nxr.mib 130 KB

123456789101112131415161718192021222324252627282930313233343536373839404142434445464748495051525354555657585960616263646566676869707172737475767778798081828384858687888990919293949596979899100101102103104105106107108109110111112113114115116117118119120121122123124125126127128129130131132133134135136137138139140141142143144145146147148149150151152153154155156157158159160161162163164165166167168169170171172173174175176177178179180181182183184185186187188189190191192193194195196197198199200201202203204205206207208209210211212213214215216217218219220221222223224225226227228229230231232233234235236237238239240241242243244245246247248249250251252253254255256257258259260261262263264265266267268269270271272273274275276277278279280281282283284285286287288289290291292293294295296297298299300301302303304305306307308309310311312313314315316317318319320321322323324325326327328329330331332333334335336337338339340341342343344345346347348349350351352353354355356357358359360361362363364365366367368369370371372373374375376377378379380381382383384385386387388389390391392393394395396397398399400401402403404405406407408409410411412413414415416417418419420421422423424425426427428429430431432433434435436437438439440441442443444445446447448449450451452453454455456457458459460461462463464465466467468469470471472473474475476477478479480481482483484485486487488489490491492493494495496497498499500501502503504505506507508509510511512513514515516517518519520521522523524525526527528529530531532533534535536537538539540541542543544545546547548549550551552553554555556557558559560561562563564565566567568569570571572573574575576577578579580581582583584585586587588589590591592593594595596597598599600601602603604605606607608609610611612613614615616617618619620621622623624625626627628629630631632633634635636637638639640641642643644645646647648649650651652653654655656657658659660661662663664665666667668669670671672673674675676677678679680681682683684685686687688689690691692693694695696697698699700701702703704705706707708709710711712713714715716717718719720721722723724725726727728729730731732733734735736737738739740741742743744745746747748749750751752753754755756757758759760761762763764765766767768769770771772773774775776777778779780781782783784785786787788789790791792793794795796797798799800801802803804805806807808809810811812813814815816817818819820821822823824825826827828829830831832833834835836837838839840841842843844845846847848849850851852853854855856857858859860861862863864865866867868869870871872873874875876877878879880881882883884885886887888889890891892893894895896897898899900901902903904905906907908909910911912913914915916917918919920921922923924925926927928929930931932933934935936937938939940941942943944945946947948949950951952953954955956957958959960961962963964965966967968969970971972973974975976977978979980981982983984985986987988989990991992993994995996997998999100010011002100310041005100610071008100910101011101210131014101510161017101810191020102110221023102410251026102710281029103010311032103310341035103610371038103910401041104210431044104510461047104810491050105110521053105410551056105710581059106010611062106310641065106610671068106910701071107210731074107510761077107810791080108110821083108410851086108710881089109010911092109310941095109610971098109911001101110211031104110511061107110811091110111111121113111411151116111711181119112011211122112311241125112611271128112911301131113211331134113511361137113811391140114111421143114411451146114711481149115011511152115311541155115611571158115911601161116211631164116511661167116811691170117111721173117411751176117711781179118011811182118311841185118611871188118911901191119211931194119511961197119811991200120112021203120412051206120712081209121012111212121312141215121612171218121912201221122212231224122512261227122812291230123112321233123412351236123712381239124012411242124312441245124612471248124912501251125212531254125512561257125812591260126112621263126412651266126712681269127012711272127312741275127612771278127912801281128212831284128512861287128812891290129112921293129412951296129712981299130013011302130313041305130613071308130913101311131213131314131513161317131813191320132113221323132413251326132713281329133013311332133313341335133613371338133913401341134213431344134513461347134813491350135113521353135413551356135713581359136013611362136313641365136613671368136913701371137213731374137513761377137813791380138113821383138413851386138713881389139013911392139313941395139613971398139914001401140214031404140514061407140814091410141114121413141414151416141714181419142014211422142314241425142614271428142914301431143214331434143514361437143814391440144114421443144414451446144714481449145014511452145314541455145614571458145914601461146214631464146514661467146814691470147114721473147414751476147714781479148014811482148314841485148614871488148914901491149214931494149514961497149814991500150115021503150415051506150715081509151015111512151315141515151615171518151915201521152215231524152515261527152815291530153115321533153415351536153715381539154015411542154315441545154615471548154915501551155215531554155515561557155815591560156115621563156415651566156715681569157015711572157315741575157615771578157915801581158215831584158515861587158815891590159115921593159415951596159715981599160016011602160316041605160616071608160916101611161216131614161516161617161816191620162116221623162416251626162716281629163016311632163316341635163616371638163916401641164216431644164516461647164816491650165116521653165416551656165716581659166016611662166316641665166616671668166916701671167216731674167516761677167816791680168116821683168416851686168716881689169016911692169316941695169616971698169917001701170217031704170517061707170817091710171117121713171417151716171717181719172017211722172317241725172617271728172917301731173217331734173517361737173817391740174117421743174417451746174717481749175017511752175317541755175617571758175917601761176217631764176517661767176817691770177117721773177417751776177717781779178017811782178317841785178617871788178917901791179217931794179517961797179817991800180118021803180418051806180718081809181018111812181318141815181618171818181918201821182218231824182518261827182818291830183118321833183418351836183718381839184018411842184318441845184618471848184918501851185218531854185518561857185818591860186118621863186418651866186718681869187018711872187318741875187618771878187918801881188218831884188518861887188818891890189118921893189418951896189718981899190019011902190319041905190619071908190919101911191219131914191519161917191819191920192119221923192419251926192719281929193019311932193319341935193619371938193919401941194219431944194519461947194819491950195119521953195419551956195719581959196019611962196319641965196619671968196919701971197219731974197519761977197819791980198119821983198419851986198719881989199019911992199319941995199619971998199920002001200220032004200520062007200820092010201120122013201420152016201720182019202020212022202320242025202620272028202920302031203220332034203520362037203820392040204120422043204420452046204720482049205020512052205320542055205620572058205920602061206220632064206520662067206820692070207120722073207420752076207720782079208020812082208320842085208620872088208920902091209220932094209520962097209820992100210121022103210421052106210721082109211021112112211321142115211621172118211921202121212221232124212521262127212821292130213121322133213421352136213721382139214021412142214321442145214621472148214921502151215221532154215521562157215821592160216121622163216421652166216721682169217021712172217321742175217621772178217921802181218221832184218521862187218821892190219121922193219421952196219721982199220022012202220322042205220622072208220922102211221222132214221522162217221822192220222122222223222422252226222722282229223022312232223322342235223622372238223922402241224222432244224522462247224822492250225122522253225422552256225722582259226022612262226322642265226622672268226922702271227222732274227522762277227822792280228122822283228422852286228722882289229022912292229322942295229622972298229923002301230223032304230523062307230823092310231123122313231423152316231723182319232023212322232323242325232623272328232923302331233223332334233523362337233823392340234123422343234423452346234723482349235023512352235323542355235623572358235923602361236223632364236523662367236823692370237123722373237423752376237723782379238023812382238323842385238623872388238923902391239223932394239523962397239823992400240124022403240424052406240724082409241024112412241324142415241624172418241924202421242224232424242524262427242824292430243124322433243424352436243724382439244024412442244324442445244624472448244924502451245224532454245524562457245824592460246124622463246424652466246724682469247024712472247324742475247624772478247924802481248224832484248524862487248824892490249124922493249424952496249724982499250025012502250325042505250625072508250925102511251225132514251525162517251825192520252125222523252425252526252725282529253025312532253325342535253625372538253925402541254225432544254525462547254825492550255125522553255425552556255725582559256025612562256325642565256625672568256925702571257225732574257525762577257825792580258125822583258425852586258725882589259025912592259325942595259625972598259926002601260226032604260526062607260826092610261126122613261426152616261726182619262026212622262326242625262626272628262926302631263226332634263526362637263826392640264126422643264426452646264726482649265026512652265326542655265626572658265926602661266226632664266526662667266826692670267126722673267426752676267726782679268026812682268326842685268626872688268926902691269226932694269526962697269826992700270127022703270427052706270727082709271027112712271327142715271627172718271927202721272227232724272527262727272827292730273127322733273427352736273727382739274027412742274327442745274627472748274927502751275227532754275527562757275827592760276127622763276427652766276727682769277027712772277327742775277627772778277927802781278227832784278527862787278827892790279127922793279427952796279727982799280028012802280328042805280628072808280928102811281228132814281528162817281828192820282128222823282428252826282728282829283028312832283328342835283628372838283928402841284228432844284528462847284828492850285128522853285428552856285728582859286028612862286328642865286628672868286928702871287228732874287528762877287828792880288128822883288428852886288728882889289028912892289328942895289628972898289929002901290229032904290529062907290829092910291129122913291429152916291729182919292029212922292329242925292629272928292929302931293229332934293529362937293829392940294129422943294429452946294729482949295029512952295329542955295629572958295929602961296229632964296529662967296829692970297129722973297429752976297729782979298029812982298329842985298629872988298929902991299229932994299529962997299829993000300130023003300430053006300730083009301030113012301330143015301630173018301930203021302230233024302530263027302830293030303130323033303430353036303730383039304030413042304330443045304630473048304930503051305230533054305530563057305830593060306130623063306430653066306730683069307030713072307330743075307630773078307930803081308230833084308530863087308830893090309130923093309430953096309730983099310031013102310331043105310631073108310931103111311231133114311531163117311831193120312131223123312431253126312731283129313031313132313331343135313631373138313931403141314231433144314531463147314831493150315131523153315431553156315731583159316031613162316331643165316631673168316931703171317231733174317531763177317831793180318131823183318431853186318731883189319031913192319331943195319631973198319932003201320232033204320532063207320832093210321132123213321432153216321732183219322032213222322332243225322632273228322932303231323232333234323532363237323832393240324132423243324432453246324732483249325032513252325332543255325632573258325932603261326232633264326532663267326832693270327132723273327432753276327732783279328032813282328332843285328632873288328932903291329232933294329532963297329832993300330133023303330433053306330733083309331033113312331333143315331633173318331933203321332233233324332533263327332833293330333133323333333433353336333733383339334033413342334333443345334633473348334933503351335233533354335533563357335833593360336133623363336433653366336733683369337033713372337333743375337633773378337933803381338233833384338533863387338833893390339133923393339433953396339733983399340034013402340334043405340634073408340934103411341234133414341534163417341834193420342134223423342434253426342734283429343034313432343334343435343634373438343934403441344234433444344534463447344834493450345134523453345434553456345734583459346034613462346334643465346634673468346934703471347234733474347534763477347834793480348134823483348434853486348734883489349034913492349334943495349634973498349935003501350235033504350535063507350835093510351135123513351435153516351735183519352035213522352335243525352635273528352935303531353235333534353535363537353835393540354135423543354435453546354735483549355035513552355335543555355635573558355935603561356235633564356535663567356835693570357135723573357435753576357735783579358035813582358335843585358635873588358935903591359235933594359535963597359835993600360136023603360436053606360736083609361036113612361336143615361636173618361936203621362236233624362536263627362836293630363136323633363436353636363736383639364036413642364336443645364636473648364936503651365236533654365536563657365836593660366136623663366436653666366736683669367036713672367336743675367636773678367936803681368236833684368536863687368836893690369136923693369436953696369736983699370037013702370337043705370637073708370937103711371237133714371537163717371837193720372137223723372437253726372737283729373037313732373337343735373637373738373937403741374237433744374537463747374837493750375137523753375437553756375737583759376037613762376337643765376637673768376937703771377237733774377537763777377837793780378137823783378437853786378737883789379037913792379337943795379637973798379938003801380238033804380538063807380838093810381138123813381438153816381738183819382038213822382338243825382638273828382938303831383238333834383538363837383838393840384138423843384438453846384738483849385038513852385338543855385638573858385938603861386238633864386538663867386838693870387138723873387438753876387738783879388038813882388338843885388638873888388938903891389238933894389538963897389838993900390139023903390439053906390739083909391039113912391339143915391639173918391939203921392239233924392539263927392839293930393139323933393439353936393739383939394039413942394339443945394639473948394939503951395239533954395539563957395839593960396139623963396439653966396739683969397039713972397339743975397639773978397939803981398239833984398539863987398839893990399139923993399439953996399739983999400040014002400340044005400640074008400940104011401240134014401540164017401840194020402140224023402440254026402740284029403040314032403340344035403640374038403940404041404240434044404540464047404840494050405140524053405440554056405740584059406040614062406340644065406640674068406940704071407240734074407540764077407840794080408140824083408440854086408740884089409040914092409340944095409640974098409941004101410241034104410541064107410841094110411141124113411441154116411741184119412041214122412341244125412641274128412941304131413241334134413541364137413841394140414141424143414441454146414741484149415041514152415341544155415641574158415941604161416241634164416541664167416841694170417141724173417441754176417741784179418041814182418341844185418641874188418941904191419241934194419541964197419841994200420142024203420442054206420742084209421042114212421342144215421642174218421942204221422242234224422542264227422842294230423142324233423442354236423742384239424042414242424342444245424642474248424942504251425242534254425542564257425842594260426142624263426442654266426742684269427042714272427342744275427642774278427942804281428242834284428542864287428842894290429142924293429442954296429742984299430043014302430343044305430643074308430943104311431243134314431543164317431843194320432143224323432443254326432743284329433043314332433343344335433643374338433943404341434243434344434543464347434843494350435143524353435443554356435743584359436043614362436343644365436643674368436943704371437243734374437543764377437843794380438143824383438443854386438743884389439043914392439343944395439643974398439944004401440244034404440544064407440844094410441144124413441444154416441744184419442044214422442344244425442644274428442944304431443244334434443544364437443844394440444144424443444444454446444744484449445044514452445344544455445644574458445944604461446244634464446544664467446844694470447144724473447444754476447744784479448044814482448344844485448644874488448944904491449244934494449544964497449844994500450145024503450445054506450745084509451045114512451345144515451645174518451945204521452245234524452545264527452845294530453145324533453445354536453745384539454045414542454345444545454645474548454945504551455245534554455545564557455845594560456145624563456445654566456745684569457045714572457345744575457645774578457945804581458245834584458545864587458845894590459145924593459445954596459745984599460046014602460346044605460646074608460946104611461246134614461546164617461846194620462146224623462446254626462746284629463046314632463346344635463646374638463946404641464246434644464546464647464846494650465146524653465446554656465746584659466046614662466346644665466646674668466946704671467246734674467546764677467846794680468146824683468446854686468746884689469046914692469346944695469646974698469947004701470247034704470547064707470847094710471147124713471447154716471747184719472047214722472347244725472647274728472947304731473247334734473547364737473847394740474147424743474447454746474747484749475047514752475347544755475647574758475947604761476247634764476547664767476847694770477147724773477447754776477747784779478047814782478347844785478647874788478947904791479247934794479547964797479847994800480148024803480448054806480748084809481048114812481348144815481648174818481948204821482248234824482548264827482848294830483148324833483448354836483748384839484048414842484348444845484648474848484948504851485248534854485548564857485848594860486148624863486448654866486748684869487048714872487348744875487648774878487948804881488248834884488548864887488848894890489148924893489448954896489748984899490049014902490349044905490649074908490949104911491249134914491549164917491849194920492149224923492449254926492749284929
  1. ------------------------------------------------------------
  2. -- EMERSON NETWORK POWER
  3. -- SIC MIB
  4. ------------------------------------------------------------
  5. ENP-nxr-MIB DEFINITIONS ::= BEGIN
  6. IMPORTS
  7. MODULE-IDENTITY, OBJECT-TYPE, NOTIFICATION-TYPE,
  8. Integer32, Counter32, enterprises
  9. FROM SNMPv2-SMI
  10. TEXTUAL-CONVENTION, DisplayString, DateAndTime
  11. FROM SNMPv2-TC;
  12. ------------------------------------------------------------
  13. -- Node definitions
  14. ------------------------------------------------------------
  15. enp OBJECT IDENTIFIER ::= { enterprises 13400 }
  16. products OBJECT IDENTIFIER ::= { enp 2 }
  17. nxrMIB MODULE-IDENTITY
  18. LAST-UPDATED "200911231030Z"
  19. ORGANIZATION "
  20. EMERSON NETWORK POWER (ENP)"
  21. CONTACT-INFO "
  22. EMERSON NETWORK POWER"
  23. DESCRIPTION "
  24. EMERSON NETWORK POWER (ENP) SIC MIB."
  25. ::= { products 19 }
  26. ------------------------------------------------------------
  27. -- Textual conventions
  28. ------------------------------------------------------------
  29. Status ::= TEXTUAL-CONVENTION
  30. STATUS current
  31. DESCRIPTION "
  32. The severity of the alarm. One of
  33. (0) informational
  34. (1) warning
  35. (2) critical"
  36. SYNTAX INTEGER {
  37. informational(0),
  38. warning(1),
  39. critical(2) }
  40. StatusChange ::= TEXTUAL-CONVENTION
  41. STATUS current
  42. DESCRIPTION "
  43. Indicates 'activated' (0) or 'deactivated' (1) alarm events."
  44. SYNTAX INTEGER {
  45. activated(0),
  46. deactivated(1) }
  47. ------------------------------------------------------------
  48. -- 1.1 Identification of the plant { nxrMIB 1 }
  49. ------------------------------------------------------------
  50. ident OBJECT IDENTIFIER ::= { nxrMIB 1 }
  51. identManufacturer OBJECT-TYPE
  52. SYNTAX DisplayString
  53. MAX-ACCESS read-only
  54. STATUS current
  55. DESCRIPTION "
  56. The name of the device manufacturer."
  57. ::= { ident 1 }
  58. identModel OBJECT-TYPE
  59. SYNTAX DisplayString
  60. MAX-ACCESS read-only
  61. STATUS current
  62. DESCRIPTION "
  63. The manufacturers model designation of the device."
  64. ::= { ident 2 }
  65. identIndex OBJECT-TYPE
  66. SYNTAX Integer32
  67. MAX-ACCESS read-write
  68. STATUS current
  69. DESCRIPTION "
  70. The sequence number of the device."
  71. ::= { ident 3 }
  72. ------------------------------------------------------------
  73. -- 1.2 system values { nxrMIB 2 }
  74. ------------------------------------------------------------
  75. system OBJECT IDENTIFIER ::= { nxrMIB 2 }
  76. -- ------------------------------------------------------------------------
  77. -- 1.2.1 the status group
  78. -- ------------------------------------------------------------------------
  79. status OBJECT IDENTIFIER ::= { system 1 }
  80. systemStatus OBJECT-TYPE
  81. SYNTAX Status
  82. MAX-ACCESS read-only
  83. STATUS current
  84. DESCRIPTION "
  85. Status of the complete plant (highest alarm). One of
  86. (0) normal
  87. (1) warning
  88. (2) critical"
  89. ::= { status 1 }
  90. -- ------------------------------------------------------------------------
  91. -- 1.2.2 the systemdata group
  92. -- ------------------------------------------------------------------------
  93. systemdata OBJECT IDENTIFIER ::= { system 2 }
  94. systemOutputAcitvePowerA OBJECT-TYPE
  95. SYNTAX Integer32
  96. MAX-ACCESS read-only
  97. STATUS current
  98. DESCRIPTION
  99. "System Output Acitve Power A, stored as 0.01 kW."
  100. ::= { systemdata 1 }
  101. systemOutputAcitvePowerB OBJECT-TYPE
  102. SYNTAX Integer32
  103. MAX-ACCESS read-only
  104. STATUS current
  105. DESCRIPTION
  106. "System Output Acitve Power B, stored as 0.01 kW."
  107. ::= { systemdata 2 }
  108. systemOutputAcitvePowerC OBJECT-TYPE
  109. SYNTAX Integer32
  110. MAX-ACCESS read-only
  111. STATUS current
  112. DESCRIPTION
  113. "System Output Acitve Power C, stored as 0.01 kW."
  114. ::= { systemdata 3 }
  115. systemOutputAppPowerA OBJECT-TYPE
  116. SYNTAX Integer32
  117. MAX-ACCESS read-only
  118. STATUS current
  119. DESCRIPTION
  120. "System Output App Power A, stored as 0.01 kVA."
  121. ::= { systemdata 4 }
  122. systemOutputAppPowerB OBJECT-TYPE
  123. SYNTAX Integer32
  124. MAX-ACCESS read-only
  125. STATUS current
  126. DESCRIPTION
  127. "System Output App Power B, stored as 0.01 kVA."
  128. ::= { systemdata 5 }
  129. systemOutputAppPowerC OBJECT-TYPE
  130. SYNTAX Integer32
  131. MAX-ACCESS read-only
  132. STATUS current
  133. DESCRIPTION
  134. "System Output App Power C, stored as 0.01 kVA."
  135. ::= { systemdata 6 }
  136. systemOutputReactivePowerA OBJECT-TYPE
  137. SYNTAX Integer32
  138. MAX-ACCESS read-only
  139. STATUS current
  140. DESCRIPTION
  141. "System Output Reactive Power A, stored as 0.01 KVAR."
  142. ::= { systemdata 7 }
  143. systemOutputReactivePowerB OBJECT-TYPE
  144. SYNTAX Integer32
  145. MAX-ACCESS read-only
  146. STATUS current
  147. DESCRIPTION
  148. "System Output Reactive Power B, stored as 0.01 KVAR."
  149. ::= { systemdata 8 }
  150. systemOutputReactivePowerC OBJECT-TYPE
  151. SYNTAX Integer32
  152. MAX-ACCESS read-only
  153. STATUS current
  154. DESCRIPTION
  155. "System Output Reactive Power C, stored as 0.01 KVAR."
  156. ::= { systemdata 9 }
  157. -- ------------------------------------------------------------------------
  158. -- 1.2.3 the unit group
  159. -- ------------------------------------------------------------------------
  160. unit OBJECT IDENTIFIER ::= { system 3 }
  161. unitModules OBJECT-TYPE
  162. SYNTAX Integer32
  163. MAX-ACCESS read-only
  164. STATUS current
  165. DESCRIPTION
  166. "Unit Modules, stored as 0.01."
  167. ::= { unit 1 }
  168. unitCapacity OBJECT-TYPE
  169. SYNTAX Integer32
  170. MAX-ACCESS read-only
  171. STATUS current
  172. DESCRIPTION
  173. "Unit Capacity, stored as 0.01 kVA."
  174. ::= { unit 2 }
  175. moduleCapacity OBJECT-TYPE
  176. SYNTAX Integer32
  177. MAX-ACCESS read-only
  178. STATUS current
  179. DESCRIPTION
  180. "Module Capacity, stored as 0.01 kVA."
  181. ::= { unit 3 }
  182. -- ------------------------------------------------------------------------
  183. -- 1.2.4 the main group
  184. -- ------------------------------------------------------------------------
  185. analogdata OBJECT IDENTIFIER ::= { system 4 }
  186. inputPhaseVoltageA OBJECT-TYPE
  187. SYNTAX Integer32
  188. MAX-ACCESS read-only
  189. STATUS current
  190. DESCRIPTION
  191. "Input Phase Voltage A, stored as 0.01 V."
  192. ::= { analogdata 1 }
  193. inputPhaseVoltageB OBJECT-TYPE
  194. SYNTAX Integer32
  195. MAX-ACCESS read-only
  196. STATUS current
  197. DESCRIPTION
  198. "Input Phase Voltage B, stored as 0.01 V."
  199. ::= { analogdata 2 }
  200. inputPhaseVoltageC OBJECT-TYPE
  201. SYNTAX Integer32
  202. MAX-ACCESS read-only
  203. STATUS current
  204. DESCRIPTION
  205. "Input Phase Voltage C, stored as 0.01 V."
  206. ::= { analogdata 3 }
  207. inputLineVoltageA OBJECT-TYPE
  208. SYNTAX Integer32
  209. MAX-ACCESS read-only
  210. STATUS current
  211. DESCRIPTION
  212. "Input Line Voltage A, stored as 0.01 V."
  213. ::= { analogdata 4 }
  214. inputLineVoltageB OBJECT-TYPE
  215. SYNTAX Integer32
  216. MAX-ACCESS read-only
  217. STATUS current
  218. DESCRIPTION
  219. "Input Line Voltage B, stored as 0.01 V."
  220. ::= { analogdata 5 }
  221. inputLineVoltageC OBJECT-TYPE
  222. SYNTAX Integer32
  223. MAX-ACCESS read-only
  224. STATUS current
  225. DESCRIPTION
  226. "Input Line Voltage C, stored as 0.01 V."
  227. ::= { analogdata 6 }
  228. inputCurrentA OBJECT-TYPE
  229. SYNTAX Integer32
  230. MAX-ACCESS read-only
  231. STATUS current
  232. DESCRIPTION
  233. "Input Current A, stored as 0.01 A."
  234. ::= { analogdata 7 }
  235. inputCurrentB OBJECT-TYPE
  236. SYNTAX Integer32
  237. MAX-ACCESS read-only
  238. STATUS current
  239. DESCRIPTION
  240. "Input Current B, stored as 0.01 A."
  241. ::= { analogdata 8 }
  242. inputCurrentC OBJECT-TYPE
  243. SYNTAX Integer32
  244. MAX-ACCESS read-only
  245. STATUS current
  246. DESCRIPTION
  247. "Input Current C, stored as 0.01 A."
  248. ::= { analogdata 9 }
  249. inputFrequency OBJECT-TYPE
  250. SYNTAX Integer32
  251. MAX-ACCESS read-only
  252. STATUS current
  253. DESCRIPTION
  254. "Input Frequency, stored as 0.01 Hz."
  255. ::= { analogdata 10 }
  256. inputPowerFactorA OBJECT-TYPE
  257. SYNTAX Integer32
  258. MAX-ACCESS read-only
  259. STATUS current
  260. DESCRIPTION
  261. "Input Power Factor A, stored as 0.01."
  262. ::= { analogdata 11 }
  263. inputPowerFactorB OBJECT-TYPE
  264. SYNTAX Integer32
  265. MAX-ACCESS read-only
  266. STATUS current
  267. DESCRIPTION
  268. "Input Power Factor B, stored as 0.01."
  269. ::= { analogdata 12 }
  270. inputPowerFactorC OBJECT-TYPE
  271. SYNTAX Integer32
  272. MAX-ACCESS read-only
  273. STATUS current
  274. DESCRIPTION
  275. "Input Power Factor C, stored as 0.01."
  276. ::= { analogdata 13 }
  277. dCBus1Voltage OBJECT-TYPE
  278. SYNTAX Integer32
  279. MAX-ACCESS read-only
  280. STATUS current
  281. DESCRIPTION
  282. "DCBus1 Voltage, stored as 0.01 V."
  283. ::= { analogdata 14 }
  284. dCBus2Voltage OBJECT-TYPE
  285. SYNTAX Integer32
  286. MAX-ACCESS read-only
  287. STATUS current
  288. DESCRIPTION
  289. "DCBus2 Voltage, stored as 0.01 V."
  290. ::= { analogdata 15 }
  291. outputVoltageA OBJECT-TYPE
  292. SYNTAX Integer32
  293. MAX-ACCESS read-only
  294. STATUS current
  295. DESCRIPTION
  296. "Output voltage A, stored as 0.01 V."
  297. ::= { analogdata 16 }
  298. outputVoltageB OBJECT-TYPE
  299. SYNTAX Integer32
  300. MAX-ACCESS read-only
  301. STATUS current
  302. DESCRIPTION
  303. "Output voltage B, stored as 0.01 V."
  304. ::= { analogdata 17 }
  305. outputVoltageC OBJECT-TYPE
  306. SYNTAX Integer32
  307. MAX-ACCESS read-only
  308. STATUS current
  309. DESCRIPTION
  310. "Output voltage C, stored as 0.01 V."
  311. ::= { analogdata 18 }
  312. outputCurrentA OBJECT-TYPE
  313. SYNTAX Integer32
  314. MAX-ACCESS read-only
  315. STATUS current
  316. DESCRIPTION
  317. "Output current A, stored as 0.01 A."
  318. ::= { analogdata 19 }
  319. outputCurrentB OBJECT-TYPE
  320. SYNTAX Integer32
  321. MAX-ACCESS read-only
  322. STATUS current
  323. DESCRIPTION
  324. "Output current B, stored as 0.01 A."
  325. ::= { analogdata 20 }
  326. outputCurrentC OBJECT-TYPE
  327. SYNTAX Integer32
  328. MAX-ACCESS read-only
  329. STATUS current
  330. DESCRIPTION
  331. "Output current C, stored as 0.01 A."
  332. ::= { analogdata 21 }
  333. outputFrequency OBJECT-TYPE
  334. SYNTAX Integer32
  335. MAX-ACCESS read-only
  336. STATUS current
  337. DESCRIPTION
  338. "Output Frequency, stored as 0.01 Hz."
  339. ::= { analogdata 22 }
  340. outputPowerFactorA OBJECT-TYPE
  341. SYNTAX Integer32
  342. MAX-ACCESS read-only
  343. STATUS current
  344. DESCRIPTION
  345. "Output Power Factor A, stored as 0.01."
  346. ::= { analogdata 23 }
  347. outputPowerFactorB OBJECT-TYPE
  348. SYNTAX Integer32
  349. MAX-ACCESS read-only
  350. STATUS current
  351. DESCRIPTION
  352. "Output Power Factor B, stored as 0.01."
  353. ::= { analogdata 24 }
  354. outputPowerFactorC OBJECT-TYPE
  355. SYNTAX Integer32
  356. MAX-ACCESS read-only
  357. STATUS current
  358. DESCRIPTION
  359. "Output Power Factor C, stored as 0.01."
  360. ::= { analogdata 25 }
  361. outputAcitvePowerA OBJECT-TYPE
  362. SYNTAX Integer32
  363. MAX-ACCESS read-only
  364. STATUS current
  365. DESCRIPTION
  366. "Output Acitve Power A, stored as 0.01 kW."
  367. ::= { analogdata 26 }
  368. outputAcitvePowerB OBJECT-TYPE
  369. SYNTAX Integer32
  370. MAX-ACCESS read-only
  371. STATUS current
  372. DESCRIPTION
  373. "Output Acitve Power B, stored as 0.01 kW."
  374. ::= { analogdata 27 }
  375. outputAcitvePowerC OBJECT-TYPE
  376. SYNTAX Integer32
  377. MAX-ACCESS read-only
  378. STATUS current
  379. DESCRIPTION
  380. "Output Acitve Power C, stored as 0.01 kW."
  381. ::= { analogdata 28 }
  382. outputReactivePowerA OBJECT-TYPE
  383. SYNTAX Integer32
  384. MAX-ACCESS read-only
  385. STATUS current
  386. DESCRIPTION
  387. "Output Reactive Power A, stored as 0.01 KVAR."
  388. ::= { analogdata 29 }
  389. outputReactivePowerB OBJECT-TYPE
  390. SYNTAX Integer32
  391. MAX-ACCESS read-only
  392. STATUS current
  393. DESCRIPTION
  394. "Output Reactive Power B, stored as 0.01 KVAR."
  395. ::= { analogdata 30 }
  396. outputReactivePowerC OBJECT-TYPE
  397. SYNTAX Integer32
  398. MAX-ACCESS read-only
  399. STATUS current
  400. DESCRIPTION
  401. "Output Reactive Power C, stored as 0.01 KVAR."
  402. ::= { analogdata 31 }
  403. outputAppPowerA OBJECT-TYPE
  404. SYNTAX Integer32
  405. MAX-ACCESS read-only
  406. STATUS current
  407. DESCRIPTION
  408. "Output App Power A, stored as 0.01 kVA."
  409. ::= { analogdata 32 }
  410. outputAppPowerB OBJECT-TYPE
  411. SYNTAX Integer32
  412. MAX-ACCESS read-only
  413. STATUS current
  414. DESCRIPTION
  415. "Output App Power B, stored as 0.01 kVA."
  416. ::= { analogdata 33 }
  417. outputAppPowerC OBJECT-TYPE
  418. SYNTAX Integer32
  419. MAX-ACCESS read-only
  420. STATUS current
  421. DESCRIPTION
  422. "Output App Power C, stored as 0.01 kVA."
  423. ::= { analogdata 34 }
  424. outputLoadA OBJECT-TYPE
  425. SYNTAX Integer32
  426. MAX-ACCESS read-only
  427. STATUS current
  428. DESCRIPTION
  429. "Output Load A, stored as 0.01 %."
  430. ::= { analogdata 35 }
  431. outputLoadB OBJECT-TYPE
  432. SYNTAX Integer32
  433. MAX-ACCESS read-only
  434. STATUS current
  435. DESCRIPTION
  436. "Output Load B, stored as 0.01 %."
  437. ::= { analogdata 36 }
  438. outputLoadC OBJECT-TYPE
  439. SYNTAX Integer32
  440. MAX-ACCESS read-only
  441. STATUS current
  442. DESCRIPTION
  443. "Output Load C, stored as 0.01 %."
  444. ::= { analogdata 37 }
  445. outputCrestFactorA OBJECT-TYPE
  446. SYNTAX Integer32
  447. MAX-ACCESS read-only
  448. STATUS current
  449. DESCRIPTION
  450. "Output Crest Factor A, stored as 0.01 ."
  451. ::= { analogdata 38 }
  452. outputCrestFactorB OBJECT-TYPE
  453. SYNTAX Integer32
  454. MAX-ACCESS read-only
  455. STATUS current
  456. DESCRIPTION
  457. "Output Crest Factor B, stored as 0.01 ."
  458. ::= { analogdata 39 }
  459. outputCrestFactorC OBJECT-TYPE
  460. SYNTAX Integer32
  461. MAX-ACCESS read-only
  462. STATUS current
  463. DESCRIPTION
  464. "Output Crest Factor C, stored as 0.01 ."
  465. ::= { analogdata 40 }
  466. bypassVoltageA OBJECT-TYPE
  467. SYNTAX Integer32
  468. MAX-ACCESS read-only
  469. STATUS current
  470. DESCRIPTION
  471. "Bypass Voltage A, stored as 0.01 V."
  472. ::= { analogdata 41 }
  473. bypassVoltageB OBJECT-TYPE
  474. SYNTAX Integer32
  475. MAX-ACCESS read-only
  476. STATUS current
  477. DESCRIPTION
  478. "Bypass Voltage B, stored as 0.01 V."
  479. ::= { analogdata 42 }
  480. bypassVoltageC OBJECT-TYPE
  481. SYNTAX Integer32
  482. MAX-ACCESS read-only
  483. STATUS current
  484. DESCRIPTION
  485. "Bypass Voltage C, stored as 0.01 V."
  486. ::= { analogdata 43 }
  487. bypassFrequency OBJECT-TYPE
  488. SYNTAX Integer32
  489. MAX-ACCESS read-only
  490. STATUS current
  491. DESCRIPTION
  492. "Bypass Frequency, stored as 0.01 Hz."
  493. ::= { analogdata 44 }
  494. positiveBatteryVoltage OBJECT-TYPE
  495. SYNTAX Integer32
  496. MAX-ACCESS read-only
  497. STATUS current
  498. DESCRIPTION
  499. "positive Battery Voltage, stored as 0.01 V."
  500. ::= { analogdata 45 }
  501. positiveBatteryCurrent OBJECT-TYPE
  502. SYNTAX Integer32
  503. MAX-ACCESS read-only
  504. STATUS current
  505. DESCRIPTION
  506. "positive Battery Current, stored as 0.01 A."
  507. ::= { analogdata 46 }
  508. negativeBatteryVoltage OBJECT-TYPE
  509. SYNTAX Integer32
  510. MAX-ACCESS read-only
  511. STATUS current
  512. DESCRIPTION
  513. "negative Battery Voltage, stored as 0.01 V."
  514. ::= { analogdata 47 }
  515. negativeBatteryCurrent OBJECT-TYPE
  516. SYNTAX Integer32
  517. MAX-ACCESS read-only
  518. STATUS current
  519. DESCRIPTION
  520. "negative Battery Current, stored as 0.01 A."
  521. ::= { analogdata 48 }
  522. batteryAgingRate OBJECT-TYPE
  523. SYNTAX Integer32
  524. MAX-ACCESS read-only
  525. STATUS current
  526. DESCRIPTION
  527. "Battery Aging Rate, stored as 0.01."
  528. ::= { analogdata 49 }
  529. batteryRemainsTime OBJECT-TYPE
  530. SYNTAX Integer32
  531. MAX-ACCESS read-only
  532. STATUS current
  533. DESCRIPTION
  534. "Battery Remains Time, stored as 0.01 Hour."
  535. ::= { analogdata 50 }
  536. batteryTemperature OBJECT-TYPE
  537. SYNTAX Integer32
  538. MAX-ACCESS read-only
  539. STATUS current
  540. DESCRIPTION
  541. "Battery Temperature, stored as 0.01 °C."
  542. ::= { analogdata 51 }
  543. batteryEnvironmentTemperature OBJECT-TYPE
  544. SYNTAX Integer32
  545. MAX-ACCESS read-only
  546. STATUS current
  547. DESCRIPTION
  548. "Battery Environment Temperature, stored as 0.01 °C."
  549. ::= { analogdata 52 }
  550. -- ------------------------------------------------------------------------
  551. -- 1.2.5 the bypass group
  552. -- ------------------------------------------------------------------------
  553. analogdata1 OBJECT IDENTIFIER ::= { system 5 }
  554. inputPhaseVoltageA1 OBJECT-TYPE
  555. SYNTAX Integer32
  556. MAX-ACCESS read-only
  557. STATUS current
  558. DESCRIPTION
  559. "Input Phase Voltage A, stored as 0.01 V."
  560. ::= { analogdata1 1 }
  561. inputPhaseVoltageB1 OBJECT-TYPE
  562. SYNTAX Integer32
  563. MAX-ACCESS read-only
  564. STATUS current
  565. DESCRIPTION
  566. "Input Phase Voltage B, stored as 0.01 V."
  567. ::= { analogdata1 2 }
  568. inputPhaseVoltageC1 OBJECT-TYPE
  569. SYNTAX Integer32
  570. MAX-ACCESS read-only
  571. STATUS current
  572. DESCRIPTION
  573. "Input Phase Voltage C, stored as 0.01 V."
  574. ::= { analogdata1 3 }
  575. inputLineVoltageA1 OBJECT-TYPE
  576. SYNTAX Integer32
  577. MAX-ACCESS read-only
  578. STATUS current
  579. DESCRIPTION
  580. "Input Line Voltage A, stored as 0.01 V."
  581. ::= { analogdata1 4 }
  582. inputLineVoltageB1 OBJECT-TYPE
  583. SYNTAX Integer32
  584. MAX-ACCESS read-only
  585. STATUS current
  586. DESCRIPTION
  587. "Input Line Voltage B, stored as 0.01 V."
  588. ::= { analogdata1 5 }
  589. inputLineVoltageC1 OBJECT-TYPE
  590. SYNTAX Integer32
  591. MAX-ACCESS read-only
  592. STATUS current
  593. DESCRIPTION
  594. "Input Line Voltage C, stored as 0.01 V."
  595. ::= { analogdata1 6 }
  596. inputCurrentA1 OBJECT-TYPE
  597. SYNTAX Integer32
  598. MAX-ACCESS read-only
  599. STATUS current
  600. DESCRIPTION
  601. "Input Current A, stored as 0.01 A."
  602. ::= { analogdata1 7 }
  603. inputCurrentB1 OBJECT-TYPE
  604. SYNTAX Integer32
  605. MAX-ACCESS read-only
  606. STATUS current
  607. DESCRIPTION
  608. "Input Current B, stored as 0.01 A."
  609. ::= { analogdata1 8 }
  610. inputCurrentC1 OBJECT-TYPE
  611. SYNTAX Integer32
  612. MAX-ACCESS read-only
  613. STATUS current
  614. DESCRIPTION
  615. "Input Current C, stored as 0.01 A."
  616. ::= { analogdata1 9 }
  617. inputFrequency1 OBJECT-TYPE
  618. SYNTAX Integer32
  619. MAX-ACCESS read-only
  620. STATUS current
  621. DESCRIPTION
  622. "Input Frequency, stored as 0.01 Hz."
  623. ::= { analogdata1 10 }
  624. inputPowerFactorA1 OBJECT-TYPE
  625. SYNTAX Integer32
  626. MAX-ACCESS read-only
  627. STATUS current
  628. DESCRIPTION
  629. "Input Power Factor A, stored as 0.01."
  630. ::= { analogdata1 11 }
  631. inputPowerFactorB1 OBJECT-TYPE
  632. SYNTAX Integer32
  633. MAX-ACCESS read-only
  634. STATUS current
  635. DESCRIPTION
  636. "Input Power Factor B, stored as 0.01."
  637. ::= { analogdata1 12 }
  638. inputPowerFactorC1 OBJECT-TYPE
  639. SYNTAX Integer32
  640. MAX-ACCESS read-only
  641. STATUS current
  642. DESCRIPTION
  643. "Input Power Factor C, stored as 0.01."
  644. ::= { analogdata1 13 }
  645. dCBus1Voltage1 OBJECT-TYPE
  646. SYNTAX Integer32
  647. MAX-ACCESS read-only
  648. STATUS current
  649. DESCRIPTION
  650. "DCBus1 Voltage, stored as 0.01 V."
  651. ::= { analogdata1 14 }
  652. dCBus2Voltage1 OBJECT-TYPE
  653. SYNTAX Integer32
  654. MAX-ACCESS read-only
  655. STATUS current
  656. DESCRIPTION
  657. "DCBus2 Voltage, stored as 0.01 V."
  658. ::= { analogdata1 15 }
  659. outputVoltageA1 OBJECT-TYPE
  660. SYNTAX Integer32
  661. MAX-ACCESS read-only
  662. STATUS current
  663. DESCRIPTION
  664. "Output voltage A, stored as 0.01 V."
  665. ::= { analogdata1 16 }
  666. outputVoltageB1 OBJECT-TYPE
  667. SYNTAX Integer32
  668. MAX-ACCESS read-only
  669. STATUS current
  670. DESCRIPTION
  671. "Output voltage B, stored as 0.01 V."
  672. ::= { analogdata1 17 }
  673. outputVoltageC1 OBJECT-TYPE
  674. SYNTAX Integer32
  675. MAX-ACCESS read-only
  676. STATUS current
  677. DESCRIPTION
  678. "Output voltage C, stored as 0.01 V."
  679. ::= { analogdata1 18 }
  680. outputCurrentA1 OBJECT-TYPE
  681. SYNTAX Integer32
  682. MAX-ACCESS read-only
  683. STATUS current
  684. DESCRIPTION
  685. "Output current A, stored as 0.01 A."
  686. ::= { analogdata1 19 }
  687. outputCurrentB1 OBJECT-TYPE
  688. SYNTAX Integer32
  689. MAX-ACCESS read-only
  690. STATUS current
  691. DESCRIPTION
  692. "Output current B, stored as 0.01 A."
  693. ::= { analogdata1 20 }
  694. outputCurrentC1 OBJECT-TYPE
  695. SYNTAX Integer32
  696. MAX-ACCESS read-only
  697. STATUS current
  698. DESCRIPTION
  699. "Output current C, stored as 0.01 A."
  700. ::= { analogdata1 21 }
  701. outputFrequency1 OBJECT-TYPE
  702. SYNTAX Integer32
  703. MAX-ACCESS read-only
  704. STATUS current
  705. DESCRIPTION
  706. "Output Frequency, stored as 0.01 Hz."
  707. ::= { analogdata1 22 }
  708. outputPowerFactorA1 OBJECT-TYPE
  709. SYNTAX Integer32
  710. MAX-ACCESS read-only
  711. STATUS current
  712. DESCRIPTION
  713. "Output Power Factor A, stored as 0.01."
  714. ::= { analogdata1 23 }
  715. outputPowerFactorB1 OBJECT-TYPE
  716. SYNTAX Integer32
  717. MAX-ACCESS read-only
  718. STATUS current
  719. DESCRIPTION
  720. "Output Power Factor B, stored as 0.01."
  721. ::= { analogdata1 24 }
  722. outputPowerFactorC1 OBJECT-TYPE
  723. SYNTAX Integer32
  724. MAX-ACCESS read-only
  725. STATUS current
  726. DESCRIPTION
  727. "Output Power Factor C, stored as 0.01."
  728. ::= { analogdata1 25 }
  729. outputAcitvePowerA1 OBJECT-TYPE
  730. SYNTAX Integer32
  731. MAX-ACCESS read-only
  732. STATUS current
  733. DESCRIPTION
  734. "Output Acitve Power A, stored as 0.01 kW."
  735. ::= { analogdata1 26 }
  736. outputAcitvePowerB1 OBJECT-TYPE
  737. SYNTAX Integer32
  738. MAX-ACCESS read-only
  739. STATUS current
  740. DESCRIPTION
  741. "Output Acitve Power B, stored as 0.01 kW."
  742. ::= { analogdata1 27 }
  743. outputAcitvePowerC1 OBJECT-TYPE
  744. SYNTAX Integer32
  745. MAX-ACCESS read-only
  746. STATUS current
  747. DESCRIPTION
  748. "Output Acitve Power C, stored as 0.01 kW."
  749. ::= { analogdata1 28 }
  750. outputReactivePowerA1 OBJECT-TYPE
  751. SYNTAX Integer32
  752. MAX-ACCESS read-only
  753. STATUS current
  754. DESCRIPTION
  755. "Output Reactive Power A, stored as 0.01 KVAR."
  756. ::= { analogdata1 29 }
  757. outputReactivePowerB1 OBJECT-TYPE
  758. SYNTAX Integer32
  759. MAX-ACCESS read-only
  760. STATUS current
  761. DESCRIPTION
  762. "Output Reactive Power B, stored as 0.01 KVAR."
  763. ::= { analogdata1 30 }
  764. outputReactivePowerC1 OBJECT-TYPE
  765. SYNTAX Integer32
  766. MAX-ACCESS read-only
  767. STATUS current
  768. DESCRIPTION
  769. "Output Reactive Power C, stored as 0.01 KVAR."
  770. ::= { analogdata1 31 }
  771. outputAppPowerA1 OBJECT-TYPE
  772. SYNTAX Integer32
  773. MAX-ACCESS read-only
  774. STATUS current
  775. DESCRIPTION
  776. "Output App Power A, stored as 0.01 kVA."
  777. ::= { analogdata1 32 }
  778. outputAppPowerB1 OBJECT-TYPE
  779. SYNTAX Integer32
  780. MAX-ACCESS read-only
  781. STATUS current
  782. DESCRIPTION
  783. "Output App Power B, stored as 0.01 kVA."
  784. ::= { analogdata1 33 }
  785. outputAppPowerC1 OBJECT-TYPE
  786. SYNTAX Integer32
  787. MAX-ACCESS read-only
  788. STATUS current
  789. DESCRIPTION
  790. "Output App Power C, stored as 0.01 kVA."
  791. ::= { analogdata1 34 }
  792. outputLoadA1 OBJECT-TYPE
  793. SYNTAX Integer32
  794. MAX-ACCESS read-only
  795. STATUS current
  796. DESCRIPTION
  797. "Output Load A, stored as 0.01 %."
  798. ::= { analogdata1 35 }
  799. outputLoadB1 OBJECT-TYPE
  800. SYNTAX Integer32
  801. MAX-ACCESS read-only
  802. STATUS current
  803. DESCRIPTION
  804. "Output Load B, stored as 0.01 %."
  805. ::= { analogdata1 36 }
  806. outputLoadC1 OBJECT-TYPE
  807. SYNTAX Integer32
  808. MAX-ACCESS read-only
  809. STATUS current
  810. DESCRIPTION
  811. "Output Load C, stored as 0.01 %."
  812. ::= { analogdata1 37 }
  813. outputCrestFactorA1 OBJECT-TYPE
  814. SYNTAX Integer32
  815. MAX-ACCESS read-only
  816. STATUS current
  817. DESCRIPTION
  818. "Output Crest Factor A, stored as 0.01 ."
  819. ::= { analogdata1 38 }
  820. outputCrestFactorB1 OBJECT-TYPE
  821. SYNTAX Integer32
  822. MAX-ACCESS read-only
  823. STATUS current
  824. DESCRIPTION
  825. "Output Crest Factor B, stored as 0.01 ."
  826. ::= { analogdata1 39 }
  827. outputCrestFactorC1 OBJECT-TYPE
  828. SYNTAX Integer32
  829. MAX-ACCESS read-only
  830. STATUS current
  831. DESCRIPTION
  832. "Output Crest Factor C, stored as 0.01 ."
  833. ::= { analogdata1 40 }
  834. bypassVoltageA1 OBJECT-TYPE
  835. SYNTAX Integer32
  836. MAX-ACCESS read-only
  837. STATUS current
  838. DESCRIPTION
  839. "Bypass Voltage A, stored as 0.01 V."
  840. ::= { analogdata1 41 }
  841. bypassVoltageB1 OBJECT-TYPE
  842. SYNTAX Integer32
  843. MAX-ACCESS read-only
  844. STATUS current
  845. DESCRIPTION
  846. "Bypass Voltage B, stored as 0.01 V."
  847. ::= { analogdata1 42 }
  848. bypassVoltageC1 OBJECT-TYPE
  849. SYNTAX Integer32
  850. MAX-ACCESS read-only
  851. STATUS current
  852. DESCRIPTION
  853. "Bypass Voltage C, stored as 0.01 V."
  854. ::= { analogdata1 43 }
  855. bypassFrequency1 OBJECT-TYPE
  856. SYNTAX Integer32
  857. MAX-ACCESS read-only
  858. STATUS current
  859. DESCRIPTION
  860. "Bypass Frequency, stored as 0.01 Hz."
  861. ::= { analogdata1 44 }
  862. positiveBatteryVoltage1 OBJECT-TYPE
  863. SYNTAX Integer32
  864. MAX-ACCESS read-only
  865. STATUS current
  866. DESCRIPTION
  867. "positive Battery Voltage, stored as 0.01 V."
  868. ::= { analogdata1 45 }
  869. positiveBatteryCurrent1 OBJECT-TYPE
  870. SYNTAX Integer32
  871. MAX-ACCESS read-only
  872. STATUS current
  873. DESCRIPTION
  874. "positive Battery Current, stored as 0.01 A."
  875. ::= { analogdata1 46 }
  876. negativeBatteryVoltage1 OBJECT-TYPE
  877. SYNTAX Integer32
  878. MAX-ACCESS read-only
  879. STATUS current
  880. DESCRIPTION
  881. "negative Battery Voltage, stored as 0.01 V."
  882. ::= { analogdata1 47 }
  883. negativeBatteryCurrent1 OBJECT-TYPE
  884. SYNTAX Integer32
  885. MAX-ACCESS read-only
  886. STATUS current
  887. DESCRIPTION
  888. "negative Battery Current, stored as 0.01 A."
  889. ::= { analogdata1 48 }
  890. batteryAgingRate1 OBJECT-TYPE
  891. SYNTAX Integer32
  892. MAX-ACCESS read-only
  893. STATUS current
  894. DESCRIPTION
  895. "Battery Aging Rate, stored as 0.01."
  896. ::= { analogdata1 49 }
  897. batteryRemainsTime1 OBJECT-TYPE
  898. SYNTAX Integer32
  899. MAX-ACCESS read-only
  900. STATUS current
  901. DESCRIPTION
  902. "Battery Remains Time, stored as 0.01 Hour."
  903. ::= { analogdata1 50 }
  904. batteryTemperature1 OBJECT-TYPE
  905. SYNTAX Integer32
  906. MAX-ACCESS read-only
  907. STATUS current
  908. DESCRIPTION
  909. "Battery Temperature, stored as 0.01 °C."
  910. ::= { analogdata1 51 }
  911. batteryEnvironmentTemperature1 OBJECT-TYPE
  912. SYNTAX Integer32
  913. MAX-ACCESS read-only
  914. STATUS current
  915. DESCRIPTION
  916. "Battery Environment Temperature, stored as 0.01 °C."
  917. ::= { analogdata1 52 }
  918. analogdata2 OBJECT IDENTIFIER ::= { system 6 }
  919. inputPhaseVoltageA2 OBJECT-TYPE
  920. SYNTAX Integer32
  921. MAX-ACCESS read-only
  922. STATUS current
  923. DESCRIPTION
  924. "Input Phase Voltage A, stored as 0.01 V."
  925. ::= { analogdata2 1 }
  926. inputPhaseVoltageB2 OBJECT-TYPE
  927. SYNTAX Integer32
  928. MAX-ACCESS read-only
  929. STATUS current
  930. DESCRIPTION
  931. "Input Phase Voltage B, stored as 0.01 V."
  932. ::= { analogdata2 2 }
  933. inputPhaseVoltageC2 OBJECT-TYPE
  934. SYNTAX Integer32
  935. MAX-ACCESS read-only
  936. STATUS current
  937. DESCRIPTION
  938. "Input Phase Voltage C, stored as 0.01 V."
  939. ::= { analogdata2 3 }
  940. inputLineVoltageA2 OBJECT-TYPE
  941. SYNTAX Integer32
  942. MAX-ACCESS read-only
  943. STATUS current
  944. DESCRIPTION
  945. "Input Line Voltage A, stored as 0.01 V."
  946. ::= { analogdata2 4 }
  947. inputLineVoltageB2 OBJECT-TYPE
  948. SYNTAX Integer32
  949. MAX-ACCESS read-only
  950. STATUS current
  951. DESCRIPTION
  952. "Input Line Voltage B, stored as 0.01 V."
  953. ::= { analogdata2 5 }
  954. inputLineVoltageC2 OBJECT-TYPE
  955. SYNTAX Integer32
  956. MAX-ACCESS read-only
  957. STATUS current
  958. DESCRIPTION
  959. "Input Line Voltage C, stored as 0.01 V."
  960. ::= { analogdata2 6 }
  961. inputCurrentA2 OBJECT-TYPE
  962. SYNTAX Integer32
  963. MAX-ACCESS read-only
  964. STATUS current
  965. DESCRIPTION
  966. "Input Current A, stored as 0.01 A."
  967. ::= { analogdata2 7 }
  968. inputCurrentB2 OBJECT-TYPE
  969. SYNTAX Integer32
  970. MAX-ACCESS read-only
  971. STATUS current
  972. DESCRIPTION
  973. "Input Current B, stored as 0.01 A."
  974. ::= { analogdata2 8 }
  975. inputCurrentC2 OBJECT-TYPE
  976. SYNTAX Integer32
  977. MAX-ACCESS read-only
  978. STATUS current
  979. DESCRIPTION
  980. "Input Current C, stored as 0.01 A."
  981. ::= { analogdata2 9 }
  982. inputFrequency2 OBJECT-TYPE
  983. SYNTAX Integer32
  984. MAX-ACCESS read-only
  985. STATUS current
  986. DESCRIPTION
  987. "Input Frequency, stored as 0.01 Hz."
  988. ::= { analogdata2 10 }
  989. inputPowerFactorA2 OBJECT-TYPE
  990. SYNTAX Integer32
  991. MAX-ACCESS read-only
  992. STATUS current
  993. DESCRIPTION
  994. "Input Power Factor A, stored as 0.01."
  995. ::= { analogdata2 11 }
  996. inputPowerFactorB2 OBJECT-TYPE
  997. SYNTAX Integer32
  998. MAX-ACCESS read-only
  999. STATUS current
  1000. DESCRIPTION
  1001. "Input Power Factor B, stored as 0.01."
  1002. ::= { analogdata2 12 }
  1003. inputPowerFactorC2 OBJECT-TYPE
  1004. SYNTAX Integer32
  1005. MAX-ACCESS read-only
  1006. STATUS current
  1007. DESCRIPTION
  1008. "Input Power Factor C, stored as 0.01."
  1009. ::= { analogdata2 13 }
  1010. dCBus1Voltage2 OBJECT-TYPE
  1011. SYNTAX Integer32
  1012. MAX-ACCESS read-only
  1013. STATUS current
  1014. DESCRIPTION
  1015. "DCBus1 Voltage, stored as 0.01 V."
  1016. ::= { analogdata2 14 }
  1017. dCBus2Voltage2 OBJECT-TYPE
  1018. SYNTAX Integer32
  1019. MAX-ACCESS read-only
  1020. STATUS current
  1021. DESCRIPTION
  1022. "DCBus2 Voltage, stored as 0.01 V."
  1023. ::= { analogdata2 15 }
  1024. outputVoltageA2 OBJECT-TYPE
  1025. SYNTAX Integer32
  1026. MAX-ACCESS read-only
  1027. STATUS current
  1028. DESCRIPTION
  1029. "Output voltage A, stored as 0.01 V."
  1030. ::= { analogdata2 16 }
  1031. outputVoltageB2 OBJECT-TYPE
  1032. SYNTAX Integer32
  1033. MAX-ACCESS read-only
  1034. STATUS current
  1035. DESCRIPTION
  1036. "Output voltage B, stored as 0.01 V."
  1037. ::= { analogdata2 17 }
  1038. outputVoltageC2 OBJECT-TYPE
  1039. SYNTAX Integer32
  1040. MAX-ACCESS read-only
  1041. STATUS current
  1042. DESCRIPTION
  1043. "Output voltage C, stored as 0.01 V."
  1044. ::= { analogdata2 18 }
  1045. outputCurrentA2 OBJECT-TYPE
  1046. SYNTAX Integer32
  1047. MAX-ACCESS read-only
  1048. STATUS current
  1049. DESCRIPTION
  1050. "Output current A, stored as 0.01 A."
  1051. ::= { analogdata2 19 }
  1052. outputCurrentB2 OBJECT-TYPE
  1053. SYNTAX Integer32
  1054. MAX-ACCESS read-only
  1055. STATUS current
  1056. DESCRIPTION
  1057. "Output current B, stored as 0.01 A."
  1058. ::= { analogdata2 20 }
  1059. outputCurrentC2 OBJECT-TYPE
  1060. SYNTAX Integer32
  1061. MAX-ACCESS read-only
  1062. STATUS current
  1063. DESCRIPTION
  1064. "Output current C, stored as 0.01 A."
  1065. ::= { analogdata2 21 }
  1066. outputFrequency2 OBJECT-TYPE
  1067. SYNTAX Integer32
  1068. MAX-ACCESS read-only
  1069. STATUS current
  1070. DESCRIPTION
  1071. "Output Frequency, stored as 0.01 Hz."
  1072. ::= { analogdata2 22 }
  1073. outputPowerFactorA2 OBJECT-TYPE
  1074. SYNTAX Integer32
  1075. MAX-ACCESS read-only
  1076. STATUS current
  1077. DESCRIPTION
  1078. "Output Power Factor A, stored as 0.01."
  1079. ::= { analogdata2 23 }
  1080. outputPowerFactorB2 OBJECT-TYPE
  1081. SYNTAX Integer32
  1082. MAX-ACCESS read-only
  1083. STATUS current
  1084. DESCRIPTION
  1085. "Output Power Factor B, stored as 0.01."
  1086. ::= { analogdata2 24 }
  1087. outputPowerFactorC2 OBJECT-TYPE
  1088. SYNTAX Integer32
  1089. MAX-ACCESS read-only
  1090. STATUS current
  1091. DESCRIPTION
  1092. "Output Power Factor C, stored as 0.01."
  1093. ::= { analogdata2 25 }
  1094. outputAcitvePowerA2 OBJECT-TYPE
  1095. SYNTAX Integer32
  1096. MAX-ACCESS read-only
  1097. STATUS current
  1098. DESCRIPTION
  1099. "Output Acitve Power A, stored as 0.01 kW."
  1100. ::= { analogdata2 26 }
  1101. outputAcitvePowerB2 OBJECT-TYPE
  1102. SYNTAX Integer32
  1103. MAX-ACCESS read-only
  1104. STATUS current
  1105. DESCRIPTION
  1106. "Output Acitve Power B, stored as 0.01 kW."
  1107. ::= { analogdata2 27 }
  1108. outputAcitvePowerC2 OBJECT-TYPE
  1109. SYNTAX Integer32
  1110. MAX-ACCESS read-only
  1111. STATUS current
  1112. DESCRIPTION
  1113. "Output Acitve Power C, stored as 0.01 kW."
  1114. ::= { analogdata2 28 }
  1115. outputReactivePowerA2 OBJECT-TYPE
  1116. SYNTAX Integer32
  1117. MAX-ACCESS read-only
  1118. STATUS current
  1119. DESCRIPTION
  1120. "Output Reactive Power A, stored as 0.01 KVAR."
  1121. ::= { analogdata2 29 }
  1122. outputReactivePowerB2 OBJECT-TYPE
  1123. SYNTAX Integer32
  1124. MAX-ACCESS read-only
  1125. STATUS current
  1126. DESCRIPTION
  1127. "Output Reactive Power B, stored as 0.01 KVAR."
  1128. ::= { analogdata2 30 }
  1129. outputReactivePowerC2 OBJECT-TYPE
  1130. SYNTAX Integer32
  1131. MAX-ACCESS read-only
  1132. STATUS current
  1133. DESCRIPTION
  1134. "Output Reactive Power C, stored as 0.01 KVAR."
  1135. ::= { analogdata2 31 }
  1136. outputAppPowerA2 OBJECT-TYPE
  1137. SYNTAX Integer32
  1138. MAX-ACCESS read-only
  1139. STATUS current
  1140. DESCRIPTION
  1141. "Output App Power A, stored as 0.01 kVA."
  1142. ::= { analogdata2 32 }
  1143. outputAppPowerB2 OBJECT-TYPE
  1144. SYNTAX Integer32
  1145. MAX-ACCESS read-only
  1146. STATUS current
  1147. DESCRIPTION
  1148. "Output App Power B, stored as 0.01 kVA."
  1149. ::= { analogdata2 33 }
  1150. outputAppPowerC2 OBJECT-TYPE
  1151. SYNTAX Integer32
  1152. MAX-ACCESS read-only
  1153. STATUS current
  1154. DESCRIPTION
  1155. "Output App Power C, stored as 0.01 kVA."
  1156. ::= { analogdata2 34 }
  1157. outputLoadA2 OBJECT-TYPE
  1158. SYNTAX Integer32
  1159. MAX-ACCESS read-only
  1160. STATUS current
  1161. DESCRIPTION
  1162. "Output Load A, stored as 0.01 %."
  1163. ::= { analogdata2 35 }
  1164. outputLoadB2 OBJECT-TYPE
  1165. SYNTAX Integer32
  1166. MAX-ACCESS read-only
  1167. STATUS current
  1168. DESCRIPTION
  1169. "Output Load B, stored as 0.01 %."
  1170. ::= { analogdata2 36 }
  1171. outputLoadC2 OBJECT-TYPE
  1172. SYNTAX Integer32
  1173. MAX-ACCESS read-only
  1174. STATUS current
  1175. DESCRIPTION
  1176. "Output Load C, stored as 0.01 %."
  1177. ::= { analogdata2 37 }
  1178. outputCrestFactorA2 OBJECT-TYPE
  1179. SYNTAX Integer32
  1180. MAX-ACCESS read-only
  1181. STATUS current
  1182. DESCRIPTION
  1183. "Output Crest Factor A, stored as 0.01 ."
  1184. ::= { analogdata2 38 }
  1185. outputCrestFactorB2 OBJECT-TYPE
  1186. SYNTAX Integer32
  1187. MAX-ACCESS read-only
  1188. STATUS current
  1189. DESCRIPTION
  1190. "Output Crest Factor B, stored as 0.01 ."
  1191. ::= { analogdata2 39 }
  1192. outputCrestFactorC2 OBJECT-TYPE
  1193. SYNTAX Integer32
  1194. MAX-ACCESS read-only
  1195. STATUS current
  1196. DESCRIPTION
  1197. "Output Crest Factor C, stored as 0.01 ."
  1198. ::= { analogdata2 40 }
  1199. bypassVoltageA2 OBJECT-TYPE
  1200. SYNTAX Integer32
  1201. MAX-ACCESS read-only
  1202. STATUS current
  1203. DESCRIPTION
  1204. "Bypass Voltage A, stored as 0.01 V."
  1205. ::= { analogdata2 41 }
  1206. bypassVoltageB2 OBJECT-TYPE
  1207. SYNTAX Integer32
  1208. MAX-ACCESS read-only
  1209. STATUS current
  1210. DESCRIPTION
  1211. "Bypass Voltage B, stored as 0.01 V."
  1212. ::= { analogdata2 42 }
  1213. bypassVoltageC2 OBJECT-TYPE
  1214. SYNTAX Integer32
  1215. MAX-ACCESS read-only
  1216. STATUS current
  1217. DESCRIPTION
  1218. "Bypass Voltage C, stored as 0.01 V."
  1219. ::= { analogdata2 43 }
  1220. bypassFrequency2 OBJECT-TYPE
  1221. SYNTAX Integer32
  1222. MAX-ACCESS read-only
  1223. STATUS current
  1224. DESCRIPTION
  1225. "Bypass Frequency, stored as 0.01 Hz."
  1226. ::= { analogdata2 44 }
  1227. positiveBatteryVoltage2 OBJECT-TYPE
  1228. SYNTAX Integer32
  1229. MAX-ACCESS read-only
  1230. STATUS current
  1231. DESCRIPTION
  1232. "positive Battery Voltage, stored as 0.01 V."
  1233. ::= { analogdata2 45 }
  1234. positiveBatteryCurrent2 OBJECT-TYPE
  1235. SYNTAX Integer32
  1236. MAX-ACCESS read-only
  1237. STATUS current
  1238. DESCRIPTION
  1239. "positive Battery Current, stored as 0.01 A."
  1240. ::= { analogdata2 46 }
  1241. negativeBatteryVoltage2 OBJECT-TYPE
  1242. SYNTAX Integer32
  1243. MAX-ACCESS read-only
  1244. STATUS current
  1245. DESCRIPTION
  1246. "negative Battery Voltage, stored as 0.01 V."
  1247. ::= { analogdata2 47 }
  1248. negativeBatteryCurrent2 OBJECT-TYPE
  1249. SYNTAX Integer32
  1250. MAX-ACCESS read-only
  1251. STATUS current
  1252. DESCRIPTION
  1253. "negative Battery Current, stored as 0.01 A."
  1254. ::= { analogdata2 48 }
  1255. batteryAgingRate2 OBJECT-TYPE
  1256. SYNTAX Integer32
  1257. MAX-ACCESS read-only
  1258. STATUS current
  1259. DESCRIPTION
  1260. "Battery Aging Rate, stored as 0.01."
  1261. ::= { analogdata2 49 }
  1262. batteryRemainsTime2 OBJECT-TYPE
  1263. SYNTAX Integer32
  1264. MAX-ACCESS read-only
  1265. STATUS current
  1266. DESCRIPTION
  1267. "Battery Remains Time, stored as 0.01 Hour."
  1268. ::= { analogdata2 50 }
  1269. batteryTemperature2 OBJECT-TYPE
  1270. SYNTAX Integer32
  1271. MAX-ACCESS read-only
  1272. STATUS current
  1273. DESCRIPTION
  1274. "Battery Temperature, stored as 0.01 °C."
  1275. ::= { analogdata2 51 }
  1276. batteryEnvironmentTemperature2 OBJECT-TYPE
  1277. SYNTAX Integer32
  1278. MAX-ACCESS read-only
  1279. STATUS current
  1280. DESCRIPTION
  1281. "Battery Environment Temperature, stored as 0.01 °C."
  1282. ::= { analogdata2 52 }
  1283. analogdata3 OBJECT IDENTIFIER ::= { system 7 }
  1284. inputPhaseVoltageA3 OBJECT-TYPE
  1285. SYNTAX Integer32
  1286. MAX-ACCESS read-only
  1287. STATUS current
  1288. DESCRIPTION
  1289. "Input Phase Voltage A, stored as 0.01 V."
  1290. ::= { analogdata3 1 }
  1291. inputPhaseVoltageB3 OBJECT-TYPE
  1292. SYNTAX Integer32
  1293. MAX-ACCESS read-only
  1294. STATUS current
  1295. DESCRIPTION
  1296. "Input Phase Voltage B, stored as 0.01 V."
  1297. ::= { analogdata3 2 }
  1298. inputPhaseVoltageC3 OBJECT-TYPE
  1299. SYNTAX Integer32
  1300. MAX-ACCESS read-only
  1301. STATUS current
  1302. DESCRIPTION
  1303. "Input Phase Voltage C, stored as 0.01 V."
  1304. ::= { analogdata3 3 }
  1305. inputLineVoltageA3 OBJECT-TYPE
  1306. SYNTAX Integer32
  1307. MAX-ACCESS read-only
  1308. STATUS current
  1309. DESCRIPTION
  1310. "Input Line Voltage A, stored as 0.01 V."
  1311. ::= { analogdata3 4 }
  1312. inputLineVoltageB3 OBJECT-TYPE
  1313. SYNTAX Integer32
  1314. MAX-ACCESS read-only
  1315. STATUS current
  1316. DESCRIPTION
  1317. "Input Line Voltage B, stored as 0.01 V."
  1318. ::= { analogdata3 5 }
  1319. inputLineVoltageC3 OBJECT-TYPE
  1320. SYNTAX Integer32
  1321. MAX-ACCESS read-only
  1322. STATUS current
  1323. DESCRIPTION
  1324. "Input Line Voltage C, stored as 0.01 V."
  1325. ::= { analogdata3 6 }
  1326. inputCurrentA3 OBJECT-TYPE
  1327. SYNTAX Integer32
  1328. MAX-ACCESS read-only
  1329. STATUS current
  1330. DESCRIPTION
  1331. "Input Current A, stored as 0.01 A."
  1332. ::= { analogdata3 7 }
  1333. inputCurrentB3 OBJECT-TYPE
  1334. SYNTAX Integer32
  1335. MAX-ACCESS read-only
  1336. STATUS current
  1337. DESCRIPTION
  1338. "Input Current B, stored as 0.01 A."
  1339. ::= { analogdata3 8 }
  1340. inputCurrentC3 OBJECT-TYPE
  1341. SYNTAX Integer32
  1342. MAX-ACCESS read-only
  1343. STATUS current
  1344. DESCRIPTION
  1345. "Input Current C, stored as 0.01 A."
  1346. ::= { analogdata3 9 }
  1347. inputFrequency3 OBJECT-TYPE
  1348. SYNTAX Integer32
  1349. MAX-ACCESS read-only
  1350. STATUS current
  1351. DESCRIPTION
  1352. "Input Frequency, stored as 0.01 Hz."
  1353. ::= { analogdata3 10 }
  1354. inputPowerFactorA3 OBJECT-TYPE
  1355. SYNTAX Integer32
  1356. MAX-ACCESS read-only
  1357. STATUS current
  1358. DESCRIPTION
  1359. "Input Power Factor A, stored as 0.01."
  1360. ::= { analogdata3 11 }
  1361. inputPowerFactorB3 OBJECT-TYPE
  1362. SYNTAX Integer32
  1363. MAX-ACCESS read-only
  1364. STATUS current
  1365. DESCRIPTION
  1366. "Input Power Factor B, stored as 0.01."
  1367. ::= { analogdata3 12 }
  1368. inputPowerFactorC3 OBJECT-TYPE
  1369. SYNTAX Integer32
  1370. MAX-ACCESS read-only
  1371. STATUS current
  1372. DESCRIPTION
  1373. "Input Power Factor C, stored as 0.01."
  1374. ::= { analogdata3 13 }
  1375. dCBus1Voltage3 OBJECT-TYPE
  1376. SYNTAX Integer32
  1377. MAX-ACCESS read-only
  1378. STATUS current
  1379. DESCRIPTION
  1380. "DCBus1 Voltage, stored as 0.01 V."
  1381. ::= { analogdata3 14 }
  1382. dCBus2Voltage3 OBJECT-TYPE
  1383. SYNTAX Integer32
  1384. MAX-ACCESS read-only
  1385. STATUS current
  1386. DESCRIPTION
  1387. "DCBus2 Voltage, stored as 0.01 V."
  1388. ::= { analogdata3 15 }
  1389. outputVoltageA3 OBJECT-TYPE
  1390. SYNTAX Integer32
  1391. MAX-ACCESS read-only
  1392. STATUS current
  1393. DESCRIPTION
  1394. "Output voltage A, stored as 0.01 V."
  1395. ::= { analogdata3 16 }
  1396. outputVoltageB3 OBJECT-TYPE
  1397. SYNTAX Integer32
  1398. MAX-ACCESS read-only
  1399. STATUS current
  1400. DESCRIPTION
  1401. "Output voltage B, stored as 0.01 V."
  1402. ::= { analogdata3 17 }
  1403. outputVoltageC3 OBJECT-TYPE
  1404. SYNTAX Integer32
  1405. MAX-ACCESS read-only
  1406. STATUS current
  1407. DESCRIPTION
  1408. "Output voltage C, stored as 0.01 V."
  1409. ::= { analogdata3 18 }
  1410. outputCurrentA3 OBJECT-TYPE
  1411. SYNTAX Integer32
  1412. MAX-ACCESS read-only
  1413. STATUS current
  1414. DESCRIPTION
  1415. "Output current A, stored as 0.01 A."
  1416. ::= { analogdata3 19 }
  1417. outputCurrentB3 OBJECT-TYPE
  1418. SYNTAX Integer32
  1419. MAX-ACCESS read-only
  1420. STATUS current
  1421. DESCRIPTION
  1422. "Output current B, stored as 0.01 A."
  1423. ::= { analogdata3 20 }
  1424. outputCurrentC3 OBJECT-TYPE
  1425. SYNTAX Integer32
  1426. MAX-ACCESS read-only
  1427. STATUS current
  1428. DESCRIPTION
  1429. "Output current C, stored as 0.01 A."
  1430. ::= { analogdata3 21 }
  1431. outputFrequency3 OBJECT-TYPE
  1432. SYNTAX Integer32
  1433. MAX-ACCESS read-only
  1434. STATUS current
  1435. DESCRIPTION
  1436. "Output Frequency, stored as 0.01 Hz."
  1437. ::= { analogdata3 22 }
  1438. outputPowerFactorA3 OBJECT-TYPE
  1439. SYNTAX Integer32
  1440. MAX-ACCESS read-only
  1441. STATUS current
  1442. DESCRIPTION
  1443. "Output Power Factor A, stored as 0.01."
  1444. ::= { analogdata3 23 }
  1445. outputPowerFactorB3 OBJECT-TYPE
  1446. SYNTAX Integer32
  1447. MAX-ACCESS read-only
  1448. STATUS current
  1449. DESCRIPTION
  1450. "Output Power Factor B, stored as 0.01."
  1451. ::= { analogdata3 24 }
  1452. outputPowerFactorC3 OBJECT-TYPE
  1453. SYNTAX Integer32
  1454. MAX-ACCESS read-only
  1455. STATUS current
  1456. DESCRIPTION
  1457. "Output Power Factor C, stored as 0.01."
  1458. ::= { analogdata3 25 }
  1459. outputAcitvePowerA3 OBJECT-TYPE
  1460. SYNTAX Integer32
  1461. MAX-ACCESS read-only
  1462. STATUS current
  1463. DESCRIPTION
  1464. "Output Acitve Power A, stored as 0.01 kW."
  1465. ::= { analogdata3 26 }
  1466. outputAcitvePowerB3 OBJECT-TYPE
  1467. SYNTAX Integer32
  1468. MAX-ACCESS read-only
  1469. STATUS current
  1470. DESCRIPTION
  1471. "Output Acitve Power B, stored as 0.01 kW."
  1472. ::= { analogdata3 27 }
  1473. outputAcitvePowerC3 OBJECT-TYPE
  1474. SYNTAX Integer32
  1475. MAX-ACCESS read-only
  1476. STATUS current
  1477. DESCRIPTION
  1478. "Output Acitve Power C, stored as 0.01 kW."
  1479. ::= { analogdata3 28 }
  1480. outputReactivePowerA3 OBJECT-TYPE
  1481. SYNTAX Integer32
  1482. MAX-ACCESS read-only
  1483. STATUS current
  1484. DESCRIPTION
  1485. "Output Reactive Power A, stored as 0.01 KVAR."
  1486. ::= { analogdata3 29 }
  1487. outputReactivePowerB3 OBJECT-TYPE
  1488. SYNTAX Integer32
  1489. MAX-ACCESS read-only
  1490. STATUS current
  1491. DESCRIPTION
  1492. "Output Reactive Power B, stored as 0.01 KVAR."
  1493. ::= { analogdata3 30 }
  1494. outputReactivePowerC3 OBJECT-TYPE
  1495. SYNTAX Integer32
  1496. MAX-ACCESS read-only
  1497. STATUS current
  1498. DESCRIPTION
  1499. "Output Reactive Power C, stored as 0.01 KVAR."
  1500. ::= { analogdata3 31 }
  1501. outputAppPowerA3 OBJECT-TYPE
  1502. SYNTAX Integer32
  1503. MAX-ACCESS read-only
  1504. STATUS current
  1505. DESCRIPTION
  1506. "Output App Power A, stored as 0.01 kVA."
  1507. ::= { analogdata3 32 }
  1508. outputAppPowerB3 OBJECT-TYPE
  1509. SYNTAX Integer32
  1510. MAX-ACCESS read-only
  1511. STATUS current
  1512. DESCRIPTION
  1513. "Output App Power B, stored as 0.01 kVA."
  1514. ::= { analogdata3 33 }
  1515. outputAppPowerC3 OBJECT-TYPE
  1516. SYNTAX Integer32
  1517. MAX-ACCESS read-only
  1518. STATUS current
  1519. DESCRIPTION
  1520. "Output App Power C, stored as 0.01 kVA."
  1521. ::= { analogdata3 34 }
  1522. outputLoadA3 OBJECT-TYPE
  1523. SYNTAX Integer32
  1524. MAX-ACCESS read-only
  1525. STATUS current
  1526. DESCRIPTION
  1527. "Output Load A, stored as 0.01 %."
  1528. ::= { analogdata3 35 }
  1529. outputLoadB3 OBJECT-TYPE
  1530. SYNTAX Integer32
  1531. MAX-ACCESS read-only
  1532. STATUS current
  1533. DESCRIPTION
  1534. "Output Load B, stored as 0.01 %."
  1535. ::= { analogdata3 36 }
  1536. outputLoadC3 OBJECT-TYPE
  1537. SYNTAX Integer32
  1538. MAX-ACCESS read-only
  1539. STATUS current
  1540. DESCRIPTION
  1541. "Output Load C, stored as 0.01 %."
  1542. ::= { analogdata3 37 }
  1543. outputCrestFactorA3 OBJECT-TYPE
  1544. SYNTAX Integer32
  1545. MAX-ACCESS read-only
  1546. STATUS current
  1547. DESCRIPTION
  1548. "Output Crest Factor A, stored as 0.01 ."
  1549. ::= { analogdata3 38 }
  1550. outputCrestFactorB3 OBJECT-TYPE
  1551. SYNTAX Integer32
  1552. MAX-ACCESS read-only
  1553. STATUS current
  1554. DESCRIPTION
  1555. "Output Crest Factor B, stored as 0.01 ."
  1556. ::= { analogdata3 39 }
  1557. outputCrestFactorC3 OBJECT-TYPE
  1558. SYNTAX Integer32
  1559. MAX-ACCESS read-only
  1560. STATUS current
  1561. DESCRIPTION
  1562. "Output Crest Factor C, stored as 0.01 ."
  1563. ::= { analogdata3 40 }
  1564. bypassVoltageA3 OBJECT-TYPE
  1565. SYNTAX Integer32
  1566. MAX-ACCESS read-only
  1567. STATUS current
  1568. DESCRIPTION
  1569. "Bypass Voltage A, stored as 0.01 V."
  1570. ::= { analogdata3 41 }
  1571. bypassVoltageB3 OBJECT-TYPE
  1572. SYNTAX Integer32
  1573. MAX-ACCESS read-only
  1574. STATUS current
  1575. DESCRIPTION
  1576. "Bypass Voltage B, stored as 0.01 V."
  1577. ::= { analogdata3 42 }
  1578. bypassVoltageC3 OBJECT-TYPE
  1579. SYNTAX Integer32
  1580. MAX-ACCESS read-only
  1581. STATUS current
  1582. DESCRIPTION
  1583. "Bypass Voltage C, stored as 0.01 V."
  1584. ::= { analogdata3 43 }
  1585. bypassFrequency3 OBJECT-TYPE
  1586. SYNTAX Integer32
  1587. MAX-ACCESS read-only
  1588. STATUS current
  1589. DESCRIPTION
  1590. "Bypass Frequency, stored as 0.01 Hz."
  1591. ::= { analogdata3 44 }
  1592. positiveBatteryVoltage3 OBJECT-TYPE
  1593. SYNTAX Integer32
  1594. MAX-ACCESS read-only
  1595. STATUS current
  1596. DESCRIPTION
  1597. "positive Battery Voltage, stored as 0.01 V."
  1598. ::= { analogdata3 45 }
  1599. positiveBatteryCurrent3 OBJECT-TYPE
  1600. SYNTAX Integer32
  1601. MAX-ACCESS read-only
  1602. STATUS current
  1603. DESCRIPTION
  1604. "positive Battery Current, stored as 0.01 A."
  1605. ::= { analogdata3 46 }
  1606. negativeBatteryVoltage3 OBJECT-TYPE
  1607. SYNTAX Integer32
  1608. MAX-ACCESS read-only
  1609. STATUS current
  1610. DESCRIPTION
  1611. "negative Battery Voltage, stored as 0.01 V."
  1612. ::= { analogdata3 47 }
  1613. negativeBatteryCurrent3 OBJECT-TYPE
  1614. SYNTAX Integer32
  1615. MAX-ACCESS read-only
  1616. STATUS current
  1617. DESCRIPTION
  1618. "negative Battery Current, stored as 0.01 A."
  1619. ::= { analogdata3 48 }
  1620. batteryAgingRate3 OBJECT-TYPE
  1621. SYNTAX Integer32
  1622. MAX-ACCESS read-only
  1623. STATUS current
  1624. DESCRIPTION
  1625. "Battery Aging Rate, stored as 0.01."
  1626. ::= { analogdata3 49 }
  1627. batteryRemainsTime3 OBJECT-TYPE
  1628. SYNTAX Integer32
  1629. MAX-ACCESS read-only
  1630. STATUS current
  1631. DESCRIPTION
  1632. "Battery Remains Time, stored as 0.01 Hour."
  1633. ::= { analogdata3 50 }
  1634. batteryTemperature3 OBJECT-TYPE
  1635. SYNTAX Integer32
  1636. MAX-ACCESS read-only
  1637. STATUS current
  1638. DESCRIPTION
  1639. "Battery Temperature, stored as 0.01 °C."
  1640. ::= { analogdata3 51 }
  1641. batteryEnvironmentTemperature3 OBJECT-TYPE
  1642. SYNTAX Integer32
  1643. MAX-ACCESS read-only
  1644. STATUS current
  1645. DESCRIPTION
  1646. "Battery Environment Temperature, stored as 0.01 °C."
  1647. ::= { analogdata3 52 }
  1648. analogdata4 OBJECT IDENTIFIER ::= { system 8 }
  1649. inputPhaseVoltageA4 OBJECT-TYPE
  1650. SYNTAX Integer32
  1651. MAX-ACCESS read-only
  1652. STATUS current
  1653. DESCRIPTION
  1654. "Input Phase Voltage A, stored as 0.01 V."
  1655. ::= { analogdata4 1 }
  1656. inputPhaseVoltageB4 OBJECT-TYPE
  1657. SYNTAX Integer32
  1658. MAX-ACCESS read-only
  1659. STATUS current
  1660. DESCRIPTION
  1661. "Input Phase Voltage B, stored as 0.01 V."
  1662. ::= { analogdata4 2 }
  1663. inputPhaseVoltageC4 OBJECT-TYPE
  1664. SYNTAX Integer32
  1665. MAX-ACCESS read-only
  1666. STATUS current
  1667. DESCRIPTION
  1668. "Input Phase Voltage C, stored as 0.01 V."
  1669. ::= { analogdata4 3 }
  1670. inputLineVoltageA4 OBJECT-TYPE
  1671. SYNTAX Integer32
  1672. MAX-ACCESS read-only
  1673. STATUS current
  1674. DESCRIPTION
  1675. "Input Line Voltage A, stored as 0.01 V."
  1676. ::= { analogdata4 4 }
  1677. inputLineVoltageB4 OBJECT-TYPE
  1678. SYNTAX Integer32
  1679. MAX-ACCESS read-only
  1680. STATUS current
  1681. DESCRIPTION
  1682. "Input Line Voltage B, stored as 0.01 V."
  1683. ::= { analogdata4 5 }
  1684. inputLineVoltageC4 OBJECT-TYPE
  1685. SYNTAX Integer32
  1686. MAX-ACCESS read-only
  1687. STATUS current
  1688. DESCRIPTION
  1689. "Input Line Voltage C, stored as 0.01 V."
  1690. ::= { analogdata4 6 }
  1691. inputCurrentA4 OBJECT-TYPE
  1692. SYNTAX Integer32
  1693. MAX-ACCESS read-only
  1694. STATUS current
  1695. DESCRIPTION
  1696. "Input Current A, stored as 0.01 A."
  1697. ::= { analogdata4 7 }
  1698. inputCurrentB4 OBJECT-TYPE
  1699. SYNTAX Integer32
  1700. MAX-ACCESS read-only
  1701. STATUS current
  1702. DESCRIPTION
  1703. "Input Current B, stored as 0.01 A."
  1704. ::= { analogdata4 8 }
  1705. inputCurrentC4 OBJECT-TYPE
  1706. SYNTAX Integer32
  1707. MAX-ACCESS read-only
  1708. STATUS current
  1709. DESCRIPTION
  1710. "Input Current C, stored as 0.01 A."
  1711. ::= { analogdata4 9 }
  1712. inputFrequency4 OBJECT-TYPE
  1713. SYNTAX Integer32
  1714. MAX-ACCESS read-only
  1715. STATUS current
  1716. DESCRIPTION
  1717. "Input Frequency, stored as 0.01 Hz."
  1718. ::= { analogdata4 10 }
  1719. inputPowerFactorA4 OBJECT-TYPE
  1720. SYNTAX Integer32
  1721. MAX-ACCESS read-only
  1722. STATUS current
  1723. DESCRIPTION
  1724. "Input Power Factor A, stored as 0.01."
  1725. ::= { analogdata4 11 }
  1726. inputPowerFactorB4 OBJECT-TYPE
  1727. SYNTAX Integer32
  1728. MAX-ACCESS read-only
  1729. STATUS current
  1730. DESCRIPTION
  1731. "Input Power Factor B, stored as 0.01."
  1732. ::= { analogdata4 12 }
  1733. inputPowerFactorC4 OBJECT-TYPE
  1734. SYNTAX Integer32
  1735. MAX-ACCESS read-only
  1736. STATUS current
  1737. DESCRIPTION
  1738. "Input Power Factor C, stored as 0.01."
  1739. ::= { analogdata4 13 }
  1740. dCBus1Voltage4 OBJECT-TYPE
  1741. SYNTAX Integer32
  1742. MAX-ACCESS read-only
  1743. STATUS current
  1744. DESCRIPTION
  1745. "DCBus1 Voltage, stored as 0.01 V."
  1746. ::= { analogdata4 14 }
  1747. dCBus2Voltage4 OBJECT-TYPE
  1748. SYNTAX Integer32
  1749. MAX-ACCESS read-only
  1750. STATUS current
  1751. DESCRIPTION
  1752. "DCBus2 Voltage, stored as 0.01 V."
  1753. ::= { analogdata4 15 }
  1754. outputVoltageA4 OBJECT-TYPE
  1755. SYNTAX Integer32
  1756. MAX-ACCESS read-only
  1757. STATUS current
  1758. DESCRIPTION
  1759. "Output voltage A, stored as 0.01 V."
  1760. ::= { analogdata4 16 }
  1761. outputVoltageB4 OBJECT-TYPE
  1762. SYNTAX Integer32
  1763. MAX-ACCESS read-only
  1764. STATUS current
  1765. DESCRIPTION
  1766. "Output voltage B, stored as 0.01 V."
  1767. ::= { analogdata4 17 }
  1768. outputVoltageC4 OBJECT-TYPE
  1769. SYNTAX Integer32
  1770. MAX-ACCESS read-only
  1771. STATUS current
  1772. DESCRIPTION
  1773. "Output voltage C, stored as 0.01 V."
  1774. ::= { analogdata4 18 }
  1775. outputCurrentA4 OBJECT-TYPE
  1776. SYNTAX Integer32
  1777. MAX-ACCESS read-only
  1778. STATUS current
  1779. DESCRIPTION
  1780. "Output current A, stored as 0.01 A."
  1781. ::= { analogdata4 19 }
  1782. outputCurrentB4 OBJECT-TYPE
  1783. SYNTAX Integer32
  1784. MAX-ACCESS read-only
  1785. STATUS current
  1786. DESCRIPTION
  1787. "Output current B, stored as 0.01 A."
  1788. ::= { analogdata4 20 }
  1789. outputCurrentC4 OBJECT-TYPE
  1790. SYNTAX Integer32
  1791. MAX-ACCESS read-only
  1792. STATUS current
  1793. DESCRIPTION
  1794. "Output current C, stored as 0.01 A."
  1795. ::= { analogdata4 21 }
  1796. outputFrequency4 OBJECT-TYPE
  1797. SYNTAX Integer32
  1798. MAX-ACCESS read-only
  1799. STATUS current
  1800. DESCRIPTION
  1801. "Output Frequency, stored as 0.01 Hz."
  1802. ::= { analogdata4 22 }
  1803. outputPowerFactorA4 OBJECT-TYPE
  1804. SYNTAX Integer32
  1805. MAX-ACCESS read-only
  1806. STATUS current
  1807. DESCRIPTION
  1808. "Output Power Factor A, stored as 0.01."
  1809. ::= { analogdata4 23 }
  1810. outputPowerFactorB4 OBJECT-TYPE
  1811. SYNTAX Integer32
  1812. MAX-ACCESS read-only
  1813. STATUS current
  1814. DESCRIPTION
  1815. "Output Power Factor B, stored as 0.01."
  1816. ::= { analogdata4 24 }
  1817. outputPowerFactorC4 OBJECT-TYPE
  1818. SYNTAX Integer32
  1819. MAX-ACCESS read-only
  1820. STATUS current
  1821. DESCRIPTION
  1822. "Output Power Factor C, stored as 0.01."
  1823. ::= { analogdata4 25 }
  1824. outputAcitvePowerA4 OBJECT-TYPE
  1825. SYNTAX Integer32
  1826. MAX-ACCESS read-only
  1827. STATUS current
  1828. DESCRIPTION
  1829. "Output Acitve Power A, stored as 0.01 kW."
  1830. ::= { analogdata4 26 }
  1831. outputAcitvePowerB4 OBJECT-TYPE
  1832. SYNTAX Integer32
  1833. MAX-ACCESS read-only
  1834. STATUS current
  1835. DESCRIPTION
  1836. "Output Acitve Power B, stored as 0.01 kW."
  1837. ::= { analogdata4 27 }
  1838. outputAcitvePowerC4 OBJECT-TYPE
  1839. SYNTAX Integer32
  1840. MAX-ACCESS read-only
  1841. STATUS current
  1842. DESCRIPTION
  1843. "Output Acitve Power C, stored as 0.01 kW."
  1844. ::= { analogdata4 28 }
  1845. outputReactivePowerA4 OBJECT-TYPE
  1846. SYNTAX Integer32
  1847. MAX-ACCESS read-only
  1848. STATUS current
  1849. DESCRIPTION
  1850. "Output Reactive Power A, stored as 0.01 KVAR."
  1851. ::= { analogdata4 29 }
  1852. outputReactivePowerB4 OBJECT-TYPE
  1853. SYNTAX Integer32
  1854. MAX-ACCESS read-only
  1855. STATUS current
  1856. DESCRIPTION
  1857. "Output Reactive Power B, stored as 0.01 KVAR."
  1858. ::= { analogdata4 30 }
  1859. outputReactivePowerC4 OBJECT-TYPE
  1860. SYNTAX Integer32
  1861. MAX-ACCESS read-only
  1862. STATUS current
  1863. DESCRIPTION
  1864. "Output Reactive Power C, stored as 0.01 KVAR."
  1865. ::= { analogdata4 31 }
  1866. outputAppPowerA4 OBJECT-TYPE
  1867. SYNTAX Integer32
  1868. MAX-ACCESS read-only
  1869. STATUS current
  1870. DESCRIPTION
  1871. "Output App Power A, stored as 0.01 kVA."
  1872. ::= { analogdata4 32 }
  1873. outputAppPowerB4 OBJECT-TYPE
  1874. SYNTAX Integer32
  1875. MAX-ACCESS read-only
  1876. STATUS current
  1877. DESCRIPTION
  1878. "Output App Power B, stored as 0.01 kVA."
  1879. ::= { analogdata4 33 }
  1880. outputAppPowerC4 OBJECT-TYPE
  1881. SYNTAX Integer32
  1882. MAX-ACCESS read-only
  1883. STATUS current
  1884. DESCRIPTION
  1885. "Output App Power C, stored as 0.01 kVA."
  1886. ::= { analogdata4 34 }
  1887. outputLoadA4 OBJECT-TYPE
  1888. SYNTAX Integer32
  1889. MAX-ACCESS read-only
  1890. STATUS current
  1891. DESCRIPTION
  1892. "Output Load A, stored as 0.01 %."
  1893. ::= { analogdata4 35 }
  1894. outputLoadB4 OBJECT-TYPE
  1895. SYNTAX Integer32
  1896. MAX-ACCESS read-only
  1897. STATUS current
  1898. DESCRIPTION
  1899. "Output Load B, stored as 0.01 %."
  1900. ::= { analogdata4 36 }
  1901. outputLoadC4 OBJECT-TYPE
  1902. SYNTAX Integer32
  1903. MAX-ACCESS read-only
  1904. STATUS current
  1905. DESCRIPTION
  1906. "Output Load C, stored as 0.01 %."
  1907. ::= { analogdata4 37 }
  1908. outputCrestFactorA4 OBJECT-TYPE
  1909. SYNTAX Integer32
  1910. MAX-ACCESS read-only
  1911. STATUS current
  1912. DESCRIPTION
  1913. "Output Crest Factor A, stored as 0.01 ."
  1914. ::= { analogdata4 38 }
  1915. outputCrestFactorB4 OBJECT-TYPE
  1916. SYNTAX Integer32
  1917. MAX-ACCESS read-only
  1918. STATUS current
  1919. DESCRIPTION
  1920. "Output Crest Factor B, stored as 0.01 ."
  1921. ::= { analogdata4 39 }
  1922. outputCrestFactorC4 OBJECT-TYPE
  1923. SYNTAX Integer32
  1924. MAX-ACCESS read-only
  1925. STATUS current
  1926. DESCRIPTION
  1927. "Output Crest Factor C, stored as 0.01 ."
  1928. ::= { analogdata4 40 }
  1929. bypassVoltageA4 OBJECT-TYPE
  1930. SYNTAX Integer32
  1931. MAX-ACCESS read-only
  1932. STATUS current
  1933. DESCRIPTION
  1934. "Bypass Voltage A, stored as 0.01 V."
  1935. ::= { analogdata4 41 }
  1936. bypassVoltageB4 OBJECT-TYPE
  1937. SYNTAX Integer32
  1938. MAX-ACCESS read-only
  1939. STATUS current
  1940. DESCRIPTION
  1941. "Bypass Voltage B, stored as 0.01 V."
  1942. ::= { analogdata4 42 }
  1943. bypassVoltageC4 OBJECT-TYPE
  1944. SYNTAX Integer32
  1945. MAX-ACCESS read-only
  1946. STATUS current
  1947. DESCRIPTION
  1948. "Bypass Voltage C, stored as 0.01 V."
  1949. ::= { analogdata4 43 }
  1950. bypassFrequency4 OBJECT-TYPE
  1951. SYNTAX Integer32
  1952. MAX-ACCESS read-only
  1953. STATUS current
  1954. DESCRIPTION
  1955. "Bypass Frequency, stored as 0.01 Hz."
  1956. ::= { analogdata4 44 }
  1957. positiveBatteryVoltage4 OBJECT-TYPE
  1958. SYNTAX Integer32
  1959. MAX-ACCESS read-only
  1960. STATUS current
  1961. DESCRIPTION
  1962. "positive Battery Voltage, stored as 0.01 V."
  1963. ::= { analogdata4 45 }
  1964. positiveBatteryCurrent4 OBJECT-TYPE
  1965. SYNTAX Integer32
  1966. MAX-ACCESS read-only
  1967. STATUS current
  1968. DESCRIPTION
  1969. "positive Battery Current, stored as 0.01 A."
  1970. ::= { analogdata4 46 }
  1971. negativeBatteryVoltage4 OBJECT-TYPE
  1972. SYNTAX Integer32
  1973. MAX-ACCESS read-only
  1974. STATUS current
  1975. DESCRIPTION
  1976. "negative Battery Voltage, stored as 0.01 V."
  1977. ::= { analogdata4 47 }
  1978. negativeBatteryCurrent4 OBJECT-TYPE
  1979. SYNTAX Integer32
  1980. MAX-ACCESS read-only
  1981. STATUS current
  1982. DESCRIPTION
  1983. "negative Battery Current, stored as 0.01 A."
  1984. ::= { analogdata4 48 }
  1985. batteryAgingRate4 OBJECT-TYPE
  1986. SYNTAX Integer32
  1987. MAX-ACCESS read-only
  1988. STATUS current
  1989. DESCRIPTION
  1990. "Battery Aging Rate, stored as 0.01."
  1991. ::= { analogdata4 49 }
  1992. batteryRemainsTime4 OBJECT-TYPE
  1993. SYNTAX Integer32
  1994. MAX-ACCESS read-only
  1995. STATUS current
  1996. DESCRIPTION
  1997. "Battery Remains Time, stored as 0.01 Hour."
  1998. ::= { analogdata4 50 }
  1999. batteryTemperature4 OBJECT-TYPE
  2000. SYNTAX Integer32
  2001. MAX-ACCESS read-only
  2002. STATUS current
  2003. DESCRIPTION
  2004. "Battery Temperature, stored as 0.01 °C."
  2005. ::= { analogdata4 51 }
  2006. batteryEnvironmentTemperature4 OBJECT-TYPE
  2007. SYNTAX Integer32
  2008. MAX-ACCESS read-only
  2009. STATUS current
  2010. DESCRIPTION
  2011. "Battery Environment Temperature, stored as 0.01 °C."
  2012. ::= { analogdata4 52 }
  2013. analogdata5 OBJECT IDENTIFIER ::= { system 9 }
  2014. inputPhaseVoltageA5 OBJECT-TYPE
  2015. SYNTAX Integer32
  2016. MAX-ACCESS read-only
  2017. STATUS current
  2018. DESCRIPTION
  2019. "Input Phase Voltage A, stored as 0.01 V."
  2020. ::= { analogdata5 1 }
  2021. inputPhaseVoltageB5 OBJECT-TYPE
  2022. SYNTAX Integer32
  2023. MAX-ACCESS read-only
  2024. STATUS current
  2025. DESCRIPTION
  2026. "Input Phase Voltage B, stored as 0.01 V."
  2027. ::= { analogdata5 2 }
  2028. inputPhaseVoltageC5 OBJECT-TYPE
  2029. SYNTAX Integer32
  2030. MAX-ACCESS read-only
  2031. STATUS current
  2032. DESCRIPTION
  2033. "Input Phase Voltage C, stored as 0.01 V."
  2034. ::= { analogdata5 3 }
  2035. inputLineVoltageA5 OBJECT-TYPE
  2036. SYNTAX Integer32
  2037. MAX-ACCESS read-only
  2038. STATUS current
  2039. DESCRIPTION
  2040. "Input Line Voltage A, stored as 0.01 V."
  2041. ::= { analogdata5 4 }
  2042. inputLineVoltageB5 OBJECT-TYPE
  2043. SYNTAX Integer32
  2044. MAX-ACCESS read-only
  2045. STATUS current
  2046. DESCRIPTION
  2047. "Input Line Voltage B, stored as 0.01 V."
  2048. ::= { analogdata5 5 }
  2049. inputLineVoltageC5 OBJECT-TYPE
  2050. SYNTAX Integer32
  2051. MAX-ACCESS read-only
  2052. STATUS current
  2053. DESCRIPTION
  2054. "Input Line Voltage C, stored as 0.01 V."
  2055. ::= { analogdata5 6 }
  2056. inputCurrentA5 OBJECT-TYPE
  2057. SYNTAX Integer32
  2058. MAX-ACCESS read-only
  2059. STATUS current
  2060. DESCRIPTION
  2061. "Input Current A, stored as 0.01 A."
  2062. ::= { analogdata5 7 }
  2063. inputCurrentB5 OBJECT-TYPE
  2064. SYNTAX Integer32
  2065. MAX-ACCESS read-only
  2066. STATUS current
  2067. DESCRIPTION
  2068. "Input Current B, stored as 0.01 A."
  2069. ::= { analogdata5 8 }
  2070. inputCurrentC5 OBJECT-TYPE
  2071. SYNTAX Integer32
  2072. MAX-ACCESS read-only
  2073. STATUS current
  2074. DESCRIPTION
  2075. "Input Current C, stored as 0.01 A."
  2076. ::= { analogdata5 9 }
  2077. inputFrequency5 OBJECT-TYPE
  2078. SYNTAX Integer32
  2079. MAX-ACCESS read-only
  2080. STATUS current
  2081. DESCRIPTION
  2082. "Input Frequency, stored as 0.01 Hz."
  2083. ::= { analogdata5 10 }
  2084. inputPowerFactorA5 OBJECT-TYPE
  2085. SYNTAX Integer32
  2086. MAX-ACCESS read-only
  2087. STATUS current
  2088. DESCRIPTION
  2089. "Input Power Factor A, stored as 0.01."
  2090. ::= { analogdata5 11 }
  2091. inputPowerFactorB5 OBJECT-TYPE
  2092. SYNTAX Integer32
  2093. MAX-ACCESS read-only
  2094. STATUS current
  2095. DESCRIPTION
  2096. "Input Power Factor B, stored as 0.01."
  2097. ::= { analogdata5 12 }
  2098. inputPowerFactorC5 OBJECT-TYPE
  2099. SYNTAX Integer32
  2100. MAX-ACCESS read-only
  2101. STATUS current
  2102. DESCRIPTION
  2103. "Input Power Factor C, stored as 0.01."
  2104. ::= { analogdata5 13 }
  2105. dCBus1Voltage5 OBJECT-TYPE
  2106. SYNTAX Integer32
  2107. MAX-ACCESS read-only
  2108. STATUS current
  2109. DESCRIPTION
  2110. "DCBus1 Voltage, stored as 0.01 V."
  2111. ::= { analogdata5 14 }
  2112. dCBus2Voltage5 OBJECT-TYPE
  2113. SYNTAX Integer32
  2114. MAX-ACCESS read-only
  2115. STATUS current
  2116. DESCRIPTION
  2117. "DCBus2 Voltage, stored as 0.01 V."
  2118. ::= { analogdata5 15 }
  2119. outputVoltageA5 OBJECT-TYPE
  2120. SYNTAX Integer32
  2121. MAX-ACCESS read-only
  2122. STATUS current
  2123. DESCRIPTION
  2124. "Output voltage A, stored as 0.01 V."
  2125. ::= { analogdata5 16 }
  2126. outputVoltageB5 OBJECT-TYPE
  2127. SYNTAX Integer32
  2128. MAX-ACCESS read-only
  2129. STATUS current
  2130. DESCRIPTION
  2131. "Output voltage B, stored as 0.01 V."
  2132. ::= { analogdata5 17 }
  2133. outputVoltageC5 OBJECT-TYPE
  2134. SYNTAX Integer32
  2135. MAX-ACCESS read-only
  2136. STATUS current
  2137. DESCRIPTION
  2138. "Output voltage C, stored as 0.01 V."
  2139. ::= { analogdata5 18 }
  2140. outputCurrentA5 OBJECT-TYPE
  2141. SYNTAX Integer32
  2142. MAX-ACCESS read-only
  2143. STATUS current
  2144. DESCRIPTION
  2145. "Output current A, stored as 0.01 A."
  2146. ::= { analogdata5 19 }
  2147. outputCurrentB5 OBJECT-TYPE
  2148. SYNTAX Integer32
  2149. MAX-ACCESS read-only
  2150. STATUS current
  2151. DESCRIPTION
  2152. "Output current B, stored as 0.01 A."
  2153. ::= { analogdata5 20 }
  2154. outputCurrentC5 OBJECT-TYPE
  2155. SYNTAX Integer32
  2156. MAX-ACCESS read-only
  2157. STATUS current
  2158. DESCRIPTION
  2159. "Output current C, stored as 0.01 A."
  2160. ::= { analogdata5 21 }
  2161. outputFrequency5 OBJECT-TYPE
  2162. SYNTAX Integer32
  2163. MAX-ACCESS read-only
  2164. STATUS current
  2165. DESCRIPTION
  2166. "Output Frequency, stored as 0.01 Hz."
  2167. ::= { analogdata5 22 }
  2168. outputPowerFactorA5 OBJECT-TYPE
  2169. SYNTAX Integer32
  2170. MAX-ACCESS read-only
  2171. STATUS current
  2172. DESCRIPTION
  2173. "Output Power Factor A, stored as 0.01."
  2174. ::= { analogdata5 23 }
  2175. outputPowerFactorB5 OBJECT-TYPE
  2176. SYNTAX Integer32
  2177. MAX-ACCESS read-only
  2178. STATUS current
  2179. DESCRIPTION
  2180. "Output Power Factor B, stored as 0.01."
  2181. ::= { analogdata5 24 }
  2182. outputPowerFactorC5 OBJECT-TYPE
  2183. SYNTAX Integer32
  2184. MAX-ACCESS read-only
  2185. STATUS current
  2186. DESCRIPTION
  2187. "Output Power Factor C, stored as 0.01."
  2188. ::= { analogdata5 25 }
  2189. outputAcitvePowerA5 OBJECT-TYPE
  2190. SYNTAX Integer32
  2191. MAX-ACCESS read-only
  2192. STATUS current
  2193. DESCRIPTION
  2194. "Output Acitve Power A, stored as 0.01 kW."
  2195. ::= { analogdata5 26 }
  2196. outputAcitvePowerB5 OBJECT-TYPE
  2197. SYNTAX Integer32
  2198. MAX-ACCESS read-only
  2199. STATUS current
  2200. DESCRIPTION
  2201. "Output Acitve Power B, stored as 0.01 kW."
  2202. ::= { analogdata5 27 }
  2203. outputAcitvePowerC5 OBJECT-TYPE
  2204. SYNTAX Integer32
  2205. MAX-ACCESS read-only
  2206. STATUS current
  2207. DESCRIPTION
  2208. "Output Acitve Power C, stored as 0.01 kW."
  2209. ::= { analogdata5 28 }
  2210. outputReactivePowerA5 OBJECT-TYPE
  2211. SYNTAX Integer32
  2212. MAX-ACCESS read-only
  2213. STATUS current
  2214. DESCRIPTION
  2215. "Output Reactive Power A, stored as 0.01 KVAR."
  2216. ::= { analogdata5 29 }
  2217. outputReactivePowerB5 OBJECT-TYPE
  2218. SYNTAX Integer32
  2219. MAX-ACCESS read-only
  2220. STATUS current
  2221. DESCRIPTION
  2222. "Output Reactive Power B, stored as 0.01 KVAR."
  2223. ::= { analogdata5 30 }
  2224. outputReactivePowerC5 OBJECT-TYPE
  2225. SYNTAX Integer32
  2226. MAX-ACCESS read-only
  2227. STATUS current
  2228. DESCRIPTION
  2229. "Output Reactive Power C, stored as 0.01 KVAR."
  2230. ::= { analogdata5 31 }
  2231. outputAppPowerA5 OBJECT-TYPE
  2232. SYNTAX Integer32
  2233. MAX-ACCESS read-only
  2234. STATUS current
  2235. DESCRIPTION
  2236. "Output App Power A, stored as 0.01 kVA."
  2237. ::= { analogdata5 32 }
  2238. outputAppPowerB5 OBJECT-TYPE
  2239. SYNTAX Integer32
  2240. MAX-ACCESS read-only
  2241. STATUS current
  2242. DESCRIPTION
  2243. "Output App Power B, stored as 0.01 kVA."
  2244. ::= { analogdata5 33 }
  2245. outputAppPowerC5 OBJECT-TYPE
  2246. SYNTAX Integer32
  2247. MAX-ACCESS read-only
  2248. STATUS current
  2249. DESCRIPTION
  2250. "Output App Power C, stored as 0.01 kVA."
  2251. ::= { analogdata5 34 }
  2252. outputLoadA5 OBJECT-TYPE
  2253. SYNTAX Integer32
  2254. MAX-ACCESS read-only
  2255. STATUS current
  2256. DESCRIPTION
  2257. "Output Load A, stored as 0.01 %."
  2258. ::= { analogdata5 35 }
  2259. outputLoadB5 OBJECT-TYPE
  2260. SYNTAX Integer32
  2261. MAX-ACCESS read-only
  2262. STATUS current
  2263. DESCRIPTION
  2264. "Output Load B, stored as 0.01 %."
  2265. ::= { analogdata5 36 }
  2266. outputLoadC5 OBJECT-TYPE
  2267. SYNTAX Integer32
  2268. MAX-ACCESS read-only
  2269. STATUS current
  2270. DESCRIPTION
  2271. "Output Load C, stored as 0.01 %."
  2272. ::= { analogdata5 37 }
  2273. outputCrestFactorA5 OBJECT-TYPE
  2274. SYNTAX Integer32
  2275. MAX-ACCESS read-only
  2276. STATUS current
  2277. DESCRIPTION
  2278. "Output Crest Factor A, stored as 0.01 ."
  2279. ::= { analogdata5 38 }
  2280. outputCrestFactorB5 OBJECT-TYPE
  2281. SYNTAX Integer32
  2282. MAX-ACCESS read-only
  2283. STATUS current
  2284. DESCRIPTION
  2285. "Output Crest Factor B, stored as 0.01 ."
  2286. ::= { analogdata5 39 }
  2287. outputCrestFactorC5 OBJECT-TYPE
  2288. SYNTAX Integer32
  2289. MAX-ACCESS read-only
  2290. STATUS current
  2291. DESCRIPTION
  2292. "Output Crest Factor C, stored as 0.01 ."
  2293. ::= { analogdata5 40 }
  2294. bypassVoltageA5 OBJECT-TYPE
  2295. SYNTAX Integer32
  2296. MAX-ACCESS read-only
  2297. STATUS current
  2298. DESCRIPTION
  2299. "Bypass Voltage A, stored as 0.01 V."
  2300. ::= { analogdata5 41 }
  2301. bypassVoltageB5 OBJECT-TYPE
  2302. SYNTAX Integer32
  2303. MAX-ACCESS read-only
  2304. STATUS current
  2305. DESCRIPTION
  2306. "Bypass Voltage B, stored as 0.01 V."
  2307. ::= { analogdata5 42 }
  2308. bypassVoltageC5 OBJECT-TYPE
  2309. SYNTAX Integer32
  2310. MAX-ACCESS read-only
  2311. STATUS current
  2312. DESCRIPTION
  2313. "Bypass Voltage C, stored as 0.01 V."
  2314. ::= { analogdata5 43 }
  2315. bypassFrequency5 OBJECT-TYPE
  2316. SYNTAX Integer32
  2317. MAX-ACCESS read-only
  2318. STATUS current
  2319. DESCRIPTION
  2320. "Bypass Frequency, stored as 0.01 Hz."
  2321. ::= { analogdata5 44 }
  2322. positiveBatteryVoltage5 OBJECT-TYPE
  2323. SYNTAX Integer32
  2324. MAX-ACCESS read-only
  2325. STATUS current
  2326. DESCRIPTION
  2327. "positive Battery Voltage, stored as 0.01 V."
  2328. ::= { analogdata5 45 }
  2329. positiveBatteryCurrent5 OBJECT-TYPE
  2330. SYNTAX Integer32
  2331. MAX-ACCESS read-only
  2332. STATUS current
  2333. DESCRIPTION
  2334. "positive Battery Current, stored as 0.01 A."
  2335. ::= { analogdata5 46 }
  2336. negativeBatteryVoltage5 OBJECT-TYPE
  2337. SYNTAX Integer32
  2338. MAX-ACCESS read-only
  2339. STATUS current
  2340. DESCRIPTION
  2341. "negative Battery Voltage, stored as 0.01 V."
  2342. ::= { analogdata5 47 }
  2343. negativeBatteryCurrent5 OBJECT-TYPE
  2344. SYNTAX Integer32
  2345. MAX-ACCESS read-only
  2346. STATUS current
  2347. DESCRIPTION
  2348. "negative Battery Current, stored as 0.01 A."
  2349. ::= { analogdata5 48 }
  2350. batteryAgingRate5 OBJECT-TYPE
  2351. SYNTAX Integer32
  2352. MAX-ACCESS read-only
  2353. STATUS current
  2354. DESCRIPTION
  2355. "Battery Aging Rate, stored as 0.01."
  2356. ::= { analogdata5 49 }
  2357. batteryRemainsTime5 OBJECT-TYPE
  2358. SYNTAX Integer32
  2359. MAX-ACCESS read-only
  2360. STATUS current
  2361. DESCRIPTION
  2362. "Battery Remains Time, stored as 0.01 Hour."
  2363. ::= { analogdata5 50 }
  2364. batteryTemperature5 OBJECT-TYPE
  2365. SYNTAX Integer32
  2366. MAX-ACCESS read-only
  2367. STATUS current
  2368. DESCRIPTION
  2369. "Battery Temperature, stored as 0.01 °C."
  2370. ::= { analogdata5 51 }
  2371. batteryEnvironmentTemperature5 OBJECT-TYPE
  2372. SYNTAX Integer32
  2373. MAX-ACCESS read-only
  2374. STATUS current
  2375. DESCRIPTION
  2376. "Battery Environment Temperature, stored as 0.01 °C."
  2377. ::= { analogdata5 52 }
  2378. analogdata6 OBJECT IDENTIFIER ::= { system 10 }
  2379. inputPhaseVoltageA6 OBJECT-TYPE
  2380. SYNTAX Integer32
  2381. MAX-ACCESS read-only
  2382. STATUS current
  2383. DESCRIPTION
  2384. "Input Phase Voltage A, stored as 0.01 V."
  2385. ::= { analogdata6 1 }
  2386. inputPhaseVoltageB6 OBJECT-TYPE
  2387. SYNTAX Integer32
  2388. MAX-ACCESS read-only
  2389. STATUS current
  2390. DESCRIPTION
  2391. "Input Phase Voltage B, stored as 0.01 V."
  2392. ::= { analogdata6 2 }
  2393. inputPhaseVoltageC6 OBJECT-TYPE
  2394. SYNTAX Integer32
  2395. MAX-ACCESS read-only
  2396. STATUS current
  2397. DESCRIPTION
  2398. "Input Phase Voltage C, stored as 0.01 V."
  2399. ::= { analogdata6 3 }
  2400. inputLineVoltageA6 OBJECT-TYPE
  2401. SYNTAX Integer32
  2402. MAX-ACCESS read-only
  2403. STATUS current
  2404. DESCRIPTION
  2405. "Input Line Voltage A, stored as 0.01 V."
  2406. ::= { analogdata6 4 }
  2407. inputLineVoltageB6 OBJECT-TYPE
  2408. SYNTAX Integer32
  2409. MAX-ACCESS read-only
  2410. STATUS current
  2411. DESCRIPTION
  2412. "Input Line Voltage B, stored as 0.01 V."
  2413. ::= { analogdata6 5 }
  2414. inputLineVoltageC6 OBJECT-TYPE
  2415. SYNTAX Integer32
  2416. MAX-ACCESS read-only
  2417. STATUS current
  2418. DESCRIPTION
  2419. "Input Line Voltage C, stored as 0.01 V."
  2420. ::= { analogdata6 6 }
  2421. inputCurrentA6 OBJECT-TYPE
  2422. SYNTAX Integer32
  2423. MAX-ACCESS read-only
  2424. STATUS current
  2425. DESCRIPTION
  2426. "Input Current A, stored as 0.01 A."
  2427. ::= { analogdata6 7 }
  2428. inputCurrentB6 OBJECT-TYPE
  2429. SYNTAX Integer32
  2430. MAX-ACCESS read-only
  2431. STATUS current
  2432. DESCRIPTION
  2433. "Input Current B, stored as 0.01 A."
  2434. ::= { analogdata6 8 }
  2435. inputCurrentC6 OBJECT-TYPE
  2436. SYNTAX Integer32
  2437. MAX-ACCESS read-only
  2438. STATUS current
  2439. DESCRIPTION
  2440. "Input Current C, stored as 0.01 A."
  2441. ::= { analogdata6 9 }
  2442. inputFrequency6 OBJECT-TYPE
  2443. SYNTAX Integer32
  2444. MAX-ACCESS read-only
  2445. STATUS current
  2446. DESCRIPTION
  2447. "Input Frequency, stored as 0.01 Hz."
  2448. ::= { analogdata6 10 }
  2449. inputPowerFactorA6 OBJECT-TYPE
  2450. SYNTAX Integer32
  2451. MAX-ACCESS read-only
  2452. STATUS current
  2453. DESCRIPTION
  2454. "Input Power Factor A, stored as 0.01."
  2455. ::= { analogdata6 11 }
  2456. inputPowerFactorB6 OBJECT-TYPE
  2457. SYNTAX Integer32
  2458. MAX-ACCESS read-only
  2459. STATUS current
  2460. DESCRIPTION
  2461. "Input Power Factor B, stored as 0.01."
  2462. ::= { analogdata6 12 }
  2463. inputPowerFactorC6 OBJECT-TYPE
  2464. SYNTAX Integer32
  2465. MAX-ACCESS read-only
  2466. STATUS current
  2467. DESCRIPTION
  2468. "Input Power Factor C, stored as 0.01."
  2469. ::= { analogdata6 13 }
  2470. dCBus1Voltage6 OBJECT-TYPE
  2471. SYNTAX Integer32
  2472. MAX-ACCESS read-only
  2473. STATUS current
  2474. DESCRIPTION
  2475. "DCBus1 Voltage, stored as 0.01 V."
  2476. ::= { analogdata6 14 }
  2477. dCBus2Voltage6 OBJECT-TYPE
  2478. SYNTAX Integer32
  2479. MAX-ACCESS read-only
  2480. STATUS current
  2481. DESCRIPTION
  2482. "DCBus2 Voltage, stored as 0.01 V."
  2483. ::= { analogdata6 15 }
  2484. outputVoltageA6 OBJECT-TYPE
  2485. SYNTAX Integer32
  2486. MAX-ACCESS read-only
  2487. STATUS current
  2488. DESCRIPTION
  2489. "Output voltage A, stored as 0.01 V."
  2490. ::= { analogdata6 16 }
  2491. outputVoltageB6 OBJECT-TYPE
  2492. SYNTAX Integer32
  2493. MAX-ACCESS read-only
  2494. STATUS current
  2495. DESCRIPTION
  2496. "Output voltage B, stored as 0.01 V."
  2497. ::= { analogdata6 17 }
  2498. outputVoltageC6 OBJECT-TYPE
  2499. SYNTAX Integer32
  2500. MAX-ACCESS read-only
  2501. STATUS current
  2502. DESCRIPTION
  2503. "Output voltage C, stored as 0.01 V."
  2504. ::= { analogdata6 18 }
  2505. outputCurrentA6 OBJECT-TYPE
  2506. SYNTAX Integer32
  2507. MAX-ACCESS read-only
  2508. STATUS current
  2509. DESCRIPTION
  2510. "Output current A, stored as 0.01 A."
  2511. ::= { analogdata6 19 }
  2512. outputCurrentB6 OBJECT-TYPE
  2513. SYNTAX Integer32
  2514. MAX-ACCESS read-only
  2515. STATUS current
  2516. DESCRIPTION
  2517. "Output current B, stored as 0.01 A."
  2518. ::= { analogdata6 20 }
  2519. outputCurrentC6 OBJECT-TYPE
  2520. SYNTAX Integer32
  2521. MAX-ACCESS read-only
  2522. STATUS current
  2523. DESCRIPTION
  2524. "Output current C, stored as 0.01 A."
  2525. ::= { analogdata6 21 }
  2526. outputFrequency6 OBJECT-TYPE
  2527. SYNTAX Integer32
  2528. MAX-ACCESS read-only
  2529. STATUS current
  2530. DESCRIPTION
  2531. "Output Frequency, stored as 0.01 Hz."
  2532. ::= { analogdata6 22 }
  2533. outputPowerFactorA6 OBJECT-TYPE
  2534. SYNTAX Integer32
  2535. MAX-ACCESS read-only
  2536. STATUS current
  2537. DESCRIPTION
  2538. "Output Power Factor A, stored as 0.01."
  2539. ::= { analogdata6 23 }
  2540. outputPowerFactorB6 OBJECT-TYPE
  2541. SYNTAX Integer32
  2542. MAX-ACCESS read-only
  2543. STATUS current
  2544. DESCRIPTION
  2545. "Output Power Factor B, stored as 0.01."
  2546. ::= { analogdata6 24 }
  2547. outputPowerFactorC6 OBJECT-TYPE
  2548. SYNTAX Integer32
  2549. MAX-ACCESS read-only
  2550. STATUS current
  2551. DESCRIPTION
  2552. "Output Power Factor C, stored as 0.01."
  2553. ::= { analogdata6 25 }
  2554. outputAcitvePowerA6 OBJECT-TYPE
  2555. SYNTAX Integer32
  2556. MAX-ACCESS read-only
  2557. STATUS current
  2558. DESCRIPTION
  2559. "Output Acitve Power A, stored as 0.01 kW."
  2560. ::= { analogdata6 26 }
  2561. outputAcitvePowerB6 OBJECT-TYPE
  2562. SYNTAX Integer32
  2563. MAX-ACCESS read-only
  2564. STATUS current
  2565. DESCRIPTION
  2566. "Output Acitve Power B, stored as 0.01 kW."
  2567. ::= { analogdata6 27 }
  2568. outputAcitvePowerC6 OBJECT-TYPE
  2569. SYNTAX Integer32
  2570. MAX-ACCESS read-only
  2571. STATUS current
  2572. DESCRIPTION
  2573. "Output Acitve Power C, stored as 0.01 kW."
  2574. ::= { analogdata6 28 }
  2575. outputReactivePowerA6 OBJECT-TYPE
  2576. SYNTAX Integer32
  2577. MAX-ACCESS read-only
  2578. STATUS current
  2579. DESCRIPTION
  2580. "Output Reactive Power A, stored as 0.01 KVAR."
  2581. ::= { analogdata6 29 }
  2582. outputReactivePowerB6 OBJECT-TYPE
  2583. SYNTAX Integer32
  2584. MAX-ACCESS read-only
  2585. STATUS current
  2586. DESCRIPTION
  2587. "Output Reactive Power B, stored as 0.01 KVAR."
  2588. ::= { analogdata6 30 }
  2589. outputReactivePowerC6 OBJECT-TYPE
  2590. SYNTAX Integer32
  2591. MAX-ACCESS read-only
  2592. STATUS current
  2593. DESCRIPTION
  2594. "Output Reactive Power C, stored as 0.01 KVAR."
  2595. ::= { analogdata6 31 }
  2596. outputAppPowerA6 OBJECT-TYPE
  2597. SYNTAX Integer32
  2598. MAX-ACCESS read-only
  2599. STATUS current
  2600. DESCRIPTION
  2601. "Output App Power A, stored as 0.01 kVA."
  2602. ::= { analogdata6 32 }
  2603. outputAppPowerB6 OBJECT-TYPE
  2604. SYNTAX Integer32
  2605. MAX-ACCESS read-only
  2606. STATUS current
  2607. DESCRIPTION
  2608. "Output App Power B, stored as 0.01 kVA."
  2609. ::= { analogdata6 33 }
  2610. outputAppPowerC6 OBJECT-TYPE
  2611. SYNTAX Integer32
  2612. MAX-ACCESS read-only
  2613. STATUS current
  2614. DESCRIPTION
  2615. "Output App Power C, stored as 0.01 kVA."
  2616. ::= { analogdata6 34 }
  2617. outputLoadA6 OBJECT-TYPE
  2618. SYNTAX Integer32
  2619. MAX-ACCESS read-only
  2620. STATUS current
  2621. DESCRIPTION
  2622. "Output Load A, stored as 0.01 %."
  2623. ::= { analogdata6 35 }
  2624. outputLoadB6 OBJECT-TYPE
  2625. SYNTAX Integer32
  2626. MAX-ACCESS read-only
  2627. STATUS current
  2628. DESCRIPTION
  2629. "Output Load B, stored as 0.01 %."
  2630. ::= { analogdata6 36 }
  2631. outputLoadC6 OBJECT-TYPE
  2632. SYNTAX Integer32
  2633. MAX-ACCESS read-only
  2634. STATUS current
  2635. DESCRIPTION
  2636. "Output Load C, stored as 0.01 %."
  2637. ::= { analogdata6 37 }
  2638. outputCrestFactorA6 OBJECT-TYPE
  2639. SYNTAX Integer32
  2640. MAX-ACCESS read-only
  2641. STATUS current
  2642. DESCRIPTION
  2643. "Output Crest Factor A, stored as 0.01 ."
  2644. ::= { analogdata6 38 }
  2645. outputCrestFactorB6 OBJECT-TYPE
  2646. SYNTAX Integer32
  2647. MAX-ACCESS read-only
  2648. STATUS current
  2649. DESCRIPTION
  2650. "Output Crest Factor B, stored as 0.01 ."
  2651. ::= { analogdata6 39 }
  2652. outputCrestFactorC6 OBJECT-TYPE
  2653. SYNTAX Integer32
  2654. MAX-ACCESS read-only
  2655. STATUS current
  2656. DESCRIPTION
  2657. "Output Crest Factor C, stored as 0.01 ."
  2658. ::= { analogdata6 40 }
  2659. bypassVoltageA6 OBJECT-TYPE
  2660. SYNTAX Integer32
  2661. MAX-ACCESS read-only
  2662. STATUS current
  2663. DESCRIPTION
  2664. "Bypass Voltage A, stored as 0.01 V."
  2665. ::= { analogdata6 41 }
  2666. bypassVoltageB6 OBJECT-TYPE
  2667. SYNTAX Integer32
  2668. MAX-ACCESS read-only
  2669. STATUS current
  2670. DESCRIPTION
  2671. "Bypass Voltage B, stored as 0.01 V."
  2672. ::= { analogdata6 42 }
  2673. bypassVoltageC6 OBJECT-TYPE
  2674. SYNTAX Integer32
  2675. MAX-ACCESS read-only
  2676. STATUS current
  2677. DESCRIPTION
  2678. "Bypass Voltage C, stored as 0.01 V."
  2679. ::= { analogdata6 43 }
  2680. bypassFrequency6 OBJECT-TYPE
  2681. SYNTAX Integer32
  2682. MAX-ACCESS read-only
  2683. STATUS current
  2684. DESCRIPTION
  2685. "Bypass Frequency, stored as 0.01 Hz."
  2686. ::= { analogdata6 44 }
  2687. positiveBatteryVoltage6 OBJECT-TYPE
  2688. SYNTAX Integer32
  2689. MAX-ACCESS read-only
  2690. STATUS current
  2691. DESCRIPTION
  2692. "positive Battery Voltage, stored as 0.01 V."
  2693. ::= { analogdata6 45 }
  2694. positiveBatteryCurrent6 OBJECT-TYPE
  2695. SYNTAX Integer32
  2696. MAX-ACCESS read-only
  2697. STATUS current
  2698. DESCRIPTION
  2699. "positive Battery Current, stored as 0.01 A."
  2700. ::= { analogdata6 46 }
  2701. negativeBatteryVoltage6 OBJECT-TYPE
  2702. SYNTAX Integer32
  2703. MAX-ACCESS read-only
  2704. STATUS current
  2705. DESCRIPTION
  2706. "negative Battery Voltage, stored as 0.01 V."
  2707. ::= { analogdata6 47 }
  2708. negativeBatteryCurrent6 OBJECT-TYPE
  2709. SYNTAX Integer32
  2710. MAX-ACCESS read-only
  2711. STATUS current
  2712. DESCRIPTION
  2713. "negative Battery Current, stored as 0.01 A."
  2714. ::= { analogdata6 48 }
  2715. batteryAgingRate6 OBJECT-TYPE
  2716. SYNTAX Integer32
  2717. MAX-ACCESS read-only
  2718. STATUS current
  2719. DESCRIPTION
  2720. "Battery Aging Rate, stored as 0.01."
  2721. ::= { analogdata6 49 }
  2722. batteryRemainsTime6 OBJECT-TYPE
  2723. SYNTAX Integer32
  2724. MAX-ACCESS read-only
  2725. STATUS current
  2726. DESCRIPTION
  2727. "Battery Remains Time, stored as 0.01 Hour."
  2728. ::= { analogdata6 50 }
  2729. batteryTemperature6 OBJECT-TYPE
  2730. SYNTAX Integer32
  2731. MAX-ACCESS read-only
  2732. STATUS current
  2733. DESCRIPTION
  2734. "Battery Temperature, stored as 0.01 °C."
  2735. ::= { analogdata6 51 }
  2736. batteryEnvironmentTemperature6 OBJECT-TYPE
  2737. SYNTAX Integer32
  2738. MAX-ACCESS read-only
  2739. STATUS current
  2740. DESCRIPTION
  2741. "Battery Environment Temperature, stored as 0.01 °C."
  2742. ::= { analogdata6 52 }
  2743. analogdata7 OBJECT IDENTIFIER ::= { system 11 }
  2744. inputPhaseVoltageA7 OBJECT-TYPE
  2745. SYNTAX Integer32
  2746. MAX-ACCESS read-only
  2747. STATUS current
  2748. DESCRIPTION
  2749. "Input Phase Voltage A, stored as 0.01 V."
  2750. ::= { analogdata7 1 }
  2751. inputPhaseVoltageB7 OBJECT-TYPE
  2752. SYNTAX Integer32
  2753. MAX-ACCESS read-only
  2754. STATUS current
  2755. DESCRIPTION
  2756. "Input Phase Voltage B, stored as 0.01 V."
  2757. ::= { analogdata7 2 }
  2758. inputPhaseVoltageC7 OBJECT-TYPE
  2759. SYNTAX Integer32
  2760. MAX-ACCESS read-only
  2761. STATUS current
  2762. DESCRIPTION
  2763. "Input Phase Voltage C, stored as 0.01 V."
  2764. ::= { analogdata7 3 }
  2765. inputLineVoltageA7 OBJECT-TYPE
  2766. SYNTAX Integer32
  2767. MAX-ACCESS read-only
  2768. STATUS current
  2769. DESCRIPTION
  2770. "Input Line Voltage A, stored as 0.01 V."
  2771. ::= { analogdata7 4 }
  2772. inputLineVoltageB7 OBJECT-TYPE
  2773. SYNTAX Integer32
  2774. MAX-ACCESS read-only
  2775. STATUS current
  2776. DESCRIPTION
  2777. "Input Line Voltage B, stored as 0.01 V."
  2778. ::= { analogdata7 5 }
  2779. inputLineVoltageC7 OBJECT-TYPE
  2780. SYNTAX Integer32
  2781. MAX-ACCESS read-only
  2782. STATUS current
  2783. DESCRIPTION
  2784. "Input Line Voltage C, stored as 0.01 V."
  2785. ::= { analogdata7 6 }
  2786. inputCurrentA7 OBJECT-TYPE
  2787. SYNTAX Integer32
  2788. MAX-ACCESS read-only
  2789. STATUS current
  2790. DESCRIPTION
  2791. "Input Current A, stored as 0.01 A."
  2792. ::= { analogdata7 7 }
  2793. inputCurrentB7 OBJECT-TYPE
  2794. SYNTAX Integer32
  2795. MAX-ACCESS read-only
  2796. STATUS current
  2797. DESCRIPTION
  2798. "Input Current B, stored as 0.01 A."
  2799. ::= { analogdata7 8 }
  2800. inputCurrentC7 OBJECT-TYPE
  2801. SYNTAX Integer32
  2802. MAX-ACCESS read-only
  2803. STATUS current
  2804. DESCRIPTION
  2805. "Input Current C, stored as 0.01 A."
  2806. ::= { analogdata7 9 }
  2807. inputFrequency7 OBJECT-TYPE
  2808. SYNTAX Integer32
  2809. MAX-ACCESS read-only
  2810. STATUS current
  2811. DESCRIPTION
  2812. "Input Frequency, stored as 0.01 Hz."
  2813. ::= { analogdata7 10 }
  2814. inputPowerFactorA7 OBJECT-TYPE
  2815. SYNTAX Integer32
  2816. MAX-ACCESS read-only
  2817. STATUS current
  2818. DESCRIPTION
  2819. "Input Power Factor A, stored as 0.01."
  2820. ::= { analogdata7 11 }
  2821. inputPowerFactorB7 OBJECT-TYPE
  2822. SYNTAX Integer32
  2823. MAX-ACCESS read-only
  2824. STATUS current
  2825. DESCRIPTION
  2826. "Input Power Factor B, stored as 0.01."
  2827. ::= { analogdata7 12 }
  2828. inputPowerFactorC7 OBJECT-TYPE
  2829. SYNTAX Integer32
  2830. MAX-ACCESS read-only
  2831. STATUS current
  2832. DESCRIPTION
  2833. "Input Power Factor C, stored as 0.01."
  2834. ::= { analogdata7 13 }
  2835. dCBus1Voltage7 OBJECT-TYPE
  2836. SYNTAX Integer32
  2837. MAX-ACCESS read-only
  2838. STATUS current
  2839. DESCRIPTION
  2840. "DCBus1 Voltage, stored as 0.01 V."
  2841. ::= { analogdata7 14 }
  2842. dCBus2Voltage7 OBJECT-TYPE
  2843. SYNTAX Integer32
  2844. MAX-ACCESS read-only
  2845. STATUS current
  2846. DESCRIPTION
  2847. "DCBus2 Voltage, stored as 0.01 V."
  2848. ::= { analogdata7 15 }
  2849. outputVoltageA7 OBJECT-TYPE
  2850. SYNTAX Integer32
  2851. MAX-ACCESS read-only
  2852. STATUS current
  2853. DESCRIPTION
  2854. "Output voltage A, stored as 0.01 V."
  2855. ::= { analogdata7 16 }
  2856. outputVoltageB7 OBJECT-TYPE
  2857. SYNTAX Integer32
  2858. MAX-ACCESS read-only
  2859. STATUS current
  2860. DESCRIPTION
  2861. "Output voltage B, stored as 0.01 V."
  2862. ::= { analogdata7 17 }
  2863. outputVoltageC7 OBJECT-TYPE
  2864. SYNTAX Integer32
  2865. MAX-ACCESS read-only
  2866. STATUS current
  2867. DESCRIPTION
  2868. "Output voltage C, stored as 0.01 V."
  2869. ::= { analogdata7 18 }
  2870. outputCurrentA7 OBJECT-TYPE
  2871. SYNTAX Integer32
  2872. MAX-ACCESS read-only
  2873. STATUS current
  2874. DESCRIPTION
  2875. "Output current A, stored as 0.01 A."
  2876. ::= { analogdata7 19 }
  2877. outputCurrentB7 OBJECT-TYPE
  2878. SYNTAX Integer32
  2879. MAX-ACCESS read-only
  2880. STATUS current
  2881. DESCRIPTION
  2882. "Output current B, stored as 0.01 A."
  2883. ::= { analogdata7 20 }
  2884. outputCurrentC7 OBJECT-TYPE
  2885. SYNTAX Integer32
  2886. MAX-ACCESS read-only
  2887. STATUS current
  2888. DESCRIPTION
  2889. "Output current C, stored as 0.01 A."
  2890. ::= { analogdata7 21 }
  2891. outputFrequency7 OBJECT-TYPE
  2892. SYNTAX Integer32
  2893. MAX-ACCESS read-only
  2894. STATUS current
  2895. DESCRIPTION
  2896. "Output Frequency, stored as 0.01 Hz."
  2897. ::= { analogdata7 22 }
  2898. outputPowerFactorA7 OBJECT-TYPE
  2899. SYNTAX Integer32
  2900. MAX-ACCESS read-only
  2901. STATUS current
  2902. DESCRIPTION
  2903. "Output Power Factor A, stored as 0.01."
  2904. ::= { analogdata7 23 }
  2905. outputPowerFactorB7 OBJECT-TYPE
  2906. SYNTAX Integer32
  2907. MAX-ACCESS read-only
  2908. STATUS current
  2909. DESCRIPTION
  2910. "Output Power Factor B, stored as 0.01."
  2911. ::= { analogdata7 24 }
  2912. outputPowerFactorC7 OBJECT-TYPE
  2913. SYNTAX Integer32
  2914. MAX-ACCESS read-only
  2915. STATUS current
  2916. DESCRIPTION
  2917. "Output Power Factor C, stored as 0.01."
  2918. ::= { analogdata7 25 }
  2919. outputAcitvePowerA7 OBJECT-TYPE
  2920. SYNTAX Integer32
  2921. MAX-ACCESS read-only
  2922. STATUS current
  2923. DESCRIPTION
  2924. "Output Acitve Power A, stored as 0.01 kW."
  2925. ::= { analogdata7 26 }
  2926. outputAcitvePowerB7 OBJECT-TYPE
  2927. SYNTAX Integer32
  2928. MAX-ACCESS read-only
  2929. STATUS current
  2930. DESCRIPTION
  2931. "Output Acitve Power B, stored as 0.01 kW."
  2932. ::= { analogdata7 27 }
  2933. outputAcitvePowerC7 OBJECT-TYPE
  2934. SYNTAX Integer32
  2935. MAX-ACCESS read-only
  2936. STATUS current
  2937. DESCRIPTION
  2938. "Output Acitve Power C, stored as 0.01 kW."
  2939. ::= { analogdata7 28 }
  2940. outputReactivePowerA7 OBJECT-TYPE
  2941. SYNTAX Integer32
  2942. MAX-ACCESS read-only
  2943. STATUS current
  2944. DESCRIPTION
  2945. "Output Reactive Power A, stored as 0.01 KVAR."
  2946. ::= { analogdata7 29 }
  2947. outputReactivePowerB7 OBJECT-TYPE
  2948. SYNTAX Integer32
  2949. MAX-ACCESS read-only
  2950. STATUS current
  2951. DESCRIPTION
  2952. "Output Reactive Power B, stored as 0.01 KVAR."
  2953. ::= { analogdata7 30 }
  2954. outputReactivePowerC7 OBJECT-TYPE
  2955. SYNTAX Integer32
  2956. MAX-ACCESS read-only
  2957. STATUS current
  2958. DESCRIPTION
  2959. "Output Reactive Power C, stored as 0.01 KVAR."
  2960. ::= { analogdata7 31 }
  2961. outputAppPowerA7 OBJECT-TYPE
  2962. SYNTAX Integer32
  2963. MAX-ACCESS read-only
  2964. STATUS current
  2965. DESCRIPTION
  2966. "Output App Power A, stored as 0.01 kVA."
  2967. ::= { analogdata7 32 }
  2968. outputAppPowerB7 OBJECT-TYPE
  2969. SYNTAX Integer32
  2970. MAX-ACCESS read-only
  2971. STATUS current
  2972. DESCRIPTION
  2973. "Output App Power B, stored as 0.01 kVA."
  2974. ::= { analogdata7 33 }
  2975. outputAppPowerC7 OBJECT-TYPE
  2976. SYNTAX Integer32
  2977. MAX-ACCESS read-only
  2978. STATUS current
  2979. DESCRIPTION
  2980. "Output App Power C, stored as 0.01 kVA."
  2981. ::= { analogdata7 34 }
  2982. outputLoadA7 OBJECT-TYPE
  2983. SYNTAX Integer32
  2984. MAX-ACCESS read-only
  2985. STATUS current
  2986. DESCRIPTION
  2987. "Output Load A, stored as 0.01 %."
  2988. ::= { analogdata7 35 }
  2989. outputLoadB7 OBJECT-TYPE
  2990. SYNTAX Integer32
  2991. MAX-ACCESS read-only
  2992. STATUS current
  2993. DESCRIPTION
  2994. "Output Load B, stored as 0.01 %."
  2995. ::= { analogdata7 36 }
  2996. outputLoadC7 OBJECT-TYPE
  2997. SYNTAX Integer32
  2998. MAX-ACCESS read-only
  2999. STATUS current
  3000. DESCRIPTION
  3001. "Output Load C, stored as 0.01 %."
  3002. ::= { analogdata7 37 }
  3003. outputCrestFactorA7 OBJECT-TYPE
  3004. SYNTAX Integer32
  3005. MAX-ACCESS read-only
  3006. STATUS current
  3007. DESCRIPTION
  3008. "Output Crest Factor A, stored as 0.01 ."
  3009. ::= { analogdata7 38 }
  3010. outputCrestFactorB7 OBJECT-TYPE
  3011. SYNTAX Integer32
  3012. MAX-ACCESS read-only
  3013. STATUS current
  3014. DESCRIPTION
  3015. "Output Crest Factor B, stored as 0.01 ."
  3016. ::= { analogdata7 39 }
  3017. outputCrestFactorC7 OBJECT-TYPE
  3018. SYNTAX Integer32
  3019. MAX-ACCESS read-only
  3020. STATUS current
  3021. DESCRIPTION
  3022. "Output Crest Factor C, stored as 0.01 ."
  3023. ::= { analogdata7 40 }
  3024. bypassVoltageA7 OBJECT-TYPE
  3025. SYNTAX Integer32
  3026. MAX-ACCESS read-only
  3027. STATUS current
  3028. DESCRIPTION
  3029. "Bypass Voltage A, stored as 0.01 V."
  3030. ::= { analogdata7 41 }
  3031. bypassVoltageB7 OBJECT-TYPE
  3032. SYNTAX Integer32
  3033. MAX-ACCESS read-only
  3034. STATUS current
  3035. DESCRIPTION
  3036. "Bypass Voltage B, stored as 0.01 V."
  3037. ::= { analogdata7 42 }
  3038. bypassVoltageC7 OBJECT-TYPE
  3039. SYNTAX Integer32
  3040. MAX-ACCESS read-only
  3041. STATUS current
  3042. DESCRIPTION
  3043. "Bypass Voltage C, stored as 0.01 V."
  3044. ::= { analogdata7 43 }
  3045. bypassFrequency7 OBJECT-TYPE
  3046. SYNTAX Integer32
  3047. MAX-ACCESS read-only
  3048. STATUS current
  3049. DESCRIPTION
  3050. "Bypass Frequency, stored as 0.01 Hz."
  3051. ::= { analogdata7 44 }
  3052. positiveBatteryVoltage7 OBJECT-TYPE
  3053. SYNTAX Integer32
  3054. MAX-ACCESS read-only
  3055. STATUS current
  3056. DESCRIPTION
  3057. "positive Battery Voltage, stored as 0.01 V."
  3058. ::= { analogdata7 45 }
  3059. positiveBatteryCurrent7 OBJECT-TYPE
  3060. SYNTAX Integer32
  3061. MAX-ACCESS read-only
  3062. STATUS current
  3063. DESCRIPTION
  3064. "positive Battery Current, stored as 0.01 A."
  3065. ::= { analogdata7 46 }
  3066. negativeBatteryVoltage7 OBJECT-TYPE
  3067. SYNTAX Integer32
  3068. MAX-ACCESS read-only
  3069. STATUS current
  3070. DESCRIPTION
  3071. "negative Battery Voltage, stored as 0.01 V."
  3072. ::= { analogdata7 47 }
  3073. negativeBatteryCurrent7 OBJECT-TYPE
  3074. SYNTAX Integer32
  3075. MAX-ACCESS read-only
  3076. STATUS current
  3077. DESCRIPTION
  3078. "negative Battery Current, stored as 0.01 A."
  3079. ::= { analogdata7 48 }
  3080. batteryAgingRate7 OBJECT-TYPE
  3081. SYNTAX Integer32
  3082. MAX-ACCESS read-only
  3083. STATUS current
  3084. DESCRIPTION
  3085. "Battery Aging Rate, stored as 0.01."
  3086. ::= { analogdata7 49 }
  3087. batteryRemainsTime7 OBJECT-TYPE
  3088. SYNTAX Integer32
  3089. MAX-ACCESS read-only
  3090. STATUS current
  3091. DESCRIPTION
  3092. "Battery Remains Time, stored as 0.01 Hour."
  3093. ::= { analogdata7 50 }
  3094. batteryTemperature7 OBJECT-TYPE
  3095. SYNTAX Integer32
  3096. MAX-ACCESS read-only
  3097. STATUS current
  3098. DESCRIPTION
  3099. "Battery Temperature, stored as 0.01 °C."
  3100. ::= { analogdata7 51 }
  3101. batteryEnvironmentTemperature7 OBJECT-TYPE
  3102. SYNTAX Integer32
  3103. MAX-ACCESS read-only
  3104. STATUS current
  3105. DESCRIPTION
  3106. "Battery Environment Temperature, stored as 0.01 °C."
  3107. ::= { analogdata7 52 }
  3108. analogdata8 OBJECT IDENTIFIER ::= { system 12 }
  3109. inputPhaseVoltageA8 OBJECT-TYPE
  3110. SYNTAX Integer32
  3111. MAX-ACCESS read-only
  3112. STATUS current
  3113. DESCRIPTION
  3114. "Input Phase Voltage A, stored as 0.01 V."
  3115. ::= { analogdata8 1 }
  3116. inputPhaseVoltageB8 OBJECT-TYPE
  3117. SYNTAX Integer32
  3118. MAX-ACCESS read-only
  3119. STATUS current
  3120. DESCRIPTION
  3121. "Input Phase Voltage B, stored as 0.01 V."
  3122. ::= { analogdata8 2 }
  3123. inputPhaseVoltageC8 OBJECT-TYPE
  3124. SYNTAX Integer32
  3125. MAX-ACCESS read-only
  3126. STATUS current
  3127. DESCRIPTION
  3128. "Input Phase Voltage C, stored as 0.01 V."
  3129. ::= { analogdata8 3 }
  3130. inputLineVoltageA8 OBJECT-TYPE
  3131. SYNTAX Integer32
  3132. MAX-ACCESS read-only
  3133. STATUS current
  3134. DESCRIPTION
  3135. "Input Line Voltage A, stored as 0.01 V."
  3136. ::= { analogdata8 4 }
  3137. inputLineVoltageB8 OBJECT-TYPE
  3138. SYNTAX Integer32
  3139. MAX-ACCESS read-only
  3140. STATUS current
  3141. DESCRIPTION
  3142. "Input Line Voltage B, stored as 0.01 V."
  3143. ::= { analogdata8 5 }
  3144. inputLineVoltageC8 OBJECT-TYPE
  3145. SYNTAX Integer32
  3146. MAX-ACCESS read-only
  3147. STATUS current
  3148. DESCRIPTION
  3149. "Input Line Voltage C, stored as 0.01 V."
  3150. ::= { analogdata8 6 }
  3151. inputCurrentA8 OBJECT-TYPE
  3152. SYNTAX Integer32
  3153. MAX-ACCESS read-only
  3154. STATUS current
  3155. DESCRIPTION
  3156. "Input Current A, stored as 0.01 A."
  3157. ::= { analogdata8 7 }
  3158. inputCurrentB8 OBJECT-TYPE
  3159. SYNTAX Integer32
  3160. MAX-ACCESS read-only
  3161. STATUS current
  3162. DESCRIPTION
  3163. "Input Current B, stored as 0.01 A."
  3164. ::= { analogdata8 8 }
  3165. inputCurrentC8 OBJECT-TYPE
  3166. SYNTAX Integer32
  3167. MAX-ACCESS read-only
  3168. STATUS current
  3169. DESCRIPTION
  3170. "Input Current C, stored as 0.01 A."
  3171. ::= { analogdata8 9 }
  3172. inputFrequency8 OBJECT-TYPE
  3173. SYNTAX Integer32
  3174. MAX-ACCESS read-only
  3175. STATUS current
  3176. DESCRIPTION
  3177. "Input Frequency, stored as 0.01 Hz."
  3178. ::= { analogdata8 10 }
  3179. inputPowerFactorA8 OBJECT-TYPE
  3180. SYNTAX Integer32
  3181. MAX-ACCESS read-only
  3182. STATUS current
  3183. DESCRIPTION
  3184. "Input Power Factor A, stored as 0.01."
  3185. ::= { analogdata8 11 }
  3186. inputPowerFactorB8 OBJECT-TYPE
  3187. SYNTAX Integer32
  3188. MAX-ACCESS read-only
  3189. STATUS current
  3190. DESCRIPTION
  3191. "Input Power Factor B, stored as 0.01."
  3192. ::= { analogdata8 12 }
  3193. inputPowerFactorC8 OBJECT-TYPE
  3194. SYNTAX Integer32
  3195. MAX-ACCESS read-only
  3196. STATUS current
  3197. DESCRIPTION
  3198. "Input Power Factor C, stored as 0.01."
  3199. ::= { analogdata8 13 }
  3200. dCBus1Voltage8 OBJECT-TYPE
  3201. SYNTAX Integer32
  3202. MAX-ACCESS read-only
  3203. STATUS current
  3204. DESCRIPTION
  3205. "DCBus1 Voltage, stored as 0.01 V."
  3206. ::= { analogdata8 14 }
  3207. dCBus2Voltage8 OBJECT-TYPE
  3208. SYNTAX Integer32
  3209. MAX-ACCESS read-only
  3210. STATUS current
  3211. DESCRIPTION
  3212. "DCBus2 Voltage, stored as 0.01 V."
  3213. ::= { analogdata8 15 }
  3214. outputVoltageA8 OBJECT-TYPE
  3215. SYNTAX Integer32
  3216. MAX-ACCESS read-only
  3217. STATUS current
  3218. DESCRIPTION
  3219. "Output voltage A, stored as 0.01 V."
  3220. ::= { analogdata8 16 }
  3221. outputVoltageB8 OBJECT-TYPE
  3222. SYNTAX Integer32
  3223. MAX-ACCESS read-only
  3224. STATUS current
  3225. DESCRIPTION
  3226. "Output voltage B, stored as 0.01 V."
  3227. ::= { analogdata8 17 }
  3228. outputVoltageC8 OBJECT-TYPE
  3229. SYNTAX Integer32
  3230. MAX-ACCESS read-only
  3231. STATUS current
  3232. DESCRIPTION
  3233. "Output voltage C, stored as 0.01 V."
  3234. ::= { analogdata8 18 }
  3235. outputCurrentA8 OBJECT-TYPE
  3236. SYNTAX Integer32
  3237. MAX-ACCESS read-only
  3238. STATUS current
  3239. DESCRIPTION
  3240. "Output current A, stored as 0.01 A."
  3241. ::= { analogdata8 19 }
  3242. outputCurrentB8 OBJECT-TYPE
  3243. SYNTAX Integer32
  3244. MAX-ACCESS read-only
  3245. STATUS current
  3246. DESCRIPTION
  3247. "Output current B, stored as 0.01 A."
  3248. ::= { analogdata8 20 }
  3249. outputCurrentC8 OBJECT-TYPE
  3250. SYNTAX Integer32
  3251. MAX-ACCESS read-only
  3252. STATUS current
  3253. DESCRIPTION
  3254. "Output current C, stored as 0.01 A."
  3255. ::= { analogdata8 21 }
  3256. outputFrequency8 OBJECT-TYPE
  3257. SYNTAX Integer32
  3258. MAX-ACCESS read-only
  3259. STATUS current
  3260. DESCRIPTION
  3261. "Output Frequency, stored as 0.01 Hz."
  3262. ::= { analogdata8 22 }
  3263. outputPowerFactorA8 OBJECT-TYPE
  3264. SYNTAX Integer32
  3265. MAX-ACCESS read-only
  3266. STATUS current
  3267. DESCRIPTION
  3268. "Output Power Factor A, stored as 0.01."
  3269. ::= { analogdata8 23 }
  3270. outputPowerFactorB8 OBJECT-TYPE
  3271. SYNTAX Integer32
  3272. MAX-ACCESS read-only
  3273. STATUS current
  3274. DESCRIPTION
  3275. "Output Power Factor B, stored as 0.01."
  3276. ::= { analogdata8 24 }
  3277. outputPowerFactorC8 OBJECT-TYPE
  3278. SYNTAX Integer32
  3279. MAX-ACCESS read-only
  3280. STATUS current
  3281. DESCRIPTION
  3282. "Output Power Factor C, stored as 0.01."
  3283. ::= { analogdata8 25 }
  3284. outputAcitvePowerA8 OBJECT-TYPE
  3285. SYNTAX Integer32
  3286. MAX-ACCESS read-only
  3287. STATUS current
  3288. DESCRIPTION
  3289. "Output Acitve Power A, stored as 0.01 kW."
  3290. ::= { analogdata8 26 }
  3291. outputAcitvePowerB8 OBJECT-TYPE
  3292. SYNTAX Integer32
  3293. MAX-ACCESS read-only
  3294. STATUS current
  3295. DESCRIPTION
  3296. "Output Acitve Power B, stored as 0.01 kW."
  3297. ::= { analogdata8 27 }
  3298. outputAcitvePowerC8 OBJECT-TYPE
  3299. SYNTAX Integer32
  3300. MAX-ACCESS read-only
  3301. STATUS current
  3302. DESCRIPTION
  3303. "Output Acitve Power C, stored as 0.01 kW."
  3304. ::= { analogdata8 28 }
  3305. outputReactivePowerA8 OBJECT-TYPE
  3306. SYNTAX Integer32
  3307. MAX-ACCESS read-only
  3308. STATUS current
  3309. DESCRIPTION
  3310. "Output Reactive Power A, stored as 0.01 KVAR."
  3311. ::= { analogdata8 29 }
  3312. outputReactivePowerB8 OBJECT-TYPE
  3313. SYNTAX Integer32
  3314. MAX-ACCESS read-only
  3315. STATUS current
  3316. DESCRIPTION
  3317. "Output Reactive Power B, stored as 0.01 KVAR."
  3318. ::= { analogdata8 30 }
  3319. outputReactivePowerC8 OBJECT-TYPE
  3320. SYNTAX Integer32
  3321. MAX-ACCESS read-only
  3322. STATUS current
  3323. DESCRIPTION
  3324. "Output Reactive Power C, stored as 0.01 KVAR."
  3325. ::= { analogdata8 31 }
  3326. outputAppPowerA8 OBJECT-TYPE
  3327. SYNTAX Integer32
  3328. MAX-ACCESS read-only
  3329. STATUS current
  3330. DESCRIPTION
  3331. "Output App Power A, stored as 0.01 kVA."
  3332. ::= { analogdata8 32 }
  3333. outputAppPowerB8 OBJECT-TYPE
  3334. SYNTAX Integer32
  3335. MAX-ACCESS read-only
  3336. STATUS current
  3337. DESCRIPTION
  3338. "Output App Power B, stored as 0.01 kVA."
  3339. ::= { analogdata8 33 }
  3340. outputAppPowerC8 OBJECT-TYPE
  3341. SYNTAX Integer32
  3342. MAX-ACCESS read-only
  3343. STATUS current
  3344. DESCRIPTION
  3345. "Output App Power C, stored as 0.01 kVA."
  3346. ::= { analogdata8 34 }
  3347. outputLoadA8 OBJECT-TYPE
  3348. SYNTAX Integer32
  3349. MAX-ACCESS read-only
  3350. STATUS current
  3351. DESCRIPTION
  3352. "Output Load A, stored as 0.01 %."
  3353. ::= { analogdata8 35 }
  3354. outputLoadB8 OBJECT-TYPE
  3355. SYNTAX Integer32
  3356. MAX-ACCESS read-only
  3357. STATUS current
  3358. DESCRIPTION
  3359. "Output Load B, stored as 0.01 %."
  3360. ::= { analogdata8 36 }
  3361. outputLoadC8 OBJECT-TYPE
  3362. SYNTAX Integer32
  3363. MAX-ACCESS read-only
  3364. STATUS current
  3365. DESCRIPTION
  3366. "Output Load C, stored as 0.01 %."
  3367. ::= { analogdata8 37 }
  3368. outputCrestFactorA8 OBJECT-TYPE
  3369. SYNTAX Integer32
  3370. MAX-ACCESS read-only
  3371. STATUS current
  3372. DESCRIPTION
  3373. "Output Crest Factor A, stored as 0.01 ."
  3374. ::= { analogdata8 38 }
  3375. outputCrestFactorB8 OBJECT-TYPE
  3376. SYNTAX Integer32
  3377. MAX-ACCESS read-only
  3378. STATUS current
  3379. DESCRIPTION
  3380. "Output Crest Factor B, stored as 0.01 ."
  3381. ::= { analogdata8 39 }
  3382. outputCrestFactorC8 OBJECT-TYPE
  3383. SYNTAX Integer32
  3384. MAX-ACCESS read-only
  3385. STATUS current
  3386. DESCRIPTION
  3387. "Output Crest Factor C, stored as 0.01 ."
  3388. ::= { analogdata8 40 }
  3389. bypassVoltageA8 OBJECT-TYPE
  3390. SYNTAX Integer32
  3391. MAX-ACCESS read-only
  3392. STATUS current
  3393. DESCRIPTION
  3394. "Bypass Voltage A, stored as 0.01 V."
  3395. ::= { analogdata8 41 }
  3396. bypassVoltageB8 OBJECT-TYPE
  3397. SYNTAX Integer32
  3398. MAX-ACCESS read-only
  3399. STATUS current
  3400. DESCRIPTION
  3401. "Bypass Voltage B, stored as 0.01 V."
  3402. ::= { analogdata8 42 }
  3403. bypassVoltageC8 OBJECT-TYPE
  3404. SYNTAX Integer32
  3405. MAX-ACCESS read-only
  3406. STATUS current
  3407. DESCRIPTION
  3408. "Bypass Voltage C, stored as 0.01 V."
  3409. ::= { analogdata8 43 }
  3410. bypassFrequency8 OBJECT-TYPE
  3411. SYNTAX Integer32
  3412. MAX-ACCESS read-only
  3413. STATUS current
  3414. DESCRIPTION
  3415. "Bypass Frequency, stored as 0.01 Hz."
  3416. ::= { analogdata8 44 }
  3417. positiveBatteryVoltage8 OBJECT-TYPE
  3418. SYNTAX Integer32
  3419. MAX-ACCESS read-only
  3420. STATUS current
  3421. DESCRIPTION
  3422. "positive Battery Voltage, stored as 0.01 V."
  3423. ::= { analogdata8 45 }
  3424. positiveBatteryCurrent8 OBJECT-TYPE
  3425. SYNTAX Integer32
  3426. MAX-ACCESS read-only
  3427. STATUS current
  3428. DESCRIPTION
  3429. "positive Battery Current, stored as 0.01 A."
  3430. ::= { analogdata8 46 }
  3431. negativeBatteryVoltage8 OBJECT-TYPE
  3432. SYNTAX Integer32
  3433. MAX-ACCESS read-only
  3434. STATUS current
  3435. DESCRIPTION
  3436. "negative Battery Voltage, stored as 0.01 V."
  3437. ::= { analogdata8 47 }
  3438. negativeBatteryCurrent8 OBJECT-TYPE
  3439. SYNTAX Integer32
  3440. MAX-ACCESS read-only
  3441. STATUS current
  3442. DESCRIPTION
  3443. "negative Battery Current, stored as 0.01 A."
  3444. ::= { analogdata8 48 }
  3445. batteryAgingRate8 OBJECT-TYPE
  3446. SYNTAX Integer32
  3447. MAX-ACCESS read-only
  3448. STATUS current
  3449. DESCRIPTION
  3450. "Battery Aging Rate, stored as 0.01."
  3451. ::= { analogdata8 49 }
  3452. batteryRemainsTime8 OBJECT-TYPE
  3453. SYNTAX Integer32
  3454. MAX-ACCESS read-only
  3455. STATUS current
  3456. DESCRIPTION
  3457. "Battery Remains Time, stored as 0.01 Hour."
  3458. ::= { analogdata8 50 }
  3459. batteryTemperature8 OBJECT-TYPE
  3460. SYNTAX Integer32
  3461. MAX-ACCESS read-only
  3462. STATUS current
  3463. DESCRIPTION
  3464. "Battery Temperature, stored as 0.01 °C."
  3465. ::= { analogdata8 51 }
  3466. batteryEnvironmentTemperature8 OBJECT-TYPE
  3467. SYNTAX Integer32
  3468. MAX-ACCESS read-only
  3469. STATUS current
  3470. DESCRIPTION
  3471. "Battery Environment Temperature, stored as 0.01 °C."
  3472. ::= { analogdata8 52 }
  3473. analogdata9 OBJECT IDENTIFIER ::= { system 13 }
  3474. inputPhaseVoltageA9 OBJECT-TYPE
  3475. SYNTAX Integer32
  3476. MAX-ACCESS read-only
  3477. STATUS current
  3478. DESCRIPTION
  3479. "Input Phase Voltage A, stored as 0.01 V."
  3480. ::= { analogdata9 1 }
  3481. inputPhaseVoltageB9 OBJECT-TYPE
  3482. SYNTAX Integer32
  3483. MAX-ACCESS read-only
  3484. STATUS current
  3485. DESCRIPTION
  3486. "Input Phase Voltage B, stored as 0.01 V."
  3487. ::= { analogdata9 2 }
  3488. inputPhaseVoltageC9 OBJECT-TYPE
  3489. SYNTAX Integer32
  3490. MAX-ACCESS read-only
  3491. STATUS current
  3492. DESCRIPTION
  3493. "Input Phase Voltage C, stored as 0.01 V."
  3494. ::= { analogdata9 3 }
  3495. inputLineVoltageA9 OBJECT-TYPE
  3496. SYNTAX Integer32
  3497. MAX-ACCESS read-only
  3498. STATUS current
  3499. DESCRIPTION
  3500. "Input Line Voltage A, stored as 0.01 V."
  3501. ::= { analogdata9 4 }
  3502. inputLineVoltageB9 OBJECT-TYPE
  3503. SYNTAX Integer32
  3504. MAX-ACCESS read-only
  3505. STATUS current
  3506. DESCRIPTION
  3507. "Input Line Voltage B, stored as 0.01 V."
  3508. ::= { analogdata9 5 }
  3509. inputLineVoltageC9 OBJECT-TYPE
  3510. SYNTAX Integer32
  3511. MAX-ACCESS read-only
  3512. STATUS current
  3513. DESCRIPTION
  3514. "Input Line Voltage C, stored as 0.01 V."
  3515. ::= { analogdata9 6 }
  3516. inputCurrentA9 OBJECT-TYPE
  3517. SYNTAX Integer32
  3518. MAX-ACCESS read-only
  3519. STATUS current
  3520. DESCRIPTION
  3521. "Input Current A, stored as 0.01 A."
  3522. ::= { analogdata9 7 }
  3523. inputCurrentB9 OBJECT-TYPE
  3524. SYNTAX Integer32
  3525. MAX-ACCESS read-only
  3526. STATUS current
  3527. DESCRIPTION
  3528. "Input Current B, stored as 0.01 A."
  3529. ::= { analogdata9 8 }
  3530. inputCurrentC9 OBJECT-TYPE
  3531. SYNTAX Integer32
  3532. MAX-ACCESS read-only
  3533. STATUS current
  3534. DESCRIPTION
  3535. "Input Current C, stored as 0.01 A."
  3536. ::= { analogdata9 9 }
  3537. inputFrequency9 OBJECT-TYPE
  3538. SYNTAX Integer32
  3539. MAX-ACCESS read-only
  3540. STATUS current
  3541. DESCRIPTION
  3542. "Input Frequency, stored as 0.01 Hz."
  3543. ::= { analogdata9 10 }
  3544. inputPowerFactorA9 OBJECT-TYPE
  3545. SYNTAX Integer32
  3546. MAX-ACCESS read-only
  3547. STATUS current
  3548. DESCRIPTION
  3549. "Input Power Factor A, stored as 0.01."
  3550. ::= { analogdata9 11 }
  3551. inputPowerFactorB9 OBJECT-TYPE
  3552. SYNTAX Integer32
  3553. MAX-ACCESS read-only
  3554. STATUS current
  3555. DESCRIPTION
  3556. "Input Power Factor B, stored as 0.01."
  3557. ::= { analogdata9 12 }
  3558. inputPowerFactorC9 OBJECT-TYPE
  3559. SYNTAX Integer32
  3560. MAX-ACCESS read-only
  3561. STATUS current
  3562. DESCRIPTION
  3563. "Input Power Factor C, stored as 0.01."
  3564. ::= { analogdata9 13 }
  3565. dCBus1Voltage9 OBJECT-TYPE
  3566. SYNTAX Integer32
  3567. MAX-ACCESS read-only
  3568. STATUS current
  3569. DESCRIPTION
  3570. "DCBus1 Voltage, stored as 0.01 V."
  3571. ::= { analogdata9 14 }
  3572. dCBus2Voltage9 OBJECT-TYPE
  3573. SYNTAX Integer32
  3574. MAX-ACCESS read-only
  3575. STATUS current
  3576. DESCRIPTION
  3577. "DCBus2 Voltage, stored as 0.01 V."
  3578. ::= { analogdata9 15 }
  3579. outputVoltageA9 OBJECT-TYPE
  3580. SYNTAX Integer32
  3581. MAX-ACCESS read-only
  3582. STATUS current
  3583. DESCRIPTION
  3584. "Output voltage A, stored as 0.01 V."
  3585. ::= { analogdata9 16 }
  3586. outputVoltageB9 OBJECT-TYPE
  3587. SYNTAX Integer32
  3588. MAX-ACCESS read-only
  3589. STATUS current
  3590. DESCRIPTION
  3591. "Output voltage B, stored as 0.01 V."
  3592. ::= { analogdata9 17 }
  3593. outputVoltageC9 OBJECT-TYPE
  3594. SYNTAX Integer32
  3595. MAX-ACCESS read-only
  3596. STATUS current
  3597. DESCRIPTION
  3598. "Output voltage C, stored as 0.01 V."
  3599. ::= { analogdata9 18 }
  3600. outputCurrentA9 OBJECT-TYPE
  3601. SYNTAX Integer32
  3602. MAX-ACCESS read-only
  3603. STATUS current
  3604. DESCRIPTION
  3605. "Output current A, stored as 0.01 A."
  3606. ::= { analogdata9 19 }
  3607. outputCurrentB9 OBJECT-TYPE
  3608. SYNTAX Integer32
  3609. MAX-ACCESS read-only
  3610. STATUS current
  3611. DESCRIPTION
  3612. "Output current B, stored as 0.01 A."
  3613. ::= { analogdata9 20 }
  3614. outputCurrentC9 OBJECT-TYPE
  3615. SYNTAX Integer32
  3616. MAX-ACCESS read-only
  3617. STATUS current
  3618. DESCRIPTION
  3619. "Output current C, stored as 0.01 A."
  3620. ::= { analogdata9 21 }
  3621. outputFrequency9 OBJECT-TYPE
  3622. SYNTAX Integer32
  3623. MAX-ACCESS read-only
  3624. STATUS current
  3625. DESCRIPTION
  3626. "Output Frequency, stored as 0.01 Hz."
  3627. ::= { analogdata9 22 }
  3628. outputPowerFactorA9 OBJECT-TYPE
  3629. SYNTAX Integer32
  3630. MAX-ACCESS read-only
  3631. STATUS current
  3632. DESCRIPTION
  3633. "Output Power Factor A, stored as 0.01."
  3634. ::= { analogdata9 23 }
  3635. outputPowerFactorB9 OBJECT-TYPE
  3636. SYNTAX Integer32
  3637. MAX-ACCESS read-only
  3638. STATUS current
  3639. DESCRIPTION
  3640. "Output Power Factor B, stored as 0.01."
  3641. ::= { analogdata9 24 }
  3642. outputPowerFactorC9 OBJECT-TYPE
  3643. SYNTAX Integer32
  3644. MAX-ACCESS read-only
  3645. STATUS current
  3646. DESCRIPTION
  3647. "Output Power Factor C, stored as 0.01."
  3648. ::= { analogdata9 25 }
  3649. outputAcitvePowerA9 OBJECT-TYPE
  3650. SYNTAX Integer32
  3651. MAX-ACCESS read-only
  3652. STATUS current
  3653. DESCRIPTION
  3654. "Output Acitve Power A, stored as 0.01 kW."
  3655. ::= { analogdata9 26 }
  3656. outputAcitvePowerB9 OBJECT-TYPE
  3657. SYNTAX Integer32
  3658. MAX-ACCESS read-only
  3659. STATUS current
  3660. DESCRIPTION
  3661. "Output Acitve Power B, stored as 0.01 kW."
  3662. ::= { analogdata9 27 }
  3663. outputAcitvePowerC9 OBJECT-TYPE
  3664. SYNTAX Integer32
  3665. MAX-ACCESS read-only
  3666. STATUS current
  3667. DESCRIPTION
  3668. "Output Acitve Power C, stored as 0.01 kW."
  3669. ::= { analogdata9 28 }
  3670. outputReactivePowerA9 OBJECT-TYPE
  3671. SYNTAX Integer32
  3672. MAX-ACCESS read-only
  3673. STATUS current
  3674. DESCRIPTION
  3675. "Output Reactive Power A, stored as 0.01 KVAR."
  3676. ::= { analogdata9 29 }
  3677. outputReactivePowerB9 OBJECT-TYPE
  3678. SYNTAX Integer32
  3679. MAX-ACCESS read-only
  3680. STATUS current
  3681. DESCRIPTION
  3682. "Output Reactive Power B, stored as 0.01 KVAR."
  3683. ::= { analogdata9 30 }
  3684. outputReactivePowerC9 OBJECT-TYPE
  3685. SYNTAX Integer32
  3686. MAX-ACCESS read-only
  3687. STATUS current
  3688. DESCRIPTION
  3689. "Output Reactive Power C, stored as 0.01 KVAR."
  3690. ::= { analogdata9 31 }
  3691. outputAppPowerA9 OBJECT-TYPE
  3692. SYNTAX Integer32
  3693. MAX-ACCESS read-only
  3694. STATUS current
  3695. DESCRIPTION
  3696. "Output App Power A, stored as 0.01 kVA."
  3697. ::= { analogdata9 32 }
  3698. outputAppPowerB9 OBJECT-TYPE
  3699. SYNTAX Integer32
  3700. MAX-ACCESS read-only
  3701. STATUS current
  3702. DESCRIPTION
  3703. "Output App Power B, stored as 0.01 kVA."
  3704. ::= { analogdata9 33 }
  3705. outputAppPowerC9 OBJECT-TYPE
  3706. SYNTAX Integer32
  3707. MAX-ACCESS read-only
  3708. STATUS current
  3709. DESCRIPTION
  3710. "Output App Power C, stored as 0.01 kVA."
  3711. ::= { analogdata9 34 }
  3712. outputLoadA9 OBJECT-TYPE
  3713. SYNTAX Integer32
  3714. MAX-ACCESS read-only
  3715. STATUS current
  3716. DESCRIPTION
  3717. "Output Load A, stored as 0.01 %."
  3718. ::= { analogdata9 35 }
  3719. outputLoadB9 OBJECT-TYPE
  3720. SYNTAX Integer32
  3721. MAX-ACCESS read-only
  3722. STATUS current
  3723. DESCRIPTION
  3724. "Output Load B, stored as 0.01 %."
  3725. ::= { analogdata9 36 }
  3726. outputLoadC9 OBJECT-TYPE
  3727. SYNTAX Integer32
  3728. MAX-ACCESS read-only
  3729. STATUS current
  3730. DESCRIPTION
  3731. "Output Load C, stored as 0.01 %."
  3732. ::= { analogdata9 37 }
  3733. outputCrestFactorA9 OBJECT-TYPE
  3734. SYNTAX Integer32
  3735. MAX-ACCESS read-only
  3736. STATUS current
  3737. DESCRIPTION
  3738. "Output Crest Factor A, stored as 0.01 ."
  3739. ::= { analogdata9 38 }
  3740. outputCrestFactorB9 OBJECT-TYPE
  3741. SYNTAX Integer32
  3742. MAX-ACCESS read-only
  3743. STATUS current
  3744. DESCRIPTION
  3745. "Output Crest Factor B, stored as 0.01 ."
  3746. ::= { analogdata9 39 }
  3747. outputCrestFactorC9 OBJECT-TYPE
  3748. SYNTAX Integer32
  3749. MAX-ACCESS read-only
  3750. STATUS current
  3751. DESCRIPTION
  3752. "Output Crest Factor C, stored as 0.01 ."
  3753. ::= { analogdata9 40 }
  3754. bypassVoltageA9 OBJECT-TYPE
  3755. SYNTAX Integer32
  3756. MAX-ACCESS read-only
  3757. STATUS current
  3758. DESCRIPTION
  3759. "Bypass Voltage A, stored as 0.01 V."
  3760. ::= { analogdata9 41 }
  3761. bypassVoltageB9 OBJECT-TYPE
  3762. SYNTAX Integer32
  3763. MAX-ACCESS read-only
  3764. STATUS current
  3765. DESCRIPTION
  3766. "Bypass Voltage B, stored as 0.01 V."
  3767. ::= { analogdata9 42 }
  3768. bypassVoltageC9 OBJECT-TYPE
  3769. SYNTAX Integer32
  3770. MAX-ACCESS read-only
  3771. STATUS current
  3772. DESCRIPTION
  3773. "Bypass Voltage C, stored as 0.01 V."
  3774. ::= { analogdata9 43 }
  3775. bypassFrequency9 OBJECT-TYPE
  3776. SYNTAX Integer32
  3777. MAX-ACCESS read-only
  3778. STATUS current
  3779. DESCRIPTION
  3780. "Bypass Frequency, stored as 0.01 Hz."
  3781. ::= { analogdata9 44 }
  3782. positiveBatteryVoltage9 OBJECT-TYPE
  3783. SYNTAX Integer32
  3784. MAX-ACCESS read-only
  3785. STATUS current
  3786. DESCRIPTION
  3787. "positive Battery Voltage, stored as 0.01 V."
  3788. ::= { analogdata9 45 }
  3789. positiveBatteryCurrent9 OBJECT-TYPE
  3790. SYNTAX Integer32
  3791. MAX-ACCESS read-only
  3792. STATUS current
  3793. DESCRIPTION
  3794. "positive Battery Current, stored as 0.01 A."
  3795. ::= { analogdata9 46 }
  3796. negativeBatteryVoltage9 OBJECT-TYPE
  3797. SYNTAX Integer32
  3798. MAX-ACCESS read-only
  3799. STATUS current
  3800. DESCRIPTION
  3801. "negative Battery Voltage, stored as 0.01 V."
  3802. ::= { analogdata9 47 }
  3803. negativeBatteryCurrent9 OBJECT-TYPE
  3804. SYNTAX Integer32
  3805. MAX-ACCESS read-only
  3806. STATUS current
  3807. DESCRIPTION
  3808. "negative Battery Current, stored as 0.01 A."
  3809. ::= { analogdata9 48 }
  3810. batteryAgingRate9 OBJECT-TYPE
  3811. SYNTAX Integer32
  3812. MAX-ACCESS read-only
  3813. STATUS current
  3814. DESCRIPTION
  3815. "Battery Aging Rate, stored as 0.01."
  3816. ::= { analogdata9 49 }
  3817. batteryRemainsTime9 OBJECT-TYPE
  3818. SYNTAX Integer32
  3819. MAX-ACCESS read-only
  3820. STATUS current
  3821. DESCRIPTION
  3822. "Battery Remains Time, stored as 0.01 Hour."
  3823. ::= { analogdata9 50 }
  3824. batteryTemperature9 OBJECT-TYPE
  3825. SYNTAX Integer32
  3826. MAX-ACCESS read-only
  3827. STATUS current
  3828. DESCRIPTION
  3829. "Battery Temperature, stored as 0.01 °C."
  3830. ::= { analogdata9 51 }
  3831. batteryEnvironmentTemperature9 OBJECT-TYPE
  3832. SYNTAX Integer32
  3833. MAX-ACCESS read-only
  3834. STATUS current
  3835. DESCRIPTION
  3836. "Battery Environment Temperature, stored as 0.01 °C."
  3837. ::= { analogdata9 52 }
  3838. analogdata10 OBJECT IDENTIFIER ::= { system 14 }
  3839. inputPhaseVoltageA10 OBJECT-TYPE
  3840. SYNTAX Integer32
  3841. MAX-ACCESS read-only
  3842. STATUS current
  3843. DESCRIPTION
  3844. "Input Phase Voltage A, stored as 0.01 V."
  3845. ::= { analogdata10 1 }
  3846. inputPhaseVoltageB10 OBJECT-TYPE
  3847. SYNTAX Integer32
  3848. MAX-ACCESS read-only
  3849. STATUS current
  3850. DESCRIPTION
  3851. "Input Phase Voltage B, stored as 0.01 V."
  3852. ::= { analogdata10 2 }
  3853. inputPhaseVoltageC10 OBJECT-TYPE
  3854. SYNTAX Integer32
  3855. MAX-ACCESS read-only
  3856. STATUS current
  3857. DESCRIPTION
  3858. "Input Phase Voltage C, stored as 0.01 V."
  3859. ::= { analogdata10 3 }
  3860. inputLineVoltageA10 OBJECT-TYPE
  3861. SYNTAX Integer32
  3862. MAX-ACCESS read-only
  3863. STATUS current
  3864. DESCRIPTION
  3865. "Input Line Voltage A, stored as 0.01 V."
  3866. ::= { analogdata10 4 }
  3867. inputLineVoltageB10 OBJECT-TYPE
  3868. SYNTAX Integer32
  3869. MAX-ACCESS read-only
  3870. STATUS current
  3871. DESCRIPTION
  3872. "Input Line Voltage B, stored as 0.01 V."
  3873. ::= { analogdata10 5 }
  3874. inputLineVoltageC10 OBJECT-TYPE
  3875. SYNTAX Integer32
  3876. MAX-ACCESS read-only
  3877. STATUS current
  3878. DESCRIPTION
  3879. "Input Line Voltage C, stored as 0.01 V."
  3880. ::= { analogdata10 6 }
  3881. inputCurrentA10 OBJECT-TYPE
  3882. SYNTAX Integer32
  3883. MAX-ACCESS read-only
  3884. STATUS current
  3885. DESCRIPTION
  3886. "Input Current A, stored as 0.01 A."
  3887. ::= { analogdata10 7 }
  3888. inputCurrentB10 OBJECT-TYPE
  3889. SYNTAX Integer32
  3890. MAX-ACCESS read-only
  3891. STATUS current
  3892. DESCRIPTION
  3893. "Input Current B, stored as 0.01 A."
  3894. ::= { analogdata10 8 }
  3895. inputCurrentC10 OBJECT-TYPE
  3896. SYNTAX Integer32
  3897. MAX-ACCESS read-only
  3898. STATUS current
  3899. DESCRIPTION
  3900. "Input Current C, stored as 0.01 A."
  3901. ::= { analogdata10 9 }
  3902. inputFrequency10 OBJECT-TYPE
  3903. SYNTAX Integer32
  3904. MAX-ACCESS read-only
  3905. STATUS current
  3906. DESCRIPTION
  3907. "Input Frequency, stored as 0.01 Hz."
  3908. ::= { analogdata10 10 }
  3909. inputPowerFactorA10 OBJECT-TYPE
  3910. SYNTAX Integer32
  3911. MAX-ACCESS read-only
  3912. STATUS current
  3913. DESCRIPTION
  3914. "Input Power Factor A, stored as 0.01."
  3915. ::= { analogdata10 11 }
  3916. inputPowerFactorB10 OBJECT-TYPE
  3917. SYNTAX Integer32
  3918. MAX-ACCESS read-only
  3919. STATUS current
  3920. DESCRIPTION
  3921. "Input Power Factor B, stored as 0.01."
  3922. ::= { analogdata10 12 }
  3923. inputPowerFactorC10 OBJECT-TYPE
  3924. SYNTAX Integer32
  3925. MAX-ACCESS read-only
  3926. STATUS current
  3927. DESCRIPTION
  3928. "Input Power Factor C, stored as 0.01."
  3929. ::= { analogdata10 13 }
  3930. dCBus1Voltage10 OBJECT-TYPE
  3931. SYNTAX Integer32
  3932. MAX-ACCESS read-only
  3933. STATUS current
  3934. DESCRIPTION
  3935. "DCBus1 Voltage, stored as 0.01 V."
  3936. ::= { analogdata10 14 }
  3937. dCBus2Voltage10 OBJECT-TYPE
  3938. SYNTAX Integer32
  3939. MAX-ACCESS read-only
  3940. STATUS current
  3941. DESCRIPTION
  3942. "DCBus2 Voltage, stored as 0.01 V."
  3943. ::= { analogdata10 15 }
  3944. outputVoltageA10 OBJECT-TYPE
  3945. SYNTAX Integer32
  3946. MAX-ACCESS read-only
  3947. STATUS current
  3948. DESCRIPTION
  3949. "Output voltage A, stored as 0.01 V."
  3950. ::= { analogdata10 16 }
  3951. outputVoltageB10 OBJECT-TYPE
  3952. SYNTAX Integer32
  3953. MAX-ACCESS read-only
  3954. STATUS current
  3955. DESCRIPTION
  3956. "Output voltage B, stored as 0.01 V."
  3957. ::= { analogdata10 17 }
  3958. outputVoltageC10 OBJECT-TYPE
  3959. SYNTAX Integer32
  3960. MAX-ACCESS read-only
  3961. STATUS current
  3962. DESCRIPTION
  3963. "Output voltage C, stored as 0.01 V."
  3964. ::= { analogdata10 18 }
  3965. outputCurrentA10 OBJECT-TYPE
  3966. SYNTAX Integer32
  3967. MAX-ACCESS read-only
  3968. STATUS current
  3969. DESCRIPTION
  3970. "Output current A, stored as 0.01 A."
  3971. ::= { analogdata10 19 }
  3972. outputCurrentB10 OBJECT-TYPE
  3973. SYNTAX Integer32
  3974. MAX-ACCESS read-only
  3975. STATUS current
  3976. DESCRIPTION
  3977. "Output current B, stored as 0.01 A."
  3978. ::= { analogdata10 20 }
  3979. outputCurrentC10 OBJECT-TYPE
  3980. SYNTAX Integer32
  3981. MAX-ACCESS read-only
  3982. STATUS current
  3983. DESCRIPTION
  3984. "Output current C, stored as 0.01 A."
  3985. ::= { analogdata10 21 }
  3986. outputFrequency10 OBJECT-TYPE
  3987. SYNTAX Integer32
  3988. MAX-ACCESS read-only
  3989. STATUS current
  3990. DESCRIPTION
  3991. "Output Frequency, stored as 0.01 Hz."
  3992. ::= { analogdata10 22 }
  3993. outputPowerFactorA10 OBJECT-TYPE
  3994. SYNTAX Integer32
  3995. MAX-ACCESS read-only
  3996. STATUS current
  3997. DESCRIPTION
  3998. "Output Power Factor A, stored as 0.01."
  3999. ::= { analogdata10 23 }
  4000. outputPowerFactorB10 OBJECT-TYPE
  4001. SYNTAX Integer32
  4002. MAX-ACCESS read-only
  4003. STATUS current
  4004. DESCRIPTION
  4005. "Output Power Factor B, stored as 0.01."
  4006. ::= { analogdata10 24 }
  4007. outputPowerFactorC10 OBJECT-TYPE
  4008. SYNTAX Integer32
  4009. MAX-ACCESS read-only
  4010. STATUS current
  4011. DESCRIPTION
  4012. "Output Power Factor C, stored as 0.01."
  4013. ::= { analogdata10 25 }
  4014. outputAcitvePowerA10 OBJECT-TYPE
  4015. SYNTAX Integer32
  4016. MAX-ACCESS read-only
  4017. STATUS current
  4018. DESCRIPTION
  4019. "Output Acitve Power A, stored as 0.01 kW."
  4020. ::= { analogdata10 26 }
  4021. outputAcitvePowerB10 OBJECT-TYPE
  4022. SYNTAX Integer32
  4023. MAX-ACCESS read-only
  4024. STATUS current
  4025. DESCRIPTION
  4026. "Output Acitve Power B, stored as 0.01 kW."
  4027. ::= { analogdata10 27 }
  4028. outputAcitvePowerC10 OBJECT-TYPE
  4029. SYNTAX Integer32
  4030. MAX-ACCESS read-only
  4031. STATUS current
  4032. DESCRIPTION
  4033. "Output Acitve Power C, stored as 0.01 kW."
  4034. ::= { analogdata10 28 }
  4035. outputReactivePowerA10 OBJECT-TYPE
  4036. SYNTAX Integer32
  4037. MAX-ACCESS read-only
  4038. STATUS current
  4039. DESCRIPTION
  4040. "Output Reactive Power A, stored as 0.01 KVAR."
  4041. ::= { analogdata10 29 }
  4042. outputReactivePowerB10 OBJECT-TYPE
  4043. SYNTAX Integer32
  4044. MAX-ACCESS read-only
  4045. STATUS current
  4046. DESCRIPTION
  4047. "Output Reactive Power B, stored as 0.01 KVAR."
  4048. ::= { analogdata10 30 }
  4049. outputReactivePowerC10 OBJECT-TYPE
  4050. SYNTAX Integer32
  4051. MAX-ACCESS read-only
  4052. STATUS current
  4053. DESCRIPTION
  4054. "Output Reactive Power C, stored as 0.01 KVAR."
  4055. ::= { analogdata10 31 }
  4056. outputAppPowerA10 OBJECT-TYPE
  4057. SYNTAX Integer32
  4058. MAX-ACCESS read-only
  4059. STATUS current
  4060. DESCRIPTION
  4061. "Output App Power A, stored as 0.01 kVA."
  4062. ::= { analogdata10 32 }
  4063. outputAppPowerB10 OBJECT-TYPE
  4064. SYNTAX Integer32
  4065. MAX-ACCESS read-only
  4066. STATUS current
  4067. DESCRIPTION
  4068. "Output App Power B, stored as 0.01 kVA."
  4069. ::= { analogdata10 33 }
  4070. outputAppPowerC10 OBJECT-TYPE
  4071. SYNTAX Integer32
  4072. MAX-ACCESS read-only
  4073. STATUS current
  4074. DESCRIPTION
  4075. "Output App Power C, stored as 0.01 kVA."
  4076. ::= { analogdata10 34 }
  4077. outputLoadA10 OBJECT-TYPE
  4078. SYNTAX Integer32
  4079. MAX-ACCESS read-only
  4080. STATUS current
  4081. DESCRIPTION
  4082. "Output Load A, stored as 0.01 %."
  4083. ::= { analogdata10 35 }
  4084. outputLoadB10 OBJECT-TYPE
  4085. SYNTAX Integer32
  4086. MAX-ACCESS read-only
  4087. STATUS current
  4088. DESCRIPTION
  4089. "Output Load B, stored as 0.01 %."
  4090. ::= { analogdata10 36 }
  4091. outputLoadC10 OBJECT-TYPE
  4092. SYNTAX Integer32
  4093. MAX-ACCESS read-only
  4094. STATUS current
  4095. DESCRIPTION
  4096. "Output Load C, stored as 0.01 %."
  4097. ::= { analogdata10 37 }
  4098. outputCrestFactorA10 OBJECT-TYPE
  4099. SYNTAX Integer32
  4100. MAX-ACCESS read-only
  4101. STATUS current
  4102. DESCRIPTION
  4103. "Output Crest Factor A, stored as 0.01 ."
  4104. ::= { analogdata10 38 }
  4105. outputCrestFactorB10 OBJECT-TYPE
  4106. SYNTAX Integer32
  4107. MAX-ACCESS read-only
  4108. STATUS current
  4109. DESCRIPTION
  4110. "Output Crest Factor B, stored as 0.01 ."
  4111. ::= { analogdata10 39 }
  4112. outputCrestFactorC10 OBJECT-TYPE
  4113. SYNTAX Integer32
  4114. MAX-ACCESS read-only
  4115. STATUS current
  4116. DESCRIPTION
  4117. "Output Crest Factor C, stored as 0.01 ."
  4118. ::= { analogdata10 40 }
  4119. bypassVoltageA10 OBJECT-TYPE
  4120. SYNTAX Integer32
  4121. MAX-ACCESS read-only
  4122. STATUS current
  4123. DESCRIPTION
  4124. "Bypass Voltage A, stored as 0.01 V."
  4125. ::= { analogdata10 41 }
  4126. bypassVoltageB10 OBJECT-TYPE
  4127. SYNTAX Integer32
  4128. MAX-ACCESS read-only
  4129. STATUS current
  4130. DESCRIPTION
  4131. "Bypass Voltage B, stored as 0.01 V."
  4132. ::= { analogdata10 42 }
  4133. bypassVoltageC10 OBJECT-TYPE
  4134. SYNTAX Integer32
  4135. MAX-ACCESS read-only
  4136. STATUS current
  4137. DESCRIPTION
  4138. "Bypass Voltage C, stored as 0.01 V."
  4139. ::= { analogdata10 43 }
  4140. bypassFrequency10 OBJECT-TYPE
  4141. SYNTAX Integer32
  4142. MAX-ACCESS read-only
  4143. STATUS current
  4144. DESCRIPTION
  4145. "Bypass Frequency, stored as 0.01 Hz."
  4146. ::= { analogdata10 44 }
  4147. positiveBatteryVoltage10 OBJECT-TYPE
  4148. SYNTAX Integer32
  4149. MAX-ACCESS read-only
  4150. STATUS current
  4151. DESCRIPTION
  4152. "positive Battery Voltage, stored as 0.01 V."
  4153. ::= { analogdata10 45 }
  4154. positiveBatteryCurrent10 OBJECT-TYPE
  4155. SYNTAX Integer32
  4156. MAX-ACCESS read-only
  4157. STATUS current
  4158. DESCRIPTION
  4159. "positive Battery Current, stored as 0.01 A."
  4160. ::= { analogdata10 46 }
  4161. negativeBatteryVoltage10 OBJECT-TYPE
  4162. SYNTAX Integer32
  4163. MAX-ACCESS read-only
  4164. STATUS current
  4165. DESCRIPTION
  4166. "negative Battery Voltage, stored as 0.01 V."
  4167. ::= { analogdata10 47 }
  4168. negativeBatteryCurrent10 OBJECT-TYPE
  4169. SYNTAX Integer32
  4170. MAX-ACCESS read-only
  4171. STATUS current
  4172. DESCRIPTION
  4173. "negative Battery Current, stored as 0.01 A."
  4174. ::= { analogdata10 48 }
  4175. batteryAgingRate10 OBJECT-TYPE
  4176. SYNTAX Integer32
  4177. MAX-ACCESS read-only
  4178. STATUS current
  4179. DESCRIPTION
  4180. "Battery Aging Rate, stored as 0.01."
  4181. ::= { analogdata10 49 }
  4182. batteryRemainsTime10 OBJECT-TYPE
  4183. SYNTAX Integer32
  4184. MAX-ACCESS read-only
  4185. STATUS current
  4186. DESCRIPTION
  4187. "Battery Remains Time, stored as 0.01 Hour."
  4188. ::= { analogdata10 50 }
  4189. batteryTemperature10 OBJECT-TYPE
  4190. SYNTAX Integer32
  4191. MAX-ACCESS read-only
  4192. STATUS current
  4193. DESCRIPTION
  4194. "Battery Temperature, stored as 0.01 °C."
  4195. ::= { analogdata10 51 }
  4196. batteryEnvironmentTemperature10 OBJECT-TYPE
  4197. SYNTAX Integer32
  4198. MAX-ACCESS read-only
  4199. STATUS current
  4200. DESCRIPTION
  4201. "Battery Environment Temperature, stored as 0.01 °C."
  4202. ::= { analogdata10 52 }
  4203. -- ------------------------------------------------------------------------
  4204. -- 1.2.6 the control group
  4205. -- ------------------------------------------------------------------------
  4206. -- ------------------------------------------------------------------------
  4207. -- 1.2.7 the config group
  4208. -- ------------------------------------------------------------------------
  4209. ------------------------------------------------------------
  4210. -- 1.3 Alarm trap table { nxrMIB 3 }
  4211. ------------------------------------------------------------
  4212. alarmTrapTable OBJECT-TYPE
  4213. SYNTAX SEQUENCE OF AlarmTrapEntry
  4214. MAX-ACCESS not-accessible
  4215. STATUS current
  4216. DESCRIPTION "
  4217. Table holding information about the submitted alarm traps."
  4218. ::= { nxrMIB 3 }
  4219. alarmTrapEntry OBJECT-TYPE
  4220. SYNTAX AlarmTrapEntry
  4221. MAX-ACCESS not-accessible
  4222. STATUS current
  4223. DESCRIPTION "
  4224. An entry (conceptual row) in the alarmTrapTable."
  4225. INDEX { alarmIndex }
  4226. ::= { alarmTrapTable 1 }
  4227. AlarmTrapEntry ::= SEQUENCE {
  4228. alarmIndex Counter32,
  4229. alarmTime DisplayString,
  4230. alarmStatusChange StatusChange,
  4231. alarmSeverity Status,
  4232. alarmDescription DisplayString,
  4233. alarmId Integer32 }
  4234. alarmIndex OBJECT-TYPE
  4235. SYNTAX Counter32
  4236. MAX-ACCESS read-only
  4237. STATUS current
  4238. DESCRIPTION "
  4239. The unique sequence number of this alarm trap."
  4240. ::= { alarmTrapEntry 1 }
  4241. alarmTime OBJECT-TYPE
  4242. SYNTAX DisplayString
  4243. MAX-ACCESS read-only
  4244. STATUS current
  4245. DESCRIPTION "
  4246. Date and time when event occured."
  4247. ::= { alarmTrapEntry 2 }
  4248. alarmStatusChange OBJECT-TYPE
  4249. SYNTAX StatusChange
  4250. MAX-ACCESS read-only
  4251. STATUS current
  4252. DESCRIPTION "
  4253. Indicates 'activated' (0) or 'deactivated' (1) alarm events."
  4254. ::= { alarmTrapEntry 3 }
  4255. alarmSeverity OBJECT-TYPE
  4256. SYNTAX Status
  4257. MAX-ACCESS read-only
  4258. STATUS current
  4259. DESCRIPTION "
  4260. The severity of the alarm. One of
  4261. (0) informational
  4262. (1) warning
  4263. (2) critical"
  4264. ::= { alarmTrapEntry 4 }
  4265. alarmDescription OBJECT-TYPE
  4266. SYNTAX DisplayString
  4267. MAX-ACCESS read-only
  4268. STATUS current
  4269. DESCRIPTION "
  4270. Free-text description of alarm."
  4271. ::= { alarmTrapEntry 5 }
  4272. alarmId OBJECT-TYPE
  4273. SYNTAX Integer32
  4274. MAX-ACCESS read-only
  4275. STATUS current
  4276. DESCRIPTION "
  4277. Alarm id."
  4278. ::= { alarmTrapEntry 6 }
  4279. ------------------------------------------------------------
  4280. -- End of MIB definitions
  4281. ------------------------------------------------------------
  4282. END