordIndex }
- ::= { isxModularDistModuleOutputTable 1 }
-
- IsxModularDistModuleOutputEntry ::=
- SEQUENCE {
- isxModularDistModuleOutputModIndex INTEGER,
- isxModularDistModuleOutputNumCables INTEGER,
- isxModularDistModuleOutputCordIndex INTEGER,
- isxModularDistModuleOutputName DisplayString,
- isxModularDistModuleOutputLocation DisplayString,
- isxModularDistModuleOutputStatus INTEGER,
- isxModularDistModuleOutputAlarmGeneration INTEGER,
- isxModularDistModuleOutputBreakerMap INTEGER,
- isxModularDistModuleOutputThresholdMin INTEGER,
- isxModularDistModuleOutputThresholdLow INTEGER,
- isxModularDistModuleOutputThresholdHigh INTEGER,
- isxModularDistModuleOutputThresholdMax INTEGER,
- isxModularDistModuleOutputAlarmMinEnable INTEGER,
- isxModularDistModuleOutputAlarmLowEnable INTEGER,
- isxModularDistModuleOutputAlarmHighEnable INTEGER,
- isxModularDistModuleOutputAlarmMaxEnable INTEGER,
- isxModularDistModuleOutputCableLength INTEGER,
- isxModularDistModuleOutputConnectorType DisplayString,
- isxModularDistModuleOutputAvailableVoltages INTEGER,
- isxModularDistModuleOutputTotalPower INTEGER,
- isxModularDistModuleOutputKwhUsage INTEGER,
- isxModularDistModuleOutputKwhReset INTEGER,
- isxModularDistModuleOutputKwhResetDate DisplayString
- }
- isxModularDistModuleOutputModIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of the distribution module supplying power to the load equipment."
- ::= { isxModularDistModuleOutputEntry 1 }
- isxModularDistModuleOutputNumCables OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of distribution cables provided by this module."
- ::= { isxModularDistModuleOutputEntry 2 }
- isxModularDistModuleOutputCordIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index of an individual distribution cable supplied by this module."
- ::= { isxModularDistModuleOutputEntry 3 }
- isxModularDistModuleOutputName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "A string describing the load equipment being supplied by this distribution cable."
- ::= { isxModularDistModuleOutputEntry 4 }
- isxModularDistModuleOutputLocation OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "A string describing the location of equipment being supplied by distribution cable."
- ::= { isxModularDistModuleOutputEntry 5 }
- isxModularDistModuleOutputStatus OBJECT-TYPE
- SYNTAX INTEGER {
- normal (1),
- warning (2),
- critical (3),
- notPresent (4),
- unknown (6)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This reflects the worse case severity for alarms associated with this distribution cable.
- A value of notPresent indicates that the cable does not exist for this module.
- A value of unknown indicates that the there is no communication with the
- metering segment for this distribution cable's module."
- ::= { isxModularDistModuleOutputEntry 6 }
- isxModularDistModuleOutputAlarmGeneration OBJECT-TYPE
- SYNTAX INTEGER {
- disabled (1),
- enabled (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enable or disable all alarm generation related to this distribution cable."
- ::= { isxModularDistModuleOutputEntry 7 }
- isxModularDistModuleOutputBreakerMap OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This is a bit map representing the breaker poles within the
- module that are associated with this distribution cable.
- The following 3 bits are used to indicate the indices of
- the breakers feeding the cable:
- b0 - Module breaker L1
- b1 - Module breaker L2
- b2 - Module breaker L3
- If a bit is set, the breaker is used to feed this distribution cable.
- These breakers are described in the table isxModularDistModuleBreakerTable,
- and indexed by the OID isxModularDistModuleBreakerPhaseIndex."
- ::= { isxModularDistModuleOutputEntry 8 }
- isxModularDistModuleOutputThresholdMin OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "When the current drops below this value a critical alarm will exist."
- ::= { isxModularDistModuleOutputEntry 9 }
- isxModularDistModuleOutputThresholdLow OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "When the current drops below this value a warning alarm will exist."
- ::= { isxModularDistModuleOutputEntry 10 }
- isxModularDistModuleOutputThresholdHigh OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "When the current exceeds this value a warning alarm will exist."
- ::= { isxModularDistModuleOutputEntry 11 }
- isxModularDistModuleOutputThresholdMax OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "When the current exceeds this value a critical alarm will exist."
- ::= { isxModularDistModuleOutputEntry 12 }
- isxModularDistModuleOutputAlarmMinEnable OBJECT-TYPE
- SYNTAX INTEGER {
- disabled (1),
- enabled (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enable or disable minimum current alarm generation for this distribution cable."
- ::= { isxModularDistModuleOutputEntry 13 }
- isxModularDistModuleOutputAlarmLowEnable OBJECT-TYPE
- SYNTAX INTEGER {
- disabled (1),
- enabled (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enable or disable low current alarm generation for this distribution cable."
- ::= { isxModularDistModuleOutputEntry 14 }
- isxModularDistModuleOutputAlarmHighEnable OBJECT-TYPE
- SYNTAX INTEGER {
- disabled (1),
- enabled (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enable or disable high current alarm generation for this distribution cable."
- ::= { isxModularDistModuleOutputEntry 15 }
- isxModularDistModuleOutputAlarmMaxEnable OBJECT-TYPE
- SYNTAX INTEGER {
- disabled (1),
- enabled (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enable or disable maximum current alarm generation for this distribution cable."
- ::= { isxModularDistModuleOutputEntry 16 }
- isxModularDistModuleOutputCableLength OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The length of this distribution cable. Specified in tenths of meters."
- ::= { isxModularDistModuleOutputEntry 17 }
- isxModularDistModuleOutputConnectorType OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A string describing the connector on the end of this distribution cable."
- ::= { isxModularDistModuleOutputEntry 18 }
- isxModularDistModuleOutputAvailableVoltages OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This is a bit map representing the voltages that are available at the connector.
- 6 bits are used to indicate the following:
- b0 - L1
- b1 - L2
- b2 - L3
- b3 - L1-2
- b4 - L2-3
- b5 - L3-1"
- ::= { isxModularDistModuleOutputEntry 19 }
- isxModularDistModuleOutputTotalPower OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The total power being consumed by the load equipment supplied by this distribution cable.
- Measured in tenths of kW."
- ::= { isxModularDistModuleOutputEntry 20 }
- isxModularDistModuleOutputKwhUsage OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The total energy consumed by the load equipment fed by this distribution cable.
- This is the total since the date specified in the isxModularDistModuleOutputKwhResetDate
- OID, and may be cleared using the isxModularDistModuleOutputKwhReset OID.
- Measured in tenths of kWh."
- ::= { isxModularDistModuleOutputEntry 21 }
- isxModularDistModuleOutputKwhReset OBJECT-TYPE
- SYNTAX INTEGER {
- no (1),
- yes (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Writing yes to this OID will reset the total kWh usage shown
- in the isxModularDistModuleOutputKwhUsage OID."
- ::= { isxModularDistModuleOutputEntry 22 }
- isxModularDistModuleOutputKwhResetDate OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The date that the kWh usage was reset, in the format mm/dd/yyyy. Example: 01/01/2000."
- ::= { isxModularDistModuleOutputEntry 23 }
- -- Distribution Subfeeds
- isxModularDistSubFeedInfoTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the isxModularDistSubFeedInfoTable."
- ::= { isxModularDistSubFeeds 1 }
-
- isxModularDistSubFeedInfoTable OBJECT-TYPE
- SYNTAX SEQUENCE OF IsxModularDistSubFeedInfoEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting information about distribution subfeed breakers."
- ::= { isxModularDistSubFeeds 2 }
-
- isxModularDistSubFeedInfoEntry OBJECT-TYPE
- SYNTAX IsxModularDistSubFeedInfoEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "An entry containing information about a specific distribution subfeed."
- INDEX { isxModularDistSubFeedInfoSubIndex }
- ::= { isxModularDistSubFeedInfoTable 1 }
-
- IsxModularDistSubFeedInfoEntry ::=
- SEQUENCE {
- isxModularDistSubFeedInfoSubIndex INTEGER,
- isxModularDistSubFeedInfoName DisplayString,
- isxModularDistSubFeedInfoLocation DisplayString,
- isxModularDistSubFeedInfoBreakerRating INTEGER,
- isxModularDistSubFeedInfoBreakerPosition INTEGER,
- isxModularDistSubFeedInfoAlarmStatus INTEGER,
- isxModularDistSubFeedInfoAlarmGeneration INTEGER,
- isxModularDistSubFeedInfoThresholdMin INTEGER,
- isxModularDistSubFeedInfoThresholdLow INTEGER,
- isxModularDistSubFeedInfoThresholdHigh INTEGER,
- isxModularDistSubFeedInfoThresholdMax INTEGER,
- isxModularDistSubFeedInfoAlarmMinEnable INTEGER,
- isxModularDistSubFeedInfoAlarmLowEnable INTEGER,
- isxModularDistSubFeedInfoAlarmHighEnable INTEGER,
- isxModularDistSubFeedInfoAlarmMaxEnable INTEGER,
- isxModularDistSubFeedInfoBreakerAlarmEnable INTEGER,
- isxModularDistSubFeedInfoTotalPower INTEGER,
- isxModularDistSubFeedInfoKwhUsage INTEGER,
- isxModularDistSubFeedInfoKwhReset INTEGER,
- isxModularDistSubFeedInfoKwhResetDate DisplayString
- }
- isxModularDistSubFeedInfoSubIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index of an individual subfeed."
- ::= { isxModularDistSubFeedInfoEntry 1 }
- isxModularDistSubFeedInfoName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "A string describing the load equipment being supplied by this subfeed."
- ::= { isxModularDistSubFeedInfoEntry 2 }
- isxModularDistSubFeedInfoLocation OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "A string describing the location of the equipment being supplied by this subfeed."
- ::= { isxModularDistSubFeedInfoEntry 3 }
- isxModularDistSubFeedInfoBreakerRating OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The current rating of this subfeed breaker."
- ::= { isxModularDistSubFeedInfoEntry 4 }
- isxModularDistSubFeedInfoBreakerPosition OBJECT-TYPE
- SYNTAX INTEGER {
- open (1),
- closed (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The operational status of this breaker, either closed or open (including tripped)."
- ::= { isxModularDistSubFeedInfoEntry 5 }
- isxModularDistSubFeedInfoAlarmStatus OBJECT-TYPE
- SYNTAX INTEGER {
- normal (1),
- warning (2),
- critical (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The worst case alarm status for this subfeed."
- ::= { isxModularDistSubFeedInfoEntry 6 }
- isxModularDistSubFeedInfoAlarmGeneration OBJECT-TYPE
- SYNTAX INTEGER {
- disabled (1),
- enabled (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enable or disable all alarm generation related to this subfeed."
- ::= { isxModularDistSubFeedInfoEntry 7 }
- isxModularDistSubFeedInfoThresholdMin OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "When the current drops below this value a critical alarm will exist."
- ::= { isxModularDistSubFeedInfoEntry 8 }
- isxModularDistSubFeedInfoThresholdLow OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "When the current drops below this value a warning alarm will exist."
- ::= { isxModularDistSubFeedInfoEntry 9 }
- isxModularDistSubFeedInfoThresholdHigh OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "When the current exceeds this value a warning alarm will exist."
- ::= { isxModularDistSubFeedInfoEntry 10 }
- isxModularDistSubFeedInfoThresholdMax OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "When the current exceeds this value a critical alarm will exist."
- ::= { isxModularDistSubFeedInfoEntry 11 }
- isxModularDistSubFeedInfoAlarmMinEnable OBJECT-TYPE
- SYNTAX INTEGER {
- disabled (1),
- enabled (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enable or disable minimum current alarm generation for this subfeed."
- ::= { isxModularDistSubFeedInfoEntry 12 }
- isxModularDistSubFeedInfoAlarmLowEnable OBJECT-TYPE
- SYNTAX INTEGER {
- disabled (1),
- enabled (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enable or disable low current alarm generation for this subfeed."
- ::= { isxModularDistSubFeedInfoEntry 13 }
- isxModularDistSubFeedInfoAlarmHighEnable OBJECT-TYPE
- SYNTAX INTEGER {
- disabled (1),
- enabled (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enable or disable high current alarm generation for this subfeed."
- ::= { isxModularDistSubFeedInfoEntry 14 }
- isxModularDistSubFeedInfoAlarmMaxEnable OBJECT-TYPE
- SYNTAX INTEGER {
- disabled (1),
- enabled (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enable or disable maximum current alarm generation for this subfeed."
- ::= { isxModularDistSubFeedInfoEntry 15 }
- isxModularDistSubFeedInfoBreakerAlarmEnable OBJECT-TYPE
- SYNTAX INTEGER {
- disabled (1),
- enabled (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enable or disable breaker position alarms for this subfeed."
- ::= { isxModularDistSubFeedInfoEntry 16 }
- isxModularDistSubFeedInfoTotalPower OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The total power being supplied by this subfeed. Measured in tenths of kW."
- ::= { isxModularDistSubFeedInfoEntry 17 }
- isxModularDistSubFeedInfoKwhUsage OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The total energy consumed by the load equipment fed by this subfeed.
- This is the total since the date specified in the isxModularDistSubFeedInfoKwhResetDate
- OID, and may be cleared using the isxModularDistSubFeedInfoKwhReset OID.
- Measured in tenths of kWh."
- ::= { isxModularDistSubFeedInfoEntry 18 }
- isxModularDistSubFeedInfoKwhReset OBJECT-TYPE
- SYNTAX INTEGER {
- no (1),
- yes (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Writing yes to this OID will reset the total kWh usage shown
- in the isxModularDistSubFeedInfoKwhUsage OID."
- ::= { isxModularDistSubFeedInfoEntry 19 }
- isxModularDistSubFeedInfoKwhResetDate OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The date that the kWh usage was reset, in the format mm/dd/yyyy. Example: 01/01/2000."
- ::= { isxModularDistSubFeedInfoEntry 20 }
- isxModularDistSubFeedLoadingTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the isxModularDistSubFeedLoadingTable."
- ::= { isxModularDistSubFeeds 3 }
- isxModularDistSubFeedLoadingTable OBJECT-TYPE
- SYNTAX SEQUENCE OF IsxModularDistSubFeedLoadingEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting subfeed phase loading information."
- ::= { isxModularDistSubFeeds 4 }
- isxModularDistSubFeedLoadingEntry OBJECT-TYPE
- SYNTAX IsxModularDistSubFeedLoadingEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "An entry containing data for an individual subfeed."
- INDEX { isxModularDistSubFeedLoadingSubIndex, isxModularDistSubFeedLoadingPhaseIndex }
- ::= { isxModularDistSubFeedLoadingTable 1 }
- IsxModularDistSubFeedLoadingEntry ::= SEQUENCE {
- isxModularDistSubFeedLoadingSubIndex INTEGER,
- isxModularDistSubFeedLoadingPhaseIndex INTEGER,
- isxModularDistSubFeedLoadingAlarmStatus INTEGER,
- isxModularDistSubFeedLoadingCurrent INTEGER,
- isxModularDistSubFeedLoadingPercent INTEGER,
- isxModularDistSubFeedLoadingPower INTEGER
- }
- isxModularDistSubFeedLoadingSubIndex OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The index of an individual subfeed."
- ::= { isxModularDistSubFeedLoadingEntry 1 }
- isxModularDistSubFeedLoadingPhaseIndex OBJECT-TYPE
- SYNTAX INTEGER{
- phase1(1),
- phase2(2),
- phase3(3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Description of each input phase entry in the table."
- ::= { isxModularDistSubFeedLoadingEntry 2 }
- isxModularDistSubFeedLoadingAlarmStatus OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This is a bit map representing the active alarms for this subfeed:
- b0 - Minimum current threshold exceeded (critical)
- b1 - Low current threshold exceeded (warning)
- b2 - High current threshold exceeded (warning)
- b3 - Maximum current threshold exceeded (critical)
- b4 - Breaker is open (critical)
- If a bit is set, the corresponding alarm is active."
- ::= { isxModularDistSubFeedLoadingEntry 3 }
- isxModularDistSubFeedLoadingCurrent OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The current flowing though this subfeed phase. Measured in tenths of amps."
- ::= { isxModularDistSubFeedLoadingEntry 4 }
- isxModularDistSubFeedLoadingPercent OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The loading on this subfeed phase as a percentage of the subfeed's current rating.
- Expressed in tenths of percent."
- ::= { isxModularDistSubFeedLoadingEntry 5 }
- isxModularDistSubFeedLoadingPower OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The power being supplied by this subfeed phase. Measured in tenths of kW."
- ::= { isxModularDistSubFeedLoadingEntry 6 }
- -- Distribution System Output Voltage
- isxModularDistSysOutputVoltageNominalLineToNeutral OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The nominal line-to-neutral voltage available at the distribution panel."
- ::= { isxModularDistSysVoltage 1 }
- isxModularDistSysOutputVoltageNominalLineToLine OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The nominal line-to-line voltage available at the distribution panel."
- ::= { isxModularDistSysVoltage 2 }
- isxModularDistSysOutputNominalFrequency OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The nominal system output frequency. Measured in tenths of Hertz."
- ::= { isxModularDistSysVoltage 3 }
- isxModularDistSysOutputFrequency OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The system output frequency in tenths of Hertz.
- -1 if not available."
- ::= { isxModularDistSysVoltage 4 }
- isxModularDistSysOutputVoltageMonitoring OBJECT-TYPE
- SYNTAX INTEGER {
- notPresent (1),
- present (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Indicates whether or not output voltage alarm generation is present."
- ::= { isxModularDistSysVoltage 5 }
- isxModularDistSysOutputVoltageThresholdMin OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "When the line-to-neutral voltage of any phase drops below this value a critical alarm will exist.
- Specified as a percent of the nominal voltage, isxModularDistSysOutputVoltageNominalLineToNeutral.
- A value of -1 indicates that the threshold is not available in the device."
- ::= { isxModularDistSysVoltage 6 }
- isxModularDistSysOutputVoltageThresholdLow OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "When the line-to-neutral voltage of any phase drops below this value a warning alarm will exist.
- Specified as a percent of the nominal voltage, isxModularDistSysOutputVoltageNominalLineToNeutral.
- A value of -1 indicates that the threshold is not available in the device."
- ::= { isxModularDistSysVoltage 7 }
- isxModularDistSysOutputVoltageThresholdHigh OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "When the line-to-neutral voltage of any phase exceeds this value a warning alarm will exist.
- Specified as a percent of the nominal voltage, isxModularDistSysOutputVoltageNominalLineToNeutral.
- A value of -1 indicates that the threshold is not available in the device."
- ::= { isxModularDistSysVoltage 8 }
- isxModularDistSysOutputVoltageThresholdMax OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "When the line-to-neutral voltage of any phase exceeds this value a critical alarm will exist.
- Specified as a percent of the nominal voltage, isxModularDistSysOutputVoltageNominalLineToNeutral.
- A value of -1 indicates that the threshold is not available in the device."
- ::= { isxModularDistSysVoltage 9 }
- isxModularDistSysOutputVoltageAlarmMinEnable OBJECT-TYPE
- SYNTAX INTEGER {
- disabled (1),
- enabled (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enable or disable minimum voltage alarm generation for the distribution panel."
- ::= { isxModularDistSysVoltage 10 }
- isxModularDistSysOutputVoltageAlarmLowEnable OBJECT-TYPE
- SYNTAX INTEGER {
- disabled (1),
- enabled (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enable or disable low voltage alarm generation for the distribution panel."
- ::= { isxModularDistSysVoltage 11 }
- isxModularDistSysOutputVoltageAlarmHighEnable OBJECT-TYPE
- SYNTAX INTEGER {
- disabled (1),
- enabled (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enable or disable high voltage alarm generation for the distribution panel."
- ::= { isxModularDistSysVoltage 12 }
- isxModularDistSysOutputVoltageAlarmMaxEnable OBJECT-TYPE
- SYNTAX INTEGER {
- disabled (1),
- enabled (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enable or disable maximum voltage alarm generation for the distribution panel."
- ::= { isxModularDistSysVoltage 13 }
- isxModularDistSysOutputVoltageFrequencyTolerance OBJECT-TYPE
- SYNTAX INTEGER{
- freqToleranceOff (1),
- freqTolerancePointTwo (2),
- freqTolerancePointFive (3),
- freqToleranceOne (4),
- freqToleranceOnePointFive (5),
- freqToleranceTwo (6),
- freqToleranceThree (7),
- freqToleranceFour (8),
- freqToleranceFive (9),
- freqToleranceNine (10),
- freqToleranceNotAvailable (11)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "The circuit panel output frequency tolerance in Hertz.
- When the system output frequency deviates from the nominal by more than this range,
- a critical alarm will be generated."
- ::= { isxModularDistSysVoltage 14 }
- isxModularDistSysVoltageTable OBJECT-TYPE
- SYNTAX SEQUENCE OF IsxModularDistSysVoltageEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting the system output voltage information."
- ::= { isxModularDistSysVoltage 15 }
- isxModularDistSysVoltageEntry OBJECT-TYPE
- SYNTAX IsxModularDistSysVoltageEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "An entry containing data for an individual system output phase."
- INDEX { isxModularDistSysVoltagePhaseIndex }
- ::= { isxModularDistSysVoltageTable 1 }
- IsxModularDistSysVoltageEntry ::=
- SEQUENCE {
- isxModularDistSysVoltagePhaseIndex INTEGER,
- isxModularDistSysVoltageAlarmStatus INTEGER,
- isxModularDistSysVoltageLtoN INTEGER,
- isxModularDistSysVoltageLtoL INTEGER
- }
- isxModularDistSysVoltagePhaseIndex OBJECT-TYPE
- SYNTAX INTEGER{
- phase1(1),
- phase2(2),
- phase3(3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Description of each phase entry in the table."
- ::= { isxModularDistSysVoltageEntry 1 }
- isxModularDistSysVoltageAlarmStatus OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This is a bit map representing the active alarms for this output phase:
- b0 - Minimum voltage threshold exceeded (critical)
- b1 - Low voltage threshold exceeded (warning)
- b2 - High voltage threshold exceeded (warning)
- b3 - Maximum voltage threshold exceeded (critical)
- If a bit is set, the corresponding alarm is active."
- ::= { isxModularDistSysVoltageEntry 2 }
- isxModularDistSysVoltageLtoN OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Line-to-neutral system output voltage available at the distribution panel.
- Measured in tenths of Volts."
- ::= { isxModularDistSysVoltageEntry 3 }
- isxModularDistSysVoltageLtoL OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Line-to-line system output voltage available at the distribution panel.
- Measured in tenths of Volts."
- ::= { isxModularDistSysVoltageEntry 4 }
- -- Distribution System Total Output Current
- isxModularDistSysCurrentRating OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The 100 percent current rating of the distribution panel."
- ::= { isxModularDistSysCurrent 1 }
- isxModularDistSysCurrentMonitoring OBJECT-TYPE
- SYNTAX INTEGER {
- notPresent (1),
- present (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Indicates whether or not total output current measurements and alarm generation are present."
- ::= { isxModularDistSysCurrent 2 }
- isxModularDistSysCurrentThresholdMin OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "When total system current in any phase drops below this value a critical alarm will exist.
- Specified as a percent of the panel rating, isxModularDistSysCurrentRating.
- A value of -1 indicates that the threshold is not available in the device."
- ::= { isxModularDistSysCurrent 3 }
- isxModularDistSysCurrentThresholdLow OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "When total system current in any phase drops below this value a warning alarm will exist.
- Specified as a percent of the panel rating, isxModularDistSysCurrentRating.
- A value of -1 indicates that the threshold is not available in the device."
- ::= { isxModularDistSysCurrent 4 }
- isxModularDistSysCurrentThresholdHigh OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "When total system current in any phase exceeds this value a warning alarm will exist.
- Specified as a percent of the panel rating, isxModularDistSysCurrentRating.
- A value of -1 indicates that the threshold is not available in the device."
- ::= { isxModularDistSysCurrent 5 }
- isxModularDistSysCurrentThresholdMax OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "When total system current in any phase exceeds this value a critical alarm will exist.
- Specified as a percent of the panel rating, isxModularDistSysCurrentRating.
- A value of -1 indicates that the threshold is not available in the device."
- ::= { isxModularDistSysCurrent 6 }
- isxModularDistSysCurrentAlarmMinEnable OBJECT-TYPE
- SYNTAX INTEGER {
- disabled (1),
- enabled (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enable or disable minimum total output current alarm generation."
- ::= { isxModularDistSysCurrent 7 }
- isxModularDistSysCurrentAlarmLowEnable OBJECT-TYPE
- SYNTAX INTEGER {
- disabled (1),
- enabled (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enable or disable low total output current alarm generation."
- ::= { isxModularDistSysCurrent 8 }
- isxModularDistSysCurrentAlarmHighEnable OBJECT-TYPE
- SYNTAX INTEGER {
- disabled (1),
- enabled (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enable or disable high total output current alarm generation."
- ::= { isxModularDistSysCurrent 9 }
- isxModularDistSysCurrentAlarmMaxEnable OBJECT-TYPE
- SYNTAX INTEGER {
- disabled (1),
- enabled (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Enable or disable maximum total output current alarm generation."
- ::= { isxModularDistSysCurrent 10 }
- isxModularDistSysCurrentTable OBJECT-TYPE
- SYNTAX SEQUENCE OF IsxModularDistSysCurrentEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting the total system phase current information."
- ::= { isxModularDistSysCurrent 11 }
- isxModularDistSysCurrentEntry OBJECT-TYPE
- SYNTAX IsxModularDistSysCurrentEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "An entry containing data for an individual system output phase."
- INDEX { isxModularDistSysCurrentPhaseIndex }
- ::= { isxModularDistSysCurrentTable 1 }
- IsxModularDistSysCurrentEntry ::=
- SEQUENCE {
- isxModularDistSysCurrentPhaseIndex INTEGER,
- isxModularDistSysCurrentAlarmStatus INTEGER,
- isxModularDistSysCurrentAmps INTEGER,
- isxModularDistSysCurrentPercent INTEGER
- }
- isxModularDistSysCurrentPhaseIndex OBJECT-TYPE
- SYNTAX INTEGER{
- phase1(1),
- phase2(2),
- phase3(3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Description of each phase entry in the table."
- ::= { isxModularDistSysCurrentEntry 1 }
- isxModularDistSysCurrentAlarmStatus OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "This is a bit map representing the active alarms for this output phase:
- b0 - Minimum current threshold exceeded (critical)
- b1 - Low current threshold exceeded (warning)
- b2 - High current threshold exceeded (warning)
- b3 - Maximum current threshold exceeded (critical)
- If a bit is set, the corresponding alarm is active."
- ::= { isxModularDistSysCurrentEntry 2 }
- isxModularDistSysCurrentAmps OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The current flowing though this system output phase. Measured in tenths of amps."
- ::= { isxModularDistSysCurrentEntry 3 }
- isxModularDistSysCurrentPercent OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The loading on this system output phase as a percentage of the panel current rating.
- Expressed in tenths of percent."
- ::= { isxModularDistSysCurrentEntry 4 }
- -- Distribution System Total Output Power
- isxModularDistSysPowerTotal OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The total system power being supplied. Measured in tenths of kW."
- ::= { isxModularDistSysPower 1 }
- isxModularDistSysPowerKwhUsage OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The total system energy consumed by the load equipment.
- This is the total since the date specified in the isxModularDistSysOutputKwhResetDate
- OID, and may be cleared using the isxModularDistSysOutputKwhReset OID.
- Measured in tenths of kWh."
- ::= { isxModularDistSysPower 2 }
- isxModularDistSysPowerKwhReset OBJECT-TYPE
- SYNTAX INTEGER {
- no (1),
- yes (2)
- }
- ACCESS read-write
- STATUS mandatory
- DESCRIPTION
- "Writing yes to this OID will reset the total kWh usage shown
- in the isxModularDistSysPowerKwhUsage OID."
- ::= { isxModularDistSysPower 3 }
- isxModularDistSysPowerKwhResetDate OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The date that the kWh usage was reset, in the format mm/dd/yyyy. Example: 01/01/2000."
- ::= { isxModularDistSysPower 4 }
- isxModularDistSysPowerTable OBJECT-TYPE
- SYNTAX SEQUENCE OF IsxModularDistSysPowerEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting the total system phase power loading information."
- ::= { isxModularDistSysPower 5 }
- isxModularDistSysPowerEntry OBJECT-TYPE
- SYNTAX IsxModularDistSysPowerEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "An entry containing data for an individual system output phase."
- INDEX { isxModularDistSysPowerPhaseIndex }
- ::= { isxModularDistSysPowerTable 1 }
- IsxModularDistSysPowerEntry ::=
- SEQUENCE {
- isxModularDistSysPowerPhaseIndex INTEGER,
- isxModularDistSysPowerKw INTEGER,
- isxModularDistSysPowerKwhPhaseUsage INTEGER
- }
- isxModularDistSysPowerPhaseIndex OBJECT-TYPE
- SYNTAX INTEGER{
- phase1(1),
- phase2(2),
- phase3(3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Description of each phase entry in the table."
- ::= { isxModularDistSysPowerEntry 1 }
- isxModularDistSysPowerKw OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The power being supplied by this system output phase. Measured in tenths of kW."
- ::= { isxModularDistSysPowerEntry 2 }
- isxModularDistSysPowerKwhPhaseUsage OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The energy consumed by the load equipment on this system output phase.
- This is the total since the date specified in the isxModularDistSysPowerKwhResetDate
- OID, and may be cleared using the isxModularDistSysPowerKwhReset OID.
- Measured in tenths of kWh."
- ::= { isxModularDistSysPowerEntry 3 }
- -- the isxModularPduIdent group
- isxModularPduIdentModelNumber OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the model number of the PDU.
- This value is set at the factory."
- ::= { isxModularPduIdent 1 }
- isxModularPduIdentSerialNumber OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the serial number of the PDU.
- This value is set at the factory."
- ::= { isxModularPduIdent 2 }
- isxModularPduIdentDateOfManufacture OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The date when the PDU was manufactured in mm/dd/yyyy format.
- This value is set at the factory."
- ::= { isxModularPduIdent 3 }
- isxModularPduIdentMonitorCardSerialNumber OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "A character string identifying the serial number of the PDU monitor card.
- This value is set at the factory."
- ::= { isxModularPduIdent 4 }
- isxModularPduIdentMonitorCardHardwareRev OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The hardware revision of the PDU monitor card.
- This value is set at the factory."
- ::= { isxModularPduIdent 5 }
- isxModularPduIdentMonitorCardFirmwareAppRev OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "An ID string identifying the application firmware revision of the
- PDU monitor card."
- ::= { isxModularPduIdent 6 }
- isxModularPduIdentMonitorCardFirmwareAppOSRev OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "An ID string identifying the application operating system firmware revision of the
- PDU monitor card."
- ::= { isxModularPduIdent 7 }
- -- the isxModularPduDevice group
- isxModularPduDeviceTransformerPresent OBJECT-TYPE
- SYNTAX INTEGER {
- notPresent (1),
- isoXfmrPresent (2),
- autoXfmrPresent (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Indicates the type of transformer present in this PDU."
- ::= { isxModularPduDevice 1 }
- isxModularPduDeviceServiceType OBJECT-TYPE
- SYNTAX INTEGER {
- delta (1),
- wye (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The type of utility input to the PDU. Either 3 wires (delta), or 4 wires (wye)."
- ::= { isxModularPduDevice 2 }
- isxModularPduDeviceFansPresent OBJECT-TYPE
- SYNTAX INTEGER {
- notPresent (1),
- present (2)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Indicates whether or not cooling fans are installed in the PDU."
- ::= { isxModularPduDevice 3 }
- isxModularPduDeviceNominalMainInputVoltage OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The nominal main input voltage to the system. Measured in Volts,
- line-to-line for a delta service or line-to-neutral for a wye service.
- -1 if main input voltage is not being measured."
- ::= { isxModularPduDevice 4 }
- isxModularPduAlarmStatus OBJECT-TYPE
- SYNTAX INTEGER {
- normal (1),
- warning (2),
- critical (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The overall status (worst case) of this PDU."
- ::= { isxModularPduStatus 1 }
- isxModularPduTransformerTempStatus OBJECT-TYPE
- SYNTAX INTEGER {
- normal (1),
- overtemp (2),
- noTransformerPresent (3),
- unknown (4)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Indicates if the PDU isolation transformer is over temperature."
- ::= { isxModularPduStatus 2 }
- isxModularPduFanStatus OBJECT-TYPE
- SYNTAX INTEGER {
- normal (1),
- failed (2),
- noCoolingFansPresent (3),
- unknown (4)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "Indicates if one or more of the PDU's cooling fans have failed."
- ::= { isxModularPduStatus 3 }
- -- Universal Input / Output (uio)
- -- uio Sensor Status Table
- uioSensorStatusTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the uioSensorStatusTable."
- ::= { uioSensor 1 }
- uioSensorStatusTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UIOSensorStatusEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting sensor status information."
- ::= { uioSensor 2 }
- uioSensorStatusEntry OBJECT-TYPE
- SYNTAX UIOSensorStatusEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The unit from which to get data."
- INDEX { uioSensorStatusPortID, uioSensorStatusSensorID }
- ::= { uioSensorStatusTable 1 }
- UIOSensorStatusEntry ::=
- SEQUENCE {
- uioSensorStatusPortID INTEGER,
- uioSensorStatusSensorID INTEGER,
- uioSensorStatusSensorName DisplayString,
- uioSensorStatusSensorLocation DisplayString,
- uioSensorStatusTemperatureDegF INTEGER,
- uioSensorStatusTemperatureDegC INTEGER,
- uioSensorStatusHumidity INTEGER,
- uioSensorStatusViolationStatus INTEGER,
- uioSensorStatusAlarmStatus INTEGER,
- uioSensorStatusCommStatus INTEGER
- }
- uioSensorStatusPortID OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The ID of the Universal IO port to which the sensor is attached."
- ::= { uioSensorStatusEntry 1 }
- uioSensorStatusSensorID OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The ID of the sensor."
- ::= { uioSensorStatusEntry 2 }
- uioSensorStatusSensorName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The sensor name."
- ::= { uioSensorStatusEntry 3 }
- uioSensorStatusSensorLocation OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The location of the sensor."
- ::= { uioSensorStatusEntry 4 }
- uioSensorStatusTemperatureDegF OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The sensor's current temperature reading in tenths of degrees Fahrenheit."
- ::= { uioSensorStatusEntry 5 }
- uioSensorStatusTemperatureDegC OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The sensor's current temperature reading in tenths of degrees Celsius."
- ::= { uioSensorStatusEntry 6 }
- uioSensorStatusHumidity OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The current humidity reading in tenths of percent from the sensor."
- ::= { uioSensorStatusEntry 7 }
- uioSensorStatusViolationStatus OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The violation status of the sensor. This integer should be interpreted
- as a bit map, with each bit representing the presence or absence of
- the specific alarm conditions listed below. The bit will be '1' if
- the condition is present, and '0' if the condition is not present.
-
- Bit Hex. Value Description
- 1 0x0001 Maximum temperature exceeded.
- 2 0x0002 High temperature exceeded.
- 3 0x0004 Low temperature exceeded.
- 4 0x0008 Minimum temperature exceeded.
- 5 0x0010 Short-term increasing temperature rate exceeded (Not used).
- 6 0x0020 Short-term decreasing temperature rate exceeded (Not used).
- 7 0x0040 Long-term increasing temperature rate exceeded (Not used).
- 8 0x0080 Long-term decreasing temperature rate exceeded (Not used).
- 9 0x0100 Maximum humidity exceeded.
- 10 0x0200 High humidity exceeded.
- 11 0x0400 Low humidity exceeded.
- 12 0x0800 Minimum humidity exceeded."
- ::= { uioSensorStatusEntry 8 }
- uioSensorStatusAlarmStatus OBJECT-TYPE
- SYNTAX INTEGER {
- uioNormal (1),
- uioWarning (2),
- uioCritical (3),
- sensorStatusNotApplicable (4)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The alarm status of the sensor."
- ::= { uioSensorStatusEntry 9 }
- uioSensorStatusCommStatus OBJECT-TYPE
- SYNTAX INTEGER {
- notInstalled (1),
- commsOK (2),
- commsLost (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The communications status of the sensor."
- ::= { uioSensorStatusEntry 10 }
- -- uio Input Contact Status Table
- uioInputContactStatusTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the uioInputContactStatusTable."
- ::= { uioInputContact 1 }
-
- uioInputContactStatusTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UIOInputContactStatusEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting input contact status information."
- ::= { uioInputContact 2 }
-
- uioInputContactStatusEntry OBJECT-TYPE
- SYNTAX UIOInputContactStatusEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The input contact from which to get data."
- INDEX { uioInputContactStatusPortID, uioInputContactStatusContactID }
- ::= { uioInputContactStatusTable 1 }
-
- UIOInputContactStatusEntry ::=
- SEQUENCE {
- uioInputContactStatusPortID INTEGER,
- uioInputContactStatusContactID INTEGER,
- uioInputContactStatusContactName DisplayString,
- uioInputContactStatusContactLocation DisplayString,
- uioInputContactStatusCurrentState INTEGER,
- uioInputContactStatusAlarmStatus INTEGER,
- uioInputContactStatusCommStatus INTEGER
- }
- uioInputContactStatusPortID OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The ID of the port to which the input contact is attached."
- ::= { uioInputContactStatusEntry 1 }
- uioInputContactStatusContactID OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The ID of the input contact on the module."
- ::= { uioInputContactStatusEntry 2 }
- uioInputContactStatusContactName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The input contact name."
- ::= { uioInputContactStatusEntry 3 }
- uioInputContactStatusContactLocation OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The location of the input contact."
- ::= { uioInputContactStatusEntry 4 }
- uioInputContactStatusCurrentState OBJECT-TYPE
- SYNTAX INTEGER {
- uioInputClosed (1),
- uioInputOpen (2),
- uioInputDisabled (3),
- inputStateNotApplicable (4)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The current state of the input contact. "
- ::= { uioInputContactStatusEntry 5 }
- uioInputContactStatusAlarmStatus OBJECT-TYPE
- SYNTAX INTEGER {
- uioNormal (1),
- uioWarning (2),
- uioCritical (3),
- inputStatusNotApplicable (4)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The alarm status of the input contact."
- ::= { uioInputContactStatusEntry 6 }
- uioInputContactStatusCommStatus OBJECT-TYPE
- SYNTAX INTEGER {
- notInstalled (1),
- commsOK (2),
- commsLost (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The communications status of the input contact."
- ::= { uioInputContactStatusEntry 7 }
- -- uio Output Relay Status Table
- uioOutputRelayStatusTableSize OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The number of entries in the uioOutputRelayStatusTable."
- ::= { uioOutputRelay 1 }
-
- uioOutputRelayStatusTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UIOOutputRelayStatusEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "Allows for getting output relay status information."
- ::= { uioOutputRelay 2 }
-
- uioOutputRelayStatusEntry OBJECT-TYPE
- SYNTAX UIOOutputRelayStatusEntry
- ACCESS not-accessible
- STATUS mandatory
- DESCRIPTION
- "The unit from which to get data."
- INDEX { uioOutputRelayStatusPortID, uioOutputRelayStatusRelayID }
- ::= { uioOutputRelayStatusTable 1 }
-
- UIOOutputRelayStatusEntry ::=
- SEQUENCE {
- uioOutputRelayStatusPortID INTEGER,
- uioOutputRelayStatusRelayID INTEGER,
- uioOutputRelayStatusRelayName DisplayString,
- uioOutputRelayStatusRelayLocation DisplayString,
- uioOutputRelayStatusCurrentState INTEGER,
- uioOutputRelayStatusAlarmStatus INTEGER,
- uioOutputRelayStatusCommStatus INTEGER
- }
- uioOutputRelayStatusPortID OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The ID of the module to which the output relay is attached."
- ::= { uioOutputRelayStatusEntry 1 }
- uioOutputRelayStatusRelayID OBJECT-TYPE
- SYNTAX INTEGER
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The ID of the output relay on the module."
- ::= { uioOutputRelayStatusEntry 2 }
- uioOutputRelayStatusRelayName OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The output relay name."
- ::= { uioOutputRelayStatusEntry 3 }
- uioOutputRelayStatusRelayLocation OBJECT-TYPE
- SYNTAX DisplayString
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The location of the output relay."
- ::= { uioOutputRelayStatusEntry 4 }
- uioOutputRelayStatusCurrentState OBJECT-TYPE
- SYNTAX INTEGER {
- uioOutputClosed (1),
- uioOutputOpen (2),
- outputStateNotApplicable (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The current state of the output relay."
- ::= { uioOutputRelayStatusEntry 5 }
- uioOutputRelayStatusAlarmStatus OBJECT-TYPE
- SYNTAX INTEGER {
- uioNormal (1),
- uioWarning (2),
- uioCritical (3),
- inputStatusNotApplicable (4)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The alarm status of the output relay."
- ::= { uioOutputRelayStatusEntry 6 }
- uioOutputRelayStatusCommStatus OBJECT-TYPE
- SYNTAX INTEGER {
- notInstalled (1),
- commsOK (2),
- commsLost (3)
- }
- ACCESS read-only
- STATUS mandatory
- DESCRIPTION
- "The communications status of the output relay."
- ::= { uioOutputRelayStatusEntry 7 }
- -- Traps
- -- Annotations are provided for Novell's NMS product
- --
- -- Each trap has at least one variable (mtrapargsString) which always appears
- -- as the last variable in the list. This variable contains either a static
- -- or dynamically-constructed string which provides an enhanced description of
- -- the trap's purpose and any pertinent information about the trap.
- communicationLost TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "SEVERE: Communication to the UPS has been lost. Steps
- to reestablish communication are in progress."
- --#TYPE "APC UPS: Communication lost"
- --#SUMMARY "Communication lost between the agent and the UPS."
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 1
- upsOverload TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "SEVERE: The UPS has sensed a load greater than 100 percent
- of its rated capacity."
- --#TYPE "APC UPS: Overload"
- --#SUMMARY "The UPS has sensed a load greater than 100 percent of its rated capacity."
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 2
- upsDiagnosticsFailed TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "SEVERE: The UPS failed its internal diagnostic self-test."
- --#TYPE "APC UPS: Failed self-test"
- --#SUMMARY "The UPS has failed its internal self-test."
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 3
- upsDischarged TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "SEVERE: The UPS batteries are discharged; if utility power fails
- an immediate low battery condition will exist. Sufficient runtime
- for necessary action cannot be guaranteed."
- --#TYPE "APC UPS: batteries are discharged"
- --#SUMMARY "The UPS batteries are discharged."
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 4
- upsOnBattery TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "WARNING: The UPS has switched to battery backup power."
- --#TYPE "APC UPS: On battery"
- --#SUMMARY "The UPS has switched to battery backup power."
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 5
- smartBoostOn TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "WARNING: The UPS has enabled SmartBoost(TM)."
- --#TYPE "APC UPS: SmartBoost(TM)"
- --#SUMMARY "The UPS has enabled SmartBoost(TM); low incoming line voltage."
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 6
- lowBattery TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "SEVERE: The UPS batteries are low and will soon be exhausted.
- If utility power is not restored the UPS will put itself
- to 'sleep' and immediately cut power to the load."
- --#TYPE "APC UPS: Low battery"
- --#SUMMARY "The UPS system's batteries are low and will soon be exhausted."
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 7
- communicationEstablished TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Communication with the UPS has been established."
- --#TYPE "APC UPS: Communication established"
- --#SUMMARY "UPS communication has been established."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 8
- powerRestored TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Utility power has been restored."
- --#TYPE "APC UPS: Utility power restored"
- --#SUMMARY "Returned from battery backup power; utility power restored."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 9
- upsDiagnosticsPassed TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The UPS passed its internal self-test."
- --#TYPE "APC UPS: Passed self-test"
- --#SUMMARY "The UPS passed internal self-test."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 10
- returnFromLowBattery TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The UPS has returned from a low battery
- condition."
- --#TYPE "APC UPS: Returned from Low-Battery condition"
- --#SUMMARY "The UPS has returned from a Low-Battery condition."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 11
- upsTurnedOff TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "WARNING: The UPS has been turned 'off' by the management station."
- --#TYPE "APC UPS: Turned off"
- --#SUMMARY "The UPS has been switched off by a management station."
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE NONOPERATIONAL
- ::= 12
- upsSleeping TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "WARNING: The UPS is entering 'sleep' mode. Power
- to the load will be cut off."
- --#TYPE "APC UPS: Entered sleep mode"
- --#SUMMARY "The UPS entered sleep mode. Power to the load will be cut off."
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE NONOPERATIONAL
- ::= 13
- upsWokeUp TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATION: The UPS has returned from 'sleep' mode. Power
- to the load has been restored."
- --#TYPE "APC UPS: Wake up"
- --#SUMMARY "The UPS has returned from sleep mode. Power to the load has been restored."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 14
- upsRebootStarted TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "WARNING: The UPS has started its reboot sequence.
- The UPS will reboot itself at this time."
- --#TYPE "APC UPS: Starting reboot"
- --#SUMMARY "The UPS has started its reboot sequence."
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE NONOPERATIONAL
- ::= 15
- upsDipSwitchChanged TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "WARNING: The dip switch settings on the UPS have been
- changed, possibly altering UPS performance."
- --#TYPE "APC UPS: DIP switch altered"
- --#SUMMARY "The DIP switch settings on the UPS have been changed."
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 16
- upsBatteryNeedsReplacement TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "SEVERE: The batteries of the UPS need immediate replacement."
- --#TYPE "APC UPS: UPS batteries need replacement"
- --#SUMMARY "The UPS batteries require immediate replacement."
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 17
- -- the Environmental Monitor traps
- contactFault TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "SEVERE: One of the contacts on the Environmental Monitor has
- changed from its default position. The first variable is
- the contact number that is faulted."
- --#TYPE "APC Environment: Contact fault"
- --#SUMMARY "An Environment contact closure has faulted."
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 18
- contactFaultResolved TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A fault on one of the Environmental Monitor contacts
- has been resolved. The first variable is
- the contact number that has been resolved."
- --#TYPE "APC Environment: Contact fault cleared."
- --#SUMMARY "A Environment contact closure has returned to it's default state."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 19
- -- the Matrix-UPS traps
- hardwareFailureBypass TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "SEVERE: UPS on bypass due to internal fault"
- --#TYPE "APC UPS: On bypass due to internal fault"
- --#SUMMARY "The UPS is on bypass due to an internal fault."
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 20
- softwareBypass TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "WARNING: UPS on bypass - user set via software or panel"
- --#TYPE "APC UPS: On bypass by user via software or panel"
- --#SUMMARY "UPS put on bypass by user via software or front UPS panel."
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 21
- switchedBypass TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "WARNING: UPS on bypass - initiated by user"
- --#TYPE "APC UPS: On bypass initiated by user"
- --#SUMMARY "UPS put on bypass by user."
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 22
- returnFromBypass TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: UPS has returned from bypass"
- --#TYPE "APC UPS: UPS has returned from bypass"
- --#SUMMARY "The UPS has returned from bypass mode."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 23
- bypassPowerSupplyFailure TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "SEVERE: Base module bypass power supply needs repair"
- --#TYPE "APC UPS: Base module bypass power supply needs repair"
- --#SUMMARY "The base module bypass power supply needs repair."
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE NONOPERATIONAL
- ::= 24
- baseFanFailure TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "SEVERE: Base module fan needs repair"
- --#TYPE "APC UPS: Base module fan needs repair"
- --#SUMMARY "The base module fan needs repair."
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE NONOPERATIONAL
- ::= 25
- batteryPackCommLost TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "SEVERE: Check installation of external battery packs signal cable"
- --#TYPE "APC UPS: Communication lost with battery packs"
- --#SUMMARY "Communication lost with external battery packs, check battery signal cable."
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 26
- batteryPackCommEstablished TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: UPS is communicating with the external battery packs."
- --#TYPE "APC UPS: Communication established with battery packs"
- --#SUMMARY "Communication established with external battery packs."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 27
- calibrationStart TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A battery calibration test has been initiated on the UPS."
- --#TYPE "APC UPS: Calibration initiated"
- --#SUMMARY "A battery run time calibration test has been initiated."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 28
- -- Misc. Traps
- restartAgent TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Agent restarting as commanded by manager."
- --#TYPE "APC SNMP Agent: Agent restarting"
- --#SUMMARY "Agent restarting as commanded by manager."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 29
- upsTurnedOn TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A UPS is turned on."
- --#TYPE "APC UPS: A UPS is turned on."
- --#SUMMARY " A UPS is turned on."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 30
- smartAvrReducing TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "WARNING: The UPS is reducing the line voltage via SmartTrim(TM)."
- --#TYPE "APC UPS: SmartTrim(TM) reducing"
- --#SUMMARY "The UPS has enabled SmartTrim(TM) voltage reduction."
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 31
- codeAuthenticationDone TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mconfigTFTPServerIP, newCodeAuthentViaTFTP }
- DESCRIPTION
- "INFORMATIONAL: Authentication on agent code image is done."
- --#TYPE "APC CODE: Authentication on agent code image is done."
- --#SUMMARY "Authentication on agent code image is done."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 32
- upsOverloadCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The overload condition has been cleared."
- --#TYPE "APC UPS: Overload cleared."
- --#SUMMARY "The overload condition has been cleared. ."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 33
- smartBoostOff TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The UPS has returned from SmartBoost(TM)."
- --#TYPE "APC UPS: SmartBoost(TM) off."
- --#SUMMARY "The UPS has returned from SmartBoost(TM)."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 34
- smartAvrReducingOff TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The UPS has returned from SmartTrim(TM)."
- --#TYPE "APC UPS: SmartTrim(TM) reducing off"
- --#SUMMARY "The UPS has returned from SmartTrim(TM) voltage reduction."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 35
-
- upsBatteryReplaced TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A bad battery fault has been cleared."
- --#TYPE "APC UPS: Bad battery replaced"
- --#SUMMARY "The UPS has returned from a bad battery fault."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 36
- calibrationEnd TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The UPS has finished calibrating."
- --#TYPE "APC UPS: Calibration end"
- --#SUMMARY "The UPS has finished calibrating"
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 37
- dischargeCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A UPS discharge condition has been cleared."
- --#TYPE "APC UPS: Discharge cleared."
- --#SUMMARY "The UPS discharge condition has been cleared."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 38
- gracefullShutdown TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A graceful shutdown has been initiated."
- --#TYPE "APC UPS: A graceful shutdown has been initiated."
- --#SUMMARY "A graceful shutdown has been initiated."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 39
-
- outletOn TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { sPDUOutletControlIndex }
- DESCRIPTION
- "WARNING: The specified PDU outlet has turned on.
- If sPDUOutletControlIndex equals zero, then all outlets have
- turned on."
- --#TYPE "APC PDU: Outlet has been turned on."
- --#SUMMARY "Outlet has been turned on"
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 41
-
- outletOff TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { sPDUOutletControlIndex }
- DESCRIPTION
- "WARNING: The specified PDU outlet has turned off.
- If sPDUOutletControlIndex equals zero, then all outlets
- have turned off."
- --#TYPE "APC PDU: Outlet has turned off."
- --#SUMMARY "Outlet has turned off."
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 42
-
- outletReboot TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { sPDUOutletControlIndex }
- DESCRIPTION
- "WARNING: The specified PDU outlet has rebooted.
- If sPDUOutletControlIndex equals zero, then all outlets
- have rebooted."
- --#TYPE "APC PDU: Outlet has rebooted."
- --#SUMMARY "Outlet has rebooted."
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 43
- configChangeSNMP TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "WARNING: The SNMP configuration has been changed."
- --#TYPE "APC: The SNMP configuration has been changed."
- --#SUMMARY "The SNMP configuration has been changed."
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 44
-
-
- configChangeOutlet TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { sPDUOutletConfigIndex }
- DESCRIPTION
- "WARNING: The specified PDU outlet has changed configuration.
- If sPDUOutletConfigIndex equals zero, then the Master outlet
- has changed configuration."
- --#TYPE "APC PDU: Outlet configuration has been changed."
- --#SUMMARY "Outlet configuration has been changed."
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 45
- accessViolationConsole TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "WARNING: Someone has attempted to login via the console with the incorrect password."
- --#TYPE "APC: Access violation via the console."
- --#SUMMARY "Three unsuccessful logins have been attempted via the console."
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 46
- accessViolationHTTP TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "WARNING: Someone has attempted to login via HTTP with the incorrect password."
- --#TYPE "APC: Access violation via HTTP."
- --#SUMMARY "An unsuccessful attempt to login via HTTP."
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 47
-
- passwordChange TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "WARNING: The password for the device has been changed."
- --#TYPE "APC: Password change for the device."
- --#SUMMARY "Someone has changed the password on the device."
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 48
- badVoltage TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "WARNING: The output voltage is not within acceptable range."
- --#TYPE "APC UPS: Bad output voltage."
- --#SUMMARY "The output voltage is not within acceptable range."
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 49
-
- badVoltageCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The output voltage has returned to an acceptable level."
- --#TYPE "APC UPS: The bad voltage output condition has been cleared."
- --#SUMMARY "The output voltage has returned to an acceptable level."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 50
-
- chargerFailure TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "WARNING: The battery charger has failed."
- --#TYPE "APC UPS: The battery charger has failed."
- --#SUMMARY "The battery charger has failed."
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 51
- chargerFailureCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The battery charger failure condition has been cleared."
- --#TYPE "APC UPS: The battery charger failure condition cleared"
- --#SUMMARY "The battery charger failure condition has been cleared."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 52
- batteryOverTemperature TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "WARNING: The battery temperature threshold has been violated."
- --#TYPE "APC UPS: The battery temperature threshold has been violated."
- --#SUMMARY "The battery temperature threshold has been violated."
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 53
- batteryOverTemperatureCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The battery over temperature has been cleared."
- --#TYPE "APC UPS: The battery over temperature has been cleared."
- --#SUMMARY "The battery over temperature has been cleared."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 54
-
- smartRelayFault TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "WARNING: SmartBoost(TM) or SmartTrim(TM) relay fault."
- --#TYPE "APC UPS: SmartBoost(TM) or SmartTrim(TM) relay fault."
- --#SUMMARY "SmartBoost(TM) or SmartTrim(TM) relay fault."
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 55
- smartRelayFaultCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: SmartBoost(TM) or SmartTrim(TM) relay fault has been cleared."
- --#TYPE "APC UPS: SmartBoost(TM) or SmartTrim(TM) relay fault cleared."
- --#SUMMARY "SmartBoost(TM) or SmartTrim(TM) relay fault has been cleared."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 56
-
- humidityThresholdViolation1 TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "SEVERE: Probe 1 humidity threshold violated. The
- first variable is the current humidity."
- --#TYPE "APC Environmental Monitor: Probe 1 humidity threshold violation"
- --#SUMMARY "A humidity threshold has been violated on probe 1."
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 57
- humidityThresholdViolationCleared1 TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: An Environmental Monitor humidity threshold violation has been cleared on probe 1."
- --#TYPE "APC Environmental Monitor: Probe 1 humidity violation cleared"
- --#SUMMARY "A humidity threshold violation has been cleared on probe 1."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 58
- temperatureThresholdViolation1 TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "SEVERE: An Environmental Monitor temperature threshold has been violated on probe 1.
- The first variable is the current temperature."
- --#TYPE "APC Environmental Monitor: Probe 1 temperature violation"
- --#SUMMARY "A temperature threshold has been violated on probe 1."
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 59
-
- temperatureThresholdViolationCleared1 TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: An Environmental Monitor temperature threshold violation has been cleared on probe 1."
- --#TYPE "APC Environmental Monitor: Probe 1 temperature violation cleared"
- --#SUMMARY "A temperature threshold violation has been cleared on probe 1."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 60
-
- humidityThresholdViolation2 TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "SEVERE: An Environmental Monitor humidity threshold has been violated on probe 2.
- The first variable is the current humidity."
- --#TYPE "APC Environmental Monitor: Probe 2 humidity violation"
- --#SUMMARY "A humidity threshold has been violated on probe 2."
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 61
-
- humidityThresholdViolationCleared2 TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: An Environmental Monitor humidity threshold violation has been cleared on probe 2."
- --#TYPE "APC Environmental Monitor: Probe 2 humidity violation cleared"
- --#SUMMARY "A humidity threshold violation has been cleared on probe 2."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 62
- temperatureThresholdViolation2 TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "SEVERE: An Environmental Monitor temperature threshold has been violated on probe 2.
- The first variable is the current temperature."
- --#TYPE "APC Environmental Monitor: Probe 2 temperature violation"
- --#SUMMARY "A temperature threshold has been violated on probe 2."
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 63
-
- temperatureThresholdViolationCleared2 TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: An Environmental Monitor temperature threshold violation has been cleared on probe 2."
- --#TYPE "APC Environmental Monitor: Probe 2 temperature violation cleared"
- --#SUMMARY "A temperature threshold violation has been cleared on probe 2."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 64
- mupsCommunicationEstablished TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Communication with the Environmental Monitor has been established."
- --#TYPE "APC Environmental Monitor: Communication established"
- --#SUMMARY "Communication established between the agent and the Environmental Monitor."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 65
- mupsCommunicationLost TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "SEVERE: Communication to the Environmental Monitor has been lost. Steps
- to reestablish communication are in progress."
- --#TYPE "APC Environmental Monitor: Communication failure"
- --#SUMMARY "Communication lost between the agent and the Environmental Monitor."
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 66
- batteryIncrease TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The number of batteries has increased."
- --#TYPE "APC UPS: The number of batteries has increased."
- --#SUMMARY "The number of batteries has increased."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 67
-
- batteryDecrease TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The number of batteries has decreased."
- --#TYPE "APC UPS: The number of batteries has decreased."
- --#SUMMARY "The number of batteries has decreased."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 68
-
- powerModuleIncrease TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The number of power modules has increased."
- --#TYPE "APC UPS: The number of power modules has increased."
- --#SUMMARY "The number of power modules has increased."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 69
- powerModuleDecrease TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The number of power modules has decreased."
- --#TYPE "APC UPS: The number of power modules has decreased."
- --#SUMMARY "The number of power modules has decreased."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 70
-
- intelligenceModuleInserted TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: An intelligence module has been inserted."
- --#TYPE "APC UPS: An intelligence module has been inserted."
- --#SUMMARY "An intelligence module has been inserted."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 71
- intelligenceModuleRemoved TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: An intelligence module has been removed."
- --#TYPE "APC UPS: An intelligence module has been removed."
- --#SUMMARY "An intelligence module has been removed."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 72
-
- rintelligenceModuleInserted TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A redundant intelligence module has been inserted."
- --#TYPE "APC UPS: A redundant intelligence module has been inserted."
- --#SUMMARY "A redundant intelligence module has been inserted."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 73
- rintelligenceModuleRemoved TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A redundant intelligence module has been removed."
- --#TYPE "APC UPS: A redundant intelligence module has been removed."
- --#SUMMARY "A redundant intelligence module has been removed."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 74
-
- extBatteryFrameIncease TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: An external battery frame has been added."
- --#TYPE "APC UPS: An external battery frame has been added."
- --#SUMMARY "An external battery frame has been added."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 75
- extBatteryFrameDecrease TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: An external battery frame has been removed."
- --#TYPE "APC UPS: An external battery frame has been removed."
- --#SUMMARY "An external battery frame has been removed."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 76
-
- abnormalCondition TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "SEVERE: An abnormal condition has been detected.
- The first variable is the fault condition."
- --#TYPE "APC: An abnormal condition has been detected."
- --#SUMMARY "An abnormal condition has been detected."
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 77
- abnormalConditionCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: An abnormal condition has been cleared.
- The first variable is the fault condition."
- --#TYPE "APC: An abnormal condition has been cleared."
- --#SUMMARY "An abnormal condition has been cleared."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 78
- deviceStatusChange TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString}
- DESCRIPTION
- "INFORMATIONAL: The status of the device being monitored has changed."
- --#TYPE "APC : The status of the device being monitored has changed."
- --#SUMMARY "The status of the device being monitored has changed."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 79
-
- noBatteries TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "WARNING: The UPS has no batteries attached."
- --#TYPE "APC UPS: No batteries attached."
- --#SUMMARY "The UPS has no batteries attached."
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 80
-
- noBatteriesCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The UPS's batteries have been attached."
- --#TYPE "APC UPS: The no batteries attached condition has been cleared."
- --#SUMMARY "The UPS's batteries have been attached."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 81
-
- userAdded TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A new user has been added."
- --#TYPE "APC: A new user has been added."
- --#SUMMARY "A new user has been added."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 82
- userDeleted TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A user has been deleted."
- --#TYPE "APC: A user has been deleted."
- --#SUMMARY "A user has been deleted."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 83
- userModified TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A user has been modified."
- --#TYPE "APC: A user has been modified."
- --#SUMMARY "A user has been modified."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 84
- -- MasterSwitch Vm Traps
- msvmCommunicationEstablished TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { sPDUMasterControlVMIndex, sPDUMasterControlVMName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Communications with the MasterSwitch VM has been established."
- --#TYPE "APC: Communications established with the MasterSwitch VM."
- --#SUMMARY "Communications with the MasterSwitch VM has been established."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 85
- msvmCommunicationLost TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { sPDUMasterControlVMIndex, sPDUMasterControlVMName, mtrapargsString }
- DESCRIPTION
- "SEVERE: Communications with the MasterSwitch VM has been lost."
- --#TYPE "APC: Communications lost with the MasterSwitch VM."
- --#SUMMARY "Communications with the MasterSwitch VM has been lost."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 86
- msvmOverload TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { sPDUMasterControlVMIndex, sPDUMasterControlVMName, mtrapargsString }
- DESCRIPTION
- "SEVERE: The MasterSwitch VM in an overload condition."
- --#TYPE "APC: The MasterSwitch VM is near or at an overload condition."
- --#SUMMARY "The MasterSwitch VM is near or at an overload condition."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 87
- msvmOverloadCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { sPDUMasterControlVMIndex, sPDUMasterControlVMName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The overload condition on the MasterSwitch VM has been cleared."
- --#TYPE "APC: The overload condition cleared on the MasterSwitch VM."
- --#SUMMARY "The overload condition on the MasterSwitch VM has been cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 88
- msvmOutletOn TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { sPDUMasterControlVMIndex, sPDUMasterControlVMName,
- sPDUOutletControlVMOutletIndex, sPDUOutletControlVMOutletName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: An outlet on the MasterSwitch VM has turned on."
- --#TYPE "APC: An outlet on the MasterSwitch VM has turned on."
- --#SUMMARY "An outlet on the MasterSwitch VM has turned on."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 89
- msvmOutletOff TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { sPDUMasterControlVMIndex, sPDUMasterControlVMName,
- sPDUOutletControlVMOutletIndex, sPDUOutletControlVMOutletName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: An outlet on the MasterSwitch VM has turned off."
- --#TYPE "APC: An outlet on the MasterSwitch VM has turned off."
- --#SUMMARY "An outlet on the MasterSwitch VM has turned off."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 90
- msvmDeviceConfigChange TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { sPDUMasterControlVMIndex, sPDUMasterControlVMName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A device configuration change has been made on a MasterSwitch VM."
- --#TYPE "APC: A device configuration change on a MasterSwitch VM."
- --#SUMMARY "A device configuration change has been made on a MasterSwitch VM."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 91
- msvmOutletConfigChange TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { sPDUMasterControlVMIndex, sPDUMasterControlVMName,
- sPDUOutletControlVMOutletIndex, sPDUOutletControlVMOutletName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: An outlet configuration change has been made on a MasterSwitch VM."
- --#TYPE "APC: An outlet configuration change on a MasterSwitch VM."
- --#SUMMARY "An outlet configuration change has been made on a MasterSwitch VM."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 92
- msvmLowLoad TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { sPDUMasterControlVMIndex, sPDUMasterControlVMName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The MasterSwitch VM has violated the low load threshold."
- --#TYPE "APC: The MasterSwitch VM has violated the low load threshold."
- --#SUMMARY "The MasterSwitch VM has violated the low load threshold."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 93
- msvmLowLoadCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { sPDUMasterControlVMIndex, sPDUMasterControlVMName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The low load condition on the MasterSwitch VM has been cleared."
- --#TYPE "APC: The low load condition cleared on the MasterSwitch VM."
- --#SUMMARY "The low load condition on the MasterSwitch VM has been cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 94
- msvmNearOverload TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { sPDUMasterControlVMIndex, sPDUMasterControlVMName, mtrapargsString }
- DESCRIPTION
- "SEVERE: The MasterSwitch VM is approaching an overload condition."
- --#TYPE "APC: The MasterSwitch VM is near or at an overload condition."
- --#SUMMARY "The MasterSwitch VM is near or at an overload condition."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 95
- msvmNearOverloadCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { sPDUMasterControlVMIndex, sPDUMasterControlVMName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The near overload condition on the MasterSwitch VM has been cleared."
- --#TYPE "APC: The overload condition cleared on the MasterSwitch VM."
- --#SUMMARY "The overload condition on the MasterSwitch VM has been cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 96
- msvmPowerSupplyStatusChange TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { sPDUMasterControlVMIndex, sPDUMasterControlVMName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "WARNING: The power supply status of the MasterSwitch VM has changed."
- --#TYPE "APC: The power supply status changed on MasterSwitch VM"
- --#SUMMARY "The power supply status of the MasterSwitch VM has changed."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 97
- -- MasterSwitch plus (MSP) Traps
- mspCommunicationEstablished TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { sPDUMasterControlMSPIndex, sPDUMasterControlMSPName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Communications with the MasterSwitch plus has been established."
- --#TYPE "APC: Communications established with the MasterSwitch plus."
- --#SUMMARY "Communications with the MasterSwitch plus has been established."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 98
- mspCommunicationLost TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { sPDUMasterControlMSPIndex, sPDUMasterControlMSPName, mtrapargsString }
- DESCRIPTION
- "SEVERE: Communications with the MasterSwitch plus has been lost."
- --#TYPE "APC: Communications lost with the MasterSwitch plus."
- --#SUMMARY "Communications with the MasterSwitch plus has been lost."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 99
- mspOutletOn TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { sPDUMasterControlMSPIndex, sPDUMasterControlMSPName,
- sPDUOutletControlMSPOutletIndex, sPDUOutletControlMSPOutletName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: An outlet on the MasterSwitch plus has turned on."
- --#TYPE "APC: An outlet on the MasterSwitch plus has turned on."
- --#SUMMARY "An outlet on the MasterSwitch plus has turned on."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 100
- mspOutletOff TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { sPDUMasterControlMSPIndex, sPDUMasterControlMSPName,
- sPDUOutletControlMSPOutletIndex, sPDUOutletControlMSPOutletName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: An outlet on the MasterSwitch plus has turned off."
- --#TYPE "APC: An outlet on the MasterSwitch plus has turned off."
- --#SUMMARY "An outlet on the MasterSwitch plus has turned off."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 101
- mspDeviceConfigChange TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { sPDUMasterControlMSPIndex, sPDUMasterControlMSPName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A device configuration change has been made on a MasterSwitch plus."
- --#TYPE "APC: A device configuration change on a MasterSwitch plus."
- --#SUMMARY "A device configuration change has been made on a MasterSwitch plus."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 102
- mspOutletConfigChange TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { sPDUMasterControlMSPIndex, sPDUMasterControlMSPName, sPDUOutletControlMSPOutletIndex, sPDUOutletControlMSPOutletName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: An outlet configuration change has been made on a MasterSwitch plus."
- --#TYPE "APC: An outlet configuration change on a MasterSwitch plus."
- --#SUMMARY "An outlet configuration change has been made on a MasterSwitch plus."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 103
- rsSourceSwitched TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsInteger02, mtrapargsString03, mtrapargsInteger, mtrapargsString02, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The Redundant Switch has switched source.
- The first variable is an integer representing the current source: 0=A, 1=B.
- The second variable is the 32-character name of the current source.
- The third variable is an integer representing the transfer cause:
- 0=No Transfers Recorded, 1=Due to user action or preferred switching,
- 3=Due to line notch or spike, 5=Due to low line voltage,
- 7=Transfer due to high line voltage,
- 9=Transfer due to frequency out of range.
- The fourth variable is a character string listing the transfer cause."
- --#TYPE "APC Redundant Switch: The Redundant Switch has switched source"
- --#SUMMARY "The Redundant Switch has switched source."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 104
- rsLostRedundancy TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsInteger, mtrapargsString02, mtrapargsString }
- DESCRIPTION
- "SEVERE: The Redundant Switch has lost redundancy.
- The first variable is an integer representing the source which is no longer available: 0=A, 1=B.
- The second variable is the 32-character name of the source which is no longer available."
- --#TYPE "APC Redundant Switch: The Redundant Switch has lost redundancy"
- --#SUMMARY "The Redundant Switch has lost redundancy."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 105
- rsRedundancyRestored TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsInteger, mtrapargsString02, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Redundancy has been restored to the Redundant Switch .
- The first variable is an integer representing the source which has been restored: 0=A, 1=B.
- The second variable is the 32-character name of the source which has been restored."
- --#TYPE "APC Redundant Switch: Redundancy has been restored."
- --#SUMMARY "Redundancy has been restored to the Redundant Switch ."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 106
- rsConfigChange TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A configuration change has been made on a Redundant Switch."
- --#TYPE "APC: A configuration change on a Redundant Switch."
- --#SUMMARY "A configuration change has been made on a Redundant Switch."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 107
- rsCommunicationEstablished TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Communications with the Redundant Switch has been established."
- --#TYPE "APC: Communications established with the Redundant Switch."
- --#SUMMARY "Communications with the Redundant Switch has been established."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 108
- rsCommunicationLost TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "SEVERE: Communications with the Redundant Switch has been lost."
- --#TYPE "APC: Communications lost with the Redundant Switch."
- --#SUMMARY "Communications with the Redundant Switch has been lost."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 109
- dcCommunicationEstablished TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Communications with the DC power plant has been established."
- --#TYPE "APC: Communications established with the DC power plant."
- --#SUMMARY "Communications with the DC power plant has been established."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 110
- dcCommunicationLost TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "SEVERE: Communications with the DC power plant has been lost."
- --#TYPE "APC: Communications lost with the DC power plant."
- --#SUMMARY "Communications with the DC power plant has been lost."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 111
- dcPINChanged TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The active PIN on the DC controller has been changed."
- --#TYPE "APC: The active PIN on the DC controller has been changed."
- --#SUMMARY "The active PIN on the DC controller has been changed."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 112
- dcMajorAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "SEVERE: A Major alarm is active in the DC power plant."
- --#TYPE "APC: A Major alarm is active in the DC power plant."
- --#SUMMARY "A Major alarm is active in the DC power plant."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 113
-
- dcMajorAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A Major alarm is no longer active in the DC power plant."
- --#TYPE "APC: A Major alarm is no longer active in the DC power plant."
- --#SUMMARY "A Major alarm is no longer active in the DC power plant."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 114
- dcMinorAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "WARNING: A Minor alarm is active in the DC power plant."
- --#TYPE "APC: A Minor alarm is active in the DC power plant."
- --#SUMMARY "A Minor alarm is active in the DC power plant."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 115
-
- dcMinorAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A Minor alarm is no longer active in the DC power plant."
- --#TYPE "APC: A Minor alarm is no longer active in the DC power plant."
- --#SUMMARY "A Minor alarm is no longer active in the DC power plant."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 116
- dcOutputRelayOn TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { dm3StatusOutRlyIndex, dm3StatusOutRlyName, mtrapargsString }
- DESCRIPTION
- "WARNING: An output relay for the powerplant has been activated (state changed to on).
- The first variable is an integer representing the output relay number that has gone on.
- The second variable is the 16-character name of the output relay."
- --#TYPE "APC: An output relay has gone on."
- --#SUMMARY "An output relay has gone on in the DC power plant."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 117
- dcOutputRelayOff TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { dm3StatusOutRlyIndex, dm3StatusOutRlyName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: An output relay for the powerplant has been deactivated (state changed to off).
- The first variable is an integer representing the output relay number that has gone off.
- The second variable is the 16-character name of the output relay."
- --#TYPE "APC: An output relay has gone off."
- --#SUMMARY "An output relay has gone off in the DC power plant."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 118
- dcInputRelayOn TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { dm3StatusInRlyIndex, dm3StatusInRlyName, mtrapargsString }
- DESCRIPTION
- "WARNING: An input relay for the powerplant has been activated (state changed to on).
- The first variable is an integer representing the input relay number that has gone on.
- The second variable is the 16-character name of the input relay."
- --#TYPE "APC: An input relay has gone on."
- --#SUMMARY "An input relay has gone on in the DC power plant."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 119
- dcInputRelayOff TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { dm3StatusInRlyIndex, dm3StatusInRlyName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: An input relay for the powerplant has been deactivated (state changed to off).
- The first variable is an integer representing the input relay number that has gone off.
- The second variable is the 16-character name of the input relay."
- --#TYPE "APC: An input relay has gone off."
- --#SUMMARY "An input relay has gone off in the DC power plant."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 120
- logicPowerSuppliesIncreased TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The number of system power supplies has increased."
- --#TYPE "APC UPS: The number of system power supplies has increased."
- --#SUMMARY "The number of system power supplies has increased."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 121
- logicPowerSuppliesDecreased TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The number of system power supplies has decreased."
- --#TYPE "APC UPS: The number of system power supplies has decreased."
- --#SUMMARY "The number of system power supplies has decreased."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 122
- externalSwitchGearClosed TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: External Switch Gear closed."
- --#TYPE "APC UPS: External Switch Gear closed."
- --#SUMMARY "External Switch Gear closed."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 123
- externalSwitchGearOpened TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: External Switch Gear opened."
- --#TYPE "APC UPS: External Switch Gear opened."
- --#SUMMARY "External Switch Gear opened."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 124
- generalDeviceEvent TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: APC Device event."
- --#TYPE "APC Device event"
- --#SUMMARY "APC Device event."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 125
- atsSourceSwitched TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsInteger, mtrapargsString02, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The Automatic Transfer Switch has switched source.
- The first variable is an integer representing the current source: 0=A, 1=B.
- The second variable is the 32-character name of the current source."
- --#TYPE "APC Automatic Transfer Switch: The ATS has switched source"
- --#SUMMARY "The Automatic Transfer Switch has switched source."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 126
- atsLostRedundancy TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsInteger, mtrapargsString02, mtrapargsString }
- DESCRIPTION
- "SEVERE: The Automatic Transfer Switch has lost redundancy.
- The first variable is an integer representing the source which is no longer available: 0=A, 1=B.
- The second variable is the 32-character name of the source which is no longer available."
- --#TYPE "APC Automatic Transfer Switch: The ATS has lost redundancy. "
- --#SUMMARY "The Automatic Transfer Switch has lost redundancy."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 127
- atsRedundancyRestored TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsInteger, mtrapargsString02, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Redundancy has been restored to the Automatic Transfer Switch .
- The first variable is an integer representing the source which has been restored: 0=A, 1=B.
- The second variable is the 32-character name of the source which has been restored."
- --#TYPE "APC Automatic Transfer Switch: Redundancy has been restored."
- --#SUMMARY "Redundancy has been restored to the Automatic Transfer Switch ."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 128
- atsConfigChange TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A configuration change has been made on the Automatic Transfer Switch.
- The first variable is an integer representing the configuration setting which changed:
- 0=Transfer Voltage Range, 1=Sensitivity, 2=Preferred Source
- 3=Front Panel Lockout, 4=Current Limit, 5=Reset XA Processor,
- 6=Reset to defaults, 7=Product Name, 8=Nominal Voltage, 9=Nominal Line Frequency,
- 10=Narrow VRMS, 11=Medium VRMS, 12=Wide VRMS,13=Frequency Deviation,
- 14=ColdStart ATS, 15=Events Count Cleared, 16=Phase or Bank Threshold. "
- --#TYPE "APC Automatic Transfer Switch: ATS configuration changed."
- --#SUMMARY "A configuration change has been made on a Automatic Transfer Switch."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 129
- atsCommunicationEstablished TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Communications with the Automatic Transfer Switch has been established."
- --#TYPE "APC Automatic Transfer Switch: Communications established."
- --#SUMMARY "Communications with the Automatic Transfer Switch has been established."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 130
- atsCommunicationLost TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "SEVERE: Communications with the Automatic Transfer Switch has been lost."
- --#TYPE "APC Automatic Transfer Switch: Communications lost."
- --#SUMMARY "Communications with the Automatic Transfer Switch has been lost."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 131
- atsOverCurrent TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "SEVERE: Output Current has exceeded threshold. This is same as atsOverload Trap
- for phase or total in case banked units"
-
- --#TYPE "APC Automatic Transfer Switch: Output Current exceeded threshold"
- --#SUMMARY "Output Current has exceeded Threshold. "
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 132
- atsOverCurrentCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Output Current has returned below threshold.This is same as atsOverloadCleared Trap
- for phase or total in case banked units"
- --#TYPE "APC Automatic Transfer Switch: Output Current below threshold."
- --#SUMMARY "Output Current has returned below threshold."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 133
- atsPowerSupplyFailure TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "SEVERE: The Automatic Transfer Switch Power Supply has failed.
- The first variable is an integer representing the Power Supply which
- has failed: 0 = Source A 24V,
- 1 = 12V,
- 2 = 5V,
- 3 = Source B 24V."
- --#TYPE "APC Automatic Transfer Switch: The ATS Power Supply has failed."
- --#SUMMARY "The Automatic Transfer Switch Power Supply has failed."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 134
- atsPowerSupplyFailureCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The Automatic Transfer Power Supply Failure Cleared.
- The first variable is an integer representing the Power Supply which
- has cleared: 0 = Source A 24V,
- 1 = 12V,
- 2 = 5V,
- 3 = Source B 24V."
- --#TYPE "APC Automatic Transfer Switch: Power Supply Failure Cleared."
- --#SUMMARY "The Automatic Transfer Switch Power Supply Failure Cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 135
- dcMainsFailAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "WARNING: A Mains Fail alarm is active in the DC power plant."
- --#TYPE "APC: A Mains Fail alarm is active in the DC power plant."
- --#SUMMARY "A Mains Fail alarm is active in the DC power plant."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 136
-
- dcMainsFailAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Mains Fail alarm is no longer active in the DC power plant."
- --#TYPE "APC: Mains Fail alarm is no longer active in the DC power plant."
- --#SUMMARY "Mains Fail alarm is no longer active in the DC power plant."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 137
- dcFanFailAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "WARNING: A Fan Fail alarm is active in the DC power plant."
- --#TYPE "APC: A Fan Fail alarm is active in the DC power plant."
- --#SUMMARY "A Fan Fail alarm is active in the DC power plant."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 138
-
- dcFanFailAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A Fan Fail alarm is no longer active in the DC power plant."
- --#TYPE "APC: A Fan Fail alarm is no longer active in the DC power plant."
- --#SUMMARY "A Fan Fail alarm is no longer active in the DC power plant."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 139
- dcRectifierOvertempAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "WARNING: Rect. Overtemp alarm is active in the power plant."
- --#TYPE "APC: Rect. Overtemp alarm is active in the power plant."
- --#SUMMARY "Rect. Overtemp alarm is active in the power plant."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 140
-
- dcRectifierOvertempAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Rect. Overtemp alarm is no longer active in the power plant."
- --#TYPE "APC: Rect. Overtmp alarm is no longer active in the power plant."
- --#SUMMARY "Rect. Overtemp alarm is no longer active in the power plant."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 141
- dcCurrentLimitAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "WARNING: A Current Limit alarm is active in the power plant."
- --#TYPE "APC: A Current Limit alarm is active in the power plant."
- --#SUMMARY "A Current Limit alarm is active in the power plant."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 142
-
- dcCurrentLimitAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Current Limit alarm is no longer active in the power plant."
- --#TYPE "APC: Current Limit alarm is no longer active in the power plant."
- --#SUMMARY "Current Limit alarm is no longer active in the power plant."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 143
- dcRectifierFailAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "WARNING: A Rect. Fail alarm is active in the power plant."
- --#TYPE "APC: A Rect. Fail alarm is active in the power plant."
- --#SUMMARY "A Rect. Fail alarm is active in the power plant."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 144
-
- dcRectifierFailAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Rect. Fail alarm is no longer active in the power plant."
- --#TYPE "APC: Rect. Fail alarm is no longer active in the power plant."
- --#SUMMARY "Rect. Fail alarm is no longer active in the power plant."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 145
- dcMultRectFailAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "WARNING: Multiple Rect. Fail alarm is active in the powerplant."
- --#TYPE "APC: Multiple Rect. Fail alarm is active in the powerplant."
- --#SUMMARY "Multiple Rect. Fail alarm is active in the powerplant."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 146
-
- dcMultRectFailAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Multiple Rect Fail alarm is no longer active in the powerplant."
- --#TYPE "APC: Multiple Rect Fail alarm is no longer active in powerplant."
- --#SUMMARY "Multiple Rect Fail alarm is no longer active in the powerplant."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 147
- dcBatteryBreakerAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "WARNING: Batt. Breaker alarm is active in the power plant."
- --#TYPE "APC: Batt. Breaker alarm is active in the power plant."
- --#SUMMARY "Batt. Breaker alarm is active in the power plant."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 148
-
- dcBatteryBreakerAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Batt. Breaker alarm is no longer active in the power plant."
- --#TYPE "APC: Batt. Breaker alarm is no longer active in the power plant."
- --#SUMMARY "Batt. Breaker alarm is no longer active in the power plant."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 149
- dcRectifierOVPAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "WARNING: A Rect. OVP alarm is active in the power plant."
- --#TYPE "APC: A Rect. OVP alarm is active in the power plant."
- --#SUMMARY "A Rect. OVP alarm is active in the power plant."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 150
-
- dcRectifierOVPAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A Rect. OVP alarm is no longer active in the power plant."
- --#TYPE "APC: A Rect. OVP alarm is no longer active in the power plant."
- --#SUMMARY "A Rect. OVP alarm is no longer active in the power plant."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 151
- dcLVDImminentAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "WARNING: A LVD Imminent alarm is active in the powerplant."
- --#TYPE "APC: A LVD Imminent alarm is active in the powerplant."
- --#SUMMARY "A LVD Imminent alarm is active in the powerplant."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 152
-
- dcLVDImminentAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A LVD Imminent alarm is no longer active in the powerplant."
- --#TYPE "APC: A LVD Imminent alarm is no longer active in the powerplant."
- --#SUMMARY "A LVD Imminent alarm is no longer active in the powerplant."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 153
- dcFuseCBAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "WARNING: A Fuse/CB alarm is active in the DC power plant."
- --#TYPE "APC: A Fuse/CB alarm is active in the DC power plant."
- --#SUMMARY "A Fuse/CB alarm is active in the DC power plant."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 154
-
- dcFuseCBAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A Fuse/CB alarm is no longer active in the DC power plant."
- --#TYPE "APC: A Fuse/CB alarm is no longer active in the DC power plant."
- --#SUMMARY "A Fuse/CB alarm is no longer active in the DC power plant."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 155
- dcBatteryTestFail TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "WARNING: A Battery Test failed in the DC power plant."
- --#TYPE "APC: A Battery Test failed in the DC power plant."
- --#SUMMARY "A Battery Test failed in the DC power plant."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 156
- dcTemperatureAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "WARNING: A Temperature is active in the power plant."
- --#TYPE "APC: A Temperature alarm is active in the power plant."
- --#SUMMARY "A Temperature alarm is active in the power plant."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 157
-
- dcTemperatureAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A Temperature alarm is no longer active in the power plant."
- --#TYPE "APC: A Temperature alarm is no longer active in the power plant."
- --#SUMMARY "A Temperature alarm is no longer active in the power plant."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 158
- dcHumidityAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "WARNING: A Humidity alarm is active in the DC power plant."
- --#TYPE "APC: A Humidity alarm is active in the DC power plant."
- --#SUMMARY "A Humidity alarm is active in the DC power plant."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 159
-
- dcHumidityAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A Humidity alarm is no longer active in the DC power plant."
- --#TYPE "APC: A Humidity alarm is no longer active in the DC power plant."
- --#SUMMARY "A Humidity alarm is no longer active in the DC power plant."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 160
- dcBBCommunicationEstablished TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Power plant bridging board communications established."
- --#TYPE "APC: Power plant bridging board communications established."
- --#SUMMARY "Power plant bridging board communications established."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 161
- dcBBCommunicationLost TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "SEVERE: Power plant bridging board communications lost."
- --#TYPE "APC: Power plant bridging board communications lost."
- --#SUMMARY "Power plant bridging board communications lost."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 162
- iemHighTempThresholdViolation TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { iemStatusProbeCurrentTemp, iemStatusProbeTempUnits, iemStatusProbeNumber,
- iemStatusProbeName, mtrapargsString }
- DESCRIPTION
- "SEVERE: High temperature threshold violated on Integrated
- Environmental Monitor probe. The first variable is the
- current temperature. The second variable is the temperature
- scale. The third variable is the probe number. The fourth
- variable is the probe name."
- --#TYPE "APC IEM: High temperature threshold violation."
- --#SUMMARY "High temperature threshold violation."
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 163
- iemHighTempThresholdViolationCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { iemStatusProbeNumber, iemStatusProbeName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: High temperature threshold violated on Integrated
- Environmental Monitor probe has been cleared. The first variable
- is the probe number. The second variable is the probe name."
- --#TYPE "APC IEM: High temperature threshold violation cleared."
- --#SUMMARY "High temperature threshold violation has been cleared."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 164
- iemLowTempThresholdViolation TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { iemStatusProbeCurrentTemp, iemStatusProbeTempUnits, iemStatusProbeNumber,
- iemStatusProbeName, mtrapargsString }
- DESCRIPTION
- "SEVERE: Low temperature threshold violated on integrated
- probe. The first variable is the current temperature. The
- second variable is the temperature scale. The third
- variable is the probe number. The fourth variable is the
- probe name."
- --#TYPE "APC IEM: Low temperature threshold violation."
- --#SUMMARY "Low temperature threshold violation."
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 165
- iemLowTempThresholdViolationCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { iemStatusProbeNumber, iemStatusProbeName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Low temperature threshold violated on integrated
- probe has been cleared. The first variable is the probe number.
- The second variable is the probe name."
- --#TYPE "APC IEM: Low temperature threshold violation cleared."
- --#SUMMARY "Low temperature threshold violation has been cleared."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 166
- iemHighHumidThresholdViolation TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { iemStatusProbeCurrentHumid, iemStatusProbeNumber, iemStatusProbeName,
- mtrapargsString }
- DESCRIPTION
- "SEVERE: High humidity threshold violated on integrated
- probe. The first variable is the current humidity. The
- second variable is the probe number. The third variable
- is the probe name."
- --#TYPE "APC IEM: High humidity threshold violation."
- --#SUMMARY "High humidity threshold violation."
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 167
- iemHighHumidThresholdViolationCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { iemStatusProbeNumber, iemStatusProbeName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: High humidity threshold violated on integrated
- probe cleared. The first variable is the probe number. The second
- variable is the probe name."
- --#TYPE "APC IEM: High humidity threshold violation cleared."
- --#SUMMARY "High humidity threshold violation has been cleared."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 168
- iemLowHumidThresholdViolation TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { iemStatusProbeCurrentHumid, iemStatusProbeNumber, iemStatusProbeName,
- mtrapargsString }
- DESCRIPTION
- "SEVERE: Low humidity threshold violated on integrated
- probe. The first variable is the current humidity. The
- second variable is the probe number. The third variable
- is the probe name."
- --#TYPE "APC IEM: Low humidity threshold violation."
- --#SUMMARY "Low humidity threshold violation."
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 169
- iemLowHumidThresholdViolationCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { iemStatusProbeNumber, iemStatusProbeName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Low humidity threshold violated on integrated
- probe cleared. The first variable is the probe number. The second
- variable is the probe name."
- --#TYPE "APC IEM: Low humidity threshold violation cleared."
- --#SUMMARY "Low humidity threshold violation has been cleared."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 170
- iemProbeDisconnected TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "WARNING: The temperature/humidity probe on the Integrated
- Environmental Monitor has been disconnected. This trap is
- generated when a probe that has been in communication with
- the Environmental Monitor has been disconnected or can no
- longer communicate."
- --#TYPE "APC IEM: Probe disconnected."
- --#SUMMARY "Probe has been disconnected."
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 171
- iemProbeConnected TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The temperature/humidity probe on the Integrated
- Environmental Monitor has been connected. This trap is generated
- when the Environmental Monitor establishes communication with a
- probe that had previously not been connected."
- --#TYPE "APC IEM: Probe Connected."
- --#SUMMARY "Probe has been connected."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 172
- iemContactFault TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { iemStatusContactNumber, iemStatusContactName, mtrapargsString }
- DESCRIPTION
- "SEVERE: There is a contact fault on the Integrated
- Environmental Monitor. The first argument is the number
- of the contact. The second argument is the name of the
- contact."
- --#TYPE "APC IEM: Contact fault."
- --#SUMMARY "Contact fault."
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 173
- iemContactFaultCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { iemStatusContactNumber, iemStatusContactName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The contact fault on the Integrated
- Environmental Monitor has been cleared. The first
- argument is the number of the contact. The second
- argument is the name of the contact."
- --#TYPE "APC IEM: Contact fault."
- --#SUMMARY "Contact fault cleared."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 174
- iemRelayFault TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { iemStatusRelayNumber, iemStatusRelayName, mtrapargsString02, mtrapargsString }
- DESCRIPTION
- "SEVERE: The output relay on the Integrated Environmental
- Monitor has switched to the fault state. The first
- argument is the number of the output relay. The second
- argument is the name of the output relay. The third
- argument is the event that caused the fault."
- --#TYPE "APC IEM: Output relay fault."
- --#SUMMARY "Output relay has faulted."
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 175
- iemRelayFaultCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { iemStatusRelayNumber, iemStatusRelayName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The fault condition on the output relay on the
- Integrated Environmental Monitor has cleared. The first
- argument is the number of the output relay. The second
- argument is the name of the output relay."
- --#TYPE "APC IEM: Output relay fault condition cleared."
- --#SUMMARY "Output relay fault cleared."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 176
- bmBatManCommEstab TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Serial Communications Established with Battery Manager."
- --#TYPE "BatMan : Communications Established."
- --#SUMMARY "Communications Established."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 177
- bmBatManCommLost TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "SEVERE: Serial Communications Lost with Battery Manager."
- --#TYPE "BatMan : Communications Lost."
- --#SUMMARY "Communications Lost."
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 178
- bmBatManKneeAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "SEVERE: Battery Voltage Knee Threshold Alarm Detected."
- --#TYPE "BatMan : Knee Alarm Detected."
- --#SUMMARY "Knee Alarm Detected."
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 179
- bmBatManKneeAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Battery Voltage Knee Threshold Alarm Cleared."
- --#TYPE "BatMan : Knee Alarm Cleared."
- --#SUMMARY "Knee Alarm Cleared."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 180
- bmBatManChargerAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "WARNING: Charger Alarm Detected."
- --#TYPE "BatMan : Charger Alarm Detected."
- --#SUMMARY "Charger Alarm Detected."
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 181
- bmBatManChargerAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Charger Alarm Cleared."
- --#TYPE "BatMan : Charger Alarm Cleared."
- --#SUMMARY "Charger Alarm Cleared."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 182
- bmBatManBatteryAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "WARNING: Battery Alarm Detected."
- --#TYPE "BatMan : Battery Alarm Detected."
- --#SUMMARY "Battery Alarm Detected."
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 183
- bmBatManBatteryAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Battery Alarm Cleared."
- --#TYPE "BatMan : Battery Alarm Cleared."
- --#SUMMARY "Battery Alarm Cleared."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 184
- bmBatManEnvironmentAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "WARNING: Environment Alarm Detected."
- --#TYPE "BatMan : Environment Alarm Detected."
- --#SUMMARY "Environment Alarm Detected."
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 185
- bmBatManEnvironmentAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Environment Alarm Cleared."
- --#TYPE "BatMan : Environment Alarm Cleared."
- --#SUMMARY "Environment Alarm Cleared."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 186
- bmBatManMaintenanceAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Maintenance Alarm Detected."
- --#TYPE "BatMan : Maintenance Due Alarm Detected."
- --#SUMMARY "Maintenance Due Alarm Detected."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 187
- bmBatManMaintenanceAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Maintenance Alarm Cleared."
- --#TYPE "BatMan : Maintenance Due Alarm Cleared."
- --#SUMMARY "Maintenance Due Alarm Cleared."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 188
- pduCommunicationEstablished TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Communication Established.
- The first argument is the serial number.
- The second argument is the device name."
- --#TYPE "APC PDU: Communication Established."
- --#SUMMARY "Communication Established."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 189
- pduCommunicationLost TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsString }
- DESCRIPTION
- "SEVERE: Communication Lost.
- The first argument is the serial number.
- The second argument is the device name."
- --#TYPE "APC PDU: Communication Lost."
- --#SUMMARY "Communication Lost."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 190
- pduUtilityLineUndervoltage TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "SEVERE: Utility Line Undervoltage.
- The first argument is the serial number.
- The second argument is the device name.
- The third argument is the phase number."
- --#TYPE "APC PDU: Utility Line Undervoltage."
- --#SUMMARY "Utility Line Undervoltage."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 191
- pduUtilityLineUndervoltageCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Utility Line Undervoltage Cleared.
- The first argument is the serial number.
- The second argument is the device name.
- The third argument is the phase number."
- --#TYPE "APC PDU: Utility Line Undervoltage Cleared."
- --#SUMMARY "Utility Line Undervoltage Cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 192
- pduUtilityLineOvervoltage TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "SEVERE: Utility Line Overvoltage.
- The first argument is the serial number.
- The second argument is the device name.
- The third argument is the phase number."
- --#TYPE "APC PDU: Utility Line Overvoltage."
- --#SUMMARY "Utility Line Overvoltage."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 193
- pduUtilityLineOvervoltageCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Utility Line Overvoltage Cleared.
- The first argument is the serial number.
- The second argument is the device name.
- The third argument is the phase number."
- --#TYPE "APC PDU: Utility Line Overvoltage Cleared."
- --#SUMMARY "Utility Line Overvoltage Cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 194
- pduGroundOvercurrent TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsString }
- DESCRIPTION
- "SEVERE: Ground Overcurrent.
- The first argument is the serial number.
- The second argument is the device name."
- --#TYPE "APC PDU: Ground Overcurrent."
- --#SUMMARY "Ground Overcurrent."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 195
- pduGroundOvercurrentCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Ground Overcurrent Cleared.
- The first argument is the serial number.
- The second argument is the device name."
- --#TYPE "APC PDU: Ground Overcurrent Cleared."
- --#SUMMARY "Ground Overcurrent Cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 196
- pduCircuitPanelInputUndervoltage TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "SEVERE: Circuit Panel Input Undervoltage.
- The first argument is the serial number.
- The second argument is the device name.
- The third argument is the phase number."
- --#TYPE "APC PDU: Circuit Panel Input Undervoltage."
- --#SUMMARY "Circuit Panel Input Undervoltage."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 197
- pduCircuitPanelInputUndervoltageCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Circuit Panel Input Undervoltage Cleared.
- The first argument is the serial number.
- The second argument is the device name.
- The third argument is the phase number."
- --#TYPE "APC PDU: Circuit Panel Input Undervoltage Cleared."
- --#SUMMARY "Circuit Panel Input Undervoltage Cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 198
- pduCircuitPanelInputOvervoltage TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "SEVERE: Circuit Panel Input Overvoltage.
- The first argument is the serial number.
- The second argument is the device name.
- The third argument is the phase number."
- --#TYPE "APC PDU: Circuit Panel Input Overvoltage."
- --#SUMMARY "Circuit Panel Input Overvoltage."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 199
- pduCircuitPanelInputOvervoltageCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Circuit Panel Input Overvoltage Cleared.
- The first argument is the serial number.
- The second argument is the device name.
- The third argument is the phase number."
- --#TYPE "APC PDU: Circuit Panel Input Overvoltage Cleared."
- --#SUMMARY "Circuit Panel Input Overvoltage Cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 200
- pduCircuitPanelInputUndercurrent TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "SEVERE: Circuit Panel Input Undercurrent.
- The first argument is the serial number.
- The second argument is the device name.
- The third argument is the phase number."
- --#TYPE "APC PDU: Circuit Panel Input Undercurrent."
- --#SUMMARY "Circuit Panel Input Undercurrent."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 201
- pduCircuitPanelInputUndercurrentCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Circuit Panel Input Undercurrent Cleared.
- The first argument is the serial number.
- The second argument is the device name.
- The third argument is the phase number."
- --#TYPE "APC PDU: Circuit Panel Input Undercurrent Cleared."
- --#SUMMARY "Circuit Panel Input Undercurrent Cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 202
- pduCircuitPanelInputOvercurrent TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "SEVERE: Circuit Panel Input Overcurrent.
- The first argument is the serial number.
- The second argument is the device name.
- The third argument is the phase number."
- --#TYPE "APC PDU: Circuit Panel Input Overcurrent."
- --#SUMMARY "Circuit Panel Input Overcurrent."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 203
- pduCircuitPanelInputOvercurrentCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Circuit Panel Input Overcurrent Cleared.
- The first argument is the serial number.
- The second argument is the device name.
- The third argument is the phase number."
- --#TYPE "APC PDU: Circuit Panel Input Overcurrent Cleared."
- --#SUMMARY "Circuit Panel Input Overcurrent Cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 204
- pduCircuitPanelFrequencyOutOfRange TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsString }
- DESCRIPTION
- "SEVERE: Circuit Panel Input Frequency Out Of Range.
- The first argument is the serial number.
- The second argument is the device name."
- --#TYPE "APC PDU: Circuit Panel Input Frequency Out Of Range."
- --#SUMMARY "Circuit Panel Input Frequency Out Of Range."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 205
- pduCircuitPanelFrequencyOutofRangeCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Circuit Panel Input Frequency No Longer Out Of Range.
- The first argument is the serial number.
- The second argument is the device name."
- --#TYPE "APC PDU: Circuit Panel Input Frequency No Longer Out Of Range."
- --#SUMMARY "Circuit Panel Input Frequency No Longer Out Of Range."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 206
- pduCircuitPanelNeutralOvercurrent TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsString }
- DESCRIPTION
- "SEVERE: Circuit Panel Input Neutral Overcurrent.
- The first argument is the serial number.
- The second argument is the device name."
- --#TYPE "APC PDU: Circuit Panel Input Neutral Overcurrent."
- --#SUMMARY "Circuit Panel Input Neutral Overcurrent."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 207
- pduCircuitPanelNeutralOvercurrentCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Circuit Panel Input Neutral Overcurrent Cleared.
- The first argument is the serial number.
- The second argument is the device name."
- --#TYPE "APC PDU: Circuit Panel Input Neutral Overcurrent Cleared."
- --#SUMMARY "Circuit Panel Input Neutral Overcurrent Cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 208
- pduSystemOff TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsString }
- DESCRIPTION
- "SEVERE: PDU System Off.
- The first argument is the serial number.
- The second argument is the device name."
- --#TYPE "APC PDU: System Off."
- --#SUMMARY "PDU System Off."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 209
- pduOnBatteryMode TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsString }
- DESCRIPTION
- "SEVERE: PDU is in On Battery Mode.
- The first argument is the serial number.
- The second argument is the device name."
- --#TYPE "APC PDU: On Battery Mode."
- --#SUMMARY "PDU is in On Battery Mode."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 210
- pduMaintenanceBypassMode TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: PDU is in Maintenance Bypass Mode.
- The first argument is the serial number.
- The second argument is the device name."
- --#TYPE "APC PDU: Maintenance Bypass Mode."
- --#SUMMARY "PDU is in Maintenance Bypass Mode."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 211
- pduAtypicalBypassMode TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsString }
- DESCRIPTION
- "WARNING: PDU is in Atypical Bypass Mode.
- The first argument is the serial number.
- The second argument is the device name."
- --#TYPE "APC PDU: Atypical Bypass Mode."
- --#SUMMARY "PDU is in Atypical Bypass Mode."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 212
- pduNoPanelFeedMode TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsString }
- DESCRIPTION
- "SEVERE: PDU is in No Panel Feed Mode.
- The first argument is the serial number.
- The second argument is the device name."
- --#TYPE "APC PDU: No Panel Feed Mode."
- --#SUMMARY "PDU is in No Panel Feed Mode."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 213
- pduUpsOperationMode TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: PDU is in Ups Operation Mode.
- The first argument is the serial number.
- The second argument is the device name."
- --#TYPE "APC PDU: Ups Operation Mode."
- --#SUMMARY "PDU is in Ups Operation Mode."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 214
- pduForcedBypassMode TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsString }
- DESCRIPTION
- "WARNING: PDU is in Forced Bypass Mode.
- The first argument is the serial number.
- The second argument is the device name."
- --#TYPE "APC PDU: Forced Bypass Mode."
- --#SUMMARY "PDU is in Forced Bypass Mode."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 215
- pduInputTransformerOverTemperature TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsString }
- DESCRIPTION
- "SEVERE: Input Transformer Over Temperature.
- The first argument is the serial number.
- The second argument is the device name."
- --#TYPE "APC PDU: Input Transformer Over Temperature."
- --#SUMMARY "Input Transformer Over Temperature."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 216
- pduInputTransformerOverTemperatureCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Input Transformer Over Temperature Cleared.
- The first argument is the serial number.
- The second argument is the device name."
- --#TYPE "APC PDU: Input Transformer Over Temperature Cleared."
- --#SUMMARY "Input Transformer Over Temperature Cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 217
- pduUPSInputVoltageLost TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "SEVERE: UPS Input Voltage phase-N Lost.
- The first argument is the serial number.
- The second argument is the device name.
- The third argument is the phase number."
- --#TYPE "APC PDU: UPS Input Voltage phase-N Lost."
- --#SUMMARY "UPS Input Voltage phase-N Lost."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 218
- pduUPSInputVoltageRestored TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: UPS Input Voltage phase-N Restored.
- The first argument is the serial number.
- The second argument is the device name.
- The third argument is the phase number."
- --#TYPE "APC PDU: UPS Input Voltage phase-N Restored."
- --#SUMMARY "UPS Input Voltage phase-N Restored."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 219
- pduContactFault TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "SEVERE: A contact closure in the PDU is in an abnormal position.
- The first argument is the serial number.
- The second argument is the device name.
- The third argument is the number of the contact."
- --#TYPE "APC PDU: Contact Abnormal."
- --#SUMMARY "Contact Abnormal."
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 220
- pduContactFaultCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A contact closure in the PDU is in a normal position.
- The first argument is the serial number.
- The second argument is the device name.
- The third argument is the number of the contact."
- --#TYPE "APC PDU: Contact Normal."
- --#SUMMARY "Contact Normal."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 221
- rPDUBankPhaseLowLoad TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { rPDUIdentSerialNumber, rPDUIdentName,
- rPDULoadStatusBankNumber, rPDULoadStatusPhaseNumber, mtrapargsString }
- DESCRIPTION
- "WARNING: A bank or phase on the Rack PDU has violated the low load threshold.
- The first argument is the serial number.
- The second argument is the device name.
- The third argument is the bank number (0 if this is phase data).
- The fourth argument is the phase number (0 if this is bank data)."
- --#TYPE "APC Rack PDU: Violation of bank or phase low load threshold."
- --#SUMMARY "A bank or phase on the Rack PDU has violated the low load threshold."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 222
- rPDUBankPhaseLowLoadCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { rPDUIdentSerialNumber, rPDUIdentName,
- rPDULoadStatusBankNumber, rPDULoadStatusPhaseNumber, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The bank or phase low load condition on a Rack PDU has been
- cleared.
- The first argument is the serial number.
- The second argument is the device name.
- The third argument is the bank number (0 if this is phase data).
- The fourth argument is the phase number (0 if this is bank data)."
- --#TYPE "APC Rack PDU: Bank or phase low load condition cleared."
- --#SUMMARY "The bank or phase low load condition on a Rack PDU has been cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 223
- rPDUBankPhaseNearOverload TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { rPDUIdentSerialNumber, rPDUIdentName,
- rPDULoadStatusBankNumber, rPDULoadStatusPhaseNumber, mtrapargsString }
- DESCRIPTION
- "WARNING: A bank or phase of the Rack PDU is near an overload condition.
- The first argument is the serial number.
- The second argument is the device name.
- The third argument is the bank number (0 if this is phase data).
- The fourth argument is the phase number (0 if this is bank data)."
- --#TYPE "APC Rack PDU: Bank or phase near an overload condition."
- --#SUMMARY "A bank or phase of the Rack PDU is near an overload condition."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 224
- rPDUBankPhaseNearOverloadCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { rPDUIdentSerialNumber, rPDUIdentName,
- rPDULoadStatusBankNumber, rPDULoadStatusPhaseNumber, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The bank or phase near overload condition on a Rack PDU has
- been cleared.
- The first argument is the serial number.
- The second argument is the device name.
- The third argument is the bank number (0 if this is phase data).
- The fourth argument is the phase number (0 if this is bank data)."
- --#TYPE "APC Rack PDU: Bank or phase near overload condition has cleared."
- --#SUMMARY "Rack PDU bank or phase near overload condition has cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 225
- rPDUBankPhaseOverload TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { rPDUIdentSerialNumber, rPDUIdentName,
- rPDULoadStatusBankNumber, rPDULoadStatusPhaseNumber, mtrapargsString }
- DESCRIPTION
- "SEVERE: A bank or phase of the Rack PDU is in an overload condition.
- The first argument is the serial number.
- The second argument is the device name.
- The third argument is the phase number.
- The third argument is the bank number (0 if this is phase data).
- The fourth argument is the phase number (0 if this is bank data)."
- --#TYPE "APC Rack PDU: Bank or phase overload condition."
- --#SUMMARY "A bank or phase of the Rack PDU is in an overload condition."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 226
- rPDUBankPhaseOverloadCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { rPDUIdentSerialNumber, rPDUIdentName,
- rPDULoadStatusBankNumber, rPDULoadStatusPhaseNumber, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The bank or phase overload condition on a Rack PDU has been
- cleared.
- The first argument is the serial number.
- The second argument is the device name.
- The third argument is the bank number (0 if this is phase data).
- The fourth argument is the phase number (0 if this is bank data)."
- --#TYPE "APC Rack PDU: Bank or phase overload condition has cleared."
- --#SUMMARY "The bank or phase overload condition on a Rack PDU has cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 227
- aruDeviceConfigChange TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName,
- rARUStatusAruIndex, rARUStatusAruName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Remote ARU Device Configuration change.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the ARU number.
- The fourth argument is the ARU name."
- --#TYPE "APC ARU: ARU Device configuration change."
- --#SUMMARY "ARU device configuration change."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 228
- rmPDUCommunicationLost TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsString }
- DESCRIPTION
- "SEVERE: Communication Lost.
- The first argument is the serial number.
- The second argument is the device name."
- --#TYPE "APC RM PDU: Communication Lost."
- --#SUMMARY "Communication Lost."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 229
- emsCommunicationEstablished TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Communication Established.
- The first argument is the serial number.
- The second argument is the device name."
- --#TYPE "APC EMS: Communication Established."
- --#SUMMARY "Communication Established."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 230
- emsCommunicationLost TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName, mtrapargsString }
- DESCRIPTION
- "SEVERE: Communication Lost.
- The first argument is the serial number.
- The second argument is the device name."
- --#TYPE "APC EMS: Communication Lost."
- --#SUMMARY "Communication Lost."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 231
- emsProbeConnected TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName,
- emsProbeStatusProbeIndex, emsProbeStatusProbeName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A probe has been connected to the EMS.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the probe number.
- The fourth argument is the probe name."
- --#TYPE "APC EMS: Probe Connected."
- --#SUMMARY "Probe Connected."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 232
- emsProbeDisconnected TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName,
- emsProbeStatusProbeIndex, emsProbeStatusProbeName, mtrapargsString }
- DESCRIPTION
- "SEVERE: A probe has been disconnected from the EMS.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the probe number.
- The fourth argument is the probe name."
- --#TYPE "APC EMS: Probe Disconnected."
- --#SUMMARY "Probe Disconnected."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 233
- emsSensorConnected TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName,
- emsSensorStatusSensorIndex, emsSensorStatusSensorName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A sensor has been connected to the EMS.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the sensor number.
- The fourth argument is the sensor name."
- --#TYPE "APC EMS: Sensor Connected."
- --#SUMMARY "Sensor Connected."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 234
- emsSensorDisconnected TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName,
- emsSensorStatusSensorIndex, emsSensorStatusSensorName, mtrapargsString }
- DESCRIPTION
- "SEVERE: A sensor has been disconnected from the EMS.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the sensor number.
- The fourth argument is the sensor name."
- --#TYPE "APC EMS: Sensor Disconnected."
- --#SUMMARY "Sensor Disconnected."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 235
- emsSensorFault TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName,
- emsSensorStatusSensorIndex, emsSensorStatusSensorName, mtrapargsString }
- DESCRIPTION
- "SEVERE: A EMS sensor is in the fault condition.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the sensor number.
- The fourth argument is the sensor name."
- --#TYPE "APC EMS: Sensor Fault."
- --#SUMMARY "Sensor Fault."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 236
- emsSensorFaultCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName,
- emsSensorStatusSensorIndex, emsSensorStatusSensorName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A EMS sensor fault condition has cleared.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the sensor number.
- The fourth argument is the sensor name."
- --#TYPE "APC EMS: Sensor Fault Cleared."
- --#SUMMARY "Sensor Fault Cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 237
- emsBeaconConnected TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A beacon has been connected to the EMS.
- The first argument is the host device serial number.
- The second argument is the host device name."
- --#TYPE "APC EMS: Beacon Connected."
- --#SUMMARY "Beacon Connected."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 238
- emsBeaconDisconnected TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName, mtrapargsString }
- DESCRIPTION
- "SEVERE: A beacon has been disconnected from the EMS.
- The first argument is the host device serial number.
- The second argument is the host device name."
- --#TYPE "APC EMS: Beacon Disconnected."
- --#SUMMARY "Beacon Disconnected."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 239
- emsBeaconOn TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A EMS beacon has gone on.
- The first argument is the host device serial number.
- The second argument is the host device name."
- --#TYPE "APC EMS: Beacon On."
- --#SUMMARY "Beacon On."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 240
- emsBeaconOff TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A EMS beacon has gone off.
- The first argument is the host device serial number.
- The second argument is the host device name."
- --#TYPE "APC EMS: Beacon Off."
- --#SUMMARY "Beacon Off."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 241
- emsMajorAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName, mtrapargsString }
- DESCRIPTION
- "SEVERE: A Major Alarm is present in the EMS.
- The first argument is the EMS serial number.
- The second argument is the EMS name."
- --#TYPE "APC EMS: Major Alarm."
- --#SUMMARY "Major Alarm."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 242
- emsMajorAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A Major Alarm condition has been cleared in the EMS.
- The first argument is the EMS serial number.
- The second argument is the EMS name."
- --#TYPE "APC EMS: Major Alarm Cleared."
- --#SUMMARY "Major Alarm Cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 243
- emsMinorAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName, mtrapargsString }
- DESCRIPTION
- "SEVERE: A Minor Alarm is present in the EMS.
- The first argument is the EMS serial number.
- The second argument is the EMS name."
- --#TYPE "APC EMS: Minor Alarm."
- --#SUMMARY "Minor Alarm."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 244
- emsMinorAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A Minor Alarm condition has been cleared in the EMS.
- The first argument is the EMS serial number.
- The second argument is the EMS name."
- --#TYPE "APC EMS: Minor Alarm Cleared."
- --#SUMMARY "Minor Alarm Cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 245
- emsOutletStateAbnormal TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsOutletStatusOutletIndex, emsOutletStatusOutletName,
- emsOutletStatusOutletState, emsOutletStatusOutletNormalState, mtrapargsString }
- DESCRIPTION
- "WARNING: An outlet on the EMS has changed to its abnormal state.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the outlet number.
- The fourth argument is the outlet name.
- The fifth argument is the current outlet state (1=ON, 2=OFF).
- The sixth argument is the configured normal outlet state (1=ON, 2=OFF)."
- --#TYPE "APC EMS: Outlet has changed to its abnormal state."
- --#SUMMARY "Outlet has changed to its abnormal state."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 246
- emsOutletStateNormal TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsOutletStatusOutletIndex, emsOutletStatusOutletName,
- emsOutletStatusOutletState, emsOutletStatusOutletNormalState, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: An outlet on the EMS has changed to its normal state.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the outlet number.
- The fourth argument is the outlet name.
- The fifth argument is the current outlet state (1=ON, 2=OFF).
- The sixth argument is the configured normal outlet state (1=ON, 2=OFF)."
- --#TYPE "APC EMS: Outlet has changed to its normal state."
- --#SUMMARY "Outlet has changed to its normal state."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 247
- emsInputContactStateAbnormal TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsInputContactStatusInputContactIndex,
- emsInputContactStatusInputContactName, emsInputContactStatusInputContactState,
- emsInputContactStatusInputContactNormalState, mtrapargsString }
- DESCRIPTION
- "WARNING: An input contact on the EMS has changed to its abnormal state.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the input contact number.
- The fourth argument is the input contact name.
- The fifth argument is the input contact state (1=CLOSED, 2=OPEN).
- The sixth argument is the configured normal input contact state (1=CLOSED, 2=OPEN)."
- --#TYPE "APC EMS: Input contact has changed to its abnormal state."
- --#SUMMARY "Input contact has changed to its abnormal state."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 248
- emsInputContactStateNormal TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsInputContactStatusInputContactIndex,
- emsInputContactStatusInputContactName, emsInputContactStatusInputContactState,
- emsInputContactStatusInputContactNormalState, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: An input contact on the EMS has changed to its normal state.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the input contact number.
- The fourth argument is the input contact name.
- The fifth argument is the input contact state (1=CLOSED, 2=OPEN).
- The sixth argument is the configured normal input contact state (1=CLOSED, 2=OPEN)."
- --#TYPE "APC EMS: Input contact has changed to its normal state."
- --#SUMMARY "Input contact has changed to its normal state."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 249
- emsOutputRelayStateAbnormal TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsOutputRelayStatusOutputRelayIndex,
- emsOutputRelayStatusOutputRelayName, emsOutputRelayStatusOutputRelayState,
- emsOutputRelayStatusOutputRelayNormalState, mtrapargsString }
- DESCRIPTION
- "WARNING: An output relay on the EMS has changed to its abnormal state.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the output relay number.
- The fourth argument is the output relay name.
- The fifth argument is the current output relay state (1=CLOSED, 2=OPEN).
- The sixth argument is the configured normal output relay state (1=CLOSED, 2=OPEN)."
- --#TYPE "APC EMS: Output Relay has changed to its abnormal state."
- --#SUMMARY "Output Relay has changed to its abnormal state."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 250
- emsOutputRelayStateNormal TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsOutputRelayStatusOutputRelayIndex,
- emsOutputRelayStatusOutputRelayName, emsOutputRelayStatusOutputRelayState,
- emsOutputRelayStatusOutputRelayNormalState, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: An output relay on the EMS has changed to its normal state.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the output relay number.
- The fourth argument is the output relay name.
- The fifth argument is the current output relay state (1=CLOSED, 2=OPEN).
- The sixth argument is the configured normal output relay state (1=CLOSED, 2=OPEN)."
- --#TYPE "APC EMS: Output Relay has changed to its normal state."
- --#SUMMARY "Output Relay has changed to its normal state."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 251
- emsDeviceConfigChange TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A device configuration change has been made on the EMS.
- The first argument is the EMS serial number.
- The second argument is the EMS name."
- --#TYPE "APC: A device configuration change on a EMS."
- --#SUMMARY "A device configuration change has been made on a EMS."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 252
- envHighTempThresholdViolation TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsProbeStatusProbeTemperature, emsStatusSysTempUnits,
- emsProbeStatusProbeIndex, emsProbeStatusProbeName, mtrapargsString }
- DESCRIPTION
- "SEVERE: High temperature threshold violated on the probe.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the current temperature.
- The fourth argument is the temperature scale.
- The fifth argument is the probe number.
- The sixth argument is the probe name."
- --#TYPE "APC ENV: High temperature threshold violation."
- --#SUMMARY "High temperature threshold violation."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 253
- envHighTempThresholdViolationCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsProbeStatusProbeTemperature, emsStatusSysTempUnits,
- emsProbeStatusProbeIndex, emsProbeStatusProbeName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: High temperature threshold violation cleared on the probe.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the current temperature.
- The fourth argument is the temperature scale.
- The fifth argument is the probe number.
- The sixth argument is the probe name."
- --#TYPE "APC ENV: High temperature threshold violation cleared."
- --#SUMMARY "High temperature threshold violation cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 254
- envLowTempThresholdViolation TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsProbeStatusProbeTemperature, emsStatusSysTempUnits,
- emsProbeStatusProbeIndex, emsProbeStatusProbeName, mtrapargsString }
- DESCRIPTION
- "SEVERE: Low temperature threshold violated on the probe.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the current temperature.
- The fourth argument is the temperature scale.
- The fifth argument is the probe number.
- The sixth argument is the probe name."
- --#TYPE "APC ENV: Low temperature threshold violation."
- --#SUMMARY "Low temperature threshold violation."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 255
- envLowTempThresholdViolationCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsProbeStatusProbeTemperature, emsStatusSysTempUnits,
- emsProbeStatusProbeIndex, emsProbeStatusProbeName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Low temperature threshold violation cleared on the probe.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the current temperature.
- The fourth argument is the temperature scale.
- The fifth argument is the probe number.
- The sixth argument is the probe name."
- --#TYPE "APC ENV: Low temperature threshold violation cleared."
- --#SUMMARY "Low temperature threshold violation cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 256
- envHighHumidityThresholdViolation TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsProbeStatusProbeHumidity,
- emsProbeStatusProbeIndex, emsProbeStatusProbeName, mtrapargsString }
- DESCRIPTION
- "SEVERE: High humidity threshold violated on the probe.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the current humidity
- The fourth argument is the probe number.
- The fifth argument is the probe name."
- --#TYPE "APC ENV: High humidity threshold violation."
- --#SUMMARY "High humidity threshold violation."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 257
- envHighHumidityThresholdViolationCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsProbeStatusProbeHumidity,
- emsProbeStatusProbeIndex, emsProbeStatusProbeName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: High humidity threshold violation cleared on the probe.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the current humidity.
- The fourth argument is the probe number.
- The fifth argument is the probe name."
- --#TYPE "APC ENV: High humidity threshold violation cleared."
- --#SUMMARY "High humidity threshold violation cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 258
- envLowHumidityThresholdViolation TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsProbeStatusProbeHumidity,
- emsProbeStatusProbeIndex, emsProbeStatusProbeName, mtrapargsString }
- DESCRIPTION
- "SEVERE: Low humidity threshold violated on the probe.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the current humidity
- The fourth argument is the probe number.
- The fifth argument is the probe name."
- --#TYPE "APC ENV: Low humidity threshold violation."
- --#SUMMARY "Low humidity threshold violation."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 259
- envLowHumidityThresholdViolationCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsProbeStatusProbeHumidity,
- emsProbeStatusProbeIndex, emsProbeStatusProbeName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Low humidity threshold violation cleared on the probe.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the current humidity.
- The fourth argument is the probe number.
- The fifth argument is the probe name."
- --#TYPE "APC ENV: Low humidity threshold violation cleared."
- --#SUMMARY "Low humidity threshold violation cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 260
- -- Switched and Metered Rack PDU Traps
- rPDUCommunicationEstablished TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { rPDUIdentSerialNumber, rPDUIdentName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Communication with a Rack PDU has been established.
- The first argument is the serial number.
- The second argument is the device name."
- --#TYPE "APC Rack PDU: Communication established."
- --#SUMMARY "Communication with a Rack PDU established."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 266
- rPDUCommunicationLost TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { rPDUIdentSerialNumber, rPDUIdentName, mtrapargsString }
- DESCRIPTION
- "SEVERE: Communication with a Rack PDU has been lost.
- The first argument is the serial number.
- The second argument is the device name."
- --#TYPE "APC Rack PDU: Communication lost."
- --#SUMMARY "Communication with a Rack PDU has been lost."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 267
- rPDUOutletOn TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { rPDUIdentSerialNumber, rPDUIdentName,
- rPDUOutletControlIndex, rPDUOutletControlOutletName,
- mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: An outlet on a Switched Rack PDU has turned on.
- The first argument is the serial number.
- The second argument is the device name.
- The third argument is the outlet index number.
- The fourth argument is the outlet name."
- --#TYPE "APC Switched Rack PDU: An outlet has turned on."
- --#SUMMARY "An outlet on a Switched Rack PDU has turned on."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 268
- rPDUOutletOff TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { rPDUIdentSerialNumber, rPDUIdentName,
- rPDUOutletControlIndex, rPDUOutletControlOutletName,
- mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: An outlet on a Switched Rack PDU has turned off.
- The first argument is the serial number.
- The second argument is the device name.
- The third argument is the outlet index number.
- The fourth argument is the outlet name."
- --#TYPE "APC Switched Rack PDU: An outlet has turned off."
- --#SUMMARY "An outlet on a Switched Rack PDU has turned off."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 269
- rPDUDeviceConfigChange TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { rPDUIdentSerialNumber, rPDUIdentName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A device configuration change has been made on a
- Rack PDU.
- The first argument is the serial number.
- The second argument is the device name."
- --#TYPE "APC Rack PDU: Device configuration change made."
- --#SUMMARY "Device configuration change has been made on a Rack PDU."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 270
- rPDUOutletConfigChange TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { rPDUIdentSerialNumber, rPDUIdentName,
- rPDUOutletControlIndex, rPDUOutletControlOutletName,
- mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: An outlet configuration change has been made on a
- Switched Rack PDU.
- The first argument is the serial number.
- The second argument is the device name.
- The third argument is the outlet index number.
- The fourth argument is the outlet name."
- --#TYPE "APC Switched Rack PDU: Outlet configuration change made."
- --#SUMMARY "Outlet configuration change has been made on a Switched Rack PDU."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 271
- rPDULowLoad TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { rPDUIdentSerialNumber, rPDUIdentName,
- rPDULoadStatusPhaseNumber, mtrapargsString }
- DESCRIPTION
- "WARNING: A Rack PDU has violated the low load threshold.
- The first argument is the serial number.
- The second argument is the device name.
- The third argument is the phase number."
- --#TYPE "APC Rack PDU: Violation of low load threshold."
- --#SUMMARY "A Rack PDU has violated the low load threshold."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 272
- rPDULowLoadCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { rPDUIdentSerialNumber, rPDUIdentName,
- rPDULoadStatusPhaseNumber, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The low load condition on a Rack PDU has been
- cleared.
- The first argument is the serial number.
- The second argument is the device name.
- The third argument is the phase number."
- --#TYPE "APC Rack PDU: Low load condition cleared."
- --#SUMMARY "The low load condition on a Rack PDU has been cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 273
- rPDUNearOverload TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { rPDUIdentSerialNumber, rPDUIdentName,
- rPDULoadStatusPhaseNumber, mtrapargsString }
- DESCRIPTION
- "WARNING: A Rack PDU is near an overload condition.
- The first argument is the serial number.
- The second argument is the device name.
- The third argument is the phase number."
- --#TYPE "APC Rack PDU: Near an overload condition."
- --#SUMMARY "A Rack PDU is near an overload condition."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 274
- rPDUNearOverloadCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { rPDUIdentSerialNumber, rPDUIdentName,
- rPDULoadStatusPhaseNumber, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The near overload condition on a Rack PDU has
- been cleared.
- The first argument is the serial number.
- The second argument is the device name.
- The third argument is the phase number."
- --#TYPE "APC Rack PDU: Near overload condition has cleared."
- --#SUMMARY "Rack PDU near overload condition has cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 275
- rPDUOverload TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { rPDUIdentSerialNumber, rPDUIdentName,
- rPDULoadStatusPhaseNumber, mtrapargsString }
- DESCRIPTION
- "SEVERE: A Rack PDU is in an overload condition.
- The first argument is the serial number.
- The second argument is the device name.
- The third argument is the phase number."
- --#TYPE "APC Rack PDU: Overload condition."
- --#SUMMARY "A Rack PDU is in an overload condition."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 276
- rPDUOverloadCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { rPDUIdentSerialNumber, rPDUIdentName,
- rPDULoadStatusPhaseNumber, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The overload condition on a Rack PDU has been
- cleared.
- The first argument is the serial number.
- The second argument is the device name.
- The third argument is the phase number."
- --#TYPE "APC Rack PDU: Overload condition has cleared."
- --#SUMMARY "The overload condition on a Rack PDU has cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 277
- rPDUPowerSupply1Fail TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { rPDUIdentSerialNumber, rPDUIdentName, mtrapargsString }
- DESCRIPTION
- "SEVERE: Power Supply 1 on Rack PDU is in FAIL state.
- The first argument is the serial number.
- The second argument is the device name."
- --#TYPE "APC Rack PDU: Power Supply 1 is in FAIL state."
- --#SUMMARY "Power Supply 1 on Rack PDU is in FAIL state."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 278
- rPDUPowerSupply1Ok TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { rPDUIdentSerialNumber, rPDUIdentName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Power Supply 1 on Rack PDU is operating normally.
- The first argument is the serial number.
- The second argument is the device name."
- --#TYPE "APC Rack PDU: Power Supply 1 is operating normally."
- --#SUMMARY "Power Supply 1 on Rack PDU is operating normally."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 279
- rPDUPowerSupply2Fail TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { rPDUIdentSerialNumber, rPDUIdentName, mtrapargsString }
- DESCRIPTION
- "SEVERE: Power Supply 2 on Rack PDU is in FAIL state.
- The first argument is the serial number.
- The second argument is the device name."
- --#TYPE "APC Rack PDU: Power Supply 2 is in FAIL state."
- --#SUMMARY "Power Supply 2 on Rack PDU is in FAIL state."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 280
- rPDUPowerSupply2Ok TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { rPDUIdentSerialNumber, rPDUIdentName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Power Supply 2 on Rack PDU is operating normally.
- The first argument is the serial number.
- The second argument is the device name."
- --#TYPE "APC Rack PDU: Power Supply 2 is operating normally."
- --#SUMMARY "Power Supply 2 on Rack PDU is operating normally."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 281
- rPDUPhaseConfigChange TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { rPDUIdentSerialNumber, rPDUIdentName,
- rPDULoadPhaseConfigIndex, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A phase configuration change has been made on a
- Rack PDU.
- The first argument is the serial number.
- The second argument is the device name.
- The third argument is the phase index number."
- --#TYPE "APC Rack PDU: Phase configuration change made."
- --#SUMMARY "Phase configuration change has been made on a Rack PDU."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 282
- rPDUCancelPendingCommand TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { rPDUIdentSerialNumber, rPDUIdentName,
- rPDUOutletControlIndex, rPDUOutletControlOutletName,
- mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A cancel pending command has been made on a
- Switched Rack PDU.
- The first argument is the serial number.
- The second argument is the device name.
- The third argument is the outlet index number (0 indicates all outlets).
- The fourth argument is the outlet name (or device name if all outlets)."
- --#TYPE "APC Switched Rack PDU: Cancel Pending Command made."
- --#SUMMARY "A Cancel Pending Command has been made on a Switched Rack PDU."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 283
- aruAlinkCommunicationEstablished TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName,
- rARUStatusAruIndex, rARUStatusAruName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Remote ARU Communication Established.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the ARU number.
- The fourth argument is the ARU name."
- --#TYPE "APC ARU: Communication Established."
- --#SUMMARY "Communication Established."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 284
- aruAlinkCommunicationLost TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName,
- rARUStatusAruIndex, rARUStatusAruName, mtrapargsString }
- DESCRIPTION
- "SEVERE: Remote ARU Communication Lost.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the ARU number.
- The fourth argument is the ARU name."
- --#TYPE "APC ARU: Communication Lost."
- --#SUMMARY "Communication Lost."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 285
- aruFanFail TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName,
- rARUStatusAruIndex, rARUStatusAruName, mtrapargsString }
- DESCRIPTION
- "SEVERE: Remote ARU Fan Fail.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the ARU number.
- The fourth argument is the ARU name."
- --#TYPE "APC ARU: Fan Failure."
- --#SUMMARY "Fan Fail."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 286
- aruFanFailCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName,
- rARUStatusAruIndex, rARUStatusAruName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Remote ARU Fan Fail Cleared.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the ARU number.
- The fourth argument is the ARU name."
- --#TYPE "APC ARU: Fan Fail Cleared."
- --#SUMMARY "Fan Fail Cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 287
- aruSmokeAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName,
- rARUStatusAruIndex, rARUStatusAruName, mtrapargsString }
- DESCRIPTION
- "SEVERE: Remote ARU Smoke Alarm.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the ARU number.
- The fourth argument is the ARU name."
- --#TYPE "APC ARU: Smoke Alarm."
- --#SUMMARY "Smoke Alarm."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 288
- aruSmokeAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName,
- rARUStatusAruIndex, rARUStatusAruName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Remote ARU Smoke Alarm Cleared.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the ARU number.
- The fourth argument is the ARU name."
- --#TYPE "APC ARU: Smoke Alarm Cleared."
- --#SUMMARY "Smoke Alarm Cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 289
- aruHighTemperatureAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName,
- rARUStatusAruIndex, rARUStatusAruName, mtrapargsString }
- DESCRIPTION
- "WARNING: ARU Exhaust temperature has exceeded the override
- threshold and the ARU has increased fan speed to
- maintain a safe environment in the rack.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the ARU number.
- The fourth argument is the ARU name."
- --#TYPE "APC ARU: High Temperature Alarm."
- --#SUMMARY "High Temperature Alarm."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 290
- aruHighTemperatureAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName,
- rARUStatusAruIndex, rARUStatusAruName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: ARU temperature override state has been cleared.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the ARU number.
- The fourth argument is the ARU name."
- --#TYPE "APC ARU: High Temperature Alarm Cleared."
- --#SUMMARY "High Temperature Alarm Cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 291
- aruExhaustTemperatureAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName,
- rARUStatusAruIndex, rARUStatusAruName, mtrapargsString }
- DESCRIPTION
- "SEVERE: ARU Extreme Exhaust Temperature Alarm.
- The ARU is unable to control the temperature within the rack
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the ARU number.
- The fourth argument is the ARU name."
- --#TYPE "APC ARU: Exhaust Temperature Alarm."
- --#SUMMARY "Exhaust Temperature Alarm."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 292
- aruExhaustTemperatureAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName,
- rARUStatusAruIndex, rARUStatusAruName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Remote ARU Exhaust Temperature Alarm Cleared.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the ARU number.
- The fourth argument is the ARU name."
- --#TYPE "APC ARU: Exhaust Temperature Alarm Cleared."
- --#SUMMARY "Exhaust Temperature Alarm Cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 293
- envAlinkCommunicationEstablished TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName,
- emsProbeStatusProbeIndex, emsProbeStatusProbeName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Remote Probe Communication Established.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the probe number.
- The fourth argument is the probe name."
- --#TYPE "APC ENV: Communication Established."
- --#SUMMARY "Communication Established."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 294
- envAlinkCommunicationLost TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName,
- emsProbeStatusProbeIndex, emsProbeStatusProbeName, mtrapargsString }
- DESCRIPTION
- "SEVERE: Remote Probe Communication Lost.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the probe number.
- The fourth argument is the probe name."
- --#TYPE "APC ENV: Communication Lost."
- --#SUMMARY "Communication Lost."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 295
- emsAlinkPowerOverload TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName, mtrapargsString }
- DESCRIPTION
- "SEVERE: Alink Power Overload.
- The first argument is the host device serial number.
- The second argument is the host device name."
- --#TYPE "APC EMS: Alink Power Overload."
- --#SUMMARY "Alink Power Overload."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 296
- emsAlinkPowerOverloadCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Alink Power Overload Cleared.
- The first argument is the host device serial number.
- The second argument is the host device name."
- --#TYPE "APC EMS: Alink Power Overload Cleared."
- --#SUMMARY "Alink Power Overload Cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 297
- upsOutletGroupTurnedOn TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { upsOutletGroupControlIndex, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The specified Outlet Group turned on."
- --#TYPE "APC UPS: Outlet Group turned on."
- --#SUMMARY "Outlet Group turned on"
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 298
- upsOutletGroupTurnedOff TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { upsOutletGroupControlIndex, mtrapargsString }
- DESCRIPTION
- "WARNING: The specified Outlet Group turned off."
- --#TYPE "APC UPS: Outlet Group turned off."
- --#SUMMARY "Outlet Group turned off."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 299
- smwCriticalCondition TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsGauge, mtrapargsString }
- DESCRIPTION
- "SEVERE: A Symmetra MW UPS critical condition has been detected.
- The first variable is the fault condition."
- --#TYPE "APC Symmetra MW UPS: A critical condition has been detected."
- --#SUMMARY "A critical condition has been detected."
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 300
- smwCriticalConditionCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsGauge, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A Symmetra MW UPS critical condition has been cleared.
- The first variable is the fault condition."
- --#TYPE "APC Symmetra MW UPS: A critical condition has been cleared."
- --#SUMMARY "A critical condition has been cleared."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 301
- smwWarningCondition TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsGauge, mtrapargsString }
- DESCRIPTION
- "WARNING: A Symmetra MW UPS warning condition has been detected.
- The first variable is the fault condition."
- --#TYPE "APC Symmetra MW UPS: A warning condition has been detected."
- --#SUMMARY "A warning condition has been detected."
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 302
- smwWarningConditionCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsGauge, mtrapargsString }
- DESCRIPTION
- "WARNING: A Symmetra MW UPS warning condition has been cleared.
- The first variable is the fault condition."
- --#TYPE "APC Symmetra MW UPS: A warning condition has been cleared."
- --#SUMMARY "A warning condition has been cleared."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 303
- smwInformationalCondition TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsGauge, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A Symmetra MW UPS informational condition has been detected.
- The first variable is the fault condition."
- --#TYPE "APC Symmetra MW UPS: Informational condition detected."
- --#SUMMARY "An informational condition has been detected."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 304
- smwInformationalConditionCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsGauge, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A Symmetra MW UPS informational condition has been cleared.
- The first variable is the fault condition."
- --#TYPE "APC Symmetra MW UPS: Informational condition cleared."
- --#SUMMARY "An informational condition has been cleared."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 305
- airCriticalCondition TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "SEVERE: An Air critical condition was detected.
- The first variable is the error condition text message.
- The second variable is the error number."
- --#TYPE "APC Air: A critical condition was detected. "
- --#SUMMARY "A critical condition was detected. "
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 306
- airCriticalConditionCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: An Air critical condition was cleared.
- The first variable is the error condition text message.
- The second variable is the error number."
- --#TYPE "APC Air: A critical condition was cleared. "
- --#SUMMARY "A critical condition was cleared. "
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 307
- airWarningCondition TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "WARNING: An Air warning condition was detected.
- The first variable is the error condition text message.
- The second variable is the error number."
- --#TYPE "APC Air: A warning condition was detected. "
- --#SUMMARY "A warning condition was detected. "
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 308
- airWarningConditionCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "WARNING: An Air warning condition was cleared.
- The first variable is the error condition text message.
- The second variable is the error number."
- --#TYPE "APC Air: A warning condition was cleared. "
- --#SUMMARY "A warning condition was cleared. "
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 309
- airInformationalCondition TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: An Air informational condition was detected.
- The first variable is the error condition text message.
- The second variable is the error number."
- --#TYPE "APC Air: Informational condition detected. "
- --#SUMMARY "An informational condition was detected. "
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 310
- airInformationalConditionCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: An Air informational condition was cleared.
- The first variable is the error condition text message.
- The second variable is the error number."
- --#TYPE "APC Air: Informational condition was cleared. "
- --#SUMMARY "An informational condition was cleared. "
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 311
- -- xPDU Traps (part 1)
- xPDUInputVoltageLowAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
- mtrapargsInteger02, mtrapargsInteger03, mtrapargsString }
- DESCRIPTION
- "SEVERE: Three-phase input voltage to the device is outside the specified limits.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N, 4=unused, 5=L1-L2, 6=L2-L3, 7=L3-L1).
- The fourth argument is the measured voltage in tenths of Volts.
- The fifth argument is the threshold, in tenths of Volts, from which the alarm was generated."
- --#TYPE "APC XPDU: Main input low voltage alarm."
- --#SUMMARY "Input voltage is below threshold."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 312
- xPDUInputVoltageLowAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
- mtrapargsInteger02, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Three-phase input voltage to the device is back within the specified limits.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N, 4=unused, 5=L1-L2, 6=L2-L3, 7=L3-L1).
- The fourth argument is the measured voltage in tenths of Volts."
- --#TYPE "APC XPDU: Main input low voltage alarm cleared."
- --#SUMMARY "Main input low voltage cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 313
- xPDUInputVoltageHighAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
- mtrapargsInteger02, mtrapargsInteger03, mtrapargsString }
- DESCRIPTION
- "SEVERE: Three-phase input voltage to the device is outside the specified limits.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N, 4=unused, 5=L1-L2, 6=L2-L3, 7=L3-L1).
- The fourth argument is the measured voltage in tenths of Volts.
- The fifth argument is the threshold, in tenths of Volts, above which the alarm was generated."
- --#TYPE "APC XPDU: Main input high voltage alarm."
- --#SUMMARY "Main input voltage is above threshold."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 314
- xPDUInputVoltageHighAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
- mtrapargsInteger02, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Three-phase input voltage to the device is back within the specified limits.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N, 4=unused, 5=L1-L2, 6=L2-L3, 7=L3-L1).
- The fourth argument is the measured voltage in tenths of Volts."
- --#TYPE "APC XPDU: Main input high voltage alarm cleared."
- --#SUMMARY "Main input high voltage alarm cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 315
- xPDUBypassVoltageLowAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
- mtrapargsInteger02, mtrapargsInteger03, mtrapargsString }
- DESCRIPTION
- "SEVERE: Three-phase bypass input voltage to the device is outside the specified limits.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N).
- The fourth argument is the measured voltage in tenths of Volts.
- The fifth argument is the threshold, in tenths of Volts, from which the alarm was generated."
- --#TYPE "APC XPDU: Bypass input low voltage alarm."
- --#SUMMARY "Bypass input voltage is below threshold."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 316
- xPDUBypassVoltageLowAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
- mtrapargsInteger02, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Three-phase bypass input voltage to the device is back within the specified limits.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N).
- The fourth argument is the measured voltage in tenths of Volts."
- --#TYPE "APC XPDU: Bypass input low voltage alarm cleared."
- --#SUMMARY "Bypass input low voltage alarm cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 317
- xPDUBypassVoltageHighAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
- mtrapargsInteger02, mtrapargsInteger03, mtrapargsString }
- DESCRIPTION
- "SEVERE: Three-phase bypass input voltage to the device is outside the specified limits.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N).
- The fourth argument is the measured voltage in tenths of Volts.
- The fifth argument is the threshold, in tenths of Volts, above which the alarm was generated."
- --#TYPE "APC XPDU: Bypass input high voltage alarm."
- --#SUMMARY "Bypass input voltage is above threshold."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 318
- xPDUBypassVoltageHighAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
- mtrapargsInteger02, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Three-phase bypass input voltage to the device is back within the specified limits.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N).
- The fourth argument is the measured voltage in tenths of Volts."
- --#TYPE "APC XPDU: Bypass input high voltage alarm cleared."
- --#SUMMARY "Bypass input voltage alarm cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 319
- xPDUOutputVoltageLowAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
- mtrapargsInteger02, mtrapargsInteger03, mtrapargsString }
- DESCRIPTION
- "SEVERE: The three-phase output voltage of the device is outside the specified limits.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N).
- The fourth argument is the measured voltage in tenths of Volts.
- The fifth argument is the threshold, in tenths of Volts, from which the alarm was generated."
- --#TYPE "APC XPDU: Output low voltage alarm."
- --#SUMMARY "Output voltage is below threshold."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 320
- xPDUOutputVoltageLowAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
- mtrapargsInteger02, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The three-phase output voltage of the device is back within the specified limits.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N).
- The fourth argument is the measured voltage in tenths of Volts."
- --#TYPE "APC XPDU: Output low voltage alarm cleared."
- --#SUMMARY "Output low voltage alarm cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 321
- xPDUOutputVoltageHighAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
- mtrapargsInteger02, mtrapargsInteger03, mtrapargsString }
- DESCRIPTION
- "SEVERE: The three-phase output voltage of the device is outside the specified limits.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N).
- The fourth argument is the measured voltage in tenths of Volts.
- The fifth argument is the threshold, in tenths of Volts, above which the alarm was generated."
- --#TYPE "APC XPDU: Output high voltage alarm."
- --#SUMMARY "Output voltage is above threshold."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 322
- xPDUOutputVoltageHighAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
- mtrapargsInteger02, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The three-phase output voltage of the device is back within the specified limits.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N).
- The fourth argument is the measured voltage in tenths of Volts."
- --#TYPE "APC XPDU: Output high voltage alarm cleared."
- --#SUMMARY "Output high voltage alarm cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 323
- xPDUOutputCurrentLowAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
- mtrapargsInteger02, mtrapargsInteger03, mtrapargsString }
- DESCRIPTION
- "SEVERE: The three-phase output load current of the device is outside the specified limits.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the phase (1=L1, 2=L2, 3=L3).
- The fourth argument is the measured current in tenths of Amps.
- The fifth argument is the threshold, in tenths of Amps, from which the alarm was generated."
- --#TYPE "APC XPDU: Output low current alarm."
- --#SUMMARY "Output current is below threshold."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 324
- xPDUOutputCurrentLowAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
- mtrapargsInteger02, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The three-phase output load current of the device is back within the specified limits.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the phase (1=L1, 2=L2, 3=L3).
- The fourth argument is the measured current in tenths of Amps."
- --#TYPE "APC XPDU: Output low current alarm cleared."
- --#SUMMARY "Output low current alarm cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 325
- xPDUOutputCurrentHighAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
- mtrapargsInteger02, mtrapargsInteger03, mtrapargsString }
- DESCRIPTION
- "SEVERE: The three-phase load current of the device is outside the specified limits.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the phase (1=L1, 2=L2, 3=L3).
- The fourth argument is the measured current in tenths of Amps.
- The fifth argument is the threshold, in tenths of Amps, above which the alarm was generated."
- --#TYPE "APC XPDU: Output high current alarm."
- --#SUMMARY "Output current is above threshold."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 326
- xPDUOutputCurrentHighAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
- mtrapargsInteger02, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The three-phase output current of the device is back within the specified limits.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the phase (1=L1, 2=L2, 3=L3).
- The fourth argument is the measured current in tenths of Amps."
- --#TYPE "APC XPDU: Output high current alarm cleared."
- --#SUMMARY "Output high current alarm cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 327
- xPDUOutputFrequencyAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "SEVERE: The devices output frequency is outside the specified limits.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the frequency deviation from the nominal in tenths of Hertz."
- --#TYPE "APC XPDU: Output frequency out-of-range alarm."
- --#SUMMARY "Output frequency is out-of-range."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 328
- xPDUOutputFrequencyAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The devices output frequency is back within the specified limits.
- The first argument is the host device serial number.
- The second argument is the host device name."
- --#TYPE "APC XPDU: Output frequency back in range."
- --#SUMMARY "Output frequency in range."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 329
- xPDUSystemGroundCurrentAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger, mtrapargsInteger02, mtrapargsString }
- DESCRIPTION
- "SEVERE: The earth ground current of the device is over the specified limits.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the measured current in tenths of Amps.
- The fourth argument is the threshold, in tenths of Amps, above which the alarm was generated."
- --#TYPE "APC XPDU: Earth ground high current alarm."
- --#SUMMARY "Earth ground current is above threshold."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 330
- xPDUSystemGroundCurrentAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The earth ground current of the device is back within the specified limits.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the measured current in tenths of Amps."
- --#TYPE "APC XPDU: Earth ground high current alarm cleared."
- --#SUMMARY "Earth ground high current alarm cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 331
- xPDUInputContactStateAbnormal TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
- mtrapargsString02, mtrapargsInteger02, mtrapargsInteger03, mtrapargsString }
- DESCRIPTION
- "SEVERE: A user input contact on the device has changed to its abnormal state.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the input contact number.
- The fourth argument is the input contact name.
- The fifth argument is the input contact state (1=OPEN, 2=CLOSED).
- The sixth argument is the configured normal input contact state (1=OPEN, 2=CLOSED)."
- --#TYPE "APC XPDU: Input contact has changed to its abnormal state."
- --#SUMMARY "Input contact has changed to its abnormal state."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 332
- xPDUInputContactStateNormal TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
- mtrapargsString02, mtrapargsInteger02, mtrapargsInteger03, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A user input contact on the device has changed to its normal state.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the input contact number.
- The fourth argument is the input contact name.
- The fifth argument is the input contact state (1=CLOSED, 2=OPEN).
- The sixth argument is the configured normal input contact state (1=OPEN, 2=CLOSED)."
- --#TYPE "APC XPDU: Input contact has changed to its normal state."
- --#SUMMARY "Input contact has changed to its normal state."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 333
- xPDUOutputNeutralCurrentHighAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
- mtrapargsInteger02, mtrapargsString }
- DESCRIPTION
- "WARNING: The three-phase neutral current of the device is outside the specified limits.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the measured current in tenths of Amps.
- The fourth argument is the threshold, in tenths of Amps, above which the alarm was generated."
- --#TYPE "APC XPDU: Output high neutral current alarm."
- --#SUMMARY "Output neutral current is above threshold."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 334
- xPDUOutputNeutralCurrentHighAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
- mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The output neutral current of the device is back within the specified limits.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the measured current in tenths of Amps."
- --#TYPE "APC XPDU: Output neutral high current alarm cleared."
- --#SUMMARY "Output neutral high current alarm cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 335
- xPDUCoolingFanAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsString }
- DESCRIPTION
- "SEVERE: The device's internal cooling fans have failed.
- The first argument is the host device serial number.
- The second argument is the host device name."
- --#TYPE "APC XPDU: Cooling fan failure alarm."
- --#SUMMARY "Cooling fan failure."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 336
- xPDUCoolingFanAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The device's cooling fans are now functioning properly.
- The first argument is the host device serial number.
- The second argument is the host device name."
- --#TYPE "APC XPDU: Cooling fan alarm cleared."
- --#SUMMARY "Cooling fan alarm cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 337
- xPDUTransformerTempAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsString }
- DESCRIPTION
- "SEVERE: The device's isolation transformer is over temperature.
- The first argument is the host device serial number.
- The second argument is the host device name."
- --#TYPE "APC XPDU: Isolation transformer over temperature alarm."
- --#SUMMARY "Transformer temp alarm."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 338
- xPDUTransformerTempAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The device's isolation transformer is no longer over temperature.
- The first argument is the host device serial number.
- The second argument is the host device name."
- --#TYPE "APC XPDU: Isolation transformer over temperature alarm cleared."
- --#SUMMARY "Transformer temp alarm cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 339
- xPDUBranchCurrentLowAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
- mtrapargsInteger02, mtrapargsInteger03, mtrapargsString }
- DESCRIPTION
- "WARNING: The current in a branch circuit is outside the limits specified for that
- branch circuit.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the panel position of the branch circuit (1-based index).
- The fourth argument is the measured current in tenths of Amps.
- The fifth argument is the threshold, in tenths of Amps, from which the alarm was generated."
- --#TYPE "APC XPDU: Branch circuit low current alarm."
- --#SUMMARY "Branch circuit current is below threshold."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 340
- xPDUBranchCurrentLowAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
- mtrapargsInteger02, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The current in a branch circuit is back within the limits
- specified for that branch circuit.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the panel position of the branch circuit (1-based index).
- The fourth argument is the measured current in tenths of Amps."
- --#TYPE "APC XPDU: Branch circuit low current alarm cleared."
- --#SUMMARY "Branch circuit low current alarm cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 341
- xPDUBranchCurrentHighAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
- mtrapargsInteger02, mtrapargsInteger03, mtrapargsString }
- DESCRIPTION
- "WARNING: The current in a branch circuit is outside the limits specified for that
- branch circuit.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the panel position of the branch circuit (1-based index).
- The fourth argument is the measured current in tenths of Amps.
- The fifth argument is the threshold, in tenths of Amps, above which the alarm was generated."
- --#TYPE "APC XPDU: Branch circuit high current alarm."
- --#SUMMARY "Branch circuit current is above threshold."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 342
- xPDUBranchCurrentHighAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
- mtrapargsInteger02, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The current in a branch circuit is back within the limits
- specified for that branch circuit.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the panel position of the branch circuit (1-based index).
- The fourth argument is the measured current in tenths of Amps."
- --#TYPE "APC XPDU: Branch circuit high current alarm cleared."
- --#SUMMARY "Branch circuit high current alarm cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 343
- xPDUInternalCommError TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsString }
- DESCRIPTION
- "SEVERE: There is an internal communication error in the device.
- The first argument is the host device serial number.
- The second argument is the host device name."
- --#TYPE "APC XPDU: Internal communication error."
- --#SUMMARY "Internal communication error."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 344
- emsHardwareStateAbnormal TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName, mtrapargsString }
- DESCRIPTION
- "SEVERE: The device's hardware is improperly configured and operating outside
- normal bounds for the hardware. This can be caused by improper devices being
- connected to the EMS ports or Alink Current limit detection."
- --#TYPE "APC EMS: Hardware is in an abnormal state."
- --#SUMMARY "Hardware is in an abnormal state."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 345
- emsHardwareStateNormal TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The device's hardware is in its normal operational state.
- The first argument is the host device serial number."
- --#TYPE "APC EMS: Hardware is in a normal state."
- --#SUMMARY "Hardware is in its normal state."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 346
-
- ceSevereCondition TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "SEVERE: A Custom Event severe condition was detected.
- The first variable is the custom event text message.
- The second variable is the custom event number."
- --#TYPE "APC Custom Event: A severe condition was detected. "
- --#SUMMARY "A severe condition was detected. "
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 347
- ceSevereConditionCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A Custom Event severe condition was cleared.
- The first variable is the custom event text message.
- The second variable is the custom event number."
- --#TYPE "APC Custom Event: A severe condition was cleared. "
- --#SUMMARY "A severe condition was cleared. "
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 348
- ceWarningCondition TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "WARNING: A Custom Event warning condition was detected.
- The first variable is the custom event text message.
- The second variable is the custom event number."
- --#TYPE "APC Custom Event: A warning condition was detected. "
- --#SUMMARY "A warning condition was detected. "
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 349
- ceWarningConditionCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A Custom Event warning condition was cleared.
- The first variable is the custom event text message.
- The second variable is the custom event number."
- --#TYPE "APC Custom Event: A warning condition was cleared. "
- --#SUMMARY "A warning condition was cleared. "
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 350
- ceInformationalCondition TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A Custom Event informational condition was detected.
- The first variable is the custom event text message.
- The second variable is the custom event number."
- --#TYPE "APC Custom Event: Informational condition detected. "
- --#SUMMARY "An informational condition was detected. "
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 351
- ceInformationalConditionCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A Custom Event informational condition was cleared.
- The first variable is the custom event text message.
- The second variable is the custom event number."
- --#TYPE "APC Custom Event: Informational condition was cleared. "
- --#SUMMARY "An informational condition was cleared. "
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 352
-
- upsInternalOverTemperature TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "WARNING: The internal over temperature condition exists."
- --#TYPE "APC UPS: The internal over temperature condition exists."
- --#SUMMARY "The internal over temperature condition exists."
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 353
- upsInternalOverTemperatureCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The internal over temperature condition cleared."
- --#TYPE "APC UPS: The internal over temperature condition cleared."
- --#SUMMARY "The internal over temperature condition cleared."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 354
-
- upsMpuReset TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The MPU has been reset."
- --#TYPE "APC UPS: The MPU has been reset."
- --#SUMMARY "The MPU has been reset."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 355
- upsOutputSwitchClosed TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The Output Switch is closed."
- --#TYPE "APC UPS: The Output Switch is closed."
- --#SUMMARY "The Output Switch is closed."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 356
- upsOutputSwitchOpened TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The Output Switch is open."
- --#TYPE "APC UPS: The Output Switch is open."
- --#SUMMARY "The Output Switch is open."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 357
- upsCalibrationStackChanged TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A calibration value in the stack was changed."
- --#TYPE "APC UPS: A calibration value in the stack was changed."
- --#SUMMARY "A calibration value in the stack was changed."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 358
-
- -- Upgraded EMS now has more env traps
- envMaxTempThresholdViolation TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsProbeStatusProbeTemperature, emsStatusSysTempUnits,
- emsProbeStatusProbeIndex, emsProbeStatusProbeName, mtrapargsString }
- DESCRIPTION
- "SEVERE: Max temperature threshold violated on the probe.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the current temperature.
- The fourth argument is the temperature scale.
- The fifth argument is the probe number.
- The sixth argument is the probe name."
- --#TYPE "APC ENV: Max temperature threshold violation."
- --#SUMMARY "Max temperature threshold violation."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 359
- envMaxTempThresholdViolationCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsProbeStatusProbeTemperature, emsStatusSysTempUnits,
- emsProbeStatusProbeIndex, emsProbeStatusProbeName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Max temperature threshold violation cleared on the probe.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the current temperature.
- The fourth argument is the temperature scale.
- The fifth argument is the probe number.
- The sixth argument is the probe name."
- --#TYPE "APC ENV: Max temperature threshold violation cleared."
- --#SUMMARY "Max temperature threshold violation cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 360
- envMinTempThresholdViolation TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsProbeStatusProbeTemperature, emsStatusSysTempUnits,
- emsProbeStatusProbeIndex, emsProbeStatusProbeName, mtrapargsString }
- DESCRIPTION
- "SEVERE: Min temperature threshold violated on the probe.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the current temperature.
- The fourth argument is the temperature scale.
- The fifth argument is the probe number.
- The sixth argument is the probe name."
- --#TYPE "APC ENV: Min temperature threshold violation."
- --#SUMMARY "Min temperature threshold violation."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 361
- envMinTempThresholdViolationCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsProbeStatusProbeTemperature, emsStatusSysTempUnits,
- emsProbeStatusProbeIndex, emsProbeStatusProbeName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Min temperature threshold violation cleared on the probe.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the current temperature.
- The fourth argument is the temperature scale.
- The fifth argument is the probe number.
- The sixth argument is the probe name."
- --#TYPE "APC ENV: Min temperature threshold violation cleared."
- --#SUMMARY "Min temperature threshold violation cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 362
- envMaxHumidityThresholdViolation TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsProbeStatusProbeHumidity,
- emsProbeStatusProbeIndex, emsProbeStatusProbeName, mtrapargsString }
- DESCRIPTION
- "SEVERE: Max humidity threshold violated on the probe.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the current humidity
- The fourth argument is the probe number.
- The fifth argument is the probe name."
- --#TYPE "APC ENV: Max humidity threshold violation."
- --#SUMMARY "Max humidity threshold violation."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 363
- envMaxHumidityThresholdViolationCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsProbeStatusProbeHumidity,
- emsProbeStatusProbeIndex, emsProbeStatusProbeName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Max humidity threshold violation cleared on the probe.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the current humidity.
- The fourth argument is the probe number.
- The fifth argument is the probe name."
- --#TYPE "APC ENV: Max humidity threshold violation cleared."
- --#SUMMARY "Max humidity threshold violation cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 364
- envMinHumidityThresholdViolation TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsProbeStatusProbeHumidity,
- emsProbeStatusProbeIndex, emsProbeStatusProbeName, mtrapargsString }
- DESCRIPTION
- "SEVERE: Min humidity threshold violated on the probe.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the current humidity
- The fourth argument is the probe number.
- The fifth argument is the probe name."
- --#TYPE "APC ENV: Min humidity threshold violation."
- --#SUMMARY "Min humidity threshold violation."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 365
- envMinHumidityThresholdViolationCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsProbeStatusProbeHumidity,
- emsProbeStatusProbeIndex, emsProbeStatusProbeName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Min humidity threshold violation cleared on the probe.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the current humidity.
- The fourth argument is the probe number.
- The fifth argument is the probe name."
- --#TYPE "APC ENV: Min humidity threshold violation cleared."
- --#SUMMARY "Min humidity threshold violation cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 366
- envSTIncTempRateViolation TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsProbeStatusProbeTemperature, emsStatusSysTempUnits,
- emsProbeStatusProbeIndex, emsProbeStatusProbeName, mtrapargsString }
- DESCRIPTION
- "SEVERE: Short-term increasing temperature rate violated on the probe.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the current temperature.
- The fourth argument is the temperature scale.
- The fifth argument is the probe number.
- The sixth argument is the probe name."
- --#TYPE "APC ENV: Short-term inc. temp rate violation."
- --#SUMMARY "Short-term inc. temp rate violation."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 367
- envSTIncTempRateViolationCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsProbeStatusProbeTemperature, emsStatusSysTempUnits,
- emsProbeStatusProbeIndex, emsProbeStatusProbeName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Short-term increasing temperature rate cleared on the probe.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the current temperature.
- The fourth argument is the temperature scale.
- The fifth argument is the probe number.
- The sixth argument is the probe name."
- --#TYPE "APC ENV: Short-term inc. temp rate violation cleared."
- --#SUMMARY "Short-term inc. temp rate violation cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 368
- envSTDecTempRateViolation TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsProbeStatusProbeTemperature, emsStatusSysTempUnits,
- emsProbeStatusProbeIndex, emsProbeStatusProbeName, mtrapargsString }
- DESCRIPTION
- "SEVERE: Short-term decreasing temperature rate violated on the probe.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the current temperature.
- The fourth argument is the temperature scale.
- The fifth argument is the probe number.
- The sixth argument is the probe name."
- --#TYPE "APC ENV: Short-term dec. temp rate violation."
- --#SUMMARY "Short-term dec. temp rate violation."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 369
- envSTDecTempRateViolationCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsProbeStatusProbeTemperature, emsStatusSysTempUnits,
- emsProbeStatusProbeIndex, emsProbeStatusProbeName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Short-term decreasing temperature rate cleared on the probe.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the current temperature.
- The fourth argument is the temperature scale.
- The fifth argument is the probe number.
- The sixth argument is the probe name."
- --#TYPE "APC ENV: Short-term dec. temp rate violation cleared."
- --#SUMMARY "Short-term dec. temp rate violation cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 370
- envLTIncTempRateViolation TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsProbeStatusProbeTemperature, emsStatusSysTempUnits,
- emsProbeStatusProbeIndex, emsProbeStatusProbeName, mtrapargsString }
- DESCRIPTION
- "SEVERE: Long-term increasing temperature rate violated on the probe.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the current temperature.
- The fourth argument is the temperature scale.
- The fifth argument is the probe number.
- The sixth argument is the probe name."
- --#TYPE "APC ENV: Long-term inc. temp rate violation."
- --#SUMMARY "Long-term inc. temp rate violation."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 371
- envLTIncTempRateViolationCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsProbeStatusProbeTemperature, emsStatusSysTempUnits,
- emsProbeStatusProbeIndex, emsProbeStatusProbeName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Long-term increasing temperature rate cleared on the probe.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the current temperature.
- The fourth argument is the temperature scale.
- The fifth argument is the probe number.
- The sixth argument is the probe name."
- --#TYPE "APC ENV: Long-term inc. temp rate violation cleared."
- --#SUMMARY "Long-term inc. temp rate violation cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 372
- envLTDecTempRateViolation TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsProbeStatusProbeTemperature, emsStatusSysTempUnits,
- emsProbeStatusProbeIndex, emsProbeStatusProbeName, mtrapargsString }
- DESCRIPTION
- "SEVERE: Long-term decreasing temperature rate violated on the probe.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the current temperature.
- The fourth argument is the temperature scale.
- The fifth argument is the probe number.
- The sixth argument is the probe name."
- --#TYPE "APC ENV: Long-term dec. temp rate violation."
- --#SUMMARY "Long-term dec. temp rate violation."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 373
- envLTDecTempRateViolationCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsProbeStatusProbeTemperature, emsStatusSysTempUnits,
- emsProbeStatusProbeIndex, emsProbeStatusProbeName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Long-term decreasing temperature rate cleared on the probe.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the current temperature.
- The fourth argument is the temperature scale.
- The fifth argument is the probe number.
- The sixth argument is the probe name."
- --#TYPE "APC ENV: Long-term dec. temp rate violation cleared."
- --#SUMMARY "Long-term dec. temp rate violation cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 374
- -- Battery Management System Traps
- bmsCriticalCondition TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "SEVERE: A Battery Management System critical condition was detected.
- The first variable is the error condition text message.
- The second variable is the error number."
- --#TYPE "APC BMS: A critical condition was detected. "
- --#SUMMARY "A critical condition was detected. "
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 375
- bmsCriticalConditionCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A Battery Management System critical condition was cleared.
- The first variable is the error condition text message.
- The second variable is the error number."
- --#TYPE "APC BMS: A critical condition was cleared. "
- --#SUMMARY "A critical condition was cleared. "
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 376
- bmsWarningCondition TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "WARNING: A Battery Management System warning condition was detected.
- The first variable is the error condition text message.
- The second variable is the error number."
- --#TYPE "APC BMS: A warning condition was detected. "
- --#SUMMARY "A warning condition was detected. "
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 377
- bmsWarningConditionCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "WARNING: A Battery Management System warning condition was cleared.
- The first variable is the error condition text message.
- The second variable is the error number."
- --#TYPE "APC BMS: A warning condition was cleared. "
- --#SUMMARY "A warning condition was cleared. "
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 378
- bmsInformationalCondition TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A Battery Management System informational condition was detected.
- The first variable is the error condition text message.
- The second variable is the error number."
- --#TYPE "APC BMS: Informational condition detected. "
- --#SUMMARY "An informational condition was detected. "
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 379
- bmsInformationalConditionCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A Battery Management System informational condition was cleared.
- The first variable is the error condition text message.
- The second variable is the error number."
- --#TYPE "APC BMS: Informational condition was cleared. "
- --#SUMMARY "An informational condition was cleared. "
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 380
- -- xATS Traps
- xATSOutputVoltageLowAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger,
- mtrapargsInteger02, mtrapargsInteger03, mtrapargsString }
- DESCRIPTION
- "SEVERE: The device three-phase output voltage of the device is outside the specified limits.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N, 4=unused, 5=L1-L2, 6=L2-L3, 7=L3-L1).
- The fourth argument is the measured voltage in tenths of Volts.
- The fifth argument is the threshold, in tenths of Volts, from which the alarm was generated."
- --#TYPE "APC XATS: Output low voltage alarm."
- --#SUMMARY "Output voltage is below threshold."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 381
- xATSOutputVoltageLowAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger,
- mtrapargsInteger02, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The devices three-phase output voltage is back within the specified limits.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N, 4=unused, 5=L1-L2, 6=L2-L3, 7=L3-L1).
- The fourth argument is the measured voltage in tenths of Volts."
- --#TYPE "APC XATS: Output low voltage alarm cleared."
- --#SUMMARY "Output low voltage alarm cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 382
- xATSOutputVoltageHighAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger,
- mtrapargsInteger02, mtrapargsInteger03, mtrapargsString }
- DESCRIPTION
- "SEVERE: The device three-phase output voltage of the device is outside the specified limits.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N, 4=unused, 5=L1-L2, 6=L2-L3, 7=L3-L1).
- The fourth argument is the measured voltage in tenths of Volts.
- The fifth argument is the threshold, in tenths of Volts, above which the alarm is generated."
- --#TYPE "APC XATS: Output high voltage alarm."
- --#SUMMARY "Output voltage is above threshold."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 383
- xATSOutputVoltageHighAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger,
- mtrapargsInteger02, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The devices three-phase output voltage is back within the specified limits.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N, 4=unused, 5=L1-L2, 6=L2-L3, 7=L3-L1).
- The fourth argument is the measured voltage in tenths of Volts."
- --#TYPE "APC XATS: Output high voltage alarm cleared."
- --#SUMMARY "Output high voltage alarm cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 384
- xATSOutputCurrentLowAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger,
- mtrapargsInteger02, mtrapargsInteger03, mtrapargsString }
- DESCRIPTION
- "SEVERE: The three-phase load current of the device is outside the specified limits.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the phase (1=L1, 2=L2, 3=L3).
- The fourth argument is the measured current in Amps.
- The fifth argument is the threshold, in Amps, from which the alarm was generated."
- --#TYPE "APC XATS: Output low current alarm."
- --#SUMMARY "Output current is below threshold."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 385
- xATSOutputCurrentLowAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger,
- mtrapargsInteger02, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The three-phase load current of the device is back within the specified limits.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the phase (1=L1, 2=L2, 3=L3).
- The fourth argument is the measured current in Amps."
- --#TYPE "APC XATS: Output low current alarm cleared."
- --#SUMMARY "Output low current alarm cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 386
- xATSOutputCurrentHighAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger,
- mtrapargsInteger02, mtrapargsInteger03, mtrapargsString }
- DESCRIPTION
- "SEVERE: The three-phase output load current of the device is outside the specified limits.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the phase (1=L1, 2=L2, 3=L3).
- The fourth argument is the measured current in Amps.
- The fifth argument is the threshold, in Amps, from which the alarm was generated."
- --#TYPE "APC XATS: Output high current alarm."
- --#SUMMARY "Output current is above threshold."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 387
- xATSOutputCurrentHighAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger,
- mtrapargsInteger02, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The three-phase output load current of the device is back within the specified limits.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the phase (1=L1, 2=L2, 3=L3).
- The fourth argument is the measured current in Amps."
- --#TYPE "APC XATS: Output high current alarm cleared."
- --#SUMMARY "Output high current alarm cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 388
- xATSOutputFrequencyAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger,
- mtrapargsInteger02, mtrapargsString }
- DESCRIPTION
- "SEVERE: The devices output frequency is outside the specified limits.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the frequency deviation from the nominal in tenths of Hertz.
- The fourth argument is the frequency deviation threshold in tenths of Hertz,
- from which the alarm was generated."
- --#TYPE "APC XATS: Output frequency out-of-range alarm."
- --#SUMMARY "Output frequency is out-of-range."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 389
- xATSOutputFrequencyAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The devices output frequency is back within the specified limits.
- The first argument is the host device serial number.
- The second argument is the host device name."
- --#TYPE "APC XATS: Output frequency back in range."
- --#SUMMARY "Output frequency in range."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 390
- xATSInternalCommError TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
- DESCRIPTION
- "SEVERE: There is an internal communication error in the device.
- The first argument is the host device serial number.
- The second argument is the host device name."
- --#TYPE "APC XATS: Internal communication error."
- --#SUMMARY "Internal communication error."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 391
- xATSInternalCommErrorCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Internal communication has been restored.
- The first argument is the host device serial number.
- The second argument is the host device name."
- --#TYPE "APC XATS: Internal Communication error cleared."
- --#SUMMARY "ATS Communication error cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 392
- xATSDataCommMismatchError TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
- DESCRIPTION
- "SEVERE: A data incompatibility exists within the device. This
- is typically the result of mismatches between firmware revisions
- of the transfer switch controller and the Network Management interface.
- The first argument is the host device serial number.
- The second argument is the host device name."
- --#TYPE "APC XATS: Data mismatch error."
- --#SUMMARY "ATS data mismatch error."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 393
- xATSDataCommMismatchErrorCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The internal data incompatibility has been resolved.
- The first argument is the host device serial number.
- The second argument is the host device name."
- --#TYPE "APC XATS: data mismatch error cleared."
- --#SUMMARY "ATS data mismatch error cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 394
- xATSGenCommLost TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
- DESCRIPTION
- "WARNING: The XATS cannot communicate with the generator.
- This will make unavailable all the xATSGenerator OIDs.
- The first argument is the host device serial number.
- The second argument is the host device name."
- --#TYPE "APC XATS: No communication with generator."
- --#SUMMARY "ATS/Generator communication lost."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 395
- xATSGenCommEstablished TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The XATS has established communication with the generator.
- The first argument is the host device serial number.
- The second argument is the host device name."
- --#TYPE "APC XATS: Communication with generator established."
- --#SUMMARY "ATS/generator communication established."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 396
-
- xATSNeutralPosition TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger,
- mtrapargsString }
- DESCRIPTION
- "WARNING: XATS has transferred to neutral position.
- In this position neither Source 1 nor Source 2 is selected,
- and the XATS will have no output voltage.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the mode in which the switch is operating
- (1=Auto, 2=Not-in-Auto, Abnormal Condition 3=Not-in-Auto, manual)."
- --#TYPE "APC XATS: Transferred to the neutral (no output power) position."
- --#SUMMARY "Transferred to neutral."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 397
- xATSSwitchTransferEvent TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger,
- mtrapargsInteger02, mtrapargsInteger03, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: XATS has transferred from one source to the other.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the mode in which the switch is operating.
- (1=Auto, 2=Not-in-Auto, Abnormal Condition 3=Not-in-Auto, manual).
- The fourth argument is the input source selected (1=Source 1, 2=Source 2).
- The fifth argument is type of transfer that took place. (1=Closed, 2=Open, 3=Unknown)"
- --#TYPE "APC XATS: Transferred from Source-X to Source-Y."
- --#SUMMARY "Source-to-Source transfer."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 398
- xATSInternalATSFault TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "SEVERE: An internal XATS fault has been detected.
- The XATS may have forced itself to not-in-auto mode (abnormal condition),
- as indicated by the xATSSwitchStatusAutoSwitchOperationalMode OID.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument indicates the detected fault.
- 1=Cannot Close S1
- 2=Cannot Close S2
- 3=Cannot Open S1
- 4=Cannot Open S2
- 5=Cannot Trip Open S1
- 6=Cannot Trip Open S2
- 7=Start Contact Failure
- 8=Voltage Sensing Failure"
- --#TYPE "APC XATS: Internal fault detected."
- --#SUMMARY "ATS internal fault detected."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 399
- xATSInternalATSFaultCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The detected internal XATS fault has been cleared.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument indicates the detected fault.
- 1=Cannot Close S1
- 2=Cannot Close S2
- 3=Cannot Open S1
- 4=Cannot Open S2
- 5=Cannot Trip Open S1
- 6=Cannot Trip Open S2
- 7=Start Contact Failure
- 8=Voltage Sensing Failure"
- --#TYPE "APC XATS: Internal fault cleared."
- --#SUMMARY "ATS internal fault cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 400
- xATSEngineStartAsserted TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The XATS has asserted the Engine Start contact.
- This should result in the generator producing output voltage.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument indicates the reason that the start signal was asserted
- 1=Unknown, 2=S1 Low Voltage, 3=S1 High Voltage, 4=S1 Line Imbalance,
- 5=S1 Freq Range, 6=S1 Bad Rotation."
- --#TYPE "APC XATS: Engine Start signal asserted."
- --#SUMMARY "Engine Start asserted."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 401
- xATSEngineStopAsserted TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The XATS has de-asserted the Engine Start contact.
- This should result in the generator shutting down, and producing no output voltage.
- The first argument is the host device serial number.
- The second argument is the host device name."
- --#TYPE "APC XATS: Engine Stop signal asserted."
- --#SUMMARY "Engine Stop asserted."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 402
- xATSStartFailure TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "SEVERE: The generator failed to start. After assertion of the
- Engine Start signal, the quality of Source 2 was not seen as good.
- This alarm can be cleared using the xATSSwitchStatusClearLatchedAlarms OID.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument indicates the line quality at S2
- 1=Unknown, 2=S2 Low Voltage, 3=S2 High Voltage, 4=S2 Line Imbalance,
- 4=S2 Freq Range, 5=S2 Bad Rotation."
- --#TYPE "APC XATS: Generator failed to start alarm."
- --#SUMMARY "Generator failed to start."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 403
- xATSStopFailure TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
- DESCRIPTION
- "WARNING: The generator failed to stop. After de-assertion of the
- Engine Start signal, the quality of Source 2 continued to be seen as good.
- This alarm can be cleared using the xATSSwitchStatusClearLatchedAlarms OID.
- The first argument is the host device serial number.
- The second argument is the host device name."
- --#TYPE "APC XATS: Generator failed to stop alarm."
- --#SUMMARY "Generator failed to stop."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 404
- xATSNotInAutomaticMode TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
- DESCRIPTION
- "SEVERE: Automatic Transfer Switch is not in automatic mode.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The xATSSwitchStatusAutoSwitchStatus OID and the
- xATSSwitchStatusAutoSwitchOperationalMode OID
- can provide more information about the state of the XATS."
- --#TYPE "APC XATS: XATS is not-in-automatic mode."
- --#SUMMARY "ATS not in auto."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 405
- xATSNotInAutomaticModeCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Automatic Transfer Switch is in automatic mode.
- The first argument is the host device serial number.
- The second argument is the host device name."
- --#TYPE "APC XATS: XATS in auto mode."
- --#SUMMARY "ATS in auto mode."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 406
- xATSEpoTripped TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
- DESCRIPTION
- "SEVERE: The device's Emergency Power Off (EPO) circuit is tripped.
- The first argument is the host device serial number.
- The second argument is the host device name."
- --#TYPE "APC XATS: Emergency Power Off (EPO) tripped."
- --#SUMMARY "EPO tripped."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 407
- xATSEpoReset TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The device's Emergency Power Off (EPO) circuit has been
- reset to the armed position.
- The first argument is the host device serial number.
- The second argument is the host device name."
- --#TYPE "APC XATS: Emergency Power Off (EPO) reset."
- --#SUMMARY "EPO armed."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 408
- xATSEpoTestMode TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
- DESCRIPTION
- "WARNING: The device's Emergency Power Off (EPO) circuit has been
- switched back to the test position.
- The first argument is the host device serial number.
- The second argument is the host device name."
- --#TYPE "APC XATS: Emergency Power Off (EPO) in test mode."
- --#SUMMARY "EPO disabled."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 409
- xATSEpoArmed TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The device's Emergency Power Off (EPO) circuit has been
- switched back to the armed position.
- The first argument is the host device serial number.
- The second argument is the host device name."
- --#TYPE "APC XATS: Emergency Power Off (EPO) enabled."
- --#SUMMARY "EPO armed."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 410
- xATSTestInitiated TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A scheduled test has been initiated.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the type of test initiated (1=scheduled, 2=manual)."
- --#TYPE "APC XATS: Test initiated."
- --#SUMMARY "Test initiated."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 411
- xATSTestCanceled TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The scheduled test has been canceled
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the type of test initiated (1=scheduled, 2=manual)."
- --#TYPE "APC XATS: Test canceled."
- --#SUMMARY "Test canceled."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 412
- xATSTestFailed TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
- DESCRIPTION
- "SEVERE: The initiated test has failed.
- This alarm can be cleared using the xATSSwitchStatusClearLatchedAlarms OID.
- The first argument is the host device serial number.
- The second argument is the host device name."
- --#TYPE "APC XATS: Initiated test failed."
- --#SUMMARY "Initiated test failed."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 413
- xATSTestPassed TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The initiated test has passed
- switched back to the armed position.
- The first argument is the host device serial number.
- The second argument is the host device name."
- --#TYPE "APC XATS: Initiated test passed."
- --#SUMMARY "Initiated test passed."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 414
- xATSInputContactStateAbnormal TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger,
- mtrapargsString02, mtrapargsInteger02, mtrapargsInteger03, mtrapargsString }
- DESCRIPTION
- "SEVERE: A user input contact on the device has changed to its abnormal state.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the input contact number.
- The fourth argument is the input contact name.
- The fifth argument is the input contact state (1=OPEN, 2=CLOSED).
- The sixth argument is the configured normal input contact state (1=OPEN, 2=CLOSED)."
- --#TYPE "APC XATS: Input contact has changed to its abnormal state."
- --#SUMMARY "Input contact has changed to its abnormal state."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 415
- xATSInputContactStateNormal TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger,
- mtrapargsString02, mtrapargsInteger02, mtrapargsInteger03, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A user input contact on the device has changed to its normal state.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the input contact number.
- The fourth argument is the input contact name.
- The fifth argument is the input contact state (1=OPEN, 2=CLOSED).
- The sixth argument is the configured normal input contact state (1=OPEN, 2=CLOSED)."
- --#TYPE "APC XATS: Input contact has changed to its normal state."
- --#SUMMARY "Input contact has changed to its normal state."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 416
- xATSRemoteStartContactMismatch TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
- DESCRIPTION
- "SEVERE: The state of the generator's Remote Start input
- and the ATS's Engine Start output do not match.
- This indicates something wrong in the Engine Start wiring,
- which must be corrected. This condition will prevent the
- generator from being started when needed.
- (See also: xATSGeneratorStatusRemoteStart
- and xATSSwitchStatusEngineStartSignal OIDs)
- The first argument is the host device serial number.
- The second argument is the host device name."
- --#TYPE "APC XATS: Generator/ATS start contact mismatch."
- --#SUMMARY "Generator/ATS start contact mismatch."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 417
- xATSRemoteStartContactMismatchCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Mismatch in the state of the generator's
- Remote Start input and the ATS's Engine Start output as been resolved.
- This indicates something wrong in the Engine Start wiring,
- which must be corrected. This condition will prevent the
- generator from being started when needed.
- (See also: xATSGeneratorStatusRemoteStart
- and xATSSwitchStatusEngineStartSignal OIDs)
- The first argument is the host device serial number.
- The second argument is the host device name."
- --#TYPE "APC XATS: Generator/ATS start contact mismatch cleared."
- --#SUMMARY "Generator/ATS start contact mismatch cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 418
- xATSDoorOpenAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
- DESCRIPTION
- "WARNING: The XATS exterior panel door is open.
- The first argument is the host device serial number.
- The second argument is the host device name."
- --#TYPE "APC XATS: Panel door is open alarm."
- --#SUMMARY "Panel door open alarm."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 419
- xATSDoorOpenAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The external door to the device is closed.
- The first argument is the host device serial number.
- The second argument is the host device name."
- --#TYPE "APC XATS: Panel door open alarm cleared."
- --#SUMMARY "Panel door open alarm cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 420
- xATSDCBackupAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
- DESCRIPTION
- "WARNING: The XATS's DC backup has been lost. The XATS will lose power
- on Source 1 failure, causing the Engine Start signal to be asserted.
- The XATS will then restart from Source 2.
- The first argument is the host device serial number.
- The second argument is the host device name."
- --#TYPE "APC XATS: DC backup failure."
- --#SUMMARY "ATS DC backup failure."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 421
- xATSDCBackupAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: DC backup alarm has been cleared in the device.
- The first argument is the host device serial number.
- The second argument is the host device name."
- --#TYPE "APC XATS: DC backup alarm cleared."
- --#SUMMARY "DC backup alarm cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 422
- -- xATS Generator Traps
- xATSGeneratorLowCoolantLevelAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "SEVERE: Low coolant level has been detected in the generator.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the OEM's fault/event code."
- --#TYPE "APC XGEN: Generator low coolant level alarm."
- --#SUMMARY "Generator low coolant level alarm."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 423
- xATSGeneratorLowCoolantLevelAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The detected low coolant level has been cleared in the generator.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the OEM's fault/event code."
- --#TYPE "APC XGEN: Generator low coolant level alarm cleared."
- --#SUMMARY "Generator low coolant level alarm cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 424
- xATSGeneratorVeryLowCoolantLevelAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "SEVERE: Very low coolant level has been detected in the generator.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the OEM's fault/event code."
- --#TYPE "APC XGEN: Generator very low coolant level alarm."
- --#SUMMARY "Generator very low coolant level alarm."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 425
- xATSGeneratorVeryLowCoolantLevelAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The detected Very low coolant level has been cleared in the generator.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the OEM's fault/event code."
- --#TYPE "APC XGEN: Generator very low coolant level alarm cleared."
- --#SUMMARY "Generator very low coolant level alarm cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 426
- xATSGeneratorHighCoolantTempAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "SEVERE: High coolant temperature has been detected in the generator.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the OEM's fault/event code."
- --#TYPE "APC XGEN: Generator high coolant temperature alarm."
- --#SUMMARY "Generator high coolant temperature alarm."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 427
- xATSGeneratorHighCoolantTempAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The detected high coolant temperature has been cleared in the generator.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the OEM's fault/event code."
- --#TYPE "APC XGEN: Generator high coolant temperature alarm cleared."
- --#SUMMARY "Generator high coolant temperature alarm cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 428
- xATSGeneratorVeryHighCoolantTempAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "SEVERE: Very high coolant temperature has been detected in the generator.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the OEM's fault/event code."
- --#TYPE "APC XGEN: Generator very high coolant temperature alarm."
- --#SUMMARY "Generator very high coolant temperature alarm."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 429
- xATSGeneratorVeryHighCoolantTempAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The Very high coolant temperature condition has been cleared in the generator.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the OEM's fault/event code."
- --#TYPE "APC XGEN: Generator very high coolant temperature alarm cleared."
- --#SUMMARY "Generator very high coolant temperature alarm cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 430
- xATSGeneratorLowCoolantTempAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "WARNING: Low coolant temperature has been detected in the generator.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the OEM's fault/event code."
- --#TYPE "APC XGEN: Generator low coolant temperature alarm."
- --#SUMMARY "Generator low coolant temperature alarm."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 431
- xATSGeneratorLowCoolantTempAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The low coolant temperature condition has been cleared in the generator.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the OEM's fault/event code."
- --#TYPE "APC XGEN: Generator low coolant temperature alarm cleared."
- --#SUMMARY "Generator low coolant temperature alarm cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 432
- xATSGeneratorLowOilLevelAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "SEVERE: Low oil level has been detected in the generator.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the OEM's fault/event code."
- --#TYPE "APC XGEN: Generator low oil level alarm."
- --#SUMMARY "Generator low oil level alarm."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 433
- xATSGeneratorLowOilLevelAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Low oil level alarm has been cleared in the generator.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the OEM's fault/event code."
- --#TYPE "APC XGEN: Generator low oil level alarm cleared."
- --#SUMMARY "Generator low oil level alarm cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 434
-
- xATSGeneratorLowBatteryVoltDuringCrankAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "SEVERE: The generator's battery voltage has been detected
- as low while cranking the engine.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the OEM's fault/event code."
- --#TYPE "APC XGEN: Low batt. voltage while cranking alarm."
- --#SUMMARY "Generator low battery volts while cranking alarm."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 435
- xATSGeneratorLowBatteryVoltDuringCrankAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The generator's low battery voltage while
- cranking condition has been cleared.
- The second argument is the host device name.
- The third argument is the OEM's fault/event code."
- --#TYPE "XGEN: Generator low batt. voltage while cranking alarm cleared."
- --#SUMMARY "Generator low battery volts while cranking alarm cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 436
- xATSGeneratorVeryLowBatteryVoltDuringCrankAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "SEVERE: The generator's battery voltage has been detected
- as very low while cranking the engine.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the OEM's fault/event code."
- --#TYPE "XGEN: Generator v.low battery voltage while cranking alarm."
- --#SUMMARY "Generator v.low battery volts while cranking alarm."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 437
- xATSGeneratorVeryLowBatteryVoltDuringCrankAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The generator's high battery voltage while
- cranking condition has been cleared.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the OEM's fault/event code."
- --#TYPE "XGEN: Generator v.low batt volt, while cranking alarm cleared."
- --#SUMMARY "Generator v.low battery volts while cranking alarm cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 438
- xATSGeneratorEStop TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsInteger02, mtrapargsString }
- DESCRIPTION
- "SEVERE: The generator's emergency stop input has been activated.
- After the emergency stop signal has been removed, the E-Stop condition
- must be cleared before the generator can be started again.
- E-Stop conditions can only be cleared via the generator front panel.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the OEM's fault/event code.
- The fourth argument is the type of E-Stop (1=LOCAL, 2=REMOTE)."
- --#TYPE "APC XGEN: Generator emergency stop engaged."
- --#SUMMARY "Generator emergency stop engaged."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE NONOPERATIONAL
- ::= 439
- xATSGeneratorEStopCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsInteger02, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The generator's emergency stop condition has been cleared.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the OEM's fault/event code.
- The fourth argument is the type of E-Stop (1=LOCAL, 2=REMOTE)."
- --#TYPE "APC XGEN: Generator emergency stop condition cleared."
- --#SUMMARY "Generator emergency stop condition cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 440
- xATSGeneratorHighBatteryVolt TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "WARNING: The generator's battery voltage has been detected as high.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the OEM's fault/event code."
- --#TYPE "APC XGEN: Generator high battery voltage."
- --#SUMMARY "Generator high battery volts."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 441
- xATSGeneratorHighBatteryVoltCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The detected high battery voltage has been cleared, on the generator.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the OEM's fault/event code."
- --#TYPE "APC XGEN: Generator high battery voltage condition cleared."
- --#SUMMARY "Generator high battery volts condition cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 442
- xATSGeneratorLowBatteryVolt TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "SEVERE: The generator's battery voltage has been detected as low.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the OEM's fault/event code."
- --#TYPE "APC XGEN: Generator low battery voltage."
- --#SUMMARY "Generator low battery volts."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 443
- xATSGeneratorLowBatteryVoltCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The detected low battery voltage has been cleared, on the generator.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the OEM's fault/event code."
- --#TYPE "APC XGEN: Generator low battery voltage condition cleared."
- --#SUMMARY "Generator low battery volts condition cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 444
- xATSGeneratorControlSwitchNotAuto TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "SEVERE: The control switch on the generator is not in auto position.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the OEM's fault/event code."
- --#TYPE "APC XGEN: Generator not-in-automatic mode."
- --#SUMMARY "Generator not-in-auto."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 445
- xATSGeneratorControlSwitchNotAutoCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The control switch on the generator is in auto position.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the OEM's fault/event code."
- --#TYPE "APC XGEN: Generator automatic mode restored."
- --#SUMMARY "Generator not-in-auto cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 446
- xATSGeneratorLowOilPressure TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "SEVERE: The generator's oil pressure has been detected as low.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the OEM's fault/event code."
- --#TYPE "APC XGEN: Generator low oil pressure."
- --#SUMMARY "Generator low oil pressure."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 447
- xATSGeneratorLowOilPressureCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The detected low oil pressure has been cleared, on the generator.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the OEM's fault/event code."
- --#TYPE "APC XGEN: Generator low oil pressure condition cleared."
- --#SUMMARY "Generator low oil pressure condition cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 448
- xATSGeneratorVeryLowOilPressure TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "SEVERE: The generator's oil pressure has been detected as very low.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the OEM's fault/event code."
- --#TYPE "APC XGEN: Generator v.low oil pressure."
- --#SUMMARY "Generator v.low oil pressure."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 449
- xATSGeneratorVeryLowOilPressureCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The detected v.low oil pressure has been cleared, on the generator.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the OEM's fault/event code."
- --#TYPE "APC XGEN: Generator v.low oil pressure condition cleared."
- --#SUMMARY "Generator v.low oil pressure condition cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 450
- xATSGeneratorOverload TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "SEVERE: The generator is overloaded.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the OEM's fault/event code."
- --#TYPE "APC XGEN: Generator is in overload event."
- --#SUMMARY "Generator on overload event."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 451
- xATSGeneratorOverloadCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The generator is running within loading limits.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the OEM's fault/event code."
- --#TYPE "APC XGEN: Generator is in overload event cleared."
- --#SUMMARY "Generator on overload event cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 452
- xATSGeneratorLowACVEvent TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "SEVERE: The generator AC voltage is outside the acceptable bounds.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the OEM's fault/event code."
- --#TYPE "APC XGEN: State of the Generator AC voltage."
- --#SUMMARY " State of the Generator AC voltage."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 453
- xATSGeneratorLowACVEventCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The generator AC voltage is within normal bounds.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the OEM's fault/event code."
- --#TYPE "APC XGEN: State of the Generator AC voltage cleared."
- --#SUMMARY "State of the Generator AC voltage cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 454
- xATSGeneratorHighACVEvent TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "SEVERE: The generator AC voltage is outside the acceptable bounds.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the OEM's fault/event code."
- --#TYPE "APC XGEN: State of the Generator AC voltage."
- --#SUMMARY " State of the Generator AC voltage."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 455
- xATSGeneratorHighACVEventCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The generator AC voltage is within normal bounds.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the OEM's fault/event code."
- --#TYPE "APC XGEN: State of the Generator AC voltage cleared."
- --#SUMMARY "State of the Generator AC voltage cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 456
- xATSGeneratorOverspeed TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "SEVERE: The generator is running over the acceptable RPM.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the OEM's fault/event code."
- --#TYPE "APC XGEN: Generator overspeed condition."
- --#SUMMARY "Generator overspeed condition."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 457
- xATSGeneratorOverspeedCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The generator overspeed shutdown has been cleared.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the OEM's fault/event code."
- --#TYPE "APC XGEN: Generator overspeed condition cleared."
- --#SUMMARY "Generator overspeed condition cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 458
- xATSGeneratorEngineCold TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "SEVERE: The generator engine is cold, may not start.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the OEM's fault/event code."
- --#TYPE "APC XGEN: Generator engine is cold, may not start."
- --#SUMMARY "Generator engine is cold."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 459
- xATSGeneratorEngineColdCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The engine is not cold to start.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the OEM's fault/event code."
- --#TYPE "APC XGEN: Engine is cold to start condition cleared."
- --#SUMMARY "Engine is cold to start condition cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 460
- xATSGeneratorOutputBreakerOpen TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "SEVERE: The generators output breaker has been detected as open.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the OEM's fault/event code."
- --#TYPE "APC XGEN: Generator output breaker open alarm."
- --#SUMMARY "Generator output breaker open."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE NONOPERATIONAL
- ::= 461
- xATSGeneratorOutputBreakerOpenCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The engine is not cold to start.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the OEM's fault/event code."
- --#TYPE "APC XGEN: Generator output breaker open alarm cleared."
- --#SUMMARY "Generator output breaker open cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 462
- xATSGeneratorLowFuelLevelAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "WARNING: The tank fuel level is below the limits specified
- in the xATSGeneratorFuelSystemLowFuelLevelThreshold OID.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the measured fuel level in percent of full."
- --#TYPE "APC XGEN: Low fuel level alarm."
- --#SUMMARY "Generator low fuel level alarm."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 463
- xATSGeneratorLowFuelLevelAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The tank fuel level is back above the specified limit.
- The first argument is the host device serial number.
- The second argument is the host device name."
- --#TYPE "APC XGEN: Low fuel level alarm cleared."
- --#SUMMARY "Generator low fuel level alarm cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 464
- xATSGeneratorVeryLowFuelLevelAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "SEVERE: The tank fuel level is below the low threshold limits.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the measured tank fuel level in percent of full."
- --#TYPE "APC XGEN: Very Low fuel level alarm."
- --#SUMMARY "Generator very low fuel level alarm."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 465
- xATSGeneratorVeryLowFuelLevelAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The detected low tank level has been cleared in the device.
- The first argument is the host device serial number.
- The second argument is the host device name."
- --#TYPE "APC XGEN: Very low fuel level alarm cleared."
- --#SUMMARY "Generator very low fuel level alarm cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 466
- xATSGeneratorLowRunTimeAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "WARNING: The estimated runtime is below the limits specified.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the estimated runtime in hours."
- --#TYPE "APC XGEN: Low run time alarm."
- --#SUMMARY "Generator low run time alarm."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 467
- xATSGeneratorLowRunTimeAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The detected low runtime has been cleared in the device.
- The first argument is the host device serial number.
- The second argument is the host device name."
- --#TYPE "APC XGEN: Low run time alarm cleared."
- --#SUMMARY "Generator low run time alarm."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 468
- xATSGeneratorVeryLowRunTimeAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "SEVERE: The estimated runtime is below the limits specified
- in the xATSGeneratorFuelSystemVeryLowRunTimeThreshold OID.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the estimated runtime in hours."
- --#TYPE "APC XGEN: Very low run time alarm."
- --#SUMMARY "Generator very low run time alarm."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 469
- xATSGeneratorVeryLowRunTimeAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The detected low runtime has been cleared in the device.
- The first argument is the host device serial number.
- The second argument is the host device name."
- --#TYPE "APC XGEN: Very low run time alarm cleared."
- --#SUMMARY "Generator very low run time alarm."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 470
- xATSGeneratorServiceDueAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
- DESCRIPTION
- "WARNING: The generator is due for scheduled service.
- Generation of this alarm is based on calendar days since
- and/or actual generator run-hours since last service.
- This alarm is cleared using the xATSGeneratorServiceResetRecord OID.
- (See also: xATSGeneratorServiceCalendarIntervalThreshold
- and xATSGeneratorServiceRunHoursThreshold OIDs)
- The first argument is the host device serial number.
- The second argument is the host device name."
- --#TYPE "APC XATS: Generator scheduled maintenance is due."
- --#SUMMARY "Generator maintenance due."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 471
- xATSGeneratorServiceDueAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The generator's service registers have been reset.
- The first argument is the host device serial number.
- The second argument is the host device name."
- --#TYPE "APC XATS: Generator service due alarm is cleared."
- --#SUMMARY "Generator service alarm is cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 472
- xATSGeneratorShutdown TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "SEVERE: The generator is shutdown.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the OEM's fault/event code."
- --#TYPE "APC XGEN: Generator shutdown."
- --#SUMMARY "Generator shutdown"
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 473
- xATSGeneratorShutdownCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The generator shutdown alarm is cleared.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the OEM's fault/event code."
- --#TYPE "APC XGEN: Generator shutdown is cleared."
- --#SUMMARY "Generator shutdown is cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 474
- xATSGeneratorBatteryCharger TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "SEVERE: The generator battery charger is nonfunctional.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the OEM's fault/event code."
- --#TYPE "APC XGEN: Generator batt. charger is nonfunctional."
- --#SUMMARY "Generator battery charger is nonfunctional"
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 475
- xATSGeneratorBatteryChargerCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Fault in the generator battery charger is cleared.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the OEM's fault/event code."
- --#TYPE "APC XGEN: Fault in the generator battery charger is cleared."
- --#SUMMARY "Fault in the generator battery charger is cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 476
- xATSGeneratorGenericEvent TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "WARNING: Any generic generator event.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the OEM's fault/event code."
- --#TYPE "APC XGEN: Generator generic event."
- --#SUMMARY "Generator generic event."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 477
- xATSGeneratorGenericEventCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Generated generic generator event is cleared.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the OEM's fault/event code."
- --#TYPE "APC XGEN: Generic generator event is cleared."
- --#SUMMARY "Generic generator event is cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 478
- -- xPDU Traps (part 2)
- xPDUInternalCommErrorCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Internal communication has been restored.
- The first argument is the host device serial number.
- The second argument is the host device name."
- --#TYPE "APC XPDU: Internal Communication error cleared."
- --#SUMMARY "Communication error cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 479
- xPDUSystemStateAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName,
- mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "SEVERE: The PDU's breakers (Q1, Q2 & Q3) are in a configuration that might lead
- to system unavailability. it may signify a temporary condition, when the breakers
- are placed in an atypical manner as the user transitions to (UPS OPERATION or MAINTENANCE BYPASS)
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the type of state change (1=NO UPS INPUT, 2=NO PANEL FEED, 3=ATYPICAL BYPASS MODE).
- note: The NO_PANEL_FEED alarm is applicable only for PDUs with system bypass."
- --#TYPE "APC XPDU: System state change alarm."
- --#SUMMARY "PDU state change alarm."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 480
- xPDUSystemStateAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName,
- mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The PDU's breakers (Q1, Q2 & Q3) are set in a configuration
- that is a non-alarm state.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the type of state change (1=NO UPS INPUT, 2=NO PANEL FEED, 3=ATYPICAL BYPASS MODE).
- note: The NO_PANEL_FEED alarm is applicable only for PDUs with system bypass."
- --#TYPE "APC XPDU: Normal system state change."
- --#SUMMARY "PDU normal state change."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 481
- xPDUEpoTestMode TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsString }
- DESCRIPTION
- "WARNING: The device's Emergency Power Off (EPO) circuit has been
- switched back to the test position.
- The first argument is the host device serial number.
- The second argument is the host device name."
- --#TYPE "APC XPDU: Emergency Power Off (EPO) in test mode."
- --#SUMMARY "EPO disabled."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 482
- xPDUEpoArmed TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The device's Emergency Power Off (EPO) circuit has been
- switched back to the armed position.
- The first argument is the host device serial number.
- The second argument is the host device name."
- --#TYPE "APC XPDU: Emergency Power Off (EPO) enabled."
- --#SUMMARY "EPO armed."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 483
- xPDUFuseBlownAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName,
- mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "SEVERE: One or more fuses in this PDU have been detected as open.
- These fuses are in the feed to the UPS associated with this PDU.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the phase (1=L1, 2=L2, 3=L3)."
- --#TYPE "APC XPDU: Check fuse alarm."
- --#SUMMARY "Fuse detected opened."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 484
- xPDUFuseBlownAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName,
- mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A previous check fuse alarm in this PDU has cleared.
- These fuses are in the feed to the UPS associated with this PDU.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the phase (1=L1, 2=L2, 3=L3)."
- --#TYPE "APC XPDU: Check fuse alarm cleared."
- --#SUMMARY "Fuse alarm cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 485
- xPDUBreakerPositionAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName,
- mtrapargsInteger, mtrapargsInteger02, mtrapargsString }
- DESCRIPTION
- "SEVERE: A PDU breaker is in a state that compromises system availability.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the breaker (1=MAIN INPUT, 2=BYPASS INPUT, 3=CROSS TIE, 4=OUTPUT).
- note: The OUTPUT breaker position alarm is applicable only for PDUs with no system bypass.
- The fourth argument is the breaker position (1=OPEN, 2=CLOSED)."
- --#TYPE "APC XPDU: Breaker position alarm."
- --#SUMMARY "Breaker position alarm."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 486
- xPDUBreakerPositionAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName,
- mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A PDU breaker is no longer in a state that compromises system availability.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the breaker (1=MAIN INPUT, 2=BYPASS INPUT, 3=CROSS TIE, 4=OUTPUT).
- note: The OUTPUT breaker position alarm cleared is applicable only for PDUs with no system bypass."
- --#TYPE "APC XPDU: Breaker position alarm cleared."
- --#SUMMARY "Breaker alarm cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 487
- xPDUBreakerChangeEvent TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
- mtrapargsInteger02, mtrapargsInteger03, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A system breaker or switch within the device has changed state.
- They are generated when any of the Q1, Q2 or Q3 breakers have changed states.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the breaker that has changed
- (1=UPS FEED (Q1), 2=UPS OUTPUT(Q2), 3=MAINTENANCE BYPASS (Q3).
- The fourth argument is the state of the breaker that has changed (1=OPEN, 2=CLOSED).
- The fifth argument is a 8-bit field representing the state of all breakers in the system,
- when any of one of the Q1, Q2 or Q3 breakers have changed state.
- The bit map is represented in the following manner (b7, b6 ... b0)
- b0 - UPS FEED (Q1)
- b1 - MAINTENANCE BYPASS (Q3)
- b2 - UPS OUTPUT (Q2)
- b3 - MAIN INPUT
- b4 - BYPASS INPUT
- b5 - CROSS-TIE OUTPUT
- Example: value of 60 (0x3C) indicates that the CROSS_TIE, BYPASS and MAIN INPUT, and Q2 breakers
- are CLOSED and Q3, Q1 breakers are OPEN."
- --#TYPE "APC XPDU: Breaker/switch change event."
- --#SUMMARY "Breaker/switch change event."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 488
- xPDUDataCommMismatchError TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsString }
- DESCRIPTION
- "SEVERE: A data incompatibility exists within the device. This
- is typically the result of mismatches between firmware revisions
- of the transfer switch controller and the Network Management interface.
- The first argument is the host device serial number.
- The second argument is the host device name."
- --#TYPE "APC XPDU: Data mismatch error."
- --#SUMMARY "XPDU data mismatch error."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 489
- xPDUDataCommMismatchErrorCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The internal data incompatibility has been resolved.
- The first argument is the host device serial number.
- The second argument is the host device name."
- --#TYPE "APC XPDU: data mismatch error cleared."
- --#SUMMARY "XPDU data mismatch error cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 490
- xPDUSystemInMaintenanceBypassMode TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsString }
- DESCRIPTION
- "WARNING: The PDU state has changed to maintenance bypass mode.
- The first argument is the host device serial number.
- The second argument is the host device name."
- --#TYPE "APC XPDU: System state changed to maintenance bypass."
- --#SUMMARY "PDU state changed to maintenance bypass."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 491
- xPDUSystemInUPSOperationalMode TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The PDU state has changed to UPS operational mode.
- The first argument is the host device serial number.
- The second argument is the host device name."
- --#TYPE "APC XPDU: System state changed to UPS operational."
- --#SUMMARY "PDU state changed to UPS operational."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 492
- xATSGeneratorFuelTankRuptureAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "WARNING: Detected a rupture in the inner wall of the generator fuel tank.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the OEM's fault/event code."
- --#TYPE "APC XGEN: Generator inner wall rupture alarm."
- --#SUMMARY "Generator inner wall rupture alarm."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 493
- xATSGeneratorFuelTankRuptureAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The rupture in the inner wall of the generator is not detected.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the OEM's fault/event code."
- --#TYPE "APC XGEN: Generator inner wall rupture alarm cleared."
- --#SUMMARY "Generator inner wall rupture alarm cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 494
- xATSGeneratorGroundFaultAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "SEVERE: Generator ground fault alarm.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the OEM's fault/event code."
- --#TYPE "APC XGEN: Generator ground fault alarm."
- --#SUMMARY "Generator ground fault alarm."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 495
- xATSGeneratorGroundFaultAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Generator ground fault alarm cleared.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the OEM's fault/event code."
- --#TYPE "APC XGEN: Generator ground fault alarm cleared."
- --#SUMMARY "Generator ground fault alarm cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 496
- xATSOutputLoadPoweredByGeneratorAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "WARNING: The system load on the output of the ATS is being powered by source 2 (generator).
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument indicates if the load is powered by the generator,
- when 'load testing' the generator (1 = LIVE, 2 = TEST)."
- --#TYPE "APC XATS: System load powered by generator alarm."
- --#SUMMARY "System load powered by generator."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 497
-
- xATSOutputLoadPoweredByGeneratorAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The system load on the output of the ATS is no longer being powered by source 2 (generator).
- The first argument is the host device serial number.
- The second argument is the host device name."
- --#TYPE "APC XATS: System load powered by generator alarm cleared."
- --#SUMMARY "System load powered by generator alarm cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 498
- xAPCControllerFirmwareUpdateTransferStart TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString05, mtrapargsString04, mtrapargsString02, mtrapargsString03,
- mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Start controller firmware transfer in the device.
- The first argument is the host device serial number.
- The second argument is the host model name that initiated the transfer.
- The third argument is the name of the file that is transferred.
- The fourth argument is the updated revision of the file, if available
- The fifth argument is the reason for the update, if available
- (1=User request, 2=Automatic upgrade by NMC, 3=Unknown)."
- --#TYPE "APC: Start update transfer."
- --#SUMMARY "Start update transfer."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 499
- xAPCControllerFirmwareUpdateTransferComplete TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString05, mtrapargsString04, mtrapargsString02,
- mtrapargsString03, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Transfer of controller firmware was completed in the device.
- The first argument is the host device serial number.
- The second argument is the host device model name that completed the transfer.
- The third argument is the name of the file that was transferred.
- The fourth argument is the revision of the file that was transferred, if available."
- --#TYPE "APC : Update transfer complete."
- --#SUMMARY "Update transfer complete."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 500
- xAPCControllerFirmwareUpdateTransferFailed TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString05, mtrapargsString04, mtrapargsString02,
- mtrapargsString03, mtrapargsString }
- DESCRIPTION
- "SEVERE: Transfer of controller firmware failed.
- The first argument is the host device serial number.
- The second argument is the host device model name that failed to transfer.
- The third argument is the name of the file that failed the transfer, if available.
- The fourth argument is the reason for failure."
- --#TYPE "APC: Update transfer failed."
- --#SUMMARY "Update transfer failed."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 501
- upsPfcInputRelayFailure TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "WARNING: The PFC (Power Factor Correction) input relay failure exists."
- --#TYPE "APC UPS: The PFC input relay failure exists."
- --#SUMMARY "The PFC (Power Factor Correction) input relay failure exists."
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 502
- upsPfcInputRelayFailureCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The PFC (Power Factor Correction) input relay failure cleared."
- --#TYPE "APC UPS: The PFC input relay failure cleared."
- --#SUMMARY "The PFC (Power Factor Correction) input relay failure cleared."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 503
-
- upsInverterOverTemperature TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "WARNING: The inverter over temperature condition exists."
- --#TYPE "APC UPS: The inverter over temperature condition exists."
- --#SUMMARY "The inverter over temperature condition exists."
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 504
- upsInverterOverTemperatureCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The inverter over temperature condition cleared."
- --#TYPE "APC UPS: The inverter over temperature condition cleared."
- --#SUMMARY "The inverter over temperature condition cleared."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 505
- upsBatteryOverVoltage TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "WARNING: The battery over voltage condition exists."
- --#TYPE "APC UPS: The battery over voltage condition exists."
- --#SUMMARY "The battery over voltage condition exists."
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 506
- upsBatteryOverVoltageCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The battery over voltage condition cleared."
- --#TYPE "APC UPS: The battery over voltage condition cleared."
- --#SUMMARY "The battery over voltage condition cleared."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 507
- upsEepromFault TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "WARNING: The EEPROM fault exists."
- --#TYPE "APC UPS: The EEPROM fault exists."
- --#SUMMARY "The EEPROM fault exists."
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 508
- upsEepromFaultCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The EEPROM fault cleared."
- --#TYPE "APC UPS: The EEPROM fault cleared."
- --#SUMMARY "The EEPROM fault cleared."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 509
-
- -- rARU Traps (part 2)
- aruFanRuntimeAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName,
- rARUStatusAruIndex, rARUStatusAruName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "WARNING: The total running hours for a fan has exceeded
- the run hour threshold.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the ARU number.
- The fourth argument is the ARU name.
- The fifth argument indicates which fan in the ARU."
- --#TYPE "APC ARU: Fan Runhour Warning."
- --#SUMMARY "Fan Runhour Alarm."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 510
- aruFanRuntimeAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName,
- rARUStatusAruIndex, rARUStatusAruName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The total running hours for a fan is no longer
- above the fan runhour threshold.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the ARU number.
- The fourth argument is the ARU name.
- The fifth argument indicates which fan in the ARU."
- --#TYPE "APC ARU: Fan Runhour Alarm Cleared."
- --#SUMMARY "Fan Runhour Alarm Cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 511
- aruFanPoorPerformanceAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName,
- rARUStatusAruIndex, rARUStatusAruName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "WARNING: Poor fan performance has been detected in the ARU,
- indicating that the fan may be close to failing.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the ARU number.
- The fourth argument is the ARU name.
- The fifth argument indicates which fan in the ARU."
- --#TYPE "APC ARU: Poor Fan Performance Warning."
- --#SUMMARY "Fan Health Alarm."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 512
- aruFanPoorPerformanceAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName,
- rARUStatusAruIndex, rARUStatusAruName, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Fan performance is no longer degraded.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the ARU number.
- The fourth argument is the ARU name.
- The fifth argument indicates which fan in the ARU."
- --#TYPE "APC ARU: Poor Fan Performance Warning Cleared."
- --#SUMMARY "Fan Health Alarm Cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 513
- aruRedundantPowerLostAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName,
- rARUStatusAruIndex, rARUStatusAruName, mtrapargsString }
- DESCRIPTION
- "WARNING: One of the redundant line cords on the ARU is no longer receiving AC power.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the ARU number.
- The fourth argument is the ARU name."
- --#TYPE "APC ARU: Redundant AC Input is not Present."
- --#SUMMARY "AC Redundancy Lost."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 514
- aruRedundantPowerLostAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { emsIdentSerialNumber, emsIdentEMSName,
- rARUStatusAruIndex, rARUStatusAruName, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Line-cord redundancy has been restored to the ARU.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the ARU number.
- The fourth argument is the ARU name."
- --#TYPE "APC ARU: Redundant AC Input is Present."
- --#SUMMARY "AC Redundancy Restored."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 515
- apcDeviceConfigChange TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A device configuration change has been made on the device.
- The first argument is the device serial number.
- The second argument is the device name.
- The third argument is a secondary device id number."
- --#TYPE "APC: A device configuration change on a device."
- --#SUMMARY "A device configuration change has been made on a device."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 516
- apcEnvSensorConnected TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
- mtrapargsInteger, mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A sensor has been connected to the host device.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is a secondary device id number.
- The fourth argument is the sensor number.
- The fifth argument is the sensor name."
- --#TYPE "APC ENV: Sensor Connected."
- --#SUMMARY "Sensor Connected."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 517
- apcEnvSensorDisconnected TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
- mtrapargsInteger, mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "SEVERE: A sensor has been disconnected from the device.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is a secondary device id number.
- The fourth argument is the sensor number.
- The fifth argument is the sensor name."
- --#TYPE "APC ENV: Sensor Disconnected."
- --#SUMMARY "Sensor Disconnected."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 518
- apcEnvMaxTempThresholdViolation TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
- mtrapargsInteger, mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "SEVERE: Max temperature threshold violated on the sensor.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is a secondary device id number.
- The fourth argument is the sensor number.
- The fifth argument is the sensor name."
- --#TYPE "APC ENV: Max temperature threshold violation."
- --#SUMMARY "Max temperature threshold violation."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 519
- apcEnvMaxTempThresholdViolationCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
- mtrapargsInteger, mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Max temperature threshold violation cleared on the sensor.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is a secondary device id number.
- The fourth argument is the sensor number.
- The fifth argument is the sensor name."
- --#TYPE "APC ENV: Max temperature threshold violation cleared."
- --#SUMMARY "Max temperature threshold violation cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 520
- apcEnvHighTempThresholdViolation TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
- mtrapargsInteger, mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "WARNING: High temperature threshold violated on the sensor.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is a secondary device id number.
- The fourth argument is the sensor number.
- The fifth argument is the sensor name."
- --#TYPE "APC ENV: High temperature threshold violation."
- --#SUMMARY "High temperature threshold violation."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 521
- apcEnvHighTempThresholdViolationCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
- mtrapargsInteger, mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: High temperature threshold violation cleared on the sensor.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is a secondary device id number.
- The fourth argument is the sensor number.
- The fifth argument is the sensor name."
- --#TYPE "APC ENV: High temperature threshold violation cleared."
- --#SUMMARY "High temperature threshold violation cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 522
- apcEnvLowTempThresholdViolation TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
- mtrapargsInteger, mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "WARNING: Low temperature threshold violated on the sensor.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is a secondary device id number.
- The fourth argument is the sensor number.
- The fifth argument is the sensor name."
- --#TYPE "APC ENV: Low temperature threshold violation."
- --#SUMMARY "Low temperature threshold violation."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 523
- apcEnvLowTempThresholdViolationCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
- mtrapargsInteger, mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Low temperature threshold violation cleared on the sensor.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is a secondary device id number.
- The fourth argument is the sensor number.
- The fifth argument is the sensor name."
- --#TYPE "APC ENV: Low temperature threshold violation cleared."
- --#SUMMARY "Low temperature threshold violation cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 524
- apcEnvMinTempThresholdViolation TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
- mtrapargsInteger, mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "SEVERE: Min temperature threshold violated on the sensor.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is a secondary device id number.
- The fourth argument is the sensor number.
- The fifth argument is the sensor name."
- --#TYPE "APC ENV: Min temperature threshold violation."
- --#SUMMARY "Min temperature threshold violation."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 525
- apcEnvMinTempThresholdViolationCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
- mtrapargsInteger, mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Min temperature threshold violation cleared on the sensor.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is a secondary device id number.
- The sixth argument is the sensor number.
- The seventh argument is the sensor name."
- --#TYPE "APC ENV: Min temperature threshold violation cleared."
- --#SUMMARY "Min temperature threshold violation cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 526
- apcEnvSTIncTempRateViolation TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
- mtrapargsInteger, mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "SEVERE: Short-term increasing temperature rate violated on the sensor.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is a secondary device id number.
- The fourth argument is the sensor number.
- The fifth argument is the sensor name."
- --#TYPE "APC ENV: Short-term inc. temp rate violation."
- --#SUMMARY "Short-term inc. temp rate violation."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 527
- apcEnvSTIncTempRateViolationCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
- mtrapargsInteger, mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Short-term increasing temperature rate cleared on the sensor.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is a secondary device id number.
- The fourth argument is the sensor number.
- The fifth argument is the sensor name."
- --#TYPE "APC ENV: Short-term inc. temp rate violation cleared."
- --#SUMMARY "Short-term inc. temp rate violation cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 528
- apcEnvSTDecTempRateViolation TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
- mtrapargsInteger, mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "SEVERE: Short-term decreasing temperature rate violated on the sensor.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is a secondary device id number.
- The fourth argument is the sensor number.
- The fifth argument is the sensor name."
- --#TYPE "APC ENV: Short-term dec. temp rate violation."
- --#SUMMARY "Short-term dec. temp rate violation."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 529
- apcEnvSTDecTempRateViolationCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
- mtrapargsInteger, mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Short-term decreasing temperature rate cleared on the sensor.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is a secondary device id number.
- The fourth argument is the sensor number.
- The fifth argument is the sensor name."
- --#TYPE "APC ENV: Short-term dec. temp rate violation cleared."
- --#SUMMARY "Short-term dec. temp rate violation cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 530
- apcEnvLTIncTempRateViolation TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
- mtrapargsInteger, mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "SEVERE: Long-term increasing temperature rate violated on the sensor.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is a secondary device id number.
- The fourth argument is the sensor number.
- The fifth argument is the sensor name."
- --#TYPE "APC ENV: Long-term inc. temp rate violation."
- --#SUMMARY "Long-term inc. temp rate violation."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 531
- apcEnvLTIncTempRateViolationCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
- mtrapargsInteger, mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Long-term increasing temperature rate cleared on the sensor.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is a secondary device id number.
- The fourth argument is the sensor number.
- The fifth argument is the sensor name."
- --#TYPE "APC ENV: Long-term inc. temp rate violation cleared."
- --#SUMMARY "Long-term inc. temp rate violation cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 532
- apcEnvLTDecTempRateViolation TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
- mtrapargsInteger, mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "SEVERE: Long-term decreasing temperature rate violated on the sensor.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is a secondary device id number.
- The fourth argument is the sensor number.
- The fifth argument is the sensor name."
- --#TYPE "APC ENV: Long-term dec. temp rate violation."
- --#SUMMARY "Long-term dec. temp rate violation."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 533
- apcEnvLTDecTempRateViolationCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
- mtrapargsInteger, mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Long-term decreasing temperature rate cleared on the sensor.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is a secondary device id number.
- The fourth argument is the sensor number.
- The fifth argument is the sensor name."
- --#TYPE "APC ENV: Long-term dec. temp rate violation cleared."
- --#SUMMARY "Long-term dec. temp rate violation cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 534
- apcEnvMaxHumidityThresholdViolation TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
- mtrapargsInteger, mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "SEVERE: Max humidity threshold violated on the sensor.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is a secondary device id number.
- The fourth argument is the sensor number.
- The fifth argument is the sensor name."
- --#TYPE "APC ENV: Max humidity threshold violation."
- --#SUMMARY "Max humidity threshold violation."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 535
- apcEnvMaxHumidityThresholdViolationCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
- mtrapargsInteger, mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Max humidity threshold violation cleared on the sensor.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is a secondary device id number.
- The fourth argument is the sensor number.
- The fifth argument is the sensor name."
- --#TYPE "APC ENV: Max humidity threshold violation cleared."
- --#SUMMARY "Max humidity threshold violation cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 536
- apcEnvHighHumidityThresholdViolation TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
- mtrapargsInteger, mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "WARNING: High humidity threshold violated on the sensor.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is a secondary device id number.
- The fourth argument is the sensor number.
- The fifth argument is the sensor name."
- --#TYPE "APC ENV: High humidity threshold violation."
- --#SUMMARY "High humidity threshold violation."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 537
- apcEnvHighHumidityThresholdViolationCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
- mtrapargsInteger, mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: High humidity threshold violation cleared on the sensor.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is a secondary device id number.
- The fourth argument is the sensor number.
- The fifth argument is the sensor name."
- --#TYPE "APC ENV: High humidity threshold violation cleared."
- --#SUMMARY "High humidity threshold violation cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 538
- apcEnvLowHumidityThresholdViolation TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
- mtrapargsInteger, mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "WARNING: Low humidity threshold violated on the sensor.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is a secondary device id number.
- The fourth argument is the sensor number.
- The fifth argument is the sensor name."
- --#TYPE "APC ENV: Low humidity threshold violation."
- --#SUMMARY "Low humidity threshold violation."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 539
- apcEnvLowHumidityThresholdViolationCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
- mtrapargsInteger, mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Low humidity threshold violation cleared on the sensor.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is a secondary device id number.
- The fourth argument is the sensor number.
- The fifth argument is the sensor name."
- --#TYPE "APC ENV: Low humidity threshold violation cleared."
- --#SUMMARY "Low humidity threshold violation cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 540
- apcEnvMinHumidityThresholdViolation TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
- mtrapargsInteger, mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "SEVERE: Min humidity threshold violated on the sensor.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is a secondary device id number.
- The fourth argument is the sensor number.
- The fifth argument is the sensor name."
- --#TYPE "APC ENV: Min humidity threshold violation."
- --#SUMMARY "Min humidity threshold violation."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 541
- apcEnvMinHumidityThresholdViolationCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
- mtrapargsInteger, mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Min humidity threshold violation cleared on the sensor.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is a secondary device id number.
- The fourth argument is the sensor number.
- The fifth argument is the sensor name."
- --#TYPE "APC ENV: Min humidity threshold violation cleared."
- --#SUMMARY "Min humidity threshold violation cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 542
- apcBeaconConnected TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A beacon has been connected to the device.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is a secondary device id number."
- --#TYPE "APC: Beacon Connected."
- --#SUMMARY "Beacon Connected."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 543
- apcBeaconDisconnected TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04, mtrapargsString }
- DESCRIPTION
- "SEVERE: A beacon has been disconnected from the device.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is a secondary device id number. "
- --#TYPE "APC: Beacon Disconnected."
- --#SUMMARY "Beacon Disconnected."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 544
- apcBeaconOn TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A beacon has gone on (activated).
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is a secondary device id number. "
- --#TYPE "APC: Beacon On."
- --#SUMMARY "Beacon On."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 545
- apcBeaconOff TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A beacon has gone off (deactivated).
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is a secondary device id number. "
- --#TYPE "APC: Beacon Off."
- --#SUMMARY "Beacon Off."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 546
- apcOutletStateAbnormal TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04, mtrapargsInteger, mtrapargsString04,
- mtrapargsInteger02, mtrapargsInteger03, mtrapargsString }
- DESCRIPTION
- "WARNING: An outlet on the device has changed to its abnormal state.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is a secondary device id number.
- The fourth argument is the outlet number.
- The fifth argument is the outlet name.
- The sixth argument is the current outlet state (1=ON, 2=OFF).
- The seventh argument is the configured normal outlet state (1=ON, 2=OFF)."
- --#TYPE "APC: Outlet has changed to its abnormal state."
- --#SUMMARY "Outlet has changed to its abnormal state."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 547
- apcOutletStateNormal TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04, mtrapargsInteger, mtrapargsString04,
- mtrapargsInteger02, mtrapargsInteger03, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: An outlet on the device has changed to its normal state.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is a secondary device id number.
- The fourth argument is the outlet number.
- The fifth argument is the outlet name.
- The sixth argument is the current outlet state (1=ON, 2=OFF).
- The seventh argument is the configured normal outlet state (1=ON, 2=OFF)."
- --#TYPE "APC: Outlet has changed to its normal state."
- --#SUMMARY "Outlet has changed to its normal state."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 548
- apcOutputRelayStateAbnormal TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04, mtrapargsInteger,
- mtrapargsString04, mtrapargsInteger02,
- mtrapargsInteger03, mtrapargsString }
- DESCRIPTION
- "WARNING: An output relay on the device has changed to its abnormal state.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is a secondary device id number.
- The fourth argument is the output relay number.
- The fifth argument is the output relay name.
- The sixth argument is the current output relay state (1=CLOSED, 2=OPEN).
- The seventh argument is the configured normal output relay state (1=CLOSED, 2=OPEN)."
- --#TYPE "APC: Output Relay has changed to its abnormal state."
- --#SUMMARY "Output Relay has changed to its abnormal state."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 549
- apcOutputRelayStateNormal TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04, mtrapargsInteger,
- mtrapargsString04, mtrapargsInteger02,
- mtrapargsInteger03, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: An output relay on the device has changed to its normal state.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is a secondary device id number.
- The fourth argument is the output relay number.
- The fifth argument is the output relay name.
- The sixth argument is the current output relay state (1=CLOSED, 2=OPEN).
- The seventh argument is the configured normal output relay state (1=CLOSED, 2=OPEN)."
- --#TYPE "APC: Output Relay has changed to its normal state."
- --#SUMMARY "Output Relay has changed to its normal state."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 550
- apcHardwareStateAbnormal TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
- mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "SEVERE: The device's hardware is improperly configured and operating outside
- normal bounds for the hardware. This can be caused by improper devices being
- connected to device ports or Alink Current limit detection.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is a secondary device id number.
- The fourth argument is a hardware specific state code."
- --#TYPE "APC: Hardware is in an abnormal state."
- --#SUMMARY "Hardware is in an abnormal state."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 551
- apcHardwareStateNormal TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03,
- mtrapargsInteger04, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The device's hardware is in its normal operational state.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is a secondary device id number."
- --#TYPE "APC EMS: Hardware is in a normal state."
- --#SUMMARY "Hardware is in its normal state."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 552
- apcCriticalDiscreteInputContactStateAbnormal TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04, mtrapargsInteger,
- mtrapargsString04, mtrapargsInteger02,
- mtrapargsInteger03, mtrapargsString }
- DESCRIPTION
- "SEVERE: A discrete input contact on the device has changed to its abnormal state.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is a secondary device id number.
- The fourth argument is the input contact number.
- The fifth argument is the input contact name.
- The sixth argument is the input contact state (1=CLOSED, 2=OPEN).
- The seventh argument is the configured normal input contact state (1=CLOSED, 2=OPEN)."
- --#TYPE "APC: Discrete input contact has changed to its abnormal state."
- --#SUMMARY "Discrete input contact has changed to its abnormal state."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 553
- apcCriticalDiscreteInputContactStateNormal TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04, mtrapargsInteger,
- mtrapargsString04, mtrapargsInteger02,
- mtrapargsInteger03, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A discrete input contact on the device has changed to its normal state.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is a secondary device id number.
- The fourth argument is the input contact number.
- The fifth argument is the input contact name.
- The sixth argument is the input contact state (1=CLOSED, 2=OPEN).
- The seventh argument is the configured normal input contact state (1=CLOSED, 2=OPEN)."
- --#TYPE "APC: Discrete input contact has changed to its normal state."
- --#SUMMARY "Discrete input contact has changed to its normal state."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 554
- apcWarningDiscreteInputContactStateAbnormal TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04, mtrapargsInteger,
- mtrapargsString04, mtrapargsInteger02,
- mtrapargsInteger03, mtrapargsString }
- DESCRIPTION
- "WARNING: A discrete input contact on the device has changed to its abnormal state.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is a secondary device id number.
- The fourth argument is the input contact number.
- The fifth argument is the input contact name.
- The sixth argument is the input contact state (1=CLOSED, 2=OPEN).
- The seventh argument is the configured normal input contact state (1=CLOSED, 2=OPEN)."
- --#TYPE "APC: Discrete input contact has changed to its abnormal state."
- --#SUMMARY "Discrete input contact has changed to its abnormal state."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 555
- apcWarningDiscreteInputContactStateNormal TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04, mtrapargsInteger,
- mtrapargsString04, mtrapargsInteger02,
- mtrapargsInteger03, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A discrete input contact on the device has changed to its normal state.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is a secondary device id number.
- The fourth argument is the input contact number.
- The fifth argument is the input contact name.
- The sixth argument is the input contact state (1=CLOSED, 2=OPEN).
- The seventh argument is the configured normal input contact state (1=CLOSED, 2=OPEN)."
- --#TYPE "APC: Discrete input contact has changed to its normal state."
- --#SUMMARY "Discrete input contact has changed to its normal state."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 556
- apcInformationalDiscreteInputContactStateAbnormal TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04, mtrapargsInteger,
- mtrapargsString04, mtrapargsInteger02,
- mtrapargsInteger03, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A discrete input contact on the device has changed to its abnormal state.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is a secondary device id number.
- The fourth argument is the input contact number.
- The fifth argument is the input contact name.
- The sixth argument is the input contact state (1=CLOSED, 2=OPEN).
- The seventh argument is the configured normal input contact state (1=CLOSED, 2=OPEN)."
- --#TYPE "APC: Discrete input contact has changed to its abnormal state."
- --#SUMMARY "Discrete input contact has changed to its abnormal state."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 557
- apcInformationalDiscreteInputContactStateNormal TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04, mtrapargsInteger,
- mtrapargsString04, mtrapargsInteger02,
- mtrapargsInteger03, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A discrete input contact on the device has changed to its normal state.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is a secondary device id number.
- The fourth argument is the input contact number.
- The fifth argument is the input contact name.
- The sixth argument is the input contact state (1=CLOSED, 2=OPEN).
- The seventh argument is the configured normal input contact state (1=CLOSED, 2=OPEN)."
- --#TYPE "APC: Discrete input contact has changed to its normal state."
- --#SUMMARY "Discrete input contact has changed to its normal state."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 558
- apcAnalogInputMaxThresholdViolation TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
- mtrapargsInteger, mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "SEVERE: Maximum threshold violated on an analog input.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is a secondary device id number.
- The fourth argument is the input number.
- The fifth argument is the input name."
- --#TYPE "APC: Maximum threshold violation on analog input."
- --#SUMMARY "Max threshold violation on input."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 559
- apcAnalogInputMaxThresholdViolationCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
- mtrapargsInteger, mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Maximum threshold violation cleared on the analog input.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is a secondary device id number.
- The fourth argument is the input number.
- The fifth argument is the input name."
- --#TYPE "APC: Max threshold violation cleared."
- --#SUMMARY "Max threshold violation cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 560
- apcAnalogInputHighThresholdViolation TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
- mtrapargsInteger, mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "WARNING: High threshold violated on an analog input.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is a secondary device id number.
- The fourth argument is the input number.
- The fifth argument is the input name."
- --#TYPE "APC: High threshold violation on analog input."
- --#SUMMARY "High threshold violation on input."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 561
- apcAnalogInputHighThresholdViolationCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
- mtrapargsInteger, mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: High threshold violation cleared on the analog input.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is a secondary device id number.
- The fourth argument is the input number.
- The fifth argument is the input name."
- --#TYPE "APC: High threshold violation cleared."
- --#SUMMARY "High threshold violation cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 562
- apcAnalogInputLowThresholdViolation TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
- mtrapargsInteger, mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "WARNING: Low threshold violated on an analog input.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is a secondary device id number.
- The fourth argument is the input number.
- The fifth argument is the input name."
- --#TYPE "APC: Low threshold violation on analog input."
- --#SUMMARY "Low threshold violation on input."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 563
- apcAnalogInputLowThresholdViolationCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
- mtrapargsInteger, mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Low threshold violation cleared on the analog input.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is a secondary device id number.
- The fourth argument is the input number.
- The fifth argument is the input name."
- --#TYPE "APC: Low threshold violation cleared."
- --#SUMMARY "Low threshold violation cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 564
- apcAnalogInputMinThresholdViolation TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
- mtrapargsInteger, mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "SEVERE: Minimum threshold violated on an analog input.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is a secondary device id number.
- The fourth argument is the input number.
- The fifth argument is the input name."
- --#TYPE "APC: Min threshold violation on analog input."
- --#SUMMARY "Min threshold violation on input."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 565
- apcAnalogInputMinThresholdViolationCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
- mtrapargsInteger, mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Minimum threshold violation cleared on the analog input.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is a secondary device id number.
- The fourth argument is the input number.
- The fifth argument is the input name."
- --#TYPE "APC: Min threshold violation cleared."
- --#SUMMARY "Min threshold violation cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 566
- apcDeviceClearLostComms TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Lost communications reset command has been issued.
- The first argument is the device serial number.
- The second argument is the device name.
- The third argument is a secondary device id number."
- --#TYPE "APC: Lost communications reset command has been issued."
- --#SUMMARY "Lost communications reset command has been issued."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 567
- apcDeviceConnected TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03,
- mtrapargsInteger, mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A device has been connected to the host.
- The first argument is the host serial number.
- The second argument is the host name.
- The third argument is the device number.
- The fourth argument is the device name."
- --#TYPE "APC: Device Connected."
- --#SUMMARY "Device Connected."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 568
- apcDeviceDisconnected TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03,
- mtrapargsInteger, mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "SEVERE: A device has been disconnected from the host.
- The first argument is the host serial number.
- The second argument is the host name.
- The third argument is the device number.
- The fourth argument is the device name."
- --#TYPE "APC: Device Disconnected."
- --#SUMMARY "Device Disconnected."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 569
- apcUnregisteredUserAccessDenied TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsString04,
- mtrapargsInteger, mtrapargsString05, mtrapargsString}
- DESCRIPTION
- "INFORMATIONAL: An unregistered user has tried to access the device.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the host device location.
- The fourth argumant is the door identifier.
- The fifth argument is the unregistered user's RFID."
- --#TYPE "APC: Unregistered user."
- --#SUMMARY "Unregistered user."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 570
- apcRegisteredUserAccessDenied TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsString04,
- mtrapargsInteger, mtrapargsString05, mtrapargsString}
- DESCRIPTION
- "INFORMATIONAL: A registered user has been denied access to the device.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the host device location.
- The fourth argumant is the door identifier.
- The fifth argument is the user name."
- --#TYPE "APC: Access denied."
- --#SUMMARY "Access denied."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 571
- apcRegisteredUserConfigChange TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03,
- mtrapargsString04, mtrapargsString05, mtrapargsString}
- DESCRIPTION
- "INFORMATIONAL: Registered user configuration change.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the host device location.
- The fourth argument is the user name."
- --#TYPE "APC: Registered user configuration change."
- --#SUMMARY "Registered user configuration change."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 572
- apcDoorUnlocked TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsString04,
- mtrapargsInteger, mtrapargsString05, mtrapargsInteger02, mtrapargsString}
- DESCRIPTION
- "INFORMATIONAL: A door has been unlocked.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the host device location.
- The fourth argument is the door identifier.
- The fifth argument is the door access user.
- The sixth argument is the door access type."
- --#TYPE "APC: Door unlocked."
- --#SUMMARY "Door unlocked."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 573
- apcDoorLocked TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsString04,
- mtrapargsInteger, mtrapargsString05, mtrapargsInteger02, mtrapargsString}
- DESCRIPTION
- "INFORMATIONAL: A door has been locked.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the host device location.
- The fourth argument is the door identifier.
- The fifth argument is the door access user.
- The sixth argument is the door access type."
- --#TYPE "APC: Door locked."
- --#SUMMARY "Door locked."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 574
- apcHandleOpened TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03,
- mtrapargsString04, mtrapargsInteger, mtrapargsString}
- DESCRIPTION
- "INFORMATIONAL: A door handle has been opened.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the host device location.
- The fourth argument is the door identifier, (1=front, 2=rear)."
- --#TYPE "APC: Door handle opened."
- --#SUMMARY "Door handle opened."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 575
- apcHandleClosed TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03,
- mtrapargsString04, mtrapargsInteger, mtrapargsString}
- DESCRIPTION
- "INFORMATIONAL: A door handle has been closed.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the host device location.
- The fourth argument is the door identifier, (1=front, 2=rear)."
- --#TYPE "APC: Door handle closed."
- --#SUMMARY "Door handle closed."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 576
- apcDoorOpened TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03,
- mtrapargsString04, mtrapargsInteger, mtrapargsString}
- DESCRIPTION
- "INFORMATIONAL: A door has been opened.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the host device location.
- The fourth argument is the door identifier, (1=front, 2=rear)."
- --#TYPE "APC: Door opened."
- --#SUMMARY "Door opened."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 577
- apcDoorClosed TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03,
- mtrapargsString04, mtrapargsInteger, mtrapargsString}
- DESCRIPTION
- "INFORMATIONAL: A door has been closed.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the host device location.
- The fourth argument is the door identifier, (1=front, 2=rear)."
- --#TYPE "APC: Door closed."
- --#SUMMARY "Door closed."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 578
- -- trap number 579 available
- apcKeyOverrideUnlocked TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03,
- mtrapargsString04, mtrapargsInteger, mtrapargsString}
- DESCRIPTION
- "SEVERE: Key override unlock has occurred.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the host device location.
- The fourth argument is the door identifier, (1=front, 2=rear)."
- --#TYPE "APC: Key override unlock has occurred."
- --#SUMMARY "Key override unlock has occurred."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 580
- apcKeyOverrideLocked TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03,
- mtrapargsString04, mtrapargsInteger, mtrapargsString}
- DESCRIPTION
- "INFORMATIONAL: Key override lock has occurred.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the host device location.
- The fourth argument is the door identifier, (1=front, 2=rear)."
- --#TYPE "APC: Key override lock has occurred."
- --#SUMMARY "Key override lock has occurred."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 581
- apcForcedEntry TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03,
- mtrapargsString04, mtrapargsInteger, mtrapargsString}
- DESCRIPTION
- "SEVERE: A forced entry condition has occurred.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the host device location.
- The fourth argument is the door identifier, (1=front, 2=rear)."
- --#TYPE "APC: A forced entry condition has occurred."
- --#SUMMARY "A forced entry has occurred."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 582
- apcForcedEntryCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03,
- mtrapargsString04, mtrapargsInteger, mtrapargsString}
- DESCRIPTION
- "INFORMATIONAL: A forced entry condition has been cleared.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the host device location.
- The fourth argument is the door identifier, (1=front, 2=rear)."
- --#TYPE "APC: A forced entry condition has been cleared."
- --#SUMMARY "A forced entry has been cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 583
- apcRelockTimeout TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03,
- mtrapargsString04, mtrapargsInteger, mtrapargsString}
- DESCRIPTION
- "SEVERE: A relock timout has occured.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the host device location.
- The fourth argument is the door identifier, (1=front, 2=rear)."
- --#TYPE "APC: Relock timout."
- --#SUMMARY "Relock timeout."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 584
- apcRelockTimeoutCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03,
- mtrapargsString04, mtrapargsInteger, mtrapargsString}
- DESCRIPTION
- "INFORMATIONAL: A relock timout has been cleared.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the host device location.
- The fourth argument is the door identifier, (1=front, 2=rear)."
- --#TYPE "APC: relock timout has been cleared."
- --#SUMMARY "Relock timout has been cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 585
- apcDoorSenseDisconnected TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03,
- mtrapargsString04, mtrapargsInteger, mtrapargsString}
- DESCRIPTION
- "SEVERE: A door sensor was disconnected.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the host device location.
- The fourth argument is the door identifier, (1=front, 2=rear)."
- --#TYPE "APC: A door sensor was disconnected."
- --#SUMMARY "A door sensor was disconnected."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 586
- apcDoorSenseConnected TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03,
- mtrapargsString04, mtrapargsInteger, mtrapargsString}
- DESCRIPTION
- "INFORMATIONAL: A forced entry condition has been cleared.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the host device location.
- The fourth argument is the door identifier, (1=front, 2=rear)."
- --#TYPE "APC: A door sensor was connected."
- --#SUMMARY "A door sensor was connected."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 587
- apcDoorLostComms TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03,
- mtrapargsString04, mtrapargsInteger, mtrapargsString}
- DESCRIPTION
- "SEVERE: Communications have been lost with the door.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the host device location.
- The fourth argument is the door identifier, (1=front, 2=rear)."
- --#TYPE "APC: A door has lost communications."
- --#SUMMARY "A door has lost communications."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 588
- apcDoorEstablishedComms TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03,
- mtrapargsString04, mtrapargsInteger, mtrapargsString}
- DESCRIPTION
- "INFORMATIONAL: Communications have been established with the door.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the host device location.
- The fourth argument is the door identifier, (1=front, 2=rear)."
- --#TYPE "APC: A door has established communications."
- --#SUMMARY "A door has established communications."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 589
- apcRegisteredUserAccessChange TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03,
- mtrapargsString04, mtrapargsString05, mtrapargsString}
- DESCRIPTION
- "INFORMATIONAL: Registered user access changed.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the host device location.
- The fourth argument is the user name."
- --#TYPE "APC: Registered user access change."
- --#SUMMARY "Registered user access change."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 590
- apcUnregisteredUserStatusChange TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03,
- mtrapargsString04, mtrapargsString05, mtrapargsString}
- DESCRIPTION
- "INFORMATIONAL: Unregistered user status changed.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the host device location.
- The fourth argument is the user name."
- --#TYPE "APC: Unregistered user status change."
- --#SUMMARY "Unregistered user status change."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 591
- apcDeviceClearUserConfigs TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: User configurations reset command has been issued.
- The first argument is the device serial number.
- The second argument is the device name.
- The third argument is a secondary device id number."
- --#TYPE "APC: User configurations reset command has been issued."
- --#SUMMARY "User configurations reset command has been issued."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 592
- -- Add more events starting at 600 for UPS Devices
- upsBatteryTempSensorFault TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "WARNING: The battery temperature sensor fault exists."
- --#TYPE "APC UPS: The battery temperature sensor fault exists."
- --#SUMMARY "The battery temperature sensor fault exists."
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 600
- upsBatteryTempSensorFaultCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The battery temperature sensor fault cleared."
- --#TYPE "APC UPS: The battery temperature sensor fault cleared."
- --#SUMMARY "The battery temperature sensor fault cleared."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 601
-
- upsBatterySoftBusStartFault TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "WARNING: A battery bus soft start fault exists."
- --#TYPE "APC UPS: A battery bus soft start fault exists."
- --#SUMMARY "A battery bus soft start fault exists."
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 602
- upsBatterySoftBusStartFaultCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A battery bus soft start fault exists cleared."
- --#TYPE "APC UPS: A battery bus soft start fault exists cleared."
- --#SUMMARY "A battery bus soft start fault exists cleared."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 603
-
- apcOutputShortCircuit TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "WARNING: An output short circuit condition exists."
- --#TYPE "APC Device: An output short circuit condition exists."
- --#SUMMARY "An output short circuit condition exists."
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 604
- apcOutputShortCircuitCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: An output short circuit condition cleared."
- --#TYPE "APC Device: An output short circuit condition cleared."
- --#SUMMARY "An output short circuit condition cleared."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 605
-
- apcOutputRelayFault TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "WARNING: An output relay (or its driver) fault exists."
- --#TYPE "APC Device: An output relay (or its driver) fault exists."
- --#SUMMARY "An output relay (or its driver) fault exists."
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 606
- apcOutputRelayFaultCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: An output relay (or its driver) fault cleared."
- --#TYPE "APC Device: An output relay (or its driver) fault cleared."
- --#SUMMARY "An output relay (or its driver) fault cleared."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 607
-
- upsPfcFault TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "WARNING: A PFC fault exists."
- --#TYPE "APC UPS: A PFC fault exists."
- --#SUMMARY "A PFC fault exists."
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 608
- upsPfcFaultCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The PFC fault cleared."
- --#TYPE "APC UPS: The PFC fault cleared."
- --#SUMMARY "The PFC fault cleared."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 609
-
- apcDcBusOverVoltage TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "WARNING: The DC bus voltage is too high."
- --#TYPE "APC Devcie: DC bus voltage is too high."
- --#SUMMARY "The DC bus voltage is too high."
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 610
- apcDcBusOverVoltageCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The DC bus voltage is too high cleared."
- --#TYPE "APC Device: The DC bus voltage is too high cleared."
- --#SUMMARY "The DC bus voltage is too high cleared."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 611
-
- upsInverterFault TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "WARNING: The inverter fault exists."
- --#TYPE "APC UPS: The inverter fault exists."
- --#SUMMARY "The inverter fault exists."
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 612
- upsInverterFaultCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The inverter fault cleared."
- --#TYPE "APC UPS: The inverter fault cleared."
- --#SUMMARY "The inverter fault cleared."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 613
-
- apcAdConverterFault TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "WARNING: The A/D converter fault exists."
- --#TYPE "APC Device: The A/D converter fault exists."
- --#SUMMARY "The A/D converter fault exists."
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 614
- apcAdConverterFaultCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The A/D converter fault cleared."
- --#TYPE "APC Device: The A/D converter fault cleared."
- --#SUMMARY "The A/D converter fault cleared."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 615
-
- apcLogicPowerSupplyFault TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "WARNING: A logic power supply fault exists."
- --#TYPE "APC Device: A logic power supply fault exists."
- --#SUMMARY "A logic power supply fault exists."
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 616
- apcLogicPowerSupplyFaultCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A logic power supply fault cleared."
- --#TYPE "APC Device: A logic power supply fault cleared."
- --#SUMMARY "A logic power supply fault cleared."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 617
-
- apcTransformerDCImbalanceFault TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "WARNING: The DC component of the transformer's current is too high."
- --#TYPE "APC Device: The DC component of the tformer's curr is too high."
- --#SUMMARY "The DC component of the transformer's current is too high."
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 618
- apcTransformerDCImbalanceFaultCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "WARNING: The DC component of the transformer's current is normal."
- --#TYPE "APC Device: The DC component of the tformer's curr is normal."
- --#SUMMARY "The DC component of the transformer's current is normal."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 619
-
- upsBackfeedRelayFault TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "WARNING: The backfeed relay (or its driver) has a fault."
- --#TYPE "UPS Device: The backfeed relay (or its driver) has a fault."
- --#SUMMARY "The backfeed relay (or its driver) has a fault."
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 620
- upsBackfeedRelayFaultCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "WARNING: The backfeed relay (or its driver) has a fault cleared."
- --#TYPE "UPS Device: The bfeed rly (or its drver) has a flt cleared."
- --#SUMMARY "The backfeed relay (or its driver) has a fault cleared."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 621
-
- upsBypassRelayFault TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "WARNING: A bypass relay (or its driver) has a fault."
- --#TYPE "APC Device: A bypass relay (or its driver) has a fault."
- --#SUMMARY "A bypass relay (or its driver) has a fault."
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 622
- upsBypassRelayFaultCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "WARNING: A bypass relay (or its driver) has a fault cleared."
- --#TYPE "APC Device: A bypass relay (or its driver) has a fault cleared."
- --#SUMMARY "A bypass relay (or its driver) has a fault cleared."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 623
-
- xPDUBranchCurrentMinAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
- mtrapargsInteger02, mtrapargsInteger03, mtrapargsString }
- DESCRIPTION
- "SEVERE: The current in a branch circuit is outside the limits specified for that
- branch circuit.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the panel position of the branch circuit (1-based index).
- The fourth argument is the measured current in tenths of Amps.
- The fifth argument is the threshold, in tenths of Amps, from which the alarm was generated."
- --#TYPE "APC XPDU: Branch circuit minimum current alarm."
- --#SUMMARY "Branch circuit current is below threshold."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 626
- xPDUBranchCurrentMinAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
- mtrapargsInteger02, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The current in a branch circuit is back within the limits
- specified for that branch circuit.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the panel position of the branch circuit (1-based index).
- The fourth argument is the measured current in tenths of Amps."
- --#TYPE "APC XPDU: Branch circuit minimum current alarm cleared."
- --#SUMMARY "Branch circuit low current alarm cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 627
- xPDUBranchCurrentMaxAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
- mtrapargsInteger02, mtrapargsInteger03, mtrapargsString }
- DESCRIPTION
- "SEVERE: The current in a branch circuit is outside the limits specified for that
- branch circuit.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the panel position of the branch circuit (1-based index).
- The fourth argument is the measured current in tenths of Amps.
- The fifth argument is the threshold, in tenths of Amps, above which the alarm was generated."
- --#TYPE "APC XPDU: Branch circuit maximum current alarm."
- --#SUMMARY "Branch circuit current is above threshold."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 628
- xPDUBranchCurrentMaxAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
- mtrapargsInteger02, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The current in a branch circuit is back within the limits
- specified for that branch circuit.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the panel position of the branch circuit (1-based index).
- The fourth argument is the measured current in tenths of Amps."
- --#TYPE "APC XPDU: Branch circuit maximum current alarm cleared."
- --#SUMMARY "Branch circuit high current alarm cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 629
- rPDUOutletLowLoad TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { rPDUIdentSerialNumber, rPDUIdentName,
- rPDUOutletStatusIndex, mtrapargsString }
- DESCRIPTION
- "WARNING: A Rack PDU has violated the outlet low load threshold.
- The first argument is the serial number.
- The second argument is the device name.
- The third argument is the outlet number."
- --#TYPE "APC Rack PDU: Violation of outlet low load threshold."
- --#SUMMARY "A Rack PDU has violated the outlet low load threshold."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 630
- rPDUOutletLowLoadCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { rPDUIdentSerialNumber, rPDUIdentName,
- rPDUOutletStatusIndex, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The outlet low load condition on a Rack PDU has been
- cleared.
- The first argument is the serial number.
- The second argument is the device name.
- The third argument is the outlet number."
- --#TYPE "APC Rack PDU: Low load condition cleared."
- --#SUMMARY "The low load condition on a Rack PDU has been cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 631
- rPDUOutletNearOverload TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { rPDUIdentSerialNumber, rPDUIdentName,
- rPDUOutletStatusIndex, mtrapargsString }
- DESCRIPTION
- "WARNING: A Rack PDU is near an outlet overload condition.
- The first argument is the serial number.
- The second argument is the device name.
- The third argument is the outlet number."
- --#TYPE "APC Rack PDU: Near an overload condition."
- --#SUMMARY "A Rack PDU is near an outlet overload condition."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 632
- rPDUOutletNearOverloadCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { rPDUIdentSerialNumber, rPDUIdentName,
- rPDUOutletStatusIndex, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The outlet near overload condition on a Rack PDU has
- been cleared.
- The first argument is the serial number.
- The second argument is the device name.
- The third argument is the outlet number."
- --#TYPE "APC Rack PDU: Outlet Near overload condition has cleared."
- --#SUMMARY "Rack PDU outlet near overload condition has cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 633
- rPDUOutletOverload TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { rPDUIdentSerialNumber, rPDUIdentName,
- rPDUOutletStatusIndex, mtrapargsString }
- DESCRIPTION
- "SEVERE: A Rack PDU is in an overload condition.
- The first argument is the serial number.
- The second argument is the device name.
- The third argument is the outlet number."
- --#TYPE "APC Rack PDU: Outlet Overload condition."
- --#SUMMARY "A Rack PDU is in an outlet overload condition."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 634
- rPDUOutletOverloadCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { rPDUIdentSerialNumber, rPDUIdentName,
- rPDUOutletStatusIndex, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The outlet overload condition on a Rack PDU has been
- cleared.
- The first argument is the serial number.
- The second argument is the device name.
- The third argument is the outlet number."
- --#TYPE "APC Rack PDU: Overload condition has cleared."
- --#SUMMARY "The outlet overload condition on a Rack PDU has cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 635
- apcTestTrap TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsInteger02, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Trap used to test SNMP trap functionality.
- The first argument is a place holder for test variables."
- --#TYPE "APC: Test trap."
- --#SUMMARY "Test Trap."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 636
- baseFanFailureCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Base module fan has been repaired"
- --#TYPE "APC UPS: Base module fan has been repaired"
- --#SUMMARY "The base module fan has been repaired."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 637
-
- -- MODULAR POWER DISTRIBUTION SYSTEM
- isxModularDistributionCommLost TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "SEVERE: Communication with a metering segment of the modular
- distribution system has been lost.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the segment number.
- The fourth argument describes the modules served by this metering segment."
- --#TYPE "APC MDS: Com lost in modular distribution system."
- --#SUMMARY "Modular distribution communication lost."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 652
- isxModularDistributionCommEstablished TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: Communication with a metering segment of the modular
- distribution system has been restored.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the segment number.
- The fourth argument describes the modules served by this metering segment."
- --#TYPE "APC MDS: Com restored in modular distribution system."
- --#SUMMARY "Modular distribution communication restored."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 653
- isxModularDistributionModuleInserted TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A distribution module has been inserted into the system.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the module location number."
- --#TYPE "APC MDS: Distribution module inserted."
- --#SUMMARY "Distribution module inserted.
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 654
- isxModularDistributionModuleRemoved TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: A distribution module has been removed from the system.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the module location number."
- --#TYPE "APC MDS: Distribution module removed."
- --#SUMMARY "Distribution module removed.
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 655
- isxModularBreakerOpenAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsInteger03,
- mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "SEVERE: A distribution module breaker is open and in an alarm condition.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the module number.
- The fourth argument is the module breaker(s) (1=L1, 2=L2, 3=L3, 4=L12, 5=L23, 6=L123).
- The fifth argument is the load name associated with the circuit/cable fed by this breaker."
- --#TYPE "APC MDS: Distribution breaker open alarm."
- --#SUMMARY "Distribution breaker open alarm."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 656
- isxModularBreakerOpenAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsInteger03,
- mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: An alarm caused by a distribution breaker being open has been cleared.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the module number.
- The fourth argument is the breaker(s) (1=L1, 2=L2, 3=L3, 4=L12, 5=L23, 6=L123).
- The fifth argument is the load name associated with the circuit/cable fed by this breaker."
- --#TYPE "APC MDS: Distribution breaker open alarm cleared."
- --#SUMMARY "Distribution breaker open alarm cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 657
- isxModularMinCurrentThresholdViolation TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsInteger03,
- mtrapargsInteger02, mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "SEVERE: The current in a distribution module is below the minimum/critical
- limit specified for the circuit/cable.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the module number.
- The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3).
- The fifth argument is the threshold, in tenths of Amps, from which the alarm was generated.
- The sixth argument is the load name associated with the circuit/cable fed by this breaker."
- --#TYPE "APC MDS: Distribution minimum current alarm."
- --#SUMMARY "Distribution current is below the critical threshold."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 658
- isxModularMinCurrentThresholdViolationCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsInteger03,
- mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The current in a distribution module is no longer below the minimum/critical
- limit specified for the circuit/cable.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the module number.
- The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3).
- The fifth argument is the load name associated with the circuit/cable fed by this breaker."
- --#TYPE "APC MDS: Distribution minimum current alarm cleared."
- --#SUMMARY "Distribution current no longer below the critical threshold."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 659
- isxModularLowCurrentThresholdViolation TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsInteger03,
- mtrapargsInteger02, mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "WARNING: The current in a distribution module is below the low/warning
- limit specified for the circuit/cable.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the module number.
- The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3).
- The fifth argument is the threshold, in tenths of Amps, from which the alarm was generated.
- The sixth argument is the load name associated with the circuit/cable fed by this breaker."
- --#TYPE "APC MDS: Distribution low current alarm."
- --#SUMMARY "Distribution current is below the warning threshold."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 660
- isxModularLowCurrentThresholdViolationCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsInteger03,
- mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The current in a distribution module is no longer below the low/warning
- limit specified for the circuit/cable.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the module number.
- The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3).
- The fifth argument is the load name associated with the circuit/cable fed by this breaker."
- --#TYPE "APC MDS: Distribution low current alarm cleared."
- --#SUMMARY "Distribution current no longer below the warning threshold."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 661
- isxModularHighCurrentThresholdViolation TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsInteger03,
- mtrapargsInteger02, mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "WARNING: The current in a distribution module is above the high/warning
- limit specified for the circuit/cable.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the module number.
- The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3).
- The fifth argument is the threshold, in tenths of Amps, from which the alarm was generated.
- The sixth argument is the load name associated with the circuit/cable fed by this breaker."
- --#TYPE "APC MDS: Distribution high current alarm."
- --#SUMMARY "Distribution current is above the warning threshold."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 662
- isxModularHighCurrentThresholdViolationCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsInteger03,
- mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The current in a distribution module is no longer above the high/warning
- limit specified for the circuit/cable.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the module number.
- The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3).
- The fifth argument is the load name associated with the circuit/cable fed by this breaker."
- --#TYPE "APC MDS: Distribution high current alarm cleared."
- --#SUMMARY "Distribution current no longer above the warning threshold."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 663
- isxModularMaxCurrentThresholdViolation TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsInteger03,
- mtrapargsInteger02, mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "SEVERE: The current in a distribution module is above the maximum/critical
- limit specified for the circuit/cable.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the module number.
- The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3).
- The fifth argument is the threshold, in tenths of Amps, from which the alarm was generated.
- The sixth argument is the load name associated with the circuit/cable fed by this breaker."
- --#TYPE "APC MDS: Distribution maximum current alarm."
- --#SUMMARY "Distribution current is above the critical threshold."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 664
- isxModularMaxCurrentThresholdViolationCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsInteger03,
- mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The current in a distribution module is no longer above the maximum/critical
- limit specified for the circuit/cable.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the module number.
- The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3).
- The fifth argument is the load name associated with the circuit/cable fed by this breaker."
- --#TYPE "APC MDS: Distribution maximum current alarm cleared."
- --#SUMMARY "Distribution current no longer above the critical threshold."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 665
- isxModularSubfeedBreakerOpenAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger,
- mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "SEVERE: A distribution subfeed breaker is open and in an alarm condition.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the subfeed number.
- The fourth argument is the load name associated with the subfeed."
- --#TYPE "APC MDS: Distribution subfeed breaker open alarm."
- --#SUMMARY "Distribution subfeed breaker open alarm."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 666
- isxModularSubfeedBreakerOpenAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger,
- mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: An alarm caused by a distribution subfeed breaker being open has been cleared.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the subfeed number.
- The fourth argument is the load name associated with the subfeed."
- --#TYPE "APC MDS: Distribution subfeed breaker open alarm cleared."
- --#SUMMARY "Distribution subfeed breaker open alarm cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 667
- isxModularSubfeedMinCurrentThresholdViolation TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsInteger03,
- mtrapargsInteger02, mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "SEVERE: The current in a distribution subfeed is below the minimum/critical limit specified.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the subfeed number.
- The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3).
- The fifth argument is the threshold, in tenths of Amps, from which the alarm was generated.
- The sixth argument is the load name associated with the subfeed."
- --#TYPE "APC MDS: Distribution subfeed minimum current alarm."
- --#SUMMARY "Distribution subfeed current is below the critical threshold."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 668
- isxModularSubfeedMinCurrentThresholdViolationCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsInteger03,
- mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The current in a distribution subfeed is no longer below the minimum/critical limit specified.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the subfeed number.
- The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3).
- The fifth argument is the load name associated with the subfeed."
- --#TYPE "APC MDS: Distribution subfeed minimum current alarm cleared."
- --#SUMMARY "Distribution subfeed current no longer below the critical threshold."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 669
- isxModularSubfeedLowCurrentThresholdViolation TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsInteger03,
- mtrapargsInteger02, mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "WARNING: The current in a distribution subfeed is below the low/warning limit specified.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the subfeed number.
- The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3).
- The fifth argument is the threshold, in tenths of Amps, from which the alarm was generated.
- The sixth argument is the load name associated with the subfeed."
- --#TYPE "APC MDS: Distribution subfeed low current alarm."
- --#SUMMARY "Distribution subfeed current is below the warning threshold."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 670
- isxModularSubfeedLowCurrentThresholdViolationCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsInteger03,
- mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The current in a distribution subfeed is no longer below the low/warning limit specified.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the subfeed number.
- The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3).
- The fifth argument is the load name associated with the subfeed."
- --#TYPE "APC MDS: Distribution subfeed low current alarm cleared."
- --#SUMMARY "Distribution subfeed current is no longer below the warning threshold."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 671
- isxModularSubfeedHighCurrentThresholdViolation TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsInteger03,
- mtrapargsInteger02, mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "WARNING: The current in a distribution subfeed is above the high/warning limit specified.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the subfeed number.
- The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3).
- The fifth argument is the threshold, in tenths of Amps, from which the alarm was generated.
- The sixth argument is the load name associated with the subfeed."
- --#TYPE "APC MDS: Distribution subfeed high current alarm."
- --#SUMMARY "Distribution subfeed current is above the warning threshold."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 672
- isxModularSubfeedHighCurrentThresholdViolationCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsInteger03,
- mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The current in a distribution subfeed is no longer above the high/warning limit specified.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the subfeed number.
- The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3).
- The fifth argument is the load name associated with the subfeed."
- --#TYPE "APC MDS: Distribution subfeed high current alarm cleared."
- --#SUMMARY "Distribution subfeed current no longer above the warning threshold."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 673
- isxModularSubfeedMaxCurrentThresholdViolation TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsInteger03,
- mtrapargsInteger02, mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "SEVERE: The current in a distribution subfeed is above the maximum/critical limit specified.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the subfeed number.
- The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3).
- The fifth argument is the threshold, in tenths of Amps, from which the alarm was generated.
- The sixth argument is the load name associated with the subfeed."
- --#TYPE "APC MDS: Distribution subfeed maximum current alarm."
- --#SUMMARY "Distribution subfeed current is above the critical threshold."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 674
- isxModularSubfeedMaxCurrentThresholdViolationCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsInteger03,
- mtrapargsString04, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The current in a distribution subfeed is no longer above the maximum/critical limit specified.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the subfeed number.
- The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3).
- The fifth argument is the load name associated with the subfeed."
- --#TYPE "APC MDS: Distribution subfeed maximum current alarm cleared."
- --#SUMMARY "Distribution subfeed current no longer above the critical threshold."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 675
- isxModularTotalOutputCurrentMinThresholdViolation TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger,
- mtrapargsInteger03, mtrapargsString }
- DESCRIPTION
- "SEVERE: The total output current of the distribution is below the minimum/critical limit specified.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the phase index (1=L1, 2=L2, 3=L3).
- The fourth argument is the threshold, in tenths of Amps, from which the alarm was generated."
- --#TYPE "APC MDS: Total distribution output minimum current alarm."
- --#SUMMARY "Distribution total current is below the critical threshold."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 676
- isxModularTotalOutputCurrentMinThresholdViolationCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger,
- mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The total output current of the distribution is no longer below the minimum/critical limit specified.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the phase index (1=L1, 2=L2, 3=L3)."
- --#TYPE "APC MDS: Total output minimum current alarm cleared."
- --#SUMMARY "Distribution total current no longer below the critical threshold."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 677
- isxModularTotalOutputCurrentLowThresholdViolation TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger,
- mtrapargsInteger03, mtrapargsString }
- DESCRIPTION
- "WARNING: The total output current of the distribution is below the low/warning limit specified.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the phase index (1=L1, 2=L2, 3=L3).
- The fourth argument is the threshold, in tenths of Amps, from which the alarm was generated."
- --#TYPE "APC MDS: Total output low current alarm."
- --#SUMMARY "Distribution total current is below the warning threshold."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 678
- isxModularTotalOutputCurrentLowThresholdViolationCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger,
- mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The total output current of the distribution is no longer below the low/warning limit specified.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the phase index (1=L1, 2=L2, 3=L3)."
- --#TYPE "APC MDS: Total output low current alarm cleared."
- --#SUMMARY "Distribution total current no longer below the warning threshold."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 679
- isxModularTotalOutputCurrentHighThresholdViolation TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger,
- mtrapargsInteger03, mtrapargsString }
- DESCRIPTION
- "WARNING: The total output current of the distribution is above the high/warning limit specified.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the phase index (1=L1, 2=L2, 3=L3).
- The fourth argument is the threshold, in tenths of Amps, from which the alarm was generated."
- --#TYPE "APC MDS: Total output high current alarm."
- --#SUMMARY "Distribution total current is above the warning threshold."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 680
- isxModularTotalOutputCurrentHighThresholdViolationCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger,
- mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The total output current of the distribution is no longer above the high/warning limit specified.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the phase index (1=L1, 2=L2, 3=L3)."
- --#TYPE "APC MDS: Total output high current alarm cleared."
- --#SUMMARY "Distribution total current no longer above the warning threshold."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 681
- isxModularTotalOutputCurrentMaxThresholdViolation TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger,
- mtrapargsInteger03, mtrapargsString }
- DESCRIPTION
- "SEVERE: The total output current of the distribution is above the maximum/critical limit specified.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the phase index (1=L1, 2=L2, 3=L3).
- The fourth argument is the threshold, in tenths of Amps, from which the alarm was generated."
- --#TYPE "APC MDS: Total output maximum current alarm."
- --#SUMMARY "Distribution total current is above the critical threshold."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 682
- isxModularTotalOutputCurrentMaxThresholdViolationCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger,
- mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The total output current of the distribution is no longer above the maximum/critical limit specified.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the phase index (1=L1, 2=L2, 3=L3)."
- --#TYPE "APC MDS: Total output maximum current alarm cleared."
- --#SUMMARY "Distribution total current no longer above the critical threshold."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 683
- isxModularOutputVoltageMinThresholdViolation TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger,
- mtrapargsInteger03, mtrapargsString }
- DESCRIPTION
- "SEVERE: The distribution output voltage is below the minimum/critical limit specified.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the phase index (1=L1, 2=L2, 3=L3).
- The fourth argument is the threshold, in tenths of Volts, from which the alarm was generated."
- --#TYPE "APC MDS: Distribution minimum output voltage alarm."
- --#SUMMARY "Distribution output voltage is below the critical threshold."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 684
- isxModularOutputVoltageMinThresholdViolationCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger,
- mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The distribution output voltage is no longer below the minimum/critical limit specified.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the phase index (1=L1, 2=L2, 3=L3)."
- --#TYPE "APC MDS: Distribution minimum output voltage alarm cleared."
- --#SUMMARY "Distribution output voltage no longer below the critical threshold."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 685
- isxModularOutputVoltageLowThresholdViolation TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger,
- mtrapargsInteger03, mtrapargsString }
- DESCRIPTION
- "WARNING: The distribution output voltage is below the low/warning limit specified.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the phase index (1=L1, 2=L2, 3=L3).
- The fourth argument is the threshold, in tenths of Volts, from which the alarm was generated."
- --#TYPE "APC MDS: Distribution low output voltage alarm."
- --#SUMMARY "Distribution output voltage is below the warning threshold."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 686
- isxModularOutputVoltageLowThresholdViolationCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger,
- mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The distribution output voltage is no longer below the low/warning limit specified.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the phase index (1=L1, 2=L2, 3=L3)."
- --#TYPE "APC MDS: Distribution low output voltage alarm cleared."
- --#SUMMARY "Distribution output voltage no longer below the warning threshold."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 687
- isxModularOutputVoltageHighThresholdViolation TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger,
- mtrapargsInteger03, mtrapargsString }
- DESCRIPTION
- "WARNING: The distribution output voltage is above the high/warning limit specified.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the phase index (1=L1, 2=L2, 3=L3).
- The fourth argument is the threshold, in tenths of Volts, from which the alarm was generated."
- --#TYPE "APC MDS: Distribution high output voltage alarm."
- --#SUMMARY "Distribution output voltage is above the warning threshold."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 688
- isxModularOutputVoltageHighThresholdViolationCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger,
- mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The distribution output voltage is no longer above the high/warning limit specified.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the phase index (1=L1, 2=L2, 3=L3)."
- --#TYPE "APC MDS: Distribution high output voltage alarm cleared."
- --#SUMMARY "Distribution output voltage no longer above the warning threshold."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 689
- isxModularOutputVoltageMaxThresholdViolation TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger,
- mtrapargsInteger03, mtrapargsString }
- DESCRIPTION
- "SEVERE: The distribution output voltage is above the maximum/critical limit specified.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the phase index (1=L1, 2=L2, 3=L3).
- The fourth argument is the threshold, in tenths of Volts, from which the alarm was generated."
- --#TYPE "APC MDS: Distribution maximum output voltage alarm."
- --#SUMMARY "Distribution output voltage is above the critical threshold."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 690
- isxModularOutputVoltageMaxThresholdViolationCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger,
- mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The distribution output voltage is no longer above the maximum/critical limit specified.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the phase index (1=L1, 2=L2, 3=L3)."
- --#TYPE "APC MDS: Distribution maximum output voltage alarm cleared."
- --#SUMMARY "Distribution output voltage no longer above the critical threshold."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 691
- apcDoorClosedImproperly TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03,
- mtrapargsString04, mtrapargsInteger, mtrapargsString}
- DESCRIPTION
- "SEVERE: A door has been closed improperly.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the host device location.
- The fourth argument is the door identifier, (1=front, 2=rear)."
- --#TYPE "APC: Door closed improperly."
- --#SUMMARY "Door closed improperly."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 692
- apcDoorClosedImproperlyCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03,
- mtrapargsString04, mtrapargsInteger, mtrapargsString}
- DESCRIPTION
- "INFORMATIONAL: A door is no longer closed improperly.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the host device location.
- The fourth argument is the door identifier, (1=front, 2=rear)."
- --#TYPE "APC: Door no longer closed improperly."
- --#SUMMARY "Door no longer closed improperly."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 693
- apcUserScheduleViolation TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03,
- mtrapargsString04, mtrapargsInteger, mtrapargsString}
- DESCRIPTION
- "SEVERE: A user has had a door opened past the scheduled access period.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the host device location.
- The fourth argument is the door identifier, (1=front, 2=rear)."
- --#TYPE "APC: User schedule violated."
- --#SUMMARY "User schedule violated."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 694
- apcUserScheduleViolationCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03,
- mtrapargsString04, mtrapargsInteger, mtrapargsString}
- DESCRIPTION
- "INFORMATIONAL: User schedule violation has been cleared.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the host device location.
- The fourth argument is the door identifier, (1=front, 2=rear)."
- --#TYPE "APC: User schedule violation cleared."
- --#SUMMARY "User schedule violation cleared."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 695
- isxModularOutputFrequencyThresholdViolation TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "SEVERE: The distribution output frequency is outside of the operating range specified.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the threshold, in tenths of Hertz, from which the alarm was generated."
- --#TYPE "APC MDS: Distribution output frequency out of range."
- --#SUMMARY "Distribution output frequency out of range."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 696
- isxModularOutputFrequencyViolationCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The distribution output frequency is no longer out of range.
- The first argument is the host device serial number.
- The second argument is the host device name."
- --#TYPE "APC MDS: Distribution output frequency no longer out of range."
- --#SUMMARY "Distribution output frequency no longer out of range."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 697
- atsSourceStatusFail TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { atsIdentSerialNumber, atsConfigProductName,
- mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "SEVERE: ATS Source failed.
- The first argument is the serial number.
- The second argument is the product name.
- The third argument is an integer representing the source: 0=A, 1=B."
- --#TYPE "APC ATS: ATS Source failed."
- --#SUMMARY "ATS Source failed."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 698
-
- atsSourceStatusOk TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { atsIdentSerialNumber, atsConfigProductName,
- mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: ATS Source OK.
- The first argument is the serial number.
- The second argument is the product name.
- The third argument is an integer representing the source: 0=A, 1=B."
- --#TYPE "APC ATS: ATS Source OK."
- --#SUMMARY "ATS Source OK."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 699
- atsHardwareStatusFail TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { atsIdentSerialNumber, atsConfigProductName,
- mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "SEVERE: ATS display board hardware failed.
- The first argument is the serial number.
- The second argument is the product name.
- The third argument is an integer representing the failed hardware:
- 0= Phase LEDs/Push-button hardware failure
- 1= Seven-segment display hardware failure."
- --#TYPE "APC ATS: ATS display board hardware failed."
- --#SUMMARY "ATS display board hardware failed."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 700
-
- atsHardwareStatusOk TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { atsIdentSerialNumber, atsConfigProductName,
- mtrapargsInteger, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: ATS display board hardware ok.
- The first argument is the serial number.
- The second argument is the product name.
- The third argument is an integer representing the hardware:
- 0= Phase LEDs/Push-button hardware failure
- 1= Seven-segment display hardware failure."
- --#TYPE "APC ATS: ATS display board hardware ok."
- --#SUMMARY "ATS display board hardware ok."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 701
- atsControllerRestart TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: ATS Controller restarted."
- --#TYPE "APC ATS: ATS Controller restarted."
- --#SUMMARY "ATS Controller restarted."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 702
- xATSS1BadPhaseRotation TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
- DESCRIPTION
- "SEVERE: The device's source 1 phase rotation is bad.
- The first argument is the host device serial number.
- The second argument is the host device name."
- --#TYPE "APC XATS: S1 bad phase rotation alarm."
- --#SUMMARY "Phase rotation on source 1 is bad."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 724
- xATSS1BadPhaseRotationCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString}
- DESCRIPTION
- "INFORMATIONAL: The device's source 1 phase rotation is back to normal.
- The first argument is the host device serial number.
- The second argument is the host device name."
- --#TYPE "APC XATS: S1 phase rotation back to normal."
- --#SUMMARY "S1 phase rotation back to normal."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 725
- xATSS1BadPhaseBalance TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger,
- mtrapargsString}
- DESCRIPTION
- "SEVERE: The device's source 1 phase balance is out of bounds.
- The first argument is the host device serial number.
- The second argument is the host device name.
- The third argument is the minimum phase balance as a percentage."
- --#TYPE "APC XATS: S1 phase imbalance exceeds threshold alarm."
- --#SUMMARY "Phase imbalance on source 1 exceeds threshold."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 726
- xATSS1BadPhaseBalanceCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString}
- DESCRIPTION
- "INFORMATIONAL: The device's source 1 phase balance is back to normal.
- The first argument is the host device serial number.
- The second argument is the host device name."
- --#TYPE "APC XATS: S1 phase balance back to normal."
- --#SUMMARY "S1 phase balance back to normal."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 727
- isxModularTransformerOverheating TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsString }
- DESCRIPTION
- "SEVERE: The distribution transformer temperature is too hot.
- The first argument is the host device serial number.
- The second argument is the host device name."
- --#TYPE "APC MDS: Transformer overheating."
- --#SUMMARY "Distribution transformer temperature is too hot."
- --#ARGUMENTS { }
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 728
- isxModularTransformerOverheatingCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: The distribution transformer temperature has returned to normal.
- The first argument is the host device serial number.
- The second argument is the host device name."
- --#TYPE "APC MDS: Transformer temperature has returned to normal."
- --#SUMMARY "Distribution transformer temperature has returned to normal."
- --#ARGUMENTS { }
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 729
- apcInternalCommunicationFault TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "SEVERE: An internal UPS communication fault exists."
- --#TYPE "APC Device: An internal UPS communication fault exists."
- --#SUMMARY "An internal UPS communication fault exists."
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 730
- apcInternalCommunicationFaultCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: An internal UPS communication fault no longer exists."
- --#TYPE "APC Device:An internal UPS communication fault no longer exists."
- --#SUMMARY "An internal UPS communication fault no longer exists."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 731
- upsOutletGroupCommand TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { upsOutletGroupControlIndex, mtrapargsString }
- DESCRIPTION
- "WARNING: The specified Outlet Group command has been issued."
- --#TYPE "APC UPS: Outlet Group command issued."
- --#SUMMARY "Outlet Group command issued."
- --#ARGUMENTS { }
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 732
- onbatterycommunicationLost TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString }
- DESCRIPTION
- "SEVERE: Communication to the UPS when the UPS is on Battery. Steps
- to reestablish communication are in progress."
- --#TYPE "APC UPS: Communication lost"
- --#SUMMARY "Communication lost between the agent and the UPS when UPS is on Battery."
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE DEGRADED
- ::= 733
- isxcInformationalAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02,
- mtrapargsOctetString,
- mtrapargsInteger,
- mtrapargsString03,
- mtrapargsOctetString02,
- mtrapargsString04,
- mtrapargsOctetString03,
- mtrapargsString05,
- mtrapargsString06,
- mtrapargsString07,
- mtrapargsOctetString04,
- mtrapargsOctetString05,
- mtrapargsString08,
- mtrapargsOctetString06,
- mtrapargsOctetString07,
- mtrapargsInteger02,
- mtrapargsInteger03,
- mtrapargsOctetString08,
- mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: An ISXC Alarm exists.
- The first argument is the unique ISXC alarm ID.
- The second argument is the ISXC alarm label as a UTF8 string.
- The third argument is the ISXC alarm code.
- The fourth argument is the unique ISXC device ID.
- The fifth argument is the ISXC device label as a UTF8 string.
- The sixth argument is the ISXC parent host.
- The seventh argument is the ISXC device type as a UTF8 string.
- The eighth argument is the device serial number.
- The ninth argument is the device model number.
- The tenth argument is the device host.
- The eleventh argument is the device location as a UTF8 string.
- The twelfth argument is the device contact as a UTF8 string.
- The thirteenth argument is the unique ISXC sensor ID.
- The fourteenth argument is the ISXC sensor label as a UTF8 string.
- The fifteenth argument is the sensor value as a UTF8 string.
- The sixteenth argument is the ISXC alarm start time.
- The seventeenth argument is the ISXC alarm resolution time.
- The eighteenth argument is the description as a UTF8 string."
- --#TYPE "APC ISXC: An ISXC Informational Alarm exists."
- --#SUMMARY "An ISXC Informational Alarm exists."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 740
- isxcInformationalAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02,
- mtrapargsOctetString,
- mtrapargsInteger,
- mtrapargsString03,
- mtrapargsOctetString02,
- mtrapargsString04,
- mtrapargsOctetString03,
- mtrapargsString05,
- mtrapargsString06,
- mtrapargsString07,
- mtrapargsOctetString04,
- mtrapargsOctetString05,
- mtrapargsString08,
- mtrapargsOctetString06,
- mtrapargsOctetString07,
- mtrapargsInteger02,
- mtrapargsInteger03,
- mtrapargsOctetString08,
- mtrapargsString }
- DESCRIPTION
- "INFORMATIONAL: An ISXC Alarm has been cleared.
- The first argument is the unique ISXC alarm ID.
- The second argument is the ISXC alarm label as a UTF8 string.
- The third argument is the ISXC alarm code.
- The fourth argument is the unique ISXC device ID.
- The fifth argument is the ISXC device label as a UTF8 string.
- The sixth argument is the ISXC parent host.
- The seventh argument is the ISXC device type as a UTF8 string.
- The eighth argument is the device serial number.
- The ninth argument is the device model number.
- The tenth argument is the device host.
- The eleventh argument is the device location as a UTF8 string.
- The twelfth argument is the device contact as a UTF8 string.
- The thirteenth argument is the unique ISXC sensor ID.
- The fourteenth argument is the ISXC sensor label as a UTF8 string.
- The fifteenth argument is the sensor value as a UTF8 string.
- The sixteenth argument is the ISXC alarm start time.
- The seventeenth argument is the ISXC alarm resolution time.
- The eighteenth argument is the description as a UTF8 string."
- --#TYPE "APC ISXC: An ISXC Informational Alarm has been cleared."
- --#SUMMARY "An ISXC Informational Alarm has been cleared."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 741
- isxcWarningAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02,
- mtrapargsOctetString,
- mtrapargsInteger,
- mtrapargsString03,
- mtrapargsOctetString02,
- mtrapargsString04,
- mtrapargsOctetString03,
- mtrapargsString05,
- mtrapargsString06,
- mtrapargsString07,
- mtrapargsOctetString04,
- mtrapargsOctetString05,
- mtrapargsString08,
- mtrapargsOctetString06,
- mtrapargsOctetString07,
- mtrapargsInteger02,
- mtrapargsInteger03,
- mtrapargsOctetString08,
- mtrapargsString }
- DESCRIPTION
- "WARNING: An ISXC Alarm exists.
- The first argument is the unique ISXC alarm ID.
- The second argument is the ISXC alarm label as a UTF8 string.
- The third argument is the ISXC alarm code.
- The fourth argument is the unique ISXC device ID.
- The fifth argument is the ISXC device label as a UTF8 string.
- The sixth argument is the ISXC parent host.
- The seventh argument is the ISXC device type as a UTF8 string.
- The eighth argument is the device serial number.
- The ninth argument is the device model number.
- The tenth argument is the device host.
- The eleventh argument is the device location as a UTF8 string.
- The twelfth argument is the device contact as a UTF8 string.
- The thirteenth argument is the unique ISXC sensor ID.
- The fourteenth argument is the ISXC sensor label as a UTF8 string.
- The fifteenth argument is the sensor value as a UTF8 string.
- The sixteenth argument is the ISXC alarm start time.
- The seventeenth argument is the ISXC alarm resolution time.
- The eighteenth argument is the description as a UTF8 string."
- --#TYPE "APC ISXC: An ISXC Warning Alarm exists."
- --#SUMMARY "An ISXC Warning Alarm exists."
- --#SEVERITY WARNING
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 742
- isxcWarningAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02,
- mtrapargsOctetString,
- mtrapargsInteger,
- mtrapargsString03,
- mtrapargsOctetString02,
- mtrapargsString04,
- mtrapargsOctetString03,
- mtrapargsString05,
- mtrapargsString06,
- mtrapargsString07,
- mtrapargsOctetString04,
- mtrapargsOctetString05,
- mtrapargsString08,
- mtrapargsOctetString06,
- mtrapargsOctetString07,
- mtrapargsInteger02,
- mtrapargsInteger03,
- mtrapargsOctetString08,
- mtrapargsString }
- DESCRIPTION
- "WARNING: An ISXC Alarm has been cleared.
- The first argument is the unique ISXC alarm ID.
- The second argument is the ISXC alarm label as a UTF8 string.
- The third argument is the ISXC alarm code.
- The fourth argument is the unique ISXC device ID.
- The fifth argument is the ISXC device label as a UTF8 string.
- The sixth argument is the ISXC parent host.
- The seventh argument is the ISXC device type as a UTF8 string.
- The eighth argument is the device serial number.
- The ninth argument is the device model number.
- The tenth argument is the device host.
- The eleventh argument is the device location as a UTF8 string.
- The twelfth argument is the device contact as a UTF8 string.
- The thirteenth argument is the unique ISXC sensor ID.
- The fourteenth argument is the ISXC sensor label as a UTF8 string.
- The fifteenth argument is the sensor value as a UTF8 string.
- The sixteenth argument is the ISXC alarm start time.
- The seventeenth argument is the ISXC alarm resolution time.
- The eighteenth argument is the description as a UTF8 string."
- --#TYPE "APC ISXC: An ISXC Warning Alarm has been cleared."
- --#SUMMARY "An ISXC Warning Alarm has been cleared."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 743
-
- isxcErrorAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02,
- mtrapargsOctetString,
- mtrapargsInteger,
- mtrapargsString03,
- mtrapargsOctetString02,
- mtrapargsString04,
- mtrapargsOctetString03,
- mtrapargsString05,
- mtrapargsString06,
- mtrapargsString07,
- mtrapargsOctetString04,
- mtrapargsOctetString05,
- mtrapargsString08,
- mtrapargsOctetString06,
- mtrapargsOctetString07,
- mtrapargsInteger02,
- mtrapargsInteger03,
- mtrapargsOctetString08,
- mtrapargsString }
- DESCRIPTION
- "ERROR: An ISXC Alarm exists.
- The first argument is the unique ISXC alarm ID.
- The second argument is the ISXC alarm label as a UTF8 string.
- The third argument is the ISXC alarm code.
- The fourth argument is the unique ISXC device ID.
- The fifth argument is the ISXC device label as a UTF8 string.
- The sixth argument is the ISXC parent host.
- The seventh argument is the ISXC device type as a UTF8 string.
- The eighth argument is the device serial number.
- The ninth argument is the device model number.
- The tenth argument is the device host.
- The eleventh argument is the device location as a UTF8 string.
- The twelfth argument is the device contact as a UTF8 string.
- The thirteenth argument is the unique ISXC sensor ID.
- The fourteenth argument is the ISXC sensor label as a UTF8 string.
- The fifteenth argument is the sensor value as a UTF8 string.
- The sixteenth argument is the ISXC alarm start time.
- The seventeenth argument is the ISXC alarm resolution time.
- The eighteenth argument is the description as a UTF8 string."
- --#TYPE "APC ISXC: An ISXC Error Alarm exists."
- --#SUMMARY "An ISXC Error Alarm exists."
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 744
- isxcErrorAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02,
- mtrapargsOctetString,
- mtrapargsInteger,
- mtrapargsString03,
- mtrapargsOctetString02,
- mtrapargsString04,
- mtrapargsOctetString03,
- mtrapargsString05,
- mtrapargsString06,
- mtrapargsString07,
- mtrapargsOctetString04,
- mtrapargsOctetString05,
- mtrapargsString08,
- mtrapargsOctetString06,
- mtrapargsOctetString07,
- mtrapargsInteger02,
- mtrapargsInteger03,
- mtrapargsOctetString08,
- mtrapargsString }
- DESCRIPTION
- "ERROR: An ISXC Alarm has been cleared.
- The first argument is the unique ISXC alarm ID.
- The second argument is the ISXC alarm label as a UTF8 string.
- The third argument is the ISXC alarm code.
- The fourth argument is the unique ISXC device ID.
- The fifth argument is the ISXC device label as a UTF8 string.
- The sixth argument is the ISXC parent host.
- The seventh argument is the ISXC device type as a UTF8 string.
- The eighth argument is the device serial number.
- The ninth argument is the device model number.
- The tenth argument is the device host.
- The eleventh argument is the device location as a UTF8 string.
- The twelfth argument is the device contact as a UTF8 string.
- The thirteenth argument is the unique ISXC sensor ID.
- The fourteenth argument is the ISXC sensor label as a UTF8 string.
- The fifteenth argument is the sensor value as a UTF8 string.
- The sixteenth argument is the ISXC alarm start time.
- The seventeenth argument is the ISXC alarm resolution time.
- The eighteenth argument is the description as a UTF8 string."
- --#TYPE "APC ISXC: An ISXC Error Alarm has been cleared."
- --#SUMMARY "An ISXC Error Alarm has been cleared."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 745
-
- isxcCriticalAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02,
- mtrapargsOctetString,
- mtrapargsInteger,
- mtrapargsString03,
- mtrapargsOctetString02,
- mtrapargsString04,
- mtrapargsOctetString03,
- mtrapargsString05,
- mtrapargsString06,
- mtrapargsString07,
- mtrapargsOctetString04,
- mtrapargsOctetString05,
- mtrapargsString08,
- mtrapargsOctetString06,
- mtrapargsOctetString07,
- mtrapargsInteger02,
- mtrapargsInteger03,
- mtrapargsOctetString08,
- mtrapargsString }
- DESCRIPTION
- "CRITICAL: An ISXC Alarm exists.
- The first argument is the unique ISXC alarm ID.
- The second argument is the ISXC alarm label as a UTF8 string.
- The third argument is the ISXC alarm code.
- The fourth argument is the unique ISXC device ID.
- The fifth argument is the ISXC device label as a UTF8 string.
- The sixth argument is the ISXC parent host.
- The seventh argument is the ISXC device type as a UTF8 string.
- The eighth argument is the device serial number.
- The ninth argument is the device model number.
- The tenth argument is the device host.
- The eleventh argument is the device location as a UTF8 string.
- The twelfth argument is the device contact as a UTF8 string.
- The thirteenth argument is the unique ISXC sensor ID.
- The fourteenth argument is the ISXC sensor label as a UTF8 string.
- The fifteenth argument is the sensor value as a UTF8 string.
- The sixteenth argument is the ISXC alarm start time.
- The seventeenth argument is the ISXC alarm resolution time.
- The eighteenth argument is the description as a UTF8 string."
- --#TYPE "APC ISXC: An ISXC Critical Alarm exists."
- --#SUMMARY "An ISXC Critical Alarm exists."
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 746
- isxcCriticalAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02,
- mtrapargsOctetString,
- mtrapargsInteger,
- mtrapargsString03,
- mtrapargsOctetString02,
- mtrapargsString04,
- mtrapargsOctetString03,
- mtrapargsString05,
- mtrapargsString06,
- mtrapargsString07,
- mtrapargsOctetString04,
- mtrapargsOctetString05,
- mtrapargsString08,
- mtrapargsOctetString06,
- mtrapargsOctetString07,
- mtrapargsInteger02,
- mtrapargsInteger03,
- mtrapargsOctetString08,
- mtrapargsString }
- DESCRIPTION
- "CRITICAL: An ISXC Alarm has been cleared.
- The first argument is the unique ISXC alarm ID.
- The second argument is the ISXC alarm label as a UTF8 string.
- The third argument is the ISXC alarm code.
- The fourth argument is the unique ISXC device ID.
- The fifth argument is the ISXC device label as a UTF8 string.
- The sixth argument is the ISXC parent host.
- The seventh argument is the ISXC device type as a UTF8 string.
- The eighth argument is the device serial number.
- The ninth argument is the device model number.
- The tenth argument is the device host.
- The eleventh argument is the device location as a UTF8 string.
- The twelfth argument is the device contact as a UTF8 string.
- The thirteenth argument is the unique ISXC sensor ID.
- The fourteenth argument is the ISXC sensor label as a UTF8 string.
- The fifteenth argument is the sensor value as a UTF8 string.
- The sixteenth argument is the ISXC alarm start time.
- The seventeenth argument is the ISXC alarm resolution time.
- The eighteenth argument is the description as a UTF8 string."
- --#TYPE "APC ISXC: An ISXC Critical Alarm has been cleared."
- --#SUMMARY "An ISXC Critical Alarm has been cleared."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 747
-
- isxcFailureAlarm TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02,
- mtrapargsOctetString,
- mtrapargsInteger,
- mtrapargsString03,
- mtrapargsOctetString02,
- mtrapargsString04,
- mtrapargsOctetString03,
- mtrapargsString05,
- mtrapargsString06,
- mtrapargsString07,
- mtrapargsOctetString04,
- mtrapargsOctetString05,
- mtrapargsString08,
- mtrapargsOctetString06,
- mtrapargsOctetString07,
- mtrapargsInteger02,
- mtrapargsInteger03,
- mtrapargsOctetString08,
- mtrapargsString }
- DESCRIPTION
- "FAILURE: An ISXC Alarm exists.
- The first argument is the unique ISXC alarm ID.
- The second argument is the ISXC alarm label as a UTF8 string.
- The third argument is the ISXC alarm code.
- The fourth argument is the unique ISXC device ID.
- The fifth argument is the ISXC device label as a UTF8 string.
- The sixth argument is the ISXC parent host.
- The seventh argument is the ISXC device type as a UTF8 string.
- The eighth argument is the device serial number.
- The ninth argument is the device model number.
- The tenth argument is the device host.
- The eleventh argument is the device location as a UTF8 string.
- The twelfth argument is the device contact as a UTF8 string.
- The thirteenth argument is the unique ISXC sensor ID.
- The fourteenth argument is the ISXC sensor label as a UTF8 string.
- The fifteenth argument is the sensor value as a UTF8 string.
- The sixteenth argument is the ISXC alarm start time.
- The seventeenth argument is the ISXC alarm resolution time.
- The eighteenth argument is the description as a UTF8 string."
- --#TYPE "APC ISXC: An ISXC Failure Alarm exists."
- --#SUMMARY "An ISXC Failure Alarm exists."
- --#SEVERITY SEVERE
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 748
- isxcFailureAlarmCleared TRAP-TYPE
- ENTERPRISE apc
- VARIABLES { mtrapargsString02,
- mtrapargsOctetString,
- mtrapargsInteger,
- mtrapargsString03,
- mtrapargsOctetString02,
- mtrapargsString04,
- mtrapargsOctetString03,
- mtrapargsString05,
- mtrapargsString06,
- mtrapargsString07,
- mtrapargsOctetString04,
- mtrapargsOctetString05,
- mtrapargsString08,
- mtrapargsOctetString06,
- mtrapargsOctetString07,
- mtrapargsInteger02,
- mtrapargsInteger03,
- mtrapargsOctetString08,
- mtrapargsString }
- DESCRIPTION
- "FAILURE: An ISXC Alarm has been cleared.
- The first argument is the unique ISXC alarm ID.
- The second argument is the ISXC alarm label as a UTF8 string.
- The third argument is the ISXC alarm code.
- The fourth argument is the unique ISXC device ID.
- The fifth argument is the ISXC device label as a UTF8 string.
- The sixth argument is the ISXC parent host.
- The seventh argument is the ISXC device type as a UTF8 string.
- The eighth argument is the device serial number.
- The ninth argument is the device model number.
- The tenth argument is the device host.
- The eleventh argument is the device location as a UTF8 string.
- The twelfth argument is the device contact as a UTF8 string.
- The thirteenth argument is the unique ISXC sensor ID.
- The fourteenth argument is the ISXC sensor label as a UTF8 string.
- The fifteenth argument is the sensor value as a UTF8 string.
- The sixteenth argument is the ISXC alarm start time.
- The seventeenth argument is the ISXC alarm resolution time.
- The eighteenth argument is the description as a UTF8 string."
- --#TYPE "APC ISXC: An ISXC Failure Alarm has been cleared."
- --#SUMMARY "An ISXC Failure Alarm has been cleared."
- --#SEVERITY INFORMATIONAL
- --#TIMEINDEX 1
- --#HELP ""
- --#HELPTAG 0
- --#STATE OPERATIONAL
- ::= 749
- END
|